engineering & installation manual engineering & installation manual

7 downloads 399 Views 2MB Size Report
OWNER SHALL MAINTAIN THIS MANUAL IN LEGIBLE CONDITION FOR ..... Liquid Volume Control. Overheat Protection. EX-100G(O). 100 HP. 3,450 LB/HR.
MIURA EX BOILER 170/250 PSI Designs

®

ENGINEERING & INSTALLATION MANUAL ®

C

®

APPROVED

EX - HIGH EFFICIENCY SERIES MIURA BOILER WEST, INC.

* IN OUR CONTINUING EFFORT TO IMPROVE OUR PRODUCT, INFORMATION IN THIS MANUAL MAY BE CHANGED WITHOUT NOTICE OWNER SHALL MAINTAIN THIS MANUAL IN LEGIBLE CONDITION FOR FUTURE REFERENCE PUBLICATION REVISED MARCH 2000 ENGINEERING REVISED FEBRUARY 2000

ECONOMIZER

FLUE

FLUE GAS OUTLET

ONO TO EC

TH GAS PA

MIZER

STEAM OUTLET VALVE

SECONDARY LOW WATER CUT OFF SOOT BLOWER PIPE

HIGH LIMIT STEAM PRESSURE SWITCH

SECONDARY WATER PUMP CONTROL

HIGH STEAM PRESSURE SWITCH (LOW FIRE CONTROL)

FLAME EYE

LOW STEAM PRESSURE SWITCH (HIGH FIRE CONTROL)

MAIN GAS INLET

STEAM SEPARATOR

PRESSURE GAUGE DAMPER

FLAME PORT SAFETY VALVE OUTLET AIR INLET INSPECTION PORT

CASTABLE LIQUID VOLUME CONTROLLER (PRIMARY PUMP CONTROL) BAFFLE PLATE

EXPANSION RING STOPS FEEDWATER PUMP INSULATION

STARTS FEEDWATER PUMP

AUTO “SURFACE” BLOWDOWN VALVE

LOW WATER CUT OFF FLUE GAS OUTLET

SAMPLE WATER THERMOCOUPLE CONDUCTIVITY SENSOR

FEEDWATER INLET

CASTABLE INSPECTION PORT INNER FEEDWATER PIPE

Figure 1 Functional Outline of EX-300 and Economizer

ii

MANUAL BOTTOM BLOWOFF

LIST OF ILLUSTRATION FIGURES LIST OF TABLES

v vi

1 SECTION ONE - INTRODUCTION

1

1.1 CODE AND REGULATORY AGENCIES 1.2 NATIONAL REGULATORY ORGANIZATIONS 1.2.1 MIURA BOILER STEAM GENERATORS (INSPECTOR BRIEFING) 1.3 STANDARD EQUIPMENT 1.4 GUARANTEE 1.5 DEFINITIONS AND SYMBOLS 1.6 ABOUT THIS MANUAL 1.7 OFFICES

1 2 3 5 6 6 7 7

2 SECTION TWO - SPECIFICATIONS

8

3 SECTION THREE - INSTALLATION

14

3.1 UNLOADING 3.2 ASSEMBLING 3.2.1 FEED WATER PUMP 3.2.2 FEED WATER CONTROL VALVES 3.2.3 BLOWER ASSEMBLY 3.2.4 STEAM SEPARATOR ASSEMBLY 3.3 BOILER POSITIONING AND ANCHORING 3.3.1 BOILER PROPER 3.3.2 ECONOMIZER INSTALLATION 3.4 STEAM PIPING 3.5 FEED WATER SYSTEM PIPING 3.6 FEED WATER PUMP 3.6.1 FEED WATER CONTROL VALVES 3.6.2 PIPING FLUSHING 3.7 SAFETY RELIEF VALVES, INSTALLATION 3.8 BLOW DOWN PIPING 3.9 FUEL SUPPLY ARRANGEMENTS 3.9.1 GAS PIPING 3.9.2 OIL PIPING 3.10 ELECTRICAL INSTALLATION 3.10.1 PANEL LAYOUT 3.10.2 BOILER INTERFACE CAPABILITIES 3.11 CLEARANCE 3.12 VENTILATION 3.13 STACKS AND BREACHING

14 15 15 16 16 18 19 19 19 20 21 23 26 26 27 28 30 30 33 34 36 36 37 37 38

4 SECTION FOUR - OPERATION

41

4.1 SAFETY FEATURES AND OPERATING CONTROLS 4.1.1 LOW WATER VOLUME CUT-OFF 4.1.2 OVERHEAT MONITOR TEMPERATURE 4.1.3 SCALE MONITOR TEMPERATURE 4.1.4 HIGH PRESSURE LIMIT CUT-OFF 4.1.5 MISFIRE

41 41 42 42 42 43

iii

4.1.6 FALSE SIGNALS 4.1.7 POWER OVERLOAD 4.1.8 AIR PRESSURE 4.1.9 FUEL GAS PRESSURE 4.1.10 FUEL OIL PRESSURE 4.2 ROUTINE BOILER OPERATION 4.2.1 PREPARATION BEFORE START-UP 4.2.2 START-UP 4.2.3.1 BLOW DOWN 4.2.3.1 BOTTOM BLOW DOWN 4.2.3.2 AUTOMATIC BOTTOM BLOW DOWN (OPTION) 4.2.4 SHUTDOWN 4.2.5 CAUTIONS DURING OPERATION 4.2.6 EXTENDED SHUTDOWN 4.2.7 CARRY OVER 4.2.8 MAKE-UP WATER 4.2.9 MAKE-UP WATER MAINTENANCE CHECK 4.2.10 WATER SPECIFICATIONS

43 43 43 44 44 44 44 45 45 45 46 47 47 48 48 48 49 49

5 SECTION FIVE - MAINTENANCE

50

5.1 MAINTENANCE & CLEANING SCHEDULE 5.2 TROUBLE SHOOTING 5.2.1 PHYSICAL PROBLEM AND CORRECTIVE ACTION 5.3 OPERATING DISCIPLINES 5.4 RECOMMENDED SPARE PARTS LIST

50 51 51 54 55

iv

LIST OF ILLUSTRATION FIGURES Figure 1 Functional Outline of EX-300 and Economizer Figure 2 Lifting and Handling Points Figure 3 Feed Water Pump Foundation and Installation Figure 4 Pump Base Mounting Holes Figure 5 Blower Foundation Dimensions Figure 6 Blower and Air Duct Assembly Figure 7 EX-250~300 Steam Separator Assembly Figure 8 Junction Box Figure 9 Conductivity Sensor E-6 Figure 10 EX Series Boiler Base Plate Figure 11 Economizer Mounting Figure 12 Steam Line and Trap Arrangement Figure 13 Recommended Feed Water Piping Arrangement Figure 14 Economizer Safety Relief Valve Installation Figure 15 Boiler Safety Valve Installation Figure 16 Blow Down Piping Arrangement Figure 17 Double Blow Down Isolation Valve Options Figure 18 Automatic Blow Down System Check Valve Figure 19 Typical EX Series Gas Train and Vent Points Figure 20 Main Gas Pressure Regulator Vent Piping Figure 21 Pilot Gas Regulator Vent Line Connection Figure 22 Gas or Air Pressure Switch Connection Figure 23 Oil Pump Piping Figure 24 EX Series Boiler Electrical Connection Figure 25 Boiler Control Panel Figure 26 Stack Installation Figure 27 Stack Design Figure 28 Stack and Economizer Bolting Dimensions Figure 29 Water Volume Control Illustration

v

ii 15 15 16 17 17 18 18 18 19 20 21 21 27 27 28 29 29 31 31 32 32 33 34 35 38 38 39 40

LIST OF TABLES Table 1 EX Series Specifications (without Economizer) Table 2 EX Series Specifications (with Economizer) Table 3 EX Series Specifications Flue Gas Re-Circulation Table 4 EXH-100(S)G(O) Specifications Table 5 EXH-200 (S)G(O) Specifications Table 6 EXH-300 (S)G(O) Specifications Table 7 EX Series Feed Pump Foundation Dimensions Table 8 EX Series Blower Foundation Dimensions Table 9 Main Steam Outlet Connection Size Table 10 Feed Water Pump Suction Strainer Size Table 11 Feed Water Pump Recommendations Table 12 Blow Down Piping Sizes Table 13 EX Gas Piping Sizes Table 14 Oil Inlet Pipe Sizing Table 15 Electrical Specifications Table 16 Boiler Minimum Clearance Requirements Table 17 Minimum Boiler Ventilation Opening Requirements Table 18 Floatless Switches and Probes Table 19 Boiler Water Chemistry Specifications Table 20 Recommended Periodic Maintenance Schedule Table 21 Motor Service and Lubrication Schedule Table 22 Physical Problem and Corrective Action Chart Table 23 Recommended Spare Parts List

vi

8 9 10 11 12 13 16 17 20 21 25 27 30 32 33 36 36 40 48 49 49 50 54

1 SECTION ONE - INTRODUCTION Muira Boiler Co., Ltd. began North American activities in 1988 when the manufacturing plant in Brantford, Ontario, was established. Their engineering department developed procedures to meet ASME codes and listing approval from IRI/FM, UL, and pre-approval for the SCAQMD (Southern California Air Quality Management District). The United States corporate sales office, Miura Boiler West, Inc., was established and has developed relationships with national, state, and city inspectors and agencies. The North American network consists of branches in Chicago, Los Angeles, and Ontario. The parent company, Miura Boiler, Ltd. in Japan, is the leading manufacturer of boilers and other thermal equipment in the Pacific Rim holding more than 55% of the market. With factories in five countries, production now exceeds 14,000 units per year. As a result of design necessities in Japan, such as limited space and total dependence on foreign energy, the MIURA STEAM BOILER has been engineered as a highly efficient, vertical water tube, once-through forced-flow design. The MIURA Boiler features a compact unit with a low-water content and is designed to run with a minimum amount of maintenance with simple push-button controls. Operation is quiet, radiant heat losses are minimal, and steam quality is second to none. Miura Boilers are often installed in a multiple boiler network. MIURA Boilers, along with the patented MIURA Multiple Installation panel, allow appropriate horsepower to be brought on and off line quickly to meet sophisticated production needs with maximum fuel economy. The 35-year, field-proven ‘Miura Advantage’ is the ability to reach full output steam from cold start in less than five minutes using the least amount of energy and having the lowest environmental impact. The high efficiency Miura Boiler has won numerous awards from engineering societies and gas associations because it is a compact, safe, cost-effective boiler.

1.1 CODE AND REGULATORY AGENCIES There are a number of codes, standards, laws, and regulations covering boilers and related equipment that should be considered when designing a system. Regulatory requirements are dictated by a variety of sources and are all focused primarily on safety. The equipment shall be installed in accordance with the current regulations, codes, and specifications of the applicable city, county, state, and federal agencies. Authorities having jurisdiction should be consulted before installations are made. For more information on how the various rules affect boiler selection and operation, you may want to contact your local MIURA authorized representative or the engineering firm designing the boiler installation. Here are some essential rules to consider: • The boiler industry is tightly regulated by the American Society of Mechanical Engineers (ASME) and the ASME codes, which control boiler design, inspection, and quality assurance. The boiler’s pressure vessel must have an ASME stamp. (Deaerators, economizers, and other pressure vessels must also be ASME stamped.) • The insurance company insuring the facility or boiler may dictate additional requirements. Boiler manufacturers provide special boiler trim according to the requirements of the major insurance companies. Special boiler trim items usually pertain to added safety controls. Some industries, such as food processing, brewing, or pharmaceuticals, may also have additional regulations that have an impact on the boiler and the boiler room. • UL and /or ASME-CSD1 specifications may be required. State or local authorities may require data on the boiler controls or basic design criteria. • Most areas have established a maximum temperature at which water can be discharged to the sewer. In this case, a blow down separator after cooler is required. • Most state, local, or provincial authorities require a permit to install and /or operate a boiler. Additional restrictions may apply in non-attainment areas where air quality does not meet the national ambient air quality standards, and emission regulations are more stringent. Be sure to investigate this before buying a boiler. • For all new boilers with inputs over 10 Million Btu/Hr, U.S. Federal emission standards apply, including permitting and reporting procedures. 1

• A full-time boiler operator may be required. Operator requirement depends on the boiler’s size, pressure, heating surface area, and volume of water. Boilers can be selected which minimize the requirements, either by falling under the requirements and being exempt, or with special equipment with special equipment that

gives the operator more freedom in the facility. Contact the local boiler inspector for details. • Most states or provinces require an annual boiler inspection. There may be other requirements on piping as well. A partial list of agencies having jurisdiction over boiler installation and operation is given below. This list is comprehensive but by no means all-inclusive. United States Environmental Protection Agency A.S.M.E. Codes and Standards National Board Licensing Requirements American Gas Association Standards Underwriters Laboratories, Inc. Factory Mutual Insurers Industrial Risk Insurers Occupational Safety and Health Administration Food and Drug Administration Local, City, and State Fire Marshall State Boiler Inspection Division Division of Labor and Industry for the Local State or City Local Building and Construction Code Inspectors MIURA Boiler recommends contacting your actual insurance provider as well as the utility companies for assistance in identifying and complying with codes. 1.2 NATIONAL REGULATORY ORGANIZATIONS

A.S.M.E. 345 East 47th Street New York, NY 10017 PHONE: (212) 705-7800

NATIONAL BOARD 1055 Crupper Avenue Columbus, OH 43229 PHONE: (614) 888-8320

ASME - C.S.D.1 345 East 47th Street New York, NY 10017 PHONE: (212) 705-7800

N.F.P.A. P.O. Box 9146 Quincy, MA 02169 PHONE: (800) 344-3555

NATIONAL UNDERWRITERS 505 Gest Street Cincinnati, OH 45203

UNDERWRITERS LABORATORIES 333 Pfingsten Road Northbrook, IL 60062 PHONE: (847) 272-8800

2

1.2.1 MIURA BOILER STEAM GENERATORS (Inspector briefing) The Miura steam generator is an unfamiliar design to most inspectors in the field. The purpose of this section is to address common questions and familiarize the inspector with the Miura steam generator through a general overview of the design and operational characteristics. The Miura boiler EX design consists of straight water tubes between upper and lower annular headers. Both headers are encased in a castable refractory, leaving only the tubes exposed to combustion gases. There is very little water and consequently very little energy stored in the steam generator. Water volume is exclusively in the tubes with only incidental bubbling in the upper header. Therefore, the design has no natural circulation such as a riser, down-comer effect common to natural circulation boilers. Water is forced into the bottom header and tubes by means of a feed water pump. The water is flashed into steam in the tubes, forming a dynamic bubbling system that cools the tubes. This bubbling action may be best described as a “steam gradient,” with more steam at the top of the tubes than at the bottom. Steam is accumulated in the upper header with a final separation in the external separator. Condensate dropped by the external separator is fed back into the lower header. Because of the steam gradient, there is no defined stream/water level and thus no sight glass. Special modifications are incorporated into the boiler construction and safety system to accommodate this. First, probes are inserted directly into the top of the tubes. One probe is long, for low water cut out; and one probe is shorter for feed water control. This water volume control relies on electrical resistance and the bubbling action is what cools the tubes. As the volume of water in the steam generator is consumed, there is less bubbling at the top of the tubes, increasing the amount of electrical resistance. Once the effective electrical resistance reaches a pre-determined level, a ten-second-time delay is tripped, after which the feed water pump is turned on. It continues to run until the bubbles re-establish effective contact with the probe. Should the water volume ever become so low as to lose effective contact with the low water cutout probe, the boiler will shut down. Secondly, probes are inserted into a water column on the side of the boiler. This water control system relies on a conventional electrical conductance system. When water contacts a probe, a circuit is formed. Three probes control the boiler feed; the short probe controls the pump in Low Fire, the medium-length probe controls the pump in High Fire. The long probe is the primary low water cut out. This safety can be confusing for the inspector who encounters the Miura steam generator in the field for the first time, because a water column typically equals a “fixed water level”. This is not true, however, for the Miura EX Series steam generator because of the low water content and the fierce boiling action of the steam gradient. This dynamic system is stabilized by a special modification of the water column to create an artificial level. The flanged pipe leading form the boiler body runs through the column with three holes drilled in the pipe to create an orifice effect. Yet, even with this orifice effect, the artificial “level” formed is not the level in the boiler; and oscillates - especially with load swings on the system. This oscillation is normal and is directly proportional to the volume of water in the boiler tubes. Either of these feed water control systems can operate without the other for proper feed water control. However, the combination of these two systems provides for double low water safety and is called the “two-way water volume control system.” Thirdly, thermocouples are attached directly to the tubes. The thermocouples measure the temperature of the tube and will shut the boiler down if a low water volume condition is detected due to insufficient bubbling, dry fire, or if scale build-up is detected. Scale formation is monitored directly by the rise in tube surface temperature because of lower heat transfer rates. This temperature sensing method can detect a formation of scale of less than 1/64” and will shut down the boiler. The early detection of scale formation is an important factor in maintaining a high efficiency boiler. According to the US National Bureau of Standards, ¼” of scale build upon heating units requires up to 55% more energy to attain the same temperature. Other methods of detecting scale, such as a pressure gage on the discharge of the feed water pump, are much less sensitive. The MIURA XJ1 Intelligent Steam Management microcomputer automatically adjusts the alarm settings for the scale monitor based on current boiler steam pressure and boiler firing rate. 3

The boiler will not operate should any low water safeties fail. Only through tampering could the boiler operate without safeties and develop a dry fire condition. Even in the unlikely event this condition should ever be created, before the tubes superheat enough to destroy the tensile strength of the metal, the amount of energy contained in the remaining water is so small that the possibility of a pressure explosion is negligible. The Miura Steam Generator design has been used for more than thirty-five years with over 200,000 units presently in operation worldwide. There is no record of ANY pressure vessel explosions. Steam is produced within five minutes from cold start-up and selected tubes can be visually inspected through two-inch openings located on the top and bottom headers. A complete inspection is typically accomplished in a thirty-minute period. All Miura EX steam generators are annotated as a forced flow steam generator (with no fixed steam or water level) on the pressure vessel’s P-3 form and registered with the National Board. The complete packaged steam generator is listed with UL as a standard and can be built to IRI, FM and /or ASME-CSD1 at customer request. Please note that all flanges and fittings identified in this manual as 150# ASA comply with ASME/ANSI standard B16.5. The 150# stamping refers to a standard classification not Maximum Allowable Working Pressure (MAWP). As specified in Table A-361 of ASME codes, Section I, 1995 edition, the MAWP for 150# flanges is 205 psig for saturated steam service and 170 psig for Boiler Feed and Blow-off line service. This specification matches the 170psi MAWP rating of the MIURA boiler. Miura is dedicated to reliable and safe operation of its steam generators through sound engineering principles and years of in-the-field experience. Please contact us at our Chicago office at (847) 465-0001 or the Los Angeles office at (626) 305-6622 should you have any further questions or comments.

4

1.3 STANDARD EQUIPMENT A fully Packaged Forced Draft Steam Boiler, the EX series receives complete operational testing at our factory to insure trouble free installation. (Service Parts are non-proprietary.) The EX has the following items as standard equipment: • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

Boiler Design is UL approved and labeled A.S.M.E. “S” stamped - A.S.M.E. CSD-1, IRI or FM Available Mounted Control Panel - wired with all necessary components (No Main Electrical Disconnect included) Microprocessor based integrated burner controller with UV flame sensor MIURA XJ1 micro-processor boiler control with fault history Computer interface capability for remote monitoring by factory service department (Requires optional equipment)(Monitoring contract required) Service parts are non-proprietary Centrifugal forced draft blower and motor Combustion air proving switch Automatic combustion air damper and motor Thermocouples on water tubes prevent overheat condition caused by low water volume or scale build up Thermocouples for feed water temperature, stack temperature and gas meter available as options Two independent water volume controls and low water cut-off safety devices, plus manual reset Liquid volume control column and bottom blow down valves Steam pressure sensor and control switches, plus an independent high-pressure safety requiring manual reset Gas regulator with threaded connections for main burner and pilot flame High and low gas pressure switches Dual pilot gas solenoid valves for natural gas Dual fluid actuated main gas valves and plugged leak test port (vent valve optional) Soot blower ports for fast convenient cleaning of soot External steam separator Ports for direct visual inspection of internals A.S.M.E. approved safety relief valves for boiler and optional economizer (if installed) Intermittent blow down system with strainer and manual shut off valve Boiler water test valve Operating hours display with start cycle aggregate and five-fault history display Heavy duty galvanized economizer (“S” series) (optional) Completely enclosed heavy gauge casing Steam (and oil on “O” series) pressure gauges installed Oil pump and motor (“O”, “GO,” or “SGO” series) Triplex, high-low-off, main oil valves (“O,” “GO,” or “SGO” series) Multi-stage feed water pump and motor with stainless steel impellers and ceramic bearings (optional)

5

1.4 GUARANTEE: • Refer to warranty documents for specific details. • SIX-MONTH labor warranty from boiler start up may be available, contact Local Sales and Service representa tives for details. This labor warranty covers routine inspection and repairs at the job site. Travel and lodging expenses are not covered except within local representative service area. • ONE YEAR Standard warranty for parts from boiler commissioning date or 18 months from shipping date, whichever occurs first. Express shipping cost for overnight or next day delivery of parts is not included. Damage to the boiler or parts of the boiler after leaving the factory is not covered. Parts replaced under this warranty must be returned to MIURA. If the failed part is not returned, the customer will be charged for the new item. • SEVEN-YEAR limited factory warranty on pressure vessel against material or workmanship defects.

1.5 DEFINITIONS AND SYMBOLS “Note,” “Caution,” and “Danger” are used throughout this manual with the following definitions and symbols.

NOTE: Note indicates an area or subject of special merit, emphasizing either the product capabilities or common errors in operation or maintenance.

CAUTION: Caution indicates possible damage to equipment. It also indicates any condition or practice, which, if not observed or remedied, could result in damage or destruction of the equipment.

DANGER: Danger indicates any condition or practice, which, if not observed, could result in personal injury or possible death. CAUTION: All steam engines require proper water treatment. This treatment is mandatory from the time the MIURA BOILER is started. Failure to follow the recommended water treatment and maintenance procedures could shorten the life (as well as the efficiency) of the boiler. None of the Miura warranties cover repair due to improper water treatment.

6

1.6 ABOUT THIS MANUAL This manual is written to support engineering and mechanical contractor firms. Some basic information is given for the operator and maintenance personnel. More specific information on operation and maintenance of the unit is given in the MIURA OPERATION AND MAINTENANCE MANUAL. If a question about boiler installation is not contained in the text of this manual and is not answered by one of the drawings, please call the MIURA representative or the company offices in Chicago or Los Angeles. We will be glad to help. This manual is available on disk for Microsoft Word 2000 and Word 95/97. In addtion, detailed drawings are available on disk in Auto CAD 14 files. If computer copies are desired, please contact the Chicago Office of MIURA Boiler. A small fee is required for shipping and handling.

1.7 OFFICES MIURA BOILER CO., LTD. (Factory) 8 Copernicus Boulevard Brantford, Ontario Canada N3P 1Y4 PHONE: (519) 758-8111 FAX: (519) 758-5294 e-mail: Canada@ miuraboiler.com MIURA BOILER WEST, INC. (Chicago Office) 600 Northgate Parkway, Suite M Wheeling, IL 60090-3201 PHONE: (847) 465-0001 FAX: (847) 465-0011 e-mail: [email protected]

MIURA BOILER WEST, INC. (LA Office) 1945 South Myrtle Avenue Monrovia, CA 91016-4854 PHONE: (626) 305-6622 FAX: (626) 305-6624 e-mail: [email protected]

7

2 SECTION TWO - SPECIFICATIONS Table 1 EX Series Specifications (without Economizer) ITEM

EX-200G(O)

EX-100G(O)

Utilization Horsepower Maximum Pressure Equivalent Output Fuel Gas Heat Input Steam Heat Output Efficiency (Fuel to Steam) Heating Surface Area Full Water Content Operational Water Content Operational Weight Shipping Weight Combustion Control Combustion System Ignition System Spark System Power Supply Max. Electrical Consumption Blower Motor Output Gas Consumption No. 2 Oil Gas Supply Pressure Air Changes (Pre-purge) Flue Gas Volume (Wet) Flue Gas Volume (Dry) Flue Gas Velocity Flue Gas Temperature Emissions, Oil Fired Emissions, Gas Fired Main Steam Outlet Valve Safety Valve Outlet Main Water Inlet Fuel Gas Inlet Fuel Oil Inlet Automatic Surface Blow Down Manual Blow Down Stack Diameter (ID) Flame Detector Pressure Control Liquid Volume Control Overheat Protection

EX-250G(O)

EX-300G(O)

200 HP 300 HP 250 HP 170 PSIG Design, 150 PSIG Maximum Operating 6,900 LB/HR 10,350 LB/HR 8,625 LB/HR

100 HP 3,450 LB/HR

4,185,000 BTU/HR Gas 8,369,000 BTU/HR Gas 10,461,000 BTU/HR Gas 12,563,000 BTU/HR Gas 4,083,000 BTU/HR Oil 8,165,000 BTU/HR Oil 10,206,000 BTU/HR Oil 12,256,000 BTU/HR Oil 3,348,000 BTU/HR

6,695,000 BTU/HR

8,369,000 BTU/HR

80% Gas Fired, 82% Oil Fired 407 FT² 323 FT² 265 GAL 170 GAL 80 GAL 75 GAL 15,000 LBS 9,700 LBS 13,800 LBS 9,000 LBS 3 Position Step Burner HIGH-LOW-OFF Proprietary Forced Draft Electric Spark Ignited, Interrupted Gas Pilot 15,000 V 230 or 460 V, 3 PHASE, 60 HZ 32 KVA (34 for Oil) 13 KVA (14 for Oil) 24 KVA (14 for Oil) 25 HP 10 HP 20 HP 10,420 SCFH 4,170 SCFH 8,340 SCFH 72.9 GAL/HR 29.2 GAL/HR 58.3 GAL/HR 3-5 PSIG (Natural Gas or Propane) 193 FT² 100 GAL 54 GAL 5,500 LBS 5,000 LBS

55,900 SCFH Gas 54,700 SCFH Oil 47,700 SCFH Gas 49,700 SCFH Oil 26.0 FT/Sec Gas 25.4 FT/Sec Oil 470°

2” One 2” 1” 2” 3/4” One 3/8” Two 1” 14”

>4 (>8*) 111,700 SCFH Gas 109,100 SCFH Oil 95,500 SCFH Gas 99,200 SCFH Oil 25.4 FT/Sec Gas 24.8 FT/Sec Oil 470°

139,600 SCFH Gas 136,500 SCFH Oil 119,300 SCFH Gas 124,000 SCFH Oil 31.8 FT/Sec Gas 31.1 FT/Sec Oil 470°

Smoke=8*) 105,200 SCFH Gas 103,000 SCFH Oil 89,900 SCFH Gas 93,600 SCFH Oil 18.8 FT/Sec Gas 18.4 FT/Sec Oil 270°F

131,400 SCFH Gas 128,600 SCFH Oil 112,300 SCFH Gas 116,900 SCFH Oil 23.5 FT/Sec Gas 23.0 FT/Sec Oil 270°F

10,050,000 BTU/HR

390 FT² 280 GAL 94 GAL 18,000 LBS 17,100 LBS

32 KVA (34 for Oil) 25 HP 11,780 SCFH 82.5 GAL/HR

157,800 SCFH Gas 154,500 SCFH Oil 134,800 SCFH Gas 140,300 SCFH Oil 16.7 FT/Sec Gas 16.3 FT/Sec Oil 270°F

Smoke=8*) 105,200 SCFH Gas 103,000 SCFH Oil 89,900 SCFH Gas 93,600 SCFH Oil 18.8 FT/Sec Gas 18.4 FT/Sec Oil 270°F

131,400 SCFH Gas 128,600 SCFH Oil 112,300 SCFH Gas 116,900 SCFH Oil 13.9 FT/Sec Gas 13.6 FT/Sec Oil 270°F

Smoke=8*) 55,900 SCFH Gas 54,700 SCFH Oil 47,700 SCFH Gas 49,700 SCFH Oil 27.5 FT/Sec Gas 26.9 FT/Sec Oil 470°F

52,500 SCFH Gas 51,500 SCFH Oil 44,900 SCFH Gas 46,800 SCFH Oil 20.2 FT/Sec Gas 19.9 FT/Sec Oil 270°F

Smoke=8*) 111,700 SCFH Gas 109,100 SCFH Oil 95,500 SCFH Gas 99,200 SCFH Oil 26.9 FT/Sec Gas 26.3 FT/Sec Oil 470°F

105,200 SCFH Gas 103,000 SCFH Oil 89,900 SCFH Gas 93,600 SCFH Oil 19.9 FT/Sec Gas 19.5 FT/Sec Oil 270°F

Smoke=8*) 169,700 SCFH Gas 165,900 SCFH Oil 145,000 SCFH Gas 150,700 SCFH Oil 23.6 FT/Sec Gas 23.1 FT/Sec Oil 500°F

159,700 SCFH Gas 156,300 SCFH Oil 136,400 SCFH Gas 142,000 SCFH Oil 17.6 FT/Sec Gas 17.2 FT/Sec Oil 300°F

Smoke=