Distributed I/O-I/O Module/Digital I/O Module/Remote I/O-Industrial I/O

3 downloads 38921 Views 60MB Size Report
DeviceNetTM, Modbus and Koyo remote I/O; some adapters include an ... Use Terminator I/O as robust PLC remote ..... For example, a PC running KEPDirect.
For the latest prices, please check AutomationDirect.com.

Universal Field I/O

Up-to-date price list:

www.automationdirect.com/pricelist

FREE Technical Support: In this interactive PDF you can: • Use bookmarks to navigate by product category

www.automationdirect.com/support

• Use bookmarks to save, search, print or e-mail the catalog section

FREE Documentation:

• Click on part #s to link directly to our online store for current pricing, specs, stocking information and more

FREE CAD drawings:

FREE Videos:

www.automationdirect.com/videos

www.automationdirect.com/documentation

www.automationdirect.com/cad

TM

www.automationdirect.com/fieldIO

Universal Field I/O

mFED-1

For the latest prices, please check AutomationDirect.com.

TM

Xpansion I/O for your application and every application

The Perfect Fit

Simple Wiring

Protos X I/O is a perfect fit for most applications, particularly where you need distributed or compact I/O. Regardless of the size, budget or demand, this product can accommodate your needs and deliver every time.

With the push-in, spring clamp wiring system on the Protos X I/O terminals, installation has never been easier. There is never a concern for over tightening or under tightening. No screw heads to fiddle with or making sure you have a screwdriver that fits. Simply strip your wire and push it in to the terminal point.

At just 12mm thick, the super thin and attractive form factor allows you to manage the overall size and cost of your mechanical design. Now you can fit more I/O into a smaller footprint (linear DIN rail space), saving you money when sourcing enclosures for new applications or making it a more attractive fit for existing ones. When compared to more traditional Field I/O, Protos X I/O saves you roughly 70% more linear DINRail space! This practical product makes your everyday applications easier to accomplish and saves you time. The footprint allows you to install Protos X I/O on or near the equipment it is monitoring. This reduces field wiring and provides fast and reliable updates to your control system.

Power and Expansion

• 24VDC or 120-230 VAC power feed terminals let you switch voltage on the power bus • Bus Expansion End Terminals and Couplers let you expand the system easily

Note: Either the PX-901 End terminal or PX-902 Expansion End terminal are required on every system.

Monitor just a couple points or a couple hundred points The Protos X I/O offers a wide selection of I/O modules, also called terminals. With densities ranging from 2 points per I/O terminal up to 16 points per terminal, you have the ability to precisely configure your control system to the exact number of points you need, eliminating overpaying for unused I/O points. You designed your system for the number of points that you need, why pay for more?

Communicate with Modbus With both Serial Modbus RTU and Ethernet Modbus TCP bus couplers available, you have the freedom to connect to hundreds of control devices in our industry, including the most popular PLCs and SCADA/HMI packages. This flexibility allow each user to select the control platform that best fits the project and still save money by selecting a universal I/O product to complete the job.

The Signals you Need

• 2, 4, 8 and 16-point discrete I/O terminals available in a variety of signals including 24VDC, 120VAC & 240VAC • 2, 4 and 8-point analog terminals with signal ranges of 4-20mA, +/-10VDC, 0-5/0-10VDC • 2 and 4-channel temperature modules in both thermocouple (J and K types) and RTD (Pt100).

Bus Couplers

• PX-MOD with Serial Modbus RTU protocol • PX-TCP1 with Ethernet Modbus TCP (single port) • PX-TCP2 with Ethernet Modbus TCP (dual port)

mFED-2

Universal Field I/O

I/O Terminal Selection Offering a wide variety of signals, voltage ranges and number of points, the Protos X I/O terminals make it simple to configure your system. Whether you need a couple of points or a couple hundred points, you can easily build a comprehensive I/O platform with these terminals.

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

PLC or PLC-based PAC

SCADA/HMI

Unique Design Because of the interlocking design of the terminals, the data and power buses are carried from module to module and picked up only when needed! This unique design allows the system to easily switch the module’s required field power while continuing to keep the data bus intact. This design also makes it simple to provide a specific voltage to a series of modules, like an internal jumper, supplying power from module to module.

I/O Bus contacts

Note: PX-TCP2 (shown) is expanded via the second Ethernet port included on the bus coupler. The expansion terminals are not supported. The PX-TCP1 only has one Ethernet port and requires the PX-902/903 expansion terminals if you need to add more than a single group or for remote terminals.

www.automationdirect.com/fieldIO

Terminal power bus contact

Terminal power bus pass through

Terminal power bus contact

Terminal power bus pass through

Terminal PE bus contact

Terminal PE bus pass through

Universal Field I/O

mFED-3

For the latest prices, please check AutomationDirect.com.

The Xact I/O you need, where you need it Why Remote I/O?

I/O Where you Need it

With the infusion of lower-cost PC technology working its way into industrial controllers, PLCs and PLC-based PACs are becoming more and more powerful. Greater processing power and larger memory capacity in these controllers means that you can accomplish more with a single control system. However, the field wiring in these systems becomes increasingly expensive and difficult to manage. It’s not practical to think you can control an entire logistical distribution system out of a single control cabinet … You must network.

The unique slim design and low cost of the Protos X I/O makes it the most practical distributed I/O available today. The ultra slender form factor makes it easy to install on or near your machine or application components. This saves you time and money by eliminating excess field wiring and speeds up troubleshooting.

With distributed or remote I/O, you can localize a low-cost I/O solution on or near the equipment you’re controlling and monitoring, drastically reducing your field wiring. You can keep the hundreds of control signal wires on the machine and transfer all data back to the main control panel with an off-the-shelf Ethernet or serial cable.

This ultra-compact design makes it perfect for those applications where a typical PLC or I/O solution simply would not fit.

mFED-4

Universal Field I/O

The slim design also allows you to more precisely select the I/O count you need for your system. By building a system that contains the exact I/O count required and not a lot of extra, unused points, you’re only paying for what you need.

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

With Xcellent options and easy configuration, the choice is clear Serial Modbus RTU

Bus Couplers

PX-MOD

Protos X gets you connected with the most common protocol interfaces. Choose from the Serial Modbus RTU module, Ethernet Modbus TCP (single port with support for expansion), or our dual-port Modbus TCP interface with a built-in Ethernet switch to easily daisy-chain multiple couplers. These common bus couplers make it easy for you to expand any system. Select the one that best connects to your control system and use our free configuration utility to configure your system. Within minutes you’re ready to control this low-cost I/O.

PX-TCP1 PX-TCP2 Ethernet Modbus TCP

Easy Configuration

Software Requirements

The PX-CFGSW software is designed to do exactly what you need and nothing more. This quick and easy-to-use configuration utility helps you set up the bus coupler to match the configuration of your network so you’re talking in no time. The software also provides a very simple-to-read layout that identifies each terminal with:

Purchase on CD - $19.00

A B C D E

Slot: the physical location of the terminal Terminal Name: the part number of the terminal Short Description: description of the terminal Long Description: more details Modbus Range: the Modbus Address for the terminal

You can also use this tool to disable or set the Watchdog timer for applications where you encounter delays in the communications, to set the Modbus address offset based on the requirements of your controller, and restart the bus coupler as needed.

A

B

C

www.automationdirect.com/fieldIO

Also available for free download: http://support.automationdirect.com/products/pxcfgsw.html Operating System Compatibility · Windows 8.1 - (32 & 64 bit) · Windows 8 - (32 & 64 bit) · Windows 7 - (32 & 64 bit) · Windows Vista - (32 & 64 bit) · Windows XP Hardware Requirements · Processor: 333 Mhz (XP) 1 Ghz (Win 7 & Win 8) · Memory: 512 Mb (XP) 1 GB RAM (32-bit) or 2 GB RAM (64-bit)(Win 7 & Win 8) · HD Space: 300 Mb free space · Video: None specified

D

E

Universal Field I/O

mFED-5

The Terminator Field I/O System: Great Features at an AutomationDirect Price PC-based Controls Terminator I/O What is it? Terminator I/O is one of the most practical distributed Field I/O systems you can buy. It combines the I/O points with their field terminations into a modular package to save panel space and money. With Terminator I/O, you can distribute I/O nodes close to field devices for faster and more efficient wiring and troubleshooting. Terminator I/O was custom-designed for us by Koyo (the same people who designed the original GE Series One PLC), a trusted name in control technology since 1983.

What’s it got? • Network interface modules supporting Ethernet, PROFIBUSTM, DeviceNetTM, and Modbus; some adapters include an on-board RS-232 serial port. • Discrete and analog I/O modules with modular terminal bases. • Configuration flexibility by plugging together a network interface module with up to 16 I/O modules. Use local expansion for large I/O drops. No more confining I/O bases. • AC or DC power supplies. For high power systems, combine multiple supplies on a single I/O set. • Horizontal or vertical DIN-rail mounting

Ethernet DeviceNet TM Modbus® PROFIBUS TM Starting at $184.00

What can I do with it? • Use Terminator I/O as robust PLC remote I/O with triple stack terminal bases and hot-swap I/O modules. • Add Terminator I/O to Allen-Bradley, Siemens, Modicon or GE systems for 1/2 to 1/3 the price of their comparable field I/O products. • Use Terminator I/O as low-cost field I/O for your SCADA, PC-based control system or WinPLC™ system.

Modular I/O

Terminator I/O allows you to connect serial devices, like an operator interface panel, along with your I/O, so there’s no need to purchase adapters or run additional wiring*. * Serial communication options available on T1H-EBC and T1K-DEVNETS only

16-module system with multiple power supplies

Terminator I/O

PLC Control

Distributed Control

Terminator I/O

Terminal connectors

Terminator I/O includes specialty modules like our 16-channel RTD temperature module (T1F-16RTD) and the counter module (T1H-CTRIO)

RTD

ature tempedrules mo

ter Couondule m

Add additional power module where needed

Output modules have replaceable fuses

L

a l o c

Exp

ans

ion

Modules slide into the modular terminal bases. Plug together any combination of modules and power sources for your application.

For the latest prices, please check AutomationDirect.com.

Protos X I/O TM

The Protos X I/O system (seen below) is a modular, field I/O system consisting of a Bus Coupler and its associated input/output terminals. The Protos X field I/O series offers

• • • • •

2, 4, 8, and 16-point discrete I/O terminals, 2, 4 and 8-channel analog I/O terminals, three Bus Couplers that utilize the Modbus protocol with Modbus RTU/ASCII and Modbus TCP option, bus expansion terminals for expansion up to 255 I/O terminals per specific Bus Couplers, a variety of power supply options.

Bus Coupler

Discrete

I/O Terminals

Analog

I/O Terminals Power Seperation Terminal

Bus End Terminal

Bus Couplers

Bus Couplers are available in three configurations. The PX-MOD provides Modbus RTU/ASCII over RS-485. The PX-TCP1 and PX-TCP2 offer Modbus TCP over Ethernet. The PX-TCP2 provides an additional port which can act as a switch to other couplers of the same type.

Protos X Bus Couplers Part Number

Description

Price

PX-MOD

Modbus RTU/ASCII Bus Coupler

$268.00

PX-TCP1

Modbus TCP Bus Coupler (1 port)

$244.00

PX-TCP2

Modbus TCP Bus Coupler (2 ports)

$384.00

PX-MOD

www.automationdirect.com/fieldIO

PX-TCP1

PX-TCP2

Universal Field I/O

tFED-1

For the latest prices, please check AutomationDirect.com.

Protos X I/O Bus End Terminal/ Bus Expansion Coupler Terminals

Bus Expansion Terminals Part Number Description Bus End Terminal PX-901 Bus Expansion End Terminal PX-902

A Bus End Terminal, located at the end of a terminal assembly, is required for proper I/O bus communication. Bus expansion is available for the PX-MOD and PX-TCP1 Bus Couplers. Bus expansion requires that a Bus Expansion End Terminal be used in place of the Bus End Terminal and a Bus Expansion Coupler Terminal be used in place of the PX-MOD or PX-TCP1 at each expansion assembly.

PX-901

$13.00 $55.00

Bus Expansion Coupler Terminal

PX-903

PX-903

Price

$86.00

PX-902

Power Feed Terminals

Power Feed Terminals Part Number Description 24VDC Power Feed Terminal PX-940

Two Power Feed Terminals, 24VDC or 120-230 VAC, are available to add or change supply power to the Terminal Power Bus.

PX-970

PX-940

Price $18.00

120-230 VAC Power Feed Terminal

$24.00

PX-970

Power Distribution Terminal

Power Distribution Terminal Part Number PX-949

A Power Distribution Terminal provides access to the integrated 24VDC Terminal Power Bus. The terminal provides 8 connection points each of 24V and 0V.

Description

Price

24VDC Power Distribution Terminal

$29.00

PX-949

tFED-2

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Protos X I/O Discrete I/O Terminals

Discrete Input/Output Terminals Part Number

There are twelve discrete input and output terminals available offering 2 points, 4 points, 8 points or 16 points per terminal and include AC, DC and relay form factors.

Description

Price $34.00

PX-172-1

24VDC 4-point Input Terminal 24VDC 8-point Input Terminal 24VDC 16-point Input Terminal 120-230 VAC 2-point Input Terminal

PX-172-2

120 VAC/VDC 2-point Input Terminal

$36.00

PX-244-1

24VDC 4-point Output Terminal (0.5 A per point) 24VDC 4-point Output Terminal (2A per point) 24VDC 8-point Output Terminal 24VDC 16-point Output Terminal 230 VAC/VDC 2-point Output Terminal (0.3 A per point) 230VAC/30VDC 2-point Output Terminal (2A per point) 24VDC 8-point Input/ 24VDC 8-point Output Combination Terminal

$51.00

PX-144 PX-148 PX-149

PX-244-2 PX-248 PX-249 PX-172-2

PX-244-1 PX-549

PX-248

PX-272-1 PX-272-2 PX-549

Analog I/O Terminals

$55.00 $95.00 $36.00

$61.00 $63.00 $89.00 $68.00 $53.00 $98.00

Analog Input/Output Terminals Part Number

There are eighteen analog input and output terminals available offering 2 channels, 4 channels or 8 channels per terminal and include 4-20 mA, PT100 RTD, Type J and K thermocouple and 0-10 or ±10 VDC form factors.

Description

Price

PX-302

4-20 mA 2-channel Current Input Terminal

$216.00

PX-304

4-20 mA 4-channel Current Input Terminal

$191.00

PX-308

4-20 mA 8-channel Current Input Terminal +/-10VDC 2-channel Voltage Input Terminal +/-10VDC 4-channel Voltage Input Terminal +/-10VDC 8-channel Voltage Input Terminal

$244.00

PX-322-1 PX-324-1

2 Channel RTD Terminal

$233.00

4 Channel RTD Terminal

$268.00

PX-332-J

2 Channel Thermocouple Terminal (J type)

$240.00

PX-332-K

2 Channel Thermocouple Terminal (K type) 4 Channel Thermocouple Terminal (J type) 4 Channel Thermocouple Terminal (K type) 4-20 mA 2-channel Current Output Terminal 4-20 mA 4-channel Current Output Terminal 4-20 mA 8-channel Current Output Terminal 0-10 VDC 2-channel Voltage Output Terminal 0-10 VDC 4-channel Voltage Output Terminal +/-10VDC 8-channel Voltage Output Terminal

$240.00

PX-312 PX-314 PX-318

PX-314

PX-302 PX-332-J PX-404

PX-334-J PX-334-K PX-402 PX-404 PX-408 PX-412 PX-414 PX-418

www.automationdirect.com/fieldIO

Universal Field I/O

$216.00 $191.00 $244.00

$277.00 $277.00 $204.00 $191.00 $244.00 $204.00 $174.00 $244.00

tFED-3

For the latest prices, please check AutomationDirect.com.

Protos X I/O Power Separation Terminal A Power Separation Terminal is available to provide interruption of power along the Terminal Power Bus.

Configuration Cable (USB v2.0) A communications cable is available for configuration of the Bus Couplers. The cable has a USB type A connector for the PC and a 4-pin custom micro connector for the bus coupler.

tFED-4

Universal Field I/O

Power Separation Terminal Part Number Description Power Separation Terminal PX-908

Price $17.00

Configuration Cable (USB) Part Number

Description

Price

PX-USB-232

Configuration Cable 3m (9.8 ft.)

$56.00

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Bus Couplers PX-MOD PX-MOD I/O Bus Specifications

PX-MOD $268.00

24VDC (-15%/+20%) Supply Power for I/O Bus Input Current from Power Supply 70mA + (total I/O bus current) / 4 10A Max Recommended Fuse 1000mA Max I/O Bus Current Supply Number of Bus Terminals 64 per assembly, 255 w/ I/O Bus Expansion (based on power budget) Supported Number of Discrete Inputs/Outputs 1020 Inputs and 1020 Outputs with 255 terminals Number of Analog Inputs/Outputs 256 inputs and 256 outputs Maximum Number of Data Bytes* 512 Input Bytes and 512 Output Bytes

24V 0V 5

1

* Total number of terminals cannot exceed 512 input bytes and 512 output bytes.

+ +

PX-MOD Terminal Power Bus Specifications

6

2

Supply Power for Terminal Bus Maximum Current Number of Power Contacts

– – 7

3

24 VAC/VDC 10A 2 (+24 VAC/DC, 0V)

PX-MOD Modbus Port Specifications 4

8

D PX-MO

The PX-MOD Modbus RTU/ASCII Slave Bus Coupler allows connection of up to 64 terminals per assembly, 255 termiUsserial nals total, inWD a Modbus RTU/ASCII network. The 5PX-MOD communicates 1 RXModbus commands Upand using high-level 16 5 2 512 bytes supports of input data and 512 2 6 37 bytes3of outputTX data.7 I/O RUN 4 8 4 8

224V 4V 00V V RS-485 Errorincludes Error /O ERR The PX-MOD one II/O

24V 0V

D-sub 9-pin port that functions in half duplex for connection to a Modbus master. Configuration figuration Port 1 2

5 6

3 4

7 8

I/O Bus contacts

24V 0V Modbus 9-Pin, D-Sub Port

Us GNDs

+ +

DIN Rail Locking Wheel

Up

78

456

78

23

456

X10

9 01

.nc

Rotary Switches Modbus RTU/ASCII (default = RTU) 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400 baud 4000 ft. (1,200m) 9-pin, D-Sub, RS-485 24AWG, Shielded, Twisted Pair

General Specifications 32° to 131°F (0° to 55 °C) 13° to 185°F (-25° to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27 conforms to EN 61000-6-2 IP20 100g 44mm x 100mm x 66.4 mm (1.73 in x 3.94 in x 2.61 in) UL/cUL File No. E157382, CE

* T o obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

Terminal Power In 24 VAC/VDC

IMPORTANT!

Hot-Swapping Information Note: This device cannot be Hot Swapped.

Terminal Power In 0V

9 01

23

X1

99

Operating Temperature Storage Temperature Relative Humidity Environment Air Mounting/Orientation Restrictions Vibration Shock Noise Immunity Protection Class Weight Dimensions (WxHxD) Agency Approvals*

DIN Rail Release Tab GNDp

Modbus Station Rotary Switches

Bus Coupler Power In 24VDC

Number of Stations Station Configuration Protocol Data Transfer Rates Maximum Cable Length Connector Type Recommended Cable

Terminal Power Bus Contacts

.nc

PX-MOD

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-5

For the latest prices, please check AutomationDirect.com.

Bus Couplers PX-MOD Configuration Port

The Service Port connector is located under the flip-cover shown. This port is used for communication with the software configuration tool. The software configuration tool autoconfigures the Modbus addresses of the I/O terminals and the interface allows the user to: • Run the configurator • View the configured Modbus addresses • Change the Modbus offset

• Modify the baud rate

• Reboot the coupler • Disable or modify Watchdog timer

Requires cable PX-USB-232, with a USB type A connector for the PC and a 4-pin custom micro connector for the Bus Coupler. Works with PX-CFGSW configuration software.

Status LEDs

Us

WD 1 2 3 4

1 2 3

5 6 7 8

4

24V 0V

5 6

RX 1

5

2

6 7 8

37 TX 4

8

Error Error

Us GNDs

+ + Up

Red LED 4: ERROR Green LED 5: Us Green LEDModbus 6: Up 9-Pin, Green LED 7:Port I/O RUN D-Sub Red LED 8: I/O ERR DIN Rail

GNDp

24V 0V

Status: OFF

Watchdog is active

Watchdog error

Data being received

No data being received

I/O Bustransmitted Data being1transmitted No data being 5 contacts 6 Data Error,23communications with 7 No dataBus error or checksum error the master 4device8 has been lost Coupler 24V 0V Bus Coupler power on Bus Coupler Powerpower In off 24VDC

Terminal power on Us GNDs I/O bus data active

Terminal power off

+ +

I/O bus error, blinking code Up

456

GNDp

78 78

X10

(TxD–/RxD–) 8 (5V) 6

9 01

23

23

PX-MOD

Modbus Station Rotary Switches

9 01

23

X1

.nc

Watchdog-timer overflow Terminal No I/O Power bus errorIn

24 VAC/VDC DIN Rail Release Tab

D-sub 9-pin, RS-485 Connector .nc

II/O /O ERR

Status: ON

456

78

23

78

224V 4V 00V V

Locking Wheel

9 01

9 01

I/O RUN

LED Descriptions LED Green LED 1: WD figuration GreenConfiguration LED 2: Port RX Green LED 3: TX

456

m ]

Up

Terminal Power In 0V Terminal

.nc

.nc

PX-MOD

Power Bus 5 (GND) Contacts

3 (TxD+/RxD+) Pin 1

456

44 mm [1.74”] Address Selection Rotary Switches

The Modbus node address for the PX-MOD is set using both rotary switches on the front of the Coupler. The address is configured within the 01 to 99 range. The configured value of 00 is reserved for programming and configuration. The lower rotary switch is used to set the tens digit (x10) of the node address. The upper rotary switch is used to set the ones digit (x1) of the node address. The switch address is accepted only when power is cycled. The example shown is configured for a node address of 21.

tFED-6

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Bus Couplers PX-MOD For expansion beyond a 64-terminal assembly, a Bus Expansion End Terminal (PX-902) is used in place of a standard Bus End Terminal (PX-901). A Bus Expansion Coupler Terminal (PX-903) is used at each expansion assembly in place of a PX-MOD Bus Coupler. Up to 31 Expansion couplers can be used in a group of assemblies. Connection is made between the Expansion Coupler Terminals via standard RJ45 Ethernet patch cable.

System Considerations The PX-MOD performs as a Modbus RTU/ASCII slave in a Modbus network. Communication to the master is via a 9-pin D-sub RS-485 port. The maximum distance from the master to the PX-MOD is 4000 feet (1200 meters) using 24 AWG shielded, twisted pair. Termination resistors are required at the beginning and end of the network. It is highly recommended that a dedicated network be used for the Protos X system. The PX-MOD Bus Coupler supports up to 64 terminals per assembly, 255 with Bus Expansion Couplers. A minimal assembly consists of a PX-MOD Bus Coupler, I/O Terminals and a Bus End Terminal.

Bus Coupler PX-MOD

An I/O Bus, powered through the Bus Coupler, provides data communication across the terminal assembly via six contacts located on the side walls of the terminals. A Terminal Power Bus provides power for the I/O terminals via two power contacts. A power source of 24VAC or 24VDC must be connected to the Bus Coupler from an external supply.

I/O-Bus

It is important to stay within the following three specifications:. 1. Do not exceed the total number of 64 Terminals allowed per Assembly. 2. Do not exceed the total number of 512 Input Bytes and 512 Output Bytes. 3. Do not exceed the Coupler I/O Bus Power Budget of 1000mA as there is no internal current protection.

Power Distribution Terminal

Bus End Terminal

0V Us GNDs

1

5

2

6

3

7

4

8

+ + Up

GNDp

78

23

90 1

456

If additional 24VDC supply is required for terminal wiring, eight points of 24VDC power can be distributed from the Terminal Power Bus using a Power Distribution Terminal (PX-949). This terminal must be mounted to the right of a terminal that passes 24VDC on the power bus. Both I/O Bus communication and terminal bus power are passed through to adjoining terminals.

.nc

78

23

90 1

.nc

PX-901 P PX X-901

PX-MOD

456

Terminal Power Bus

Power Bus Isolation

Cat5e STP cable 16.5 ft. (5m) max. length per segment

PX-MOD Example Network Diagram PX-MOD

PX-902

PX-MOD

PX-901

PX-MOD

PX-901

PX-903

PX-901

PX-903

PX-901

PC with PX-CFGSW PX-USB-232 PX-903

PX-901

P3000 CPU or other Modbus Master

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-7

Bus Couplers PX-MOD PX-MOD Wiring Connections

Label Label Us GNDs Us GNDs

1 2 3 4

Bus Coupler Bus Coupler SupplySupply Power Power 24V 0V 24V 0V

+ – + –

5 6

24VDC24VDC Power Power

7 8

24V 0V

Label Label

Us GNDs

Up

94mm

+ +

Up

Up

GNDp

GNDp

GNDp

78

456

47 mm

tFED-8

Universal Field I/O

– –

+ –

+ –

24VDC OR Power

.nc

23

78

.nc

+ + + +

24VDC Power

23

9 01

9 01

Terminal Terminals Supply Power

– –

456

100 mm

For the latest prices, please check AutomationDirect.com.

PX-MOD

.nc .nc

.nc

.nc

24VAC Power

24VAC Power

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Bus Couplers PX-TCP1 PX-TCP1 $244.00

PX-TCP1 I/O Bus Specifications 24VDC (-15%/+20%) Supply Power for I/O Bus Input Current from Power Supply 70mA + (total I/O bus current) / 4 10A Max Recommended Fuse 1000mA Max I/O Bus Current Supply Number of Bus Terminals 64 per assembly, 255 w/ I/O Bus Expansion (based on power budget) Supported Number of Discrete Inputs/Outputs 1020 Inputs and 1020 Outputs with 255 terminals Number of Analog Inputs/Outputs 128 total Maximum Number of Data Bytes* 512 Input Bytes and 512 Output Bytes

PX-TC P1 LINK/A

CT

24V 0V 5

1

* Total number of terminals cannot exceed 512 input bytes and 512 output bytes.

+ +

PX-TCP1 Terminal Power Bus Specifications

6

2

– – 7

3

DIP

1 2 3 4 5 6 7 8

ON

Supply Power for Terminal Bus Maximum Current Number of Power Contacts

1 2

ON 4

8

PX-TCP1

The PX-TCP1 Modbus TCP Server Bus Coupler allows connection of up to 64 terminals per assembly, 255 terminals Us The WDinERR total, a Modbus TCP network. PX-TCP1 1 5communicates using highCOM commands and Upsupports level Modbus 2 6 512 bytes of input data and 512 bytes of 3 7 I/O BUS RUN output data. Error 4 8

II/O /OEthernet B BUS ERR The PX-TCP1 includes one RJ45 10/100 Base-T port for connection to a Modbus client.

24V 0V

Configuration Port 1

Ethernet RJ45 Port

I/O Bus contacts

5 6 7

2 3 4

8

24V 0V Us GNDs

+ DIN Rail Locking Wheel

Up

DIP

1 2 3 4 5 6 7 8

TM

3 (+24 VAC/VDC, 0V, PE)

DIP switches and PX-CFGSW software Modbus TCP 10/100 Mbaud 100m between Coupler and switch Ethernet, RJ45 Shielded, Twisted Pair, Cat5e

General Specifications Operating Temperature Storage Temperature Relative Humidity Environment Air Mounting/Orientation Restrictions Vibration Shock Noise Immunity Protection Class Weight Dimensions (WxHxD) Agency Approvals*

32° to 131°F (0° to 55 °C) 13° to 185°F (-25° to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27 conforms to EN 61000-6-2 IP20 100g 44mm x 100mm x 66.4 mm (1.73 in x 3.94 in x 2.61 in) UL/cUL File No. E157382, CE

* T o obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

Terminal Power In 24 VAC/VDC

IMPORTANT!

Hot-Swapping Information Note: This device cannot be Hot Swapped.

Terminal Power In 0V

GNDp

PE PE

.PE

1 2

ON

DHCP BootP

Bus Coupler Power In 24VDC

Configuration Protocol Data Transfer Rates Maximum Cable Length Connector Type Recommended Cable

DIN Rail Release Tab

ON

Last Octet of IP Address

+

10A

PX-TCP1 Modbus Port Specifications

PE PE PE

24 VAC/VDC

PX-TCP1

Terminal Power In PE (Earth Ground) Terminal Power Bus Contacts

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-9

For the latest prices, please check AutomationDirect.com.

Bus Couplers PX-TCP1 Configuration Port The Service Port connector is located under the flip-cover shown. This port is used for communication

with the software configuration tool. The software configuration tool autoconfigures the Modbus addresses of the I/O terminals and the interface allows the user to: • Run the configurator • View the configured Modbus addresses • Modify the baud rate • Reboot the coupler • Change the Modbus offset • Configure first three octets of the IP address • Disable or modify Watchdog timer

Requires cable PX-USB-232, with a USB type A connector for the PC and a 4-pin custom micro connector for the Bus Coupler. Works with PX-CFGSW configuration software.

PX-TCP1 / X MOD PX-MOD

PX-902

PX-903 StatusPX LEDs 903 WD ERR

Us

1 2

COM

Up

7 Error

I/O BUS RUN

5 6

3 4

1 2 3 4

8

24V 0V

24V 0V Us GNDs G

1

Status: ON

5

Flashing: waiting for IP address if set to No error I/O Bus 1 5 DHCP or BootP 2 6 10 BASE-T/100 BASE-TX contacts 3 7 Not used 4 8 Bus LINK Bus Coupler power on BusCoupler Coupler 1 power off 24V 0V Power In Terminal power on Terminal power off

Red LED 3: ERROR Green LED 4: RTE 2 6 Green LED 5:Ethernet Us RJ45 Green LED 6: Up Port Green LED 7: I/O-Bus RUN Red LED 8: I/O-Bus ERR

Us GNDs

ON

I/O bus error, blinking code

No I/O bus error Terminal

+

OR/WHT

ON

1

PX-903 DHCP BootP

8

44 m mm m [1.73”] 3”] Address Selection DIP Switches

.PE

1 2

PX-TCP1 PX TCP11

8-pin RJ45 Connector

Crossover Cable

RJ45 TD+ 1 TD– 2 RD+ 3 4 5 RD– 6 7 8

12345678

24 5 mm 24.5 [.96”] [ 96 96”]]

OR/WHT OR GRN/WHT BLU BLU/WHT GRN BRN/WHT BRN

TD+ 1 OR TD– 2 GRN/WHT RD+ 3 GNDp BLU 4 BLU/WHT 5 GRN RD– 6 BRN/WHT 7 PE PE BRN 8 TM

ON

1 2

LINK

8

DIP

1 2 3 4 5 6 7 8

Last Octet of IP Address

4

2

6

3

7

4

8

8

Power1In 2345678 24 8-pin VAC/VDC RJ45 Connector

DIN Rail Crossover Cable

RJ45

10 BASE-T/100 BASE-TX

.PE

+

Up

ON

DIP

1 2 3 4 5 6 7 8

No I/O bus activity

DIN Rail Locking 3 7 Wheel

PE PPEE

5

RJ45 GRN/WHT GRN OR/WHT BLU BLU/WHT OR BRN/WHT BRN

24VDC

I/O bus data active (On or Flashing)

RJ45 Connector TM

1

Watchdog error

Green LEDConfiguration 2: COM Port

GNDp

Status: OFF

Watchdog is active after first Modbus write Ethernet data is active (On or Flashing) No data being received

Red LED 1: WD ERR

Up

II/O /O B BUS ERR

LED Descriptions LED

+ +

Standar Termina

1 2 3 4 5 6 7 8

TD+ TD– RD+ RD–

RJ45 TD+ 1 TD– 2 RD+ 3 4 5 RD– 6 7 8

Release Tab

Terminal Power In 0V

RJ45 GRN/WHT GRN OR/WHT BLU BLU/WHT OR BRN/WHT

Terminal BRN Power In PE (Earth Ground) Cable Patch (Straight-through)

PX-902 P X-90 02 0 2

PX-TCP1 OR/WHT OR

GRN/WHT BLU GRN

BRN/WHT BRN

TD+ TD– RD+ RD–

RJ45

Terminal OR/WHT 1 TD+ OR Power Bus 2 TD– Contacts GRN/WHT 3 RD+

27.5 mm [.96”] [.96 ]

BLU/WHT

1 2 3 4 5 6 7 8

BLU

BLU/WHT GRN BRN/WHT BRN

4 5 6 RD– 7 8

Cat5e cable recommended. See PX-USER-M manual for complete details.

12 mm [.47”]

The last octet or byte of the IP Address for the PX-TCP1 is set using the large bank of DIP switches Patch (Straight-through) Cable RJ45 on the front of RJ45 the coupler. The smaller bank of DIP switches is used to select the type of address OR/WHT OR/WHT TD+ 1 1 TD+ OR OR assignment (DHCP, BootP, firm setting). TD– 2 2 TD– GRN/WHT

GRN/WHT

3 RD+ BLU BLU that switch 1 corresponds to bit 0 (LSB) and switch 8 The IP AddressRD+ DIP34 switches are arranged so 4 BLU/WHT BLU/WHT 5 5 GRN GRN to bit 7 (MSB).RD– The base address used is configured using the PX-CFGSW software tool. With the 6 6 RD– BRN/WHT BRN/WHT 7 7 original factory settings, the IP Address is configured to the value 0.0.0.0. by default. BRN BRN 8 8 Cat5e cable recommended. See PX-USER-M manual for complete details.

tFED-10

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Bus Couplers PX-TCP1 System Considerations The PX-TCP1 performs as a Modbus TCP server in a Modbus network. Communication to the client is via an RJ45 Ethernet port. The maximum distance from the client to the PX-TCP1 is 330 feet (100 meters) using 24 AWG shielded, twisted pair Cat5e cable. It is highly recommended that a dedicated network be used for the Protos X system.

For expansion beyond a 64-terminal assembly, a Bus Expansion End Terminal (PX-902) is used in place of a standard Bus End Terminal (PX-901). A Bus Expansion Coupler Terminal (PX-903) is used at each expansion assembly in place of a PX-TCP1 Bus Coupler. Up to 31 Expansion couplers can be used in a group of assemblies. Connection is made between the Expansion Coupler Terminals via standard RJ45 Ethernet patch cable.

The PX-TCP1 Bus Coupler supports up to 64 terminals per assembly, 255 with Bus Expansion Couplers. A minimal assembly consists of a PX-TCP1 Bus Coupler, I/O Terminals and a Bus End Terminal.

Power Distribution Terminal

Bus End Terminal

24V 0V Us GNDs

1

5

2

6

3

7

4

8

+ + Up

GNDp

PE PE

TM

DIP

1 2 3 4 5 6 7 8

.PE

1 2

ON

If additional 24VDC supply is required for terminal wiring, eight points of 24VDC power can be distributed from the Terminal Power Bus using a Power Distribution Terminal (PX-949). This terminal must be mounted to the right of a terminal that passes 24VDC on the power bus. Both I/O Bus communication and terminal bus power are passed through to adjoining terminals.

I/O-Bus

ON

An I/O Bus, powered through the Bus Coupler, provides data communication across the terminal assembly via six contacts located on the side walls of the terminals. A Terminal Power Bus provides power for the I/O terminals via three contacts; 24V, 0V and PE. A power source of 24VAC or 24VDC must be connected to the Bus Coupler from an external supply. The PE Bus is available for terminals that support PE connectivity.

Bus Coupler PX-TCP1

It is important to stay within the following three specifications:. 1. Do not exceed the total number of 64 Terminals allowed per Assembly. 2. Do not exceed the total number of 512 Input Bytes and 512 Output Bytes. 3. Do not exceed the Coupler I/O Bus Power Budget of 1000mA as there is no internal current protection.

PX-901 P PX X-901

PX-TCP11

Terminal Power Bus

Power Bus Isolation

Cat5e STP cable 16.5 ft. (5m) max. length per segment

PX-TCP1 Example Network Diagram PX-USB-232

PX-TCP1

PX-902

PX-903

PX-901

PX-903

PX-901

PC with PX-CFGSW PX-TCP1

PX-901

PX-TCP1

PX-901

Stride Ethernet Switch PX-903

PX-901

P3000 CPU or other Modbus Master

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-11

For the latest prices, please check AutomationDirect.com.

Bus Couplers PX-TCP1 PX-TCP1 Wiring Connections

PX-TCP1 / X MOD PX-MOD

2

Label Label PX PX-903 903

Us GNDs Us GNDs

24V 0V 24V 0V

+ – + –

1 2 3 4

24VDC24VDC Power Power 24V 0V

24VV 00V Us GNDs G

1

+ +

+ + Up

Label 5 Up

Label Label Up

Up

2

6

3

7 GNDp GNDp

ON GNDp

GNDp TM

DIP

1 2 3 4 5 6 7 8

PE PE

Standard Bus Coupler Bus Coupler PX-902 SupplySupply Power Power Terminal

1

5

+ + TerminalTerminal Supply Supply Power Power + + + + – – – – – –

ON

1 2

2

6

3

7

24VDC24VDC 24VDC 4 Power or Power or Power

8

+ – ++ ––

PE PPEE 4

.PE

8

PX-903

PX-TCP1 PX TCP11

PE

44 m mm m [1.73”] 3”]

Terminals

.nc PE.nc

24 5 mm 24.5 (Earth Ground) (Earth [.96”] [ 96 96”] ] Ground)

PX-902 P X-90 02 0 2

24VAC Power 24VAC Power 27.5 mm [.96”] [.96 ]

12 mm 24VAC [.47”]

Power

tFED-12

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Bus Couplers PX-TCP2 PX-TCP2 $384.00

PX-TCP2 I/O Bus Specifications 24VDC (-15%/+20%) Supply Power for I/O Bus Input Current from Power Supply 70mA + (total I/O bus current) / 4 10A Max Recommended Fuse 1750mA Max I/O Bus Current Supply Number of Bus Terminals 64 per assembly (based on power budget) Supported Number of Discrete Inputs/Outputs 512 Inputs and 512 Outputs Number of Analog Inputs/Outputs 128 total Maximum Number of Data Bytes* 512 Input Bytes and 512 Output Bytes * Total number of terminals cannot exceed 512 input bytes and 512 output bytes.

PX-TCP2 Terminal Power Bus Specifications Supply Power for Terminal Bus Maximum Current Number of Power Contacts

The PX-TCP2 Modbus TCP Server Bus Coupler allows connection of up to 64 terminals in a Modbus TCP network. The PX-TCP2 communicates using high-level Modbus commands and supports 512 bytes of input data and 512 bytes of output data. The PX-TCP2 includes two RJ45 Ethernet 10/100 Base-T ports for connection to a Modbus client. Bus Coupler Power Terminal Bus Power

COM

Ethernet RJ45 Port

ERROR R WDG

I/O RUN N I/O ERR R

DIN Rail Locking Wheel

I/O Bus contacts

24V 0V

+ +

Bus Coupler Power In 24VDC

Configuration Protocol Data Transfer Rates Maximum Cable Length Connector Type Recommended Cable

1 2 3 4 5 6 7 8 9 10 ON

DHCP BootP

Configuration Port

Modbus TCP 10/100 Mbaud 100m between Client and Coupler to Coupler Ethernet, 2 x RJ45 (2 Channel Switch) Shielded, Twisted Pair, Cat5e

General Specifications 32° to 131°F (0° to 55 °C) 13° to 185°F (-25° to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27 conforms to EN 61000-6-2 IP20 170g 51mm x 100mm x 66.4 mm (2.01 in x 3.94 in x 2.61 in) UL/cUL File No. E157382, CE

* T o obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

Terminal Power In 24 VAC/VDC

IMPORTANT!

Hot-Swapping Information Note: This device cannot be Hot Swapped.

Terminal Power In 0V

TM

PX-TCP2

3 (+24 VAC/VDC, 0V, PE)

DIP switches and PX-CFGSW software

Operating Temperature Storage Temperature Relative Humidity Environment Air Mounting/Orientation Restrictions Vibration Shock Noise Immunity Protection Class Weight Dimensions (WxHxD) Agency Approvals*

DIN Rail Release Tab

Last Octet of IP Address

10A

PX-TCP2 Modbus Port Specifications

TM

Ethernet TCP/IP

24 VAC/VDC

PE PE

Terminal Power In PE (Earth Ground) Terminal Power Bus Contacts

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-13

WD

For the latest prices, please check AutomationDirect.com.

Bus Couplers PX-TCP2 Configuration Port

RX TX

The Service Port connector is located under the flip-cover shown. This port is used for communication with the software configuration tool. The software configuration tool autoconfigures the Modbus Error addresses of the I/O terminals and the interface allows the user to: • Run the configurator • View the configured Modbus addresses • Modify the baud rate • Reboot the coupler • Change the Modbus offset • Configure first three octets of the IP address • Disable or modify Watchdog timer

Requires cable PX-USB-232, with a USB type A connector for the PC and a 4-pin custom micro connector for the Bus Coupler. Works with PX-CFGSW configuration software.

PX-TCP2

PX-TCP1 / Status LEDs PX-MOD X MOD

Ethernet TCP/IP COM

ERROR WDG

0 mm 94”] 4”]

1

1

5

2

6

3 4

7 8

24V 0V

2 3 4

24V 0V

24VV 00V

+ +

I/I/O /O RUN I/I/O /O ERR

PX PX-903 903

LED Descriptions LED Status: ON Us GNDs G Green Power LED (left): Bus Bus Coupler power on Coupler Ethernett Green Power LED (right): Terminal Bus power TCP/IPon Terminal Bus COM On/Flashing: Receiving Data Green Ethernet LED: COM

Status: OFF Bus Coupler power off

+ +

Ethernet

Up

1

Terminal Bus power off

I/O Bus contacts

No data being received

10 BASE-T/100 BASE-TX

Bus

Flashing: waiting for IP address

ERROR 2 Controller Red Ethernet LED: ERROR RJ45 LINK if set to DHCP or BootP 24V 0VNo Error Power In WDG 1 Port 24VDC Watchdog is active Watchdog error Green Ethernet LED: WDG

I/O Bus Data Active (On or Flashing) I/O RUN + I/O bus error, blinking code I/O ERR

Green I/O Bus LED: I/O RUN ON

Locking Wheel

RJ45 Connectors

TM

GNDp OR/WHT

TD+ IP 1LINK OR TD– 2 Address GRN/WHT

ON

RJ45

tFED-14

Universal Field I/O

DIN Rail

7

RJ45 Release

GRN/WHT

1

GRN

TM

Crossover Cable

OR

Address Selection DIP Switches

1 2 3 4 5 6 7 824 VAC/VDC

8-pin RJ45 Connector 3

PE

RJ45

8

PX-903

Terminal GRN/WHT OR/WHT (Straight-through) Cable PX-TCP1 PX TCP11 RJ45 TD+ 1Patch 1 TD+RJ45

TD– 2OR/WHT TD+ 1 3 GRN/WHT RD+ OR Configuration TD– 2 4 BLU GRN/WHT BLU/WHT RD+ 3 5 Port GRN BLU RD– 4 6 BRN/WHT BLU/WHT 5 78 BRN GRN

44RD– m mm m 6 7 [1.73”] 3”] 8

51 mm m [2.01”]]

Terminal

Power In No I/O bus error

Tab 1 TD+ 2 TD– OR/WHT Terminal 3 RD+ BLU 4 Power In BLU/WHT 5 0V PX-TCP2 OR 6 RD– 8 1PE2 3PE4BRN/WHT 5 6 7 8 7 Terminal 4 BRN 8-pin RJ45 Connector 8 Power In

PE PPEE

RD+ 3 BLU 4 BLU/WHT 5 GRN RD– 6 BRN/WHT 7ACT .PEBRN 8 TM

6

Terminal power off

+

10 BASE-T/100Cable BASE-TX Crossover

RJ45

DIP

PE PE

8

1 2 3 4 5 6 7 8 9 10 ON

TCP2 PX-TCP2

1 2

1 2 3 4 5 6 7 8 9 10 ON

1 2 3 4 5 6 7 8

Red I/O BusDIN LED: I/O ERR Rail

5

Power LEDs

GRN

2 TD– OR/WHT OR/WHT 1 3 RD+ BLU OR 2 4 BLU/WHT GRN/WHT 5 3 OR BLU 6 RD– 4 BRN/WHT BLU/WHT 7 5 BRN 8 GRN

Power Bus TD+ Contacts

TD– RD+

24 5 mm 24.5 [.96”] [ 96 96”]]

6 RD– 7 Patch (Straight-through) Cable BRN RJ45 BRN RJ45 8 BRN/WHT

The last setting),

OR/WHT

BRN/WHT

OR/WHT

TD+ 1 1 TD+ Cat5e cable recommended. OR OR TD– 2 PX-USER-M manual for complete details. 2 TD– See GRN/WHT GRN/WHT RD+ 3 3 RD+ BLU BLU 4 4 BLU/WHT BLU/WHT 5 5 GRN GRN 6 of address assignment (DHCP, 6 RD– BootP, octet or byte of the IP Address, as well as theRD– type BRN/WHT BRN/WHT 7 7 BRN for the PX-TCP2 is set using the DIP switches on8 the front of the coupler.BRN 8

firm

Cat5e cable recommended.

The IP Address DIP switches are arranged so that switchSee 1 PX-USER-M corresponds 0 (LSB) and switch 8 to manualto for bit complete details. bit 7 (MSB). Switches 9 and 10 allow for the address assignment selection. The base address used is configured using the PX-CFGSW software tool. With the original factory settings, the IP Address is configured to the value 0.0.0.0. by default.

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Bus Couplers PX-TCP2 System Considerations The PX-TCP2 performs as a Modbus TCP server in a Modbus network. Communication to the client is via an RJ45 Ethernet port. A second port allows expansion of up to 20 total PX-TCP2 Couplers in a network. The maximum distance from a client to a PX-TCP2, and between each additional PX-TCP2, is 330 feet (100 meters) for each segment, using 24 AWG shielded, twisted pair Cat5e cable. It is highly recommended that a dedicated network be used for the Protos X system.

8

WDG

24V 0V

Us GNDss

I/O RUN I/O ERR

1

5

2

6

3

7

4

8

+ ++

Up

GNDp

TM

PX-TCP2 PX-TCP2 TM TM

DIP D IP P

PE PE PE

.PE P

1 2

ON ON

It is important to stay within the following three specifications. 1. Do not exceed the total number of 64 Terminals allowed per Assembly. 2. Do not exceed the total number of 512 Input Bytes and 512 Output Bytes. 3. Do not exceed the Coupler I/O Bus Power Budget of 1750mA as there is no internal current protection.

4

ERROR

ON N

If additional 24VDC supply is required for terminal wiring, eight points of 24VDC power can be distributed from the Terminal Power Bus using a Power Distribution Terminal (PX-949). This terminal must be mounted to the right of a terminal that passes 24VDC on the power bus. Both I/O Bus communication and terminal bus power are passed through to adjoining terminals.

Bus End Terminal

COM

1 2 3 4 5 6 7 8 9 10 ON

An I/O Bus, powered through the Bus Coupler, provides data communication across the terminal assembly via six contacts located on the side walls of the terminals. A Terminal Power Bus provides power for the I/O terminals via three contacts; 24V, 0V and PE. A power source of 24VAC or 24VDC must be connected to the Bus Coupler from an external supply. The PE Bus is available for terminals that support PE connectivity.

Power Distribution Terminal

I/O-Bus

Ethernet TCP/IP

1 2 3 4 5 6 7 8

The PX-TCP2 Bus Coupler supports up to 64 terminals per assembly. It is not compatible with Bus Expansion Couplers. A minimal assembly consists of a PX-TCP2 Bus Coupler, I/O Terminals and a Bus End Terminal (PX-901).

Bus Coupler PX-TCP2

PX-901 P PX X-901

PX-TCP1 P PX X-TCP1

Terminal Power Bus T i lP

Power Bus Isolation

PX-TCP2 Example Network Diagram PX-TCP2

PX-901

PX-TCP2

PX-901

P3000 CPU or other Modbus Master

PX-TCP2

PC with PX-CFGSW

www.automationdirect.com/fieldIO

PX-901

PX-USB-232

Universal Field I/O

tFED-15

For the latest prices, please check AutomationDirect.com.

Bus Couplers PX-TCP2 PX-TCP2 Wiring Connections

PX-TCP2Label

Us GNDs

PX-TCP1 / Bus Coupler Supply Power Label X MOD PX-MOD 24V 0V Us GNDs

Ethernet TCP/IP COM

1 2 3 4

+ –

24VDC Power ERROR WDG

I/I/O /O RUN I/I/O /O ERR

+ ++

+ +

ON

1



2

Terminals + – + PE+ PPEE 24VDC Power TM

ON

1 2



PEPE PE

PX-TCP1 PX TCP11

44 m mm m 24VAC Power [1.73”] 3”]

24VAC Power

6

+ + + – 24VDC – or Power

(Earth Ground) (Earth Ground)

51 mm m [2.01”]]

– –

Terminals

GNDp

.PE

5

+ +

+

GNDp

DIP

24VAC Power

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8 9 10 ON

TM

PE PE

+ –

24VDC Power

Terminal Supply Power

Label Terminals Up Up

TCP2 PX-TCP2

24V 0V

24V 0V

24VV 00V Us GNDs G

100 mm [3.94”] 4”]

Bus Coupler Supply Power PX PX-903 903

3

7

4

8

PX-903 24VAC Power

+ –

24.55 mm 24 24VDC Power [.96”] [ 96 96”]]

+ –

24VDC Power

PE PE (Earth Ground)

PE PE (Earth Ground)

tFED-16

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Power Budget Planning Managing Power Resources When determining the types and quantity of terminals you will be using, it is important to remember there is a defined amount of I/O Bus Current supplied from the Bus Coupler. There are also defined limits for each external source. The chart on the next page indicates the power supplied and used by each Protos X component. The chart below shows an example of how to calculate the power used by your particular system. These charts should make it easy for you to determine if the devices you have chosen will operate within the power budget of your system configuration. If the I/O terminals you have chosen exceed the maximum power available from the Bus Coupler, you may be able to resolve the problem by using expansion terminals.

Power Budget Example The example on the right shows how to calculate the power budget for a typical Protos X system. This example is constructed using a PX-MOD Bus Coupler and six I/O Terminals. It is recommended you construct a similar table for your system. Follow the steps below to determine your power budget. 1. Using a chart similar to this one, fill in columns 1 and 2.

A

Column 2

Column 3

Terminal

Terminal Type

I/O Bus (from Coupler)

B CURRENT SUPPLIED PX-MOD

Bus Coupler

1000mA

C CURRENT REQUIRED PX-144 PX-172-1 PX-322-1 PX-312 PX-244-1 PX-412

2. U  sing the tables on the next page enter the current supplied and current used by each device (column 3). 3. Add together the current used by the system (row C) for column 3 and put the total in the row labeled “Maximum Current Required” (row D).

Column 1

4pt. DC Discrete Input 2pt. AC Discrete Input 2ch. RTD Input 2ch. DC Analog Input 4pt. DC Discrete Output 2ch. DC Analog Output

5mA 3mA 60mA 65mA 9mA 75mA

D Maximum Current Required

217mA

Remaining Current Available

783mA

E

4. Subtract the calculated “Maximum Current Required” (row D), from the “Current Supplied” and place the difference in the row labeled “Remaining Current Available” (row E). 5. If “Maximum Current Required” is greater than “Current Supplied” in column 3, the power budget will be exceeded. It will be unsafe to use this configuration, and you will need to restructure your I/O configuration.

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-17

For the latest prices, please check AutomationDirect.com.

Power Requirements Power Supplied and Consumed

Power Supplied 5V(mA) I/O Bus Supply

Device

These tables show the amount of power supplied by each of the Bus Couplers and the amount of power consumed by each I/O device. The Power Consumed chart lists how much power is drawn from the I/O Bus, Terminal Power Bus (externally supplied) and from the Load (when using output terminals). Use this information when calculating the power budget for your system.

Coupler PX-MOD PX-TCP1 PX-TCP2

1000 Max 1000 Max 1750 Max

Bus Expansion Coupler PX-903

400 Max

Power Consumed Device

from Terminal 5V(mA) from I/O Bus (mA) Power Bus

(mA) from Load

Discrete Input Terminals PX-144 PX-148 PX-149 PX-172-1 PX-172-2

5 5 20 3 3

5 2 (plus load) N/A 6 6

N/A

N/A

30 30 60 (plus load) 35 (plus load)

N/A Load Load N/A N/A N/A

N/A

N/A

N/A

N/A

50 (plus load) 60 (plus load) 50 (plus load) 50 (plus load) 50 (plus load) 20

ON resistance max 100mV (plus load)

N/A

Discrete Output Terminals PX-244-1 PX-244-2 PX-248 PX-249

9 9 18 45

Analog Input Terminals PX-302 PX-304 PX-308 PX-312 PX-314 PX-318

60 85 105 65 100 140

RTD/Thermocouple Input Terminals PX-322-1 PX-324-1 PX-332-J PX-334-J PX-332-K PX-334-K

60 60 65 75 65 75

Analog Output Terminals PX-402 PX-404 PX-408 PX-412 PX-414 PX-418

60 20 25 75 75 20

Relay Output Terminals PX-272-1

10

PX-272-2

80

Combination In/Out Terminals PX-549

tFED-18

Universal Field I/O

25 (additional 3mA for inputs) 15 (plus load)

N/A

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

System Installation and Removal Bus Coupler and Bus Terminal Installation Bus Coupler Installation:

2

1. Attach a Bus Coupler by snapping it onto 35mm DIN rail and securing it into position using the DIN rail locking wheel (where applicable) located on the left side of the coupler.

Insert unit using tongue and groove ntil molded guide and press gently until it becomes firmly seated on DIN rail. ra ail. Where applicable, rotate Locking Wheel to lock Bus Coupler

Bus Terminal Installation: 2.  To add a bus terminal, insert unit onto right side of Bus Coupler using the tongue and groove at the top and bottom of the unit, pressing gently until it snaps onto the DIN rail.

1

A proper connection cannot be made by sliding the units together on the DIN rail. When correctly installed, no significant gap can be seen between the attached units. Bus connection is made through the six slide contacts located on the upper right side of the units. Add up to 64 bus terminals per Bus Coupler, including a bus end terminal.

Align tab with molded guide

Wiring Connections Wire connection is made through a spring clamp style terminal. This terminal is designed for a single-conductor solid or stranded wire. Wire connection is made by firmly pushing the screwdriver into the screwdriver slot, inserting the wire into the wire slot and removing the screwdriver, locking the wire into position.

Wiring Specifications

S Screwdriver S Slot Wire Slot

Removing Bus Coupler and Bus Terminals

Connection Type

Spring Clamp Terminals

Wire Gauge/Wire Cross Section*

28-14 AWG / 0.08 - 2.5 mm2

Screwdriver Width

2.5 mm (0.10) such as our TW-SD-MSL-2

Wire Stripping Length

8mm

* For Thermocouple terminals, a thermocouple extension wire is recommended

Where applicable, rotate Locking Wheel to unlock Bus Coupler

A locking mechanism prevents individual units from being pulled off. For bus terminal removal, pull the orange DIN rail release tab firmly to unlatch the unit from the rail. If attached to other terminal units, slide unit forward until released. For Bus Couplers with locking wheels, release the DIN rail locking wheel, then pull firmly on DIN rail release tab.

Firmly pull DIN Rail Release Tab to unlatch unit from rail.

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-19

For the latest prices, please check AutomationDirect.com.

Installation Considerations Terminal Dimensions and Spacing Requirements

1.4” 35mm min

Use the following diagrams to make sure the Protos X system can be installed in your application. Protos X terminals require 35mm DIN rail for mounting; there are no orientation restrictions.

0.8” 20mm min 0.8” 20mm min

1.4” 35mm min

To ensure proper airflow for cooling purposes, units should be spaced, at a minimum, as shown. It is also important to check the Protos X dimensions against the conditions required for your application.

1.4” 35mm min

1.4” 35mm min

See the Enclosures section for an enclosure that may be suitable for your application

PX-TCP2

PX-TCP1 / X MOD PX-MOD

PX PX-903 903

PX-902

Standard Terminal

Ethernet TCP/IP COM

1 2 3 4

ERROR WDG

Us GNDs G

100 mm [3.94”] 4”]

I/I/O /O RUN I/I/O /O ERR

5

1

5

Up

2

6

2

6

GNDp

3

7

3

7

4

8

4

8

TM

DIP

1 2 3 4 5 6 7 8

PE PE

PE PPEE

.PE

1 2

ON

Universal Field I/O

100 mm [3.94”]

ON

1 2 3 4 5 6 7 8 9 10 ON

TM

TCP2 PX-TCP2

1

+ +

+ +

51 mm m [2.01”]]

tFED-20

24V 0V

24VV 00V

44 m mm m [1.73”] 3”]

PX-TCP1 PX TCP11

PX-903

24 5 mm 24.5 [.96”] [ 96 96”]]

PX-902 P X-90 02 0 2

27.5 mm [.96”] [.96 ]

12 mm [.47”]

68.8 mm [2.71”]

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Installation Considerations Terminal Types

Protos X Five Basic Terminal Typ TM

TYPE 1

TYPE 2

I/O Bus contacts

I/O Bus contacts

Terminal power bus contact Terminal power bus contact

1

5

2

6

3

7

4

8

TYPE 3

T Terminal p power bus pass b th h through

Terminal power bus contact

Terminal T power p bus pass b through th h

Terminal power bus contact Terminal PE bus contact

Type 1: This terminal passes the terminal power bus from the preceding terminal to the next terminal and therefore it must be mounted to a preceding terminal that passes bus power.

1

5

2

6

3

7

4

8

I/O Bus contacts

Terminal power bus pass through Terminal power bus pass through Terminal PE bus pass through

Type 2: This terminal passes the terminal power bus and PE from the preceding terminal to the next terminal and therefore it must be preceded by a terminal that passes both terminal power bus and PE.

TYPE 4

I/O Bus contacts

1

5

1

5

2

6

2

6

3

7

4

8

3

7

4

8

Note, bus contacts do not exist on this module

Note, bus and pass through contacts do not exist on this module

Type 3: This terminal does not pass the terminal power bus or PE and can be preceded by any terminal, however it will interrupt the terminal power bus and PE.

Five Basic Terminal Types

PX-970 P PX X-970

TYPE 3

I/O Bus contacts

Terminal power bus pass through Terminal power bus pass through Terminal PE bus pass through

passes the nd PE from the o the next termimust be precedpasses both nd PE.

TYPE 4

TYPE 5

I/O Bus contacts

I/O Bus contacts

1

5

1

5

2

6

2

6

3

7

4

8

3

7

4

8

Note, bus contacts do not exist on this module

Note, bus and pass through contacts do not exist on this module

Type 3: This terminal does not pass the terminal power bus or PE and can be preceded by any terminal, however it will interrupt the terminal power bus and PE.

PX-970 P PX X-970

I/O Bus contacts

Terminal power bus supply Terminal power bus supply

Terminal power bus supply

Type 4: This terminal requires external voltage connection and supplies the terminal power bus to terminals located to its right. The terminals to its right must support the same power bus of 120/230 VAC or 24VDC. This terminal will not pass terminal power or PE from any preceding terminals.

www.automationdirect.com/fieldIO

Note, bus and pass through contacts do not exist on this module

Type 5: This terminal is used to separate the terminal power bus and PE from other terminals and can mounted next to any terminal.

Universal Field I/O

Terminal power bus suppl

Terminal power bus suppl

Type 4: This terminal requires external voltage connection and supplies the terminal power bus to terminals located to its right. The terminals to its right must support the same power bus of 120/230 VAC or 24VDC. This terminal will not pass terminal power or PE from any preceding terminals.

Protos XTM is a trademark of Automationdirect.com Incorporated

E2

Terminal power bus suppl

tFED-21

For the latest prices, please check AutomationDirect.com.

Bus End/Expansion Terminals PX-901 $13.00 Bus End Terminal

PX-901 Terminal Specifications

PX-901 General Specifications

Current Consumption None (from I/O Bus) Electrical Isolation

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/Orientation Restrictions Vibration

500Vms (I/O bus/signal voltage)

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 50g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in)

Shock Noise Immunity Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

PX-901

The PX-901 (type 3) Bus End Terminal is installed at the end of a terminal assembly and is required for proper I/O Bus communication.

PX-902 $55.00 Bus Expansion End Terminal

PX-902 Terminal Specifications

Electrical Isolation

500Vms (I/O bus/field potential)

Heat Dissipation Status Indicators Number of Expansion Coupler Terminals Supported Configuration Maximum Distance Between Each Expansion Coupler Connection Type

1W max None

Recommended Cable Placement

tFED-22

Universal Field I/O

I/O Bus power (approx. 6V)

Current Consumption 70mA (from I/O Bus)

The PX-902 (type 3) Bus Expansion End Terminal enables expansion of terminal assemblies. The PX-902 is installed at the end of a PX-MOD or PX-TCP1 assembly and connects the I/O Bus to a PX-903 Bus Expansion Coupler Terminal via the RJ45 port. No configuration is required.

Yes No No UL/cUL File No. E157382, CE

* T o obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

Power Source

PX-902

Yes

31 max. (using PX-903) Automatic 16.5 ft. (5m) Ethernet, RJ45 Shielded, Twisted Pair, Cat5e Used only with Bus Coupler, replaces a PX-901 End Terminal

PX-902 General Specifications Operating Temp Storage Temp Relative Humidity Environment Air Mounting/Orientation Restrictions Vibration Shock Noise Immunity Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27 conforms to EN 61000-6-2 IP20 146g 27.5 mm x 100mm x 68.8 mm (1.08 in x 3.94 in x 2.71 in) Yes

Yes No No UL/cUL File No. E157382, CE

* T o obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Bus Expansion Terminals PX-903 $86.00 Bus Expansion Coupler Terminal

PX-903 Terminal Specifications

Bus Power

Bus 24V

5

1

Power

IN 6

2

I/O Bus 7

3

1

5

2

6

3

7

4

8

Bus 0V

+ 24V

Terminal Input Power

0V

OUT 9

4

PE

03 PX-9

The PX-903 (type 4) Bus Expansion Coupler Terminal enables expansion of terminal assemblies. The PX-903 is installed at the beginning of an expansion terminal assembly and connects to a PX-902 Bus Expansion End Terminal or other PX-903 terminals. Use of the PX-902 and PX-903 allows expansion of up to 31 PX-903 couplers in a group. Communication is through the RJ45 ports. No configuration is required. Modbus Coupler

PX-902 Bus Expansion Terminal End Terminal

1 2 3 4

Us GNDs

1

5

1

5

1

5

1

5

1

5

1

5

1

5

1

5

1

5

1

5

1

5

2

6

2

6

2

6

2

6

2

6

2

6

2

6

2

6

2

6

2

6

2

6

3

7

3

7

3

7

3

7

3

7

3

7

3

7

3

7

3

7

3

7

3

7

4

8

4

8

4

8

4

8

4

8

4

8

4

8

4

8

4

8

4

8

4

8

+ + Up

PE PEE

TM

DIP

1 2 3 4 5 6 7 8

ON GNDp

.PE

1 2

ON

PX-TCP11

PX-144 4 PX-144 4 PX-144 4 PX-144 4 PX-144 4 PX-144 4 PX-144 4 PX-144 4 PX-144 4 PX-144 PX X-144 PX-144 PX-144 4 P PX-902 X-902

24VDC (-15%/+20%) Supply Power for I/O Bus Current Consumption 200mA Max, 70mA + (total I/O bus current) / 4 (from I/O Bus) 10A max Recommended Fuse 400mA max I/O Bus Current Supply 2.5 x continuous current Starting Current Number of Bus Terminals 64 Supported Supply for Terminal Power Bus 24 VAC/VDC Maximum Terminal Power Bus 10A Current Number of Terminal Power Bus 3 (+24 VAC/VDC, 0V, PE) Contacts 500Vms (I/O bus/field potential) Electrical Isolation 1W max Heat Dissipation 2 Power LEDs Status Indicators Number of Expansion Couplers in 31 max a Terminal Group Automatic Configuration Maximum Distance Between 16.5 ft. (5m) Each Expansion Coupler Ethernet, 2 x RJ45 Connection Type Shielded, Twisted Pair, Cat5e Recommended Cable

Termination Resistor Switch

PX-903 General Specifications Operating Temp Storage Temp Relative Humidity Environment Air Mounting/Orientation Restrictions Vibration Shock Noise Immunity Protection Class Weight Dimensions (WxHxD)

Termination T i ti Resistor Switch S witch

NEXT

Cat5e STP cable 16.5 ft. (5m) max. length per segment

PX-903 Bus Expansion C Co Coupler

1

5

1

5

1

5

1

5

1

5

1

5

1

5

1

5

1

5

1

5

1

5

1

5

1

5

2

6

2

6

2

6

2

6

2

6

2

6

2

6

2

6

2

6

2

6

2

6

2

6

2

6

3

7

3

7

3

7

3

7

3

7

3

7

3

7

3

7

3

7

3

7

3

7

3

7

3

7

4

8

4

8

4

8

4

8

4

8

4

8

4

8

4

8

4

8

4

8

4

8

4

8

4

8

PX-903 P PX X-903

PX-903 Bus Expansion Coupler

PX-901 Bus End Terminal

1

5

1

5

1

5

1

5

1

5

1

5

1

5

1

5

1

5

1

5

1

5

1

5

1

5

2

6

2

6

2

6

2

6

2

6

2

6

2

6

2

6

2

6

2

6

2

6

2

6

2

6

3

7

3

7

3

7

3

7

3

7

3

7

3

7

3

7

3

7

3

7

3

7

3

7

3

7

8

4

8

4

8

4

8

4

8

4

8

4

8

4

8

4

8

4

8

4

8

4

8

4

8

4

PX-903

Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27 conforms to EN 61000-6-2 IP20 146g 24.5 mm x 100mm x 68.8 mm (0.96 in x 3.94 in x 2.71 in ) Yes (Supply) Yes (Supply) Yes (Supply) Yes (Supply) CE

* T o obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

PX-901 X-901 PX-144 PX 4 PX-144 4 PX-144 4 PX-144 4 PX-144 4 PX-144 4 PX-144 4 PX-144 4 PX-144 4 PX-144 X-144 X 144 4 PX PX-144 144 4 P

Termination on Resistor Switch

LAST

PX-901 Bus End T Te erminal erminal i l Terminal

Dip Switch, set to Last for last coupler in expansion group, otherwise set to Next

Bus Expansion Connection LED Status LED Green I/O Bus In Red I/O Bus In

LED ON I/O Bus is transferring data I/O Bus fault

PX-901 X-901 PX-144 4 PX-144 4 PX-144 4 PX-144 4 PX-144 4 PX-144 4 PX-144 4 PX-144 4 PX-144 4 PX-144 X-144 X 144 4 PX PX-144 144 4 P

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-23

For the latest prices, please check AutomationDirect.com.

Power Feed Terminals PX-940 $18.00 Power Feed Terminal, 24VDC

PX-940 Terminal Specifications

LED Power

1

5

2

6

3

7

Supply Power to Terminal Maximum Current Number of Power Contacts Current Consumption (from I/O Bus) Electrical Isolation Heat Dissipation Status Indicators

24VDC 10A 3 (+24VDC, 0V, PE) None 500Vms (I/O bus/signal voltage) 1W max 1 Power LED



PX-940

The PX-940 (type 4) Power Feed Terminal allows adding or changing power voltage sources within a terminal assembly. Terminals mounted to the right of the PX-940 receive 24VDC through the terminal input connections.

PX-970 $24.00 Power Feed Terminal, 120-230 VAC LED Power

5

2

6

3

7

4

8

PX-970 Terminal Specifications

120–230V N PE

The PX-970 (type 4) Power Feed Terminal allows adding or changing power voltage sources within a terminal assembly. Terminals mounted to the right of the PX-970 receive 120-230 VAC through the terminal input connections. Universal Field I/O

35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 50g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes

Yes Yes (Supply) Yes (Supply) UL/cUL File No. E157382, CE

120-230 VAC 10A 3 (120-230 VAC, 0V, PE) None 500Vms (I/O bus/signal voltage) 1W max 1 Power LED

PX-970 General Specifications Operating Temp Storage Temp Relative Humidity Environment Air Mounting/Orientation Restrictions Vibration Shock Noise Immunity Protection Class Weight Dimensions (WxHxD)

120–230 VAC Supply

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted

* T o obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

Supply Power to Terminal Maximum Current Number of Power Contacts Current Consumption (from I/O Bus) Electrical Isolation Heat Dissipation Status Indicators

PX-970

tFED-24

Protection Class Weight Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

+

PE

8

1

Noise Immunity

Dimensions (WxHxD)

24VDC Supply

4

PX-940 General Specifications Operating Temp Storage Temp Relative Humidity Environment Air Mounting/Orientation Restrictions Vibration Shock

Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 50g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes

Yes Yes (Supply) Yes (Supply) UL/cUL File No. E157382, CE

* T o obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Power Distribution/Separation Terminals PX-949 $26.00 Power Distribution Terminal, 24VDC

PX-949 Terminal Specifications Nominal Voltage Maximum Current Number of Power Contacts Connection Voltage

PX-949

≤ 60VDC 10A

(8) 24V and (8) 0V 24VDC

Current Consumption None (from I/O Bus) +24V 9

+24V

2

10

+24V

3

11

1

4

12

5

13

+24V +24V +24V

6

14

+24V

7

15

+24V

8

16

1

9

2

10

3

11

4 5

12 13

6

14

7

15

8

16

0V 0V 0V

Electrical Isolation

500Vms (I/O bus/signal voltage)

Heat Dissipation

1W max

0V 0V 0V 0V 0V

The PX-949 (type 1) Power Distribution Terminal provides eight 24VDC and eight 0V connections powered by the terminal power bus.

PX-908 $17.00 Power Separation Terminal

PX-949 General Specifications Operating Temp Storage Temp Relative Humidity Environment Air Mounting/Orientation Restrictions Vibration Shock Noise Immunity Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

Dimensions (WxHxD)

www.automationdirect.com/fieldIO

conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 60g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes

No Yes No UL/cUL File No. E157382, CE

PX-908 General Specifications Operating Temp Storage Temp Relative Humidity Environment Air Mounting/Orientation Restrictions Vibration Shock Protection Class Weight

The PX-908 (type 5) Power Separation Terminal provides interruption of power along the terminal power bus while passing I/O bus data. It is easily identified by the orange cover.

35mm DIN rail/None

* T o obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

Noise Immunity

PXP X-90 908 8

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted

Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 50g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes

Yes No No UL/cUL File No. E157382, CE

* T o obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

Universal Field I/O

tFED-25

For the latest prices, please check AutomationDirect.com.

Discrete Input Terminals PX-144

$34.00

General Specifications

Four-point, 24VDC Discrete Input Terminal The PX-144 (type 1) DC Input Terminal provides four electrically isolated 24VDC sinking inputs with LED status. For use with 3-wire and 2-wire sensors.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

LED Input 1

LED Input 2

LED Input 3

LED Input 4

Input 1

1

5

+24VDC 2

6

3

4

7

Input 3

1

5

2

6

3

7

4

8

Input 2 +24VDC 3Wire

0V Input 4

8

PX-144

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power

IP20

Passes PE Bus

No

55g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes, DC only

No

Terminal Specifications Inputs Per Terminal Input Type Input Data Bytes Used Input Power Source Current Consumption (from Terminal Power Bus) Operating Voltage Rating Peak Voltage Rating ON Voltage Level OFF Voltage Level Minimum ON Current Maximum OFF Current Current Consumption (from I/O Bus) Electrical Isolation Heat Dissipation OFF to ON Response ON to OFF Response Status Indicators

4 Sinking 1/2 byte (4 bits) 24VDC provided via terminal power bus 5mA typical 24VDC (-15%/+20%) 30VDC 15 to 30 VDC -3 to +5 VDC 50mA 100mA 5mA typical 500Vms (I/O bus/field potential) 1W max 3ms 3ms 4, indicates input is ON

Yes

Agency Approvals* UL/cUL File No. E157382, CE *To obtain the most current agency approval information,

see the Agency Approval Checklist section on the specific part number’s web page.

PX-148

$55.00

General Specifications

Eight-point, 24VDC Discrete Input Terminal The PX-148 (type 1) DC Input Terminal provides eight electrically isolated 24VDC sinking inputs with LED status.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

Signal LED

Signal LED

2 4 6 8

1 3 5 7

Input 1 Input 3 Input 5 Input 7

1

5

2

6

3

7

4

8

Input 2 Input 4 Input 6 Input 8

24 VDC Power Supply

+ – Connect power supply common (–) to same common as terminal power bus

Protection Class Weight Dimensions (WxHxD)

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 55g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in)

Adjacent Mounting on Bus Terminals Yes, DC only with Power Contact Adjacent Mounting on Bus Terminals No without Power Contact Passes Terminal Yes Bus Power

Terminal Specifications Inputs Per Terminal Input Type Input Data Bytes Used Input Power Source Current Consumption (from Terminal Power Bus) Operating Voltage Rating Peak Voltage Rating ON Voltage Level OFF Voltage Level Minimum ON Current Maximum OFF Current Current Consumption (from I/O Bus) Electrical Isolation Heat Dissipation OFF to ON Response ON to OFF Response Status Indicators

8 Sinking 1 byte Requires external 24VDC power source 2mA + load, typical 24VDC (-15%/+20%) 30VDC 15 to 30 VDC -3 to +5 VDC 2mA 1.5 mA 5mA typical 500Vms (I/O bus/field potential) 1W max 3ms 3ms 8, indicates input is ON

No Passes PE Bus Agency Approvals* UL/cUL File No. E157382, CE

PX-148

*To obtain the most current agency approval information,

see the Agency Approval Checklist section on the specific part number’s web page.

tFED-26

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Discrete Input Terminals PX-149

$95.00

General Specifications Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration

Sixteen-point, 24VDC Discrete Input Terminal The PX-149 (type 1) DC Input Terminal provides sixteen electrically isolated 24VDC sinking inputs with LED status.

Shock Noise Immunity

PX-149 1

Input LED 1 3

10

3

4

11 12

4 5

5

6

13

6

7

14 15 16

7 8 1

9 10 11 2 13 14 15 16

2

9

2

Input LED

Input 1 Input 2

9

2

10

3

11

4

12

5

13

6

14

7

15

8

16

Input 3 Input 4 Input 5 Input 6 Input 7 Input 8

8

1

9

2

10

3

11

4 5

12 13

6

14

7

15

8

16

24 VDC Power Supply +

Input 9



Input 10 Input 11

Connect power supply common (–) to same common as terminal power bus

Input 12 Input 13 Input 14 Input 15 Input 16

Protection Class Weight Dimensions (WxHxD)

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing

Input Power Source Current Consumption 35mm DIN rail/None (from Terminal Power Bus) Operating Voltage Rating conforms to EN 60068-2-6 Peak Voltage Rating conforms to EN 60068-2-27/ ON Voltage Level EN 60068-2-29 OFF Voltage Level conforms to EN 61000-6-2/ EN61000-6-4 Minimum ON Current Maximum OFF Current IP20 Current Consumption 60g (from I/O Bus) No corrosive gases permitted

12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in)

Adjacent Mounting on Bus Terminals Yes, DC only with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

Terminal Specifications Inputs Per Terminal Input Type Input Data Bytes Used

Electrical Isolation Heat Dissipation OFF to ON Response ON to OFF Response Status Indicators

16 Sinking 2 bytes Requires external 24VDC power source NA 24VDC (-15%/+20%) 30VDC 11 to 30 VDC -3 to +5 VDC 2mA 40mA 20mA typical 500Vms (I/O bus/field potential) 1W max 3ms 3ms 16, indicates input is ON

No

Yes No UL/cUL File No. E157382, CE

*To obtain the most current agency approval information,

see the Agency Approval Checklist section on the specific part number’s web page.

PX-172-1

$36.00

General Specifications

Two-point, 120-230 VAC Discrete Input Terminal The PX-172-1 (type 2) DC Input Terminal provides two electrically isolated 120-230 VAC inputs with LED status. For use with 4-wire, 3-wire and 2-wire devices.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

LED Input 2

LED Input 1

Input 1 120230 VAC 3Wire

0V PE

1 2

5 6

3

7

4

8

Input 2 120230 VAC 0V

4Wire

PE

Note: Terminal PX-908 is recommended to isolate terminal power or use PX-970 to supply and isolate power.

PX-172-1

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing

Terminal Specifications Inputs Per Terminal Input Type Input Data Bytes Used

2 NA 1/4 byte (2 bits)

Input Power Source

Requires external 120-230 VAC power source. PX-908 terminal recommended to provide power to the terminal power bus.

No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 60g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes, AC only

Current Consumption (from Terminal Power Bus) Operating Voltage Rating Peak Voltage Rating ON Voltage Level OFF Voltage Level Minimum ON Current Maximum OFF Current Current Consumption (from I/O Bus) Electrical Isolation

No

Yes

Heat Dissipation OFF to ON Response ON to OFF Response Status Indicators

6mA typical 120 to 230 VAC 260VAC 79 to 260 VAC 0 to 40 VAC 250mA 500mA 3mA typical 500Vms (I/O bus/field potential) 1W max 10ms 10ms 2, indicates input is ON

Yes UL/cUL File No. E157382, CE

*To obtain the most current agency approval information,

see the Agency Approval Checklist section on the specific part number’s web page.

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-27

For the latest prices, please check AutomationDirect.com.

Discrete Input Terminals PX-172-2

$36.00

General Specifications

Two-point, 120 VAC/VDC Discrete Input Terminal The PX-172-2 (type 2) DC Input Terminal provides two electrically isolated 120 VAC/VDC inputs with LED status. For use with 4-wire, 3-wire and 2-wire devices.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

LED Input 2

LED Input 1

Input 1 120 VAC/ VDC 3Wire

0V PE

1

5

2

6

3

7

4

8

Input 2 120 VAC/ VDC 0V

4Wire

PE

Note: Terminal PX-908 is recommended to isolate terminal power or use PX-970 to supply and isolate power.

PX-172

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing

Terminal Specifications Inputs Per Terminal Input Type Input Data Bytes Used

2 NA 1/4 byte (2 bits)

Input Power Source

Requires external 120 VAC/VDC power source. PX-908 terminal recommended to provide power to the terminal power bus.

No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power

IP20

Passes PE Bus

Yes

60g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes, 120 VAC/VDC only

No

Yes

Current Consumption (from Terminal Power Bus) Operating Voltage Rating Peak Voltage Rating ON Voltage Level OFF Voltage Level Minimum ON Current Maximum OFF Current Current Consumption (from I/O Bus) Electrical Isolation Heat Dissipation OFF to ON Response ON to OFF Response Status Indicators

6mA typical 120 VAC/VDC 140 VAC/VDC 80 to 140 VAC/VDC 0 to 40 VAC/VDC 250mA 500mA 3mA typical 500Vms (I/O bus/field potential) 1W max 10ms 10ms 2, indicates input is ON

Agency Approvals* UL/cUL File No. E157382, CE *To obtain the most current agency approval information,

see the Agency Approval Checklist section on the specific part number’s web page.

tFED-28

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Discrete Output Terminals PX-244-1

$51.00

General Specifications

Four-point, 0.5 A, 24VDC Discrete Output Terminal The PX-244-1 (type 1) DC Output Terminal provides four 24VDC 0.5 A short-circuit protected sourcing outputs with LED status. For use with 3-wire and 2-wire devices.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

LED Output 1

LED Output 2

LED Output 3

LED Output 4

Output 1

L

1 2

0V Output 3

5 6

3

7

4

8

Output 2 + 24VDC 0V

3Wire

Output 4

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 60g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes, DC only

No

Yes

Terminal Specifications Outputs Per Terminal Commons Per Terminal Output Type Output Data Bytes Used Output Power Source Current Consumption (from Load Voltage) Operating Voltage Maximum Load Current On Voltage Drop

30mA typical 24VDC ( -15%/+20%) 0.5 A per channel (Short-Circuit Protected) 0.4 VDC @ 0.5 A

Maximum Leakage Current 300mA Maximum Inrush Current Maximum Short-Circuit Voltage Load Type Current Consumption (from I/O Bus) Reverse Voltage Protection Electrical Isolation

Heat Dissipation OFF to ON Response UL/cUL File No. E157382, CE ON to OFF Response Status Indicators *To obtain the most current agency approval information,

PX-244-1

4 2 Sourcing 1/2 byte (4 bits) 24VDC provided via terminal power bus

No

1.5 A 35V Resistive, inductive, lamp 9mA typical No 500Vms (I/O bus/field potential) 1W max 100ms max 20ms max 4, indicates output is ON

see the Agency Approval Checklist section on the specific part number’s web page.

PX-244-2

$61.00

General Specifications

Four-point, 2A, 24VDC Discrete Output Terminal The PX-244-2 (type 1) DC Output Terminal provides four 24VDC 2A short-circuit protected sourcing outputs with LED status.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

LED Output 1

LED Output 2

LED Output 3

LED Output 4

Output 1 0V 0V Output 3

PX- 244-2

1

5

2

6

3

7

4

8

Output 2 0V

L

0V Output 4

L

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 60g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes, DC only

No

Terminal Specifications Outputs Per Terminal Commons Per Terminal Output Type Output Data Bytes Used Output Power Source Current Consumption (from Load Voltage) Operating Voltage Maximum Load Current On Voltage Drop

No UL/cUL File No. E157382, CE

*To obtain the most current agency approval information,

30mA typical 24VDC ( -15%/+20%) 2A per channel (Short-Circuit Protected) 0.14 VDC @ 2A

Maximum Leakage Current 60mA Maximum Inrush Current Maximum Short-Circuit Voltage Load Type Current Consumption (from I/O Bus) Reverse Voltage Protection Electrical Isolation

Yes

4 4 Sourcing 1/2 byte (4 bits) 24VDC provided via terminal power bus

Heat Dissipation OFF to ON Response

35A 52V Resistive, inductive, lamp 9mA typical Yes 500Vms (I/O bus/field potential) 1W max 160ms typ, 300ms max

ON to OFF Response

10ms min, 80ms max

Status Indicators

4, indicates output is ON

see the Agency Approval Checklist section on the specific part number’s web page.

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-29

For the latest prices, please check AutomationDirect.com.

Discrete Output Terminals PX-248

$63.00

General Specifications

Eight-point, 0.5 A, 24VDC Discrete Output Terminal The PX-248 (type 1) DC Output Terminal provides eight 24VDC 0.5 A short-circuit protected sourcing outputs with LED status.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

Signal LED

Signal LED

2 4 6 8

1 3 5 7

Output 1 Output 3 Output 5 Output 7

1

5

2

6

3

7

4

8

(–)

Output 2 Output 4

L L

Output 6 Output 8

Connect common (–) to same common as terminal power bus

PX-248

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN61000-6-4 IP20 70g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes, DC only

Terminal Specifications Outputs Per Terminal Commons Per Terminal Output Type Output Data Bytes Used Output Power Source Current Consumption (from Load Voltage) Operating Voltage Maximum Load Current

24VDC ( -15%/+20%) 0.5 A per channel (Short-Circuit Protected) 0.4 VDC @ 0.5 A

Maximum Inrush Current

1.5 A

Max. Short-Circuit Voltage Load Type Current Consumption (from I/O Bus) Reverse Voltage Protection

35V

Electrical Isolation

Yes

Heat Dissipation OFF to ON Response ON to OFF Response Status Indicators

UL/cUL File No. E157382, CE

60mA + load typical

On Voltage Drop Maximum Leakage Current 300mA

No

No

8 Field wired Sourcing 1 byte 24VDC provided via terminal power bus

Resistive, inductive, lamp 18mA typical Yes 500Vms (I/O bus/field potential) 1W max 100ms max 20ms max 8, indicates output is ON

*To obtain the most current agency approval information,

see the Agency Approval Checklist section on the specific part number’s web page.

PX-249

$89.00

General Specifications

Sixteen-point, 0.5 A, 24VDC Discrete Output Terminal The PX-249 (type 1) DC Output Terminal provides sixteen 24VDC 0.5 A short-circuit protected sinking outputs with LED status.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock

PX-2 249 49 1 2 3 4 5 6 7 8

Output LED 1

2

9 10 11 12 13 14 1 15 1 16 1

3

4

5

6

7

Output 1 Output 2

9

2

10

3

11

4

12

5

13

Output 3 Output 4 Output 5 Output 6 Output 7 Output 8

6

14

7

15

8

16

Noise Immunity

Output LED

8

1

9

2

10

3

11

4 5

12 13

6

14

7

15

8

16

9 10 11 12 13 14 15 16

Output 9 Output 10

Output 11 Output 12 Output 13 Output 14 Output 15 Output 16

(+)

L L If external power supply, connect common (–) to same common as terminal power bus

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None

Terminal Specifications Outputs Per Terminal Commons Per Terminal Output Type Output Data Bytes Used Output Power Source

Current Consumption (from Load Voltage) Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ Operating Voltage EN 60068-2-29 Maximum Load Current Conforms to EN 61000-6-2/ EN61000-6-4 IP20

On Voltage Drop

16 Field wired Sinking 2 bytes Requires external 24VDC power source 35mA + load typical 24VDC ( -15%/+20%) 0.5 A per channel (Short-Circuit Protected) 0.12 VDC @ 0.5 A

70g

Maximum Leakage Current 75mA

12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in)

Maximum Inrush Current Max. Short-Circuit Voltage Load Type Current Consumption (from I/O Bus) Reverse Voltage Protection

Yes, DC only

No

Electrical Isolation

Heat Dissipation OFF to ON Response No ON to OFF Response UL/cUL File No. E157382, CE Status Indicators Yes

3.5 A 36V Resistive, inductive, lamp 45mA typical Yes 500Vms (I/O bus/field potential) 1W max 0.45 ms 3.3 ms 16, indicates output is ON

*To obtain the most current agency approval information,

see the Agency Approval Checklist section on the specific part number’s web page.

tFED-30

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Discrete Relay Output Terminals PX-272-1

$68.00

General Specifications

Two-point, 0-230 VAC/VDC Discrete Solid State Relay Output Terminal The PX-272-1 (type 2) Solid State Relay Output Terminal provides two 230 VAC/ VDC 0.3 A outputs with LED status. For use with 4-wire, 3-wire and 2-wire devices.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

LED Output 2

LED Output 1

Output 1

L

230 VAC / VDC 3Wire

0V PE

PX X-27 -272-1 2-1 -

1 2

5 6

3

7

4

8

Output 2 230 VAC / VDC

0V

4Wire

PE

Note: Terminal PX-908 is recommended to isolate terminal power or use PX-970 to supply and isolate power.

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C)

Terminal Specifications

13 to 185 °F (-25 to 85 °C)

Outputs Per Terminal Commons Per Terminal

5% to 95%, non-condensing

Output Type

No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4

Output Data Bytes Used Output Power Source

Current Consumption (ON resistance max (from Terminal Power Bus) 100mV) + load Operating Voltage

0 to 230 VAC/VDC (DC 100Hz)

Maximum Load Current

0.3 A per point

IP20

Maximum Leakage Current < 1mA (off state)

55g

Maximum Inrush Current

0.5 A for 20s, 1.5 A for 100ms

Contact Resistance

2.1 V, typical 3.2 V, max.

Surge Voltage Protection Load Type Current Consumption (from I/O Bus)

From 400VAC

12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes, 230 VAC/VDC only

No

Electrical Isolation Yes

Heat Dissipation Switch-ON Time Yes Switch-OFF Time UL/cUL File No. E157382, CE Switch-ON Delay *To obtain the most current agency approval information, Switch-OFF Delay see the Agency Approval Checklist section on the specific Status Indicators part number’s web page.

www.automationdirect.com/fieldIO

2 2 Solid State Relay (DC sourcing only) 1/4 byte (2 bits) 230 VAC/VDC provided via terminal power bus

Universal Field I/O

Resistive, inductive 10mA 500Vms (I/O bus/field potential) 2500VDC (1 min.) 1W max 4 to 6 ms 0.05 to 0.1 ms 320ms 6.2 ms 2, indicates output is ON

tFED-31

For the latest prices, please check AutomationDirect.com.

Discrete Relay Output Terminals PX-272-2

$53.00

General Specifications

Two-point, 230VAC / 30VDC Discrete Relay Output Terminal The PX-272-2 (type 2) Relay Output Terminal provides two 230VAC / 30VDC 5A outputs with LED status. For use with 4-wire, 3-wire and 2-wire devices.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

LED Output 1

Output 1 1

5

L 2

3Wire

6

3

4

230VAC or 30VDC

7

8

0V PE

LED Output 2

1 2

5 6

3

7

4

8

Output 2 230VAC or 30VDC

0V

4Wire

PE

Note: Terminal PX-908 is recommended to isolate terminal power or use PX-970 to supply and isolate power.

PX- 272-2

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

Terminal Specifications

13 to 185 °F (-25 to 85 °C)

Outputs Per Terminal Commons Per Terminal

5% to 95%, non-condensing

Output Type

32 to 131 °F (0 to 55 °C)

No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 85g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes, 230VAC or 30VDC only

No

Output Data Bytes Used Output Power Source Current Consumption (from Terminal Power Bus) Operating Voltage Maximum Load Current Maximum Load Current with Resistive Load Maximum Load Current with Inductive Load, coswⱷ=0.4, L/R=7ms Minimum Load (approximate) Load Type

Yes UL/cUL File No. E157382, CE

*To obtain the most current agency approval information,

see the Agency Approval Checklist section on the specific part number’s web page.

(ON resistance typ 2.4 V, max 3.2 V) + load 230VAC/30VDC 5A per point AC: 5A @230VAC, 1250VA DC: 5A @ 30VDC, 150W AC: 2A @230VAC DC: 2A @ 30VDC 10mA @ 5VDC (as supplied) 100mA @ 20VDC (after approx. ≥ 100mA has been switched at least once) Resistive, inductive, lamp

Reaction Time: 10ms max. Release Time; 4ms max. Bounce Time: 5ms max.

Switching Times Yes

2 2 SPST Relay, normally open contact (DC sourcing only) 1/4 byte (2 bits) 230VAC/30VDC provided via terminal power bus

Contact Material Current Consumption (from I/O Bus) Electrical Isolation Heat Dissipation Switching Frequency at Maximum Contact Load Maximum Contact Resistance Minimum Insulation Resistance

Silver Cadmium Oxide 80mA 500Vms (I/O bus/field potential) 2500VDC (1 min.) 1W max 10/minute < 30mV 100MV @ 500VDC

switching Mechanical Operating Life 20,000,000 operations

Electrical Operating Life

Minimum 100,000 switching operations with resistive loads

Test Voltage Between Open 750V for 1 minute Contacts 2, indicates output is ON Status Indicators

tFED-32

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Discrete Combination Terminal PX-549

$98.00

General Specifications

Eight inputs/Eight outputs, 24VDC Discrete Input/Output Terminal The PX-549 (type 1) DC Input/Output Terminal provides eight 24VDC inputs and eight 24VDC 0.5 A outputs with reverse polarity protection and LED status.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

Input LED

PX-549

Output LED

1

9 10 11 12 13 14 15 16

2

1 2

3

4

9 10 11 12

3 4 5 6 7 8

5

6

7

13 14 15 16

1

Input 1 Input 2 Input 3

1

2

Input 4 Input 5

2

3

3

Input 6

4

4

5

Input 7 Input 8

5

6

6

7

7

8

8

8

1

9

2

10

3

11

4 5

12 13

6

14

7

15

8

16

Output 1 Output 2

Output 3 Output 4 Output 5 Output 6 Output 7 Output 8

24VDC Power Supply

+ – Connect power supply common (–) to same common as terminal power bus

L L

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None

Terminal Specifications Inputs/Outputs Per Terminal

8 sinking inputs / 8 sourcing outputs

Data Bytes Used Input/Output Power Source

1 byte (inputs) / 1 byte (outputs) Requires external 24VDC power source

Operating Voltage Rating

24VDC (-15%/+20%)

conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4

Current Consumption 25mA typical (from I/O Bus) Current Consumption 15mA + load typical (from Terminal Power Bus)

IP20

Electrical Isolation

60g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes, DC only

Heat Dissipation Status Indicators

Input Specifications

Peak Voltage Rating ON Voltage Level OFF Voltage Level No Minimum ON Current Minimum OFF Current Yes Current Consumption (from I/O Bus) No Agency Approvals* UL/cUL File No. E157382, CE OFF to ON Response ON to OFF Response

*To obtain the most current agency approval information,

see the Agency Approval Checklist section on the specific part number’s web page.

500Vms (I/O bus/field potential) 1W max 8 input and 8 output, indicates ON 30VDC 15 to 30 VDC -3 to +5 VDC 2mA 40mA 3mA typical 3ms 3ms

Output Specifications Max. Load Current per Output On Voltage Drop Maximum Leakage Current

0.5 A (Short-Circuit Protected)

Maximum Inrush Current

2A

0.14 VDC @ 2A 5mA

Maximum Short-Circuit 45V Voltage Resistive, inductive, lamp Load Type Reverse Voltage Protection Yes

www.automationdirect.com/fieldIO

OFF to ON Response

50ms

ON to OFF Response

75ms

Universal Field I/O

tFED-33

For the latest prices, please check AutomationDirect.com.

Analog Current Input Terminals PX-302

$216.00

General Specifications

Two-channel, 4-20 mA Analog Input Terminal The PX-302 (type 3) Analog Input Terminal provides two electrically isolated 4-20 mA inputs with 12-bit resolution and Run and Error LED status.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity Protection Class Weight Dimensions (WxHxD)

PX-302

1

24VDC Supply

5

LED Run 1

LED Run 2

LED Error 1

LED Error 2 +In1 +In2

3- + + wire – –

1

+

3

Ground reference optional 7

4



24VDC Supply

6

GND GND

6

3

+

–In1 –In2

2

2

– 2+ wire

5

7

Ground reference optional

Shld Shld

4

8

+In1

8

+ –

PX-302

–In1

2

24VDC Supply

13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 70g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in)

Adjacent Mounting on Bus Terminals Yes with Power Contact Adjacent Mounting on Bus Terminals Yes without Power Contact Passes Terminal No Bus Power

Terminal Specifications Number of Channels Input Ranges Resolution Input Type Data Format

2 4 to 20 mA 12 bits External ground reference Decimal: 0-32767

Data Bytes Consumed Input Power Source Current Consumption (from Terminal Power Bus) Input Impedance Absolute Max Ratings Conversion Time Full Scale Calibration Error Current Consumption (from I/O Bus) Electrical Isolation Heat Dissipation Status Indicators

PX-MOD: 4 bytes input PX-TCP1/TCP2: 8 bytes in/ 8 bytes out (not used) Loop power external NA 50V internal resistor 35VDC surge Approx. 2ms ± 0.3% of full scale 60mA 500Vms (I/O bus/field potential) 1W max 4, see LED Status chart

LED Status LED

LED ON

LED OFF Watchdog-timer overflow

Green LED: RUN Normal Operation if no data transmitted No Passes PE Bus within WD set time. Agency Approvals* UL/cUL File No. E157382, CE Red LED: Broken wire or *To obtain the most current agency approval information, current is > 21.5 mA Normal Operation see the Agency Approval Checklist section on the specific ERROR

1

4wire

32 to 131 °F (0 to 55 °C)

Shld

4

part number’s web page.

PX-304

General Specifications

$191.00

Four-channel, 4-20 mA Analog Input Terminal The PX-304 (type 1) Analog Input Terminal provides four electrically isolated 4-20 mA inputs with 12-bit resolution and Run and Error LED status.

Run 2 Error 2 Run 4 Error 4

Run 1 Error 1 Run 3 Error 3 –

1

3- + wire +

5

2

4wire 3

7

4

1

In2

5



2

6

In3

In4

3

7

+

Connect power supply common (–) to same common as terminal power bus



+ +24V +24V

24VDC Supply – +

6

In1

4

8

+24V +24V PX-304

8

PX-304

2wire

Terminate shields at signal source

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration

32 to 131 °F (0 to 55 °C)

Shock

conforms to EN 60068-2-27/ EN 60068-2-29

Noise Immunity

conforms to EN 61000-6-2/ EN61000-6-4

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

IP20

13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6

75g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes, DC only

No

Yes No UL/cUL File No. E157382, CE

*To obtain the most current agency approval information,

see the Agency Approval Checklist section on the specific part number’s web page.

tFED-34

Universal Field I/O

Terminal Specifications Number of Channels Input Ranges Resolution Input Type Data Format

4 4 to 20 mA 12 bits Single-ended Decimal: 0-32767

Data Bytes Consumed Input Power Source Current Consumption (from Terminal Power Bus) Input Impedance Absolute Max Ratings Conversion Time Full Scale Calibration Error Current Consumption (from I/O Bus) Electrical Isolation Heat Dissipation Status Indicators

PX-MOD: 8 bytes input PX-TCP1/TCP2: 16 bytes in/ 16 bytes out (not used) 24VDC provided via terminal power bus Load < 85V 30VDC surge Approx. 2ms ± 0.3% of full scale 85mA 500Vms (I/O bus/field potential) 1W max 8, see LED Status chart

LED Status LED

LED ON

Green LED: RUN Normal Operation Red LED: ERROR

LED OFF Watchdog-timer overflow if no data transmitted within WD set time.

Broken wire or current is > 20.8 mA Normal Operation

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Analog Current Input Terminals PX-308

$244.00

General Specifications

Eight-channel, 4-20 mA Analog Input Terminal The PX-308 (type 1) Analog Input Terminal provides eight electrically isolated 4-20 mA inputs with 12-bit resolution and Error LED status.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

Run Run Run Run

Run Run Run Run

1 3 5 7 In1

1

1

5

In2



5

In3

In4

In5

In6

2

2

2 4 6 8

+

Terminate shield at signal source

6

6

3

3

7

In7

4

7

In8

8

PX-308 4

8

PX-308

2Wire

+



24VDC Supply Connect power supply common to same common (–) as terminal power bus

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 75g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes, DC only

No

Yes

Terminal Specifications Number of Channels Input Ranges Resolution Input Type Data Format Data Bytes Consumed Input Power Source Current Consumption (from Terminal Power Bus) Input Impedance Absolute Max Ratings Conversion Time Full Scale Calibration Error Current Consumption (from I/O Bus)

8 4 to 20 mA 12 bits Single-ended Decimal: 0-32767 PX-MOD: 16 bytes input PX-TCP1/TCP2: 32 bytes in/32 bytes out (not used) Requires external 24VDC power source Load < 85V 30VDC surge Approx. 4ms ± 0.3% of full scale 105mA

Heat Dissipation

500Vms (I/O bus/field potential) 1W max

Status Indicators

8, Red: Error, broken wire or current is > 20.8 mA

Electrical Isolation

No UL/cUL File No. E157382, CE

*To obtain the most current agency approval information,

see the Agency Approval Checklist section on the specific part number’s web page.

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-35

For the latest prices, please check AutomationDirect.com.

Analog Voltage Input Terminals PX-312

$216.00

General Specifications

Two-channel, -10 to +10 VDC Analog Input Terminal The PX-312 (type 3) Analog Input Terminal provides two electrically isolated -10 to +10 VDC inputs with 12-bit resolution and LED status.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

PX-312

LED Run 1

24VDC Supply

3- + + wire – –

+

LED Run 2

+In1 +In2

1

+

5

+

–In1 –In2

2



6

3

7

Ground reference optional

Shld Shld

4

8

Connect power supply common (–) to same common as terminal power bus

+In1

+ –

PX-312

4wire

+

24VDC Supply

GND GND Ground reference optional

2wire

1

–In1

$191.00

The PX-314 (type 1) Analog Input Terminal provides four electrically isolated -10 to +10 VDC inputs with 12-bit resolution and LED status.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

1

Run 1

Run 2

Run 3

Run 4



5

24VDC Supply – + 2

In1

1

In2

+

5

+ GND GND

2

6

3

4

7

+

In3

In4

– Connect power supply common (–) to same common as terminal power bus

3

7

4

8

8

PX-314

tFED-36



+

24VDC Supply GND GND PX-314

2wire

Terminate shield at signal source

6

4wire

5% to 95%, non-condensing

Resolution

No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 70g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes

2 -10 to +10 VDC 12 bits (11 bits between 0 to 10 VDC) External ground reference

Input Type Data Format

Decimal: -32767 to +32767

Data Bytes Consumed Input Power Source Current Consumption (from Terminal Power Bus) Input Impedance Absolute Max Ratings Conversion Time Full Scale Calibration Error Current Consumption (from I/O Bus) Electrical Isolation

Yes

Heat Dissipation Status Indicators

PX-MOD: 4 bytes input PX-TCP1/TCP2: 8 bytes in/ 8 bytes out (not used) Voltage source external NA > 200kV 35VDC surge Approx. 2ms ± 0.3% of full scale 65mA 500Vms (I/O bus/field potential) 1W max 2, indicates I/O Bus activity

No No UL/cUL File No. E157382, CE

General Specifications

Four-channel, -10 to +10 VDC Analog Input Terminal

+ 3- + wire

13 to 185 °F (-25 to 85 °C)

see the Agency Approval Checklist section on the specific part number’s web page.

Shld

4

PX-314

Terminal Specifications Number of Channels Input Ranges

*To obtain the most current agency approval information,

2

24VDC Supply

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C)

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C)

Terminal Specifications

13 to 185 °F (-25 to 85 °C)

Number of Channels Input Ranges

5% to 95%, non-condensing

Resolution

No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 75g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes, DC only

Input Type Data Format

Decimal: -32767 to +32767

Data Bytes Consumed Input Power Source Current Consumption (from Terminal Power Bus) Input Impedance Absolute Max Ratings Conversion Time Full Scale Calibration Error Current Consumption (from I/O Bus) Electrical Isolation

No

4 -10 to +10 VDC 12 bits (11 bits between 0 to 10 VDC) Single-ended

Heat Dissipation Status Indicators

PX-MOD: 8 bytes input PX-TCP1/TCP2: 16 bytes in/ 16 bytes out (not used) Voltage source external NA > 130kV 30VDC surge Approx. 2ms ± 0.3% of full scale 100mA 500Vms (I/O bus/field potential) 1W max 4, indicates I/O Bus activity

Yes No UL/cUL File No. E157382, CE

*To obtain the most current agency approval information,

see the Agency Approval Checklist section on the specific part number’s web page.

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Analog Voltage Input Terminals PX-318

$244.00

General Specifications

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration

Eight-channel, -10 to +10 VDC Analog Input Terminal The PX-318 (type 1) Analog Input Terminal provides eight electrically isolated -10 to +10 VDC inputs with 12-bit resolution and LED status.

Shock Noise Immunity

Run Run Run Run 1

3- + wire + –

5

2

24VDC Supply – +

6

Run Run Run Run

1 3 5 7 In1

In2

In3

In4

In5

In6

1 2 3

3

7

In7

4

5 6 7

In8

8

PX-318 4

8

PX-318

2 4 6 8 24VDC Supply + –

+ +

2wire

Terminate shields at signal source Connect power supply common (–) to same common as terminal power bus

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C)

Terminal Specifications

13 to 185 °F (-25 to 85 °C)

Number of Channels Input Ranges

5% to 95%, non-condensing

Resolution

No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 75g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes, DC only

No

Yes

Input Type Data Format Data Bytes Consumed

8 -10 to +10 VDC 12 bits (11 bits between 0 to 10 VDC) Single-ended Decimal: -32767 to +32767 PX-MOD: 16 bytes input PX-TCP1/TCP2: 32 bytes in/ 32 bytes out (not used) Voltage source external

Input Power Source Current Consumption NA (from Terminal Pwr Bus) > 130kV Input Impedance Absolute Max Ratings 30VDC surge Approx. 4ms Conversion Time Full Scale Calibration ± 0.3% of full scale Error Current Consumption 140mA (from I/O Bus) Heat Dissipation

500Vms (I/O bus/field potential) 1W max

Status Indicators

8, indicates I/O Bus activity

Electrical Isolation

No UL/cUL File No. E157382, CE

*To obtain the most current agency approval information,

see the Agency Approval Checklist section on the specific part number’s web page.

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-37

For the latest prices, please check AutomationDirect.com.

RTD Input Terminals PX-322-1

$233.00

General Specifications

Two-channel RTD Input Terminal The PX-322-1 (type 3) RTD Input Terminal provides two PT100 RTD inputs with full linearization and LED status.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

PX-322-1

3Wire RTD

LED Run 1

LED Run 2

LED Error 1

LED Error 2 +R1 +R2

+

1



+

5



RL1 RL2

2

Connect two wires to one side of a 2-wire RTD

6

–R1 –R2

3

2Wire RTD

7

Shld Shld

4

8

PX-322-1

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

0 to 55 °C -25 to 85 °C 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 70g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes

Yes

No No UL/cUL File No. E157382, CE

*To obtain the most current agency approval information,

Terminal Specifications Number of Channels

2

Range

-200 to 850 °C

Resolution

0.1 °C per digit

Input Type

PT100 PX-MOD: 4 bytes input

Data Bytes Consumed PX-TCP1/TCP2: 8 bytes in/ Connection Method Power Supply Conversion Time Measuring Current Linearity Error Current Consumption (from I/O Bus) Electrical Isolation Heat Dissipation Status Indicators

8 bytes out (not used) 2-wire or 3-wire (3-wire default) Via I/O Bus Approx. 250ms 5mA typical < ± 1°C 60mA 500Vms (I/O bus/field potential) 1W max 4, see LED Status chart

LED Status LED

LED ON

LED OFF

Green LED: Normal Operation RUN

Watchdog-timer overflow if no data transmitted within WD set time.

Red LED: ERROR

No Error

Sensor fault, e.g. broken wire

see the Agency Approval Checklist section on the specific part number’s web page.

PX-324-1

$268.00

General Specifications

Four-channel RTD Input Terminal The PX-324-1 (type 3) RTD Input Terminal provides four PT100 RTD inputs with full linearization and LED status.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

PX-324-1

LED Error 1

LED Error 2

LED Error 3

LED Error 4 +R1 +R2

1

5

+ –

– R1 – R2

2

6

+R3 +R4

3

7

– R3 – R4

4

8

PX-324-1

2Wire RTD

Terminate shields at signal source

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

0 to 55 °C -25 to 85 °C 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 70g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes

Yes

Terminal Specifications Number of Channels

4

Range

-200 to 850 °C

Resolution

0.1 °C per digit

Input Type

PT100 PX-MOD: 8 bytes input

Data Bytes Consumed PX-TCP1/TCP2: 16 bytes in/ Connection Method Power Supply Conversion Time Measuring Current Linearity Error Current Consumption (from I/O Bus) Electrical Isolation Heat Dissipation Status Indicators

16 bytes out (not used) 2-wire Via I/O Bus Approx. 250ms 5mA typical < ± 1°C 60mA 500Vms (I/O bus/field potential) 1W max 4, Red: sensor fault

No No UL/cUL File No. E157382, CE

*To obtain the most current agency approval information,

see the Agency Approval Checklist section on the specific part number’s web page.

tFED-38

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Thermocouple Input Terminals PX-332-J

$240.00

General Specifications

Two-channel Type J Thermocouple Input Terminal The PX-332-J (type 3) Thermocouple Input Terminal provides two Type J thermocouple inputs with full linearization, cold-junction compensation, and LED status.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

PX-332-J

LED Run 1

LED Run 2

LED Error 1

LED Error 2 +TC1 +TC2

1

5

+ –

–TC2 –TC2

2

6

3

7

For grounded thermocouples differential should not exceed ±2V

Shld Shld

4

8

Thermocouple extension wire recommended

Protection Class Weight Dimensions (WxHxD)

Number of Channels

2

-25 to 85 °C

Range

-100 to 1200 °C

Resolution

0.1 °C per digit

Input Type

Type J thermocouple

5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 70g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in)

Adjacent Mounting on Bus Terminals Yes with Power Contact Adjacent Mounting on Bus Terminals Yes without Power Contact Passes Terminal No Bus Power No Passes PE Bus Agency Approvals* UL/cUL File No. E157382, CE

PX-332-J

*To obtain the most current agency approval information,

see the Agency Approval Checklist section on the specific part number’s web page.

PX-334-J

$277.00

The PX-334-J (type 3) Thermocouple Input Terminal provides four Type J thermocouple inputs with full linearization, cold-junction compensation, and LED status.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

LED Error 1

LED Error 2

LED Error 1

LED Error 2 +TC1 +TC2

1

5

5

2

6

6

+TC3 +TC4

3

3

7

7

–TC3 –TC4

4

8

PX-334-J 4

+ –

–TC2 –TC2 2

8

PX-334-J

PX-MOD: 4 bytes input

Data Bytes Consumed PX-TCP1/TCP2: 8 bytes in/

Terminate shield at signal source

For grounded thermocouples differential should not exceed ±2V Thermocouple extension wire recommended

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

0 to 55 °C -25 to 85 °C 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4

8 bytes out (not used) 2-wire (Thermocouple extension wire recommended)

Connection Method Power Supply Conversion Time Measuring Current

Via I/O Bus

Linearity Error

± 0.5% (relative to full scale value)

Current Consumption (from I/O Bus)

65mA

Approx. 250ms 5mA typical

500Vms (I/O bus/field potential)

Electrical Isolation Heat Dissipation Status Indicators

1W max 4, see LED Status chart

LED Status LED

LED ON

LED OFF

Green LED: RUN

Watchdog-timer overflow Normal Operation if no data transmitted within WD set time.

Red LED: ERROR

Sensor fault, e.g. broken wire

General Specifications

Four-channel Type J Thermocouple Input Terminal

1

Terminal Specifications

0 to 55 °C

No Error

Terminal Specifications Number of Channels 4 Range

-100 to 1200 °C

Resolution

0.1 °C per digit

Input Type

Type J thermocouple PX-MOD: 8 bytes input

Data Bytes Consumed PX-TCP1/TCP2: 16 bytes in/ Connection Method

16 bytes out (not used) 2-wire (Thermocouple extension wire recommended) Via I/O Bus

70g

Power Supply Conversion Time Measuring Current

12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in)

Linearity Error

± 0.5% (relative to full scale value)

Yes

Current Consumption 75mA (from I/O Bus)

IP20

Yes

Approx. 250ms 5mA typical

Electrical Isolation

500Vms (I/O bus/field potential)

Heat Dissipation

1W max

Status Indicators

4, Red: sensor fault/broken wire

No No UL/cUL File No. E157382, CE

*To obtain the most current agency approval information,

see the Agency Approval Checklist section on the specific part number’s web page.

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-39

For the latest prices, please check AutomationDirect.com.

Thermocouple Input Terminals PX-332-K

$240.00

General Specifications

Two-channel Type K Thermocouple Input Terminal The PX-332-K (type 3) Thermocouple Input Terminal provides two Type K thermocouple inputs with full linearization, cold-junction compensation, and LED status.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

PX-332-K

LED Run 1

LED Run 2

LED Error 1

LED Error 2 +TC1 +TC2

1

5

+ –

–TC2 –TC2

2

6

3

7

For grounded thermocouples differential should not exceed ±2V

Shld Shld

4

8

Thermocouple extension wire recommended

Protection Class Weight Dimensions (WxHxD)

Number of Channels

2

-25 to 85 °C

Range

-100 to 1370 °C

Resolution

0.1 °C per digit

Input Type

Type K thermocouple

5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 70g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in)

Adjacent Mounting on Bus Terminals Yes with Power Contact Adjacent Mounting on Bus Terminals Yes without Power Contact Passes Terminal No Bus Power No Passes PE Bus Agency Approvals* UL/cUL File No. E157382, CE

PX-332-K

*To obtain the most current agency approval information,

see the Agency Approval Checklist section on the specific part number’s web page.

PX-334-K

$277.00

The PX-334-K (type 3) Thermocouple Input Terminal provides four Type K thermocouple inputs with full linearization, cold-junction compensation, and LED status.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

1

LED Error 1

LED Error 2

LED Error 1

LED Error 2 1

5

5

2

2

6

6

+TC3 +TC4

3

3

7

7

–TC3 –TC4

4

8

PX-334-K 4

+ –

–TC2 –TC2

8

PX-334-K

PX-MOD: 4 bytes input

Data Bytes Consumed PX-TCP1/TCP2: 8 bytes in/ Connection Method

Terminate shield at signal source

For grounded thermocouples differential should not exceed ±2V Thermocouple extension wire recommended

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

0 to 55 °C -25 to 85 °C 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4

8 bytes out (not used) 2-wire (Thermocouple extension wire recommended)

Power Supply Conversion Time Measuring Current

Via I/O Bus

Linearity Error

± 0.5% (relative to full scale value)

Current Consumption (from I/O Bus)

65mA

Electrical Isolation Heat Dissipation Status Indicators

Approx. 250ms 5mA typical

500Vms (I/O bus/field potential) 1W max 4, see LED Status chart

LED Status LED

LED ON

LED OFF

Green LED: Normal Operation RUN

Watchdog-timer overflow if no data transmitted within WD set time.

Red LED: ERROR

No Error

General Specifications

Four-channel Type K Thermocouple Input Terminal

+TC1 +TC2

Terminal Specifications

0 to 55 °C

Sensor fault, e.g. broken wire

Terminal Specifications Number of Channels 4 Range

-100 to 1370 °C

Resolution

0.1 °C per digit

Input Type

Type K thermocouple PX-MOD: 8 bytes input

Data Bytes Consumed PX-TCP1/TCP2: 16 bytes in/ 16 bytes out (not used)

Connection Method

2-wire (Thermocouple extension wire recommended) Via I/O Bus

70g

Power Supply Conversion Time Measuring Current

12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in)

Linearity Error

± 0.5% (relative to full scale value)

Yes

Current Consumption 75mA (from I/O Bus)

IP20

Yes

Approx. 250ms 5mA typical

Electrical Isolation

500Vms (I/O bus/field potential)

Heat Dissipation

1W max

Status Indicators

4, Red: sensor fault/broken wire

No No UL/cUL File No. E157382, CE

*To obtain the most current agency approval information,

see the Agency Approval Checklist section on the specific part number’s web page.

tFED-40

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Analog Current Output Terminals PX-402

$204.00

General Specifications

Two-channel, 4-20 mA Analog Output Terminal The PX-402 (type 1) Analog Output Terminal provides two electrically isolated, 4-20 mA outputs with 12-bit resolution and Run LED status.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

LED Run 1

LED Run 2

+O1 +O2 1

1

5

+

5

Load

– +24V +24V

2

2

6

0V

0V

6

3

3

7

7

Shld Shld

4

4

8

8

PX-402

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 80g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes, DC only

No

Four-channel, 4-20 mA Analog Output Terminal The PX-404 (type 1) Analog Output Terminal provides four electrically isolated, 4-20 mA outputs with 12-bit resolution and Run LED status.

Shock Noise Immunity Run 1

Run 2

Run 3

Run 4 Out 1 Out 2

1

5

2

1

5

0V

0V

2

6

6

Out 3 Out 4 3

4

3

7

4

8

7

8

PX-404

0V 0V PX-404

+ Load – Terminate shield at signal source

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

Single-ended Decimal: 0-32767 PX-MOD: 4 bytes output PX-TCP1/TCP2: 8 bytes out/ 8 bytes in (not used)

Source Load

< 500V (short-circuit protected)

Conversion Time

Approx. 1.5 ms ± 0.5 LSB linearity error, ± 0.5 LSB offset error ± 0.1% of the full scale value

Accuracy I/O Bus current Consumption (5V) Heat Dissipation Status Indicators

50mA + load

60mA 500Vms (I/O Bus/signal voltage) 1W max 2, see LED Status chart

LED Status

No

LED

UL/cUL File No. E157382, CE

Green LED: Normal Operation RUN

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 80g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes, DC only

LED ON

No

Data Bytes Consumed

Watchdog-timer overflow if no data transmitted within WD set time.

4 4 to 20 mA 12 bit Single-ended Decimal: 0-32767 PX-MOD: 8 bytes output PX-TCP1/TCP2: 16 bytes out/ 16 bytes in (not used)

Output Power Source Current Consumption (from Load Voltage)

24VDC via terminal power bus

Source Load

< 350V (short-circuit protected)

Conversion Time

Approx. 4ms ± 0.5 LSB linearity error, ± 0.5 LSB offset error ± 0.1% of the full scale value

Accuracy I/O Bus current Consumption (5V) Heat Dissipation Status Indicators

Yes

60mA + load

20mA 500Vms (I/O Bus/signal voltage) 1W max 4, see LED Status chart

LED Status

No

LED

UL/cUL File No. E157382, CE

Green LED: Normal Operation RUN

see the Agency Approval Checklist section on the specific part number’s web page.

LED OFF

Terminal Specifications Number of Channels Output Ranges Resolution Output Type Data Format

Electrical Isolation

*To obtain the most current agency approval information,

www.automationdirect.com/fieldIO

12 bit

24VDC via terminal power bus

General Specifications Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration

2 4 to 20 mA

Output Power Source Current Consumption (from Load Voltage)

Yes

see the Agency Approval Checklist section on the specific part number’s web page.

$191.00

Data Bytes Consumed

Electrical Isolation

*To obtain the most current agency approval information,

PX-404

Terminal Specifications Number of Channels Output Ranges Resolution Output Type Data Format

LED ON

Universal Field I/O

LED OFF Watchdog-timer overflow if no data transmitted within WD set time.

tFED-41

For the latest prices, please check AutomationDirect.com.

Analog Current Output Terminals PX-408

$244.00

General Specifications

Eight-channel, 4-20 mA Analog Output Terminal The PX-408 (type 1) Analog Output Terminal provides eight electrically isolated, 4-20 mA outputs with 12-bit resolution and Run LED status.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

Run Run Run Run

Run Run Run Run

1 3 5 7 Out 1 Out 2

1

1

5

5

Out 3 Out 4

2

2

6

6

Out 5 Out 6

3

3

7

Out 7 Out 8

4

4

8

7 8

PX-408

PX-408

2 4 6 8

+ Load – Terminate shield at signal source

– Connect

to same common as terminal power bus

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 80g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes, DC only

No

No UL/cUL File No. E157382, CE

*To obtain the most current agency approval information,

Universal Field I/O

8 4 to 20 mA 12 bit Single-ended Decimal: 0-32767 PX-MOD: 16 bytes output

Data Bytes Consumed

PX-TCP1/TCP2: 32 bytes out/ 32 bytes in (not used)

Output Power Source Current Consumption (from Load Voltage)

24VDC via terminal power bus

Source Load

< 150V (short-circuit protected)

Conversion Time

Approx. 8ms ± 0.5 LSB linearity error, ± 0.5 LSB offset error ± 0.1% of the full scale value

Accuracy I/O Bus current Consumption (5V) Heat Dissipation Status Indicators

50mA + load

25mA

Electrical Isolation

Yes

see the Agency Approval Checklist section on the specific part number’s web page.

tFED-42

Terminal Specifications Number of Channels Output Ranges Resolution Output Type Data Format

500Vms (I/O Bus/signal voltage) 1W max 8, see LED Status chart

LED Status LED

LED ON

Green LED: Normal Operation RUN

LED OFF Watchdog error if no data transmitted within WD set time.

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Analog Voltage Output Terminals PX-412

$204.00

General Specifications

Two-channel, 0 to 10 VDC Analog Output Terminal The PX-412 (type 3) Analog Output Terminal provides two electrically isolated, 0 to 10 VDC outputs with 12-bit resolution, common ground potential, and Run LED status.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

PX-412

LED Run 1

LED Run 2

+O1 +O2 1

1

5

+

5

Load –

2 2

6

6

GND GND

3

3

7

7

Shld Shld

4

4

8

8

PX-412

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 85g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes

Yes

Four-channel, 0 to 10 VDC Analog Output Terminal The PX-414 (type 3) Analog Output Terminal provides four electrically isolated, 0 to 10 VDC outputs with 12-bit resolution, common ground potential, and Run LED status.

Shock Noise Immunity

Run 1

Run 2

Run 3

Run 4 O1

1

1

5

5

0V

0V

O3

O4

2

2

O2

6

6

3

3

7

4

4

7

8

PX-414

8

0V 0V PX-414

+ Load – Terminate shield at signal source

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

Single-ended Decimal: 0-32767 PX-MOD: 4 bytes output PX-TCP1/TCP2: 8 bytes out/ 8 bytes in (not used) 24VDC via terminal power bus

Source Load

> 5kV (short-circuit protected)

Conversion Time

Approx. 1.5 ms ± 0.5 LSB linearity error, ± 0.5 LSB offset error ± 0.1% of the full scale value

Accuracy I/O Bus current Consumption (5V) Electrical Isolation Heat Dissipation Status Indicators

50mA + load

75mA 500Vms (I/O Bus/signal voltage) 1W max 2, see LED Status chart

LED Status LED

UL/cUL File No. E157382, CE

Green LED: Normal Operation RUN

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 85g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes, DC only

LED ON

Yes

Data Bytes Consumed

UL/cUL File No. E157382, CE

see the Agency Approval Checklist section on the specific part number’s web page.

Watchdog error if no data transmitted within WD set time.

4 0 to 10 VDC 12 bit Single-ended Decimal: 0-32767 PX-MOD: 8 bytes output PX-TCP1/TCP2: 16 bytes out/ 16 bytes in (not used)

Output Power Source Current Consumption (from Load Voltage)

24VDC via terminal power bus

Source Load

> 5kV (short-circuit protected)

Conversion Time

Approx. 1.5 ms ± 0.5 LSB linearity error, ± 0.5 LSB offset error ± 0.1% of the full scale value

Accuracy I/O Bus current Consumption (5V) Heat Dissipation Status Indicators

No No

LED OFF

Terminal Specifications Number of Channels Output Ranges Resolution Output Type Data Format

Electrical Isolation

*To obtain the most current agency approval information,

www.automationdirect.com/fieldIO

12 bit

Output Power Source Current Consumption (from Load Voltage)

General Specifications Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration

2 0 to 10 VDC

No

*To obtain the most current agency approval information,

$174.00

Data Bytes Consumed

No

see the Agency Approval Checklist section on the specific part number’s web page.

PX-414

Terminal Specifications Number of Channels Output Ranges Resolution Output Type Data Format

50mA + load

75mA 500Vms (I/O Bus/signal voltage) 1W max 2, see LED Status chart

LED Status LED

LED ON

Green LED: Normal Operation RUN Universal Field I/O

LED OFF Watchdog error if no data transmitted within WD set time.

tFED-43

For the latest prices, please check AutomationDirect.com.

Analog Voltage Output Terminals PX-418

$244.00

General Specifications

Eight-channel, -10 to +10 VDC Analog Output Terminal The PX-418 (type 1) Analog Output Terminal provides eight electrically isolated, -10 to +10 VDC outputs with 12-bit resolution, common ground potential, and Run LED status.

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity

Run Run Run Run

Run Run Run Run

1 3 5 7 Out 1 Out 2

1

1

5

5

Out 3 Out 4

2

2

6

6

Out 5 Out 6

3

3

7

Out 7 Out 8

4

4

8

7 8

PX-418

PX-418

2 4 6 8

+ Load – Terminate shield at signal source

– Connect

to same common as terminal power bus

Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C) 13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None conforms to EN 60068-2-6 conforms to EN 60068-2-27/ EN 60068-2-29 conforms to EN 61000-6-2/ EN61000-6-4 IP20 85g 12mm x 100mm x 68.8 mm (0.47 in x 3.94 in x 2.71 in) Yes, DC only

No

Output Power Source Current Consumption (from Load Voltage)

No UL/cUL File No. E157382, CE

8 -10 to +10 VDC 12 bit Single-ended Decimal: 0-32767 PX-MOD: 16 bytes output PX-TCP1/TCP2: 32 bytes out/ 32 bytes in (not used) 24VDC via terminal power bus 20mA

Source Load

> 5kV (short-circuit protected)

Conversion Time

Approx. 8ms ± 0.5 LSB linearity error, ± 0.5 LSB offset error ± 0.1% of the full scale value

Accuracy I/O Bus current Consumption (5V) Heat Dissipation Status Indicators

Yes

*To obtain the most current agency approval information,

Universal Field I/O

Data Bytes Consumed

Electrical Isolation

see the Agency Approval Checklist section on the specific part number’s web page.

tFED-44

Terminal Specifications Number of Channels Output Ranges Resolution Output Type Data Format

20mA 500Vms (I/O Bus/signal voltage) 1W max 8, see LED Status chart

LED Status LED

LED ON

Green LED: Normal Operation RUN

LED OFF Watchdog error if no data transmitted within WD set time.

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

The Terminator Field I/O System: Great Features at an AutomationDirect Price PC-based Controls Terminator I/O What is it? Terminator I/O is one of the most practical distributed Field I/O systems you can buy. It combines the I/O points with their field terminations into a modular package to save panel space and money. With Terminator I/O, you can distribute I/O nodes close to field devices for faster and more efficient wiring and troubleshooting. Terminator I/O was custom-designed for us by Koyo (the same people who designed the original GE Series One PLC), a trusted name in control technology since 1983.

What’s it got? • Network interface modules supporting Ethernet, PROFIBUSTM, DeviceNetTM, and Modbus; some adapters include an on-board RS-232 serial port. • Discrete and analog I/O modules with modular terminal bases. • Configuration flexibility by plugging together a network interface module with up to 16 I/O modules. Use local expansion for large I/O drops. No more confining I/O bases. • AC or DC power supplies. For high power systems, combine multiple supplies on a single I/O set. • Horizontal or vertical DIN-rail mounting

Ethernet DeviceNet TM Modbus® PROFIBUS TM Starting at $184.00

What can I do with it? • Use Terminator I/O as robust PLC remote I/O with triple stack terminal bases and hot-swap I/O modules. • Add Terminator I/O to Allen-Bradley, Siemens, Modicon or GE systems for 1/2 to 1/3 the price of their comparable field I/O products. • Use Terminator I/O as low-cost field I/O for your SCADA, PC-based control system or WinPLC™ system.

Modular I/O

Terminator I/O allows you to connect serial devices, like an operator interface panel, along with your I/O, so there’s no need to purchase adapters or run additional wiring*. * Serial communication options available on T1H-EBC and T1K-DEVNETS only

16-module system with multiple power supplies

tFED-45

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Terminator I/O

PLC Control

Distributed Control

Terminator I/O

Terminal connectors

Terminator I/O includes specialty modules like our 16-channel RTD temperature module (T1F-16RTD) and the counter module (T1H-CTRIO)

D

RT ture a tempedrules mo

Add additional power module where needed

Output modules have replaceable fuses

L

A L O C

EXP

ANS

ION

Modules slide into the modular terminal bases. Plug together any combination of modules and power sources for your application.

ter Couondule m

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-46

For the latest prices, please check AutomationDirect.com.

It’s All Included With Terminator I/O Terminator I/O combines all the features of terminal blocks and I/O modules into one convenient package. We took the proven I/O technology of the DirectLOGIC DL205/405 PLC families and combined it with a modular terminal block base to create a practical I/O solution for any automation project.

Terminator I/O features: • Lower installed cost than conventional I/O and terminal blocks; even reduces panel space by 30% over an equivalent DL205 system with terminal blocks. • Easy troubleshooting at the device termination, with status and blown fuse indicators. • No-tools installation and removal of I/O modules • Hot-swap capability helps you get your system operating in a hurry.

tFED-47

Universal Field I/O

(

Modular I/O

+

Terminal connectors

=

Terminator I/O

)

• Triple-stack terminal blocks for three-wire devices, integrated bussed power and common terminals, plus fused outputs are all integrated into the Terminator package. • Fast to install and wire, Terminator I/O saves you time and money. Typically no need for additional terminal blocks, fuse blocks or external relays.

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Pick Your Pieces and Drop ‘em In Two sizes of terminal bases accommodate all I/O modules • Half-size bases for modules with up to 8 points for only $55.00 (T1K-08B, T1K-08B-1) • Full size bases for modules with up to 16 points for only $69.00 (T1K-16B, T1K-16B-1) • Triple-stack terminal blocks standard, easy to connect multi-wire devices • Same bases for all I/O modules AC, DC, and analog • Screw and spring clamp terminals

Network interface modules for your favorite fieldbus

• Ethernet - the “common sense network” 10/100Base-T for $267.00, DeviceNet for $195.00, Modbus for $184.00, even Profibus for $332.00 • All network modules include on-board RS-232 serial port with varied support for operator interfaces, bar code readers, printers or other serial devices (check specific network adapter specifications)

Power supplies - freedom of choice, freedom to expand

• DC power supplies for $111.00 (T1K-01DC), AC versions only $116.00 (T1K-01AC) • AC supplies include 24 VDC auxiliary supply for convenient field device wiring • Need more power for high current devices or modules? Just add another power supply before the next modules in the system!

Analog modules at a super low price per channel 8-channel I/O

16-channel I/O

Four types of 8-channel I/O Four types of 16-channel I/O Two types of combination I/O Thermocouple, Thermistor, and RTD modules

• 8-channel I/O modules starting at $290.00 • 16-channel I/O modules starting at $591.00 • 0-20mA/4-20 mA and unipolar/bipolar voltage models available • 14-channel thermocouple module only $519.00 (T1F-14THM) • 16-channel thermistor module only $000.00 (T1F-16TMST) • Hot-swap analog modules for fast system maintenance

T1H-EBC100 Ethernet

T1H-PBC PROFIBUSTM

T1K-DEVNETS DeviceNetTM

T1K-MODBUS Modbus®

Discrete I/O with the features you need • 8-point I/O modules starting at only $69.00 • 16-point I/O starting at only $119.00 • All DC input modules are sink/source jumper configurable • Diagnostic LEDs for blown fuse and 24 VDC power on applicable modules • Hot-swap capability makes troubleshooting easy

Specialty modules

• Counter module with pulse out, $311.00 (T1H-CTRIO)

Local expansion - up to two additional rows

e odul se m r to-u lever fo p” y s Ea tion -swa t c o e h j e nt “ ity enie il conv capab

8-point I/O

16-point I/O

Easy-access replaceable fuses on all discrete output modules

• Full backplane expansion through cables • Connect up to 16 modules across three total rows by plugging expansion cables from the side of one module to the side of the next. The system automatically recognizes the I/O. • Optional cable that includes 24 VDC pins maximizes your power supply capability.

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-48

For the latest prices, please check AutomationDirect.com.

You’ll terminate your current supplier after comparing these features. Our Terminator I/O

Only four I/O modules for this system

16 discrete in, 16 discrete out 8 analog in, 8 analog out

$1,556.00 A-B Flex I/O

Five full size I/O modules!

16 discrete in, 16 discrete out 8 analog in, 8 analog out

$5,092.00 GE VersaMax

16 discrete in, 16 discrete out 8 analog in, 8 analog out

$2,450.90

Opto22 Snap I/O 16 discrete in, 16 discrete out 8 analog in, 8 analog out

Where are all the terminations? Do I need extra terminal blocks?

$2,667.00

Terminator I/O is tops in its class when compared to the competition. Look at these identical 32-point discrete I/O/16-channel analog I/O systems (above), and you can clearly see that Terminator I/O uses less modules, takes up less panel space, and has more terminations to make your system design more efficient and easier to implement. With its blue translucent package, Terminator I/O not only looks good, it performs even better. You don’t have to be ugly to be industrial! *All prices are U.S. published prices. Prices and specifications may vary by dealer and configuration. Many of the vendors listed above also offer other sizes of fixed field I/O. AutomationDirect prices as of 6/5/2015. Allen-Bradley Flex I/O Product Data Catalog; Publication 1794-2.1; Allen-Bradley Flex Integra I/O Product Data Catalog; Publication 1793-2.1; prices from www. wernerelectric.com 5/25/2015 GE Fanuc VersaMax Modules, Power Supplies and Carriers; User’s Manual GFK-1504D. GE Fanuc Series 90 Micro PLC User’s Manual June 1998 GFK1065F; prices from www.automationwarehouse.com 5/25/2015. OPTO22 SNAP I/O Modules Data Sheet Form 773-990204; prices from www.opto22.com 5/25/2015.

tFED-49

Universal Field I/O

Check out these features Field I/O

AutomationDirect Terminator I/O

A-B Flex I/O and Flex Integra

GE Fanuc Versa Max

OPTO22 Snap I/O

3-Row Terminal Blocks Standard

YES

Optional on Flex I/O

NO *2-row standard

2-row only on Flex Integra

and auxiliary (3rd) sold separately and manually attached.

Number of Modules per Node

16

8

8

16

Maximum Relay Output Current

5

2A

2A

.75A

YES

YES

YES

NO

Integrated Serial ports on I/F Modules

YES

NO

NO

YES

Local Expansion

YES

YES

NO

NO

Multiple Backplane Power Supply Capability

YES

NO

YES

NO

Isolated Output Modules

AC & Relay

2-Rows

AC & Relay

1-Rows

AC & Relay

NO

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

We tried to think of everything to make your installation easier. When wiring a Terminator I/O system, you’ll see that the little extras make a big difference. Features like versatile half and full-size I/O modules, standard triple-stack terminal bases for all I/O modules, and bussed 24 VDC power through the backplane (for DC input devices) will make your installation

quicker and cleaner. Other features include an RS-232 serial port on selected network interface modules and replaceable fuses integrated into all discrete output modules. Try to find that on Allen-Bradley’s Flex I/O!

Local expansion of up to two rows (16 total modules)

Six interface choices Serial port included

ct’s

Half and full-size modules

Dire n o i t a tom

Au

Separate power supply

Fused outputs standard

24 VDC through backplane

Auxiliary 24 VDC terminals

Triple stack terminals standard

Allen-Bradley Flex I/O

®

No serial port

One size module only Local expansion of up to one row (8 total modules)

Power supply and Interface module only sold as integrated unit

Inconvenient 24 VDC jumpers

www.automationdirect.com/fieldIO

Optional three-row terminal base

Fusing requires special terminal base; only 8-point low density available

Universal Field I/O

tFED-50

For the latest prices, please check AutomationDirect.com.

Use Terminator I/O with DeviceNetTM or PROFIBUSTM and save a ton of money. Terminator I/O offers a DeviceNet slave network interface module (T1K-DEVNETS) that can connect to any DeviceNet master controller, even Allen-Bradley© PLCs! The PROFIBUS interface module (T1H-PBC) does the same for Siemens or GE PLCs. This means you can substitute any DeviceNet or PROFIBUS slave I/O station with Terminator I/O, but won’t have to change any other hardware or network cabling in your system.

We know that many of the industries you serve will specify another PLC as the master controller on DeviceNet or PROFIBUS, but may not demand a certain manufacturer’s I/O. This is where AutomationDirect and Terminator I/O can help you save money and win the bidding war on these projects. Check out the sample systems below to see how AutomationDirect can “show you the money”.

_ _

DeviceNet system example*:

A-B FlDCexIn I/O 16 pt.. 8 pt.. 8 pt.. 8 ch. 3-wire

B

A-

x Fle

DC out relay out analog in terminal bases

$3,270

I/O

Terminator I/O DC In

It’s your choice to save money-

Term



inato

r I/O

16 8 8 8

pt.. pt.. DC out pt.. relay out ch. analog in

base Triple-stack terminal

$1112

Terminator I/O DeviceNet slave network interface module, T1K-DEVNETS, is an ODVA-certified DeviceNet-compliant slave I/O interface product. See www.odva.org for more information.

PROFIBUS system example*:

_ _

rsamax GE Ve AC In 8 pt.. 8 CH.. Analog Input

out 8 pt.. isolated relay

carriers 2-row boxy style I/O

1-row auxiliary box ps style terminal stri

x ma

a

It’s your choice to save money-

GE

rs Ve

Term

inato

r I/O

$1,683

Terminator I/O AC In

16 pt.. 8 CH.. Analog Input 8 pt.. relay out

base Triple-stack terminal

$1119

Terminator I/O Profibus slave network interface module, T1H-PBC, is a PTO-certified Profibus-compliant slave I/O interface product. See www.profibus.com for more information.

tFED-51

Universal Field I/O

*All prices are U.S. published prices. AutomationDirect prices are from October 2014 Price List. Allen-Bradley Flex I/O prices from www.plccenter.com. GE Fanuc VersaMax prices from www.automationwarehouse.com.

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Just a few applications where Terminator I/O fits PLC systems Terminator I/O, with its variety of DC and AC discrete, analog, analogcombination and specialty modules, fills the need for distributed I/O in any size PLC system. An Ethernet Remote Master (H2-ERM100 and H4-ERM100) from a DL205 or DL405 series PLC, paired with an Ethernet Base Controller (T1H-EBC100) at remote I/O locations can supply you with up to a maximum of sixteen Terminator I/O nodes per Ethernet Remote Master channel. With hot-swappable modules and each node capable of handling hundreds of I/O points, Terminator I/O increases the capability of the PLC system you’re already using, at a price that won’t push the budget of your project.

Use the E-SW050U Ethernet Switch for deterministic Ethernet control for your application.

PLC systems

SCADA systems Terminator I/O can provide great low-cost I/O for your SCADA (Statistical Control and Data Acquisition) system. For example, a PC running KEPDirect Ethernet I/O OPC Server can monitor and control your distributed I/O via an Ethernet Base Controller (T1H-EBC100). Terminator I/O is also offered with DeviceNet, Modbus and Profibus interfaces. Terminator I/O’s convenient, modular terminal bases are perfect for your remote I/O locations. Terminator I/O’s slim profile and optional panel or DIN-rail mounting make it easy to install and wire the perfect combination of I/O in small junction boxes or other tight spaces close to your field devices.

SCADA Systems

PC-based control systems Terminator I/O is the clear choice for PC-based control I/O systems. Choose a network interface module and the I/O modules to meet your application’s needs. Terminator I/O is compatible with several PC-based control packages, including Think & Do Studio and Think & Do Live! flowchart-based control software. Choose Think & Do Live!, add one of our industrial monitors to your PC, and you have a PC control system that is Ethernet-ready to connect to Terminator I/O.

PC-based control systems

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-52

For the latest prices, please check AutomationDirect.com.

Terminator I/O How it works: Terminator I/O combines all the features of terminal blocks and I/O modules into one convenient package.

One of the best features of Terminator I/O is its connectivity. We offer a choice of five plug-compatible network interface modules to connect you to your choice of network.

Achieve maximum system flexibility with our DIN rail mountable Terminator I/O system. Shorten wiring runs by locating I/O near field devices. Add modules in the future without buying new bases.

Each system needs at least one AC or DC power supply, but you can add more power if you need it. And, we offer a wide variety of discrete and analog I/O modules.

Our removable I/O modules connect internally to three-tier spring clamps or screw-type terminal blocks.

Building a system from Terminator I/O components With Terminator I/O, you mount just the I/O modules you need to your DIN rail (or you can panel-mount them). You are not limited by a fixed base size. And you can choose any compatible PC, PLC or other fieldbus network master.

You’ll save the cost of separate terminal blocks (and save the labor required to wire from traditional PLC I/O to separate terminal blocks). Maybe you need fused outputs? We offer those, too!

les 6 modu Up to 1 orizontally h d te moun ically or vert

tFED-53

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Terminator I/O

Terminator I/O junction Box

d pair Twiste able c rk o netw

Terminator I/O junction box

Network master controller: PC, PLC, other.

Terminator I/O junction box

I/O module addressing Up to two rows of local expansion

Local expansion Terminator I/O systems can contain up to 16 modules per node. Each node can be divided into two rows of local expansion (1 network interface base + 2 expansion bases) to accommodate flexible panel space requirements in remote junction boxes. Terminator I/O can be mounted either horizontally or vertically.

www.automationdirect.com/fieldIO

Terminator I/O module addressing will be different depending on which network interface protocol is used. For example, DeviceNet™ and PROFIBUS™ support “word” data types for mapping analog modules. For Koyo remote I/O, only discrete (“X” inputs, “Y” outputs) data types are supported, and mapping analog modules is accomplished in blocks of 32 I/O points per channel. Each of the following I/O module specification pages includes an entry for number of I/O points (bits) per module.

Universal Field I/O

tFED-54

For the latest prices, please check AutomationDirect.com.

Dimensions and Installation It is important to understand the installation requirements for your Terminator I/O system. This will ensure that the Terminator I/O products work within their environmental and electrical limits.

See the Enclosures section for an enclosure that may be suitable for your application

Plan for safety This catalog should never be used as a replacement for the technical data sheet that comes with the products or the T1K-INST-M Installation and I/O Manual (available online at www.automationdirect.com.) The technical data sheet contains information that must be followed. The system installation should comply with all appropriate electrical codes and standards.

Unit dimensions and mounting orientation Use the following diagrams to make sure the Terminator I/O system can be installed in your application. Terminator I/O units should be mounted horizontally. To ensure proper airflow for cooling purposes, units should not be mounted upside-down. It is important to check the Terminator I/O dimensions against the conditions required for your application. For example, it is recommended to leave 2” depth for ease of access and cable clearance. However, your distance may be greater or less. Also, check the installation guidelines for the recommended cabinet clearances.

48mm (1.89in)

tFED-55

Ambient Operating Temperature

32°F to 131°F (0°C to 55°C)

Storage Temperature

-4°F to 158°F (-20°C to 70°C)

Ambient Humidity

5% to 95% (Non-condensing)

Atmosphere

No corrosive gases. The level of environmental pollution = 2 (UL 840)

Vibration Resistance

MIL STD 810C, Method 514.2

Shock Resistance

MIL STD 810C, Method 516.2

Voltage Withstand (Dielectric)

1500 VAC, 1 minute

Insulation Resistance

500 VDC, 10 Mq

Noise Immunity

NEMA ICS3-304 Impulse noise 1µs, 1000 V FCC class A RFI (144 MHz, 430 MHz 10 W, 10 cm)

Agency Approvals

UL, CE, FCC class A, NEC Class 1 Division 2

48mm (1.89in)

80mm (3.15in)

Power Supply

Terminator I/O Environmental Specifications

48mm (1.89in)

80mm (3.15in)

Network Interface Module

Universal Field I/O

89mm (3.5in)

80mm (3.15in)

Half-size I/O Module with Base

83.3mm (3.28in)

80mm (3.15in)

Full-size I/O Module with Base

System Depth

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

I/O Module Installation I/O module installation Terminator I/O modules feature separate terminal bases for easy installation.

DN-ASB-1 angled mounting bracket

1

To install I/O modules: 1. Slide the module into its terminal base (until it clicks into position)

Great for mounting in upper locations

2.  Hook upper DIN rail tabs over the top of DIN rail, and press the assembly firmly onto the DIN rail.

Great for mounting in lower locations

3.  Slide the module along the DIN rail until it engages with the adjacent module.

Optional angled support bracket raises and tilts the mounting rail for easier access and wiring. Use with 35 mm DIN rail. See the Connection Systems in this catalog for details.

2

3

Removing I/O modules is a snap Grip the locking handle, as shown, and pull gently to eject the I/O module from its base. The module will slide out for easy replacement. This procedure does not apply to network interface modules or power supplies, which have integral bases.

www.automationdirect.com/fieldIO

Hot-swappable I/O modules You can remove I/O modules under power, but exercise caution while doing so. Do not touch the terminals with your hands or any conductive material. Always remove power when possible.

Universal Field I/O

tFED-56

For the latest prices, please check AutomationDirect.com.

Power Supplies and Power Requirements Power supplies

Power requirements

The Terminator I/O product line offers two power supply options: AC or DC. The power supplies are always positioned to the left of the modules to which they supply power. Consult the system configuration examples and the power budgeting example for more information on positioning power supplies.

Module

5VDC 24VDC

Interface Modules 0

T1H-08TDS

200

0

T1F-08AD-1

75

­50*

530

0

T1K-08TD1

100

200*

T1F-08AD-2

75

50*

T1K-DEVNETS

250

45

T1K-16TD1

200

400*

T1F-16AD-1

75

50*

T1K-MODBUS

300

0

T1K-08TD2-1

200

0

T1F-16AD-2

75

50*

T1K-16TD2-1

200

0

T1F-16RTD

150

0

T1K-08ND3

35

0

AC Output Modules

T1F-16TMST

150

0

T1K-16ND3

70

0

T1K-08TA

250

0

T1F-14THM

60

70*

T1K-16TA

450

0

Analog Output Modules

T1K-08NA-1

35

0

T1K-08TAS

300

0

T1F-08DA-1

75

75*

T1K-16NA-1

70

0

Relay Output Modules

T1F-08DA-2

75

75*

350

0

T1F-16DA-1

75

150*

T1K-16TR

700

0

T1F-16DA-2

75

150*

T1K-08TRS

400

0

Combination Analog Modules

Specialty Modules

T1K-01DC $111.00

T1K-01AC $116.00

T1K-08TR

T1H-CTRIO

Input Frequency

50/60 Hz

N/A

Maximum Power

50 VA

30 W

To calculate the power budget, read the available power (current rating) from the Power Supply Specifications table and subtract the power consumed by each module to the right of the power supply. Do not include modules to the right of an additional power supply.

Voltage Withstand

1 min. @ 1500 VAC between primary, secondary and field ground

Voltage

5.25 VDC

5.25 VDC

2000 mA max

5VDC Current Rating (see current option note PWR below)

24VDC PWR

2000 mA max

Ripple

5% max.

5% max.

Voltage

24 VDC

N/A

300 mA max. current Current Rating (see option note N/A below)

Ripple

10% max.

400

0

* Use either internal or external source for 24VDC

Calculating the power budget

> 10 Mq @ 500 VDC

Analog Input Modules

300

Input Voltage Range 110/220 VAC 12/24 VDC

Insulation Resistance

5VDC 24VDC

T1H-PBC

Power supply specifications

10 A

Module

T1H-EBC100

AC Input Modules

Max. Inrush Current 20 A

5VDC 24VDC

DC Output Modules

DC Input Modules

Power Supply Specifications

Module

Adding additional power supplies

T1F-8AD4DA-1

75

60*

T1F-8AD4DA-2

75

70*

* Use either internal or external source for 24VDC

Power Budget Example Module

5VDC

24VDC

T1K-01AC

+2000 mA

+300 mA

T1H-EBC100

-300 mA

-0 mA

T1K-16ND3

-70 mA

-0 mA

T1K-16TD2

-200 mA

-0 mA

T1F-08AD-1

-75 mA

-50 mA

Remaining

+1355 mA

+250 mA

Each power supply furnishes power only to the network interface and I/O modules to its right. Inserting a second power supply closes the power loop for the power supply to the left, while also powering the modules to its right. Perform a power budget calculation for each power supply in the system.

N/A

Fuse 1 (primary), not replaceable MVSTBW MVSTBW Replacement 2.5/4-ST-5.08 2.5/6-ST-5.08 Terminal Block BK BK (Phoenix Contact) Note: 500 mA @ 24 VDC can be achieved by lowering the 5VDC from 2000 mA to 1500 mA.

This power supply powers the network interface module and This power supply powers these three I/O the next two I/O modules modules

tFED-57

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Expansion I/O Configurations T1K-05CBL-LL T1K-05CBL-LL-1* Left side to left side expansion cable

Expansion cables T1K-10CBL $42.00 T1K-10CBL-1* $55.00 Right side to left side expansion cable The T1K-10CBL(-1) connects the right side of an I/O base to the left side of the next I/O base. A maximum of two T1K-10CBL(-1) cables can be used per expansion system.

$29.25 $33.50

T1K-05CBL-RR

RETIRED

Right side to right side expansion cable is no longer available

The T1K-05CBL-LL(-1) connects the left side of an I/O base to the left side of the next I/O base. Only one T1K-05CBL-LL (-1) cable can be used per expansion system and must be used with a T1K-05CBL-RR cable. This cable cannot be connected to the left side of the network interface base.

Some of the examples below show the T1K-05CBL-RR expansion cable. This cable is no longer available. Refer to the examples if you already have these cables. If you are purchasing new cables, we recommend the T1K-10CBL(-1) cables.

The T1K-05CBL-RR connects the right side of an I/O base to the right side of the next I/O base. A maximum Cable length = 0.5m of one T1K-05CBL-RR cable can be Cable length = 1.0m used per expansion system. Note: When this cable is used, the expansion I/O assignments are from right to left (reversed). *Note: The (-1) versions of the expansion cables pass 24 VDC through on an isolated wire. (All cables pass the 5 VDC base power.) Any local expansion DC input module configured for “internal power” (current sourcing) must either have a power supply preceding it on the same base or, have a (-1) version cable pass 24 VDC from a power supply on the preceeding base.

Using two T1K-10CBL expansion cables In the system below, power supplies can be used anywhere.

Using T1K-10CBL expansion cable and T1K-05CBL-RR expansion cable Power supplies can be used anywhere in the first two bases, but not in the last expansion base.

T1K-10CBL(-1)

I/O Addressing

A power supply can be used on either base.

I/O Addressing T1K-10CBL

T1K-10CBL(-1) T1K-05CBL-RR (Retired Product)

Using T1K-05CBL-RR expansion cable and T1K-05CBL-LL expansion cable Power supplies can be used anywhere in the first and third bases, but not in the second base. Do not connect a T1K-05CBL-LL(-1) to the left side of the network interface base.

I/O Addressing

Using T1K-05CBL-RR expansion cable Power supplies can be used anywhere in the first base, but not in the second base.

I/O Addressing T1K-05CBL-RR (Retired Product)

T1K-05CBL-RR (Retired Product)

T1K-05CBL-LL

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-58

For the latest prices, please check AutomationDirect.com.

Field Device Wiring and Power Options Terminal base specifications

T1K-08B $55.00

T1K-08B-1 $55.00

Terminator I/O terminal bases are available in screw clamp and spring clamp versions for both half-size and full-size modules. Hot stamp silkscreen labeling is used for numbering I/O points, commons, and all power terminals. Screw clamp, half-size

Terminal Base Specifications Terminal Type

Screw type

Recommended 1.77-3.54 lb-in (0.2 - 0.4 Nm) Torque Wire Gauge

Solid: 25-12 AWG Stranded: 26-12 AWG

T1K-16B $69.00

Spring clamp, half-size

T1K-16B-1 $69.00

Spring clamp n/a Solid: 25-14 AWG Stranded: 26-14 AWG Screw clamp, full-size

Spring clamp, full-size

Field device wiring options Power your DC input devices from the integrated 24 VDC power supply bus. T1K-08ND3 and T1K-16ND3 DC input modules include jumpers for selecting the internal 24 VDC power supply available for 2- and 3-wire field devices. Clearly labeled triple stack terminals make it easy to wire 2- and 3-wire devices ensuring clean wiring with only one wire per termination.

2 and 3-wire DC input devices using bussed 24 VDC power

External user supplied 24 VDC power, or auxiliary 24 VDC terminals from T1K-01AC, can be easily applied directly to one end of the terminal rows and jumpered across each base in the system. This is a convenient solution for powering analog I/O and discrete DC output devices whose modules do not have direct access to the internal bussed 24 VDC. If current consumption increases, simply add additional T1K-01AC power supplies into the system.

Use externally supplied 24 VDC power or 24 VDC auxiliary power from T1K-01AC

Do not jumper modules together to create a 24 VDC bus when using the “hot swap” feature. See Note below.

Hot-swap feature The hot-swap feature allows Terminator I/O modules to be replaced while system power is on. Be careful not to touch the terminals with your hands or other conductive material to avoid the risk of personal injury or equipment damage. Always remove power if it is equally convenient to do so.

tFED-59

Universal Field I/O

Note: Before hot-swapping analog or DC output modules in a Terminator I/O system, make sure that each of the analog and DC output module’s 24 VDC and 0 VDC base terminals are wired directly to the external power supply individually. If the external 24 VDC and 0 VDC is jumpered from base to base in a daisy chain

fashion, and an analog or DC output module is removed from its base, the risk of disconnecting the external 24 VDC and 0 VDC to the subsequent I/O modules exists.

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Modbus RTU Slave T1K-MODBUS $184.00

Asynchronous communications In most applications, the Modbus master polls the slaves individually (T1K-MODBUS) to read/write each slave’s I/O. The communication between the Modbus master and slave will often be asynchronous to the master CPU scan. For this reason, applications should be limited to those that do not require the I/O points to update every master CPU scan.

OR

Any PLC or PC MODBUS RTU master

The Terminator I/O Modbus network interface module allows you to connect I/O as a slave station on a Modbus RTU network. The T1K-MODBUS can communicate with any Modbus RTU network master using high-level Modbus commands.

T1K-MODBUS slaves

DirectLOGIC Modbus communications Some of our DirectLOGIC PLCs can be used as Modbus masters, directly through a communication port on the CPU. (Consult the PLC section of this catalog for more information.)

Network configuration options You can configure a simple point-to-point network or create a multidrop network using the RS-232, RS-422/485 HD-15 Modbus port. The T1K-MODBUS has two rotary switches that can be set to designate the module’s slave address. Set the rotary switches to give each slave a unique address in a range from 1-F7 hex (1-247 decimal). The T1K-MODBUS also has an auxiliary RJ12 RS-232 serial port that can be used to configure the Modbus port with the T1K-MODBUS Setup Tool.

Specifications Modbus Port

RS-232 15 m (50 ft.): 300, 600, 1200, 2400, 4800, 9600; 19.2 K, 38.4 K baud Cable Lengths and Baud Rates RS-422/485 1000 m (3300 ft): 300, 600, 1200, 2400, 4800, 9600; 19.2 K,

38.4 K baud

Max. I/O Points per Controller

Discrete: inputs: 1024, outputs: 1024; Analog: inputs: 64 channels, outputs: 64 channels

Recommended Cable

Belden 9729 or equivalent (RS-422)

Terminal Type

15-pin female high-density (VGA style) D-sub connector

RJ12 Serial Port

RS-232; 9600/19200 baud; supports K-Sequence and ASCII (Use to configure Modbus port using T1K-MODBUS setup tool)

Base Power Requirement

250 mA @ 5 VDC

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-60

For the latest prices, please check AutomationDirect.com.

Ethernet Slave T1H-EBC100

$287.00

T1H-EBC100

The T1H-EBC100 module provides a low-cost, high-performance Ethernet link between Terminator I/O and your PC-based control or WinPLC/ DL205/DL405 CPUs using the H*-ERM100 module for remote I/O. Not recommended for use Productivity3000 processors.

T1H-EBC100

with

These interface modules support industry standard 10Base-T or 100Base-T communications.

Supported protocols The Terminator T1H-EBC100 supports TCP/IP, UDP/IP, IPX and Modbus TCP at 100 Mbps maximum.

Network masters Network masters include the DL205, DL405 DirectLOGIC PLCs and WinPLCs using the Ethernet Remote Master module (ERM), and PCs using PC-based control software that includes embedded Ethernet I/O drivers.

• S ave money on your Terminator I/O system when compared with competitive I/O

T1H-EBC100 as H*-ERM100 slave

•V  irtually unlimited number of I/O points (up to sixteen modules per EBC system) •D  eterministic I/O updates on dedicated networks

When using a DirectLOGIC CPU with an ERM module as the network master, the T1H-EBC100 slave provides fast analog I/O update times ( 10.0 VDC

OFF Voltage Level

< 2.0 VDC

Min. ON Current

4 mA

Max. OFF Current

0.5 mA

OFF to ON Response

2-8 ms, Typ: 4 ms

ON to OFF Response

2-8 ms, Typ: 4 ms

Base Power Required

70 mA @ 5 VDC

Status Indicators

Logic side

Weight

160 g

Note: When using external power, the module can be wired to either sink current or source current regardless of the module’s sink/source jumper position. When using internal power, the sink/source jumpers determine the module’s configuration.

External Power

Internal Power

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-76

For the latest prices, please check AutomationDirect.com.

AC Input Modules T1K-08NA-1 $90.00 T1K-16NA-1 $147.00 8-point and 16-point, 90-120 VAC input modules The 8-point AC input module uses a T1K-08B or T1K-08B-1 base, which is purchased separately. The 16-point AC input module uses a T1K-16B or T1K-16B-1 base, which is purchased separately.

Specifications

T1K-08NA-1

T1K-16NA-1

Inputs Per Module

8

16

Commons per Module

2, 4 pts. /com (isolated)

4, 4 pts. /com (isolated)

Input Voltage Range

80-132 VAC, 47-63 Hz

Operating Voltage Range

90-120 VAC, 47-63 Hz

Input Current

8 mA @ 100 VAC (50 Hz) 10 mA @ 100 VAC (60 Hz) 12 mA @ 132 VAC (50 Hz) 15 mA @ 132 VAC (60 Hz)

Input Impedance

14 Kq @ 50 Hz, 12 Kq @ 60 Hz

ON Current/Voltage

> 6 mA @ 75 VAC

OFF Current/Voltage

< 2 mA @ 20 VAC

OFF to ON Response

< 40 ms

ON to OFF Response

< 40 ms

Base Power Required

35 mA @ 5 VDC

Status Indicators

Logic side

Weight

70 g

8 mA @ 100 VAC (50 Hz) 10 mA @ 100 VAC (60 Hz) 12 mA @ 132 VAC (50 Hz) 15 mA @ 132 VAC (60 Hz)

70 mA @ 5 VDC 120 g

Equivalent Input Circuit

tFED-77

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

DC Output Modules T1K-08TD1 T1K-16TD1

$79.00 $121.00

8-point and 16-point, current sinking DC output modules The 8-point DC module uses a T1K-08B or T1K-08B-1 base, which is purchased separately. The 16-point DC module uses a T1K-16B or T1K-16B-1 base, which is purchased separately.

Specifications

T1K-08TD1

T1K-16TD1

Outputs per Module

8 (sink)

16 (sink)

Commons per Module

2 internally connected

4 internally connected

Operating Voltage Range

6-27 VDC min./max.

Output Voltage Range

5-30 VDC min. / max.

Peak Voltage

50 VDC

Max. Output Current

1A / pt., 4A / common

Max. Leakage Current

15 µA @ 30 VDC

ON Voltage Drop

0.3 VDC @ 1.0A

Max. Inrush Current

2A for 100 ms

OFF to ON Response

< 10 µs

ON to OFF Response

< 60 µs

Base Power Required

100 mA @ 5 VDC

200 mA @ 5 VDC

External Power Required

200 mA max. @ 20-28 VDC

400 mA max. @ 20-28 VDC

Status Indicators

Logic side

Error Status Indicators

24 V ON = low external power FU1/FU2 ON = blown fuse

FU1/FU2 ON = fuse 1 or 2 blown FU3/FU4 ON = fuse 3 or 4 blown

Fuses (User Replaceable) T1K-FUSE-1

2

4

Weight

85 g

(6.3 A, 250 V / common) NQ3-6.3 SOC Corp. 140 g

Equivalent Output Circuit

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-78

For the latest prices, please check AutomationDirect.com.

DC Output Modules T1K-08TD2-1 $79.00 T1K-16TD2-1 $119.00 8-point and 16-point, 12/24 VDC current sourcing DC output module The 8-point DC module uses a T1K-08B or T1K-08B-1 base, which is purchased separately. The 16-point DC module uses a T1K-16B or T1K-16B-1 base, which is purchased separately.

T1K–08TD2–1 FU1

1

2

T1K-08TD2-1

3

4

5

6

T1K-16TD2-1

8 (source)

16 (source)

Commons per Module

2 internally connected

4 internally connected

Output Voltage Range

10.8-26.4 VDC

Operating Voltage Range 12-24 VDC Peak Voltage

50 VDC

Max. Output Current

1A / pt., 4A / common

Max. Leakage Current

15 µA @ 26.4 VDC

ON Voltage Drop

1.2 VDC @ 1.0 A

Max. Inrush Current

2A for 100 ms

OFF to ON Response

< 10 µs

ON to OFF Response

< 0.5 ms

Base Power Required

100 mA @ 5 VDC

Status Indicators Error Status Indications(LEDs )

Logic side FU1/FU2 ON = fuse 1 or 2 blown

Fuses (User Replaceable) 2 qty., (6.3 A, 250 V / common) NQ3-6.3 SOC Corp. T1K-FUSE-1 100 g Weight

FU2

0

Specifications Outputs per Module

1A / pt., 4A / common (subject to derating)

200 mA @ 5 VDC FU1/FU2 ON = fuse 1 or 2 blown FU3/FU4 ON = fuse 3 or 4 blown 4 qty., (6.3 A, 250 V / common) NQ3-6.3 SOC Corp. 140 g

7

0 1 2 3 4 5 6 7

Equivalent Output Circuit

tFED-79

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

DC Output Modules T1H-08TDS

$161.00

Module Specifications

T1H-08TDS

8-point isolated DC output module with electronic over current protection

Outputs Per Module

8 (isolated, sink/source)

Commons

8 (isolated)

Operating Voltage Range

5-36 VDC

The 8-point DC module uses a T1K-16B or T1K-16B-1 base, which is purchased separately.

Max. Voltage

36 VDC

Output Clamp Voltage

40 VDC

Max. Load Current

2A per point, 16 A per module

Electronic Over Current Protection

Output trips at 6A min., 12 A max.

Max. Load Voltage

36 VDC

Max. Leakage Current

75 µA

Max. ON State Voltage Drop

0.3 V at 2A, 0.15 V at 1A

Inrush Current

5A for 20 ms

OFF to ON Response

50 mA, 4.0 VAC @ < 50 mA

Max. Leakage Current

4 mA @ 264 VAC

Max. Inrush Current

10 A for 10 ms

Min. Load

10 mA

OFF to ON Response

< 1 ms

ON to OFF Response

< 1 ms + 1/2 cycle

Base Power Required

300 mA @ 5 VDC

Status Indicators

Logic Side

Error Status Indications(LEDS)

FU1/FU2 ON = fuse 1 or 2 blown FU3/FU4 ON = fuse 3 or 4 blown FU5/FU6 ON = fuse 5 or 6 blown FU7/FU8 ON = fuse 7 or 8 blown

Fuses (User Replaceable) T1K-FUSE-3 Weight

8, (10 A, 250 V / common), 1 pt. / fuse NQ3-10 SOC Corp. 190 g

Equivalent Output Circuit

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-82

For the latest prices, please check AutomationDirect.com.

Relay Output Modules T1K-08TR T1K-16TR

$87.00 $153.00

8-point and 16-point, relay output modules The 8-point relay output module uses a T1K-08B or T1K-08B-1 base, which is purchased separately. The 16-point Relay output module uses a T1K-16B or T1K-16B-1 base, which is purchased separately.

Specifications

T1K-08TR

T1K-16TR

Outputs per Module

8 normally open

16 normally open

Isolated Commons

2 (4 pts. / common) isolated

4 (4 pts. / common) isolated

Operating Voltage Range 6-240 VAC (47-63)Hz, 6-27 VDC Output Voltage Range

5-264 VAC (47-63Hz), 5-30 VDC min./max.

Max. Load Current

2A / pt., 8A / common

Max. Leakage Current

0.1 mA @ 264 VAC

Max. Inrush Current

6A for 10 mS / pt.; 20 A for 10 mS / com.

Min. Load

5 mA @ 5 VDC

OFF to ON Response

< 15 ms

ON to OFF Response

< 10 ms

Base Power Required

350 mA @ 5 VDC

Status Indicators Error Status Indications(LEDs ) Fuses (User Replaceable) T1K-FUSE-1 Weight

Logic side

2A / pt., 6A / common (subject to derating)

700 mA @ 5 VDC

FU1 ON = fuse 1 blown FU2 ON = fuse 2 blown

FU1/FU2 ON = fuse 1 or 2 blown FU3/FU4 ON = fuse 3 or 4 blown

2, (10 A, 250 V / common) 5 x 20 mm type

4, (10 A, 250 V / common) 5 x 20 mm type

110 g

200 g

Typical Relay Life (Operations) Voltage and Load Type

Load Current 1A

2A

24 VDC Resistive

500 K

250 K

24 VDC Solenoid

100 K

50 K

110 VAC Resistive

500 K

250 K

110 VAC Solenoid

200 K

100 K

220 VAC Resistive

350 K

200 K

220 VAC Solenoid

100 K

50 K

Equivalent Output Circuit

tFED-83

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Relay Output Modules T1K-08TRS

$115.00

8-point, isolated relay output module

T1K-08TRS Output Specification Outputs per Module

8 normally open

Commons

8, 1 pt. / common (isolated)

Operating Voltage Range

6-240 VAC (47-63 Hz), 6-27 VDC

The 8-point relay output module uses a T1K-16B or T1K-16B-1 base, which is Output Voltage Range purchased separately. Max. Load Current

5-264 VAC (47-63 Hz), 5-30 VDC min./max. 7A / pt. (subject to derating)

Max. Leakage Current

0.1 mA @ 264 VAC

Max. Inrush Current

8A for 10 ms

Min. Load

5 mA @ 5 VDC

OFF to ON Response

< 15 ms

ON to OFF Response

< 10 ms

Base Power Required

400 mA @ 5 VDC

Status Indicators

Logic side

Error Status Indications(LEDS)

FU1/FU2 ON = fuse 1 or 2 blown FU3/FU4 ON = fuse 3 or 4 blown FU5/FU6 ON = fuse 5 or 6 blown FU7/FU8 ON = fuse 7 or 8 blown

Fuses (User Replaceable) T1K-FUSE-3 Weight

8, (10 A, 250 V / common), 1 pt. / fuse NQ3-10 SOC Corp. 185 g

Typical Relay Life (Operations) Load Current

Voltage and Load Type

1A

2A

5A

7A

24 VDC Resistive

1000 K

500 K

200 K

100 K

24 VDC Solenoid

300 K

100 K

see note

see note

110 VAC Resistive

1000 K

500 K

200 K

100 K

110 VAC Solenoid

300 K

100 K

see note

see note

220 VAC Resistive

500 K

250 K

125 K

60 K

220 VAC Solenoid

300 K

100 K

see note

see note

Note: Solenoid (inductive) loads >2A cannot be used.

Equivalent Output Circuit

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-84

For the latest prices, please check AutomationDirect.com.

Analog Current Input Module T1F-08AD-1 $290.00 8-channel analog current input module The 8-channel current input module uses a T1K-08B or T1K-08B-1 base, which is purchased separately.

T1F-08AD-1 Analog Input Specification Number of Channels

8, single-ended (1 common)

Input Ranges

-20 to 20 mA, 0-20 mA, 4-20 mA

Resolution

14 bit (13 bit plus sign bit)

Frequency Response

-3 db @ 500 Hz, -20 db/decade

Input Resistance

250 q

Absolute Max. Ratings

8V max. input

Conversion Time

Normal mode: 5 ms per channel (default); Fast mode*: 0.5 ms per channel

Linearity Error

± 2 counts max.

Input Stability

Normal mode: ± 1 count (default); Fast mode*: ± 5 counts

Full Scale Error (Offset Error Not Included)

16 counts max.

Offset Error Max. Full Scale Inaccuracy (% of full scale); All errors included Master Update Rate

2 counts max.

Input Points Required

256 discrete pts. or 8 Dwords (32-bit words) (Network interface dependent)

Base Power Required

75 mA @ 5 VDC

External Module Power Required

21.6-26.4 VDC, 50 mA, class 2

Recommended Fuse

0.032 A, Series 217 Fast Acting

Weight

136 g

0.18% @ 25°C 0.36% @ 60°C 8 channels per scan max.

* Fast mode is supported in module hardware version B or later. Fast mode is only supported when using the analog module  with the T1H-EBC(100) or T1H-PBC Interface module.

Equivalent Input Circuit

NOTES: 1: Shields should be grounded at the signal source. 2: More than one external power supply can be used, provided all the power supply commons are connected. 3: A Series 217, 0.032A fast-acting fuse is recommended for 4-20 mA current loops. 4: If the power supply common of an external power supply is not connected to the 0V terminal on the module, then the output of the external transmitter must be isolated. To avoid “ground loop” errors, recommended 4-20 mA transmitter types are: - For 2 or 3 wire connections: Isolation between the input supply signal and the power supply. - For 4 wire connections: Isolation between the input supply signal, the power supply and the 4-20mA output.

tFED-85

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Analog Voltage Input Module T1F-08AD-2 $300.00 8-channel analog voltage input module The 8-channel voltage input module uses a T1K-08B or T1K-08B-1 base, which is purchased separately.

T1F-08AD-2 Analog Input Specification Channels Per Module

8 single-ended (1 common)

Input Ranges

0-5 V, 0-10 V, ± 5V, ± 10V

Resolution

14 bit (13 bit plus sign bit)

Frequency Response

-3 db @ 500 Hz, -20 db/decade

Input Resistance

200 Kq min.

Absolute Max. Ratings

Fault protected input 130 V(rms) or 100 VDC

Conversion Time

Normal mode: 5 ms per channel (default); Fast mode*: 0.5 ms per channel

Linearity Error

± 2 count max.

Input Stability

Normal mode: ± 1 count (default); Fast mode*: ± 5 counts

Calibration Full Scale Error

8 counts max.

Calibration Offset Error Max. Full Scale Inaccuracy (% of full scale); All errors included Master Update Rate

2 counts max.

Input Points Required

256 discrete pts. or 8 Dwords (32-bit words) (Network Interface Dependent)

Base Power Required

75 mA @ 5 VDC

External Module Power Required

21.6-26.4 VDC, 50 mA, class 2

Weight

136 g

0.08% @ 25°C 0.26% @ 60°C 8 channels per scan max.

* Fast mode is supported in module hardware version B or later. Fast mode is only supported when using the analog module w  ith the T1H-EBC(100) or T1H-PBC Interface module.

Equivalent Input Circuit

NOTES: 1: Shields should be grounded at the signal source. 2: Unused inputs should be connected to common (0 VDC). 3: More than one external power supply can be used, provided all the power supply commons are connected.

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-86

For the latest prices, please check AutomationDirect.com.

Analog Current Input Module T1F-16AD-1 $414.00

T1F-16AD-1 Analog Input Specification

16-channel analog current input module The 16-channel current input module uses a T1K-16B or T1K-16B-1 base, which is purchased separately.

Number of Channels

16, single ended (1 common)

Input Ranges

-20 to 20 mA, 0-20 mA, 4-20 mA

Resolution

14 bit (13 bit plus sign bit)

Frequency Response

-3 db @ 500 Hz, -20 db/decade

Input Resistance

250 q

Absolute Max. Ratings

8V max. input

Conversion Time

5 ms per channel

Linearity Error

± 2 counts max.

Input Stability Full Scale Error (Offset Error not included) Offset Error Max. Full Scale Inaccuracy (% of full scale). All errors included Master Update Rate

± 1 count

Input Points Required

512 discrete pts. or 16 Dwords (32-bit words) (network interface dependent)

Base Power Required

75 mA @ 5 VDC

External Module Power Required

21.6-26.4 VDC, 50 mA, class 2

Recommended Fuse

0.032 A, Series 217 fast acting

Weight

168 g

16 counts max. 2 counts max. 0.18% @ 25°C 0.36% @ 60°C 16 channels per scan max.

Equivalent Input Circuit

NOTES: 1: Shields should be grounded at the signal source. 2: More than one external power supply can be used, provided all the power supply commons are connected. 3: A Series 217, 0.032 A fast-acting fuse is recommended for 4-20 mA current loops. 4: If the power supply common of an external power supply is not connected to the 0V terminal on the module, then the output of the external transmitter must be isolated. To avoid “ground loop” errors, recommended 4-20 mA transmitter types are: - For 2 or 3 wire connections: Isolation between the input supply signal and the power supply. - For 4 wire connections: Isolation between the input supply signal, the power supply and the 4-20 mA output.

tFED-87

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Analog Voltage Input Module T1F-16AD-2 $414.00

T1F-16AD-2 Analog Input Specification

16-channel analog voltage input module

Number of Channels

16, single ended (1 common)

Input Ranges

0-5 V, 0-10 V, ± 5V, ± 10 V

The 16-channel voltage input module uses a T1K-16B or T1K-16B-1 base, which is purchased separately.

Resolution

14 bit (13 bit plus sign bit)

Frequency Response

-3 db @ 500 Hz, -20 db/decade

Input Resistance

200 Kq min.

Absolute Max. Ratings

Fault protected input 130 V(rms) or 100 VDC

Conversion Time

5 ms per channel

Linearity Error

± 2 count max.

Input Stability

± 1 count

Calibration Full Scale Error

8 counts max.

Calibration Offset Error Max. Full Scale Inaccuracy (% of full scale). All errors included Master Update Rate

2 counts max.

Input Points Required

512 discrete points or 16 Dwords (32-bit words) (Network Interface Dependent)

Base Power Required

75 mA @ 5 VDC

External Module Power Required

21.6-26.4 VDC, 50 mA, class 2

Weight

160 g

0.08% @ 25°C 0.26% @ 60°C 16 channels per scan max.

Equivalent Input Circuit

NOTES: 1: Shields should be grounded at the signal source. 2: Unused inputs should be connected to common (0 VDC). 3: More than one external power supply can be used, provided all the power supply commons are connected.

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-88

For the latest prices, please check AutomationDirect.com.

RTD Input Module T1F-16RTD $414.00 16-channel RTD input module

T1F–16RTD

The 16-channel RTD input module uses a T1K-16B or T1K-16B-1 base, which is purchased separately.

T1F-16RTD 16-Channel RTD Input Specifications

RTD Input Ranges

Number of Channels

16

Common Mode Range

0-5 VDC

Resolution

± 0.1 ºC or ºF

Notch Filter

>50db notches @ 50/60 Hz; f - 3db = 13.1 Hz

Absolute Maximum Ratings

±50 VDC

Converter Type

Charge balancing, 24-bit

Master Update Rate

16 channels per scan max.

Input Points Required

512 Discrete I/O points /16 Double Words Network Interface Dependent

Sampling Rate

140ms / channel

Base Power Required

150 mA max., 5 VDC

Temperature Drift

25 ppm / ºC (max.)

Maximum Inaccuracy

± 1 ºC

RTD Excitation Current

200 µA

Operating Temperature

32º to 140ºF (0º to 60ºC)

Storage Temperature

-4º to 158ºF (-20º to 70ºC)

Relative Humidity

5 to 95% (non-condensing)

Environmental Air

No corrosive gases permitted

Vibration

MIL STD 810C 514.2

Shock

MIL STD 810C 516.2

Noise Immunity

NEMA ICS3-304

Weight

168 g

Pt100 -200 to 850cC Pt1000 -200 to 595ºC Pt100 -38 to 450ºC Type CU 10 -200ºC to 260ºC Type CU 25 -200ºC to 260ºC 120 q Nickel -80 to 260ºC

Input Ranges

-328 to 1562ºF -328 to 1103ºF -36 to 842ºF -328 to 500ºF -328 to 500ºF -112 to 500ºF

Channel Inputs (+)

CH1 +

CH2 +

CH3 +

CH4 +

CH5 +

CH6 +

CH7 +

CH8 +

CH9 +

CH10 +

CH11 +

CH12 +

CH13 +

CH14 +

CH15 CH16 + +

CH12 –

CH13 –

CH14 –

CH15 CH16 – –

Channel Inputs (–) CH1 –

CH2 –

CH3 –

CH4 –

CH5 –

CH6 –

CH7 –

CH8 –

CH9 –

CH10 –

CH11 –

RTD Commons

Notes: 1: The three wires connecting the RTD to the module must be the same type and length. Do not use the shield or drain wire for the third connection. 2: If an RTD sensor has four wires, the plus sense wire should be left unconnected as shown.

Equivalent Input Circuit 200 µA Current Source V0-V3 (RTD Returns) Ref. Adj.

tFED-89

Universal Field I/O

Analog Switch

x Note 2

A to D Converter 200 µA Current Source

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Thermistor Input Module T1F-16TMST $399.00 16-channel Thermistor input module

T1F–16TMST

The 16-channel Thermistor input module uses a T1K-16B or T1K-16B-1 base, which is purchased separately.

Specifications Number of Channels Resolution Input Impedence Common Mode Range Absolute Max. Ratings Converter Type Sampling Rate Master Update Rate Input Points Required

Recommended Cable Weight 1 “Accuracy”

pertains to module only and does not include tolerances of thermistor element, wiring resistance, etc. For example, 22 gauge wire is 0.016q per foot, so 200 feet of wire adds 3.2q.

2 Meets

Input Ranges 10K-AN (Type 3) 10K-CP (Type 2) 5K 3K 2252 1.8K

Range -40º to 150º C (-40º to 300º F) -40º to 150º C (-40º to 300º F) -40º to 150º C (-40º to 300º F) -40º to 150º C (-40º to 300º F) -40º to 150º C (-40º to 300º F) -40º to 150º C (-40º to 300º F)

Equivalent Input Circuit Internal Module Circuitry

CHxA

Ref. Adj. Analog Switch

Base Power Required Operating Temperature Storage Temperature Temperature Drift Maximum Inaccuracy 1 Excitation Current Electrical Isolation Relative Humidity Environmental Air Vibration Shock Noise Immunity

16 + / - 0.1º C or ºF > 1Mq 0 - 5 VDC + / - 50 VDC Charge balancing, 24 - bit 140 ms / channel 16 channels per scan max. 512 discrete pts. or 16 dwords (d (double) word = 32 bit word) Network Interface dependent 150 mA @ 5 VDC 0º to 60º C (32º to 140º F) -20º to 70º C (-4º to 158º F) 25 ppm / ºC (max.) + / - 1ºC 10 µA 1500VDC field wire to backplane 5 to 95% (non-condensing) No corrosive gases permitted IEC 60068-2-6 (Test FC) IEC 60068-2-27 (Test Ea) EN61131-2:2007 2 AutomationDirect P/N: PLTC3-18-1S-XXX Belden 8761 or equivalent 168 g

Thermistor Input Ranges

CHxB

A to D Converter 10 uA Current Source

COMMON (V0 - V3) Field side ground

Channel Inputs (+) CH1 A

CH2 A

CH3 A

CH4 A

CH5 A

CH6 A

CH7 A

CH8 A

CH9 A

CH10 CH11 CH12 CH13 CH14 CH15 CH16 A A A A A A A

EMC & Safety Requirements Channel Inputs (–) CH1 B

CH2 B

CH3 B

CH4 B

CH5 B

CH6 B

CH7 B

CH8 B

CH9 B

CH10 CH11 CH12 CH13 CH14 CH15 CH16 B B B B B B B

Commons

If inputs are not used, tie CHxA and CHxB together to COMMON terminal block. Tie COMMONS to field side ground.

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-90

For the latest prices, please check AutomationDirect.com.

Thermocouple Input Module T1F-14THM $519.00 14-channel thermocouple input module The 14-channel thermocouple input module uses a T1K-16B screwtype terminal base only, which is purchased separately.

T1F-14THM 14-Channel Thermocouple Input Specifications Use I/O Base

T1K-16B Only

Number of Channels

14, differential

Common Mode Range

±5 VDC

Common Mode Rejection

90 dB min. @ DC, 150 dB min. @ 50/60 Hz.

Input Impedance

1 Mq

Absolute Maximum Ratings

Fault-protected inputs to ±50 VDC

Accuracy vs. Temperature

±5 ppm/ºC maximum full scale calibration. (including maximum offset change)

Master Update Rate

14 channels per scan max.

Input Points Required

512 Discrete I/O points /16 Double Words Network Interface Dependent

Thermocouple Specifications (Cont.)

Input Ranges

Type J -190 to 760ºC Type E -210 to 1000ºC Type K -150 to 1372ºC Type R 65 to 1768ºC Type S 65 to 1768ºC Type T -230 to 400ºC Type B 529 to 1820ºC Type N -70 to 1300ºC Type C 65 to 2320ºC

-310 to 1400ºF -346 to 1832ºF -238 to 2502ºF 149 to 3214ºF 149 to 3214ºF -382 to 752ºF 984 to 3308ºF -94 to 2372ºF 149 to 4208ºF

Display Resolution

±0.1 ºC or ±0.1 ºF

Cold Junction Compensation

Automatic; CJC (part #: T1F-CJC) included with module must be installed in terminal base (refer to the module’s data sheet)

Conversion Time

100 ms

Warm-Up Time

30 minutes typically ± 1ºC repeatability

External Module Power Required

70mA maximum, 24VDC ± 5%

Base Power Required

60 mA max., 5 VDC

Operating Temperature

32º to 140ºF (0º to 60ºC)

Storage Temperature

-4º to 158ºF (-20º to 70ºC)

Relative Humidity

5 to 95% (non-condensing)

Environmental Air

No corrosive gases permitted

Vibration

MIL STD 810C 514.2

Shock

MIL STD 810C 516.2

16 bit (1 in 65535) Resolution Full Scale Calibration Error ±13 counts typical ±33 maximum (Offset Error Included) ±1 count maximum, @ 0V input Offset Calibration Error

Noise Immunity

NEMA ICS3-304

Linearity Error (End to End) ±1 count maximum

Weight

168 g

Maximum Inaccuracy

Linearity Error (End to End) ±.05 ºC maximum, ±.01ºC typical Maximum Inaccuracy

±3 ºC (excluding thermocouple error)

Voltage Input Specifications Voltage Ranges

0-5 V, ±5V, 0-156.25 mV, ±156.25 mVDC

±.0.02% @ 25ºC (77ºF)

Notes: 1: Shields should be grounded at the signal source. 2: Connect unused inputs to a common terminal (0 VDC). 3: W  hen using 0-156 mV and 5V ranges, connect (-) or (0) volts terminal to 0V to ensure common mode range acceptance. 4: T he Cold Junction Compensation (CJC) temperature sensing unit must be installed into the I/O base terminals to perform CJC of the thermocouple inputs.

Equivalent Input Circuit

tFED-91

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Analog Current Output Module T1F-08DA-1 Analog Output Specification

T1F-08DA-1 $383.00 8-channel analog current output module The 8-channel current output module uses a T1K-08B or T1K-08B-1 base, which is purchased separately.

Channels Per Module

8

Output Ranges

0-20 mA, 4-20 mA

Output Type

Single-ended, 1 common

Resolution

12 bit (1 in 4096)

Max. Loop Supply

30 VDC

Peak Output Voltage

30 VDC

Load Impedance

0q min.

Max. Load (ohm) / Power Supply

620/18 V, 910/24 V, 1200/30 V

Min. Load (ohm) / Power Supply

0/24 V, 350/30 V @ 40°C 250/24V, 600/30 V @ 60°C

Linearity Error (end to end)

± 2 counts max. ± 0.05% of full scale max.

Conversion Settling Time

400 µs max. full scale change

Full Scale Calibration Error

± 12 counts max.

Offset Calibration Error

0-20 mA: ± 6 counts max. 4-20 mA: ± 6 counts max.

Accuracy vs. Temperature

± 50 ppm/°C full scale calibration change

Max. Full Scale Inaccuracy (% of full scale); all errors included Master Update Rate

0.2% @ 25°C 0.4% @ 60°C

Output Points Required

256 discrete pts. or 8 Dwords (32-bit words) (network interface dependent)

Base Power Required

75 mA @ 5 VDC

External Module Power Required

21.6-26.4 VDC, 150 mA, class 2

Weight

145 g

8 channels per scan max.

Equivalent Output Circuit

NOTES: 1: Shields should be connected to the 0V terminal of the module or the 0V of the power supply. 2. Unused current outputs should remain open (no connections) for minimum power consumption.

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-92

For the latest prices, please check AutomationDirect.com.

Analog Voltage Output Module T1F-08DA-2 $404.00 8-channel analog voltage output module

T1F-08DA-2 Analog Output Specification Number of Channels

8

Output Ranges

0-5V, 0-10V, ± 5V, ± 10V

Output Type

Single-ended, 1 common

The 8-channel voltage output module uses a T1K-08B or T1K-08B-1 base, which is Resolution purchased separately. Peak Output Voltage

12 bit (1 in 4096) 15VDC

Load Impedance

4Kq min.

Load Capacitance

0.01µF max.

Linearity Error (end to end)

± 2 counts max. ± 0.05% of full scale max.

Conversion Settling Time

100 µs max. full scale change

Full Scale Calibration Error

± 12 counts max.

Offset Calibration Error

10 V ranges: ± 6 counts max. 5V ranges: ± 11 counts max.

Accuracy vs. Temperature

± 50 ppm/°C full scale calibration change

Max. Full Scale Inaccuracy (% of full scale). all errors included

10V ranges: 0.2% @ 25°C 0.4% @ 60°C 5V ranges: 0.3% @ 25°C 0.5% @ 60°C

Master Update Rate

8 channels per scan max.

Output Points Required

256 discrete pts. or 8 Dwords (32-bit words) (network interface dependent)

Base Power Required

75 mA @ 5 VDC

External Module Power Required

21.6-26.4 VDC, 150 mA, class 2

Weight

145 g

Equivalent Output Circuit

NOTES: 1: Shields should be connected to the 0V terminal of the module or the 0V of the power supply. 2. Unused current outputs should remain open (no connections) for minimum power consumption.

tFED-93

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Analog Current Output Module T1F-16DA-1 $591.00

T1F-16DA-1 Analog Output Specification

16-channel analog current output module

Number of Channels

16

Output Ranges

0-20 mA, 4-20 mA

The 16-channel current output module uses a T1K-16B or T1K-16B-1 base, which is purchased separately.

Output Type

Single-ended, 1 common

Resolution

12 bit (1 in 4096)

Max. Loop Supply

30 VDC

Peak Output Voltage

30 VDC

Max. Load (q) / Power Supply

620/18 V, 910/24 V, 1200/30 V

Min. Load (q) / Power Supply

0/24 V, 350/30 V, @ 40°C 250/24 V, 600/30 V @ 60°C

Linearity Error (end to end)

± 2 counts max. ± 0.05% of full scale max.

Conversion Settling Time

100 µs max. full scale change

Full Scale Calibration Error

± 12 counts max.

Offset Calibration Error

± 4 counts max.

Accuracy vs. Temperature

± 50 ppm/°C full scale calibration change

Max. Full Scale Inaccuracy (% of full scale), All errors included Master Update Rate

0.2% @ 25°C 0.4% @ 60°C

Output Points Required

512 discrete points or 16 Dwords (32-bit words) (network interface dependent)

Base Power Required

75 mA @ 5 VDC

External Power Supply

21.6-26.4 VDC, 150 mA, class 2

Weight

172 g

16 channels per scan max.

Equivalent Output Circuit

NOTES: 1: Shields should be connected to the 0V terminal of the module or the 0V of the power supply. 2. Unused current outputs should remain open (no connections) for minimum power consumption.

www.automationdirect.com/fieldIO

Universal Field I/O

tFED-94

For the latest prices, please check AutomationDirect.com.

Analog Voltage Output Module T1F-16DA-2 $622.00 16-channel analog voltage output module

T1F-16DA-2 Analog Output Specification Number of Channels

16

Output Ranges

0-5V, 0-10 V, ± 5V, + / - 10V

Output Type

Single-ended, 1 common

The 16-channel voltage output module uses a T1K-16B or T1K-16B-1 base, Resolution which is purchased separately. Peak Output Voltage

12 bit (1 in 4096) 15 VDC

Load Impedance

4 Kq min.

Load Capacitance

0.01 µF max.

Linearity Error (end to end)

± 2 counts max. ± 0.05% of full scale max.

Conversion Settling Time

100 µs max. full scale change

Full Scale Calibration Error

± 12 counts max.

Offset Calibration Error

10 V ranges: ± 6 counts max. 5V ranges: ± 11 counts max.

Accuracy vs. Temperature

± 50 ppm/°C full scale calibration change

Max. Full Scale Inaccuracy (% of full scale), All errors included

10V ranges: ± 0.2% @ 25°C ± 0.4% @ 60°C 5V ranges: ± 0.3% @ 25°C ± 0.5% @ 60°C

Master Update Rate

16 channels per scan max.

Output Points Required

512 discrete points or 16 Dwords (32-bit words) (Network Interface Dependent)

Base Power Required

75 mA @ 5 VDC

External Power Supply

21.6-26.4 VDC, 150 mA, class 2

Weight

172 g

Equivalent Output Circuit

NOTES: 1: Shields should be connected to the 0V terminal of the module or the 0V of the power supply. 2. Unused current outputs should remain open (no connections) for minimum power consumption.

tFED-95

Universal Field I/O

1-800-633-0405

For the latest prices, please check AutomationDirect.com.

Analog Current Combination Module T1F-8AD4DA-1 $363.00 8-channel analog current input 4-channel analog current output The combination 8-in and 4-out current module uses a T1K-8B or T1K-8B-1 base, which is purchased separately.

Analog Output Specification

? ?

?

? ? ?

?

?

?

Channels Per Module

4, sink/source by wiring

Output Ranges

4-20 mA

Output Type

Single-ended, 1 common

Resolution

12 bit (1 in 4096)

Max. Loop Supply

30 VDC

Source Load / Loop Power Supply 0-400 q / 18-30 VDC

T1F-8AD4DA-1 Analog Input Specification Number of Channels

8, single-ended (1 common)

Input Ranges

-20 to 20 mA, 0-20 mA, 4-20 mA

Resolution

14 bit (13 bit plus sign bit)

Frequency Response

-3db @ 500Hz, -20db/decade

Input Resistance

250q

Absolute Max. Ratings

8V max. input

Conversion Time

5ms per channel

Linearity Error

± 2 counts max.

Input Stability Full Scale Error (Offset Error not included) Offset Error Max. Full Scale Inaccuracy (% of full scale), all errors included Master Update Rate

± 1 count

Sink Load / Loop Power Supply

0-600 q / 18 VDC 0-900 q / 24 VDC 0-1200 q / 30 VDC

Total Load (Sink + Source)

600 q/18V, 900 q/24V, 1200 q/30V

Linearity Error (End to End)

± 2 counts max. ± 0.05% of full scale max.

Conversion Settling Time

400 µs max. full scale change

Full Scale Calibration Error (Note: source error depends upon the load from the source terminal to ground)

SINK: ± 12 counts max. @ any load SOURCE: ± 26 counts max. @ 400 q ± 18 counts max. @ 250 q ± 12 counts max. @ 125 q

Offset Calibration Error

SINK: ± 6 counts max. @ any load SOURCE: ± 10 counts max. @ 400 q ± 8 counts max. @ 250 q ± 6 counts max. @ 125 q

Max. Full Scale Inaccuracy (% of Full Scale) All Errors Included

SINK: (any load) 0.3% @ 25°C (any load) 0.5% @ 60°C SOURCE: 400 q load 0.63% @ 25°C 400 q 0.83% @ 60°C 250 q 0.44% @ 25°C 250 q load 0.64% @ 60°C 125 q load 0.30% @ 25°C 125 q load 0.50% @ 60°C

Master Update Rate

4 channels per scan max.

Output Points Required

128 discrete pts. or 4 Dwords (32-bit words) (network interface dependent)

16 counts max. 2 counts max. 0.18% @ 25°C 0.36% @ 60°C 8 channels per scan max.

Input Points Required

256 discrete pts. or 8 Dwords (32-bit words) (Network Interface Dependent)

Base Power Required

75mA @ 5 VDC

External Power Required

21.6-26.4 VDC, 60mA, class 2 (plus 20mA per output loop)

Recommended Fuse

0.032 A, Series 217 Fast Acting

Weight

136 g

Equivalent Output Circuit

Equivalent Input Circuit

NOTES: 1: Shields should be grounded at the signal source. 2: More than one external power supply can be used, provided all the power supply commons are connected. 3: A Series 217, 0.032A fast-acting fuse is recommended for 4-20 mA current loops. 4: If the power supply common of an external power supply is not connected to the 0V terminal on the module, then the output of the external transmitter must be isolated. To avoid “ground loop” errors, recommended 4-20 mA transmitter types are: - For 2 or 3 wire connections: Isolation between the input supply signal and the power supply. - For 4 wire connections: Isolation between the input supply signal, the power supply and the 4-20 mA output.

www.automationdirect.com/fieldIO

NOTES: 1: S  hields should be connected to the 0V terminal of the module or the 0V of the power supply. 2. U  nused current outputs should remain open (no connections) for minimum power consumption.

Universal Field I/O

tFED-96

For the latest prices, please check AutomationDirect.com.

Analog Voltage Combination Module T1F-8AD4DA-2 $363.00 8-channel analog voltage input 4-channel analog voltage output

? ?

? ?

? ? ?

?

?

The combination 8-in and 4-out voltage module uses a T1K-8B or T1K-8B-1 base, which is purchased separately.

T1F-8AD4DA-2 Analog Input Specification

T1F-8AD4DA-2 Analog Output Specification

Channels Per Module

8 single-ended (1 common)

Number of Channels

4

Input Ranges

0-5V, 0-10 V, ± 5V, ± 10 V

Output Ranges

0-5V, 0-10 V, ± 5V, ± 10V

Resolution

14 bit (13 bit plus sign bit)

Output Type

single ended, 1 common

Frequency Response

-3db @ 500 Hz, -20 db/decade

Resolution

12 bit (1 in 4096)

Input Resistance

200 Kq min.

Peak Output Voltage

15 VDC

Absolute Max. Ratings

Fault Protected Input 130V(rms) or 100 VDC

Load Impedance

4 Kq min.

Conversion Time

5.5ms per channel

Load Capacitance

0.01 µF max.

Linearity Error

± 2 count max.

Linearity Error (End to End)

± 2 counts max. ± 0.05% of full scale max.

Input Stability

± 1 count

Conversion Settling Time

300 µs max. full scale change

Calibration Full Scale Error

8 counts max.

Full Scale Calibration Error

± 12 counts max.

Calibration Offset Error

2 counts max.

Offset Calibration Error

Max. Full Scale Inaccuracy (% of full scale), all errors included

10 V ranges: ± 5 counts max. 5V ranges: ± 9 counts max.

0.08% @ 25°C 0.26% @ 60°C

Accuracy vs. Temperature

± 50 ppm/°C full scale calibration change

Master Update Rate

8 channels per scan max.

Input Points Required

256 discrete pts. or 8 dwords (32-bit words) (Network Interface Dependent)

Max. Full Scale Inaccuracy (% of full scale) All errors and temp drift included

10V ranges: ± 0.2% @ 25°C ± 0.4% @ 60°C 5V ranges: ± 0.3% @ 25°C ± 0.5% @ 60°C

Base Power Required

75 mA @ 5 VDC

Master Update Rate

4 channels per scan max.

External Power Supply

21.6-26.4 VDC, 70 mA, class 2

Weight

136 g

Output Points Required

128 discrete pts. or 4 Dwords (32-bit words) (Network Interface Dependent)

Equivalent Input Circuit

NOTES: 1: Shields should be grounded at the signal source. 2: Unused inputs should be connected to common (0 VDC). 3: More than one external power supply can be used, provided all the power supply commons are connected.

tFED-97

Universal Field I/O

Equivalent Output Circuit

NOTES: 1: S  hields should be connected to the 0V terminal of the module or the 0V of the power supply. 2. Unused current outputs should remain open (no connections) for minimum power consumption.