Chap. 4 HG3F/4F Specifications - Idec

202 downloads 3144 Views 461KB Size Report
Chapter 4 Specifications of HG3F/4F. 1 Product List ..... Japanese manual ..... A6. 39. CSEL#. 15. A5. 40. VS2#. 16. A4. 41. RESET. 17. A3. 42. WAIT#. 18. A2. 43.
Chapter 4 Specifications of HG3F/4F

1 Product List................................................................................................4-2 1.1 Main Unit..................................................................................................................... 4-2 1.2 Accessories ................................................................................................................... 4-2 1.3 Options ......................................................................................................................... 4-2

2 Part names and Functions .........................................................................4-4 2.1 Front............................................................................................................................. 4-4 2.2 Rear .............................................................................................................................. 4-5 2.3 Layout of Touch Switches ........................................................................................... 4-7

3 Main Unit Specifications ............................................................................4-9

Chap.4

3.1 Applicable Standards .................................................................................................. 4-9 3.2 General Specifications................................................................................................. 4-9 3.3 External Dimensions................................................................................................. 4-11 3.4 Function Specifications ............................................................................................. 4-13 3.5 Display Specifications ............................................................................................... 4-14 3.6 Operation Specifications ........................................................................................... 4-15 3.7 Power supply Input Specifications ........................................................................... 4-15 3.8 Serial Interface1 Specifications ................................................................................ 4-16 3.9 Serial Interface2 Specifications ................................................................................ 4-17 3.10 Expansion Interface Specifications ........................................................................ 4-18 3.11 O/I link Interface Specifications ............................................................................. 4-18 3.12 Ethernet (LAN) Interface Specifications................................................................ 4-18 3.13 Compact Flash(CF) interface specification ............................................................ 4-19 3.14 Parallel Interface Specifications............................................................................. 4-19

4 Installation and Wiring .............................................................................4-21 4.1 Installation Location ................................................................................................. 4-21 4.2 Installation................................................................................................................. 4-21 4.3 Wiring......................................................................................................................... 4-22

5 Inspection ................................................................................................4-24

4-1

Chapter4 Specifications of HG3F/4F

1 Product List 1.1 Main Unit

1.3 Options

Main Unit

Configuration software (WindO/I-NV2)

Display Type 10.4inch

Interface RS232C/485(422)

Type No. HG3F-FT22TF-*

TFT color

Ethernet·CF I/F

LCD

RS232C/485(422)

HG3F-FT22VF-*

12.1inch

RS232C/485(422)

HG4F-JT22TF-*

TFT color

Ethernet·CF I/F

LCD

RS232C/485(422)

*: Main Unit Color

HG4F-JT22VF-*

1.2 Accessories HG9Z-4K1 B-748, 749

Japanese manual

HG9Y-B1119

English manual

SW1A-W1C

CD-ROM

Maintenance Cable HG9Z-XCM22

Description 2m D-sub 9P socket (PC side) for Windows PC

Mounting Clip HG9Z-4K1PN10

Operating Instruction Sheet (1) Operating Instruction Sheet (1)

Description Mounting clip (HG9Z-4K1), 10 pieces per package

Mounting Clip (4)

(HG4F)

4-2

HG9Y-B1118

Type No. Notes

(HG3F) B-750, 751

Description

Type No.

B: Dark gray W: Light gray

Type No.

Type No.

PLC Connecting Cable Type No.

Description

PF3S-KS1

For IDEC FA3S Link Unit, 5m

FC4A-KC2C

For IDEC MicroSmart, 5m

HG9Z-3C115

For IDEC MICRO3, 5m

HG9Z-3C125

For IDEC MICRO3C, OpenNet Controller MicroSmart, 5m

HG9Z-3C135

RS-232C (25pin, D-sub), for Mitsubishi, Omron, etc. link unit, 5m

HG9Z-3C145

RS-232C (9pin, D-sub), Mitsubishi, etc. link unit, 5m

HG9Z-3C155

RS-232C (9pin, D-sub), Omron etc. RS-232C I/F, 5m

HG9Z-3C165

For Mitsubishi A and FX series programming port, 5m

1 Product List Protective Sheet Type No. HG9Z-3DAPN02

Description Protective sheet for touch switch type (2 sheets per package for HG3F)

HG9Z-4DAPN02

Protective sheet for touch switch type (2 sheets per package for HG4F)

Replacement Backlight Type No.

Description

HG9Z-3FB

Backlight for HG3F

HG9Z-4FB1 or

Backlight for HG4F

HG9Z-4FB2 (*)

Expansion Unit Type No. HG9Z-3P102

Description Digital I/O (16 inputs and 16 outputs)

O/I Link Unit Type No.

Dedicated communication unit

CF Card Type No. HG9Z-MF32

Chap.4

HG9Z-2G1

Description

Description CF Card (32MB)

(*) Type No. of Replacement Backlight The HG4F uses two different types of replacement backlights depending on the production date. When ordering a replacement backlight, look for the Replacement Backlight Type No. label on the back of the HG4F. For the label position, see the figure “2 Part names and Functions”. When the label is found, specify HG9Z-4FB1 or HG9Z-4FB2 indicated on the label. If the label is not found, specify HG9Z-4FB1.

4-3

Chapter4 Specifications of HG3F/4F

2 Part names and Functions 2.1 Front • HG3F-FT22∆F-* (Touch Switch Type) Touch switches

• HG4F-JT22∆F-* (Touch Switch Type) Touch switches

4-4

2 Part names and Functions

2.2 Rear (3) • HG3F-FT22ΔF-*

(10)

(8) (7)

(11)

(5) (1)

(2) (6)

(9)

(4)

(3) • HG4F-JT22ΔF-*

(10) (8) Chap.4

(7)

(11)

(5)

(1)

(2)

(12)

(6)

(9)

(4)

4-5

Chapter4 Specifications of HG3F/4F No. 1 2 3 4 5 6 7 8 9 10 11 12

4-6

Name Power Supply and Function Ground Serial Interface 2 Expansion Interface Serial Interface 1 O/I Link Interface Parallel Interface CF Interface Access Stop Switch Ethernet Interface Rubber Packing Nameplate Replacement Backlight Type No. Label

Description Terminal block 3P Mini-DIN 8P connector 60P connector D-sub25P connector Special connector D-sub25P connector Connects the Compact Flash CF extraction permission switch Connects to Ethernet (10BASE-T)

Indicates the replacement backlight Type No.

2 Part names and Functions

2.3 Layout of Touch Switches Touch switches can be placed on the grids. The physical switch layout is as shown in the illustration below. ・ HG3F-FT22ΔF-*

640

480

20

20

800

600

20

20

Chap.4

・ HG4F-JT22ΔF-*

4-7

Chapter4 Specifications of HG3F/4F ・ EX4R 800

600

1

1

• Pressing the touch panel of EX4R will not work while the maintenance cable is inserted into Serial Interface 2. • For the initial settings of the analog touch panel, refer to Chapter 33 "2.1.2 Initialize" in the "MICRO/I HG2G, HG1F/2F/2S/3F/4F Instruction Manual". • When more than one button is pressed, the touch screen will not be able to detect such operation. Instead, the center point between buttons pressed in the display area will be triggered. This is due to the detection characteristics of the analog touch panel. When more than one button is pressed simultaneously, the resulting operation may vary.

4-8

3 Main Unit Specifications

3 Main Unit Specifications 3.1 Applicable Standards Safety Standards

EMC Standards

Environmental Specifications

UL508, UL1604,

Operating Ambient

HG3F:0 to 50°C

CSA C22.2

Temperature

HG4F:0 to 45°C

IEC/EN61131

(operation)

(no freezing)

IEC/EN61000-6-4,

Operating Relative

20 to 85%RH (no dew)

IEC/EN61131-2

Humidity (operation)

(no condensation)

Storage Ambient

-20 to 60°C

Temperature

(no freezing)

Storage Relative

20 to 85%RH

Humidity

(no condensation)

Altitude

0 to 2000m (operation),

No.213

3.2 General Specifications Electrical Specifications Rated Operating

24VDC

0 to 3000m (transport)

Voltage Power Voltage

80% to 120% of rated

Range

voltage (including ripple)

Power

25W maximum

Consumption Allowable

10ms maximum, Level PS-2

Momentary Power (IEC/EN61131) Inrush Current

15A maximum.(cold start)

Dielectric Strength 1500VAC 10mA, 1 minute (between power terminals and

10 to 55Hz 9.8m/s2 (2 hours each in 3 axes) (IEC60068-2-6)

Shock

147m/s2 ,11ms

Resistance

(5 shocks each in 3 axes)

Pollution

Pollution degree 2

Degree

(IEC60664-1)

Corrosion Immunity

Free from corrosive gases

(IEC60068-2-27) Chap.4

Interruption

(IEC61131-2) Vibration Resistance

FG) Insulation

10MΩ minimum (500VDC

Effect of Incorrect Connection

Resistance

mega)

Reversal of DC

No damage but the equipment will

(between power terminals and

power supply

not operate

FG)

polarity Connection to

Permanent failure likely

Power supply that exceeds ratings

Earthing Function earth

Wire to ensure stable equipment operation

4-9

Chapter4 Specifications of HG3F/4F Construction

Noise Specifications

Installation

Buried panel

Electrostatic ESD-3 (RH-1)

Protection

IP66 (at the front of the

Discharge

Terminals Dimensions Weight

IEC/EN61000-4-2

level 3

installation panel),

Contact +/-6KV/

NEMA TYPE 4,4x,13

Air +/-8KV

Power supply input: M4 screw

Electro-

10V/m AM80%

Tightening torque: 1.0 to 1.3Nm

magnetic

80MHz

HG3F: 324(W) x 240(H) x 56(D)mm

Field

to 1000 MHz

HG4F: 348(W) x 270(H) x 58(D)mm

Fast

Common mode:

HG3F: 2800g (approx.)

Transient

Level 3

HG3F: 3400g (approx.)

Burst

Power supply:

Withstand-

+/-2KV

ability

Communication

IEC/EN61000-4-3

IEC/EN61000-4-4

line: +/-1KV Damped

Serial mode:

Oscillatory

Power supply:

Wave

+/-1KV

Power-up

Between 500V

Surge

L-FG

Immunity Radiated Emission

4-10

IEC/EN61000-6-4

IEC/EN61000-4-12

IEC/EN61000-4-5

3 Main Unit Specifications

3.3 External Dimensions HG3F-FT22ΔF-*

(Panel Thickness)

Chap.4

4-11

Chapter4 Specifications of HG3F/4F

(Panel Thickness)

HG4F-JT22ΔF-*

4-12

3 Main Unit Specifications

3.4 Function Specifications Number of

Base Screens: 3,000 screens

Goto Screen Command

screens

Popup Screens: 3,000 screens

Print Command

Screen

Approx. 6Mbyte max.(Flash memory)

Screen Script Command

memory

(including the optional fonts)

Multi Command Timer

Screen types Base Screen, Popup Screen, Number of

System Screen

Operation

480/screen (Base Screen)

modes

parts

480/screen (Popup screen)

Number of

256 read, 512 write/screen

host devices

Parts

Run Mode: Normal operation Data Transfer Mode: Data upload and download System Mode:

(Base Screen) 64 read, 128 write/screen

Initial setting,

(Popup Screen)

clock setting,

Bit Button

system information,

Word Button

self diagnosis and debug

Goto Screen Button

Screen

WindO/I-NV2 software

Print Button

creation and

application

Key Button

operation

Multi Button

settings

Keypad

Calendar

Year, Month, Day, Hour, Min., Sec. and Day-of-week

Potentiometer

+/-30 sec. per month (at 25°C)

Numerical Input

Power failure Maintenance object:

Character Input

maintenance Calendar, Alarm Log Data: 1024

Pilot Lamp

points (max.), Data Log Data: approx.

Multi-State Lamp

3000 points (max.), and 1024 keep

Picture Display

internal relay/1024 resister

Message Display

Maintenance period:

Message Switching Display

1 month (at 25°C)

Chap.4

Selector Switch

Alarm List Display Alarm Log Display Numerical Display Bar Graph Trend Chart Pie Chart Meter Calendar Bit Write Command Word Write Command

4-13

Chapter4 Specifications of HG3F/4F

3.5 Display Specifications Display Functions Display

HG3F: 10.4 inch TFT color LCD

16 x 32 dots, 24 x 48 dots,

(transparent type)

32 x 64 dots:

HG4F: 12.1 inch TFT color LCD

ISO-8859-1(European)

(transparent type) Effective

16 x 16 dot: Japanese: 1st and 2nd

display HG3F: 211(W) x 158(H) mm

standard JIS, Chinese,

HG4F: 246(W) x 184(H) mm

area

Korean, Taiwanese

Display resolution HG3F: 640(W) x 480(H) dots

32 x 32 dots:

HG4F: 800(W) x 600(H) dots Pixel pitch

HG3F: 0.33(W) x 0.33(H) mm

Japanese: 1st and 2nd

HG4F: 0.3075(W) x 0.3075(H)

standard JIS

mm

Charact Magnification: 0.5, 1, 2, 3, 4

256

er

Contrast

Can be adjusted from the front

attribute Attributes: Blink, reverse,

adjustment

touch panel

s

Display colors

Character Size/ Display

number

1/4 size: 8 x 8 dots/ HG3F: 80 characters x 60 lines HG4F: 100 characters x 75 lines 1/2 size: 8 x 16 dots/ HG3F: 80 characters x 30 lines HG4F: 100 characters x 37 lines Full size: 16 x 16 dots/ HG3F: 40 characters x 30 lines HG4F: 50 characters x 37 lines Double size: 32 x 32 dots/ HG3F: 20 characters x 15 lines HG4F: 25 characters x 18 lines

Types

8 x 8 dots, 8 x 16 dot: English, Katakana, Symbols

(JIS8

bit

code),

ISO-8859-1(European), ANSI1250(Central ANSI1257(Baltic), ANSI1251(Cyrillic)

4-14

European),

and 8 (ver. and hor.) bold, embossed

3 Main Unit Specifications

Graphics

Line, rectangle, Polyline

Types

polygon, circle, ellipse, pie,

Display

arc, polygon (3, 4, 5, 6, and 8 sided), bitmap image and paint Line

Solid, dotted, dashed, long

types

dashed, long dashed dot and long dashed dot dot 1,2,3 and 5 dots

Line width Graphic

Blink switch display

symbol

between specified colors (1

attribute

or 0.5 second period)

Presumed Life Of

HG3F: 100,000hours (min.)

Display

HG4F: 80,000 hours (min.)

3.6 Operation Specifications Touch Switches Switch mechanism

Touch switches

Switch method

Matrix resistive film type HG3F: 32 x 24

Composition

HG4F: 40 x 30 Operation force

0.2 to 0.8N

Life

1,000,000 cycles min.

Confirmation

Electronic buzzer

3.7 Power supply Input Specifications Wire: 0.75-2.0mm2(AWG18-14)

Wiring

Maintain separation between the input wiring and the power, output and

(at 25°C)

communications wiring. Connector

Terminal block 3P: M4 screw

Backlight Light Source

Cold-cathode tube

Connector Pin Layout

Presumed Life Of Standard 50,000 hours*

1

*Luminance drop to half after

2

3

continuous lighting at room temperature Replacement

Possible

Control

Auto off

+

Chap.4

Back Light



Connector Pin Functions Symbol

Function

+

Power supply +24V DC

-

Power supply -24V DC Function ground

Ground the functional ground terminal to ensure stable operation.

4-15

Chapter4 Specifications of HG3F/4F

3.8 Serial Interface1 Specifications Only one of the RS-232C or RS-485 (422)

RS-232C Electrical

EIA RS-232C compliant

ports can be used at one time.

characteristics Transmission

1200, 2400, 4800, 9600,

speed

19200, 38400, 57600 and 115200bps

Connector Connector

(socket)

Synchronization Asynchronous Communication

Half or full duplex

Control system

Hardware control/none

Protocol

(1) PLC-link protocol for a variety of PLCs and communication units (2) DM Link

Transmission

15m (5m when connected to a

distance

PLC programming port)

Connection

1:1

format

RS-485 (422) EIA RS-485 (422) compliant 1200, 2400, 4800, 9600, 19200, 38400, 57600 and

115200bps Synchronization Asynchronous Communication Half or full duplex method Control system Hardware control/none Protocol

(1) PLC-link protocol for a variety of PLCs and communication units (2) DM Link

Transmission distance

300m (5m when connected to a

Connection format

1:1 or 1:N

4-16

Connecting and

500 cycles (min.)

disconnecting cycles

method

Electrical characteristics Transmission speed

D-sub 25P connector

PLC programming port)

Connector Pin Layout

3 Main Unit Specifications

3.9 Serial Interface2 Specifications

Connector Pin Functions No. Name 1

FG

Frame Ground

2

SD

Send Data (RS-232C)

3

RD Receive Data (RS-232C)

4

RS

Send Demand (RS-232C)

5

CS

Clear to Send (RS-232C)

6

---

---

7

SG

Signal Ground

8

---

--RS-485

characteristics

RS-422

RDA Receive Data A

RD+

11

SDA Send Data A

SD+ Send Data (+)

TERM Terminator*1 Receive Data

---

---

---

---

13

---

---

---

---

---

---

---

---

---

---

Mini DIN8P connector

Connection and 1000 cycles (min.) disconnection cycles

Connector Pin Layout 6

7 8

SD- Send Data (-) RD-

CS-

19

RS-

(-) ---

CS+

22

RS+

5

Clear to Send Request to Send (-) Clear to Send (+) Request to Send (+)

23

---

---

---

---

24

---

---

---

---

25

---

---

---

---

*1 To enable the 330Ω built-in terminator, connect terminal No.9 [TERM] and terminal No.10 [RDA/RD (+)] together.

4 2

(-)

Data Terminal Ready (RS-232C)

21

3

Receive Data

---

18

20 ER

Dedicated protocol

Connector

Chap.4

17

RDB Receive Data B

Protocol

(+)

12

16

and 115200 bps

method

10

SDB Send Data B

9600, 19200, 38400, 57600

speed

Communication Half duplex

TERM Terminator*1

15

Transmission

Synchronization Asynchronous

9

14

EIA RS-232C compliant

Electrical

Function

1

Connector Pin Functions No.

Name

Function

1

RS

Request to send

2

ER

Data terminal ready

3

SD

Send data

4

RD

Receive data

5

DR

Data set ready

6

EN

Use as needed

7

SG

Signal ground

8

NC

No connection

Connect pin 6 (EN) and pin 2 (ER) unless performing maintenance communications for downloading project data.

4-17

Chapter4 Specifications of HG3F/4F

3.10 Expansion Interface

3.12 Ethernet (LAN) Interface

Specifications Method

Specifications

Dedicated Interface to Expansion Unit

Compatible Unit Digital I/O unit Electrical

HG Series dedicated bus

characteristics Connector

Internet Specification: IEEE802.3 compliance Network Type: 10BASE-T Connector: RJ-45 modular jack

Connector Pin Layout Dedicated connector

Outline The HG3F/4F can be used in conjunction with optional units. Refer to the Expansion Unit instruction manual for details.

3.11 O/I link Interface Specifications Method Connector

Dedicated interface to O/I link

Connector Pin Functions Pin #

Name

Function

1

TDP

Transmit data+

Dedicated connector

2

TDM

Transmit data-

3

RDP

Received data+

4

NC

No connection

5

NC

No connection

6

RDM

Received data-

7

NC

No connection

8

NC

No connection

cable Conductor

resistance:85Ω/km

maximum Shield

resistance:20Ω/km

maximum

Outline The HG3F/4F Operator Interface can be connected to an O/I Link Unit for 1:N communication with a PLC. This allows high-speed communication with the PLC host.

4-18

1

Unit Recommended 0.3mm2 Twisted-pair shielded cable

8

standard

3 Main Unit Specifications

3.13 Compact Flash(CF) interface specification Interface specification:CFA* standard compliance Connector: 50-pin CF card connector

3.14 Parallel Interface Specifications Electrical

Centronics interface

characteristics

compliant

Support

ESC/P, PC-PR, PCL

The printer is initialized in the following

Connector Pin Layout

cases.

Eject Bottom

• The HG3F/4F is turned off when connected to a printer that is on.

1 Pin No.

50

26 Name

Pin No.

25

• The printer cable is disconnected and connected again while the HG3F/4F is off and the printer is on.

Name

GND

26

CD1#

2

D3

27

D11

3

D4

28

D12

4

D5

29

D13

5

D6

30

D14

6

D7

31

D15

7

CE1#

32

CE2#

8

A10

33

VS1#

9

OE#

34

IORD#

10

A9

35

IOWR#

11

A8

36

WE#

12

A7

37

IREQ#

13

VCC

38

VCC

14

A6

39

CSEL#

15

A5

40

VS2#

16

A4

41

RESET

17

A3

42

WAIT#

18

A2

43

INPACK#

19

A1

44

REG#

20

A0

45

BVD/SPKR#

21

D0

46

BVD1/STSC

22

D1

47

D8

23

D2

48

D9

Connector Connector

D-sub 25P connector (socket)

Connecting and

500 cycle (min.)

disconnecting cycles

Connector Pin Layout Chap.4

1

HG#

24

WP_IOIS16#

49

D10

25

CD2#

50

GND

4-19

Chapter4 Specifications of HG3F/4F Connector Pin Functions

Please perform the following wiring when HG3F/4F be connected with the printer. Refer to the printer instruction manual for details.

Pin No.

Name

Function

1

STRB

Strobe

2

PD0

Data Bit 0

3

PD1

Data Bit 1

4

PD2

Data Bit 2

5

PD3

Data Bit 3

D-sub 25P

6

PD4

Data Bit 4

Connector

7

PD5

Data Bit 5

8

PD6

Data Bit 6

9

PD7

Data Bit 7

10

---

11

BUSY

12

---

---

13

---

---

14

---

15

---

16

INIT

17

---

---

18

SG

19

4-20

HG3F/4F

Name

Printer

Pin No.

Shielding

Name

Shield

Cover

Shield

STRB

1

STROBE

PD0

2

DATA0

---

PD1

3

DATA1

---

PD2

4

DATA2

PD3

5

DATA3

Signal ground

PD4

6

DATA4

SG

Signal ground

PD5

7

DATA5

20

SG

Signal ground

21

SG

Signal ground

PD6

8

DATA6

22

SG

Signal ground

PD7

9

DATA7

23

SG

Signal ground

BUSY

11

BUSY

24

SG

Signal ground

25

SG

Signal ground

INIT

16

INIT

SG

18-25

SG

--Busy

Reset

4 Installation and Wiring

4 Installation and Wiring Be aware of the following when mounting the HG Series main unit and wiring it to the host unit.

forced-air cooling, or lower the ambient

Operating Environmental Considerations To ensure reliable and safe operation of the equipment, avoid the types of installation locations listed below. ・ Places where there is a lot of dust, salt or iron filings. ・ Places where the equipment will be splashed with oil or chemicals. ・ Places where the equipment will be exposed to direct sunlight. ・ Places where corrosive or flammable gasses are present. where

airflow for cooling when installed vertically. If you install it using any other orientation, use

4.1 Installation Location

・ Places

・ The HG3F/4F has been designed to use natural

operating temperature.

4.2 Installation Place the HG3F/4F in a panel cut-out and fasten with the attached mounting clips at four places to a torque of 0.4 through 0.6 N・m uniformly. Do not tighten excessively or unevenly, otherwise the HG3F/4F may be damaged. Take into consideration the viewing angle and switch operation factors when choosing the installation height. Panel

vibration

will

be

Mounting Clip

directly

transmitted to the equipment. sudden temperature changes.

HG3F/4F

Chap.4

・ Places where condensation may occur due to

Ambient temperature considerations ・ Allow sufficient space for ventilation, and install the equipment away from heat sources. ・ Allow at least 100mm between the HG3F/4F and walls or other equipment. ・ If installing the HG3F/4F in a location where the

If the installation screws are not installed so that they are at right angles to the panel, the unit may separate from the panel.

ambient temperature will exceed the allowed rating, install cooling fans or air-conditioning equipment.

4-21

Chapter4 Specifications of HG3F/4F

4.3 Wiring Panel Cut-out Dimensions [Dimension: mm]

Wiring Considerations ・ Do not install the HG3F/4F close to high-voltage

HG3F-FT22∆F-*

or arc-generating equipment (such as circuit breakers etc.). ・ Install the unit at least 200mm from the high

228±0.5

input voltage of the power supply. ・ In the case of DC power supply models, keep

t = 2 to 5

the distance between the unit and the power supply as short as possible. ・ Use separate power supplies and wiring for

302±0.5

electromotive equipment and I/O equipment. ・ A host connection cable is provided with the equipment. Please specify your requirement.

HG4F-JT22∆F-*

・ If you will use your own cable for connecting to the host, ensure that the connector and wiring

258+10

are of the recommended type. Also, do not exceed the recommended length for the

t = 2 to 5

332+10

4-22

cable.

4 Installation and Wiring ・ Use an IEC60127-approved fuse of 1A on the

Wiring to the Power Supply Terminals

power line to meet voltage and current

・ Terminal No. allocation is as follows.

requirements (recommended fuse: Littelfuse 5 x 20mm slow-blow type 218000 series Type T). This is required when exporting equipment containing the HG3F/4F to Europe.

Note: Special Conditions



― ・ If you decide to use a single power supply for HG3F/4F with more than one external device,

Symbol

・ Use

take extra precautions.

Function

+

Power supply +24VDC

Some external devices may produce electrical



Power supply -24VDC

noise and short circuit the entire system setup,

Function ground

therefore,

applicable

cables

for

wiring

and

recommended ferrules, (made by JST ) as follows: Applicable cable -------- Twist the AWG14 to 18(0.75 to 2.0mm2)

circuit

damaging

of

the

HG3F/4F

communication

and

non-isolated

Communication Device (i.e. PLC). To prevent such damage, choose a proper solution depending on your system setup. ・ Use a separate earth ground from the external

considerable.

・ The wire for grounding should be thick and short in order to direct the noise from the

・ The tightening torque range is 1.0N.m to 1.3N.m.

Chap.4

noise source device.

Use V1.25-4(RAV1.25-4),V2-P4(JST)

noise source device to the earth ground. ・ Use a separate power supply from the external

2

・ Twist the AWG14 to 18(0.75 to 2.0mm ) power

noise source device.

supply wires as tightly together as possible,

・ Disconnect the Function Ground terminal of

and keep the wiring distance between the

HG3F/4F from earth ground. (Be sure to

power supply and the unit as short as

check the EMC performance on your system

possible.

because

・ Function Ground and Signal Ground are connected internally of HG3F/HG4F. ・ Use separate power supplies and wiring for electromotive equipment and I/O equipment. ・ For safety purposes, connect Function Ground terminal of HG3F/HG4F to earth ground.

if

disconnected,

the it

Function may

Ground

decrease

is

EMC

performance.) ・ Connect Function Ground terminal of HG3F/4F and 0V of the Power Supply in order to direct the noise to 0V. This will avoid the noise from going through the communication circuit.

4-23

Chapter4 Specifications of HG3F/4F ・ Insert an isolator on the communication line of HG3F/HG4F

and

the

non-isolated

communication device (i.e. PLC) to prevent damage.

Wiring Serial Interface 1 ・ Use the recommended connector (connector: JBZ-25P-90(JST), cover: J-C25-C2(JST)).

5 Inspection Periodically inspect the HG3F/4F to keep it in the best operating condition at all times. ・ The HG3F/4F display screen and protective sheet are easily damaged. Never attempt to operate the unit with tools or other hard objects.

・ Perform the wiring in accordance with the

・ To clean the display screen, wipe it with a soft

requirements of the communication method

cloth moistened with a mild detergent or

used. This will minimize the influence of

alcohol.

external electrical noise and electrical noise generated by the wiring itself. EMC evaluation has not been done for the cables. ・ Use shielding for the cables, and install line clamp filters near each end of the cable.

Example TDK: ZCAT2035-0930

Never attempt to clean the display screen using paint thinner, ammonia, strong acid, strong alkaline, or other powerful solvents. ・ Terminals and connectors Check for loose screws, loose connectors and damaged wiring. ・ Installation Check the installation brackets and screws for warping and looseness.

4-24