Indian code for reinforced concrete design, published by the Bureau of ...
Structure and structural elements shall normally be designed by Limit State.
Method.
Chapter - 2
STRUCTURAL DESIGN OF RCC BUILDING COMPONENTS
Rajendra Mathur Dy. Dir(BS-C) 09412739 232(M) e-mail –
[email protected]
©BSNL India
For Internal Circulation Only
Page: 1
Structural Design of RCC Building Components 1.0 Introduction The procedure for anal ysis and design of a given building will depend on the t ype of building, its complexit y, the number of stories etc. First the architectural drawings of the building are studied, structural sys tem is finalized sizes of structural members are decided and brought to the knowledge of the concerned architect. The procedure for structural design will involve some steps which will depend on the t ype of building and also its complexity and the time ava ilable for structural design. Often, the work is required to start soon, so the steps in design are to be arranged in such a way the foundation drawings can be taken up in hand within a reasonable period of time. Further, before starting the structural design, the following information of data are required: (i) A set of architectural drawings;(ii) Soil Investigation report (SIR) of soil data in lieu thereof; (iii) Location of the place or cit y in order to decide on wind and seismic loadings;(iv) Data for lifts, water tank capacities on top, special roof features or loadings, etc. Choice of an appropriate structural system for a given building is vital for its economy and safet y. There are two t ype of building s ystems:(a) Load Bearing Masonry Buildings. (b) Framed Buildings. (a) Load Bearing Masonry Buildings: Small buildings like houses with small spans of beams, slabs generall y constructed as load bearing brick walls with reinforced concrete slab beams. This system is suitable for building up to four or less stories.(as shown in fig. below). In such buildings crushing strength of bricks shall be 100 kg/cm 2 minimum for four stories. This s ystem is adequate for vertical lo ads it also serves to resists horizontal loads like wind & earthquake by box action . Further, to ensure its action against earthquake , it is necessary to provide RCC Bands in horizontal & vertical reinforcement in brick wall as per IS: 43261967( Indian Standards Code of Practice for Earthquake Resistant Construction of Buildings.) . In some Buildings, 115mm thick brick walls are provided since these walls are incapable of supporting vertical loads, beams have to be provide along their lengths to support adjoining slab & the weight of 115mm thick brick wall of upper storey. These beams are to rest on 230 mm thick brick walls or reinforced concrete columns if required. The design of Load Bearing ©BSNL India
For Internal Circulation Only
Page: 2
Masonry Buildings are done as per IS:1905-1980 (Indian Standards Code of Practice for Structural Safety of Buildings: Masonry Walls(Second Revision).
Load bearing brick wall Structural system (b) Framed Buildings:In these t ypes of buildings reinforced concrete frames are provided in both principal directions to resist vertical loads and the vertical loads are transmitted to vertical framing system i.e columns and Foundations. This t ype of system is effective in resisting both vertical & horizontal loads. The brick walls are to be regarded as non load bearing filler walls onl y. This system is suitable for multi -storied building which is also effective in resisting horizontal loads due to earthquake. In this system the floor slabs, generall y 10 0-150 mm thick with spans ranging from 3.0 m to 7.0 m. In certain earthquake prone areas, even single or double storey buildings are made framed structures for safet y reasons. Also the single storey buildings of large storey heights (5.0m or more ) ,like electric substation etc. are made
©BSNL India
For Internal Circulation Only
Page: 3
framed structure as brick walls of large heights are slender and load carrying capacit y of such walls reduces due to slenderness.
Framed Structural system
2.0 Basic Codes for Design . The design should be carried so as to conform to the following Indian code for reinforced concrete design, published by the Bureau of Indian Standards, New Delhi: Purpose of Codes National building codes have been formulated in different countries to lay down guidelines for the design and construction of structure. The codes have evolved from the collective wisdom of expert structural engineers, gained over the years. These codes are periodicall y revised to bring them in line with current rese arch, and often, current trends. The codes serve at least four distinct functions .
©BSNL India
For Internal Circulation Only
Page: 4
Firstl y, they ensure adequate structural safet y, by specifying certain essential minimum requirement for design. Secondl y, they render the task of the designer relativel y simple; often, the result of sophisticate anal yses is made available in the form of a simple formula or chart. Thirdl y, the codes ensure a measure of consistency among different designers. Finall y, they have some legal validit y in that they protect the structural designer from any liabilit y due to structural failures that are caused by inadequate supervision and/or fault y material and construction. (i)IS 456 : 2000 – Plain and reinforced concret e – code of practice (fourth revision) (ii) Loading Standards These loads to be considered for structural design are specified in the following loading standards: IS 875 (Part 1-5) : 1987 – Code of practice for design loads (other than earthquake) for buildings and structures (second revision) Part 1 : Dead loads Part 2 : Imposed (live) loads Part 3 : Wind loads Part 4 : Snow loads Part 5 : Special loads and load combinations IS 1893 : 2002 – Criteria for earthquake resistant design of structure (fourth revision). IS 13920 : 1993 – Ductile detailing of reinforced concrete structure subject to seismic forces. Design Handbooks The Bureau of Indian standards has also published the following handbooks, which serve as useful supplement to the 1978 version of the codes. Although the handbooks need to be updated to bring them in line with the recently revised (2000 version) of the Code, many of the provisions continue to be valid (especiall y with regard to structural design provisions). SP 16 : 1980 – Design Aids (for Reinforced Concrete) to IS 456 : 1978 SP 24 : 1983 – Explanatory handbook on IS 456 : 1978 SP 34 : 1987 – Handbooks on Concrete Reinforced and Detailing.
General Design Consideration of IS: 456-2000.
©BSNL India
For Internal Circulation Only
Page: 5
The general design and construction of reinforced concrete buildings shall be governed by the provisions of IS 456 –2000 AIM OF DESIGN The aim of design is achievement of an acceptable probability that structures being designed shall, with an appropriate degree of safety – Perform satisfactorily during their intended life. Sustain all loads and deformations of normal construction & use Have adequate durability Have adequate resistance to the effects of misuse and fire. METHOD OF DESIGN – Structure and structural elements shall normally be designed by Limit State Method. Where the Limit State Method cannot be conveniently adopted, Working Stress Method may be used MINIMUM GRADE OF CONCRETE The minimum grade of concrete for plain & reinforced concrete shall be as per table below –
26.4 ©BSNL India
Nominal Cover to Reinforcement For Internal Circulation Only
Page: 6
26.4.1 Nominal Cover Nominal cover is the design depth of concrete cover to all steel reinforcements, including links. It is the dimension used in design and indicated in the drawings. It shall be not less than the diameter of the bar. 26.4.2 Nominal Covers to Meet Durability Requirement Minimum values for the nominal cover of normal weight aggregate concrete which should be provided to all reinforcement, including links depending on the condition of exposure described in 8.2.3 shall be as given in Table 16. Table 16 Nominal Cover to Meet Durability Requirements (Clause 26.4.2) Exposure Nominal Concrete Cover in mm not Less Than Mild
20
Moderate
30
Severe
45
Very Severe
50
Extreme
75
NOTES 1. 2. 3.
For main reinforcement up to 12 mm diameter bar for mild exposure the nominal cover may be reduced by 5 mm. Unless specified otherwise, actual concrete cover should not deviate from the required nominal cover by + 10 mm For exposure condition ‘severe’ and ‘very severe’, reduction of 5 mm may be made, where concrete grade is M35 and above.
26.4.2.1 However for a longitudinal reinforcing bar in a column nominal cover shall in any case not be less than 40 mm, or less than the diameter of such bar. In the case of columns of minimum dimension of 200 mm or under, whose reinforcing bars do not exceed 12 mm, a nominal cover of 25 mm may be used.
26.4.2.2 For footing minimum cover shall be 50 mm.
26.4.3 Nominal Cover to Meet Specified Period of Fire Resistance
©BSNL India
For Internal Circulation Only
Page: 7
Minimum values of nominal cover of normal-weight aggregate concrete to be provided to all reinforcement including links to meet specified period of fire resistance shall be as given in Table 16A.
21.4 Minimum Dimensions of RC members for specified Period of Fire Resistance
DESIGN LOAD ©BSNL India
For Internal Circulation Only
Page: 8
Design load is the load to be taken for use in appropriate method of design. It is – Characteristic load in case of working stress method & Characteristic load with appropriate partial safety factors for limit state design.
LOAD COMBINATIONS As per IS 1893 (Part 1): 2002 Clause no. 6.3.1.2, the following load cases have to be considered for analysis: 1.5 (DL + IL) 1.2 (DL + IL ± EL) 1.5 (DL ± EL) 0.9 DL ± 1.5 EL Earthquake load must be considered for +X, -X, +Z and –Z directions. Moreover, accidental eccentricity during earthquake can be such that it causes clockwise or anticlockwise moments. So both clockwise & anticlockwise torsion is to be considered. Thus, ±EL above implies 8 cases, and in all, 25 cases must be considered. It is possible to reduce the load combinations to 13 instead of 25 by not using negative torsion considering the symmetry of the building.
STIFFNESS
©BSNL India
For Internal Circulation Only
Page: 9
22.3.1
Relative Stiffness: The relative stiffness of the members may be based on the moment of inertia of the section determined on the basis of any one of the following definitions: a) b)
c)
Gross Section Transformed Section Cracked Section
The cross-section of the member ignoring reinforcement The concrete cross-section plus the area of reinforcement transformed on the basis of modular ratio The area of concrete in compression plus the area of reinforcement transformed on the basis of modular ratio
The assumptions made shall be consistent for all the numbers of the structure throughout any analysis. 22.3.2
For deflection calculations, appropriate values of moment of inertia as specified in Annexure of IS 456-2000 should be used.
STRUCTURAL FRAMES 22.4
The simplifying assumptions as given in 22.4.1 to 22.4.3 may be used in the analysis of frames.
ARRANGEMENT OF LIVE LOAD 22.4.1 a) Consideration may be limited to combinations of: 1) Design dead load on all spans with full design live load on two adjacent spans; and 2) Design dead load on all spans with dull design live load on alternate spans. 22.4.1 b) When design live load does not exceed three-fourths of the design dead load, the load arrangement may be design dead load and design live load on all the spans. Note: For beams continuous over support 22.4.1 (a) may be assumed. 22.4.2
22.4.3
Substitute Frame: For determining the moments and shears at any floor or roof level due to gravity loads, the beams at that level together with columns above and below with their far ends fixed may be considered to constitute the frame. For lateral loads, simplified methods may be used to obtain the moments and shears for structures that are symmetrical. For unsymmetrical or very tall structures, more rigorous methods should be used.
MOMENT AND SHEAR COFFICIENTS FOR CONTINUOUS BEAMS
©BSNL India
For Internal Circulation Only
Page: 10
22.5.1
Unless more exact estimates are made, for beams of uniform cross-section which support substantially uniformly distributed load over three or more spans which do not differ by more than 15 percent of the longest, the bending moments and shear forces used in design may be obtained using the coefficients given in Tables below. For moments at supports where two unequal spans meet or in case where the spans are not equally loaded, the average of the two values for the negative moment at the support may be taken for design. Where coefficients given in Table below are used for calculation of bending moments, redistribution referred to in 22.7 shall not be permitted.
22.5.2
Beams Over Free End Supports Where a member is built into a masonry wall which develops only partial restraint, the member shall be designed to resist a negative moment at the face of the support of W1/24 where W is the total design load and 1 is the effective span, or such other restraining moment as may be shown to be applicable. For such a condition shear coefficient given in Table below at the end support may be increased by 0.05.
------------------------------------------------------------------------------------------------------BENDING MOMENT COFFICIENTS ------------------------------------------------------------------------------------------------------Span Moments Support Moments ------------------------------------------------------------------------------------Types of Load Near Middle At Middle At Support At Other of End Span of interior next to the Interior span end support Supports ------------------------------------------------------------------------------------------------------Dead load and 1 1 1 1 imposed load +-+-(- )-(- )-(fixed) 12 16 10 12 Imposed load (not fixed)
1 +-10
1 +-12
1 (- )-9
1 (- )-9
Note:
For obtaining the bending moment, the coefficient shall be multiplied by the total design load and effective span. -------------------------------------------------------------------------------------------------------
------------------------------------------------------------------------------------------------------SHEAR FORCE COFFICIENTS -------------------------------------------------------------------------------------------------------
©BSNL India
For Internal Circulation Only
Page: 11
Type of Load
At End Support
At Support Next At All Other to the end Support Interior Support Outer side Inner Side ------------------------------------------------------------------------------------------------------Dead load and imposed load 0.40 0.60 0.55 0.50 (fixed) Imposed load (not fixed)
0.45
0.60
0.60
0.60
Note:
For obtaining the shear force, the coefficient shall be multiplied by the total design load. ------------------------------------------------------------------------------------------------------CRITICAL SECTIONS FOR MOMENT AND SHEAR 22.6.1
For monolithic construction, the moments computed at the face of the supports shall be used in the design of the members at those sections. For non-monolithic construction the design of the member shall be done keeping in view 22.2.
22.6.2
Critical Section for Shear
22.6.2.1
The shears computed at the face of the Support shall be used in the design of the member at that section except as in 22.6.2.1 When the reaction in the direction of the applied shear introduces compression into the end region of the member, sections located at a distance less than d from the face of the support may be designed for the same shear as that computed at distance d.
REDISTRIBUTION OF MOMENTS 22.7
Redistribution of moments may be done in accordance with 37.1.1 for limit state method and in accordance with B-1.2 for working stress method. However, where simplified analysis using coefficients is adopted, redistribution of moments shall not be done.
EFFECTIVE DEPTH 23.0
Effective depth of a beam is the distance between the centroid of the area of tension reinforcement and the maximum compression fibre, excluding the thickness of finishing material not placed monolithically with the member and the thickness of any concrete provided to allow for wear. This will not apply to deep beams.
CONTROL OF DEFLECTION
©BSNL India
For Internal Circulation Only
Page: 12
23.2
The deflection of a structure or part thereof shall not adversely affect the appearance or efficiency of the structure or finishes or partitions. The deflection shall generally be limited to the following: a) The final deflection due to all loads including the effects of temperature, creep and shrinkage and measured from the as-cast level of the supports of floors, roofs and all other horizontal members, should not normally exceed span/250. b) The deflection including the effects of temperature, creep and shrinkage occurring after erection of partitions and the application of finishes should not normally exceed span/350 or 20mm whichever is less.
23.2.1 For beams, the vertical deflection limits may generally be assumed to be satisfied provided that the span to depth ratio are not greater than the value obtained as below: a) Basic values of span to effective depth ratios for spans up to 10m: Cantilever Simply supported Continuous
7 20 26
b) For spans above 10m, the values in (a) may be multiplied by 10/span in metres, except for cantilever in which case deflection calculations should be made. c) Depending on the area and the type of steel for tension reinforcement, the value in (a) or (b) shall be modified as per Fig. 4 d) Depending on the area of compression reinforcement, the value of span to depth ratio be further modified as per Fig. 5 e) For flanged beams, the value of (a) or (b) be modified as per Fig. 6 and the reinforcement percentage for use in fig. 4 and 5 should be based on area of section equal to bf d.
Note: When deflections are required to be calculated, the method given Annexure ‘C’ of IS 456-2000 may be used.
©BSNL India
For Internal Circulation Only
Page: 13
CONTROL OF DEFLECTION – SOLID SLABS 24.1 General The provisions of 32.2 for beams apply to slabs also. NOTES
©BSNL India
For Internal Circulation Only
Page: 14
1. For slabs spanning in two directions, the shorter of the two spans should be used for calculating the span to effective depth rations. 2. For two-way slabs of shorter spans (up to 3.5 m) with mild steel reinforcement, the span to overall depth rations given below may generally be assumed to satisfy vertical deflection limits for loading class up to 3 kN/m2. Simply supported slab 35 Continuous slabs 40 For high strength deformed bars of grade Fe 415,the values given above should be multiplied by 0.8. Simply supported slab 28 Continuous slabs 32 23.3
Slabs Continuous Over Supports Slabs spanning in one direction and continuous over supports shall be designed according to the provisions applicable to continuous beams.
23.4 Slabs Monolithic with Supports Bending moments in slabs (except flat slabs) constructed monolithically with the supports shall be calculated by taking such slabs either as continuous over supports and capable of free, or as members of a continuous frame work with the supports, taking into account the stiffness of such support. If such supports are formed due to beams which justify fixity at the support of slabs, then the effects on the supporting beam, such as, the bending of the web in the transverse direction of the beam, wherever applicable, shall also be considered in the design of the beams. 23.4.1 For the purpose of calculation of moment in slabs in a monolithic structure, it will generally be sufficiently accurate to assumed direct members connected to the ends of such slab are fixed in position and direction at the end remote from their connection with the slab. 26.5 REQUIREMENT OF REINFORCEMENT FOR STRUCTURAL MEMBER 26.5.1 Beams 26.5.1.1 Tension reinforcement (a) Minimum reinforcement:- The minimum area of tension reinforcement shall not be less than that given by the following:As = 0.85 bd fy where As = minimum area of tension reinforcement. b = breadth of beam or the breadth of the web of T-beam. d = effective depth, and
©BSNL India
For Internal Circulation Only
Page: 15
fy = characteristic strength of reinforcement in M/mm2 (b) Maximum reinforcement:- the maximum area of tension reinforcement shall not exceed 0.04bD. 26.5.1.2 Compression reinforcement The maximum area of comparison reinforcement shall not exceed 0.04 bd. Comparison reinforcement in beams shall be enclosed by stirrups for effective lateral restraint. 26.5.1.3 Side face reinforcement Where the depth of the web in the beam exceeds 750mm, side face reinforcement shall be provided along the two faces. The total area of such reinforcement shall be not less than 0.1 % of the web area and shall be distributed on the equally on the two face at spacing not exceeding 300mm or web thickness whichever is less. 26.5.1.4 Transverse reinforcement in beam for shear torsion The transverse reinforcement in beam shall be taken around the outer most tension & compression bars. In T-beams and I-beams, such reinforcement shall pass around longitudinal bars located close to the outer face of the flange. 26.5.1.5 Maximum spacing of shear reinforcement Maximum spacing of shear reinforcement means long by axis of the member shall not exceed 0.75 d for vertical stirrups and d for inclined stirrups at 45” where d is the effective depth on the section under consideration. In no case shall be spacing exceed 300mm. 26.5.1.6 Minimum shear reinforcement Minimum shear reinforcement in the form of stirrups shall be provided such that: Asv bsv
0.4 0.87 fy
Where Asv = total cross-sectional area of stirrups legs effective in shear. Sv = stirrups spacing along the length of the member B = breadth of the beam or breadth of the web of flange beam, and fy = characteristic strength of the stirrups reinforcement in N/mm2 which shall not taken greater than 415 N/mm2 Where the maximum shear stress calculated is less than half the permissible value in member of minor structure importance such as lintels, this provision need not to be complied with. 26.5.1.7 Distribution of torsion reinforcement When a member is designed for torsion torsion reinforcement shall be provided as below: ©BSNL India
For Internal Circulation Only
Page: 16
a)
the transverse reinforcement for torsion shall be rectangular closed stirrups placed perpendicular to the axis of the member. The spacing of the stirrups shall not exceed the list of x1, x1+y1/4 and 300 mm, where x1, y1 are respectively the short & long dimensions of the stirrup.
b)
Longitudinal reinforcement shall be place as closed as is practicable to the corner of the cross section & in all cases, there shall be atleast one longitudinal bar in each corner of the ties. When the cross sectional dimension of the member exceed 450 mm additional longitudinal bar shall be provided to satisfied the requirement of minimum reinforcement & spacing given in 26.5.1.3.
26.3.2 Minimum Distance between Individual Bars (a) The horizontal distance between two parallel main reinforcing bars shall usually be not-less than the greatest of the following: (i) Dia of larger bar and (ii) 5 mm more than nominal maximum size of coarse aggregate. (b) When needle vibrators are used it may be reduced to 2/3rd of nominal maximum size of coarse aggregate, Sufficient space must be left between bars to enable vibrator to be immersed. (c) Where there are two or more rows of bars, bars shall be vertically in line and the minimum vertical distance between bars shall be 15 mm, 2/3rd of nominal maximum size of aggregate or the maximum size of bars, whichever is greater. 26.5.2 Slabs The rule given in 26.5.2.1 and 26.5.2.2 shall apply to slabs in addition to those given in the appropriate clause. 26.5.2.1 Minimum reinforcement
©BSNL India
For Internal Circulation Only
Page: 17
The mild steel reinforcement in either direction in slabs shall not be less than 0.15 percent of the total cross-sectional area. However, this value can be reduced to 0.12 percent when high strength deformed bars or welded wire fabric are used. 26.5.2.2 Maximum diameter The diameter of reinforcing bars shall not exceed one eight of the total thickness of slab. 26.3.3 Maximum distance between bars - Slabs 1) The horizontal distance between parallel main reinforcement bars shall not be more than three times the effective depth of solid slab or 300 mm whichever is smaller. 2) The horizontal distance between parallel reinforcement bars provided against shrinkage and temperature shall not be more than five times the effective depth of a solid slab or 300 mm whichever is smaller. Torsion reinforcement - Slab Torsion reinforcement is to be provided at any corner where the slab is simply supported on both edges meeting at that corner. It shall consist of top and bottom reinforcement, each with layers of bars placed parallel to the sides of the slab and extending from the edges a minimum distance of one-fifth of the shorter span. The area of reinforcement in each of these four layers shall be three-quarters of the area required for the maximum mid-span moment in the slab. D-l.9 Torsion reinforcement equal to half that described in D-l.8 shall be provided at a corner contained by edges over only one of which the slab is continuous. D-1.10 Torsion reinforcements need not be provided at any comer contained by edges over both of which the slab is continuous.
26.5.3 Columns A. Longitudinal Reinforcement a. The cross sectioned area of longitudinal reinforcement shall be not less than 0.8% nor more than 6% of the gross sectional area of the column. Although it is recommended that the maximum area of steel should not exceed 4% to avoid practical difficulties in placing & compacting concrete. b. In any column that has a larger cross sectional area than that required to support the load, the minimum percentage steel must be based on the area of concrete resist the direct stress & not on the actual area.
©BSNL India
For Internal Circulation Only
Page: 18
c. The bar should not be less than 12 mm in diameter so that it is sufficiently rigid to stand up straight in the column forms during fixing and concerting. d. The minimum member of longitudinal bars provided in a column shall be four in rectangular columns & six in circular columns. e. A reinforced concrete column having helical reinforcement must have at least six bars of longitudinal reinforcement with the helical reinforcement. These bars must be in contact with the helical reinforcement & equidistance around its inner circumference. f. Spacing of longitudinal should not exceed 300 mm along periphery of a column. g. In case of pedestals, in which the longitudinal reinforcement is not taken into account in strength calculations, nominal reinforcement should be not be less than 0.15% of cross sectional area. B.
Transverse Reinforcement a. The diameter of lateral ties should not be less than ¼ of the diameter of the largest longitudinal bar in no case should not be less than 6 mm. b. Spacing of lateral ties should not exceed least of the following:Least lateral dimension of the column. 16 times the smallest diameter of longitudinal bars to be tied. 300mm.
SHEAR 40.1 Nominal Shear Stress The nominal shear stress in beams of uniform depth shall be obtained by the following equation: τv = Vu/ b.d where Vu = shear force due to design loads; b = breadth of the member, which for flanged section shall be taken as the breadth of the web, bw; and d = effective depth. 40.2.3 With Shear Reinforcement Under no circumstances, even with shear reinforcement, shall the nominal shear stress in beams should not exceed given in Table 20. 40.2.3.1 For solid slabs, the nominal shear stress shall not exceed half the appropriate values given in Table 20.
©BSNL India
For Internal Circulation Only
Page: 19
40.3 Minimum Shear Reinforcement When τv, is less than τc given in Table 19, minimum shear reinforcement shall be provided in accordance with 26.5.1.6.
40.4 Design of Shear Reinforcement When τv, is exceeds τc , given in Table 19, shear reinforcement shall be provided in any of the following forms: a) Vertical stirrups, b) Bent-up bars along with stirrups, and Where bent-up bars are provided, their contribution towards shear resistance shall not be more than half that of the total shear reinforcement. Shear reinforcement shall be provided to carry a shear equal to Vu – τ strength of shear reinforcement Vus shall be calculated as below:
c
b d. the
a) For Vertical Stirrups:
Vus ©BSNL India
=
0.87 fy Asv d ___________
For Internal Circulation Only
Page: 20
Sv b) For inclined stirrups or a series of bars bent up at different cross – section: 0.87 fy Asv d ___________ (Sin ά + Cos ά) Sv c) For single bar or single group of parallel bars, all bent up at the same cross sections: Vus
=
Vus
=
0.87 fy Asv Sin ά
Where Asv =
total cross –sectional area of stirrups legs or bent-up bar within a distance Sv,
Sv
=
spacing of the stirrups or bent-up bars along the length of the member.
τv
=
nominal shear stress,
τc
=
design shear strength of the concrete,
b
= breadth of the member which for flanged beams, shall be taken as the breadth of the web bw.
fy
=
characteristic strength of the stirrup or bent-up reinforcement which shall not be taken greater than 415 N/mm2,
ά
=
angle between the inclined stirrup or bent up bar and the axis of the member not less than 45o,
and d
=
effective depth
DEVELOPMENT LENGTH OF BARS 26.2 Development of Stress in Reinforcement The calculated tension or compression in any bar at any section shall be developed on each side of the section by an appropriate development length or end anchorage or by a combination thereof. Development length Ld is given by
©BSNL India
For Internal Circulation Only
Page: 21
Ld = υσst /4τbd υ = nominal diameter of bar, τbd = design bond stress σst = stress in bar at the section considered at design load Design bond stress in limit state method for plain bars in tension is given in clause 26.2.1.1 For deformed bars conforming to IS 1786 these values are to be increased by 60 %. For bars in compression, the values of bond stress for bars in tension is to be increased by 25 percent
B. Shear reinforcement (STIRRUPS) Development length and anchorage requirement is satisfied, in case of stirrups and transverse ties, when Bar is bent – • Through an angle of at least 90 degrees (round a bar of at least its own dia) & is continued beyond for a length of at least 8 φ, or • Through an angle of 135 degrees & is continued beyond for a length of at least 6 φ or • Through an angle of 180 degrees and is continued beyond for a length of at least 4 φ DUCTILE DETAILING AS PER IS: 13920 •
Provisions of IS 13920-1993 shall be adopted in all reinforced concrete structures which are located in seismic zone III, IV or V
The provisions for reinforced concrete construction given in IS 13920-1993 shall apply specifically to monolithic reinforced concrete construction. Precast and/or
©BSNL India
For Internal Circulation Only
Page: 22
prestressed concrete members may be used only if they can provide the same level of ductility as that of a monolithic reinforced concrete construction during or after an earthquake. The definition of seismic zone and importance factor are given in IS 1893-2002. CODAL PROVISIONS OF IS 13920 5.2 For all buildings which are more than 3 storeys in height, the minimum grade of concrete shall be M20 (fck = 20 MPa ). 5.3 Steel reinforcements of grade Fe 415 (see IS 1786 : 1985 ) or less only shall be used. However, high strength deformed steel bars, produced by the thermomechanical treatment process, of grades Fe 500 and Fe 550, having elongation more than 14.5 percent and conforming to other requirements of IS 1786 : 1985 may also be used for the reinforcement. Flexure Members 6.1.2 The member shall preferably have a width-to-depth ratio of more than 0.3. 6.1.3 The width of the member shall not be less than 200 mm. 6.1.4 The depth D of the member shall preferably be not more than 1/4 of the clear span. 6.2 Longitudinal Reinforcement 6.2.1 a) The top as well as bottom reinforcement shall consist of at least two bars throughout the member length. b) The tension steel ratio on any face, at any section, shall not be less than ρmin = 0.24(fck)1/2 /fy ; where fck and fy are in MPa. 6.2.2 The maximum steel ratio on any face at any section, shall not exceed ρmax = 0.025. 6.2.3 The positive steel at a joint face must be at least equal to half the negative steel at that face. 6.2.4 The steel provided at each of the top and bottom face of the member at any section along its length shall be at least equal to one-fourth of the maximum negative moment steel provided at the face of either joint 6.2.6 The longitudinal bars shall be spliced, only if hoops are provided over the entire splice length, at a spacing not exceeding 150 mm 6.3 Web Reinforcement 6.3.1 Web reinforcement shall consist of vertical hoops. A vertical hoop is a closed stirrup having a 135° hook with a 10 diameter extension (but not < 75 mm) at each end that is embedded in the confined core 6.3.2 The minimum diameter of the bar forming a hoop shall be 6 mm. However, in beams with clear span exceeding 5 m, the minimum bar diameter shall be 8 mm. 6.3.4 The contribution of bent up bars and inclined hoops to shear resistance of the section shall not be considered. 6.3.5 The spacing of hoops over a length of 2d at either end of a beam shall not exceed (a) d/4, and (b) 8 times the diameter of the smallest longitudinal bar; however,
©BSNL India
For Internal Circulation Only
Page: 23
it need not be less than 100 mm. Elsewhere, the beam shall have vertical hoops at a spacing not exceeding d/2. Columns 7.1.2 The minimum dimension of the member shall not be less than 200 mm. However, in frames which have beams with centre to centre span exceeding 5 m or columns of unsupported length exceeding 4 m, the shortest dimension of the column shall not be less than 300 mm. 7.1.3 The ratio of the shortest cross sectional dimension to the perpendicular dimension shall preferably not be less than 0.4. 7.2 Longitudinal Reinforcement 7.2.1 Lap splices shall be provided only in the central half of the member length. It should be proportioned as a tension splice. Hoops shall be provided over the entire splice length at spacing not exceeding 150 mm centre to centre. Not more than 50 percent of the bars shall be spliced at one section. 7.3 Transverse Reinforcement 7.3.1 Transverse reinforcement for circular columns shall consist of spiral or circular hoops. In rectangular columns, rectangular hoops may be used. A rectangular hoop is a closed stirrup, having a 135° hook with a 10 diameter extension (but not < 75 mm) at each end, that is embedded in the confined core. 7.3.3 The spacing of hoops shall not exceed half the least lateral dimension of the column, except where special confining reinforcement is provided, as per 7.4. 7.4 Special Confining Reinforcement This requirement shall be met with, unless a larger amount of transverse reinforcement is required from shear strength considerations. 7.4.1 Special confining reinforcement shall be provided over a length lo from each joint face, towards midspan, and on either side of any section, where flexural yielding may occur under the effect of earthquake forces. The length ‘lo’ shall not be less than (a) larger lateral dimension of the member at the section where yielding occurs, (b) 1/6 of clear span of the member, and (c) 450 mm. 7.4.2 When a column terminates into a footing or mat, special confining reinforcement shall extend at least 300 mm into the footing or mat. 7.4.6 The spacing of hoops used as special confining reinforcement shall not exceed 1/4 of minimum member dimension but need not be less than 75 mm nor more than 100 mm. 8 JOINTS OF FRAMES 8.1 The special confining reinforcement as required at the end of column shall be provided through the joint as well, unless the joint is confined as specified by 8.2. 8.2 A joint which has beams framing into all vertical faces of it and where each beam width is at least 3/4 of the column width, may be provided with half the special confining reinforcement required at the end of the column. The spacing of hoops shall not exceed 150 mm.
©BSNL India
For Internal Circulation Only
Page: 24
DEAD LOADS – UNIT WEIGHTS OF SOME MATERIALS/BUILDING COMPONENTS As per IS-875(Part-1)-1987 UNIT WEIGHT MATERIAL
kN/m3
PLAIN CONCRETE
24
REINFORCED CONCRETE
25
BRICK MASONRY
19-20
STONE MASONRY
21-27
TIMBER
6-10
CEMENT-PLASTER
21
LIME -PLASTER
18
STEEL
78.5
AC SHEET -ROOFING
0.16
GI SHEET -ROOFING
0.15
MANGLORE TILES
0.65
STEEL WORK -ROOFING
©BSNL India
kN/m2
For Internal Circulation Only
0.16-0.23
Page: 25
LIVE LOADS ON FLOORS AS PER IS-875(Part-2)-1987
TYPE OF FLOOR USAGE
LIVE LOAD (kN/m2)
RESIDENTIAL
2.0
OFFICIAL – WITH SEPARATE STORAGE
2.5
– WITHOUT SEPARATE STORAGE
4.0
SHOPS,CLASS ROOMS,WAITINGS ROOMS, RESTAURANTS,WORK ROOMS,THEATRES ETC - WITH FIXED SEATING - WITHOUT FIXED SEATING FACTORIES & WAREHOUSES
4.0 5.0 5.0-10
STACK ROOM IN LIBRARIES ,BOOK STORES
10.0
GARRAGES –LIGHT VEHICLES
4.0
–HEAVY VEHICLES
7.5
STAIRS-NOT LIABLE TO OVER CROWDING
4.0
- LIABLE TO OVER CROWDING
5.0
LIVE LOADS ON FLOORS OF T.E.BLDGS
TYPE OF FLOOR USAGE
LIVE LOAD (kN/m2)
SWITCH ROOM(NEW TECHNOLOGY)
6.0
OMC ROOM,DDF ROOM,POWER PLANT, BATTERY ROOM
6.0
MDF ROOM
10.0
WEATHER MAKER
12.0
LIVE LOADS ON ROOFS
©BSNL India
ROOF WITH ACCESS
1.5
ROOF WITHOUT ACCESS
0.75
For Internal Circulation Only
Page: 26
©BSNL India
For Internal Circulation Only
Page: 27
3.0 Steps for Design of a Multi-Storeyed Building:Manual Method of Analysis & Design:Step1: Study of architectural Drawings:- Before proceeding for structural design of any building it is ensure that approved working drawings are available in the office. All working drawings i.e. each floor plan, elevations, sections, are studied thoroughly & discrepancy if any brought to the notice of concern Architect for rectification/correction. The problems coming in finalization of structural configuration may also be intimated to concern Architect for rectification/correction if any. Step2: Finalization of structural Configuration. After receiving corrected working drawing from the architectural wing, the structural system is finalized. The structural arrangements of a building is so chosen as to make it efficient in resisting vertical as well as horizontal loads due to earthquake. The span of slabs co chosen that thickness of slab 100-150mm and slab panels, floor beams, and columns, are all marked and numbered on the architectural plans. Now the building is ready for structural design to start.
ISOMETRIC VIEW OF FRAMED STRUCTURE Step3: Load Calculation and analysis. For each floor or roof, the loading intensity of slab is calculated taking into account the dead load of the slab, finish plaster, etc. including partitions and the live load expected on the floor, depending on the usage of the floor or roof. The linear loading of beams, columns, walls, parapets, etc. also calculated. Step3 (a): Preliminary Sizes of structural members. Before proceeding for load calculation preliminary sizes of slabs, beams,& columns decided. In manual load ©BSNL India
For Internal Circulation Only
Page: 28
calculation preliminary sizes of structural members should be judicially fixed as once load calculation & analysis is done it is not easy to revise the same. But in computer aided analysis & design it can be revised easily. Slab:- The thickness of the slab decided on the basis of span/d ratio assuming appropriate modification factor. Beam : The width the beam generally taken as the width of wall i.e 230 or 300 mm. The width of beam is help full in placement of reinforcement in one layer & more width is help full in resisting shear due to torsion. The depth of beam is generally taken as 1/12 th (for Heavy Loads) to 1/15 th (for Lighter Loads) of span. Column:- Size of column depends upon the moments from the both the direction and the axial load. Preliminary Column size may be finalized by approximately calculation of axial load & moments. Procedure for vertical load calculation on Columns: Step(i): First, the load from slab (including Live load & Dead Load) is transferred on to the adjoining beams using formulas given below|:For computation of shear force on beams & reactions on columns, an equivalent uniformly distributed load per linear meter of beam may be taken as : Equivalent u.d.l. on short beam of slab panel = w B/4.0 Equivalent u.d.l. on long beam of slab panel = w B/4 x [2-(B/L)] Where w is the total load on the slab panel in Kn/Sqm & L & B are long span & short spans of slab panel respectively. Step(ii): Over this load, the weight of wall (if any), self weight of beam etc. are added to get the load on beam (in running metre). Step(iii):The load (in running metre) on each beam is calculated as in Step 1 & Step 2. Step(iv):Then the loads from the beams are transferred to the columns. Step(v):Step (i) to Step (v) is repeated for each floor. Step(vi):These loads at various floors on each column are then added to get the total loads on each column, footing and the whole building. Step4: HORIZONTAL (SEISMIC) LOAD CALCULTAION: The Horizontal Load Calculation or the Load Calculations for Seismic case is carried out as per the Indian Standard Code IS:1893-2002. The loads calculated in Para-II above at various floor levels are modified as per the requirement of Para 7.3.1 of IS:1893-2002.
©BSNL India
For Internal Circulation Only
Page: 29
The Seismic Shear at various floor levels is calculated for the whole Building using the values from IS 1893-2002. Calculation of horizontal loads on buildings (As per is-1893-2002) Sample example for horizontal loa d calculation (I) (II)
BUILDING IS ON SEISMIC ZONE -IV FOUNDATION TYPE ISOLATED FOOTINGS
As per clause 7.5.3 of IS-1893-2002 Design base shear v b V
b
= Ah W
(F)
Where A h = Design Horizontal acceleration spectrum value as per 6.4.2 of the code = (Z/2) (I/R) (Sa/g) Where
I R (S a /g)
Z
= Zone factor as per table 2 of IS Code (1893 -2002) = 0.24 (in this case) = Importance factor as per table 6 of IS -1893-2002) = 1.5 (Assuming that the bldg. is T.E. Bldg.) = Response reduction factor as per table 7 of IS code = 3.0 (for ordinary R.C. Moment resisting frame (OMRF) = Average response acceleration coefficie nt for soil t ype & appropriate natural periods and lamping of the structure.
For calculating of (Sa/g) value as above we have to calculate value of T i.e. Fundamental National Period (Seconds) ( Clause 7.6 of IS Code) T h
= 0.075 h 0 . 7 5 (For RC Frame building) = 0.0 85 h 0 . 7 5 (For Steel frame building) = Height of building in Meter
In case of building with brick in fills walls. T = 0.09 h /d 1 / 2 Where h and d
©BSNL India
= height of building in Meter = Base dimension of the building at the plinth level in Meter along the considered direction of the lateral force.
For Internal Circulation Only
Page: 30
Value of (Sa/g) is to be read from fig 2 on page 16 of IS Code depending upon Soil condition & Fundamental Natural period T. Or the value of (Sa/g) may be calculated on the basis of Following. Formulas:(i) For rocky, or hard soil sites (Sa/g) = 1+15 T if 0.00≤T≤ 0.10 = 2.50 if 0.10≤T≤ 0.40 =1.00/T if 0.40≤T≤ 4.00 (ii) For medium soil sites (Sa/g)
= 1+15 T if = 2.5 0 if = 1.36/T if
0.00≤T≤ 0.10 0.10≤T≤0.55 0.55≤T≤ 4.00
(iii) For soft soil sites (Sa/g)
= 1+15 T if 0.00≤T≤