GE Security Aritech Fire Systems Products Catalogue

338 downloads 1677 Views 7MB Size Report
GE. Security. Aritech Fire Systems Products Catalogue g ... Aritech FP400, FP500 , FP600 and FP700 series conventional fire panels, ..... Heat detector, 90º C CS.
GE Security

Aritech Fire Systems Products Catalogue

g

In this catalogue you will find a wide range of Fire Protection equipment from GE Security. GE Security is a global technology leader dedicated to supporting the needs of the rapidly growing electronic security industry and to expanding current technologies, products and services that

GE Security, unrivalled expertise in Fire Protection

create revenue growth opportunities for its customers. As part of the GE family, GE Security shares the spirit of innovation that has distinguished GE for well over 100 years. GE Security's commitment to the ongoing success of its partners and affiliates means that we maintain a sharp focus on product and service innovation, world-class manufacturing practices and operational excellence. GE Security is a worldwide organisation with sales and technical support operations in 27 countries, and manufacturing and logistics operations in Europe, the U.S. and China. GE Security has expertise in all areas of electronic security, including: z

Intrusion and Fire Protection

z

Electronic Access and Facility Management

z

Key Management and Remote Access Systems and Services

z

Fibre Optic Transmission and Reception Equipment

z

CCTV, Digital Video and Surveillance Equipment

z

Video Multiplexing and Digital Storage

When you're looking for the finest in Fire Protection products with leading-edge technology and the backing of a world leader, you need look no further than this catalogue.

Perimeter detection Page : 3

DI322I

Ionisation detector, conventional

The 300 Series conventional fire detectors are the ideal solution for any conventional installation. They are built specifically for use with the Aritech FP400, FP500, FP600 and FP700 series conventional fire panels, but can also be connected to most 3rd party industry standard conventional control panels. Specifications

Operating voltage

18 to 28 VDC

Current consumption Quiescent at 24 VDC

30 A

Alarm at 24 VDC

< 100 mA

Radio-active source

Americium 241

Average activity

0.33 +/-0.04 Ci (12.1 +/- 1.5 kBq)

Remote alarm output

< 100 mA

Heat specification Operating temperature

-10 to +60 °C

Storage temperature

-10 to +70 °C

Humidity (non-condensing)

0 - 95%

IP rating

IP43

Number of detectors per zone

20

Recommended protection resistor

300 ohm

Head

45 mm x 99 mm

Base

24 mm x 103 mm EN54 (BOSEC)

* Check current status with local office

Ordering Information DI322I

detectors

E An ultra-fine grid prevents the ingress of dust and

Dimensions (h x Ø)

Approvals*

E Full line consisting of Optical, Ionisation and Heat

Ionisation detector, conventional

KZ700 Universal fire detector base KZ705 Universal fire detector base with earth connection KZ705D Conventional fire detector base with diode PA25/3L Low current remote LED indicator

insects in smoke detectors

E Attractive, low-profile design E EN54 approved * E Innovative base compensates for uneven surfaces

Page : 4

Optical detector, conventional, with field exchangeable optical block

DP331I

The 300 Series conventional fire detectors are the ideal solution for any conventional installation. They are built specifically for use with the Aritech FP400, FP500, FP600 and FP700 series conventional fire panels, but can also be connected to most 3rd party industry standard conventional control panels. Specifications

Operating voltage

9 to 28 VDC

Current consumption Quiescent at 24 VDC

85 A

Alarm at 24 VDC

< 100 mA

Radio-active source Average activity Remote alarm output

< 100 mA

Heat specification Operating temperature

-10 °C to +70 °C

Storage temperature

-10 °C to +70 °C

Humidity (non-condensing)

95%

IP rating

IP43

Number of detectors per zone

20

Recommended protection resistor

300 ohm

Head

45 mm x 99 mm

Base

24 mm x 103 mm EN54 (BOSEC)

* Check current status with local office

Ordering Information DP331I

Optical detector, conventional, with field exchangeable optical block

KOB700 Replacement Optical Chamber for KL731/A & DP331I/1561 detectors KZ700 KZ705 KZ705D KZ705R

detectors

E An ultra-fine grid prevents the ingress of dust and

Dimensions (h x Ø)

Approvals*

E Full line consisting of Optical, Ionisation and Heat

Universal fire detector base Universal fire detector base with earth connection Conventional fire detector base with diode Conventional 12 VDC fire detector base with relay

PA25/3L Low current remote LED indicator

insects in smoke detectors

E Attractive, low-profile design E EN54 approved * E Innovative base compensates for uneven surfaces

Conventional Fire Systems Page : 5

DT313I

Temperature detector (fixed and rate-of-rise), conventional

The 300 Series conventional fire detectors are the ideal solution for any conventional installation. They are built specifically for use with the Aritech FP400, FP500, FP600 and FP700 series conventional fire panels, but can also be connected to most 3rd party industry standard conventional control panels. Specifications

Operating voltage

18 to 28 VDC

Current consumption Quiescent at 24 VDC

70 A

Alarm at 24 VDC

< 100 mA

Radio-active source Average activity Remote alarm output

< 100 mA

Heat specification

Max. & ROR to EN54p5

Operating temperature

-10 °C to +70 °C

Storage temperature

-10 °C to +80 °C

Humidity (non-condensing)

95%

IP rating

IP43

Number of detectors per zone

20

Recommended protection resistor

300 ohm

Head

45 mm x 99 mm

Base

24 mm x 103 mm EN54 (BOSEC)

* Check current status with local office

Ordering Information DT313I

detectors

E An ultra-fine grid prevents the ingress of dust and

Dimensions (h x Ø)

Approvals*

E Full line consisting of Optical, Ionisation and Heat

Temperature detector (fixed and rate-of-rise), conventional

KZ700 Universal fire detector base KZ705 Universal fire detector base with earth connection KZ705D Conventional fire detector base with diode PA25/3L Low current remote LED indicator

insects in smoke detectors

E Attractive, low-profile design E EN54 approved * E Innovative base compensates for uneven surfaces

Conventional Fire Systems Page : 6

KCT731

Calibration Tool for KL731/DP331I Fire Detectors

The KCT731 is a calibration tool to recalibrate the conventional detectors after replacement of the field exchangeable optical block. Specifications

Supply

2 x 9 V batteries

Dimensions (w x h x d)

104 x 195 x 63 mm

Ordering Information KCT731 Calibration Tool for KL731/DP331I Fire Detectors

E Easy to use E Simple "go/no-go" function E Battery operated

Detector Bases & Accessories Page : 7

KZ700

Universal fire detector base

The KZ700 is a 4 contact universal detector base. It has the ability to compensate for uneven mounting surfaces. It is also available in black for special applications in false ceilings. Specifications

Dimensions Diameter

104 mm

Height

24 mm

Ordering Information KZ700 Universal fire detector base KZ700B Universal fire detector base (for KL700/A and Dx300/1500) - Black

E Polarity sensitive E Universal base fits conventional and analogue detectors

E E E E

Compensates for uneven surfaces Remote indicator contact available EN54 approved Variant in black also available

Detector Bases & Accessories Page : 8

KZ705

Universal fire detector base with earth connection

The KZ705 is a 5 contact universal detector base for use with the KL700/Dx300 and KL700A/Dx1500 series detectors from GE-Interlogix. In addition to the normal base and remote indication connectors, the KZ705 also has an additional earth terminal connector to allow for easy terminations of a possible cable screen. Specifications

Dimensions (Ø x h)

100 x 29 mm

Operating Voltage

-

Current Consumption

-

Isolation Current

-

Isolation Resistance

-

Sounder Frequency

-

Sound Output @ 3 mA

-

@ 5 mA

-

Environmental Characteristics Operating Temperature

-10 to 70 °C

Storage Temperature

-10 to 70 °C

Relative Humidity (max)

95 % (non-cond.)

Ordering Information KZ705 Universal fire detector base with earth connection

E Polarity sensitive E Universal base fits conventional and analogue detectors

E Additional earth terminal available E Remote indicator contact available

Conventional Fire Systems Page : 9

KZ705D

Conventional fire detector base with diode

The KZ705D is a 5 contact universal detector base for use with the KL700/Dx300 series detectors from GE-Interlogix. In addition to the normal base and remote indication connectors, the KZ705D also has an additional earth terminal connector to allow for easy terminations of a possible cable screen. The built in diode is specifically targeted at systems using active end-of-line devices. Specifications

Dimensions (Ø x h)

100 x 29 mm

Operating Voltage

-

Current Consumption

-

Isolation Current

-

Isolation Resistance

-

Sounder Frequency

-

Sound Output @ 3 mA

-

@ 5 mA

-

Environmental Characteristics Operating Temperature

-10 to 70 °C

Storage Temperature

-10 to 70 °C

Relative Humidity (max)

95 % (non-cond.)

Ordering Information KZ705D Conventional fire detector base with diode

E E E E E

Polarity sensitive Universal base for conventional detectors Additional earth terminal available Remote indicator contact available Built in diode for active end-of-line systems

EOL-ACT

Active end-of-line device for use with FP400/KL700 fire panels

The EOL-ACT is designed for use with the NK700/FP400 fire panels from GE-Interlogix. It is an active end-of-line device to allow the monitoring of a conventional zone through a diode base (such as the KZ705D).

Ordering Information EOL-ACT Active end-of-line device for use with FP400/KL700 fire panels

E Small E Easy to install

Conventional Fire Systems Page : 10

KZ705R

Conventional 12 VDC fire detector base with relay

The KZ705R is a 5 contact detector base for use with the KL731/DP331I detectors from GE-Interlogix. In addition to the normal base and remote indication connectors, the KZ705R also has an additional earth terminal connector to allow for easy terminations of a possible cable screen. A built in 12 V relay makes it ideal for use on low voltage intrusion systems. Specifications

Dimensions (Ø x h)

100 x 29 mm

Operating Voltage

12 V ± 10%

Current Consumption

12 A

Isolation Current

-

Isolation Resistance

-

Sounder Frequency

-

Sound Output @ 3 mA

-

@ 5 mA

-

Environmental Characteristics Operating Temperature

-10 °C to +70 °C

Storage Temperature

-10 °C to +70 °C

Relative Humdity

95 % (non cond.)

Ordering Information KZ705R Conventional 12 VDC fire detector base with relay

E E E E

Polarity sensitive 12 V relay for 4 wire systems Additional earth terminal available Remote indicator contact available

Detector Bases & Accessories Page : 11

S700

Surface mount accessory for KZ700 and KZ705 series bases

The S700 is a base accessory designed for use with the KZ700 series detector bases. It allows for a surface mount conduit and cable to enter the base from the side. The KZ700 series base fits on top of this accessory. Specifications

Dimensions Diameter

95 mm

Height

30 mm

Ordering Information S700 Surface mount accessory for KZ700 and KZ705 series bases

E Surface mount accessory for KZ700 series bases

Conventional Fire Systems Page : 12

DP721I

Photoelectric smoke detector with remote alarm LED output

700 series The smoke detector continually monitors its own sensitivity and operational status. Once a day, it performs a full diagnostic test which includes dynamically testing the sensing chamber and internal electronics. Specifications

Operating voltage

8.5 - 33 V dc

Current consumption Quiescent at 24 V dc

100 A; Max. 70 A average

In alarm at 24 V dc

60 mA

Alarm indication

White LED (red alarm)

Fault indication

Yellow LED

Remote alarm output

30 mA

RY contact rating Relay models

2 A @ 30 V dc;1 A @ 120 V ac

Humidity

0 - 95%; Non-condensing

IP rating

IP 43

Operating temperature

-10°C - 60°C

Sensitivity

10%/m (+1.6%, -3.3%)

Reset voltage

2,5 V max

Reset time

1 sec

Dimensions

10 cm Ø, H = 5 cm

E Automatic Self Diagnostics : Dynamic full detector test, Sensitivity test

E Manual Self Diagnostic routine with visual sensitivity indication

Ordering Information DP721I Photoelectric smoke detector with remote alarm LED output DP721R Photoelectric smoke detector with C/O relay output DB702 10 cm diameter base - 6 terminals

E E E E E E E

Field sensitivity testing without external meters Field exchangeable and disposable optical chamber High false alarm immunity Floating background with drift compensation Separate fire and trouble LED 12 - 24 V dc operation Polarity insensitive

E Full range : optical, heat and optical/heat multi criteria sensor

E EN 54 approved

Conventional Fire Systems Page : 13

Photoelectric smoke and heat detector head with remote alarm LED

DP721T

700 series Fitted with a field-exchangeable optical block. The smoke detector continually monitors its own sensitivity and operational status. Once a day, it performs a full diagnostic test which includes dynamically testing the sensing chamber and internal electronics. Specifications

Operating voltage

8.5 - 33 V dc FWR

Current consumption Quiescent at 24 V dc

100 A; Max. 70 A average

In alarm at 24 V dc

60 mA

Alarm indication

White LED (red alarm)

Fault indication

Yellow LED

Remote alarm output

30 mA

RY contact rating

2 A @ 30 V dc;1 A @ 120 V ac

Humidity

0 - 95%; Non-condensing

IP rating

IP 43

Sensitivity

10%/m (+1.6%, -3.3%)

Reset voltage

2,5 V max

Reset time

1 sec

Dimensions

10 cm Ø, H = 5 cm

E Automatic Self Diagnostics : Dynamic full detector test, Sensitivity test

Ordering Information

E Manual Self Diagnostic routine with visual sensitivity DP721T DP721RT DP721RTA DB702

Photoelectric smoke and heat detector head with remote alarm LED Photoelectric smoke and heat detector with relay output Photoelectric smoke and heat detector with relay output, autoreset 10 cm diameter base - 6 terminals

indication

E E E E E E E

Field sensitivity testing without external meters Field exchangeable and disposable optical chamber High false alarm immunity Floating background with drift compensation Separate fire and trouble LED 12 - 24 V dc operation Polarity insensitive

E Full range : optical, heat and optical/heat multi criteria sensor

E EN 54 approved

Conventional Fire Systems Page : 14

DT713-5

57º C fixed and rate-of-rise heat detector

700 series The smoke detector continually monitors its own sensitivity and operational status. Once a day, it performs a full diagnostic test which includes dynamically testing the sensing chamber and internal electronics. Specifications

Operating voltage

8.5 - 33 V dc FWR

Current consumption Quiescent at 24 V dc

100 A; Max. 70 A average

In alarm at 24 V dc

60 mA

Alarm indication

Red LED

Fault indication

Yellow LED

Remote alarm output

30 mA

RY contact rating

2 A @ 30 V dc;1 A @ 120 V ac

Humidity

0 - 95%; Non-condensing

IP rating

IP 43

Heat specification Max.

57º C ± 1.5º C

R.O.R.

8º C/min and > 40° C

Sensitivity Reset voltage

2,5 V max

Reset time

1 sec

Dimensions

10 cm Ø, H = 5 cm

Ordering Information DT713-5 57º C fixed and rate-of-rise heat detector DT713-5R 57º C and R.O.R. heat detector, with relay output DB702 10 cm diameter base - 6 terminals

E Automatic Self Diagnostics : Dynamic full detector test, Sensitivity test

E Manual Self Diagnostic routine with visual sensitivity indication

E E E E E E E

Field sensitivity testing without external meters Field exchangeable and disposable optical chamber High false alarm immunity Floating background with drift compensation Separate fire and trouble LED 12 - 24 V dc operation Polarity insensitive

E Full range : optical, heat and optical/heat multi criteria sensor

E EN 54 approved

Conventional Fire Systems Page : 15

DT713-7

70º C fixed and R.O.R. heat detector

700 series The smoke detector continually monitors its own sensitivity and operational status. Once a day, it performs a full diagnostic test which includes dynamically testing the sensing chamber and internal electronics. Specifications

Operating voltage

8.5 - 33 V dc FWR

Current consumption Quiescent at 24 V dc

100 A; Max. 70 A average

In alarm at 24 V dc

60 mA

Alarm indication

Red LED

Fault indication

Yellow LED

Remote alarm output

30 mA

RY contact rating

2 A @ 30 V dc;1 A @ 120 V ac

Humidity

0 - 95%; Non-condensing

IP rating

IP 43

Heat specification Max.

70º C ± 1.5º C

R.O.R.

8º C/min and > 40° C

Reset voltage

2,5 V max

Reset time

1 sec

Dimensions

10 cm Ø, H = 5 cm

E Automatic Self Diagnostics : Dynamic full detector test, Sensitivity test

E Manual Self Diagnostic routine with visual sensitivity indication

Ordering Information DT713-7 70º C fixed and R.O.R. heat detector DB702 10 cm diameter base - 6 terminals

E E E E E E E

Field sensitivity testing without external meters Field exchangeable and disposable optical chamber High false alarm immunity Floating background with drift compensation Separate fire and trouble LED 12 - 24 V dc operation Polarity insensitive

E Full range : optical, heat and optical/heat multi criteria sensor

E EN 54 approved

Conventional Fire Systems Page : 16

DB702

10 cm diameter base - 6 terminals

700 series Detector base for 700 series detectors

Ordering Information DB702 10 cm diameter base - 6 terminals DB702U 15 cm diameter base - 6 terminals

E Automatic Self Diagnostics : Dynamic full detector test, Sensitivity test

E Manual Self Diagnostic routine with visual sensitivity indication

E E E E E E E

Field sensitivity testing without external meters Field exchangeable and disposable optical chamber High false alarm immunity Floating background with drift compensation Separate fire and trouble LED 12 - 24 V dc operation Polarity insensitive

E Full range : optical, heat and optical/heat multi criteria sensor

E EN 54 approved

Conventional Fire Systems Page : 17

DI650

Ionisation smoke detector

650 series This elegant slim-line ionisation detector offers high performance and wide operating voltage Specifications

Size of detector (mm) Height

42

Diameter

100

Size of detector + base (mm) Height

50

Diameter

100

Supply voltage

9 - 33 V dc

Quiescent Current at 24 V (typical)

28 A

Alarm indication

LED

Normal operating temp. range (no icing)

-20 to + 60°C

Humidity (no condensation)

0-95% RH

Max. wind

10m/s

Remote alarm output current

17 mA

IP Rating

43

Ordering Information DI650 Ionisation smoke detector DI651 Integrating ionisation smoke dectector DB860 Standard Base

E E E E E E E E E

Wide operating voltage Advanced electronic technology Flashing LED option Polarity insensitive Common base Elegant slim-line design EN54 approved Magnetic test switch option Proven detection performance

Conventional Fire Systems Page : 18

DP652

Optical smoke detector

650 series This elegant slim-line optical sensor provides high performance and wide operating range. Specifications

Size of detector (mm) Height

42

Diameter

100

Size of detector + base (mm) Height

50

Diameter

100

Supply voltage

9 - 33 V dc

Quiescent Current at 24 V (typical)

40 A

Alarm indication

LED

Normal operating temp. range (no icing)

-20 to + 60°C

Humidity (no condensation)

0-95% RH

Max. wind

Not affected

Remote alarm output current

17 mA

IP Rating

43

Ordering Information DP652 Optical smoke detector DB860 Standard Base

E E E E E

Polarity insensitive Common base Elegant slim-line design EN 54 approved Wide operating voltage

Conventional Fire Systems Page : 19

DT654

Heat detector, R.O.R., 57º C A1R

650 series This elegant slim-line heat sensor has a wide operating temperature and is available in four ranges Specifications

Size of detector (mm) Height

42

Diameter

100

Size of detector + base (mm) Height

50

Diameter

100

Supply voltage

9 - 33 V dc

Quiescent Current at 24 V (typical)

45 A

Alarm indication

LED

Normal operating temp. range (no icing)

-20 to + 60°C

Humidity (no condensation)

0-95% RH

Max. wind

Not affected

Remote alarm output current

17 mA

IP Rating

54

Ordering Information DT654 DT655 DT656 DT657 DB860

Heat detector, R.O.R., 57º C A1R Heat detector, 75º C BR Heat detector, 95º C CR Heat detector, 90º C CS Standard Base

E E E E E E E E E

Wide operating voltage Advanced electronic technology Flashing LED option Polarity insensitive Common base Elegant slim-line design EN54 approved Magnetic test switch option Proven detection performance

Conventional Fire Systems Page : 20

DB860

Standard Base

650 series The base has been designed to enable detectors to be plugged in without any need for force - particularly useful when fitting to suspended ceilings.

Ordering Information DB860 Standard Base DB860U Standard base 15 cm diameter

E E E E E Backplate for Ingress Protection 860-950

860 series Conventional fire detectors Polarity insensitive Common base Elegant slim-line design EN 54 approved

DB861

Ordering Information DB861 Backplate for Ingress Protection 860-950

E Can prevent most ingress into the base and detector

Conventional Fire Systems Page : 21

DB806

Conduit box for 860 / 950 series bases

An inexpensive and versatile accessory for surface mounting 860 and 950 series bases

Ordering Information DB806 Conduit box for 860 / 950 series bases

DB650

650 series relay base

650 series The relay base provides a volt-free contact for use in 4 wire control systems, and other applications

Ordering Information DB650 650 series relay base

E E E E

DB650 For use with 4 wire control systems Automatic door closers Volt-free relay contacts

Addressable Fire Systems Page : 22

DI1552

Ionisation Sensor

The 1500 Series uses a microprocessor for measurement and communication. An enhanced protocol ensures the overall integrity and error free operation of the system, without compromising detection speed. All sensors are compatible with a standard base that makes them easily interchangeable and support the connection of a remote indicator. Specifications

Operating voltage

22 to 38 VDC

Current consumption Quiescent @ 38 VDC

200 A

In Alarm

< 11 mA

Alarm indication (Dual LED)

White OFF - Red ON

Remote Alarm Output

Available

Environment Storage Temperature

-10 to +70 °C

Operating Temperature

-10 to +60 °C

Humidity (non-condensing)

0-95%

IP rating

IP42

Radioactive Source

0.33 ± 0.04 Ci Am 241

Dimensions (h x Ø)

45 x 99 mm

Ordering Information DI1552

Ionisation Sensor

KZ700 KZ705 KZ705AS KZ705I KZ705IAS

Universal fire detector base Universal fire detector base with earth connection Analogue fire detector base with sounder Analogue fire detector base with isolator Analogue fire detector base with isolator and sounder

PA25/3L

Low current remote LED indicator

E E E E E E

Remote signalling capabilities Optical sensor with field exchangeable optical chamber Easy soft addressing (1-125) SMD technology Reliable communication protocol Full diagnostic self testing

E Full range: Ionisation, Optical and Heat and Dual sensors (optical/heat)

E Full range of supporting I/O units and accessories E EN54 Approved

Addressable Fire Systems Page : 23

DP1561

Optical sensor with field exchangeable optical block

The 1500 series detectors use a microprocessor for measurement and communication. An enhanced protocol ensures the overall integrity and error free operation of the system, without compromising detection speed. All sensors are compatible with a standard base that makes them easily interchangeable and support the connection of the PA25/3L remote indicator. Specifications

Operating voltage

22 to 38 VDC

Current consumption Quiescent @ 38 VDC

350 A

In Alarm

< 11 mA

Alarm indication (Dual LED)

Red

Remote Alarm Output

Available

Environment Storage Temperature

-10 to +70 °C

Operating Temperature

-10 to +60 °C

Humidity (non-condensing)

0-95%

IP rating

IP42

Remote signalling capabilities

DP1561

Optical sensor with field exchangeable optical block

E E E E E E

KOB700

Replacement Optical Chamber for KL731/A & DP331I/1561 detectors

E Full range: Ionisation, Optical and Heat and Dual

KZ700 KZ705 KZ705AS KZ705I KZ705IAS

Universal fire detector base Universal fire detector base with earth connection Analogue fire detector base with sounder Analogue fire detector base with isolator Analogue fire detector base with isolator and sounder

E Full range of supporting I/O units and accessories E EN54 Approved

PA25/3L

Low current remote LED indicator

Radioactive Source

NA

Dimensions (h x Ø)

45 x 99 mm

Ordering Information

Optical sensor with field exchangeable optical chamber Easy soft addressing (1-125) SMD technology Reliable communication protocol Full diagnostic self testing sensors (optical/heat)

Addressable Fire Systems Page : 24

DP1551T

Dual Sensor (Optical/Heat)

The 1500 Series uses a microprocessor for measurement and communication. An enhanced protocol ensures the overall integrity and error free operation of the system, without compromising detection speed. All sensors are compatible with a standard base that makes them easily interchangeable and support the connection of aremote indicator. Specifications

Operating voltage

22 to 38 VDC

Current consumption Quiescent @ 38 VDC

350 A

In Alarm

< 5 mA

Alarm indication (Dual LED)

Red

Remote Alarm Output

Available

Environment Storage Temperature

-10 to +70 °C

Operating Temperature

-10 to +70 °C

Humidity (non-condensing)

0-95%

IP rating

IP42

Radioactive Source

NA

Dimensions (h x Ø)

51 x 99 mm

Ordering Information DP1551T Dual Sensor (Optical/Heat) KZ700 KZ705 KZ705AS KZ705I KZ705IAS

Universal fire detector base Universal fire detector base with earth connection Analogue fire detector base with sounder Analogue fire detector base with isolator Analogue fire detector base with isolator and sounder

PA25/3L

Low current remote LED indicator

E E E E E E

Remote signalling capabilities Optical sensor with field exchangeable optical chamber Easy soft addressing (1-125) SMD technology Reliable communication protocol Full diagnostic self testing

E Full range: Ionisation, Optical and Heat and Dual sensors (optical/heat)

E Full range of supporting I/O units and accessories E EN54 Approved

Addressable Fire Systems Page : 25

DT1553

Heat Sensor

The 1500 Series uses a microprocessor for measurement and communication. An enhanced protocol ensures the overall integrity and error free operation of the system, without compromising detection speed. All sensors are compatible with a standard base that makes them easily interchangeable and support the connection of aremote indicator. Specifications

Operating voltage

22 to 38 VDC

Current consumption Quiescent @ 38 VDC

250 A

In Alarm

< 11 mA

Alarm indication (Dual LED)

White OFF - Red ON

Remote Alarm Output

Available

Environment Storage Temperature

-10 to +80 °C

Operating Temperature

-10 to +70 °C

Humidity (non-condensing)

0-95%

IP rating

IP42

Radioactive Source

NA

Dimensions (h x Ø)

45 x 99 mm

Ordering Information DT1553

Heat Sensor

KZ700 KZ705 KZ705AS KZ705I KZ705IAS

Universal fire detector base Universal fire detector base with earth connection Analogue fire detector base with sounder Analogue fire detector base with isolator Analogue fire detector base with isolator and sounder

PA25/3L

Low current remote LED indicator

E E E E E E

Remote signalling capabilities Optical sensor with field exchangeable optical chamber Easy soft addressing (1-125) SMD technology Reliable communication protocol Full diagnostic self testing

E Full range: Ionisation, Optical and Heat and Dual sensors (optical/heat)

E Full range of supporting I/O units and accessories E EN54 Approved

Addressable Fire Systems Page : 26

PG700

Fire sensor programmer

The PG700 is a handheld device programmer and tester for the KL700A/Dx1500 series detectors. It is battery operated and allows the installer to perform installation tasks (such as device addressing) and maintenance tasks (such as device calibration) in the field without external assistance. Specifications

Supply

2 x 9 V batteries

Dimensions (w x h x d)

104 x 195 x 63 mm

Ordering Information PG700 Fire sensor programmer

E Easy to use E Battery operated E 4 User selectable programs

-Device analogue value -Change Device Address -Sequential device addressing -KL731A Calibration

Addressable Fire Systems Page : 27

KZ705I

Analogue fire detector base with isolator

The KZ705I is a detector base with built in isolator for use with the KL700A/Dx1500 series detectors from GE-Interlogix. The isolator protects the loop from short circuit conditions. A LED on the side of the base indicates the status of the isolator. Specifications

Dimensions (Ø x h)

100 x 29 mm

Operating Voltage

17 - 34 V

Current Consumption

50 A

Isolation Current

6 mA

Isolation Resistance

140 Mohm

Sounder Frequency

-

Sound Output @ 3 mA

-

@ 5 mA

-

Environmental Characteristics Operating Temperature

-10 °C to +70 °C

Storage Temperature

-10 °C to +70 °C

Relative Humidity (max)

95 % (non cond.)

Ordering Information KZ705I Analogue fire detector base with isolator

E E E E E

Polarity sensitive Universal base for analogue detectors Additional earth terminal available Remote indicator contact available Built in isolator

Addressable Fire Systems Page : 28

KZ705AS

Analogue fire detector base with sounder

The KZ705AS is a detector base with built in analogue addressable sounder for use with the KL700A/Dx1500 series detectors from GE-Interlogix. The sounder has its own address on the fire panel loop and works independent of the detector. It is fully controlled from the fire panel. Specifications

Dimensions (Ø x h)

120 x 58 mm

Operating Voltage

22 - 38 V

Current Consumption

300 A Quiescent

Isolation Current

-

Isolation Resistance

-

Sounder Frequency

1 kHz (Continuous)

Sound Output @ 3 mA

85 dBA

@ 5 mA

90 dBA

Environmental Characteristics Operating Temperature

-10 °C to +70 °C

Storage Temperature

-10 °C to +70 °C

Relative Humidity (max)

95 % (non cond.)

IP Rating

IP21c

Ordering Information KZ705AS Analogue fire detector base with sounder

E E E E E E E

Polarity sensitive Universal base for analogue detectors Additional earth terminal available Remote indicator contact available Built in sounder Up to 90 dBA sound output Low current consumption

Addressable Fire Systems Page : 29

KZ705IAS

Analogue fire detector base with isolator and sounder

The KZ705IAS is a detector base with built in analogue addressable sounder and isolator for use with the KL700A/Dx1500 series detectors from GE-Interlogix. The sounder has its own address on the fire panel loop and works independent of the detector. It is fully controlled from the fire panel. The isolator protects the loop from short circuit conditions. Specifications

Dimensions (Ø x h)

120 x 58 mm

Operating Voltage

22 - 38 V

Current Consumption

350 A Quiescent

Isolation Current

6 mA

Isolation Resistance

140 Mohm

Sounder Frequency

1 kHz (Continuous)

Sound Output @ 3 mA

85 dBA

@ 5 mA

90 dBA

Environmental Characteristics Operating Temperature

-10 °C to +70 °C

Storage Temperature

-10 °C to +70 °C

Relative Humidity (max)

95 % (non cond.)

IP Rating

IP21c

Ordering Information KZ705IAS Analogue fire detector base with isolator and sounder

E E E E E E E E

Polarity sensitive Universal base for analogue detectors Additional earth terminal available Remote indicator contact available Built in sounder Up to 90 dBA sound output Low current consumption Built in isolator

Addressable Fire Systems Page : 30

KAL410

Conventional Zone Monitor Unit - 1 Zone

Allows the connection of one conventional zone to the analogue fire system loop. This zone is constantly monitored. Up to 20 conventional devices may be connected to this zone. Specifications

Supply voltage

22-38 VDC

Current consumption Quiescent @ 24 V

90 A

Quiescent @ 35 V

105 A

Alarm

< 3 mA

Aux. supply (24 VDC) quiescent

200 A + equip

Aux. supply (24 VDC) alarm

< 85 mA

End-of-line resistor

4.7 kohm

Relay contact rating

NA

Environmental Storage temperature

-10 °C to +50°C

Operating temperature

-10 °C to +70°C

Relative humidity

95 % (non condensing)

Dimensions (L x W x H)

117 x 80 x 44 mm

Ordering Information KAL410 Conventional Zone Monitor Unit - 1 Zone

E E E E E E

Easy numeric addressing Continuous supervision of the conventional zones Surface mount Local alarm indication Externally or loop powered Aesthetically pleasing

E Part of family of I/O modules consisting of:

-Conventional Zone Monitors -Digital Input Modules -Extinguishing Control Modules -Isolator Modules -Manual Call Points -Output Units -Retention Units -Supervised Output Units for sounder control

Addressable Fire Systems Page : 31

KAL414C

Conventional Zone Monitor Unit - 4 Zones

Allows the connection of four conventional zones to the analogue fire system loop. These zones are constantly monitored. Up to 20 conventional devices may be connected to any zone. Specifications

Supply voltage

22-38 VDC

Current consumption Quiescent @ 24 V

110 A

Quiescent @ 35 V

135 A

Alarm

< 5 mA

Aux. Supply (24V DC) Quiescent

200 A + equip

Aux. Supply (24V DC) Alarm

< 360 mA

End-of-line resistor

4.7 kOhm

Relay contact rating

NA

Environmental Storage temperature

-10 to +50°C

Operating temperature

-10 to +70°C

Relative humidity (non-condensing)

0-95 %

Dimensions (l x w x h)

163 x 107 x 36 mm

Ordering Information KAL414C Conventional Zone Monitor Unit - 4 Zones

E E E E E E E E E E E E E E E

Easy numeric addressing Continuous supervision of the conventional zones Surface mount Local alarm indication Externally powered Aesthetically pleasing Part of a family of I/O modules consisting of: - Conventional Zone Monitors - Digital Input Modules - Extinguishing Control Modules - Isolator Modules - Manual Call Points - Output Units - Retention Units - Supervised Output Units for sounder control

Addressable Fire Systems Page : 32

KAL426C

Extinguishing Control Module

The 400 Series modules consists of a complete range of interfaces developed for input/output control in the KSA700/FP1500 analogue fire systems from GE Interlogix. The KAL426 allows for the connection and control of one extinguishing area to the addressable fire panel loop. Specifications

Supply voltage

22-38 VDC

Current consumption Quiescent @ 24 V

110 A

Quiescent @ 35 V

210 A

Alarm

< 10 mA

Aux. supply (24 VDC) quiescent

120 mA

Aux. supply (24 VDC) alarm

27 Kohm

Normal

1.2 - 18 Kohm

Short circuit

< 470 ohm

Ordering Information SOB708 LON700 output board with 8 supervised outputs

SOB708

Conventional Fire Systems Page : 95

FB708

FP700 black box with 7 slot card cage

LON700 series The FB708 and FB740 'black boxes' allow for the distribution of LON700 input / output units. When used with the NC700 or FM740, the FB7xx is connected to the FP700 / FP2000 firepanels with the LON700 bus.

Ordering Information FB708 FP700 black box with 7 slot card cage FB740 FP700 black box with 11 slot card cage and PS700 NC700 LON700 interface board

E E E E E E E

Fully modular Echelon based network Various output boards Microprocessor based Local and remote control For fire panel distributed systems 7 slot card cage or 11 slot card cage with power supply

LON700 Devices Page : 96

LON700 interface board

NC700

The NC700 is an interface board to connect a LON700 bus from a fire panel to a FB7xx 'black box'.

Ordering Information NC700 LON700 interface board

Plug-in power supply 3.5 A

The PS700 power supply can be used to extend the power output in LON700 systems.

Ordering Information PS700 Plug-in power supply 3.5 A

PS700

Addressable Fire Systems Page : 97

FP1501

Analogue addressable fire detection panel - 1 loop

The FP1501 1 loop analogue addressable fire alarm control panel is the ideal solution for small to medium-sized installations. Very powerful and cost-effective, it is extremely simple to install and use due to is ergonomic, advanced design. The panel is supplied in an elegant, high-quality, conveniently sized, heavy-duty enclosure. It has a high-quality keyboard with audible metallic click and good travel. Specifications

Supply Voltage

110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%)

Current Consumption

175 mA Quiescent / 241 mA in alarm with no devices connected

Batteries Capacity

2 x 12 V - 7 AH (SLA type)

Fuse Rating

3A

Charger Rating

350 mA @ 27.6 VDC @ 20 °C (Temperature compensated -3 V / °C)

Loop characteristics per loop Capacity

250 addresses per loop

Maximum Load

400 mA / 26 VDC to 32 VDC

Maximum Electrical Characteristics

44 Ohm / 500 nF approximately 2 km of 1.5 mm2 diameter cable

Sounders (reverse polarity supervision) Maximum Load Delays Relay Outputs (potential free)

250 mA each (2 Sounder outputs available) / 18 VDC to 24 VDC 10 seconds to 600 seconds, software adjustable in 10 second intervals 1 A @ 30 VDC

24 V Auxiliary Output Maximum Load

250 mA @ 18 VDC to 28 VDC

Environment Working Temperature

-5°C to +40 °C

Relative Humidity

0-95% non-condensing

IP Rating

IP30

Physical Characteristics Size

420 mm (w) x 335 (h) x 110 (d)

Weight

6.2 kg without batteries / 10.7 kg with 2 x 7 Ah batteries

Ordering Information FP1501 Analogue addressable fire detection panel - 1 loop

E E E E E E E E E E E E E E E E E

One and two loop control panels 4 x 40 characters LCD display 20 Display zones EN54 approved 2 User access levels 2 Monitored sounder outputs 2 Programmable voltage free relays 24 Volt auxiliary output I/O programming capabilities with Boolean functions Day/night sensitivity settings Coincidence within zones Installation test capability Full networking capabilities up to 10 nodes 2-wire RS485 communications network Industry standard RS232 communications port Easy up/download programming from a standard PC Graphic PC software

Addressable Fire Systems Page : 98

FP1502

Analogue addressable fire detection panel - 2 loops

The FP1500 series analogue addressable fire alarm control panels is the ideal solution for small to medium-sized installations. Very powerful and cost-effective, they are extremely simple to install and use due to their ergonomic, advanced design. The panels are supplied in an elegant, high-quality, conveniently sized, heavy-duty metal enclosure and are finished in a high-gloss paint. All panels have a high-quality keyboard with audible metallic click and good travel. The batteries for the system may be housed inside the cabinet. Specifications

Supply Voltage

110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%)

Current Consumption

175 mA Quiescent / 241 mA in alarm with no devices connected

Batteries Capacity

2 x 12 V - 7 AH (SLA type)

Fuse Rating

3A

Charger Rating

350 mA @ 27.6 VDC @ 20 °C (Temperature compensated -3 V / °C)

Loop characteristics per loop Capacity

250 addresses per loop

Maximum Load

400 mA / 26 VDC to 32 VDC

Maximum Electrical Characteristics

44 Ohm / 500 nF approximately 2 km of 1.5 mm2 diameter cable

Sounders (reverse polarity supervision) Maximum Load Delays Relay Outputs (potential free)

250 mA each (2 Sounder outputs available) / 18 VDC to 24 VDC 10 seconds to 600 seconds, software adjustable in 10 second intervals 1 A @ 30 VDC

24 V Auxiliary Output Maximum Load

250 mA @ 18 VDC to 28 VDC

Environment Working Temperature

-5°C to +40 °C

Relative Humidity

0-95% non-condensing

IP Rating

IP30

Physical Characteristics Size

420 mm (w) x 335 (h) x 110 (d)

Weight

6.2 kg without batteries / 10.7 kg with 2 x 7 Ah batteries

Ordering Information FP1502 Analogue addressable fire detection panel - 2 loops

E E E E E E E E E E E E E E E E E

One and two loop control panels 4 x 40 characters LCD display 20 Display zones EN54 approved 2 User access levels 2 Monitored sounder outputs 2 Programmable voltage free relays 24 Volt auxiliary output I/O programming capabilities with Boolean functions Day/night sensitivity settings Coincidence within zones Installation test capability Full networking capabilities up to 10 nodes 2-wire RS485 communications network Industry standard RS232 communications port Easy up/download programming from a standard PC Graphic PC software

Addressable Fire Systems Page : 99

NC785

RS485 expansion kit for KSA701/FP1500 fire panels

The NC785 RS485 expander allows for an easy upgrade to the KSA701/FP1500 series addressable fire panels. Each module adds an additional industry standard RS485 communication port to the panel. This port could be used for communications with other network nodes in the fire panel network. Specifications

Number of ports

1

Communications medium

RS485

Technical specifications Maximum cable length

1200 m

Communication speed

9600 baud

Cable

CAT5 - twisted with screen

Termination resistance

150 Ohm

Ordering Information NC785 RS485 expansion kit for KSA701/FP1500 fire panels

E Industry standard RS485 communications E No hardware configuration required

Addressable Fire Systems Page : 100

FR1500

Analogue addressable LCD Repeater/Emulator (AC Powered)

The FP1500 Series analogue addressable fire alarm panels are the ideal solution for small to medium-sized installations. Very powerful and cost-effective, they are easy to install and use due to their ergonomic, advanced design. The FR1500 LCD repeater is supplied in the same enclosure as the FP1500. Specifications

Supply Voltage AC Version

110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%)

DC Version

24 VDC

Current Consumption

175 mA Quiescent / 200 mA in alarm

Battery Charger (AC Version only) Capacity

2 x 12 V - 7 AH (SLA type)

Fuse Rating

3A

Charger Rating

350 mA @ 27.6 VDC @ 20 °C (Temperature compensated -3 V / °C)

Environment Working Temperature

-5°C to +40 °C

Relative Humidity

0-95% non-condensing

IP Rating

IP30

Physical Characteristics Size

420 mm (w) x 335 (h) x 110 (d)

Weight

6.2 kg without batteries / 10.7 kg with 2 x 7 Ah batteries RS232 and RS485 standard

Communication Ports

Ordering Information FR1500 Analogue addressable LCD Repeater/Emulator (AC Powered)

E E E E E E E E

Modern, attractive design 4 x 40 characters LCD display 20 Display zones EN54 compliant with approvals pending 3 User access levels 24 VDC or 230 VAC models available Panel networking Full system control

Addressable Fire Systems Page : 101

MODGSM

GSM Modem for KSA700/FP1500 Series Fire Panels

The MODGSM modem may be used in KSA701/FP1500, KSA702 and KSA705 fire panel from GE-Interlogix. It is ideal for use as a standard modem for making and receiving calls from and to the fire panel, but may also be used for GSM messaging. Specifications

GSM Band

900/1800 MHz

Services

Data, SMS, Voice and Fax

AT Commands

GSM 07.07 and 07.05

Output Power (max) GSM900

2W

GSM1800

1W

Input Voltage

5 to 32 V

Current @ 5V Avarage

330 mA

Peak

1.8 A

SIM Interface

3V / 5V

Dimensions (h x w x d)

98 x 54 x 25 mm

Weight

130 g

Environmental Temperature Storage

- 25 °C to + 70 °C

Operating

- 20 °C to + 55 °C

Ordering Information MODGSM GSM Modem for KSA700/FP1500 Series Fire Panels

E E E E

Dual-Band 900/1800 MHz Data and SMS services Remote control by AT commands Wide input voltage range

Addressable Fire Systems Page : 102

Graphic Software for KSA700/FP1500 Fire Systems (1 panel-2 loops)

PCG-Graphic102

The PCG-Config series consists of 3 software applications. The individual software formats allows the graphic package to grow with the installation. PCG-Config102 operates with a single panel and allows for the configuration of all devices up to a maximum of two loops. Specifications

Hardware requirements Communication

RS232, modem and/or TCP/IP

Display

SVGA or higher resolution

Hard disk

2 Gb with 650 Mb free space

Keyboard

Required

Pointing device

Required

Printer

System printer required for printing

Processor

1 GHz or higher Pentium III-compatible CPU

RAM

256 Mb or more

Removable media

1.44 Mb stiffy and CD-ROM or DVD drive

Software requirements Operating system

Windows '98 or Windows 2000

Ordering Information

E Bi-directional communication with single panels and networked fire systems

PCG-Graphic102 Graphic Software for KSA700/FP1500 Fire Systems (1 panel-2 loops)

E E E E E E E E E

Local or remote connection via modem or TCP/IP Large selection of user configurable icons Visualises device alarms and status of in- and outputs Event texts retrieval from the panel Configurator and operator contol levels Navigation buttons allowed Event logs with reporting facilities Basic drawing package included Imports bmp & drw format graphics

Addressable Fire Systems Page : 103

PCG-GraphicNW

Graphic Software for KSA700/FP1500 Fire Systems (multi-panel)

The PCG-Config series consists of 3 software applications. The individual software formats allows the graphic package to grow with the installation. PCG-ConfigNW allows for monitoring on networked systems with multiple panels. Specifications

Hardware requirements Communication

RS232, modem and/or TCP/IP

Display

SVGA or higher resolution

Hard disk

2 Gb with 650 Mb free space

Keyboard

Required

Pointing device

Required

Printer

System printer required for printing

Processor

1 GHz or higher Pentium III-compatible CPU

RAM

256 Mb or more

Removable media

1.44 Mb stiffy and CD-ROM or DVD drive

Software requirements Operating system

Windows '98 or Windows 2000

Ordering Information

E Bi-directional communication with single panels and networked fire systems

PCG-GraphicNW Graphic Software for KSA700/FP1500 Fire Systems (multi-panel)

E E E E E E E E E

Local or remote connection via modem or TCP/IP Large selection of user configurable icons Visualises device alarms and status of in- and outputs Event texts retrieval from the panel Configurator and operator contol levels Navigation buttons allowed Event logs with reporting facilities Basic drawing package included Imports bmp & drw format graphics

Addressable Fire Systems Page : 104

FP1216EN

Analogue addressable fire panel 2 - 4 loops, 16 zones

The FP1216EN is a versatile, cost effective analogue addressable fire panel with 2 to 4 loops and powerfull I/O features. It supports all the LON700 devices and repeaters, and can be optionally upgraded to provide full networking. The FP1216EN is truly user friendly and provides a generous 8 x 40 graphic, backlit display. I/O control is done via the powerful FP2000/FP1200 series boolean I/O programing module. Extensive maintenance features are provided standard. The FP1216EN supports both 2000 and 900 series sensors and I/O units. Specifications

Supply voltage

230 V ac (+10/-15%)

Min. supply current @ 24 VDC

50 Hz 220 VA 0.2 A

Battery charger rating @ 27.6 VDC

1.6 A

Total supply rating @ 27.6 VDC

4A

Relay rating @ 24 VDC

2A

Weight (no batteries)

7.5 kg

Dimensions (h x w x d)

440 x 444 x 125 mm

Ordering Information FP1216EN

Analogue addressable fire panel 2 - 4 loops, 16 zones

FR2000

LCD repeater with emulator functions

FP-RIM1270 LC2002 LON2000 MOD2000 NC2011 NC2051 NE2011 NE2051

Rim surround for the 780 and 1200N series fire panel boxes 2-loop extension board for FP1200 / FP2000 fire panels LON700 driver for FP1200 / FP2000 Modem kit ARCNET RS485 network card with single RS485 interface ARCNET network card with single optical interface board RS485 network extension board Fibre optic network extension board

PCG-N PCG-S PCC2000 PCM2000

Graphics package network application with copy protection key Graphics package with copy protection key Programming and configuration software Maintenance and support software with copy protection key

E E E E E E E

One man maintenance Soak test On-line diagnostics and statistics Power supply for 72 hour autonomy Floating background for 2000 series sensors Coincidence within and in between zones Start-up default mode

E Upload/download, remote maintenance and graphic PC software

E E E E E

I/O programming including Boolean functions EN 54 p2 & 4 approved Bosec certified 2 or 4 class A loops Full range of LON700 devices

Addressable Fire Systems Page : 105

FP2416

Analogue addressable fire panel 2 - 4 loops, 16 zones

FP2000 Series A versatile, powerful analogue addressable fire panel, 2 to 4 loops, 16 displayed zones with extensive I/O features. The fire panel can operate within a 31 panel network and can communicate with global repeaters and PC grahics. It also supports all the LON700 devices and repeaters using a seperate two wire bus. The FP2000 series is truly user-friendly, and provides a generous 8 x 40 backlit graphic display. I/O control is done via the powerful FP2000/FP1200 series boolean I/O programing module. Extensive maintenance features are provided standard. The FP2000 series supports both 2000 and 900 series sensors and I/O units. Specifications

Supply voltage 1

190 - 270 V ac

Supply voltage 2

40- 60 Hz 160 VA max. 21 - 27 V dc

Current consumption Quiescent @ 24 V dc (equipped loop)

500 mA

Alarm current @ 24 V dc

600 mA

Available auxiliary current in alarm

3.4 A

Battery charger rating @ 27.5 V dc

3A

Total supply rating @ 27.5 V dc

4A

Relay rating @ 24 V dc

2A

Weight (no batteries)

11 kg

Dimensions (mm) (H x W x D)

609 x 441 x 109

Ordering Information FP2416 FR2000 LC2002 NC2011 NC2051 NE2011 NE2051 LON2000 LON700 FRL700 MOD2000 PCM2000 PCC2000 PCG Series PR2000

Analogue addressable fire panel 2 - 4 loops, 16 zones LCD repeater with emulator functions 2-loop extension board for FP1200 / FP2000 fire panels ARCNET RS485 network card with single RS485 interface ARCNET network card with single optical interface board RS485 network extension board Fibre optic network extension board LON700 driver for FP1200 / FP2000 2 wire repeaters LCD repeater Modem kit Maintenance and support software with copy protection key Programming and configuration software PC Graphic Software Packages for Aritech Fire Sytems Internal printer

E E E E E E E E E E E E

One man maintenance Graphic maintenance Maintenance warning Service reminder signal Soak test On-line diagnostics and statistics Floating background Day/night sensitivity setting Coincidence within and in between zones Automatic timed and manual on/off zones Start-up default mode Service switch

E Upload/download, remote maintenance and graphic PC software

E E E E E E

I/O programming including Boolean functions ARCNET panel networking EN54 approved, certified Bosec, VdS, NFA2P Networkable "black box" and "global zone" system Full range of repeater panels Full range of LON700 devices

Addressable Fire Systems Page : 106

FP2432

Analogue addressable fire panel 2 - 4 loops, 16 - 32 zones

FP2000 Series A versatile, powerful analogue addressable fire panel, 2 to 4 loops, 16 to 32 displayed zones with extensive I/O features. The fire panel can operate within a 31 panel network and can communicate with global repeaters and PC grahics. It also supports all the LON700 devices and repeaters using a seperate two wire bus. The FP2000 series is truly user-friendly, and provides a generous 8 x 40 backlit graphic display. I/O control is done via the powerful FP2000/FP1200 series boolean I/O programing module. Extensive maintenance features are provided standard. The FP2000 series supports both 2000 and 900 series sensors and I/O units. Specifications

Supply voltage 1

190 - 270 V ac

Supply voltage 2

40- 60 Hz 160 VA max. 21 - 27 V dc

Current consumption Quiescent @ 24 V dc (equipped loop)

500 mA

Alarm current @ 24 V dc

600 mA

Available auxiliary current in alarm

3.4 A

Battery charger rating @ 27.5 V dc

3A

Total supply rating @ 27.5 V dc

4A

Relay rating @ 24 V dc

2A

Weight (no batteries)

11 kg

Dimensions (mm H x W x D)

609 x 441 x 109

Ordering Information FP2432 FR2000 LC2002 ZE2016 NC2011 NC2051 NE2011 NE2051 LON2000 LON700 FRL700 MOD2000 PCM2000 PCC2000 PCG Series

Analogue addressable fire panel 2 - 4 loops, 16 - 32 zones LCD repeater with emulator functions 2-loop extension board for FP1200 / FP2000 fire panels 16-zone LED extension fire and fault LED ARCNET RS485 network card with single RS485 interface ARCNET network card with single optical interface board RS485 network extension board Fibre optic network extension board LON700 driver for FP1200 / FP2000 2 wire repeaters LCD repeater Modem kit Maintenance and support software with copy protection key Programming and configuration software PC Graphic Software Packages for Aritech Fire Sytems

E E E E E E E E E E E E

One man maintenance Graphic maintenance Maintenance warning Service reminder signal Soak test On-line diagnostics and statistics Floating background Day/night sensitivity setting Coincidence within and in between zones Automatic timed and manual on/off zones Start-up default mode Service switch

E Upload/download, remote maintenance and graphic PC software

E E E E E E

I/O programming including Boolean functions ARCNET panel networking EN54 approved, certified Bosec, VdS, NFA2P Networkable "black box" and "global zone" system Full range of repeater panels Full range of LON700 devices

Addressable Fire Systems Page : 107

FP2864

Analogue addressable fire panel, 2 - 8 loops, 16 - 64 zones

The FP2864 is a versatile, powerful analogue addressable fire panel, 2 to 8 loops, 16 to 64 displayed zones with extensive I/O features. It can operate within a 31 panel network and can communicate with global repeaters and PC grahics. It also supports all the LON700 devices and repeaters using a seperate two wire bus.The panel is truly user-friendly, and provides a generous 8 x 40 backlit graphic display. I/O control is done via the powerful 2000/1200 series boolean I/O programing module. Extensive maintenance features are provided standard. The FP2864 supports 2000, 1500 and 900 series sensors and I/O units. Specifications

Supply voltage 1

190 - 270 VAC

Supply voltage 2

40 - 60 Hz 160 VA max. 21 - 27 VDC

Current consumption Quiescent @ 24 VDC (equipped loop)

800 mA

Alarm current @ 24 VDC

1A

Available auxiliary current in 3 A alarm Battery charger rating @ 27.5 VDC

3A

Total supply rating @ 27.5 VDC

4A

Relay rating @ 24 VDC

2A

Weight (no batteries)

15 kg

Dimensions (H x W x D)

804 x 441 x 109 mm

Ordering Information FP2864

Analogue addressable fire panel, 2 - 8 loops, 16 - 64 zones

BUS2000 ESPA2000 LC1502 LON2000 LON2000R MOD2000 NC2011 NC2051 NE2011 NE2051 PR2000 RB2016 RE2004 ZE2016

2000 Series bus termination board ESPA protocol hardware key 2-loop extension board for 1200/2000 series fire panels LON700 driver for FP1200 / FP2000 LON driver for FP1200/2000 - closed loop systems Modem kit ARCNET RS485 network card with single RS485 interface ARCNET network card with single optical interface board RS485 network extension board Fibre optic network extension board Internal printer Relay extension board for 1200/2000 series fire panels 2000 Series Memory Expansion Kit 16-zone LED extension fire and fault LED

PCM2000 PCC2000

Maintenance and support software with copy protection key Programming and configuration software

PCG-N PCG-S

Graphics package network application with copy protection key Graphics package with copy protection key

E E E E E E E E E E E E

One man maintenance Graphic maintenance Maintenance warning Service reminder signal Soak test On-line diagnostics and statistics Floating background Day/night sensitivity setting Coincidence within and in between zones Automatic timed and manual on/off zones Start-up default mode Service switch

E Upload/download, remote maintenance and graphic PC software

E E E E E E

I/O programming including Boolean functions ARCNET panel networking EN54 approved, certified Bosec, VdS, NFA2P Networkable "black box" and "global zone" system Full range of repeater panels Full range of LON700 devices

Addressable Fire Systems Page : 108

FB2400

Analogue addressable fire panel 2 - 4 loops, 'black box'

FP2000 series The FB2400 / FB2800 'black box' system allows a cost-effective network of fire panels to be interconnected to a global repeater using the FP2000 series arcnet network. The FB black boxes have all the features of the FP2000 series of fire panels, but have no display / keyboard. All controls and display is done via the global repeater. Specifications

Supply voltage 1

190 - 270 V ac

Supply voltage 2

40- 60 Hz 160 VA max. 21 - 27 V dc

Current consumption Quiescent @ 24 V dc (equipped loop)

500 mA

Alarm current @ 24 V dc

600 mA

Available auxiliary current in alarm

3.4 A

Battery charger rating @ 27.5 V dc

3A

Total supply rating @ 27.5 V dc

4A

Relay rating @ 24 V dc

2A

Weight (no batteries)

11 kg

Dimensions (mm) (H x W x D)

609 x 441 x 109

Ordering Information FB2400 Analogue addressable fire panel 2 - 4 loops, 'black box' FB2800 Analogue addressable fire panel 2 - 8 loops, 'black box'

E E E E E E E E E E E E

One man maintenance Graphic maintenance Maintenance warning Service reminder signal Soak test On-line diagnostics and statistics Floating background Day/night sensitivity setting Coincidence within and in between zones Automatic timed and manual on/off zones Start-up default mode Service switch

E Upload/download, remote maintenance and graphic PC software

E E E E

I/O programming including Boolean functions ARCNET panel networking Networkable "black box" and "global zone" system Full range of repeater panels

Addressable Fire Systems Page : 109

2-loop extension board for FP1200 / FP2000 fire panels

LC2002

FP1200 / FP2000 series Specifications

Current consumption Quiescent @ 24 V dc (Fully equipped loop)

+ 150 mA (252 detectors)

Ordering Information LC2002 2-loop extension board for FP1200 / FP2000 fire panels

16-zone LED extension fire and fault LED

The ZE2016 allows the extension of the zones of the Fx2x32 and Fx2x64 fire panels and repeaters by 16 additional zones.

Ordering Information ZE2016 16-zone LED extension fire and fault LED

ZE2016

Addressable Fire Systems Page : 110

LON700 driver for FP1200 / FP2000

LON2000

FP1200 / FP2000 series A LON700 driver that connects FP1200 / FP2000 fire panels to LON700 devices

Ordering Information LON2000 LON700 driver for FP1200 / FP2000

ARCNET RS485 network card with single RS485 interface

The NC2011 is an interface board to connect an RS485 copper network directly into the 1200/2000 series fire panels. It is supplied with one NE2011 pre installed.

Ordering Information NC2011 ARCNET RS485 network card with single RS485 interface NE2011 RS485 network extension board

NC2011

Addressable Fire Systems Page : 111

ARCNET network card with single optical interface board

NC2051

The NC2051 is an interface board to connect a fiber optic network directly into the 1200/2000 series fire panels. It is supplied with one NE2051 pre installed.

Ordering Information NC2051 ARCNET network card with single optical interface board NE2051 Fibre optic network extension board

RS485 network extension board

The NE2011 is a RS485 network extension board for the NC2011 to allow dual bus and closed ring networks.

Ordering Information NE2011 RS485 network extension board

NE2011

Addressable Fire Systems Page : 112

Fibre optic network extension board

FP1200 / FP2000 series An extension board for the NC2051 to allow a fibre optic ring bus

Ordering Information NE2051 Fibre optic network extension board

NE2051

LON700 Devices Page : 113

FRL700

LCD repeater

The LON700 LCD repeater is a smart and compact, cost-effective solution for fire panel repeaters. It is also available as an FBP700 fire brigade panel for Dutch and Scandinavian norms. Specifications

Dimensions (l x w x d)

240 x 320 x 60 mm

Weight

1.5 kg

Operating temp °C

-5°C to +40°C

Operating voltage

15 - 30 VDC

Current consumption Max. quiesent

100 mA

Bus Connection

two wire LON700

Bus Cable

CAT 5

Total number of repeaters 700/1200/2000 Series

15

Ordering Information FRL700 LCD repeater

E E E E E

2 wire connection between fire panel and repeaters Up to 1500 metre bus length 24 Volt power supply Cost effective repeater solutions Easily installed, simple operation

E 4 x 20 charater LCD display, common LED's, push button control

E LON700 module

Addressable Fire Systems Page : 114

FR2000

LCD repeater with emulator functions

FP1200 / FP2000 series A powerful LCD repeater that can be used as a local or global repeater on a FP1200 / FP2000 fire panel network. Fire panels can be emulated from the FR2000. An 80 x 40 backlit graphic display and full indication and control keyboard is provided standard. Specifications

Supply voltage

230 V ac (+10/-15%)

Min. supply current @ 24 V dc

50 Hz 50 VA 0.15 A

Battery charger rating @ 27.6 V dc

0.3 A

Total supply rating @ 27.6 V dc

1A

Relay rating @ 24 V dc

2A

Weight (no batteries)

7.5 kg

Dimensions (mm H x W x D)

365 x 444 x 111

Ordering Information FR2000 NE2011 NE2051 FP-RIM1270

LCD repeater with emulator functions RS485 network extension board Fibre optic network extension board Rim surround for the 780 and 1200N series fire panel boxes

E 8 x 40 character graphic display E Arcnet network connection to FP1200/FP2000 series firepanels

E E E E

Global repeater function Comprehensive control and display functions Fire panel emulation function Dual RS232 ports

Addressable Fire Systems Page : 115

FR2032

Repeater / emulator 16 - 32 zones or panels

FP1200 / FP2000 series A repeater / emulator with 16, expandable to 32, displayed fire and fault zones, used in FP1200 / FP2000 networked systems. The repeater is connected on the arcnet network and can operate in a local or global repeater mode. An 80 x 40 backlit graphic display and full indication and control keyboard is provided standard. Specifications

Supply voltage

21 - 28 V dc

Current consumption

300 mA max

Weight

11 kg

Dimensions (mm H x W x D)

609 x 441 x 109

Ordering Information FR2032 NE2011 NE2051 ZE2016

Repeater / emulator 16 - 32 zones or panels RS485 network extension board Fibre optic network extension board 16-zone LED extension fire and fault LED

E 8 x 40 character graphic display E Arcnet network connection to FP1200 / FP2000 series firepanels

E E E E E

Global repeater function Comprehensive control and display functions 16 zones fire and fault expandable to 32 zones 24 Volt operation Emulation functions

Addressable Fire Systems Page : 116

FR2064

Repeater/emulator 16 - 64 zones or panels

A repeater/emulator with 16 fire and fault zones, expandable to 64, used in 1200/2000 series networked systems. The repeater is connected on the arcnet network and can operate in a local or global repeater mode. An 80 x 40 character, backlit graphic display and full indication and control keyboard is provided standard. Specifications

Supply voltage 1

Supply voltage 2

160 VA max. 21 - 27 VDC

Current consumption Quiescent @ 24 VDC (equipped loop)

300 mA

Alarm current @ 24 VDC Available auxiliary current in alarm Battery charger rating @ 27.5 VDC Total supply rating @ 27.5 VDC Relay rating @ 24 VDC Weight (no batteries)

15 kg

Dimensions (H x W x D)

804 x 441 x 109 mm

Ordering Information FR2064

Repeater/emulator 16 - 64 zones or panels

BUS2000 ESPA2000 LON2000 LON2000R MOD2000 NE2011 NE2051 PR2000 ZE2016

2000 Series bus termination board ESPA protocol hardware key LON700 driver for FP1200 / FP2000 LON driver for FP1200/2000 - closed loop systems Modem kit RS485 network extension board Fibre optic network extension board Internal printer 16-zone LED extension fire and fault LED

E 8 x 40 character graphic display E Arcnet network connection to FP1200 / FP2000 series firepanels

E E E E E

Global repeater function Comprehensive control and display functions Emulation function 16 to 64 zones fire and fault displayed 24 volt operation

Addressable Fire Systems Page : 117

UN2011

FP1200 / FP2000 arcnet to RS232 converter

FP1200 / FP2000 series The unversal node allows the fire panel arcnet network to be extended to computer software applications either locally with the RS232 interface, or remotely using the MOD2000. It has a 230 volt power supply and battery charger self contained in the unit. Specifications

Input voltage

230 V ac, 50 Hz, 10 VA

Battery type

12 V 1,2 Ah

Fault relay

2 A @ 24 V dc, 50 W dc

Weight

5 kg

Dimensions mm (H x W x D)

400 x 300 x 65

Operating remperature

0 - 40 °C

Ordering Information UN2011 FP1200 / FP2000 arcnet to RS232 converter MOD2000 Modem kit

E FP1200 / FP2000 arcnet to RS232 interface E Allows computer applications to operate on the fire panel network

E 230V operation and battery charger E Can be extended with MOD2000 for remote operation E 'Black box' operation

Addressable Fire Systems Page : 118

MOD2000

Modem kit

FP1200 / FP2000 series An internal modem for the FP1200 / FP2000 fire panels or a UN2011 universal node. The modem has the autonomy of the fire panel power supply, and has extended telephone line protectection. The MOD2000 can also be used with a computer.

Ordering Information MOD2000 Modem kit

E E E E

MOD2000 For fire panel and universal node operation Internal installation Autonomous power supply

Addressable Fire Systems Page : 119

PCC2000

Programming and configuration software

PCC2000 allows easy, menu driven, programming of all the panel's features and settings. Common texts can be easily copied while sensors, zones and areas increment or follow automatically. Boolean logic programming becomes simple as inputs and outputs are continuously displayed for the programmer's convenience. Specifications

Processor

486 66 MHz

RAM

12 Mb

Display adapter

VGA

Hard disk space

20 MB

Pointing device

MS Mouse

Graphical environment

Windows 98, 2000, XP

Communications ports

1 x RS232 1 x Parallel

Ordering Information PCC2000 Programming and configuration software

E Provide communication with single fire panels and networked fire systems, both locally or remote via modem

E E E E

Windows 98, 2000 and XP compatible For use with 2000/1200 series panels Menu driven Full or partial up- and download

Addressable Fire Systems Page : 120

PCM2000

Maintenance and support software with copy protection key

PCM2000 allows local and remote maintenance facilities for 1200/2000 series fire panels. Amongst others, it allows for full panel emulation, data retrieval and central alarm monitoring. Specifications

Processor

Pentium 133Mhz (or better)

RAM

32 Mb (or more)

Display Adapter

VGA

Hard Disk Space

20 MB

Pointing Device

Bus or P/S2 Mouse

Graphical Environment

Windows 98, NT or 2000

Communications ports

Depending on Drivers Printer port (for key) 1 Parallel

Ordering Information PCM2000 Maintenance and support software with copy protection key

E Provide communication with single fire panels and networked fire systems, both locally or remote via modem

E E E E E E E E

Windows 95, 98 and NT compatible For use with FP2000, FP1200 Full panel emulation Data retrieval Central station History log Address book Dynamic Link Library (DLL) for third party integration

Addressable Fire Systems Page : 121

PCG-S

Graphics package with copy protection key

2 Packages allow the graphic package to grow with the installation. The basic version PCG-S operates with a single panel, while the PCG-N supports a network. Upgrades do not require rework on the existing database, drawings, etc. Specifications

Item

Recommended

Processor

Pentium II 266 MHz (or better)

RAM

64 Mb (or more)

Display adapter

SVGA or better

Hard disk space

200 MB

Pointing device

MS Mouse, Bus or P/S2

Graphical environment

Windows NT

Communication ports

1 x RS-232 - Depending on drivers 1 x Parallel - Printer port (for key)

Ordering Information PCG-S Graphics package with copy protection key

E Provide bi-directional communication with single fire panels and networked fire systems, both locally and remote via modem

E E E E E E E E E E E E

Windows 2000 and NT compatible For use with FP2000, FP1200, FP1100 and FP700 Constructed around Sybase SQL Anywhere Large selection of icons Visualises inputs & outputs Information page per point Get texts from panel Several operator levels and passwords Operator configurable Multiple navigation buttons Event logs Basic drawing package included

E Imports .bmp & .wmf drawings from virtually any package

E Hardware key protected

Content DI322I DP331I DT313I KCT731 KZ700 KZ705 KZ705D EOL-ACT KZ705R S700 DP721I DP721T DT713-5 DT713-7 DB702 DI650 DP652 DT654 DB860 DB861 DB806 DB650 DI1552 DP1561 DP1551T DT1553 PG700 KZ705I KZ705AS KZ705IAS KAL410 KAL414C KAL426C KAL430 KAL434C KAL440 KAL450 KAL460 KAL470 KAL490 DP2051 DP2061 DP2061T DP2071

Ionisation detector, conventional

Page : 3

Optical detector, conventional, with field exchangeable optical block

Page : 4

Temperature detector (fixed and rate-of-rise), conventional

Page : 5

Calibration Tool for KL731/DP331I Fire Detectors

Page : 6

Universal fire detector base

Page : 7

Universal fire detector base with earth connection

Page : 8

Conventional fire detector base with diode

Page : 9

Active end-of-line device for use with FP400/KL700 fire panels

Page : 9

Conventional 12 VDC fire detector base with relay

Page : 10

Surface mount accessory for KZ700 and KZ705 series bases

Page : 11

Photoelectric smoke detector with remote alarm LED output

Page : 12

Photoelectric smoke and heat detector head with remote alarm LED

Page : 13

57º C fixed and rate-of-rise heat detector

Page : 14

70º C fixed and R.O.R. heat detector

Page : 15

10 cm diameter base - 6 terminals

Page : 16

Ionisation smoke detector

Page : 17

Optical smoke detector

Page : 18

Heat detector, R.O.R., 57º C A1R

Page : 19

Standard Base

Page : 20

Backplate for Ingress Protection 860-950

Page : 20

Conduit box for 860 / 950 series bases

Page : 21

650 series relay base

Page : 21

Ionisation Sensor

Page : 22

Optical sensor with field exchangeable optical block

Page : 23

Dual Sensor (Optical/Heat)

Page : 24

Heat Sensor

Page : 25

Fire sensor programmer

Page : 26

Analogue fire detector base with isolator

Page : 27

Analogue fire detector base with sounder

Page : 28

Analogue fire detector base with isolator and sounder

Page : 29

Conventional Zone Monitor Unit - 1 Zone

Page : 30

Conventional Zone Monitor Unit - 4 Zones

Page : 31

Extinguishing Control Module

Page : 32

Relay Module - 1 Relay

Page : 33

Addressable Relay Module - 4 Relays

Page : 34

Supervised Relay Module

Page : 35

Addressable Manual Call Point

Page : 36

Digital Input Module

Page : 37

Isolator Module

Page : 38

Retention Module - 1 Input / 1 Output

Page : 39

Optical Sensor

Page : 40

Optical Sensor with remote LED output

Page : 41

Optical and heat multi-sensor with remote LED output

Page : 42

Optical Sensor with 7-segment display

Page : 43

DT2053 DT2063 DT2073 DB2001 DB2002 DB2016 IU2016 DB2003 DM2000 DM2000E IO2014 IU2050 IU2055 GBX2000 IU2080 FD2705R AS2015 DI950 DP951 DT952 DM960 DI970 DP971 DT972 DM970 PT971 GBX70 II950 II952 II955 IO950 IO955 IO956 IU950 AS950 AS955 FD950 DB950 DB951 DB961 DB970 IU980 FP202 FP204

2000 Series heat sensor

Page : 44

2000 series heat sensor with remote LED output

Page : 45

Heat Sensor with 7-segment Display and Remote LED Output

Page : 46

2000 series base, 2 terminals

Page : 47

2000 series base, 4 terminals

Page : 48

Isolating base

Page : 49

Loop Isolator

Page : 50

Base for the IU2016 isolator

Page : 51

Manual call point, flying leads

Page : 52

Manual call point - Red IP67 waterproof, including backbox

Page : 53

Input Output unit - 4 inputs

Page : 54

Single Input Module

Page : 55

Conventional Zone Monitor

Page : 56

Galvanic barrier

Page : 57

Indicating Circuit Controller

Page : 57

2000 series addressable reflective beam detector 5 - 50m

Page : 58

2000 series loop powered sounder

Page : 59

Analogue addressable ionisation sensor

Page : 60

Optical sensor

Page : 60

Analogue addressable temperature sensor

Page : 61

950 series analogue addressable manual callpoint

Page : 61

Intrinsic safe analogue addressable ionisation detector

Page : 62

Intrisic safe optical detector

Page : 62

Intrinsic safe heat detector

Page : 63

Intrinsic safe manual call point

Page : 63

Intrinsic safe protocol translator

Page : 64

Galvanic barrier (single channel)

Page : 64

950 series mini switch monitor unit

Page : 65

950 series switch monitor unit - surface mount

Page : 65

950 series zone monitor unit - surface mount

Page : 66

950 series single channel IO - surface mount

Page : 66

950 series output unit - surface mount

Page : 67

950 series sounder circuit controller - surface mount

Page : 67

950 series loop isolator

Page : 68

950 series loop powered sounder

Page : 69

950 series high output loop powered sounder

Page : 70

950 series loop-powered beam detector

Page : 71

950 series standard base

Page : 72

Base for IU 950

Page : 72

Isolating base (20 devices)

Page : 73

Detector base for 970 series intrinsic safe sensors

Page : 73

Coded cards, addresses 1 - 18

Page : 74

Conventional fire alarm panel with 2 zones

Page : 75

Conventional fire alarm panel with 4 zones

Page : 76

FP206 FP402 FP408 FP412 FP416 RB404 SB404 FEC403 FEC406 FP604 ZI602 RC606 FP708 FR708 ZE708 ZI708 FM740 OCB724 RB708 SOB708 FB708 NC700 PS700 FP1501 FP1502 NC785 FR1500 MODGSM PCG-Graphic102 PCG-GraphicNW FP1216EN FP2416 FP2432 FP2864 FB2400 LC2002 ZE2016 LON2000 NC2011 NC2051 NE2011 NE2051 FRL700 FR2000

Conventional fire alarm panel with 6 zones

Page : 77

Conventional fire alarm panel with 2 zones

Page : 78

Conventional fire alarm panel with 8 zones

Page : 79

Conventional fire alarm panel with 12 zones

Page : 80

Conventional fire alarm panel with 16 zones

Page : 81

Relay module, 4 potential free relays for NK700/Fx400 fire panels

Page : 82

Relay module, 4 supervised relays for NK700/Fx400 fire panels

Page : 83

Conventional extinguishing control panel with 3 zones

Page : 84

Conventional extinguishing control panel with 6 zones

Page : 85

4-zone Conventional Fire Panel

Page : 86

Two zone extension board, including 6 outputs

Page : 87

Set of 6 bi-stable magnetic latch relays

Page : 87

Fire panel equipped with 8 zones

Page : 88

Repeater 8 zones, 24 VDC input

Page : 89

8 zone indicator LED extension board fire/fault

Page : 90

8 zone input extension board

Page : 91

Synoptic driver for 80 LEDs and common signals

Page : 92

LON700 output board with 24 open collector outputs

Page : 93

LON700 output board with 8 relays

Page : 93

LON700 output board with 8 supervised outputs

Page : 94

FP700 black box with 7 slot card cage

Page : 95

LON700 interface board

Page : 96

Plug-in power supply 3.5 A

Page : 96

Analogue addressable fire detection panel - 1 loop

Page : 97

Analogue addressable fire detection panel - 2 loops

Page : 98

RS485 expansion kit for KSA701/FP1500 fire panels

Page : 99

Analogue addressable LCD Repeater/Emulator (AC Powered)

Page : 100

GSM Modem for KSA700/FP1500 Series Fire Panels

Page : 101

Graphic Software for KSA700/FP1500 Fire Systems (1 panel-2 loops)

Page : 102

Graphic Software for KSA700/FP1500 Fire Systems (multi-panel)

Page : 103

Analogue addressable fire panel 2 - 4 loops, 16 zones

Page : 104

Analogue addressable fire panel 2 - 4 loops, 16 zones

Page : 105

Analogue addressable fire panel 2 - 4 loops, 16 - 32 zones

Page : 106

Analogue addressable fire panel, 2 - 8 loops, 16 - 64 zones

Page : 107

Analogue addressable fire panel 2 - 4 loops, 'black box'

Page : 108

2-loop extension board for FP1200 / FP2000 fire panels

Page : 109

16-zone LED extension fire and fault LED

Page : 109

LON700 driver for FP1200 / FP2000

Page : 110

ARCNET RS485 network card with single RS485 interface

Page : 110

ARCNET network card with single optical interface board

Page : 111

RS485 network extension board

Page : 111

Fibre optic network extension board

Page : 112

LCD repeater

Page : 113

LCD repeater with emulator functions

Page : 114

FR2032 FR2064 UN2011 MOD2000 PCC2000 PCM2000 PCG-S

Repeater / emulator 16 - 32 zones or panels

Page : 115

Repeater/emulator 16 - 64 zones or panels

Page : 116

FP1200 / FP2000 arcnet to RS232 converter

Page : 117

Modem kit

Page : 118

Programming and configuration software

Page : 119

Maintenance and support software with copy protection key

Page : 120

Graphics package with copy protection key

Page : 121

www.gesecurity.net

IPSCAT-2005-12-6 15:44:32