Document not found! Please try again

Experiments on Capacitive Current Interruption with ... - TU Eindhoven

1 downloads 0 Views 298KB Size Report
Jun 22, 2009 - ignitions. In order to investigate this transient phenomenon, a ... ignition and recovery voltage are analyzed and results are discussed in detail.
Experiments on Capacitive Current Interruption with Air-break High Voltage Disconnectors Y. Chai1, P.A.A.F. Wouters1, R.T.W.J. van Hoppe1

R.P.P. Smeets1, 2, D.F.Peelo3

1, Department of Electrical Engineering, Eindhoven University of Technology, the Netherlands email: [email protected], [email protected], [email protected]

2, KEMA T&D Testing Services, Arnhem, the Netherlands 3, D.F. Peelo and Associates, British Columbia, Canada email: [email protected],[email protected]

Abstract—Capacitive current interruption with air-break disconnectors in a high-voltage network is an interactive event between circuit and arc with a variety of interruptions and reignitions. In order to investigate this transient phenomenon, a series of interruption tests was performed at KEMA High Power Laboratory. In this paper, a brief analysis of the interruption process is presented and is compared with experimental data from the test. Typical wave shapes of voltages across the capacitances, disconnector and current through the disconnector are given. Re-ignition voltage and energy input to the arc on reignition are also investigated. Comparison shows that the test data are in good agreement with simulation. It is concluded that besides higher interruption current and higher power supply level, a lower ratio between source side and load side capacitance leads to more severe interruption and longer arc duration. In the end, the actual status of IEC recommendations on testing, that has taken into account this arc-circuit interaction, will be discussed. Keywords-Arc, capacitive current, disconnector, disconnect switches, high voltage, interruption, measurements, re-ignition, substation, standards, testing.

I.

INTRODUCTION

In a power substation, disconnectors (in North America, disconnectors are called disconnect switches) are commonly used mechanical devices. The definition of a disconnector is: “A mechanical switching device which provides, in open position, an isolating distance in accordance with specific requirements” by International Electrotechnical Vocabulary (IEV) 441-14-05. That means disconnectors only have a safety function. However, in practice due to parasitic capacitances such as from unloaded bus bars, lines etc. in the networks, there is always a capacitive current that disconnectors need to interrupt. Moreover, although not designed for interrupting current, the disconnectors do have a certain current interrupting capability thanks to one or more moving contacts during switching operations. According to the IEC 62271-102 [1], this small capacitive current, which is called “negligible current”, does not exceed 0.5A for rated voltage 420kV and below. In the past, the current interrupting capability of the air-break disconnectors has therefore been taken as 0.5A or less. Nowadays, with the fast development of power networks in the world, user’s requirement for small capacitive current

interruption using air-break disconnectors frequently exceeds the above stated 0.5A. Literature related to capacitive current interruption using air-break disconnectors is quite sparse, for instance [2]-[15]. A good overview is provided in [12]. The principal work in the past is that of Andrews et al. in the 1940s. Some results from literature such as [3], [8] were collected for IEC and IEEE recommendations [11] as well. However, literature provides only a limited insight into the experiments on the capacitive current interruption by an air-break disconnector. In this contribution we will therefore present a more detailed approach to the electrical phenomena during arcing that, by the associated voltage transients, may endanger nearby network components such as instrument transformers. Specifically, a study on experimental data obtained from tests is presented in detail. In principle, the capacitive current interruption capability of a disconnector may be affected by various factors such as air humidity, wind speed, earthing type of the system and phase spacing. In this paper, however, only effects of electrical parameters, such as capacitances, inductances, etc. are evaluated. Based on measured data, factors affecting the arc characteristics, re-ignition voltages and other phenomena such as energy input into the arc on reignition and recovery voltage are analyzed and results are discussed in detail. The paper concludes with suggestions for standardization. II.

BRIEF INTERRUPTION PROCESS ANALYSIS

Capacitive current interruption with a disconnector consists of a succession of interactive events between circuit and arc with a repetitive sequence of interruptions and re-ignitions. The re-ignition is characterized in terms of oscillation frequency, transients of current and voltage, etc. An arc is characterized in terms of arc duration, arc reach (perpendicular distance of outermost arc position to a line connecting the contacts), arc type (repetitive or continuous), and energy input from circuit during the re-ignition, and so forth. The basic equivalent circuit for capacitive current interruption is shown in Fig.1. The disconnector is marked with D; The short-circuit inductance Ls is based on the short-time current for which the disconnector is rated; Rs, Cs and Cl stand for resistance, capacitance at supply side and load side

978-1-4244-2487-0/09/$25.00 ©2009 IEEE Authorized licensed use limited to: Eindhoven University of Technology. Downloaded on June 22, 2009 at 09:45 from IEEE Xplore. Restrictions apply.

respectively; id is current through the disconnector to be interrupted; us is the voltage of the power supply of the network.

Cs and Cl were selected. The value of Ls was fixed at 480mH. The test was performed on a 300kV center-break disconnector. During the tests, general arc behaviour such as arc duration, gap length, blade angle at arc extinction, and overvoltage across Cl were recorded. Instantaneous current id and voltages ucs and ucl were also recorded during the current interruption process. Further, high-speed video recording of the arc was made. Initial analysis of the test data was done in [12], [13] and revealed: −

Arc duration increases with interruption current magnitude (at constant Cs);



Arc duration increases with decreasing value of Cs /Cl and the minimum blade angle of the disconnector required for the arc extinction is about 50 degrees. The disconnector can be close to fully open for the smallest values of Cs /Cl before current was finally interrupted;



Overvoltage across load side capacitor reached maximum values when Cs /Cl