Edison Fuses – Dual Element J Class - AutomationDirect.com

25 downloads 119 Views 2MB Size Report
An understanding of circuit types and circuit protection products is critical to ensure their ... Ideal replacement for fuses that are applied as supplementary protec-.
For latest prices, please check AutomationDirect.com

Dual Element Time-Delay Class J Fuses EDISON JDL Class J fuses are among the most popular current limiting time-delay fuses available. Their small physical size and high performance characteristics make Class J fuses ideal for any space-limited application.

JDL5

JDL40

JDL Features

JDL150

Self-Certified Interruptin Rating: 300,000 RMS Symmetrical Amps

• UL Listed, Class J, Guide JDDZ, File E162363 • CSA Certified HRCI-J per C22.2, No. 248.8

CROSS REFERENCE

AJT

LITTELFUSE

LPJ

MERSEN GOULD

BUSSMANN

EDISON

VOLTS

600 JDL

JTD URRENT LIMITING

JDL Dimensions inches (mm) DIMENSIONS Cat No. JFL and JDL, Class J

35-60 70-100 110-200 225-400 450-600

Barrel Length D – – 2-5/8 3 3-3/8 3-314

Blade Thickness E – – 1/8 3/16 1/4 3/8

Blade Width F – – 3/4 1-1/8 1-5/8 2

Mounting Hole Spacing G H J – – – – – – 1/2 3-518 3/8 11/16 4-3/8 3/8 15/16 5-1/4 17/32 1 6 11/16

JDL Series Dimensions - Inches [mm]

A

B

2.25 0.81 [57.15] [20.6] 2.38 1.06 [60.5] [26.92] 4.63 1.13 [117.5] [28.6] 5.75 1.63 [146.1] [41.3] 7.13 2.13 [181] [54] 8 2.5 [203.2] [63.5]

K – – 9/32 9/32 13/32 17/32

Blade Width

1-30

Blade Length C – – 1 1-3/8 1-7/8 2-1/8

Blade Thickness

Range

Max. Dia. B 13/16 1-1/16 1-1/18 1-5/8 2-1/8 2-5/8

C

D

E

F

G

H

J

K

















Barrel Length

Overall Length A 2-1/4 2-3/8 4-5/8 5-3/4 7-1/8 8

Blade Length

Ampere Rating Range 1-30 35-60 70-100 110-200 225-400 450-600

Max. Dia.

Circuit Protection

Interrupting Rating: 200,000 RMS Symmetrical Amps

Agency Approvals

• Recommended for Type 2 (no damage) protection of IEC style motor starters and contactors. • Use to protect lower interrupting rated circuit breakers. • All general purpose circuits with inductive (high inrush) loads, including motor and motor branch circuits, and transformer circuits. Also suitable for lighting loads.

Overall Length

tCPR-142

Ampere Rating: 1–600 Amps

Current Limiting: Class J Fuse

Applications

Ampere Rating

Rated Part AMP Voltage Pcs/ Package Price Number Rating Pkg Weight AC Max 1 $129.00 JDL1 2 $129.00 JDL2 3 $129.00 JDL3 4 $135.00 JDL4 5 $129.00 JDL5 6 $129.00 JDL6 8 $135.00 JDL8 1.00 lb. $129.00 JDL10 10 $135.00 JDL12 12 $129.00 10 JDL15 15 $135.00 JDL17-5 17.5 $129.00 JDL20 20 $129.00 JDL25 25 $129.00 JDL30 30 $228.00 JDL35 35 $228.00 JDL40 40 $228.00 JDL45 45 2.00 lb $228.00 JDL50 50 600V 60 $228.00 JDL60 70 $228.00 JDL70 $228.00 JDL80 80 5 1.70 lb $244.00 JDL90 90 $228.00 JDL100 100 $96.00 JDL110 110 $90.00 JDL125 125 $96.00 4.25 lb JDL150 150 $97.00 JDL175 175 $90.00 JDL200 200 $162.00 JDL225 225 $152.00 1 JDL250 250 1.70 lb $190.00 JDL300 300 $165.00 JDL350 350 $152.00 JDL400 400 $253.00 JDL450 450 $253.00 2.80 lb JDL500 500 600 $253.00 JDL600

Voltage Rating: JDL - 600 VAC

Self-Certified DC Ratings: Voltage Rating: JDL - 300 VDC Interrupting Rating: JDL - 20,000 Amperes DC

• Space saving dimensions compared to Class R • Dual-Element construction provides superior time-delay to pass harmless motor or transformer surges • High performance with fatiguefree cycling capabilities • Extremely current limiting

JDL Series Dual-element Time-delay Fuses

Specifications

Mounting Hole Spacing

















1 [25.4] 1.38 [34.9] 1.88 [47.8] 2.13 [54]

2.63 [66.7] 3 [76.2] 3.38 [85.8] 3..75 [95.3]

0.13 [3.2] 0.19 [4.8] 0.25 [6.35] 0.38 [9.5]

0.75 [19.1] 1.13 [28.6] 1.63 [41.3] 2 [50.8]

0.5 [12.7] 0.69 [17.5] 0.94 [23.8] 1 [25.4]

3.63 [92.1] 4.38 [111.1] 5.25 [133.4] 6 [152.4]

0.38 [9.5] 0.38 [9.5] 0.56 [14.3] 0.75 [19.1]

0.28 [7.1] 0.28 [7.1] 0.41 [10.3] 0.53 [13.5]

1 - 8 0 0 - 633 - 0 4 0 5

For latest prices, please check AutomationDirect.com

Dual Element Time-Delay Class J Fuses Current Curves

600A

Ampere Rating

200

40,000 30,000

100 80 60

10 7 6 3

20,000 10,000 8,000 6,000

AMPERE RATING 60, 000 80, 000 100, 000

100

30, 000 40, 000

.1 .08 .06

20, 000

200

100

.2

400 300

6, 000 8, 000 10, 000

.4 .3

3, 000 4, 000

1 .8 .6

1,000 800 600

2, 000

2

A

2,000

600 800 1, 000

4 3

4,000 3,000

300 400

10 8 6

1

200

20

200, 000

40 30

TIME IN SECONDS

B

100,000 80,000 60,000

INSTANTANEOUS PEAK LET-THRU CURRENT IN AMPS

400A

200A 225A

125A

100A

15A 20A 30A 40A 50A 60A

300

10A

Cat. No. JDL (Amp) 600V

5A

Cat. No. JDL (Amp) 600V 3A

PEAK LET-THROUGH CURRENT CURVES

1A

AVERAGE TIME/CURRENT CURVE

RMS SYMMETRICAL CURRENTS IN AMPERES A–B=ASYMMETRICAL AVAILALBE PEAK (2.3 X SYMM RMS AMPS)

.04 .03

4,000 3,000

AMPERE RATING

2,000 1,000 800 600 400 300

A

200, 000

60, 000 80, 000 100, 000

30, 000 40, 000

20, 000

6, 000 8, 000 10, 000

3, 000 4, 000

100

2, 000

200

600 800 1, 000

400A 600A — —± — — 4,400 — 5,540 8,000 6,420 9,000 7,000 10,000 7,500 11,100 8,000 11,800 8,330 12,500 9,000 13,270 9,380 13,820 10,000 15,000 11,270 16,000 12,180 17,270 14,360 19,270 15,820 20,600

100 60 50 40 30 20 15

10,000 8,000 6,000

300 400

1,000 3,000 5,000 10,000 15,000 20,000 25,000 30,000 35,000 40,000 50,000 60,000 80,000 100,000 150,000 200,000

Let-Thru Current (Apparent RMS Symmetrical) JDL (600V) Fuse Ratings 15A 30A 60A 100A 200A 270 470 750 — — 370 670 1,130 1,640 2,360 450 800 1,420 1,910 2,760 550 1,000 1,730 2,450 3,520 625 1,220 1,890 2,850 4,000 700 1,330 2,120 3,090 4,400 750 1,440 2,250 3,400 5,000 800 1,530 2,370 3,650 5,140 820 1,600 2,580 3,780 5,430 900 1,640 2,670 4,000 5,640 925 1,760 2,790 4,470 6,000 1,000 1,850 3,000 4,670 6,420 1,160 2,000 3,220 5,000 7,400 1,220 2,150 3,520 5,360 7,950 1,400 2,460 4,000 6,170 9,000 1,560 2,640 4,450 7,000 10,000

200

20,000

200

*Prosp. S.C.C.

600 400

40,000 30,000

100

Current-Limiting Effects

B

100,000 80,000 60,000

INSTANTANEOUS PEAK LET-THRU CURRENT IN AMPS

3,000 4,000

6,000 8,000 10,000

RMS SYMMETRICAL CURRENT IN AMPERES

2,000

600 800 1,000

300 400

200

60 80 100

30 40

20

6 8 10

3 4

1

.01

2

.02

RMS SYMMETRICAL CURRENTS IN AMPERES A–B=ASYMMETRICAL AVAILABLE PEAK (2.3 X SYMM RMS AMPS)

*RMS Symmetrical Amperes Short-Circuit Current. NOTE:Data derived from Current Limiting Curves.

w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n

Circuit Protection

tCPR-143

For latest prices, please check AutomationDirect.com

Selection Guide Line Overview

The fuse selection guide below is a general summary of the specifications included for each fuse type. This selection guide does not include the many variables that can exist for specific situations such as local codes, unusual temperature, or other operating conditions. When selecting fuses, be sure to comply with any applicable PUBLIC SAFETY standards that apply to Overcurrent Protection Devices (OPD).

The Edison family of fuses, fuse blocks and fuse holders is divided into two classes: 1. Current Limiting: Class CC, Class J, Class L, Class RK, Class T 2. General Purpose: Class M Midget and Small Dimension

Edison Fuses Selection Guide and General Specifications Description

Class J Fuse Type Fast-Acting Time-Delay Part Number JHL JDL Voltage Rating

600VAC 450VDC

Amp Rating Interrupting Rating Current Limiting

Agency Approvals

Dimensions

Current Limiting Class RK1 Class T

Class RK5

Time-Delay

ECNR

ECSR LENRK LESRK

TJN

250VAC 250VAC VDC* 125VDC* 600VAC 125 600VAC 600VAC 300VAC (1-200A) 300VDC* (10-60A) 300VDC* 160 VDC 300VDC* 250VDC* 250VDC* (15-600A) (201-600A) (70-600A)

1 - 600

1 - 600

3 - 600

Class L

Extremely Fast-Acting

10 - 600

5 - 600

Class CC

Fast-Acting Fast-Acting

TJS

LCU

HCLR

600VAC

600V

600VAC 300VDC (15-20A)

1 - 600

601 - 1200

0.5 - 30

Time-Delay

HCTR

EDCC

600VAC 600VAC 300VDC (0.5-2.25A) (20–30A) 0.25 - 30

0.5 - 30

200,000 RMS Symmetrical Amps Class J

Class RK5

Class RK1

Class T

Class L

Class CC

UL Listed Class J UL Listed Guide JDDZ Class J UL Listed, File E162363 Guide JDDZ UL Listed, Class RK, Guide JDDZ, UL Listed, Class T, Std. 248-10 UL Listed to 248.4, Class CC, CSA Certified File E162363 File E162363 Guide JDDZ, File E162363 CSA Certified, Guide JDDZ, File E162363, HRCI-J per CSA Certified CSA Certified HRCI-R per C22.2, No. 248.12, CSA Certified HRCI-T per HRC-L C22.2 certified HRCI-MISC per C22.2 C22.2, HRCI-J per File 700489 C22.2, No. 248.12, File 53787, No. 248.10, CSA No. 248.8 C22.2, No. (LENRK CSA File 053787) Class 1422-02 & 1422-82 Class 1422-02, No. 248.4, File 700489 File 700489 248.8 File 53787 RoHS File 700489 compliant See product specification pages. ferrule (in): 13/32, length (in): 1-1/2

* Self-certified DC ratings

Edison Fuses Selection Guide and General Specifications Description

General Purpose – Midget

Fuse Type

Fast-Acting

Part Number

MCL

MOL

Time-Delay

MEQ

MEN

General Purpose – Small Dimension Electronic Fast-Acting Ceramic

ABC

250 VAC to 30A) 600 VAC 250 VAC 500 VAC 250 VAC (0.5 125VDC: (0.5 to 30A)

Voltage Rating

Amp Rating 0.5 to 50 0.5 to 30 0.25 to 30 0.5 to 30 Interrupting 100,000 10,000 RMS Amps RMS Amps Rating Current N/A Limiting

Agency Approvals

UL Listed to 248.14, File E162443 CSA Cert. C22.2 Part 59.2, LR 700489

0.5 to 30

Fast-Acting Glass

AGC

GMA

250VAC: 250VAC (0.1 to 10A) (0.063 - 3A) 32VAC: 125VAC (15 to 30A) (4 - 15A) 0.10 to 30

0.063 to 15

Medium Time- Time-Delay Time-Delay Fast-Acting Delay Glass Ceramic Glass Glass

TimeDelay Glass

GMC

MDA

MDL

S500

S506

250VAC (0.5 - 3A) 125VAC (4 - 10A)

250VAC 125VDC (20A)

250VAC: (0.0625 to 8A) 32VAC: (10 to 20A)

250VAC

250VAC

0.5 to 10

0.5 to 20

0.0625 to 20

0.032 to 10

0.25 to 6.3

See specifications table on product pages N/A UL Listed standard 248-14 UL Listed Guide and File nos. Designed to UL/CSA 248-14 (ABC 0.25-20 A): UL Listed, Guide JDYX, File (AGC 1/100-10 A) E19180 63mA-6A JDYX and E19180 UL Recognition Guide and UL Recognition, Guide JDYX2, File nos. (ABC 20-30A):(AGC File E19180, 7A-15A 11-30) CSA Certified, File JDYX2 and E19180 053787_C_000, CSA Certification Record No: 63mA-6A Class 1422-01 053787 C 000 and Class No: 1422 01 and 1422 30

UL Listed standard 248-14 UL Listed Card: MDA 2/10-20A , MDL 1/16-8A (Guide JDYX, File E19180 UL Recognized Card: MDA 25-30A MDL 9-30A (Guide JDYX2, File E19180) CSA Certification Card: MDA 2/10-15A (Class No. 1422-01)

 L Recognized Guide U JDYX2, File E19180 Semko Approval VDE Approval BSI Approval IMQ Approval RoHS compliant

RoHS

Dimensions ferrule (in): 13/32 length (in): 1-1/2

tCPR-140

Circuit Protection

1/4” x 1-1/4”, (6.3mm x 32mm)

0.197” x 0.788” (5mm x 20mm)

1/4” x 1-1/4”, (6.3mm x 32mm)

0.197” x 0.788” (5mm x 20mm)

1 - 8 0 0 - 633 - 0 4 0 5

For latest prices, please check AutomationDirect.com

Modular Ferrule Fuse Blocks for Class J Fuses Description

Agency Approvals

JM Series for use with Class J fuses JHL & JDL

Fuse Blocks • UL® Listed E14853 - IZLT • CSA® Certified 47235-6225-01 • CE • RoHS Compliant • Conflict mineral free • REACH Compliant Covers • Covers are included in the overall UL Listing/Recognition and CSA Certification • IP20 finger-safe • RoHS compliant • REACH Compliant

Mounting 35mm DIN rail or panel mount

Specifications Materials: Base – Thermoplastic Terminals – Tin-plated copper brass Covers – Thermoplastic Screws and pressure plates – Zinc-plated steel SCCR: 200kA Flammability rating: Blocks – UL 94V0, self-extinguishing Covers – UL 94HB, self-extinguishing Operating and storage temp range: Blocks – -40° to 120°C [-40° to 248°F] Covers – indicating -20° to 90°C [-4° to 194°F] non-indicating -40° to 120°C [-40° to 248°F] Wire: Cu – 75°/90°C [ 167°/194°F] Al – 75°C [167°F] Ring or Fork terminal to fit a #10-32 screw

R

2011/65/EU

To obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number's web page.

Clear IP20 finger-safe cover (sold separately)

Patented lockout / tagout

Modular dove-tail design for tool-less snap together assembly

Test probe holes

DIN Rail or panel mount

Box lug Compact Footprint

Box lug

Pressure Plate

Box lug

Pc/ Price Volts Amps Part Number pkg JM60030-1CR JM60030-2CR JM60030-3CR JM60030-1PR JM60030-2PR JM60030-3PR JM60060-1CR JM60060-2CR JM60060-3CR

Poles

Type

Modular Ferrule Fuse Blocks for Class J Fuses

1

$16.00

1

1

$31.25

2

1

$46.00

1

$15.75

1

$31.00

1

$46.75

1

$18.75

1

$36.50

1

$47.00

30 600V AC/DC

3

Wire Range solid and stranded 14-2 AWG (Cu) 8-2 AWG (Al)

Torque

1

0.15 [0.08]

2 18-10 AWG (Cu) 18-10 AWG

20 [2.3]

0.25 [0.12]

50 [5.6] 45 [5.1] 40 [4.5] 35 [4.0]

0.20 [0.10]

3 1 60

2 3

Wt.

fine stranded lb·in [N·m] lb [kg] (Cu) 3-2 AWG 50 [5.6] 0.15 [0.08] 6-4 AWG 45 [5.1] 0.25 [0.12] 8AWG 40 [4.5] 14-10 AWG 35 [4.0] 0.40 [0.18]

Covers (sold separately) w/o Indication

w/ Indication¹

Pc/ pkg

CVR-J-60030 CVRI-J-60030

1

CVR-J-60060 CVRI-J-60060

1

$5.00

$6.50

0.40 [0.18] 14-2 AWG (Cu) 8-2 AWG (Al)

3-2 AWG 6-4 AWG 8AWG 14-10 AWG

0.35 [0.16] 0.55 [0.26]

$6.00

$7.00

¹ Open fuse indication requires 90V minimum and closed circuit to operate.

tCPR-196

Circuit Protection

1 - 8 0 0 - 633 - 0 4 0 5

For latest prices, please check AutomationDirect.com

Modular Ferrule Fuse Blocks for Class J Fuses Dimensions in [mm]

JM60030

JM60060

Please see our website www.AutomationDirect.com for complete engineering drawings. Dimensions are approximate. Not for construction purposes.

w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n

Circuit Protection

tCPR-197

For latest prices, please check AutomationDirect.com

Fuse Blocks for Class J Fuses Description

Specifications

For use with Edison JDL class J fuses

Construction: T hermoplastic, UL Flammability; 94V-0

Terminal type: • C = Box lug type • CR = Box lug type, with retaining clip • P = Pressure plate. Clip reinforcin springs are standard on fuseblocks rated 100A and above.

Voltage Ratings: 600 Volts AC Ampere Ratings: 0.50 - 600 Amps Short-circuit current Rating: 200,000 RMS Symmetrical Amps

Agency Approvals • UL Listed, UL 512, Guide IZLT, File E14853 • CSA, certified, C22.2 No. 39, Class 6225-01, File 47235

J60060-1C

Class J Fuse Blocks Part Number J60030-1P J60030-2P J60030-3P J60060-1C J60060-2C J60060-3C J60100-1CR J60100-3CR J60200-1CR J60200-3CR J60400-1CR J60400-3CR

J60030-2P

Maximum Wire Size

Amps Poles

Wt. Fig # Pcs/ Pkg (lbs.) Price

1 0.5 to 30

31 to 60

61 to 100 101 to 200 201 to 400

J60600-3CR* 401 to 600

2

#10-14 Cu

1

0.44

$18.50

2

0.35

$32.00

3

3

0.45

$48.50

1

1

0.44

$20.50 $39.00

2

2

0.35

3

3

0.55

$50.00

1

4

0.98

$34.50

3 1 3 1 3 3

#2-14 Cu-Al

1/0-8 Cu-Al 250MCM-6 Cu-Al 500MCM-4 Cu-Al (2) 500MCM-4/0 Cu-Al

1

5

1.55

$89.00

6

1.70

$133.00

9

6.70

$396.00

7

3.10

$202.00

10

14.0

$568.00

11

8.0

$969.00

* Not UL

Class J Fuseholder Dimensions

J60030-3P

0.5 Amp to 60 Amp 2.42 [61.3]

1.70 [43.2] .75 [19.1]

3.20 [81.3] 2.25 [57.2]

4.70 [119.4]

2.28 [58] .30 [7.62]

2.25 [57.2]

.75 [19.1]

C L

CL

4.01 [102]

6.28"

[160

1.50 [38.1]

Figure 1

Figure 2

Figure 3

Note: All dimensions shown in inches [mm]

tCPR-198

Circuit Protection

1 - 8 0 0 - 633 - 0 4 0 5

For latest prices, please check AutomationDirect.com

Fuse Blocks for Class J Fuses

0 3]

2]

4.70

.75 [19.1]

2.28 [58] .30 [7.62]

61 Amp[119.4] to 100 Amp 2.25 [57.2]

[49.4]

.94 [23.8]

[38.1]

1.58 [40.1]

5 [127]

[5.6]

[12.7]

C L

CL

4.01 [102]

6.28"

.22 [5.6] Dia. .5 [12.7] C'Bore

[160]

3.14 [79.8] 1.50 [38.1]

101 Amp to 200 Amp

2 [50.8] 3.06 [77.7]

Figure 4 3.1 [78.7]

3 [76.2] .5 [12.7]

Figure 5 3.15 [80]

.344 [8.74] dia. hole through .750 [19.1] dia. c'bore

6.13 [155.7] 1.69 [42.9]

.34 [8.6] dia.

201 Amp to 400 Amp

3.5 [88.9] 7.5 [191]

.750 [19.1]

Figure 7

Figure 6 3 [76.2] 1.75 [44.5]

1.5 [38.1]

8.31 [211.1] 7.00 [177.8]

.75 [19.1] .31 [7.8]

.75 [19.1] c'bore

6.13 [155.7]

1.75 [44.5]

4 [101.6] 1 [25.4]

.625 [15.9]

10.51 [267] 9.00 [228] 6.00 [152.4]

.56 [14.2]

4.00 [101.6]

7.50 [191]

.75 [19.1] c'bore .34 [8.6] dia.

.344 [8.7] dia. hole through .750 [19.1] dia. c'bore

2.0 [50.8]

.5 [12.7]

Figure 9

Figure 8

.50 [12.7]

1.00 [25.4]

401 Amp to 600 Amp 4 [101.6] 1.75 [44.5]

4.99 [126.7] 1.125 [28.6]

14.144 [359.3] 11.00 [279.4]

1 [25.4] .56 [14.2]

4.99 [126.7]

3.25 [82.6] 8.875 [225.4]

2.38 [60.5]

.75 [19.1] c'bore .34 [8.6] dia.

Figure 10

8.88 [226] 2.88 [73.2]

Note: All dimensions shown in inches [mm]

w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n

.344 [8.7] dia. hole through .750 [19.1] dia. c'bore

Figure 11

.50 [12.7]

1.00 [25.4]

Circuit Protection

tCPR-199

For latest prices, please check AutomationDirect.com

Modular Fuse Holders for Class J Fuses

CH30J3

CH30J2I

CH30J1

Description

Specifications

• Choice of LED indicator or non-indicating fuse holder • Comes in standard 1-, 2- and 3-Pole ganged assemblies where all fuses are extracted simultaneously • Meets requirements of IEC 60529 for IP-20 finger safe rating • 35 mm DIN rail and chassis (6-32 UNC Pan Head recommended) mounting features • Fuseholder wire ports dual wire rated from 18 to 3 AWG

Agency Approvals • Listed UL 512, Guide IZLT, File E14853 • CSA Certified per C22.2 Nos. 39 Class 6225-01, File LR47235 • CE compliance for the European Union Low Voltage Directive

Construction: Thermoplastic, with tin-plated copper clip UL Flammability: 94V-0 Voltage Ratings: 600 Volts AC Ampere Ratings: 1 - 60 Amps Interrupting Rating: 200,000 RMS Symmetrical Amps Minimum Indicating Voltage (neon lamp): 90 Volts Nominal Operating Current (neon lamp): 34 mA (460 VAC)

CH Series Modular Fuse Holders for Class J Fuses Amp Part Rating Number CH30J1 CH30J2 CH30J3 30A CH30J1I CH30J2I CH30J3I CH60J1 CH60J2 CH60J3 60A CH60J1I CH60J2I CH60J3I

Amps

0.5 to 30

31 to 60

Type

Poles

A B C D E F G H

tCPR-200

CH30J in (mm)

Weight (lbs.)

Price

Easy ID window

1

6

$126.00

2

3

$176.00

Easy ID window

3

2

Neon indicator

1

6

Neon indicator

2

3

$202.00

Neon indicator

3

2

$193.00

Easy ID window

1

6

$170.00

Easy ID window

2

3

$199.00

Easy ID window

3

2

Neon indicator

1

6

Neon indicator

2

3

$237.00

Neon indicator

3

2

$215.00

18 -1 AWG Single 18 -3 AWG Dual 75°C

$172.00

2.8

$148.00

$203.00

3.4

E

$191.00

H

G

CH60J in (mm)

1.28 (32.5)

1.58 (40.0)

2.56 (65.0)

3.16 (80.0)

3.84 (97.5)

4.72 (120.0)

4.59 (116.6)

4.88 (124.0)

2.83 (71.8)

3.31 (84.1)

3.56 (90.4)

3.85 (97.9)

1.28 (32.5)

1.58 (40.0)

0.18 (4.44)

0.18 (4.44)

Circuit Protection

Pcs/Pkg

Easy ID window

Dimensions Dimension

Maximum Wire Size

D F

3 POLE CLASS J Modular Fuse Holder

30A AND 60A Ganging Assembly

A

B C

1 - 8 0 0 - 633 - 0 4 0 5

For latest prices, please check AutomationDirect.com

Accessories Accessories Part Number

Description

FP-2

Fuse puller for fuse dia. 13/32” - 13/16”. Fuse type: 0-60A, 250V; 0-30A, 600V Multi-pole connection kit to connect new design multiple Class CC and Midget Class fuse holders together. Kit consists of 6 connectors and 3 handle pins to connect up to 4 fuse holders.

JV-L* (Not Field Installable)

Pcs/Pkg Price 1

$16.50 $6.50

Note: Will not work with retired design fuse holders shipped before November 1, 2009. *Roll pin punch or installation tool is required to install handle pins (Tool not sold by Automationdirect.com).

FP2

Handle Pin Dimensions Diameter = 0.0625 in [1.58 mm] Length = 0.632 in [16.07 mm]

JV-L JV-L

w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n

Circuit Protection

tCPR-223

For latest prices, please check AutomationDirect.com

Cross Reference Guide CROSS REFERENCE GUIDE By manufacturers type reference or series number. Ampere ratings must be added for ordering purposes. FUSE TYPE

VOLT EDISON

BRUSH/ BUSSMANN MERSEN / GEC/CEFCO LITTELFUSE DORMAN GOULD

UL CLASS CURRENT LIMITING FUSES (CSA CLASS) CC (HRCI-CC)

RK1 RK5 J T

Time-Delay

600

EDCC



LP-CC

ATDR



CCMR

Time-Delay

600

HCTR



FNQ-R

ATQR



KLDR

Fast-Acting

600

HCLR

HCLR

KTK-R

ATMR

CTK-R

KLKR

250

LENRK



LPN-RK-SP

A2DR



LLNRK

600

LESRK



LPS-RK-SP

A6DR



LLSRK

250

ECNR



FRN-R

TR



FLNR

600

ECSR



FRS-R

TRS



FLSR

Time-Delay Dual Element 600

JDL



LPJ

AJT



JTD

High-Speed AC Drive

600

JHL



DFJ

HSJ





300

TJN



JJN

A3T



JLLN

600

TJS



JJS

A6T



JLLS

Time-Delay Dual Element Time-Delay Dual Element

Extremely Fast-Acting

UL CLASS GENERAL PURPOSE FUSES 600

MCL

MCL

KTK

ATM

CTK

KLK

250

MOL

MOL

BAF/BAN

OTM



BLF

500

MEQ

MEQ

FNQ

ATQ



FLQ

250

MEN

MEN

FNM

TRM



FLM

250/125 ABC

ABC

ABC

GAB



314

250/32 AGC

AGC

AGC

GGC



312

250

MDA

MDA

MDA





326

250/32 MDL

MDL

MDL

GDL



313

Fast-Acting

250/125 GMA

GMA

GMA

GGM



235

Medium Time-Delay

250/125 GMC

GMC

GMC

GSC





Fast-Acting

250

S500

BDB

GDB

GSB



217

Time-Delay

250

S506

BDC

GDC

GDG



218

FP-2







Fast-Acting Midget Time-Delay 1/4”x 1-1/4” Ceramic 1/4”x 1-1/4” Glass 1/4”x 1-1/4” Ceramic 1/4”x 1-1/4” Glass 5x20 mm Glass 5x20 mm Glass

Fast-Acting Time-Delay

Fuse Puller Fuse Puller FP-2

tCPR-224

Circuit Protection



old - 38072 – new - FP-2

1 - 8 0 0 - 633 - 0 4 0 5