AC Test Voltage. EN 61000-4-16. IEC 60870-2-1. (class VW3). 2,5 kV, 50 Hz.
Test duration: 1 min. Impulse Voltage with stand test. IEC 60255-5. IEC 60870-2-
1.
RTU500 series
Data Sheet Adapter 211ADD52
Adapter 211ADD52
Application
Fig. 1: Example 1: Connection diagram Adapter 211ADD52
The Adapter for I/O modules 211ADD52 is the standard adapter to connect RTU211 I/O modules within an RTU211/RTU560 DIN rail solution.
Characteristics The Adapter terminates the serial peripheral bus of the RTU211 (Wired-OR Bus) and generates the addresses for the connected I/O-modules automatically. The Adapter is equipped with two green LED’s, indicating the activities on the serial peripheral bus.
Fig. 2: Example 2: Connection diagram Adapter 211ADD52
Per Jumper selectable:
Doc. No.: 1KGT 150 780 V002 1
4 x I/O modules per adapter
8 x I/O modules per adapter
1
RTU500 series Data Sheet Adapter 211ADD52
Technical Data In addition to the RTU500 series general technical data, the following applies:
Power consumption Typical
0,1 Watt at 5 VDC
Mechanical dimensions Depth
120,0 mm
Height
101,0 mm
Width
35,0 mm
Connection type Connector
RTU211/RTU560 DIN rail System Cable (ribbon cable, 20 pins)
Insulation tests AC Test Voltage EN 61000-4-16 IEC 60870-2-1 (class VW3) Impulse Voltage with stand test IEC 60255-5 IEC 60870-2-1 (class VW 3)
2,5 kV, 50 Hz Test duration: 1 min
5 kV (1,2 / 50 µs)
Immunity tests Electrostatic Discharge 4 kV Contact Immunity Test 8 kV Air IEC 61000-4-2 (level 3) Performance criteria A Radiated Radio10 V/m Frequency Electromagnetic Field Immuni- Performance criteria A ty Test IEC 61000-4-3 (level 3) Immunity to Electrical 4 kV Fast Transient / Burst IEC 61000-4-4 Performance criteria A (level 3) Surge Immunity Test 2 kV IEC 61000-4-5 (level 3) Performance criteria A Immunity to Conducted 10 V Disturbances, induced by Radio-Frequency Performance criteria A Fields IEC 61000-4-6 (level 3)
Ordering information 211ADD52 R0001
1KGT 023900 R0001
Environmental conditions Nominal operating temperature range