Electronic controllers & PI controllers All our know-how is now yours
Index 3
ECA 9010 override module
6
ECL Apex 20
14
ECA 61 remote control
18
ECL Comfort 110
26
ECL Comfort 210 controller and remote control unit ECA 30 / 31
50
ECL Comfort 310 controller and remote control unit ECA 30 / 31
90
ST-1/ST-2
93
Temperature sensors (Pt 1000)
Electronic Controllers ECA 9010 override module ECL Apex 20 ECA 61 remote control ECL Comfort 110 ECL Comfort 210 controller and remote control unit ECA 30 / 31 ECL Comfort 310 controller and remote control unit ECA 30 / 31
Data sheet
ECA 9010 override module Application
The override module ECA 9010 is used for the override of the clock in the ECL Comfort 200 controller (with the ECL Cards P20 and P30) as well as ECL Comfort 300 (with the ECL Cards C14, C25, C35, C37, C47, C55, C60, C62, C66, C67 and C75). The module can override periods with comfort temperature to periods with setback temperature or vice versa. The override signal can be activated by means of a normal on-off switch (make- function).
Delimitations
The function is only possible if the controller version is 1.06 or higher. The version of the controller can be seen on the back of the controller.
A vacant sensor terminal could be available in systems without a room temperature sensor S2 connected to terminal 18 or a return temperature sensor connected to terminals 20/22.
Furthermore, a vacant sensor terminal is required. Function The override function is only active if the controller mode of the ECL Comfort controller is set to scheduled operation (automatic change-over to and from periods with comfort or setback temperature)
Setting of service parameter line 141 in the ECL Comfort controller Override, sensor signal ECL Comfort 200: OFF, 1, 2, 3 or 4 ECL Comfort 300: OFF, 1, 2, 3, 4, 5 or 6 1, 2, 3, 4, 5 or 6 refer to sensors S1, S2, S3, S4, S5 or S6.
Comfort
Setback
When terminal 2 and 3 of the module is short-circuited by means of an external switch, the clock in the controller is overridden to comfort temperature, and when terminal 1 and 3 is short-circuited, the clock is overridden to setback temperature.
DH-SM
VD.76.Y1.02 © Danfoss 10/2005
1
Data sheet Code no. and dimensions
ECA 9010 override module Type
Designation
Dimensions
Code no.
ECA 9010
Override module
L x W x H (mm) 50 x 35 x 18
087B3081
Mounting
Wiring Max. cable length between the override switch and the ECA 9010 is 100 m.
Override switch
Max. 100 m
2
VD.76.Y1.02 © Danfoss 10/2005
DH-SM
Data sheet
ECL Apex 20 controller and ECA 20 (ECL Apex Web Panel)
Description
ECA 20 (ECL Apex Web Panel) ECL Apex 20 The ECL Apex 20 and the ECA 20 (ECL Apex Web Panel) are used in large district heating applications. The products are designed and produced by the company Saia-Burgess.
Pressure input signals are based on 0 - 10 V. Activation of the motorized control valves is based on 0 - 10 V signals. Activation of the pumps is based on relay outputs.
The ECL Apex 20 is a free programmable controller (FPC / PLC) for temperature and pressure control as well as monitoring of district heating systems.
The advantages of the ECL Apex 20 are among others: • Free programmable controller • Flexible input and output configuration and extension • Flexible communication possibilities • Onboard web server • Web panel, with touch screen in colours, serves as display and is separated from the controller.
The ECL Apex 20 is operated by means of either a PC or the ECL Apex Web Panel. Temperature input signals are based on Pt 1000 or 0 - 10 V.
The ECL Apex 20 is to be placed inside a panel.
Application Example 1:
All the mentioned components (SF = flow meter, SP = pressure sensor, ST = temperature sensor, P = pump, M = motorized control valve) are wired to the ECL Apex 20.
DEN-SMT/DK
VD.KT.V2.02 © Danfoss 12/2010
1
Data sheet
ECL Apex 20 controller and ECA 20 (ECL Apex Web Panel)
Application Example 2:
All the mentioned components (SF = flow meter, SP = pressure sensor, ST = temperature sensor, P = pump, M = motorized control valve) are wired to the ECL Apex 20.
Ordering
ECL Apex 20 controller and ECA 20 (ECL Apex Web Panel) Type
Designation
Code No.
ECL Apex 20
Controller (Saia-Burgess: PCD2.M5540 equipped with one G4 I/O module). Supplied with the product: • Battery (CR 2032) for time back-up • Mounting Guide • Connectors (with numbers) for power etc.
087B2506
ECA 20, ECL Apex Web Panel
ECL Apex Web Panel (Saia-Burgess: PCD7.D457STCF Micro-Browser Panel) Supplied with the product: • Mounting Guide • Connector plug for power / RS 485 • 4 x fixing screws for mounting in the cut-out in panel front
087B2504
Type
Designation
Code No.
Saia-Burgess standard modules
PCD2.E110 (input, 8 x digital) PCD2.E165 (input, 16 x digital) PCD2.A200 (output, 4 x relays, NO) PCD2.A220 (output, 6 x relays, NO) PCD2.W200 (input, 8 x 0 - 10 V.) PCD2.W220 (input, 8 x Pt 1000 temperature sensor) PCD2.W400 (output, 4 x 0 - 10 V) PCD7.D3100E (display for insertion in the ECL Apex 20)
*)
Saia-Burgess memory module
PCD7.R551M04 (flash memory, 4 MB)
*)
Saia-Burgess extension housing
PCD2.C2000 Use PCD2.K106, connection cable between ECL Apex 20 and extension housing
*)
Extension modules
*) To be purchased at the local Saia-Burgess representative at agreed conditions
2
VD.KT.V2.02 © Danfoss 12/2010
DEN-SMT/DK
Data sheet
ECL Apex 20 controller and ECA 20 (ECL Apex Web Panel)
Ordering (continued)
Accessories Type
Designation
Code No.
Connection cable
PC - ECL Apex 20: (USB male, type A --- USB male, type B). To be purchased at a computer accessory shop.
*)
Connection cable
ECL Apex 20 - Web Panel: Ethernet cable or 9 pole D-socket to 9-pole D-socket, “Null Modem Cable”. To be purchased at a computer accessory shop.
*)
PG5
Programming Software. To be purchased at a local Saia-Burgess representative at agreed conditions.
*)
‘) Not supplied by Danfoss
Pt 1000 temperature sensors (1000 ohm / 0 oC) Type
Designation
Code No.
ESMT
Outdoor temperature sensor
084N1012
ESM-10
Room temperature sensor
087B1164
ESM-11
Surface sensor
087B1165
ESMB-12
Universal sensor
087B1184
ESMC
Surface sensor incl. 2 m cable
087N0011
ESMU-100
Immersion sensor, 100 mm, copper
087B1180
ESMU-250
Immersion sensor, 250 mm, copper
087B1181
ESMU-100
Immersion sensor, 100 mm, stainless steel
087B1182
ESMU-250
Immersion sensor, 250 mm, stainless steel
087B1183
Technical data
DEN-SMT/DK
ECL Apex 20
ECA 20 Web Panel
Supply voltage Must be a class 2 transformer (double isolated)
24 V d.c., +25% / -20%, min. 0.6 A
24 V d.c., +30% / -20%, min. 0.6 A
Ambient temperature
Placed on vertical surface: 0 - 55 °C Other positions: 0 - 40 °C
0 - 50 °C
Storage temperature
-20 - 85 °C
-20 - 70 °C
Humidity
10 - 95% RH, without condensation
5 - 95% RH, without condensation
IP class
IP 20 (to be mounted in a protection panel)
IP 65 (from front when mounted in a panel)
Enclosure, material
PC / ABS
PC / steel
Mounting
On 2 x top hat rails of each 35 mm width, In a cut-out mounted in parallel or with 4 x M4 screws
Data and clock backup
Lithium battery CR 2032
Max. input / output
1024 (when PCD2.C2000 extension housings are used)
Max. input / output modules
61 (G4 I/O module incl.)
Weight
0.95 kg + (5 modules x 0.04 kg) = 1.15 kg
- marking in accordance with the standards
EMC-Directive: 2004/108/EC, EN 61000-6-4, LVD-Directive: 73/23/EEC, 93/68/EEC, EN 61131-2
VD.KT.V2.02 © Danfoss 12/2010
1 kg
3
Data sheet
ECL Apex 20 controller and ECA 20 (ECL Apex Web Panel)
Software for programming
The ECL Apex 20 is programmed by means of the software PG5.
Programming methods offered: • S-Edit (instruction list) • GRAFTEC (sequential function chart) • FUPLA (function block diagram)
ECL Apex 20 controller, description
The ECL Apex 20 is delivered with a G4 I/O module containing 4 connectors: X11, X12, X13 and X14:
Slot 5: X12, digital input (DI), 10 x DI Slot 6: X13a, analog output (AO), 3 x 0-10 V X13b, analog input (AI), 5 x Pt 1000 Slot 7: X14, analog input (AI), 9 x 0-10 V or 0-20 mA
Slot 0: Empty Slot 1: Empty Slot 2: Empty Slot 3: Empty Slot 4: X11, digital output (DO), 5 x relays NO
Slots 0, 1, 2 and 3 can be used for additional modules.
G4 I/O module and numbering of slots
Electrical wiring
= Double isolated (double chamber)
ECA 20 (ECL Apex Web Panel), description
The ECL Apex Web Panel (Saia-Burgess: PCD7.D457STCF) has: • 5.7” STN touch screen with backlight • 256 colours • 640 x 480 pixels • 4 MB flash memory for local web server
4
VD.KT.V2.02 © Danfoss 12/2010
• • • • •
Saia-Burgess Micro-Browser RJ45 Ethernet communication RS 232 / RS 485 USB service port 24 V d.c. power input
DEN-SMT/DK
Data sheet
ECL Apex 20 controller and ECA 20 (ECL Apex Web Panel)
ECL Apex 20, connections
Service port (USB B-type), connection to PC
C1
Ethernet 1
C2
Com / PGU
ETH2
Ethernet 2
0…9
Port 2
S-Net / MPI
30 … 39
"User I/O"
10 … 19
Port 1
20 … 29
Supply 24 V dc Terminals 20 + 21 + 22 = + (plus) Terminals 23 + 24 = - (minus)
C3
I / O Bus extension
Type
Description
ModBus
The RS 485 port is used. A driver for ModBus must be downloaded to the ECL Apex 20 via the programming software PG5.
Remarks
Ethernet, RJ45
The communication between the ECL Apex 20 and the ECL Apex Web Panel as well as the internet.
USB connector
Service port (connection to the PC). For programming of the ECL Apex 20.
M-Bus
An RS 232 connection is established to an M-Bus master. The M-Bus master has the connection to the heat meters.
ECA 20 Web Panel, connections and communication
Ethernet
USB
Pin_1 : DCD Pin_2 : RX Pin_3 : TX Pin_4 : DTR Pin_5 : GND
The heat meters used in the application requires a driver, delivered by Saia-Burgess. The driver is downloaded to the ECL Apex 20.
Pin_6 : DSR Pin_7 : RTS Pin_8 : CTS Pin_9 : do not use
RS232
PS/2
Power RS485 Supply D /D GND 24 V DC GND GND
ECL Apex 20, communication
USB ETH1
1 2
X1
Possible connections
X2
X3
X4
3
4
5
6
X5
Type
Description
Remarks
X1
USB connection (B type) as Service Port
Upload of FirmWare program from PC
X2
Ethernet RJ45 connector as main (fast) communication
X3
RS 232 D-SUB 9 pole connector as printer output or S-BUS communication
Slower connection to ECL Apex 20
X4
PS/2 connection
Connection for example to a keyboard
X5
Combined connector for RS 485 / power input 24 V d.c.
Connection 1
PC x
Cable USB, A - B
2 3
ECL Apex 20 x
x
4
USB, A-B
Cable
Web Panel
x Ethernet cable
x
RS232 D-SUB 9 pole
x
x x
1 and 2 are typical connections
DEN-SMT/DK
VD.KT.V2.02 © Danfoss 12/2010
5
Data sheet
ECL Apex 20 controller and ECA 20 (ECL Apex Web Panel)
G4 I/O module X11, digital output (DO)
Output type
Relay contacts, NO (Normally Open), SPST (Single pole, single throw)
Number of outputs
5
Terminals
10 pcs. screw-type, each max. 2.5 mm²
Active output indication
One LED per output, green
Max. load
2 A at 250 V a.c., AC1 1 A at 250 V a.c., AC11 2 A at 50 V d.c., DC11 1 A at 24 V d.c., DC11
X12, digital input (DI)
X13a, analog output (AO)
X13b, analog input (AI)
6
VD.KT.V2.02 © Danfoss 12/2010
Built-in varistor for contact protection
Not present!
Input type
Switch
Number of inputs
10
Terminals
10 pcs. screw-type, each max. 2.5 mm²
Active input indication
One LED per input, red
Input activation
Source or sink operation
Logic "0"
-30 V < V.in < 5 V
Logic "1"
15 V < V.in < 30 V
Input current
4 mA per input at 24 V d.c.
Input delay
8 ms typically
Output type
0 - 10 V d.c.
Number of output
3
Terminals
8 pcs. screw-type, each max. 1.5 mm²
Resolution
12 bit
Max. load
3 K ohm
Accuracy, output signal
± 1% (= ± 50 mV)
Protection
Outputs protected against short-circuiting
Input type
Pt 1000 temperature sensor
Number of input
5
Terminals
6 pcs. screw-type, each max. 1.5 mm²
Connection cable
Shielded type, grounded at the ECL Apex 20
Input resistance
7.5 K ohm
Max. measuring current
1.5 mA
Over-voltage protection
+ / - 50 Volt
Conversion time
< 50 μsec
Resolution
10 bits
DEN-SMT/DK
Data sheet
ECL Apex 20 controller and ECA 20 (ECL Apex Web Panel)
X14, analog input (AI)
Input type
0 - 10 V / 0-20 mA
Number of input
9
Terminals
10 pcs. screw-type, each max. 2.5 mm²
Connection cable
Shielded type, grounded at the ECL Apex 20
Input resistance
20 K ohm
Over-voltage protection
+/-35 V
Resolution
10 bits
Connection examples
Example 1: 0 - 10 V d.c. control of AME electrical actuators
Example 2: 230 V a.c. control of circulation pump
ECL Apex 20, power connection
DEN-SMT/DK
VD.KT.V2.02 © Danfoss 12/2010
7
Data sheet Technical literature and additional information
ECL Apex 20 controller and ECA 20 (ECL Apex Web Panel)
Type
Description
Lit. No.
Technical manual, ECL Apex 20
The original Saia-Burgess Manual. 229 pages, 10 MB pdf file.
*)
Technical manual, ECA 20
The original Saia-Burgess Manual. 47 pages, 6.5 MB pdf file.
*)
Demo applications
Available on the Saia-Burgess website: www.sbc-support.ch
Mounting Guide (ECL Apex 20)
Supplied with the product
VIKTT200
Mounting Guide (ECA 20 Web Panel)
Supplied with the product
VIKTU100
*) Available on the Saia-Burgess website: www.sbc-support.ch. Choose Programmable Controller and PCD2.M5xxx.
Visit the Internet for Danfoss Heating literature on http://den.danfoss.com/
Dimensions (mm)
8
Use the product search facility or choose Documentation to find the literature you require.
ECL Apex 20
Width x height x depth
254 x 208 x 70
ECA 20 Web Panel
Width x height x depth
202 x 156 x 48
Cut-out for Web Panel
Width x height
189 x 142
Visible part of the Web Panel in panel
Width x height x depth
202 x 156 x 6
VD.KT.V2.02
Produced by Danfoss A/S © 12/2010
Data sheet
Remote control ECA 61
Application
The remote control ECA 61 is used for the programming of the week program, for room temperature control, and override of the electronic controller ECL Comfort 110. The remote control is connected to the ECL Comfort controller by means of a two-wire bus, and it is powered by the controller. ECA 61 has a built-in temperature sensor, but can be connected to an external room temperature sensor. It is possible to connect two ECA 61 remote controls to the same bus if you have two heating circuits.
Operating principles
The ECA 61 influences the flow temperature and keeps the room temperature at a constant level at comfort as well as reduced temperature.
A
20
Start and stop times are optimised. ECA 61 has a display and push buttons for the choice of setting and override functions. The buttons are used to choose between the following override and temperature settings: - - - -
Comfort temperature Reduced temperature Day off (comfort temperature) Holiday (reduced temperature)
Limits for heating cut out and room temperature influence can be set.
0
-3 3
6
9
12
15
19
18
21
24
A schedule can be set for the comfort and reduced room temperature as well as desired room temperature.
-3
18 35
In normal mode the display shows the outdoor, the actual and the desired room temperature.
7
12 05 HI -4
0 3 2 0 LO
The time and actual outdoor temperature can be shown in the display. It is possible to display the lowest and highest outdoor temperature since midnight.
Ordering
DH-SMT/DK
Type ECA 61 ESM-10
VD.7F.B4.02 © Danfoss 12/2012
Description Remote control Room temperature sensor
Code no. 087B1141 087B1164
1
Data sheet Technical data
Remote control ECA 61 Time periods Room temperature setting range Comfort and reduced temperature override Day off and holiday override Heating cut out Room temperature influence Transport and storage temperature Ambient temperature Installation Enclosure Weight Power supply / communication Bus cable length - marking in accordance with the standards
2 (3) periods / day 10 to 30 °C 1 to 19 hours 1 to 19 days Off, 10 to 30 °C -99 to 0 / 0 to +99 -40 to +70 °C 0 to 40 °C Wall mounting IP 20 150 g ECL Comfort bus Max. 50 m EMC-Directive 89/336/EEC, 92/31/EEC, 93/68/EEC, EN61000-6-3 and EN61000-6-1 Low Voltage Directive 73/23/EEC and 93/68/EEC
Settings
Arrow up - line selection
Arrow down - line selection
Outdoor temperature and time
Permanent override
+1
Temporary override + button - temperature adjustment - button - temperature adjustment
Dimensions
2
VD.7F.B4.02 © Danfoss 12/2012
DH-SMT/DK
Data sheet
Remote control ECA 61
Connection to ECL 110
DH-SMT/DK
VD.7F.B4.02 © Danfoss 12/2012 3
Data sheet
Remote control ECA 61
4
VD.7F.B4.02 © Danfoss 12/2012
DH-SMT/DK
Data sheet
ECL Comfort 110 230 V a.c. and 24 V a.c.
Description and application
The controller is designed for easy installation: one cable, one connector. The ECL Comfort 110 controller has a customdesigned display with backlight. For a quick overview, the display readouts are based on graphic symbols as well as text. The controller has triac outputs for motorized control valve and relay outputs for pump control.
The ECL Comfort 110 is a universal 1-circuit controller for use in district heating substations and district heating systems as well as boilerbased systems. The product is an electronic controller for • weather compensated flow temperature control (heating) • constant temperature control (domestic hot water e.g.) and prepared for new applications by means of chip card and communication interface.
Ordering
It is possible to connect up to 4 temperature sensors (Pt 1000 types) and it has 1 input for override. Remote control ECA 61 can be connected. The ECL Comfort 110 controller can be used as master or slave in controller systems. It is prepared for mounting on a DIN rail, a wall or in a panel.
Controllers Type
Designation
Code no.
ECL Comfort 110
Universal hardware - 230 V a.c.
087B1261
ECL Comfort 110
Universal hardware - 24 V a.c.
087B1251
ECL Comfort 110 with timer program
Universal hardware - 230 V a.c.
087B1262
ECL Comfort 110 with timer program
Universal hardware - 24 V a.c.
087B1252
Panel mounting kit
For ECL Comfort 110
087B1249
Instructions, appl. 116
User guide and quick guide (English)
087B8151
Instructions, appl. 130
User guide and quick guide (English)
087B8152
Pt 1000 temperature sensors
DH-SMT/DK
Type
Designation
ESMT
Outdoor temperature sensor
084N1012
ESM-10
Room temperature sensor
087B1164
ESM-11
Surface sensor
087B1165
ESMB-12
Universal sensor
087B1184
ESMC
Surface sensor incl. 2 m cable
087N0011
ESMU-100
Immersion sensor, 100 mm, copper
087B1180
ESMU-250
Immersion sensor, 250 mm, copper
087B1181
ESMU-100
Immersion sensor, 100 mm, stainless steel
087B1182
ESMU-250
Immersion sensor, 250 mm, stainless steel
087B1183
VD.KT.C4.02 © Danfoss 12/2012
Code No.
1
Data sheet
ECL Comfort 110
Ordering, continued
Accessories Type
Designation
ECA 61
Remote control with 1 zone clock and sensor
Code no. 087B1141
ECA 110*
Timer program for ECL Comfort 110 (chip card)
087B1248
* The ECA 110 is a supplement to the ECL Comfort 110 versions without a timer program, e.g., the code nos. 087B1261 and 087B1251 (see page 1). With the ECA 110 it will be possible to set personal schedules in terms of start and stop times of the system and thereby optimize the energy supply.
Domestic hot water (DHW) (Application 116) Application 116 example
Constant DHW temperature control with heat exchanger
Basic principles
Constant DHW temperature control with heat exchanger or storage tank Typically, the flow temperature is adjusted according to the desired flow temperature. • Adjustment of DHW temperature If the measured DHW temperature is lower than the desired temperature, the motorized control valve is opened gradually and vice versa.
2
VD.KT.C4.02 © Danfoss 12/2012
• Return temperature limitation The return temperature to the district heating supply should not be too high. If so, the desired flow temperature can be adjusted (typically to a lower value) thus resulting in a gradual closing of the motorized control valve. In boiler-based heating supply the return temperature should not be too low (same adjustment procedure as above). • Circulation pump control The circulation pump is ON when the desired DHW temperature is higher than a userdefined value (factory setting: 20 °C).
DH-SMT/DK
Data sheet
ECL Comfort 110
Key functions
Flow temperature control • Return temperature limitation The controller automatically changes the desired flow temperature to obtain an acceptable return temperature when the return temperature falls below or gets higher than the set value. The return temperature influence can be limited by the min. / max. flow limitation. Optimization • Auto tuning A function for automatically setting the proportional band (Xp) and integration time constant (Tn).
Safety functions • Frost protection The controller automatically switches the circulation pump ON when the flow temperature is lower than a user-defined value (factory setting: 10 °C). • Motor protection The controller prevents unstable temperature control thus resulting in a longer life of the actuator. • Pump exercise Exercise of the pump to avoid blocking in periods without heat demand.
Heating (Application 130) Application 130 examples
District heating circuit with heat exchanger
Boiler-based heating circuit
DH-SMT/DK
VD.KT.C4.02 © Danfoss 12/2012
3
Data sheet
ECL Comfort 110
Basic principles
Control of district heating circuits with or without heat exchanger and for boiler-based heating circuits Typically, the flow temperature is adjusted according to the desired flow temperature. • Adjustment of flow temperature The desired flow temperature is calculated in the ECL Comfort controller, based on the outdoor temperature. The lower the outdoor temperature, the higher the desired flow temperature. The motorized control valve is opened gradually when the flow temperature is lower than the desired flow temperature and vice versa.
4
VD.KT.C4.02 © Danfoss 12/2012
• Return temperature limitation The return temperature to the district heating supply should not be too high. If so, the desired flow temperature can be adjusted (typically to a lower value) thus resulting in a gradual closing of the motorized control valve. In boiler-based heating supply the return temperature should not be too low (same adjustment procedure as above). • Room temperature limitation If the measured room temperature does not equal the desired room temperature, the desired flow temperature can be adjusted. • Circulation pump control The circulation pump is ON when the desired flow temperature is higher than a user-defined value (factory setting: 20 °C ) or the outdoor temperature is lower than a user-defined value (factory setting: 2 °C).
DH-SMT/DK
Data sheet
General data
ECL Comfort 110
Ambient temperature
0 - 55 °C
Storage temperature
-40 - + 70 °C
Enclosure
DIN rail, wall or panel
Sensor type
Pt 1000 (1000 Ω @ 0 °C)
Grade of enclosure
IP 41 DIN 40050
- marking in accordance with the standards
EMC-Directive: 2004/108/EC Immunity: 61000-6-1 Emission: 61000-6-3 LVD-Directive: 2006/95/EC
Wiring - 230 V a.c.
* Connections for safety thermostat Supply voltage
230 V a.c. - 50 Hz
Voltage range
207 to 244 V a.c. (IEC 60038)
Power consumption
3 VA
Load on relay 1 outputs
4 (2) A - 230 V a.c.
Load on triac outputs
15 VA @ 230 V a.c.
Wiring - 24 V a.c.
* Connections for safety thermostat
DH-SMT/DK
Supply voltage
24 V a.c. - 50 Hz
Voltage range
21.6 to 26.4 V a.c. (IEC 60038)
Power consumption
3 VA
Load on relay 2 outputs
4 (2) A - 230 V a.c.
Load on triac outputs
15 VA @ 24 V a.c.
VD.KT.C4.02 © Danfoss 12/2012
5
Data sheet
ECL Comfort 110
Operation
Adjust temperatures and values.
Switch between menu lines. Select / return. 2 sec. Return to daily user menu.
Menu navigation Temp.
Mode
‘Weekday’ 5 sec. Date - time
Flow temp.
Room T limit
Return T limit
Optimize
Control param.
Application
Service
6
VD.KT.C4.02 © Danfoss 12/2012
DH-SMT/DK
Data sheet
ECL Comfort 110
Dimensions
Cut-out for mounting
Mounting in a panel (panel mounting kit, code no.: 087B1249).
DH-SMT/DK
VD.KT.C4.02 © Danfoss 12/2012
The panel thickness must not exceed 5 mm.
7
Data sheet
ECL Comfort 110
Additional documentation for ECL Comfort 110 is available on http://heating.danfoss.com
8
VD.KT.C4.02
Produced by Danfoss A/S © 12/2012
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys Designed in Denmark
Description ECL Comfort 210 controller series
The ECL Comfort 210 is an electronic weather compensated temperature controller in the ECL Comfort controller family for use in district heating, central heating and cooling systems. Energy savings can be achieved by correct control of the flow temperature in heating and cooling systems. Up to 3 circuits can be controlled. The weather compensation function in the ECL Comfort controllers measure the outdoor temperature and control the flow temperature to the heating system accordingly. The weather compensated heating system increases the comfort level and saves energy. The ECL Comfort 210 controller is configured with a selected application by means of an ECL Application Key. ECL Comfort 210 is designed for comfortable temperatures, optimum energy consumption, easy installation by means of the ECL Application Key (Plug-and-Play) and user friendly operation. Improved energy savings are facilitated by weather compensation, adjustment of temperature according to schedule, optimization as well as limitation of return temperature, flow and power. Functionalities such as data logging and alarm functions are implemented in the controller. The ECL Comfort 210 is easily operated by means of a dial (multi-functional knob) or a Remote Control Unit (RCU). The dial and the backlighted display guide the user through the text menus in the selected language. The ECL Comfort 210 controller has electronic output for motorized valve control, relay output for circulation pump / changeover valve control among others, as well as alarm output.
DEN-SMT/DK
VD.KT.W2.02 © Danfoss 12/2012
6 Pt 1000 temperature sensors can be connected. In addition, 2 inputs are configured when uploading the application. The configuration can be Pt 1000 temperature sensor input, analog input (0 – 10 V) or digital input. The enclosure is designed for mounting on wall and DIN rail. A variant ECL Comfort 210B (without display and dial) is available. It can be used for mounting inside a panel and is operated by means of the RCU ECA 30 / 31 which can be placed in front of the panel. The ECL Comfort 210 is a stand-alone controller which communicates with the RCU and other ECL Comfort 210 / 310 controllers via the ECL 485 communication bus. Remote Control Unit (RCU): The RCUs ECA 30 and ECA 31 are used for room temperature control and override of the ECL Comfort 210. The display has backlight. The RCUs are connected to the ECL Comfort controllers by means of 2 × twisted pair cable for communication and power supply (ECL 485 communication bus). The ECA 30 / 31 has a built-in room temperature sensor. An external room temperature sensor can be connected substituting the built-in temperature sensor. Furthermore, the ECA 31 has a built-in relative humidity sensor and the signal is used in relevant applications. It is possible to connect up to 2 RCUs on the ECL 485 communication bus. One RCU can monitor max. 10 ECL Comfort controllers (master/ slave system).
1
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys
Description (continued)
ECL Application Key and applications: Different ECL Application Keys make it easy for the ECL Comfort 210 hardware to run different applications. The ECL Comfort 210 controller is loaded with the desired application by means of the ECL Application Key, which contains information about applications (simple application sketches are shown in the display), languages and factory settings.
Application examples
The ECL Application Keys for ECL Comfort 210 can also be used in ECL Comfort 310. The application parameters are stored in the controller and are not affected by power break. The relevant ECL Application Keys for the ECL Comfort 210 controller can be found in the ordering section.
All mentioned components (S = temperature sensor, P = pump, M = Motorized control valve and so on) are wired to the ECL Comfort 210. A214.1, ex. a: Cooling application, duct temperature based on room temperature S1
Danfoss 87H2113.11
ECL 210 / 310 A1
M2
S5
X3
P2
F1
S3
S4
S8 S8
A214.2, ex. a: Heating application, heating temperature based on duct temperature S1
Danfoss 87H2118.11
ECL 210 / 310 A1 M1
S3 X3
S5
P2 S6
S7
F1
S4 S8 S8
2
VD.KT.W2.02 © Danfoss 12/2012
DEN-SMT/DK
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys A214.3, ex. a: Heating application, duct temperature based on room temperature Danfoss 87H2120.11
ECL 210 / 310
S1
A1
M1
S5
X3 P2
S6
S3
F1
S4
S8
S7
S8
A214.5, ex. a: Heating / cooling application, duct temperature based on room temperature
S1
Danfoss 87H2124.11
ECL 210 / 310 A1
M1
X3
M2
S5
P2 S6
S7
F1
S3
S4
S8 S8
DEN-SMT/DK
VD.KT.W2.02 © Danfoss 12/2012
3
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys A217.1, ex. a: DHW tank charging application S1
Danfoss 87H2067.11
ECL 210 / (310) A1
S2
S3
S6 A
M1
S5
S8 B
P3
P1
A217.1, ex. b: DHW tank heating application S1
Danfoss 87H2068.11
ECL 210 / (310) A1
S2
S3
M1
S6
S8
S5
P3
P1
A217.2, ex. a: DHW tank charging with preheating circuit S1
Danfoss 87H2071.11
ECL 210 / (310) A1
S2
S3
S4
S6
P1 M1
A
S5
S8 B
4
VD.KT.W2.02 © Danfoss 12/2012
P3
P2
DEN-SMT/DK
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys A217.3, ex. a: DHW heating
A217.3, ex. c: DHW heating on demand (flow switch). With or without circulation
A230.1, ex. a: Indirectly connected heating system. Wind compensation as option
DEN-SMT/DK
VD.KT.W2.02 © Danfoss 12/2012
5
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys A230.2, ex. a: Indirectly connected cooling system (district cooling)
A231.2: Indirectly connected heating system with 2-pump control and refill water function
Danfoss 87H2005.10
ECL 210
S1
R4 P S7 S2
S3
P1 P2
M1
P3
S5
S8
V1
A232.1, ex. a: Control of flow temperature (heating in floor /cooling in ceiling) in relation to outdoor, room and dew point temperature
6
VD.KT.W2.02 © Danfoss 12/2012
DEN-SMT/DK
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys A237.1, ex. a: Indirectly connected heating and DHW system S2
ECL 210 / (310)
Danfoss 87H2024.10
S1
R4 / (R6)
P1 S3 S6 P2 M1
S8
S5
P3
Danfoss 87H2022.10
A237.2, ex. a: Indirectly connected heating and DHW charging system
P1
S4
S3
S6 P2 M1
S8
S5
P3
P4
S1
(S7*)
ECL 210 / (310)
Danfoss 87H2039.11
A247.1, ex. a: Indirectly connected heating and DHW tank charging system. Parallel mode or DHW priority
A1 S3
M2
P1 S5
S4
M1
S6 A
S2
S8 B
P3
P2
(S7*) = optional in ECL Comfort 310 DEN-SMT/DK
VD.KT.W2.02 © Danfoss 12/2012
7
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys
S1
(S7*)
ECL 210 / (310)
Danfoss 87H2038.11
A247.2, ex. a: Indirectly connected heating and DHW tank charging system with preheating circuit. Parallel mode or DHW priority
A1 S3 P1 M2
S5
S4
S6 P2
M1
A
S2
S8 B
P3
P4
(S7*) = optional in ECL Comfort 310 A260.1, ex. a: Two heating systems
8
VD.KT.W2.02 © Danfoss 12/2012
DEN-SMT/DK
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys A260.1, ex. d: Two heating systems. Circuit 2 is a sub-circuit of circuit 1.
A266.1, ex. a: Heating and direct DHW heating system. Parallel mode or DHW priority.
DEN-SMT/DK
VD.KT.W2.02 © Danfoss 12/2012
9
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys A266.2: Heating and direct DHW heating system. Parallel mode or DHW priority. DHW heating on demand (flow switch)
A275.1, ex. a: Heating system with 1-stage boiler
Danfoss 87H2163.10
ECL 210 / (310)
S1
A1
S3 S7 P1 *
①
S5
B1
10
VD.KT.W2.02 © Danfoss 12/2012
DEN-SMT/DK
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys A275.2, ex. a: Heating system with 1-stage boiler and DHW tank Danfoss 87H2165.10
ECL 210 / (310)
S1
A1
S3 S7 P1
①
* S5
B1
S6
②
P3
A275.3, ex. a: Heating system with 1-stage boiler, mixing circuit and DHW tank
M2
Danfoss 87H2169.10
ECL 210 / (310)
S1
S4
S8
②
P4 S2 S3 S7 P1
①
* S5
B1
S6
③
P3
DEN-SMT/DK
VD.KT.W2.02 © Danfoss 12/2012
11
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys
Ordering
Controller, base parts and accessories: Type
Designation
Code no.
ECL Comfort 210
Universal hardware - 230 V a.c. Base part is not included. Mounting guide (no text) is included.
087H3020
ECL Comfort 210
Universal hardware - 24 V a.c. Base part is not included. Mounting guide (no text) is included.
087H3024
ECL Comfort 210B
Universal hardware - 230 V a.c. Without display and dial. Requires a Remote Control Unit. Base part is not included. Mounting guide (no text) is included.
087H3030
ECL Comfort 210 base part
For mounting on wall or DIN rail (35 mm). Mounting guide (no text) and cable 087H3220 inlet accessories is included.
ECL Comfort 310 base part
For mounting on wall or DIN rail (35 mm). ECL Comfort 210 can be mounted in an ECL Comfort 310 base part (for future upgrade). Mounting guide (no text) and cable inlet accessories is included.
087H3230
Remote Control Units and accessories Type
Designation
Code no.
ECA 30
Remote Control Unit with an integrated room temperature sensor and possibility for connecting an external Pt 1000 room temperature sensor. Base part for mounting on wall included. Mounting guide (no text) is included.
087H3200
ECA 31
Remote Control Unit with an integrated room temperature sensor and a humidity sensor. Possibility for connecting an external Pt 1000 room temperature sensor. Used for dedicated applications. Base part for mounting on wall included. Mounting guide (no text) is included.
087H3201
ECA 30 / 31 frame kit for mounting in panel front
For mounting in a panel cut-out. 087H3236 Format 144 × 96 mm, actual cut-out 139 × 93 mm. Mounting guide (no text) is included.
Accessories: Type
Designation
Code no.
ECA 99
230 V a.c. to 24 V a.c. transformer (35 VA)
087B1156
ECL Application Keys
12
Type
Application type description
A214
• Temperature control (heating / cooling) of ventilation systems. Duct / room 2 x 3-point, 2 x 2-point temperature control. Return temperature limitation. Flow / power limitation. Fire and frost protection as well as alarm function. • The A214 application key contains applications related to ECL Comfort 310 for increased functionalities (control of rotating heat-exchanger).
087H3811
A217
• Advanced temperature control of DHW (Domestic Hot Water) circuit with/ 1 x 3-point, 3 x 2-point without storage charging system. Circulation pump control. Return temperature limitation. Frost protection and alarm function. • The A217 application key contains applications related to ECL Comfort 310 for increased functionalities (M-bus).
087H3807
A230
• (A230.1) Weather compensated flow temperature control of heating 1 x 3-point, 2 x 2-point systems. Circulation pump control. Room temperature control and sliding return temperature limitation. Flow / power limitation. Wind compensation, frost protection and alarm function. • (A230.2) Flow temperature control of cooling systems. Compensation for outdoor and room temperatures. Return temperature limitation. • The A230 application key works in ECL Comfort 310 for increased functionalities (M-bus).
087H3802
A231
• Weather compensated flow temperature control of heating systems. 1 x 3-point, 3 x 2-point 2-pump control for circulation and refill water function. Sliding return temperature limitation. Frost protection and alarm function. • The A231 application key contains applications related to ECL Comfort 310 for increased functionalities (2 pumps for refill water and M-bus).
087H3805
A232
• Weather compensated flow temperature control of heating / cooling 1 x 3-point, 3 x 2-point circuit(s). Automatic change-over between heating and cooling. Circulation pump control. Dew point (cooling mode only) and surface temperature compensation. • The A232 application key contains applications related to ECL Comfort 310 for increased functionalities (return temperature limitation and separated control of heating and cooling circuits).
087H3812
VD.KT.W2.02 © Danfoss 12/2012
Controller output signals
Code no.
DEN-SMT/DK
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys ECL Application Keys (continued): Type
Application type description
Controller output signals
Code no.
A237
• Weather compensated flow temperature control of heating systems. 1 x 3-point, 3 x 2-point Circulation pump control. Room temperature control and sliding return temperature limitation. Flow / power limitation. Temperature control of secondarily connected DHW circuit with storage tank charging system or storage tank with internal heat exchanger. Optional ON / OFF control of the DHW circuit in connection with primarily connected storage tank with internal heat exchanger. DHW circulation pump control. Frost protection and alarm function. • The A237 application key contains applications related to ECL Comfort 310 for increased functionalities (M-bus).
087H3806
A247
• Weather compensated flow temperature control of heating systems. 2 x 3-point, 3 x 2-point Circulation pump control. Sliding return temperature limitation. Flow / power limitation. Temperature control of DHW circuit with storage tank charging system. DHW circulation pump control through the storage tank or the heat-exchanger. Frost protection and alarm function. • The A247 application key contains applications related to ECL Comfort 310 for increased functionalities (room temperature sensor and M-bus).
087H3808
A260
• Weather compensated flow temperature control of heating systems. 2 x 3-point, 2 x 2-point Circulation pump control, room temperature control and sliding return temperature limitation for two independent heating circuits. Flow / power limitation, frost protection and alarm function. • The A260 application key works in ECL Comfort 310 for increased functionalities (M-bus).
087H3801
A266
• Weather compensated flow temperature control of heating systems. 2 x 3-point, 2 x 2-point Circulation pump control, room temperature control and sliding return temperature limitation. • Temperature control of DHW circuit with DHW circulation. Return temperature limitation, sliding DHW priority, frost protection and alarm function. Optional control of DHW heating based on DHW demand. • The A266 application key works in ECL Comfort 310 for increased functionalities (M-bus).
087H3800
A275
• Weather compensated flow temperature control of 1-stage boiler based 1 x 3-point, 4 x 2-point heating systems. One direct heating circuit and one mixing circuit. Circulation pumps control, room temperature control and sliding return temperature limitation. • Temperature control of DHW storage tank with internal heat exchanger. Frost protection and alarm function. • The A275 application key contains applications related to ECL Comfort 310 for increased functionalities (multiple boiler stages).
087H3814
Each of the abovementioned code nos. comprises 1 ECL Application Key, 1 mounting guide and 1 set of multi-lingual user guides. Pt 1000 temperature sensors (IEC 751B, 1000 Ω / 0 °C): Type
Designation
Code No.
ESMT
Outdoor temperature sensor
084N1012
ESM-10
Room temperature sensor
087B1164
ESM-11
Pipe surface temperature sensor
087B1165
ESMB-12
Universal temperature sensor
087B1184
ESMC
Pipe surface temperature sensor incl. 2 m cable
087N0011
ESMU-100
Immersion sensor, 100 mm, copper
087B1180
ESMU-250
Immersion sensor, 250 mm, copper
087B1181
ESMU-100
Immersion sensor, 100 mm, stainless steel
087B1182
ESMU-250
Immersion sensor, 250 mm, stainless steel
087B1183
Pocket
Immersion, stainless steel 100 mm, for ESMU-100, Cu (087B1180)
087B1190
Pocket
Immersion, stainless steel 250 mm, for ESMU-250, Cu (087B1181)
087B1191
Pocket
Immersion, stainless steel 100 mm, for ESMB-12, (087B1184)
087B1192
Pocket
Immersion, stainless steel 250 mm, for ESMB-12, (087B1184)
087B1193
Accessories and spare parts:
Typical ordering, types:
DEN-SMT/DK
ECL Comfort Controller
Base part
Appl. key
Remote Control Unit
Temperature sensors
Actuators / valves
ECL 210, 230 V a.c. ECL 210 B, 230 V a.c. ECL 210, 24 V a.c.
for ECL 210 for ECL 310
A2xx
ECA 30 ECA 31
ESMT (outdoor) ESM-11 (pipe surface) ESMC (pipe surface) ESMU (immersion) ESM-10 (room) ESMB-12 (universal)
see dedicated literature
VD.KT.W2.02 © Danfoss 12/2012
13
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys
Operation
A
B
The graphical monochrome display (A) shows all temperature values as well as status information and is used for the setting of control parameters. The display has backlight. Different favorite displays can be selected. Navigation, browsing and selecting the current item in the menus is done by means of the dial (multi-functional knob (B)).
The RCUs ECA 30 / 31 are used for remote setting and override of ECL Comfort controller. By means of the built-in room temperature sensor, the flow temperature can be corrected to keep a constant room temperature at comfort or saving temperature. The ECA 30 / 31 is operated as an ECL Comfort 210 with dial and backlighted display.
Examples of favorite displays:
14
VD.KT.W2.02 © Danfoss 12/2012
DEN-SMT/DK
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys
Functions
General functions: • The ECL Comfort 210 has all the required functions of a modern electronic temperature controller for heating and DHW applications. • The controller can be used as master or slave in systems with master / slave ECL Comfort 210 / 310 controllers. • The ECL Application Key contains the application software for flexible configuration. Furthermore, an update of the controller software is done automatically, if required. • The ECL Comfort 210 contains, besides the standard functions, log and alarm functions. • The built-in Real Time Clock gives automatic summer / winter time changeover, week and holiday schedule. • Motor protection, which ensures stable control and a long life of the motorized control valve, is available for most of the applications. In periods without heat demand, the motorized control valve is exercised to avoid blocking. • Scheduled control (Comfort and Saving mode) is based on a week program. A holiday program gives the possibility to select days with comfort or saving mode. • The ECL Comfort 210 can receive pulses from a heat or flow meter to limit the power or the flow. • In many applications analog input (0 – 10 V) is configured for pressure measuring among others. The scaling is set in the controller. • Some applications are configured to handle digital input. This function can be used to have an external switch to run comfort or saving mode or react on a flow switch signal. • The control parameters, proportional band (Xp), integration time (Tn), running time of the motorized control valve and neutral zone (Nz) can be set individually for each output (3-point control).
Communication
Heating functions: • The heat curve (relationship between outdoor temperature and desired flow temperature) is set by means of 6 coordinate points or a slope value. Max. / min. limitation of the desired flow temperature can be set. • The return temperature limitation can work in relation to the outdoor temperature or be a fixed value. • The heating cut-out function can switch OFF the heating and stop the circulation pump at high outdoor temperatures. • Based on the room temperature the ECL Comfort 210 can correct the desired flow temperature in order to increase the comfort level. • The optimizer function ensures heating in the desired periods (the lower outdoor temperature, the earlier cut-in of the heating). • The ramping function makes a smooth cut-in of the heating valuable (district heating installations). • The boost function makes a powerful cut-in of the heating (boiler based installations). • The circulation pump is controlled in relation to heat demand and frost protection. In periods without heat demand, the circulation pump is exercised to avoid blocking. • The saving function gives two possibilities: · reduced flow temperature with fixed reduction or reduction in relation to outdoor temperature (the lower the outdoor temperature, the less the reduction), · heating off, still with active frost protection DHW functions: • The Auto Tuning function with automatic setting of control parameters for constant DHW temperature is integrated in the application A217 and A266. However, Auto Tuning is only applicable with valves that are approved for Auto Tuning, i.e. the Danfoss types VB 2 and VM 2 with split characteristic as well as logarithmic valves such as VF and VFS. • The anti-bacteria function can follow a schedule program. • The heating circuit can have sliding DHW priority.
The ECL Comfort 210 has an ECL 485 communication bus, which is used for closed communication between master, slave and RCUs. Additionally, the ECL Comfort 210 has a nongalvanically separated RS 485 bus for limited Modbus communication. A USB connection (type B) can be used for an ECL Tool.
Master / slave connections
Languages
Menu languages are selectable among approx. 20 languages. See “Language list”.
DEN-SMT/DK
VD.KT.W2.02 © Danfoss 12/2012
Furthermore, English is always uploaded in parallel to the selected language.
15
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys
General data
ECL Comfort controller and RCU data: ECL Comfort 210 / 210B
ECA 30 / 31
Ambient temperature
0 - 55 °C
Storage and transportation temperature
-40 - 70 °C
Mounting
Vertically, on wall or DIN rail (35 mm)
Vertically, on wall or in panel cut-out
Connections
Terminals in base part
Terminals in base part
Number of inputs
8 in total: 6 temperature sensors 2*) Pt 1000 sensor, digital, analog or pulse
-
Temperature sensor type
Pt 1000 (1000 ohm at 0 °C), IEC 751B Range: -60 – 150 °C
Alternative to built-in room temperature sensor: Pt 1000 (1000 ohm at 0 °C), IEC 751B
Digital input
12 V pull-up possible
-
Analog input
0 - 10 V, resolution 9 bits
-
Pulse input
Max. 200 Hz
-
Weight
0.46 / 0.42 kg
0.14 kg
Display (ECL Comfort 210 and ECA 30 / 31 Graphical monochrome with backlight only) 128 × 96 dots Display mode: Black background, white text Setting (ECL Comfort 210 and ECA 30 / 31 Dial with intuitive push and turn function only) Setting (ECL Comfort 210 B)
ECA 30 / 31
Min. backup time for time and date
72 hours
-
Backup of settings and data
Storage in EEPROM (timeless)
-
Grade of enclosure
IP 41
IP 20
-marking in accordance with the standards
EMC directive 2004/108/EC Immunity: EN 61000-6-1:2007 Emission: EN 61000-6-3:2007 LVD directive 2006/95/EC EN 60730
*) Configured at application upload.
ECL application key: Storage type
EEPROM
Segmentation
Part 1: Application data, not changeable Part 2: Factory settings, not changeable Part 3: Updating SW for the ECL Comfort controller, not changeable Part 4: User settings, changeable
Applications
A2xx keys work in ECL Comfort 210 and ECL Comfort 310 A3xx keys work in ECL Comfort 310 only
Lock function
If not inserted in the ECL Comfort controller, all settings can be seen, but not changed
ECL 485 communication bus data:
16
Purpose
For internal ECL Comfort 210 / 310 and ECA 30 / 31 use only (Danfoss proprietary bus)
Connection
Terminals in base part Non-galvanically isolated
Cable type
2 × twisted pair
Max. total cable length (bus cable + sensor cables)
200 m in total (inclusive sensor cables)
Max. number of ECL slaves connected
Units with unigue address (1 - 9): 9 Units with address “0”: 5
Max. number of Remote Control Units connected
2
Data sent from master
Date Time Outdoor temperature Desired room temperature DHW-priority signal
Data sent from addressed slave controller
Desired flow temperature from each circuit
Data sent from ECA 30 / 31
• Actual and desired room temperature • Function selector mode • (ECA 31) Relative humidity
VD.KT.W2.02 © Danfoss 12/2012
DEN-SMT/DK
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys Modbus communication data: Modbus RS 485
For service purposes
Connection
Terminals in base part Non-galvanically isolated
Cable type
2 × twisted pair
Max. bus cable length
20 m
USB communication data: USB CDC (Communication Device Class)
For service purposes (Windows driver is needed, to enable that Windows recognize the ECL as a virtual COM port)
Modbus over USB
Similar to the serial Modbus, but with relaxed timing
Connection, cable type
Standard USB cable (USB A -------- USB B)
A port: USB (type B female plug) C port: ECL Application Key
Languages (alphabetic order)
Bulgarian
Estonian
Italian
Russian
Croatian
Finnish
Latvian
Serbian
Czech
French
Lithuanian
Slovak
Danish
German
Polish
Slovenian
English
Hungarian
Romanian
Swedish
The selected language + English is uploaded at application upload.
References
DEN-SMT/DK
M-bus communication
ECL Comfort 310
Modbus connection (galvanic isolated)
ECL Comfort 310
Ethernet
ECL Comfort 310 has Ethernet connection, RJ45, Modbus / TCP. For SCADA solutions
Extension of input / outputs
ECL Comfort 310 (2 extra inputs, 1 extra output for actuator, 2 extra relays) ECL Comfort 310 + ECA 32 (6 inputs, 2 pulse inputs, 3 analog outputs (0 - 10 V) and 4 relays)
VD.KT.W2.02 © Danfoss 12/2012
17
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys
Wiring - 230 V a.c.
ECL Comfort 210 wiring example: Application A266.1 Supply voltage
230 V a.c. - 50 Hz
Voltage range
207 to 244 V a.c. (IEC 60038)
Power consumption
5 VA
Max. load on relay outputs
4(2) A - 230 V a.c. (4 A for ohmic load, 2 A for inductive load)
Max. load on actuator outputs
0.2 A - 230 V a.c.
Wiring - 24 V a.c.
ECL Comfort 210 wiring example: Application A266.1 Auxiliary relays (K) must be used in order to separate the 230 V a.c. supply from the 24 V a.c. supply of the controller.
18
Supply voltage
24 V a.c. - 50 Hz
Voltage range
21.6 to 26.4 V a.c. (IEC 60038)
Power consumption
5 VA
Max. load on relay output
4(2) A - 24 V a.c. (4 A for ohmic load, 2 A for inductive load)
Max. load on actuator output
1 A - 24 V a.c.
VD.KT.W2.02 © Danfoss 12/2012
DEN-SMT/DK
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys
Wiring - input
Wiring - ECA 30 / 31 Remote Control Unit
Wiring of ECL Comfort 210 and ECA 30 / 31, 230 V a.c. Supply voltage
From ECL 485 communication bus
Power consumption
1 VA
External room temperature sensor
Pt 1000 (ESM-10), substitutes the built-in room temperature sensor
ECA 31 only
Contains humidity sensor, used for special applications
Base part
ECL Comfort 210 base part
DEN-SMT/DK
VD.KT.W2.02 © Danfoss 12/2012
19
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys
Base part, continued
ECL Comfort 310 base part (can be used for ECL Comfort 210 too).
Dimensions
ECL Comfort 210
ECL Comfort 210B
ECA 30 / 31
20
VD.KT.W2.02 © Danfoss 12/2012
DEN-SMT/DK
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys
ECA 30 / 31 cut-out for mounting in panel front
DEN-SMT/DK
A frame (code no. 087H3236) is placed in the cut-out (139 × 93 mm) in which the ECA 30 / 31 is placed.
VD.KT.W2.02 © Danfoss 12/2012
21
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys
22
VD.KT.W2.02 © Danfoss 12/2012
DEN-SMT/DK
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys
DEN-SMT/DK
VD.KT.W2.02 © Danfoss 12/2012
23
Data sheet
ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys
Additional documentation for ECL Comfort 210, modules and accessories is available on http://den.danfoss.com/
24
VD.KT.W2.02
Produced by Danfoss A/S © 12/2012
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
ark
s
De
nD
di
e ign
m en
Description ECL Comfort 310 controller series
The ECL Comfort 310 is an electronic weather compensated temperature controller in the ECL Comfort controller family for use in district heating, central heating and cooling systems. Energy savings can be achieved by correct control of the flow temperature in heating and cooling systems. Up to 4 circuits can be controlled. The weather compensation function in the ECL Comfort controllers measures the outdoor temperature and control the flow temperature to the heating system accordingly. The weather compensated heating system increases the comfort level and saves energy. The ECL Comfort 310 controller is configured with a selected application by means of an ECL Application Key. The web based ECL Portal communicates with the ECL Comfort 310 for an effective and easy-to-use turnkey SCADA (Supervisory Control And Data Acquisition) tool for all users, service personnel and at commissioning. Service level can be increased and/or service costs reduced. The heating and/or cooling installation is made accessible from virtually anywhere at any time via laptops or Smartphones which increases service level and reduces response time to alarms. The ECL Tool software for ECL Comfort 310 offers possibilities for an alternative remote control in relation to ECL Portal and OPC server software.
DEN-SMT/DK
VD.KT.X2.02 © Danfoss 03/2013
ECL Comfort 310 is designed for comfortable temperatures, optimum energy consumption, easy installation by means of the ECL Application Key (Plug-and-Play) and user friendly operation. Improved energy savings are facilitated by weather compensation, adjustment of temperature according to schedule, optimization as well as limitation of return temperature, flow and power. The ECL Comfort 310 is easily operated by means of a dial (multi-functional knob) or a Remote Control Unit (RCU). The dial and the backlighted display guide the user through the text menus in the selected language. The ECL Comfort 310 controller has electronic output for motorized valve control, relay output for circulation pump / changeover valve control among others, as well as alarm output. 6 Pt 1000 temperature sensors can be connected. In addition, 4 inputs are configured when uploading the application. The configuration can be Pt 1000 temperature sensor input, analogue input (0 – 10 V) or digital input. Depending on application, the internal extension module ECA 32 (inserted into the controllers base part) can give additional input and output signals.
1
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Description (continued)
The enclosure is designed for mounting on wall and DIN rail. A variant ECL Comfort 310B (without display and dial) is available. It can be used for mounting inside a panel and is operated by means of the RCU ECA 30 / 31 which can be placed in front of the panel. The ECL Comfort 310 can work as a stand-alone controller and communicate with up to two RCUs and an extension module ECA 32 with additional inputs / outputs. The ECL Comfort 310 can also work with up to 2 x RCUs, ECA 32 and other ECL Comfort 210 / 310 controllers via the ECL 485 communication bus. Ethernet connection is integrated in the controller. Furthermore, Modbus communication to SCADA systems (Supervisory Control and Data Acquisition) and M-bus communication to heat meters are integrated.
Remote Control Unit (RCU): The RCUs ECA 30 and ECA 31 are used for room temperature control and override of the ECL Comfort 310. The display has backlight. The RCUs are connected to the ECL Comfort controllers by means of 2 × twisted pair cable for communication and power supply (ECL 485 communication bus). The ECA 30 / 31 has a built-in room temperature sensor. An external room temperature sensor can be connected substituting the built-in temperature sensor. Furthermore, the ECA 31 has a built-in relative humidity sensor and the signal is used in relevant applications. It is possible to connect up to 2 RCUs on the ECL 485 communication bus. One RCU can monitor max. 10 ECL Comfort controllers (master/ slave system).
ECL Application Key and applications: Different ECL Application Keys make it easy for the ECL Comfort 310 hardware to run different applications. The ECL Comfort 310 controller is loaded with the desired application by means of the ECL Application Key, which contains information about applications (basic application sketches are shown in the display), languages and factory settings. The ECL Application Keys, series A2xx can be used in ECL Comfort 210 and ECL Comfort 310. Most of the A2xx application keys give extended functionalities when used in ECL Comfort 310, such as additional temperature sensors and M-bus communication. The ECL Application Keys, series 3xx can be used in ECL Comfort 310 only. The application parameters are stored in the controller and are not affected by power break. The relevant ECL Application Keys for the ECL Comfort 210 / 310 controller can be found in the ordering section.
2
VD.KT.X2.02 © Danfoss 03/2013
DEN-SMT/DK
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Key overview, sub-circuits, combinations
ECL Comfort 210
ECL Comfort 310
A214
A214.1, A214.2, A214.3, A214.4, A214.5, A214.6
A214.1, A214.2, A214.3, A214.4, A214.5, A214.6 A314.1, A314.2, A314.3, A314.4, A314.5, A314.6, A314.7
A217
A217.1, A217.2, A217.3
A217.1, A217.2, A217.3 A317.1, A317.2
A230
A230.1, A230.2
A230.1, A230.2
A231
A231.1, A231.2
A231.1, A231.2 A331.1, A331.2
A232
A232.1
A232.1 A332.1, A332.2
A237
A237.1, A237.2
A237.1, A237.2 A337.1, A337.2
A247
A247.1, A247.2
A247.1, A247.2 A347.1, A347.2
A260
A260.1, A260.2
A260.1, A260.2
A266
A266.1, A266.2, A266.9
A266.1, A266.2, A266.9
A275
A275.1, A275.2, A275.3
A275.1, A275.2, A275.3 A375.1, A375.2, A375.3
Key
A333
A333.1, A333.2, A333.3
A361
A361.1, A361.2
A367
A367.1, A367.2
A368
A368.1, A368.2, A368.3, A368.4
A376
A376.1, A376.2, A376.3, A376.9
A377
A377.1, A377.2
This is an overview of currently available application keys for the ECL Comfort controllers. Not all keys are for sale in your country. Please contact your local Danfoss sales company.
DEN-SMT/DK
VD.KT.X2.02 © Danfoss 03/2013
3
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Application examples
All mentioned components (S = temperature sensor, P = pump, M = Motorized control valve and so on) are wired to the ECL Comfort 210 / 310. All applications from ECL Comfort 210 can run in ECL Comfort 310. Extra functions and communication facilities are enabled. A214.1, ex. a: Cooling application, duct temperature based on room temperature S1
Danfoss 87H2113.11
ECL 210 / 310 A1
M2
S5
X3
P2
F1
S3
S4
S8 S8
A214.2, ex. a: Heating application, heating temperature based on duct temperature S1
Danfoss 87H2118.11
ECL 210 / 310 A1 M1
S3 X3
S5
P2 S6
S7
F1
S4 S8 S8
4
VD.KT.X2.02 © Danfoss 03/2013
DEN-SMT/DK
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys A214.3, ex. a: Heating application, duct temperature based on room temperature Danfoss 87H2120.11
ECL 210 / 310
S1
A1
M1
S5
X3 P2
S6
S3
F1
S4
S8
S7
S8
A214.5, ex. a: Heating / cooling application, duct temperature based on room temperature
S1
Danfoss 87H2124.11
ECL 210 / 310 A1
M1
X3
M2
S5
P2 S6
S7
F1
S3
S4
S8 S8
DEN-SMT/DK
VD.KT.X2.02 © Danfoss 03/2013
5
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
S1
Danfoss 87H2133.11
A314.1, ex. a: Ventilation system with heating, passive cooling (outside air) and constant duct temperature control. Analogue controlled passive cooling stage (M2).
ECL 310 +ECA 32
A1
M1
S3
S5
X3 P2
M2
A
S6
F1
S4 S8
S7
S8
A314.1, ex. b: Ventilation system with heating, cooling and duct temperature control. Analogue controlled cooling stage (M2).
S1
+ECA 32 M1
S3 X3
Danfoss 87H2128.11
ECL 310 A1
M2 A
S5
P2 S6
S7
F1
S4 S8 S8
6
VD.KT.X2.02 © Danfoss 03/2013
DEN-SMT/DK
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys A314.2, ex. b: Ventilation system with heating, cooling and room temperature control. Analogue controlled cooling stage (M2).
S1
Danfoss 87H2135.11
ECL 310 A1
+ECA 32 M1
M2 A
S5
X3 P2
F1
S6
S3
S4
S8
S7
S8
A314.3, ex. a: Ventilation system with heating and room temperature control. Speed controlled fan.
+ ECA 32
Danfoss 87H2131.11
ECL 310
S1
A1
M1 S10
X3
S5
P2 S6 F1 / V1 S3
S7
S4
S8 S8
DEN-SMT/DK
VD.KT.X2.02 © Danfoss 03/2013
7
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys A217.1, ex. a: DHW tank charging application S1
Danfoss 87H2067.11
ECL 210 / (310) A1
S2
S3
S6 A
M1
S5
S8 B
P3
P1
A217.1, ex. b: DHW tank heating application S1
Danfoss 87H2068.11
ECL 210 / (310) A1
S2
S3
M1
S6
S8
S5
P3
P1
A217.2, ex. a: DHW tank charging with preheating circuit S1
Danfoss 87H2071.11
ECL 210 / (310) A1
S2
S3
S4
S6
P1 M1
A
S5
S8 B
8
VD.KT.X2.02 © Danfoss 03/2013
P3
P2
DEN-SMT/DK
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys A217.3, ex. a: DHW heating
A217.3, ex. c: DHW heating on demand (flow switch). With or without circulation
A230.1, ex. a: Indirectly connected heating system. Wind compensation as option
DEN-SMT/DK
VD.KT.X2.02 © Danfoss 03/2013
9
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys A230.2, ex. a: Indirectly connected cooling system (district cooling)
A231.2: Indirectly connected heating system with 2-pump control and refill water function
Danfoss 87H2005.10
ECL 210
S1
R4 P S7 S2
P1
S3
P2
S5
M1
S8
V1
P3
A331.2, ex. a: Heating system with two-pump control and refill water function. Supply temperature dependent flow temperature control.
R6
Danfoss 87H2004.10
ECL 310
S1
S9 P S7
S2
S10
S3
P1 P2
M1
P3
S5
S8
V1
P5
10
VD.KT.X2.02 © Danfoss 03/2013
DEN-SMT/DK
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys A232.1, ex. a: Control of flow temperature (heating in floor / cooling in ceiling) in relation to outdoor, room and dew point temperature.
A332.1, ex. a: Control of flow temperature (heating in floor / cooling in ceiling) in relation to outdoor, room and dew point temperature. Optional return temperature limitation.
A332.2, ex. a: Separated control of flow temperatures for heating / cooling in relation to outdoor, room and dew point temperature. Optional return temperature limitations.
DEN-SMT/DK
VD.KT.X2.02 © Danfoss 03/2013
11
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys A237.1, ex. a: Indirectly connected heating and DHW system S2
ECL 210 / (310)
Danfoss 87H2024.10
S1
R4 / (R6)
P1 S3 S6 P2 M1
S8
S5
P3
Danfoss 87H2022.10
A237.2, ex. a: Indirectly connected heating and DHW charging system
P1
S4
S3
S6 P2 M1
S8
S5
P3
P4
S1
(S7*)
ECL 210 / (310)
Danfoss 87H2039.11
A247.1, ex. a: Indirectly connected heating and DHW tank charging system. Parallel mode or DHW priority
A1 S3
M2
P1 S5
S4
M1
S6 A
S2
S8 B
P3
P2
(S7*) = optional in ECL Comfort 310 DEN-SMT/DK
VD.KT.X2.02 © Danfoss 03/2013
12
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
S1
(S7*)
ECL 210 / (310)
Danfoss 87H2038.11
A247.2, ex. a: Indirectly connected heating and DHW tank charging system with preheating circuit. Parallel mode or DHW priority
A1 S3 P1 M2
S5
S4
S6 P2
M1
A
S2
S8 B
P3
P4
(S7*) = optional in ECL Comfort 310
S1
S7
ECL 310
Danfoss 87H2057.10
A347.1, ex. a: Indirectly connected heating and DHW tank charging system. Parallel mode or DHW priority
R6 S3
M2
P1 S5
S4
M1
S6 A
S2
S8 B
DEN-SMT/DK
VD.KT.X2.02 © Danfoss 03/2013
P3
P2
13
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
S1
ECL 310
S7
Danfoss 87H2040.10
A347.2, ex. a: Indirectly connected heating and DHW tank charging system with preheating circuit. Parallel mode or DHW priority
R6 S3
P1 M2 S5
S4
S9 S6 P2
A
M1 S2
S8 B
P3
P4
A260.1, ex. a: Two heating systems
14
VD.KT.X2.02 © Danfoss 03/2013
DEN-SMT/DK
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys A260.1, ex. d: Two heating systems. Circuit 2 is a sub-circuit of circuit 1.
A266.1, ex. a: Heating and direct DHW heating system. Parallel mode or DHW priority.
DEN-SMT/DK
VD.KT.X2.02 © Danfoss 03/2013
15
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys A266.2: Heating and direct DHW heating system. Parallel mode or DHW priority. DHW heating on demand (flow switch)
A275.1, ex. a: Heating system with 1-stage boiler
Danfoss 87H2163.10
ECL 210 / (310)
S1
A1
S3 S7 P1 *
①
S5
B1
16
VD.KT.X2.02 © Danfoss 03/2013
DEN-SMT/DK
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys A275.2, ex. a: Heating system with 1-stage boiler and DHW tank Danfoss 87H2165.10
ECL 210 / (310)
S1
A1
S3 S7 P1
①
* S5
B1
S6
②
P3
A275.3, ex. a: Heating system with 1-stage boiler, mixing circuit and DHW tank
M2
Danfoss 87H2169.10
ECL 210 / (310)
S1
S4
S8
②
P4 S2 S3 S7 P1
①
* S5
B1
S6
③
P3
DEN-SMT/DK
VD.KT.X2.02 © Danfoss 03/2013
17
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys A375.1, ex. a: Up to 8 x boiler ON / OFF control for a heating circuit Danfoss 87H2182.10
ECL 310
S1
A1 S3
+ ECA 32
S7
B1
P1
B8
①
*
S5
A375.2, ex. a: Up to 8 x boiler ON / OFF control for a heating circuit and a DHW circuit. Optional DHW priority. Danfoss 87H2188.10
ECL 310
S1
A1 S3
+ ECA 32
S7
B1
P1
B8
①
*
S5
S6
② P4
P3
DEN-SMT/DK
VD.KT.X2.02 © Danfoss 03/2013
18
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys A375.3, ex. a: Up to 8 x boiler ON / OFF control for a direct heating circuit (1), a mixing circuit (2) and a DHW circuit (3). Optional DHW priority. Danfoss 87H2189.10
ECL 310
S1
A1 + ECA 32 M2
S3
S4
S8
②
P4 S2
S7
B1
P1
B8
①
*
S5
S6
③
P3
ECL 210
ECL 310
R2
R2
A275.1
1
1
A275.2
1
1
A275.3
1
1
Danfoss 87H2185.10
Burner control overview:
ECA 32
R3
R4
R5
2
3
4
Triac 5
Triac 6
R7
R8
R9
R10
A375.1
1
5
6
7
8
A375.2
1
2
7
8
3
4
5
6
A375.3
1
2
7
8
3
4
5
6
R2-R10 = relay nos. in ECL / ECA 32
DEN-SMT/DK
VD.KT.X2.02 © Danfoss 03/2013
19
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys A333.1, ex. a: Heating system with control of 1 or 2 circulation pumps. Refill water function with control of 1 or 2 pumps. Pressure measurements in the system.
A333.2, ex. a: Heating system with ON / OFF and speed control of 1 or 2 circulation pumps. Refill water function with ON / OFF and speed control of 1 or 2 pumps. Level control of refill water storage tank. Pressure measurements in the system.
DEN-SMT/DK
VD.KT.X2.02 © Danfoss 03/2013
20
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys A333.3, ex. a: Heating system with ON / OFF and speed control of 1 or 2 circulation pumps. Control valve M1 is 0 10 V controlled. Refill water function with ON / OFF and speed control of 1 or 2 pumps. Level control of refill water storage tank. Pressure measurements in the system.
A361.2, ex. a: 2 x heating systems with two-pump control and refill water function. Supply temperature dependent flow temperature control.
DEN-SMT/DK
VD.KT.X2.02 © Danfoss 03/2013
21
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys A367.1, ex. a: System with 2 heating circuits and secondarily connected DHW tank with internal heat exchanger. Optional DHW priority. Danfoss 87H2073.10
ECL 310
S1
R6 S4 S9 P5 M2 S2
S7
P1
S3 S6
M1
S8 S5
P3
P2
A367.2, ex. a: System with 2 heating circuits and secondarily connected DHW tank charging system. Optional DHW priority. Danfoss 87H2078.10
ECL 310
S1
R6 S4 (S7) P5 M2 S2
(S7)
P1
S3
S9 S6
M1 S5
S8
P2
DEN-SMT/DK
VD.KT.X2.02 © Danfoss 03/2013
P3
P4
22
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys A368.2, ex. a: Heating system with two-pump control and refill water function. Supply temperature dependent flow temperature control. DHW heating system with control of 1 or 2 circulation pumps.
A368.4, ex. a: Heating system with two-pump control and refill water function with 1 or 2 pumps. Supply temperature dependent flow temperature control. DHW heating system with control of 1 or 2 circulation pumps. Pressure measurements in the systems.
DEN-SMT/DK
VD.KT.X2.02 © Danfoss 03/2013
23
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys A376.1, ex. a: Two heating circuits and one direct DHW heating system. Parallel mode or DHW priority. Danfoss 87H2097.10
ECL 310
S1
R6 S3 S2
①
P2 M2 S5
S9 S7
②
P3 M3 S10
S4
③
M1 S6
P1
A376.2, ex. a: Two heating circuits and one direct DHW heating system. Parallel mode or DHW priority. DHW heating on demand (flow switch). Danfoss 87H2099.10
ECL 310
S1
R6 S3 (S2) P2
①
M2 S5
S9
S7
(S2)
②
P3 M3 S10
S4
③
M1 S6 S8
DEN-SMT/DK
VD.KT.X2.02 © Danfoss 03/2013
P1
24
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys A376.3, ex. a: Two heating circuits and one direct DHW heating system. Parallel mode or DHW priority. Control valves M1, M2 and M3 are 0 - 10 V controlled. Danfoss 87H2101.10
ECL 310
S1
R6 + ECA 32 S3 S2
①
P2 M2 S5
A
S9 S7
②
P3 M3 S10
A
S4
③
M1 A
S6
P1
ECL 310
S1
S8
S15 S16
Danfoss 87H2103.10
A376.9, ex. a: Two heating circuits and one direct DHW heating system. Parallel mode or DHW priority. Pressure measurements and temperature monitoring in the system.
R4 + ECA 32 S3
P2
①
P3
②
M2 S5
S11
S2
S7
S9
M3 S13
S12
S10
S14
S4
③
M1 S6
P1
DEN-SMT/DK
VD.KT.X2.02 © Danfoss 03/2013
25
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
S1
Danfoss 87H2139.11
A377.1, ex. a: Two heating circuits and one DHW tank charging system. Parallel mode or DHW priority. ECL 310 A1 S4
P5
②
P2
①
M3 S2
S3
M2 S5
S9 S6
③
A
M1 S10
P3
S8 B
P4
A377.2, ex. a: Two heating circuits and one DHW tank charging system. Control of the DHW heating temperature. Parallel mode or DHW priority.
Danfoss 87H2141.11
ECL 310
S1
A1 S4
② P5 M3 S2
①
P2
M1 S3
S9
S10
S6
③
A M2 S5
S8
P1
26
VD.KT.X2.02 © Danfoss 03/2013
P3
B P4
DEN-SMT/DK
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Ordering
Controller, base parts and accessories: Type
Designation
Code no.
ECL Comfort 310
Universal hardware - 230 V a.c. Base part is not included. Mounting guide (no text) is included.
087H3040
ECL Comfort 310
Universal hardware - 24 V a.c. Base part is not included. Mounting guide (no text) is included.
087H3044
ECL Comfort 310B
Universal hardware - 230 V a.c. Without display and dial. Requires a Remote Control Unit. Base part is not included. Mounting guide (no text) is included.
087H3050
ECL Comfort 310 base part
For mounting on wall or DIN rail (35 mm). ECL Comfort 210 can be mounted in an ECL Comfort 310 base part (for future upgrade). Mounting guide (no text) and cable inlet accessories is included.
087H3230
Remote Control Units and accessories Type
Designation
Code no.
ECA 30
Remote Control Unit with an integrated room temperature sensor and possibility for connecting an external Pt 1000 room temperature sensor. Base part for mounting on wall included. Mounting guide (no text) is included.
087H3200
ECA 31
Remote Control Unit with an integrated room temperature sensor and a humidity sensor. Possibility for connecting an external Pt 1000 room temperature sensor. Used for dedicated applications. Base part for mounting on wall included. Mounting guide (no text) is included.
087H3201
ECA 30 / 31 frame kit for mounting in panel front
For mounting in a panel cut-out. 087H3236 Format 144 × 96 mm, actual cut-out 139 × 93 mm. Mounting guide (no text) is included.
ECA 32
Internal extension module with additional inputs and outputs. To be placed in the ECL Comfort 310 base part. See separate data sheet.
087H3202
Type
Designation
Code no.
ECA 99
230 V a.c. to 24 V a.c. transformer (35 VA)
087B1156
Accessories:
ECL Application Keys
DEN-SMT/DK
Type
Application type description
A214
• Temperature control (heating / cooling) of ventilation systems. Duct / room 2 x 3-point, 2 x 2-point temperature control. Return temperature limitation. Flow / power limitation. Fire and frost protection as well as alarm function. • The A214 application key contains applications related to ECL Comfort 310 for increased functionalities (control of rotating heat-exchanger).
087H3811
A217
• Advanced temperature control of DHW (Domestic Hot Water) circuit with/ 1 x 3-point, 3 x 2-point without storage charging system. Circulation pump control. Return temperature limitation. Frost protection and alarm function. • The A217 application key contains applications related to ECL Comfort 310 for increased functionalities (M-bus).
087H3807
A230
• (A230.1) Weather compensated flow temperature control of heating 1 x 3-point, 2 x 2-point systems. Circulation pump control. Room temperature control and sliding return temperature limitation. Flow / power limitation. Wind compensation, frost protection and alarm function. • (A230.2) Flow temperature control of cooling systems. Compensation for outdoor and room temperatures. Return temperature limitation. • The A230 application key works in ECL Comfort 310 for increased functionalities (M-bus).
087H3802
A231
• Weather compensated flow temperature control of heating systems. 1 x 3-point, 3 x 2-point 2-pump control for circulation and refill water function. Sliding return temperature limitation. Frost protection and alarm function. • The A231 application key contains applications related to ECL Comfort 310 for increased functionalities (2 pumps for refill water and M-bus).
087H3805
A232
• Weather compensated flow temperature control of heating / cooling 1 x 3-point, 3 x 2-point circuit(s). Automatic change-over between heating and cooling. Circulation pump control. Dew point (cooling mode only) and surface temperature compensation. • The A232 application key contains applications related to ECL Comfort 310 for increased functionalities (return temperature limitation and separated control of heating and cooling circuits).
087H3812
VD.KT.X2.02 © Danfoss 03/2013
Controller output signals
Code no.
27
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys ECL Application Keys (continued): Type
Application type description
Controller output signals
Code no.
A237
• Weather compensated flow temperature control of heating systems. 1 x 3-point, 3 x 2-point Circulation pump control. Room temperature control and sliding return temperature limitation. Flow / power limitation. Temperature control of secondarily connected DHW circuit with storage tank charging system or storage tank with internal heat exchanger. Optional ON / OFF control of the DHW circuit in connection with primarily connected storage tank with internal heat exchanger. DHW circulation pump control. Frost protection and alarm function. • The A237 application key contains applications related to ECL Comfort 310 for increased functionalities (M-bus).
087H3806
A247
• Weather compensated flow temperature control of heating systems. 2 x 3-point, 3 x 2-point Circulation pump control. Sliding return temperature limitation. Flow / power limitation. Temperature control of DHW circuit with storage tank charging system. DHW circulation pump control through the storage tank or the heat-exchanger. Frost protection and alarm function. • The A247 application key contains applications related to ECL Comfort 310 for increased functionalities (room temperature sensor and M-bus).
087H3808
A260
• Weather compensated flow temperature control of heating systems. 2 x 3-point, 2 x 2-point Circulation pump control, room temperature control and sliding return temperature limitation for two independent heating circuits. Flow / power limitation, frost protection and alarm function. • The A260 application key works in ECL Comfort 310 for increased functionalities (M-bus).
087H3801
A266
• Weather compensated flow temperature control of heating systems. 2 x 3-point, 2 x 2-point Circulation pump control, room temperature control and sliding return temperature limitation. • Temperature control of DHW circuit with DHW circulation. Return temperature limitation, sliding DHW priority, frost protection and alarm function. Optional control of DHW heating based on DHW demand. • The A266 application key works in ECL Comfort 310 for increased functionalities (M-bus).
087H3800
A275
• Weather compensated flow temperature control of 1-stage boiler based 1 x 3-point, 4 x 2-point heating systems. One direct heating circuit and one mixing circuit. Circulation pumps control, room temperature control and sliding return temperature limitation. • Temperature control of DHW storage tank with internal heat exchanger. Frost protection and alarm function. • The A275 application key contains applications related to ECL Comfort 310 for increased functionalities (multiple boiler stages).
087H3814
A333
• Weather compensated flow temperature control of a heating system. ON / OFF and speed control of 1 or 2 circulation pumps and sliding return temperature limitation. Flow / power limitation. Frost protection and alarm function. ON / OFF and speed control of 1 or 2 refill water pumps. Refill water storage control. Pressure release function. Pressure and temperature monitoring. Frost protection and alarm function.
1 x 3-point, 7 x 2-point* or 1 x 0 - 10 V control*, 7 x 2-point*
087H3818
A361
• Weather compensated flow temperature control of 2 heating circuits. 2 x 3-point, 7 x 2-point* Supply temperature dependent flow temperature control. 2-pump control for circulation. Sliding return temperature limitation. Flow / power limitaion. Refill water function. Frost protection and alarm function.
087H3804
A367
• Weather compensated flow temperature control of 2 heating circuits. 2 x 3-point, 5 x 2-point Circulation pump control. Room temperature control and sliding return temperature limitation. Flow / power limitation. • Temperature control of secondarily connected DHW circuit with storage tank charging system or storage tank with internal heat exchanger. Optional ON / OFF control of the DHW circuit in connection with primarily connected storage tank with internal heat exchanger. DHW circulation pump control. Frost protection and alarm function.
087H3813
A368
• Weather compensated flow temperature control of a heating circuit. 2 x 3-point, 5 x 2-point Supply temperature dependent flow temperature control. 2-pump control for circulation. Sliding return temperature limitation. Flow / power limitation Flow / power limitation and refill water function. • Temperature control of a DHW circuit with DHW circulation, return temperature limitation and sliding DHW priority. Frost protection and alarm function.
087H3803
* ECA 32 module needed
28
VD.KT.X2.02 © Danfoss 03/2013
DEN-SMT/DK
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys ECL Application Keys (continued): Type
Application type description
Controller output signals
Code no.
A376
• Weather compensated flow temperature control of 2 heating circuits. Circulation pump control. Room temperature control and sliding return temperature limitation. Flow / power limitation. • Temperature control of a DHW circuit with DHW circulation, return temperature limitation and sliding DHW priority. Optional control of DHW heating based on DHW demand. Frost protection and alarm function.
3 x 3-point, 5 x 2-point or 3 x 0 - 10 V control*, 5 x 2-point
087H3810
A377
• Weather compensated flow temperature control of 2 heating circuits. 3 x 3-point, 5 x 2-point Circulation pump control. Room temperature control and sliding return temperature limitation. Flow / power limitation. • Temperature control of DHW circuit with storage tank charging system or storage tank with internal heat exchanger. DHW circulation pump control. Optional DHW heating temperature control. Frost protection and alarm function.
087H3817
* ECA 32 module needed
Each of the abovementioned code nos. comprises 1 ECL Application Key, 1 mounting guide and 1 set of multi-lingual user guides. Pt 1000 temperature sensors (IEC 751B, 1000 Ω / 0 °C): Type
Designation
Code No.
ESMT
Outdoor temperature sensor
084N1012
ESM-10
Room temperature sensor
087B1164
ESM-11
Pipe surface temperature sensor
087B1165
ESMB-12
Universal temperature sensor
087B1184
ESMC
Pipe surface temperature sensor incl. 2 m cable
087N0011
ESMU-100
Immersion sensor, 100 mm, copper
087B1180
ESMU-250
Immersion sensor, 250 mm, copper
087B1181
ESMU-100
Immersion sensor, 100 mm, stainless steel
087B1182
ESMU-250
Immersion sensor, 250 mm, stainless steel
087B1183
Pocket
Immersion, stainless steel 100 mm, for ESMU-100, Cu (087B1180)
087B1190
Pocket
Immersion, stainless steel 250 mm, for ESMU-250, Cu (087B1181)
087B1191
Pocket
Immersion, stainless steel 100 mm, for ESMB-12, (087B1184)
087B1192
Pocket
Immersion, stainless steel 250 mm, for ESMB-12, (087B1184)
087B1193
Accessories and spare parts:
Typical ordering, types:
Reference, additional products / software:
DEN-SMT/DK
ECL Comfort Controller
Base part
Appl. key
Remote Control Unit
Temperature sensors
Actuators / valves
ECL 310, 230 V a.c. ECL 310 B, 230 V a.c. ECL 310, 24 V a.c.
for ECL 310
A2xx A3xx
ECA 30 ECA 31
ESMT (outdoor) ESM-11 (pipe surface) ESMC (pipe surface) ESMU (immersion) ESM-10 (room) ESMB-12 (universal)
see dedicated literature
ECL Portal
Access to the ECL Comfort 310 via a web browser. After having arranged an account, access to the ECL Comfort 310 can also be done via a Smart phone.
See separate data sheet
ECL Tool
Software for laptop. Connect ECL Comfort 210 / 310 directly to laptop for e.g. parameter lists, commissioning reports.
Download from Internet
OPC server
For ECL Comfort 210 (Modbus connection) and ECL Comfort 310 (Modbus or TCP Ethernet connection).
See separate data sheet and download from Internet
VD.KT.X2.02 © Danfoss 03/2013
29
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Operation
A
B
The graphical monochrome display (A) shows all temperature values as well as status information and is used for the setting of control parameters. The display has backlight. Different favorite displays can be selected. Navigation, browsing and selecting the current item in the menus is done by means of the dial (multi-functional knob (B)).
The RCUs ECA 30 / 31 are used for remote setting and override of ECL Comfort controller. By means of the built-in room temperature sensor, the flow temperature can be corrected to keep a constant room temperature at comfort or saving temperature. The ECA 30 / 31 is operated as an ECL Comfort 310 with dial and backlighted display.
Examples of favorite displays:
30
VD.KT.X2.02 © Danfoss 03/2013
DEN-SMT/DK
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Functions
General functions: • The ECL Comfort 310 has all the required functions of a modern electronic temperature controller for heating and DHW applications. • The controller can be used as master or slave in systems with master / slave ECL Comfort 210 / 310 controllers. • The ECL Application Key contains the application software for flexible configuration. Furthermore, an update of the controller software is done automatically, if required. • The ECL Comfort 310 contains, besides the standard functions, log and alarm functions. • The built-in Real Time Clock gives automatic summer / winter time changeover, week and holiday schedule. • Motor protection, which ensures stable control and a long life of the motorized control valve, is available for most of the applications. In periods without heat demand, the motorized control valve is exercised to avoid blocking. • Scheduled control (Comfort and Saving mode) is based on a week program. A holiday program gives the possibility to select days with comfort or saving mode. • The ECL Comfort 310 can receive pulses from a heat or flow meter to limit the power or the flow. Alternatively, the data can come from heat or flow meter via the M-bus connection. • In many applications analogue input (0 – 10 V) is configured for pressure measuring among others. The scaling is set in the controller. • Some applications are configured to handle digital input. This function can be used to have an external switch to run comfort or saving mode or react on a flow switch signal. • The control parameters, proportional band (Xp), integration time (Tn), running time of the motorized control valve and neutral zone (Nz) can be set individually for each output (3-point control). • Motorized control valves in some applications can be controlled with a 0 - 10 V signal. • Several applications fulfil the demand for refill water function and / or 2-pump control.
Communication
Heating functions: • The heat curve (relationship between outdoor temperature and desired flow temperature) is set by means of 6 coordinate points or a slope value. Max. / min. limitation of the desired flow temperature can be set. In some application sub-types (for example A337, A347, A367, A375 and A377) the desired flow temperature can be set by means of a voltage in the range 0 - 10 volt. • The return temperature limitation can work in relation to the outdoor temperature or be a fixed value. • The heating cut-out function can switch OFF the heating and stop the circulation pump at high outdoor temperatures. • Based on the room temperature the ECL Comfort 310 can correct the desired flow temperature in order to increase the comfort level. • The optimizer function ensures heating in the desired periods (the lower outdoor temperature, the earlier cut-in of the heating). • The ramping function makes a smooth cut-in of the heating valuable (district heating installations). • The boost function makes a powerful cut-in of the heating (boiler based installations). • The circulation pump is controlled in relation to heat demand and frost protection. In periods without heat demand, the circulation pump is exercised to avoid blocking. • The saving function gives two possibilities: · reduced flow temperature with fixed reduction or reduction in relation to outdoor temperature (the lower the outdoor temperature, the less the reduction), · heating off, still with active frost protection DHW functions: • The Auto Tuning function with automatic setting of control parameters for constant DHW temperature is integrated in the application A217, A266, A368 and A376. However, Auto Tuning is only applicable with valves that are approved for Auto Tuning, i.e. the Danfoss types VB 2 and VM 2 with split characteristic as well as logarithmic valves such as VF and VFS. • The anti-bacteria function can follow a schedule program. • The heating circuit can have sliding DHW priority.
The ECL Comfort 310 has: • ECL 485 bus, non-galvanic isolated, for closed communication between master, slave and RCUs. • RS 485 bus, galvanic isolated, for Modbus communication. • M-bus, non-galvanic isolated, for M-bus communication with meters. • USB, type B, for ECL Tool (software for PC). • Ethernet, RJ 45, for TCP communication to SCADA systems. Master / slave connections
DEN-SMT/DK
VD.KT.X2.02 © Danfoss 03/2013
31
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Languages
Menu languages are selectable among approx. 20 languages. See “Language list”.
General data
ECL Comfort controller and RCU data:
Furthermore, English is always uploaded in parallel to the selected language.
ECL Comfort 310 / 310B Ambient temperature
ECA 30 / 31 0 - 55 °C
Storage and transportation temperature
-40 - 70 °C
Mounting
Vertically, on wall or DIN rail (35 mm)
Vertically, on wall or in panel cut-out
Connections
Terminals in base part
Terminals in base part
Number of inputs
8 in total: 6 temperature sensors 4*) Pt 1000 sensor, digital, analogue or pulse
-
Temperature sensor type
Pt 1000 (1000 ohm at 0 °C), IEC 751B Range: -60 – 150 °C
Alternative to built-in room temperature sensor: Pt 1000 (1000 ohm at 0 °C), IEC 751B
Digital input
12 V pull-up possible
-
Analog input
0 - 10 V, resolution 9 bits
-
Pulse input
Max. 200 Hz
-
Weight
0.46 / 0.42 kg
0.14 kg
Display (ECL Comfort 310 and ECA 30 / 31 Graphical monochrome with backlight only) 128 × 96 dots Display mode: Black background, white text Setting (ECL Comfort 310 and ECA 30 / 31 Dial with intuitive push and turn function only) Setting (ECL Comfort 310 B)
ECA 30 / 31
Min. backup time for time and date
72 hours
-
Backup of settings and data
Flash memory
Flash memory
Grade of enclosure
IP 41
IP 20
-marking in accordance with the standards
EMC directive 2004/108/EC Immunity: EN 61000-6-1:2007 Emission: EN 61000-6-3:2007 LVD directive 2006/95/EC EN 60730
*) Configured at application upload.
ECL application key:
32
Storage type
Flash memory
Segmentation
Part 1: Application data, not changeable Part 2: Factory settings, not changeable Part 3: Updating SW for the ECL Comfort controller, not changeable Part 4: User settings, changeable
Applications
A2xx keys work in ECL Comfort 210 and ECL Comfort 310 A3xx keys work in ECL Comfort 310 only
Lock function
If not inserted in the ECL Comfort controller, all settings can be seen, but not changed
VD.KT.X2.02 © Danfoss 03/2013
DEN-SMT/DK
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys ECL 485 communication bus data: Purpose
For internal ECL Comfort 210 / 310 and ECA 30 / 31 use only (Danfoss proprietary bus)
Connection
Terminals in base part Non-galvanic isolated
Cable type
Shielded cable, 2 x twisted pair, Min. cross section: 0,22 mm (AWG 24). Examples: LiYCY 2 × 2 × 0.25 mm2 (AWG 24) or Ethernet CAT5
Max. total cable length (bus cable + sensor cables)
200 m in total (inclusive sensor cables)
Max. number of ECL slaves connected
Units with unigue address (1 - 9): 9 Units with address “0”: 5
Max. number of Remote Control Units connected
2
Data sent from master
Date Time Outdoor temperature Desired room temperature DHW-priority signal
Data sent from addressed slave controller
Desired flow temperature from each circuit
Data sent from ECA 30 / 31
• Actual and desired room temperature • Function selector mode • (ECA 31) Relative humidity
Modbus communication data: Purpose
For SCADA system
Connection
Terminals 34 and 35 in base part. Modbus reference (terminal 36) must be connected. Galvanic isolated (500 V).
Protocol
Modbus RTU
Cable type
Shielded cable, 2 x twisted pair + Signal GND. Min. cross section: 0,22 mm2 (AWG 24). Example: LiYCY 2 × 2 × 0.25 mm2 (AWG 24)
Max. bus cable length
1200 m (dependent on cable type and installation).
Communication speed
Half duplex. 9,6 Kbit/s (default) / 19.2 Kbit/s / 38.4 Kbit/s
Serial mode
8 data bit, even parity and 1 stop bit.
Network
According to the standard Modbus Serial Line Implementation Guide V1.0.
M-bus communication data: Purpose
Connection to heat meters, max. 5 heat meters
Connection
Terminals 37 and 38 in base part. Non-galvanic isolated
M-Bus master according to
DS / EN 1434-3: 1997
Cable type
2 x 0,8 mm2 Example: JY(St)Y 2 x 0.8 mm2 (not twisted pair)
Max. cable length
50 m
Baud rate
300 baud (adjustable)
Update time
60 s (adjustable)
Gateway function
Allows the ECL Portal to read energy meters directly
Supported heat meters
Infocal 6 and many other marks and types. Information about other heat meters on request
Transmitted heat meter data
Heat meter type dependent: • Primary flow temperature • Primary return temperature • Actual flow / accumulated flow • Actual heat / power • Accumulated heat energy
Recommendations:
Danfoss recommends 230 V a.c. supplied heat meters
USB communication data:
DEN-SMT/DK
USB CDC (Communication Device Class)
For service purposes (Windows driver is needed, to enable that Windows recognize the ECL as a virtual COM port)
Modbus over USB
Similar to the serial Modbus, but with relaxed timing
Connection, cable type
Standard USB cable (USB A -------- USB B)
VD.KT.X2.02 © Danfoss 03/2013
33
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys Ethernet communication (Modbus / TCP) data: Purpose
For SCADA system
Connection
RJ45 female connector
Protocol
Modbus / TCP
Cable type
Standard Ethernet cable (CAT 5)
Max. Bus cable length
According to Ethernet standard
Auto cross-over detection
Enabled
Default Ethernet address (IP address)
192.168.1.100
Port number
502 (Modbus / TCP port)
Number of connections
1
Security
Must be provided by Ethernet infrastructure
A port: USB (type B female plug) B port: Ethernet C port: ECL Application Key
Languages (alphabetic order)
Bulgarian
Estonian
Italian
Russian
Croatian
Finnish
Latvian
Serbian
Czech
French
Lithuanian
Slovak
Danish
German
Polish
Slovenian
Dutch
Hungarian
Romanian
Swedish
English The selected language + English is uploaded at application upload.
Comparison ECL Comfort 310 / 210
34
ECL Comfort 310
ECL Comfort 210
M-bus communication
Yes
No
Modbus connection
Yes, galvanic isolated
Yes, non-galvanic isolated
Ethernet
Yes, RJ45 connection, Modbus / TCP. For SCADA solutions and ECL Portal
No
Inputs
10
8
Relay outputs
6
4
Valve actuator outputs
3 pairs
2 pairs
Extension of inputs / outputs
Yes, ECA 32, placed in base part. • 6 inputs • 2 pulse inputs • 3 analogue outputs (0 - 10 V) • 4 relays
No
VD.KT.X2.02 © Danfoss 03/2013
DEN-SMT/DK
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Wiring - 230 V a.c.
ECL Comfort 310 wiring example Supply voltage
230 V a.c. - 50 Hz
Voltage range
207 to 244 V a.c. (IEC 60038)
Power consumption
5 VA
Max. load on relay outputs
4(2) A - 230 V a.c. (4 A for ohmic load, 2 A for inductive load)
Max. load on actuator outputs
0.2 A - 230 V a.c.
Wiring - 24 V a.c.
ECL Comfort 310 wiring example Auxiliary relays (K) must be used in order to separate the 230 V a.c. supply from the 24 V a.c. supply of the controller.
DEN-SMT/DK
Supply voltage
24 V a.c. - 50 Hz
Voltage range
21.6 to 26.4 V a.c. (IEC 60038)
Power consumption
5 VA
Max. load on relay output
4(2) A - 24 V a.c. (4 A for ohmic load, 2 A for inductive load)
Max. load on actuator output
1 A - 24 V a.c.
VD.KT.X2.02 © Danfoss 03/2013
35
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Wiring - ECA 30 / 31 Remote Control Unit
ECA 30 / 31 ECL 210 / 310
Danfoss 87H2051.10
Wiring - input
B A B A
ESM-10
Wiring of ECL Comfort 310 / 310B and ECA 30 / 31 Supply voltage
From ECL 485 communication bus
Power consumption
1 VA
External room temperature sensor
Pt 1000 (ESM-10), substitutes the built-in room temperature sensor
ECA 31 only
Contains humidity sensor, used for special applications
Base part
ECL Comfort 310 base part (can be used for ECL Comfort 210 too).
36
VD.KT.X2.02 © Danfoss 03/2013
DEN-SMT/DK
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Dimensions
ECL Comfort 310
ECL Comfort 310B
ECA 30 / 31
ECA 32
DEN-SMT/DK
VD.KT.X2.02 © Danfoss 03/2013
37
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
ECA 30 / 31 cut-out for mounting in panel front
38
A frame (code no. 087H3236) is placed in the cut-out (139 × 93 mm) in which the ECA 30 / 31 is placed.
VD.KT.X2.02 © Danfoss 03/2013
DEN-SMT/DK
Data sheet Tender text:
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Electronic controller for heating and domestic hot water application 1a Electronic weather compensator for flow temperature control in heating and domestic hot water installations. Turn-push-dial, backlighted graphic display and menu based operation in local languages. The controller can operate multiple application uploaded by means of application software keys.
1b • Heat curve setting in 6 coordinates or as slope. • Flow temperature limitations. • Room temperature compensation and Comfort / Saving periods according to week schedule. • Holiday schedule. • Return temperature limitation as a fixed value (DHW) or in relation to outdoor temperature (heating). • Pumps controlled in relation to heat demand and frost protection. • Alarm functions and log pictures for all sensors. • Manuel override of the individual outputs. • Communication: M-bus (up to 5 meters), Modbus, Ethernet, ECL 485 (internal data bus). • Connection for commissioning / service via PC • 6 temperature sensor (Pt 1000) inputs. • 4 application related and configured inputs. • 6 relay outputs • 3 pairs of electronic output for noiseless operation of the motorized control valve. Extension module enables: • Additional 6 configurable inputs • 2 pulse counters • 4 relay outputs • 3 analogue outputs 1c Main data: • Supply voltage, 230 V a.c., 50 Hz: ECL 310 and ECL 310 B • Supply voltage, 24 V a.c., 50 Hz: ECL 310 • Power consumption: max. 5 VA • Ambient temperature: 0 – 55 °C • Storage temperature: -40 – 70 °C 2 Product characteristics: • Protection class: IP 41 • DIN rail adaptor integrated • Dimension (inclusive base part) L*W*H, 220*110*80 mm • Ordering code no.: ECL Comfort 310, 230 V: 087H3040 • Ordering code no.: ECL Comfort 310B, 230 V: 087H3050 • Ordering code no.: ECL Comfort 310, 24 V: 087H3044
DEN-SMT/DK
VD.KT.X2.02 © Danfoss 03/2013
39
Data sheet
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Additional documentation for ECL Comfort 310, modules and accessories is available on http://den.danfoss.com/
40
VD.KT.X2.02
Produced by Danfoss A/S © 03/2013
Safety Thermostats ST-1/ST-2
Data sheet
Safety thermostat ST-1/ST-2 Application
ST-1
ST-2
Safety thermostats ST-1 and ST-2 can be used in directly or indirectly connected district heating systems where extra safety is required. ST-1 incorporates a thermostat (TR) and a safety monitor (STW) with automatic reset. ST-2 incorporates a thermostat (TR) with automatic reset and a safety limit cutout (STB) with manual reset.
Ordering
Type
TR 30 - 120 oC 30 - 90 oC
ST-1 (TR/STW) ST-2 (TR/STB)
If ST-1 or ST-2 is used together with an AMV(E) 13, 23, or 33 three-point controlled actuator, the safety monitor (STW) or safety limit cutout (STB) releases the spring return function for forced closure of the motorized control valve. The safety thermostats are approved in accordance with DIN 3440 with the following DIN Register Nos.: ST-1: TR STW 1175 05 ST-2: TR STB 1176 05
Setting STW 100 - 120 oC -
STB 95 oC
Accessory Sensor pocket (Cu/Ms) for ST1 / ST2
Technical data
ST-1 Setting Differential Reset
TR 30 - 120 oC 4±1K Auto
Contacts Contact loads Max. ambient temperature Max. sensor temperature Cut-out accuracy Enclosure Mounting direction Sensor connection Cable entry Pressure stage Medium Sensor Sensor pockets (takes both sensors) Storage and transport temperature Approvals DH-SMT/DK
VD.77.H6.02 © Danfoss 10/2006
Code no. 087N1050 087N1051 087N1201
STW 100 - 120 oC 12 ± 3 K Auto
ST-2 Setting Differential Reset
TR 30 - 90 oC 4±1K Auto
STB 95 oC 12 ± 3 K Manual
Ag 1000/1000 10 (2.5) A 250 V ~ / 7 A 380 V ~ 80 oC 130 oC +0 K - -6 K IP 40 No restrictions R½ M 20 PN 10 Water, pH 7 - 10 2 off Ø 9 x 100 Brass Ms 58/copper -15 oC - +80 oC DIN 3440 and VDE 0631 1
Data sheet
Safety thermostat ST-1/ST2
Electrical connections
ST with Danfoss ECL Comfort and AMV(E) 13, 23, or 33 connected
Dimensions
2
VD.77.H6.02 © Danfoss 10/2006
DH-SMT/DK
Sensors Temperature sensors (Pt 1000)
Data sheet
Temperature sensors (Pt 1000) ESMT, ESM-10, ESM-11, ESMB-12, ESMC, ESMU Application
ESMB-12 ESM-10
ESMT
ESMU
- Platinum-based sensors, 1000 Ω at 0 °C All the temperature sensors are two-wire devices, and all connections are interchangeable.
Ordering
ESMC
ESM-11
The surface sensor type ESM-11 has a spring contact surface to ensure a good heat transfer on pipes of all sizes. The basic sensor contains a platinum element with a characteristic that complies with EN 60751.
Temperature sensors Type ESMT ESM-10 ESM-11 ESMB-12 ESMC ESMU-100 ESMU-250 ESMU-100 ESMU-250
Designation Outdoor sensor Room temperature sensor Surface sensor Universal sensor Surface sensor Immersion sensor, 100 mm, copper Immersion sensor, 250 mm, copper Immersion sensor, 100 mm, stainless steel Immersion sensor, 250 mm, stainless steel
Code No. 084N1012 087B1164 087B1165 087B1184 087N0011 087B1180 087B1181 087B1182 087B1183
Accessories and spare parts Type Pocket Pocket
Designation Immersion, stainless steel 100 mm, for ESMU-100, Cu ( 87B1180) Immersion, stainless steel 250 mm, for ESMU-250, Cu ( 87B1181)
Pocket Immersion, stainless steel 100 mm, for ESMB-12, ( 87B1184) Pocket Immersion, stainless steel 250 mm, for ESMB-12, ( 87B1184) Heat conducting paste 3.5 cm3 Plastic ties e.g. for ESM-11 (25 pcs)
Code No. 087B1190 087B1191 087B1192 087B1193 041E0110 087B1167
Wiring
Connection cable: 2 x 0.4 - 1.5 mm2 DH-SM
VD.74.I7.02 © Danfoss 10/2005
Resistance characteristics 1
Data sheet
Temperature sensors ESMT, ESM-10, ESM-11, ESMB-12, ESMC, ESMU
Data, general
All temperature sensors contain a Pt 1000 element. Instructions are supplied with the products. Type ESMT ESM-10 ESM-11 ESMB-12 ESMC ESMU-100/-250
Temperature range -50 to 50 °C -30 to 50 °C 0 to 100 °C 0 to 100 °C 0 to 100 °C 0 to 140 °C
Enclosure IP 54 IP 54 IP 32 IP 54 IP 54 IP 54
0 to 180 °C
-
Pocket
Time constant ≤ 15 min 8 min 3s 20 s 10 s 2 s (in water) 7 s (in air) See “Data specific”
PN 25 25
Packing
Pocket ESMT ESM-10 ESM-11
Cover: ABS Base: PC (polycarbonate) Cover: ABS Base: ABS Cover: ABS Base: PC (polycarbonate) Encapsulation: 18/8 stainless steel Cable: 2.5 m, PVC, 2 x 0.34 mm2 Encapsulation: Top part: Nyrol, button part: Nickel coated Cu Cable: 2 m, PCV, 2 x 0.2 mm2 Tube and body: AISI 316 Head: PA (polyamide) Tube: Copper (Cu) Body: Brass Head: PA (polyamide) Tube and body: AISI 316 Terminal block for 2 wires in base part Terminal block for 2 wires in base part Terminal block for 2 wires in base part
ESMB-12 ESMC ESMU-100/-250 ESMT/ESM-10 ESM-11/ESMC ESMB-12 ESMU-100/-250 Pocket
2-wire cable (2 x 0,34 mm2) spliced 2-wire cable (2 x 0,2 mm2) Terminal block for 2 wires in head, PG 9 cable entry supplied with the product Wall mounting with screws (supplied with the product) Clamp for tube DN 15-65 supplied For pipe or flat surface or in pocket G 1/2 A and water (is supplied with the product) G 1/2 A
ESMT ESM-10 ESM-11 ESMB-12 Materials ESMC ESMU-100/-250 ESMU-100/-250 Cu
Electrical connection
Mounting
xx xx xx x x x x
x = PE (polyethylene) bag xx = Cardboard
Data, specific
Sensor characteristics
Referring to EN, Class 2 B ESMU (Cu) in pocket
Time constants ESMB in pocket
2
VD.74.I7.02 © Danfoss 10/2005
Max. deviation 2 K 32 s (in water) 160 s (in air) 20 s (in water) 140 s (in air)
DH-SM
Data sheet
Temperature sensors ESMT, ESM-10, ESM-11, ESMB-12, ESMC, ESMU
Dimensions
ESMT
ESM-11
ESM-10
ESMC
ESMU-100/-250
ESMB-12
Sensor pocket for ESMB-12
Sensor pocket for ESMU-100/-250
087B1182 and 087B1183 ESMU
DH-SM
(A) (B) (C)
VD.74.I7.02 © Danfoss 10/2005
Stainless steel (AISI 316) Stainless steel (AISI 316)
087B1180 and 087B1181 Copper (Cu) Brass
3
Data sheet
Temperature sensors ESMT, ESM-10, ESM-11, ESMB-12, ESMC, ESMU
4
VD.74.I7.02 © Danfoss 10/2005
DH-SM