Apr 17, 1996 - Abstraet--A generalized heat transfer correlation for louver fin geometry is developed with the aid of a large data bank. This data bank consists ...
lnt. J. Heat Mass Transfer. Vol. 40, No. 3, pp. 53~544, 1997 Copyright © 1996 Elsevier Science Ltd Printed in Great Britain. All rights reserved 0017 9310/97515.00+0.00

l'ergmo,,

PII: S0017-9310(96)00116--0

A generalized heat transfer correlation for louver fin geometry YU-JUEI C H A N G and C H I - C H U A N W A N G Energy and Research Laboratories, Industrial Technology Research Institute, Hsinchu, Taiwan, Republic of China (Received 6 December 1995 and in final form 17 April 1996)

Abstraet--A generalized heat transfer correlation for louver fin geometry is developed with the aid of a large data bank. This data bank consists of 91 samples of louvered fin heat exchangers with different geometrical parameters, including louver angle, tube width, louver length, louver pitch, fin length and fin pitch. For the corrugated louver fin geometry, it is shown that 89.3% of the corrugated louver fin data are correlated within _+15% with mean deviation of 7.55%. The inclusion of the plate-and-tube louver fin data in the heat transfer correlation (equation (A1)) results in a mean deviation of 8,21%. Copyright © 1996 Elsevier Science Ltd. INTRODUCTION

To effectively improve the thermal performance of the air-cooled heat exchangers, it is important to reduce high air-side therrnal resistance. Therefore, extended surfaces are commonly used in the air-side of heat exchangers. The extended surface enhances the heat transfer rate by increasing the surface area and by inducing turbulent mixing of air flow. Therefore, highly interrupted surfaces are often encountered in enhanced surfaces to efficiently break up the growth of thermal bounda.ry layer from leading edge. Examples of interrupted surfaces are the offset strip fin and louvered fin. Louvered fins can be manufactured by high-speed production techniques and as a result are less expensive than other interrupted flow geometry when produced in large quantities. Figure 1 shows five typical air-cooled heat exchangers that use the louver fin geometry. As seen, the air-cooled heat exchangers generally consist of multi-louver fins and flat tube. Generally, the minor diameter of the flat tube is 1.55 mm. The flat tube design offers several advantages as outlined by Webb and Jung [1] : (1) the air flow is normal to all of the louvers; (2) the wake region behind the tube does not reduce heat transfer on downstream fin regions ; (3) it provides a higher fin efficiency; (4) the small projected area of the flat tube will result in lower profile drag than the larger diameter round tube does. More quantitative comparisons between the louver fin surface and other geometries are shown by several investigators. Using: the volume goodness comparison method, Sunden and Svantesson [2] concluded that the louvered surfaces are more efficient than the corresponding smooth surface. Chang et al. [3] used various comparison methods, including area goodness factor, volume go,adness factor and performance

evaluation criteria proposed by Cowell [4] to quantitatively study the air side of the fiat tube condenser and its round tube condenser counterpart. They found that the fiat tube geometry offers significant improvement as comparing to the round tube condenser. Recently, Cowell et al. [5] compared the louvered fin surface with offset-strip surface configuration. They reported that the louvered fins are capable of outperforming offset strips. Despite the superiority of the louver fin surface, the fact is that the louvered surfaces have been in existence since the 1950s. The available performance data in the open literature are very limited. Davenport [6] reported a comprehensive study of a non-standard variant of the flat tube and louvered corrugated heat exchangers. Totally, 32 samples of louver fin samples were tested. The fin geometry tested by Davenport is shown in Fig. 1 (Type A). Note that the fin pitch studied by Davenport is larger than that presently used and the louver fin is distinctly triangular shaped channel. Davenport had proposed a correlation for Fig. IA geometry and claimed 95% of the experimentalj factors data had been correlated within + 6 % . Achaichia and Cowell [7] were the first to present the performance data for flat tube and louvered plate fin surfaces (Fig. 1, type B). They had verified the flattening characteristics of the Stanton number at low Reynolds number previously observed by Davenport [6]. They had explained the flattening characteristics as the effective heat transfer configuration changes from 'flat plate' to 'duct flow'. A total of 15 samples were tested in their study. They also presented a correlation that claimed all the Stanton number data for ReLp > 75 to be within 10%. Webb and Jung [1] presented experimental data for six brazed aluminium heat exchangers. The fin geometry of their brazed aluminium heat exchangers includes three standard corrugated fin geometry (Fig. 1, Type C) and three splitter fin geometry (Fig. 1, 533

534

Y.-J. CHANG and C.-C. WANG

NOMENCLATURE

A Af Ai At Dh Dm Fp Fd Fi h0 j k 1 Lh

L~ Lp

rn N Nj Pr

r

total surface area (Af+ At) [m2] fin surface area [m21 louver surface area [mz] external tube surface area [m2] hydraulic diameter of fin array [ram] major diameter [mini fin pitch [mm] fin depth [mm] fin length [mm] heat transfer coefficient [W m -2 K -~] the Colburn factor [dimensionless] thermal conductivity [W m - ' K -l] fin length [mm] louver height [mm] louver length [mm] louver pitch [mm] ( ~ ) [m-q number of test data point number of full louvers over flow direction [dimensionless] the Prandtl number [dimensionless] ratio of the fin area at the sample sides to the overall louver fin area [dimensionless]

Type E). The brazed aluminium heat exchanger is made of multi-louver fins brazed to a flat, extruded tube, with a cross section of several independent passages. They found that the standard corrugated brazed aluminium flat tube design gives a 90% higher heat transfer coefficient for only 25% higher pressure drop compared with the round tube plain plate fin design. Rugh et al. [8] provided data on a high fin density (1960 fins m-]) louvered surface. Data were presented against Reynolds number (based on Dh) in the range of 150 and 300. The heat exchanger they tested is a corrugated louver fin with a splitter plate (Fig. 1, Type D). Comparisons were drawn relative to the plain fin, and they reported that the louver fins produce an approximately 25% increase in heat transfer coefficient and 110% increase in pressure drop. The investigations of heat transfer and pressure drop of standard louver fin and incline louver fin were reported by Sunden and Svantesson [2, 9]. Their investigations show that all the louvered surfaces are more efficient than the corresponding smooth surface, and the standard louver fin geometry reveals higher Stanton number than other inclined louver fin geometries. Chang et aL [10] and Chang and Wang [11] presented 27 samples of corrugated louvered fin heat exchangers (Fig. 1, Type C) with different geometrical parameters, including tube width, louver length, louver pitch, fin length and fin pitch. Results are presented as plots of friction factor, f, and the Colburnj factor against Reynolds number based on louver pitch in the range of 100-1000. They also applied the Sah-

ReDh ReLp

S,

Reynolds number based on hydraulic diameter [dimensioneless] Reynolds number based on louver pitch [dimensionless] non-louvered inlet and exit fin regions

[mm] Sz St

Tp Td

re-direction length [mm] the Stanton numer [dimensionless] tube pitch [mm] tube depth [mm].

Greek symbols louver angle [deg] 0 thickness of tube wall or fin [nun] 6 A / A , finning factor [dimensionless] e At/ A [dimensionless] el surface effectiveness [dimensionless] r/ fin efficiency [dimensionless]. qf Subscripts 1 louvered portion 2 unlouvered portion f fin.

noun and Webb [12] and the Dillen and Webb [13] models to compare with the experimental data, and showed good agreements between the experimental data and the models. By introducing 'area ratio' parameters, a simpler correlation of the Colburn j factor and friction factor f were obtained. It is shown that 85% of the experimental data of heat transfer and friction data were correlated within _ 10%. Later on, Webb et al. [14] used both Davenport [6] and Chang and Wang [11] data to develop semi-analytical heat transfer and friction correlations, which predict 95% of the heat transfer coefficient data within + 20%, and are applicable to currently used copper/brass and brazed aluminium cores. Though a few correlations are already available, the justification for proposing a new one is required. For instance, Sunden and Svantesson [9] indicated that the Achaichia and CoweU correlation [7] considerably overpredicts their fin geometry and CoweU et al. [5] argued that the use of Sunden and Svantesson's [9] correlation [7] should be very careful, since their data bank is very limited (six samples). Therefore, the objective of the present study is to propose a general heat transfer correlation that uses a much larger data bank. THE DATA BANK

An attempt has been made to collect data from a wide range of geometric dimensions. In Table 1, a complete list has been given and the relevant definition of the geometric parameters is shown in Fig. 2. Table

Generalized heat transfer correlation

535

Type (A), Corrugated Louver With Triangular Channel Triangular channel Air flow

y

Type (B), Plate-andTube Louver Fin Geome,try Louvered plate fin Air flow

Type (C), Corrugated Louver With Rectangular Channelt Air flow louver fin

Type (D), Corrugated Louver 'With Splitter Plate and Rectangular Channel Air flow

Splitter plate

Type (E), Corrugated Louver With Splitter Plate and Tri~mgular Channel Triangular channel Air flow Fig. I. Type of louver fin heat exchangers.

Splitter plate

536

Y.-J. C H A N G and C.-C. W A N G Table 1. Geometric details of the louver fin heat exchangers

Sample Core Variant source type

1 2 3 4 5 6 7 8 9 10 II 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67

D(1) D(2) D(3) D(4) D(5) D(6) D(7) D(8) D(9) D(10) D(13) D(14) D(15) D(16) D(17) D(18) D(19) D(20) D(21) D(22) D(23) D(24) D(25) D(26) D(27) D(28) D(29) D(30) D(31) D(32) C&W(1) C&W(2) C&W(3) C&W(4) C&W(5) C&W(6) C&W(7) C&W(8) C&W(9) C&W(10) C&W(ll) C&W(12) C&W(13) C&W(14) C&W(15) C&W(16) C&W(17) C&W(18) C&W(19) C&W(20) C&W(21) C&W(22) C&W(23) C&W(24) C&W(25) C&W(26) C&W(27) PSU(1) PSU(IO) PSU(ll) PSU(12) PSU(15) A&C(1) A&C(2) A&C(3) A&C(4) A&C(5)

A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C B B B B B

Louver pitch (mm)

3 3 3 2.25 2.25 2.25 1.8 1.8 1.8 1.5 1.8 3 2.25 2.25 2.25 2.25 2.25 3 2.25 1.8 1.5 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 1.318 1.318 1,318 1.42 1.42 1,42 1.481 1.481 1.481 1.534 1.534 1.534 1.693 1.693 1.693 1.546 1.546 1.546 1.86 1.86 1.86 1.59 1.59 1.59 1.532 1.532 1.532 1 1.016 1.016 1.016 0.94 1.4 1.4 1.4 1.4 1.4

Louver length (mm)

Louver angle (deg)

Fin pitch

Tube depth

(mE)

( m m ) (mm) ( m m )

9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 11.7 11 10 9 8 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 6.5 6 5 12,44 12,44 12,44 17.18 17.18 17.18 12.78 12.78 12.78 16.07 16.07 16.07 12.15 12.15 12.15 16.17 16.17 16.17 15.25 15.25 15.25 13.18 13.18 13.18 16.84 16.84 16.84 6.5 6.858 6.858 6.858 7.62 8.5 8.5 8.5 8.5 8.5

8.43 10.37 16.66 13.36 16 19.2 18.8 20.83 27.82 19.63 14.15 11.15 24.14 21.37 21.37 21.37 20.28 13.89 13.78 20.42 26.1 9.52 16.53 17.7 16 13.89 14.15 16.63 17.59 14.41 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 30 27 27 27 27 25.5 25.5 25.5 21.5 28.5

1.55 1.55 1.6 1.55 1.56 1.56 1.55 1.585 1.575 1.525 1.625 1.56 1.675 1.65 1.65 1.625 1.6 1.535 1.525 1.535 1.55 1.485 1.51 1.51 1.225 1.005 1.535 1.51 1.535 1.5 1.8 2 2.2 1.8 2 2.2 1.8 2 2.2 1.8 2 2.2 1.8 2 2.2 1.8 2 2.2 1.8 2 2.2 1.8 2 2.2 1.8 2 2.2 1.124 1.954 1.588 1.27 1.114 2.02 3.25 1.65 2.09 2.03

40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 22 22 22 22 22 22 26 26 26 26 26 26 32 32 32 32 32 32 38 38 38 44 44 44 44 44 44 16 20.32 20.32 20.32 16.26 32 32 32 32 32

Fin Fin Fin depth length thickness

40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 22 22 22 22 22 22 26 26 26 26 26 26 32 32 32 32 32 32 38 38 38 44 44 44 44 44 44 16 20.32 20.32 20.32 16.26 41.6 41.6 41.6 41.6 41.6

12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 16 16 16 19 19 19 16 16 16 19 19 19 16 16 16 19 19 19 19 19 19 16 16 16 19 19 19 8 9.22 9.22 9.22 9.15 9 9 9 9 9

(mm)

Tube pitch (mm)

0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.075 0.16 0.16 0,16 0A6 0.16 0.16 0.16 0.16 0.16 0.16 0.16 0.16 0.16 0.16 0.16 0.16 0.16 0.16 0.16 0.16 0.16 0.16 0.16 0.16 0.16 0.16 0.16 0.157 0.0508 0.0508 0.0508 0.127 0.05 0.05 0.05 0.05 0.05

14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 9.182 9.174 9.182 9.194 9.142 9.162 9.162 8.928 8.74 9.182 9.162 9.182 9.154 21 21 21 24 24 24 21 21 21 24 24 24 21 21 21 24 24 24 24 24 24 21 21 21 24 24 24 9.6 11.11 11.11 11.11 11.11 11 11 11 11 11

Rows of Dh Data tubes (ram) point l 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2

2.78 2.78 2.86 2.78 2.8 2.8 2.78 2.84 2.82 2.74 2,9 2.8 2.99 2.95 2.95 2.9 2.86 2.61 2.6 2.61 2.64 2.54 2.58 2.58 2.14 1.8 2.61 2.58 2.61 2,56 3.069 3.399 3.72 3.041 3.374 3.701 3.043 3.37 3,69 3.069 3.406 3.736 3.047 3.376 3.697 3.057 3.394 3,724 3.07 3.409 3.74 3.007 3.333 3.651 3.036 3.371 3.699 1.962 3.317 2.621 2.145 1.759 3.33 4.94 2.69 3.37 3.3

9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 5 9 9 9 9 9 9 9 9 9 9 9 9 6 5 5 6 6 9 8 9 8 8

Generalized heat transfer correlation

537

Table 1--continued Louver Sample Core pitch Variant source type (mm) 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84

A&C(6) A&C(7) A&C(8) A&C(9) A&C(10) A&C(ll) A&C(12) A&C(13) A&C(14) A&C(15) W&J(1) W&J(2) W&J(3) W&J(4) W&J(5) W&J(6) Rugh

85 86 87 88 89 90 91

S&S(1) S&S(2) S&S(3) S&S(4) S&S(5) S&S(6) Tanaka et al.(1)

Louver length (ram)

Louver angle (deg)

Fin Tube Fin Fin Fin Tube Rows pitch depth depth length thickness pitch of Dh Data ( m m ) (mm) (mm) ( m m ) ( r a m ) ( r a m ) tubes (mm) point

13 B 13 13 13 13 B B B B C C C Fi F', F', D

1.4 1.4 0.81 0,81 0,81 1.1 0.81 1.1 1.1 1.1 1.397 1.397 1.397 1.65 1.65 1.65 0.85

8.5 8.5 8.5 8.5 8.5 8.5 8.5 5.5 11.5 5.5 16.255 16.255 16.255 7.0987 7.0987 7.0987 2.13

25.5 25.5 29 29 29 30 20 28 22 22 30 30 30 30 30 30 25

2.15 1.7 2.11 1.72 3.33 2.18 2.16 2.16 2.17 2.17 2.117 1.693 1.411 2.117 1.693 1.411 0.51

16 16 32 32 32 32 32 32 32 32 25.4 25.4 25.4 25.4 25.4 25.4 15.6

20.8 20.8 41.6 41.6 41.6 41.6 41.6 41.6 41.6 41.6 25.4 25.4 25.4 25.4 25.4 25.4 15.6

9 9 9 9 9 9 9 6 12 6 18.923 18.923 18.923 8.64 8.64 8.64 2.84

0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.1575 0.1575 0.1575 0.1575 0.1575 0.1575 0.~

C. C C C C C C

1.4 1.4 1.3 1.2 1.1 0.5 1.884

10.2 10.3 10.0 6.8 6.8 5.0 18.5

22 18.5 24.5 24 25.5 28.5 35

1.5 2.0 2.0 1.8 1.8 1.9 1.5

57.4 57.4 37 37 50 47.8 50

57.4 57.4 37 37 50 47.8 50

12.5 12.4 12.4 8.6 9.6 8 20

0.06 0.~ 0.06 0.~ 0.06 0.~ 0.16

11 11 11 11 11 11 11 8

14 8

22.99 22.99 22.99 22.99 22.99 22.99 7.51

3.47 2.76 3.38 2.81 5.02 3.49 3.45 3.14 3.66 3.16 3.505 2.82 2.337 3.073 2.515 2.134 0.824

9 6 6 8 6 8 7 8 6 9 6 4 4 6 5 6 9

2.609 3.400 3.426 2.972 2.984 3.058 3.928

12 12 12 14 11 9 6

et al. 14" 13.9" 13.9*

10.1' 11.1" 9.5* 25 +

* The major tube diameter is not given, a value of 1.5 mm is assumed, + The major tube diameter is not given, a value of 5 mm is assumed. 2 gives the detailed dimensions on the louver fin, and their corresponding definition of the geometric dimensions are drawn :in Fig. 3. The present data bank includes those from Davenport [6] (30 samples, Fig. 1, Type A), T a n a k a et al. [15] (one sample, Fig. 1, Type C). Achaicl~La and Cowell [7] (15 samples, Fig. 1, Type B), Webb [16] (five samples, Fig. 1, Type C), Sunden and Svantesson [9] (6 samples, Fig. 1, Type C), Webb and Jung [1] (6 samples, Fig. 1, Type C and Type E), Rugh et al. [17] (1 sample, Fig. 1, Type D) and Chang and W a n g [11] (27 samples, Fig. 1, Type C). The original test samples of Davenport [6] are 32. However, as depicl:ed by Davenport [6], their samples of no. 11 and no. 12 are damaged. Therefore, these two samples are not included. The present experimental data all use the same fin efficiency calculation (q =(tan(ml))/ml, where m = x/(2ho)/(kf6r)) except Achaichia and Cowell [7]. As indicated by Fig. 1 (Type B), the louver fin geometry of Achaichia and Cowell [7] is quite different from that of corrugated fin geometry. The calculation of the plate-and-tube louver surface efficiency consists of two surface efficiency ql,r/2, respectively, for louvered portions and unlouvered portions. Namely, q = r/,r+r/2(1--r),

(1)

where r is the ratio of the fin area at the sample sides to the overall louver fin area. Achaichia [18] did not give the detailed calculation of r/2.To avoid any misleading of the regression result,

their data are not included in the final regression of the corrugated geometry. However, we also present another correlation that had included the plate-andtube data from Achaichia and Cowell [7], which is illustrated in the appendix. The data reduction methods in the data bank are also quite different as depicted in Table 3. Davenport [6] and T a n a k a et al. [15] use U A - L M T D reduction method with correction factor equal to 1, and other investigators use e-NTU method. The effect of correction factor is insignificant since the corresponding capacity ratio at the highest airflows of their data is very small (a value of 0.05 is shown in the thesis of Davenport [19]), The use of different flow arrangement in e-NTU method is also negligible. This may be seen in a sensitivity analysis by Chang and W a n g [11]. They reduced all the data using an unmixed/mixed relation and an unmixed/unmixed flow arrangement and found that the differences between unmixed/ unmixed and unmixed/mixed situations are quite small. The reason for this phenomenon is analogous to that of Davenport [19]. PREVIOUS LOUVER FIN CORRELATION

Correlation by Davenport [6] (Fig. l, Type A) is :

/

FL -'[1.1

j = 0.249Re£pO.42 = o . ~ . l ~

~o.=o

300 < Renh < 4000.

(2)

538

Y.-J. CHANG and C.-C. WANG

o

__t_

Td

1-Corrugated Louver Fin Geometry

Fd

I

I

!

"

!

I

I

,' *"- U n l o u v e r e d

i

i

Louver

i__

A

A+B=Td _1 I_

/"

B

area

Tube

_1

Plate-and-Tube Louver Fin Geometry. Achaichia and Cowell [7]

Unlouvered area

(

}(c Louver

Fig. 2. Definition of various geometric parameters.

?1 I

Generalized heat transfer correlation

539

Table 2. Geometric dimension of the louver fin Variant

Sample source

Fin material

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68

D(1) D(2) D(3) D(4) D(5) D(6) D(7) D(8) D(9) D(10) D(13) D(14) D(15) D(16) D(17) D(18) D(19) D(20) D(21) D(22) D (22,) D(24.) D(25) D(2~) D(27) D(28) D(29) D(30) D(31) D(32) C&W(1) C&W(2) C&W(3) C&W(4) C&W(5) C&W(6) C&W(7) C&W(8) C&W(9) C&W(I[0) C&W(I[1) C&WCt2) C&W(]I3) C&W(] 4) C&W(] 5) C&W(] 6) C&W(I 7) C&W(I 8) C&W(I 9) C&W(20) C&W(21) C&W(22) C&W(23) C&W(24) C&W(2;5) C&W(26) C&W(27) PSU(1) PSU(10) PSU(11) PSU(12) PSU(15) A&C(I ) A&C(2) A&C(2,) A&C(~.) A&C(5) A&C(6)

Cu Cu Cu Cu Cu Cu Cu Cu Cu Cu Cu Cu Cu Cu Cu Cu Cu Cu Cu Cu Cu Cu Cu Cu Cu Cu Cu Cu Cu Cu A1 AI AI AI AI A1 A1 AI A1 A1 AI AI A1 AI A1 A1 A1 A1 A1 A1 AI AI AI AI A1 A1 AI Cu Cu Cu Cu AI Cu Cu Cu Cu Cu Cu

Fin type I I 1 I 1 I 1 I 1 I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I IV IV IV II1 III III V V V I I I III III III I I I I I I I I I I VI

Louver number 8 8 8 12 12 12 16 16 16 20 16 8 12 12 12 12 12 8 12 16 20 12 12 12 12 12 12 12 12 12 12 12 12 10 10 10 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 22 22 22 18 18 18 10 10 10 10 10 20 20 20 20 20 10

S~ (mm) 4 4 4 3.25 3.25 3.25 2.8 2.8 2.8 2.5 2.8 4 3.25 3.25 3.25 3.25 3.25 4 3.25 2.8 2.5 3.25 3.25 3.25 3.25 3.25 3.25 3.25 3.25 3.25 1.815 1.815 1.815 2.78 2.78 2.78 2.39 2.39 2.39 2.725 2.725 2.725 4.82 4.82 4.82 2.8 2.8 2.8 2.582 2.582 2.582 3.335 3.335 3.335 3.615 3.615 3.615 1.75 3.4671 3.4671 3.4671 1.3335 3.8 3.8 3.8 3.8 3.8 3.4

Si number 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 4 4 4 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

$2 (mm) 8 8 8 6.5 6.5 6.5 5.6 5.6 5.6 5 5.6 8 6.5 6.5 6.5 6.5 6.5 8 6.5 5.6 5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 2.55 2.55 2.55 2.24 2.24 2.24 3.45 3.45 3.45 2.14 2.14 2.14 2.692 2.692 2.692 2.617 2.617 2.617 2.67 2.67 2.67 2.35 2.35 2.35 3.067 3.067 3.067 1.5 2.2098 2.2098 2.2098 3.2512 6 6 6 6 6 6

$2 number I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 l 1 1 1 1 1 1 1 1 3 3 3 2 2 2 1 1 1 3 3 3

Y.-J. CHANG and C.-C. WANG

540

Table 2--continued Variant

Sample source

Fin material

Fin type

Louver number

69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91

A&C(7) A&C(8) A&C(9) A&C(10) A&C(11) A&C(12) A&C(13) A&C(14) A&C(15) W&J(1) W&J(2) W&J(3) W&J(4) W&J(5) W&J(6) R et al. S&S(1) S&S(2) S&S(3) S&S(4) S&S(5) S&S(6) Tanaka et al.

Cu Cu Cu Cu Cu Cu Cu Cu Cu A1 AI A1 A1 A1 AI Cu Cn Cu Cu Cu Cu Cu A1

VI I I I I I I I I I I I I I I I II I I I I III I

10 36 36 36 26 36 26 26 26 10 10 10 10 10 10 10 30 34 22 26 38 48 20

Note that the equation is dimensional, the units of the characteristic length are in ram. They reported that 95% of the experimental data were correlated within 6%. Achaichia and Cowell [7] suggested correlation for the Stanton number (St) based on experiments (Fig. 1, type B), and is given as : (0.936

St

F.

ReLp243--1"76L0

= 1.554

× ReZ°sal\Lpp/IPl

~kZ~p/P|][

3.4 3.505 3.505 3.505 3.65 3.505 3.65 3.65 3.65 4.315 4.315 4.315 2.45 2.45 2.45 1.815 3.5 3.033 2.55 1.7 2.55 4.61 3.793

ReLp >

75.

6 5.005 5.005 5.005 5.15 5.005 5.15 5.15 5.15 2.8 2.8 2.8 4 4 4 3.75 4.2 3.733 3.3 2.4 3.1 4.86 4.734

0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 3 1

Sunden and Svantesson [9] proposed a heat transfer correlation for multilouvered surface (Fig. 1, Type C), [O\o.239[F\o.o2o6(Ft~

J=a'67ReLPo"gll~ )

I~pp)

-0.285

kLp,]

/ L ~0.0671/T, \ - 0 . 2 4 3 X

(3)

Rerp
(

100%.

x,j~ - -j*xp 1' Mean deviation = 1 ( ~ [jp~'d /,}x 100%" N: number of data point.

the corrugated louver fin data are correlated within ___15%, and the present correlation gives a mean deviation of 7.55% of the corrugated louver fin data. TESTS OF THE VARIOUS CORRELATIONS AGAINST THE DATA In addition to the correlation proposed in this paper, several other correlations were tested against the data. These correlations include the D a v e n p o r t [6], the Achaichia and Cowell [7], the Sunden and Svantesson [9] and the Chang and Wang [11] correlations. The results of the comparison of the correlations with all the corrugated louver fin data are shown in Table 4. As seen, the mean deviation of the present correlation, the Davenport correlation, the Achaichia and Cowell [7] correlation, the Chang and Wang correlation [11], and the Sunden and Svantesson [9] correlation are 7.55%, 11.51%, 27.62%, 12.48%, and 15.53%, respectively. The average deviation of the Achaichia and Cowell correlation [7] is approximately equal to its mean deviation. This indicates that their

plate-and-tube louver fin data are considerably higher than those corrugated louver fin data. The reason for this phenomenon is not very clear at present. Further work is required to quantify this phenomenon. One possible explanation is the geometric difference between the plate-and-tube and the corrugated louver fin geometry. Regarding the correlation of heat transfer, the present study does not present the friction factor correlation for the louver fin geometry, because the variations of the friction factors vs the Reynolds number are over 300%. Worse, the friction factors are nonlinear in the logarithm scale plot. Therefore, it is not easy to accurately correlate the friction factor within a short time. We do not include the correlation of friction factor in this paper at this stage. CONCLUSIONS A generalized heat transfer correlation for louver fin geometry is proposed in the present study. A total of 91 samples of louver fin heat exchangers are used in the regression analysis. F o r the corrugated louver fin geometry, it is shown that 89.3 % of the corrugated

Generalized heat transfer correlation

543

2 1.8 1.6 1.4 1.2 ¢)

1 0.8 0.6 0.4 0.2 0

2

3

10

10

Fig. 4. Heat transfer error plots for the corrugated samples.

louver fin d a t a are correlated within + 15% with m e a n deviation o f 7.55%. The inclusion o f the plate-andtube louver fin d a t a in the heat transfer correlation (equation A1) results in a m e a n deviation o f 8.21%.

7. 8.

Acknowledgements---The authors would like to express gratitude for the Energy R&D foundation funding from the Energy Commission of the Ministry of Economic Affairs, Taiwan. The authors are indebted to Professor Ralph Webb for providing valuable suggestions and PSU radiator data.

9.

REFERENCES

10.

1. R. L. Webb and S. H. Jung, Air-side performance of enhanced brazed aluminium heat exchangers, ASHRAE Trans. 98, Pt 2, 3!)1-401 (1992). 2. B. Sunden and J. Svantesson, Thermal hydraulic performance of new multilouvered fins, in Proceedings of the 9th Int. Heat Transfer Conf., Vol. 14-HX-16, pp. 9196 (1990). 3. Y. J. Chang, C. C. Wang, R. J. Shyu and Y. Z. R. Hu, Performance comparison between automotive fiat tube condenser and round tube condenser, in 4th ASME/JSME Thermal Engineering Joint Conf. Vol. 4, pp. 331-336 (199.';). 4. T. A. Cowell, A general method for the comparison of compact heat transfer surfaces, ,L Heat Transfer 112, 288-294 (1990). 5. T. A. Cowell, M. R. Heikal and A. Achaichia, Flow and heat transfer in compact louvered fin surfaces, Expl. Thermal Fluid Sci. 10, 192-199 (1995). 6. C. J. Davenport, Correlation for heat transfer and flow

11. 12. 13. 14.

15.

friction characteristics of louvered fin, AIChE Syrup. Ser. 79, 19-27 (1983). A. Achaichia and T. A. Cowell, Heat transfer and pressure drop characteristics of flat tube and louvered plated fin surfaces, Expl. Thermal ~luid Sci. 1, 147-157 (1988). J, P. Rugh, J. T. Pearson and S. Ramadhyani, A study of a very compact heat exchanger used for passenger compartment heating in automobiles, in Compact Heat Exchangers for Power and Process Industries, ASME Symp. Ser., HTD-Vol. 201, pp. 15-24. ASME, New York (1992). B. Sunden and J. Svantesson, Correlation of j- and ffactors for multilouvered heat transfer surfaces, in Proceedings of the 3rd UK National Heat Transfer ConS, pp. 805-811 (1992). Y.J. Chang, C. C. Wang and W. R. Chang, Heat transfer and flow characteristics of automotive brazed aluminium heat exchangers, ASHARE Trans. 100, Pt 2, 643-652 (1994). Y. J. Chang and C. C. Wang, Air side performance of brazed aluminium heat exchangers, J. Enhanced Heat Transfer 3, 15-28 (1996). A. Shanoun and R. L. Webb, Prediction of heat transfer and friction for the louver fin geometry, J. Heat Transfer 114, 893-900 (1992). E. R. Dillen and R. L. Webb, Rationally based heat transfer and friction correlations for the louver fin geometry, SAE Technical Paper Series 940504 (1994). R, L. Webb, Y. J. Chang and C. C. Wang, Heat transfer and friction correlations for the louver fin geometry, in Proceedings of the Vehicle Thermal Management System, Vol. 2, pp. 533-541 (1995). T. Tanaka, M. Itoh, M. Kudoh and A. Tomita, Improvement of compact heat exchangers with inclined louvered fins, Bull. JSME 27, 219-226 (1984).

544

Y.-J. CHANG and C.-C. WANG

16. R. L. Webb, PSU radiators test data, unpublished data for five radiators (1988). 17. J. P. Rugh, J. T. Pearson and S. Ramadhyani, A study of a very compact heat exchanger used for passenger compartment heating in automobiles, in Compact Heat Exchangers for Power and Process Industries, ASME Symp. Ser., HTD-Vol. 201, pp. 15-24. ASME, New York (1992). 18. A. Achaichia, The performance of louvered tube-andplate fin heat transfer surfaces, Ph.D. Thesis, Brighton Polytechnic, pp. 72-73 (1987). 19. C.J. Davenport, Heat transfer and fluid flow in louvered triangular ducts, Ph.D. thesis, Coventry (Lancaster) Polytechnic, p. 38 (1987).

x \~)

\~)

\~-~p,]

.

(AI)

Figure A1 shows the comparison of the experimental data with equation (A1). The present correlation (equation (A1)) can predict 87.8% of the experimental data within + 15%, and a mean deviation of 8.21%. Detailed comparisons with other correlations are also depicted in Table A1. For a very quick evaluation of heat transfer coefficient in engineering application, a very simple form of the correlation is proposed as follows :

APPENDIX

j = 0.425Reap°'496.

Although there are geometric differences between plateand-tube and corrugated louver fin geometry, we have included all the experimental data of the 91 samples in the regression which yields :

This simple equation can describe 88.2% of the data bank within 25%, and 70.7% of the data bank within 15%. The mean deviation of this simple equation is 12.7%.

(A2)

2 1.8 1.6 1.4 1.2 O



0.8

0.6 0.4 0.2 0 10

2

10 ReLp

3

Fig. A1. Heat transfer error plots for the all louver fin samples. Table A 1. Comparison of the correlation with all the experimental data Deviation

Present correlation

Davenport [6]

Achaichia and Cowell [7]

Chang and Wang [ 1 1 ]

Sunden and Svantesson [9]

__.10% + 15% + 20% _+25% Average deviation Mean deviation

71.48% 87.76% 94.01% 97.14% 1.02% 8.21%

54.82% 68.88% 77.99% 85.42% 0.37% 12.39%

30.60% 40.36% 48.57% 57.94% 22.73% 24.43%

47.66% 66.02% 79.56% 78.89% 1.56% 12.88%

35.42% 50.52% 67.19% 79.82% - 7.12% 16.43%