AC Test Voltage. EN 61000-4-16. IEC 60870-2-1. (class VW3). 2,5 kV, 50 Hz. Test duration: 1 min. Impulse Voltage with stand test. IEC 60255-5. IEC 60870-2- 1.
RTU500 series



Data Sheet Adapter 211ADD52

Adapter 211ADD52

Application

Fig. 1: Example 1: Connection diagram Adapter 211ADD52

The Adapter for I/O modules 211ADD52 is the standard adapter to connect RTU211 I/O modules within an RTU211/RTU560 DIN rail solution.

Characteristics The Adapter terminates the serial peripheral bus of the RTU211 (Wired-OR Bus) and generates the addresses for the connected I/O-modules automatically. The Adapter is equipped with two green LED’s, indicating the activities on the serial peripheral bus.

Fig. 2: Example 2: Connection diagram Adapter 211ADD52

Per Jumper selectable:

Doc. No.: 1KGT 150 780 V002 1



4 x I/O modules per adapter



8 x I/O modules per adapter

1

RTU500 series Data Sheet Adapter 211ADD52

Technical Data In addition to the RTU500 series general technical data, the following applies:

Power consumption Typical

0,1 Watt at 5 VDC

Mechanical dimensions Depth

120,0 mm

Height

101,0 mm

Width

35,0 mm

Connection type Connector

RTU211/RTU560 DIN rail System Cable (ribbon cable, 20 pins)

Insulation tests AC Test Voltage EN 61000-4-16 IEC 60870-2-1 (class VW3) Impulse Voltage with stand test IEC 60255-5 IEC 60870-2-1 (class VW 3)

2,5 kV, 50 Hz Test duration: 1 min

5 kV (1,2 / 50 µs)

Immunity tests Electrostatic Discharge 4 kV Contact Immunity Test 8 kV Air IEC 61000-4-2 (level 3) Performance criteria A Radiated Radio10 V/m Frequency Electromagnetic Field Immuni- Performance criteria A ty Test IEC 61000-4-3 (level 3) Immunity to Electrical 4 kV Fast Transient / Burst IEC 61000-4-4 Performance criteria A (level 3) Surge Immunity Test 2 kV IEC 61000-4-5 (level 3) Performance criteria A Immunity to Conducted 10 V Disturbances, induced by Radio-Frequency Performance criteria A Fields IEC 61000-4-6 (level 3)

Ordering information 211ADD52 R0001

1KGT 023900 R0001

Environmental conditions Nominal operating temperature range

-25 ... +70 C

Start up

-40 C

Max. operating temperature, max. 96h (EN60068 2-1, 2, 14) Relative Humidity (EN60068-2-30)

+85 C

5 ... 95 % (non condensing)

Doc. No.: 1KGT 150 780 V002 1

2

RTU500 series



Data Sheet Adapter 211ADD52

Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents - in whole or in parts - is forbidden without prior written consent of ABB AG. Copyright© 2013 ABB All rights reserved