HEAT PUMP - Spletnik.si

19 downloads 1232 Views 8MB Size Report
Thanks to its lead in heat pump technology, Daikin has made a remarkable contribution to the ..... TECHNICAL DATA  SPLIT. NEW. NEW. EKHBH008B***.
PRELIMINARY

All seasons

General 2010

CLIMATE COMFORT Heating Air conditioning Applied Systems Refrigeration

DAIKIN ‘S 4 PILLARS OF GROWTH

APPLIED SYSTEMS AIR CONDITIONING

REFRIGERATION

HEATING THE LEADER IN PRODUCT QUALITY

Daikin produces a highly energy efficient and comprehensive range of quality indoor climate control products and systems for commercial, residential and industrial applications. Our product portfolio is based on four distinct core ‘pillars’ illustrating the diversification of Daikin: 

optimised heating solutions: air to air (residential and

applied systems for central cooling and heating for

commercial application) & air to water (residential

process and comfort application

application with optional domestic hot water) state of the art direct expansion air conditioning for

medium to low temperature refrigeration for retail

residential & commercial application

environment

Each pillar harnesses advanced technologies to deliver maximum energy efficiency and minimum energy consumption and running costs throughout the equipment life cycle. The width of our product range is also extensive and embracing in its coverage of these key indoor climate control disciplines to a point where we are confident of its ability to meet the requirements of our end user, specifier, contractor and installer customer base at all times.

THE LEADER IN MANUFACTURING QUALITY AND CUSTOMER SERVICE Since our establishment in Ostend (Belgium) in 1972, we have updated and expanded our manufacturing facilities, including those opened in Milan (Italy), Plzen and Brno (Czech Republic) and through acquisitions in Cramlington (UK), Güglingen (Germany) and Cecchina (Italy), to a point where they are acknowledged as the most advanced in their field in Europe. Furthermore, all our plants benefit from our Japanese parent’s policy of zero defect production, super efficient supply chain management and unrivalled research and development support. These substantial production facilities are underpinned by a network of wholly owned affiliate companies in the UK, France, Germany, Italy, Spain, Portugal, Poland, Greece, Belgium, The Netherlands, Sweden, Central Europe and South Africa, as well as numerous independent distributors throughout Europe, Africa and the Middle East supported by several offices in Ireland, Russia and Turkey. Experienced and professional support of this order enables us to maintain an enviably close relationship with international markets, tailor our product programme to suit precise regional requirements and respond quickly and efficiently to any area of potential market expansion. 

NEW PRODUCTS 2010

28 DAIKIN ALTHERMA  HIGH TEMPERATURE APPLICATION ! Ideal for renovation: connectable to high temperature radiators ! Heating and domestic hot water ! High performance: 100% thermodynamic energy to obtain water temperatures up to 80°C without using an additional electric heater.

29 DAIKIN ALTHERMA  SOLAR CONNECTION ! High performance solar collectors ! Solar connection for Daikin Altherma low temperature thanks to the unpressurised pump station ! Solar connection for Daikin Altherma high temperature thanks to the pressurised pump station

32 DAIKIN HEAT PUMP CONVECTOR  MUCH MORE THAN A FAN COIL UNIT ! Interlink function ! Approximately 25% efficiency improvement compared to a heating system combining under floor heating and regular fan coil units ! Modest size ! Low sound level



33

PRELIMINARY PICTURE

DAIKIN ALTHERMA HIGH TEMPERATURE SERIES FOR APARTMENT BUILDINGS AND COLLECTIVE HOUSING ! Centralised outdoor unit connected to individual indoor units ! Top efficiency ! Cooling possibility ! Full comfort: heating, cooling, domestic hot water ! Savings on running costs

46 DAIKIN EMURA  FTXGJ FORM. FUNCTION. REDEFINED. ! Remarkable blend of iconic design and engineering excellence with an elegant finish in brushed aluminium or matt crystal white. ! Energy efficient units: full range A class energy labels ! Weekly timer can be set to start heating or cooling anytime on a daily or weekly basis

94 SEASONAL INVERTER  RZQE ! Seasonal efficiency in line with real-life performance ! Cost-effective upgrade from R-22/R-407C to R-410A ! Very wide operation range ! Suitable for EDP applications ! Night quiet mode

96 168 AUTO CLEANING CASSETTE  FCQC8 / FCQHD8 / FMCQA / FXFQP9 ! Daikin introduces first auto cleaning cassette to European market ! Higher efficiency and comfort from daily auto cleaning of the filter ! Lower maintenance cost thanks to auto cleaning function ! Easy removal of dust with a vacuum cleaner without opening the unit



142 ROOFTOP HEAT PUMP  UATYQBY1 ! High efficient Rooftop model ! Available in R-410A refrigerant ! 'Plug and Play' system facilitates the installation of the unit ! New control panel offered as standard ! Extended operation range: in cooling down to 0°C by field setting

148 REPLACEMENT VRV®  VRV®IIIQ ! Cost-effective upgrade from R-22/R-407C to R-410A ! Increased energy efficiency compared to R-22/R-407C systems ! Fast installation compared to total system replacement (re-use of existing piping and indoor units) ! Limited & planned downtime for system replacement ! Limited & phased investment cost ! Incease capacity compared to your existing system ! No restrictions on system history

185 BIDDLE AIR CURTAIN  CAV*/CYQ* ! VRV®/ERQ are among the first DX systems connectable to Biddle air curtains ! Payback period of less than 1.5 years (compared to an electric air curtain) ! Maximum energy efficiency stemming from the application of the rectifier technology (European patent) ! Around 85% air separation efficiency, greatly reducing both heat loss and required indoor unit heating capacity ! Easy and quick to install since no additional water systems, boilers and gas connections are required



193 194 VRV® AND ERQ AIR HANDLING APPLICATIONS ! Integrate your AHU into the VRV® heat recovery or heat pump system ! ERQ heat pump for pair application ! Connectable to heat pump air handling units ! Inverter technology ! High efficiency ! Quicker response time to variations in supply air temperature compared to a full water based AHU system ! Flexible control possibilities (VRV®) ! Large capacity range: up tot 170 kw heating capacity (VRV®)

236 CONVENIPACK ! Expands Daikin’s alternative to traditional three component systems for both small and large shops ! Uses R-410A refrigerant ! Improvement of efficiency with 10% compared to the current model ! Provides increased heating, cooling and refrigeration application possibilities with respect to the current model

244 BRC1E51A ! User friendly ! Auto update to daylight saving time ! Schedule timer ! Support multiple languages ! Built-in backup power



TABLE OF CONTENTS Daikin's 4 pillars of growth

1

New products

2

Table of contents

6

Heating & Cooling

8

Environmental awareness

10

Eco-label

11

We Care icons

11

Energy labelling

12

Seasonal Efficiency

13

Daikin solution to R-22 phase out

14

Air purifier

16

Optimised heating solutions Air to water heat pumps Air to air heat pumps

Applied systems 22 32

Air cooled chillers Water cooled chillers Condenserless chillers Fan coil units Air handling units

206 216 219 224 230

Air conditioning Residential Applications Pair applications Multi model applications

38

Light Commercial Applications

88

Pair applications Commercial multi system Twin, Triple, Double Twin applications Rooftop

94 130 132 141

VRV® VRV® Outdoor Units VRV® Indoor units

Refrigeration

44 58

Conveni-pack ZEAS commercial condensing units

144

Accessories

148 166

Selection software

187

Ventilation

188

Marine Types

196

234 238

Control Systems Options & accessories



242 248

HEATING & COOLING H E AT P U MP DAIKIN HEAT PUMPS: COMBINING EFFICIENCY AND TOTAL COMFORT At Daikin, we put our more than 50 years of experience in advanced heat pump technology at your service. Our new generation of heat pumps are all-in-one heating and cooling solutions for residential and commercial applications. They see to it that temperatures are comfortably warm in the winter and cool in summer. Because our systems extract thermal energy from the ambient air (so-called air-to-air or air-to-water heat pumps), they are far more energy efficient and emit far less CO2 than comparable fossil fuel based boiler systems. HOW ENERGY EFFICIENT ARE OUR HEAT PUMPS? A heat pump’s efficiency is measured in COP (Coefficient of Performance) for heating and EER (Energy efficiency ratio) for cooling. Daikin’s heat pumps achieve COPs and EERs of up to 4, meaning one unit of consumed energy yields 4 units of heated or cooled energy.

H E AT R E COV ERY HEAT PUMP OR HEAT RECOVERY SYSTEM? If you are looking for comfort solutions to heat and/or cool your shop, office or industrial building, we at Daikin have a lot to offer. Our highly efficient heat pumps can either heat or cool, while our heat recoveryequipped systems provide simultaneous heating and cooling, all from a single system. We offer numerous heat pumps and heat recovery systems to match your needs. They come in configurations from as small as 2kW for single room solutions, up to several MW’s for large industrial applications.

WHAT IS HEAT RECOVERY? Heat recovery is achieved by diverting exhaust heat from indoor units in cooling mode to areas requiring heating. Heat recovery in other words helps you reuse the energy available in one or more areas, and dispatch it to other areas in the same building. With a COP (Coefficient of Performance) up to 9, heat recovery systems achieve one of the highest energy efficiency levels in the industry. 8



   

+

 

    

H E AT IN G ONLY HIGHLY ENERGY-EFFICIENT HEATING SOLUTIONS Thanks to its lead in heat pump technology, Daikin has made a remarkable contribution to the residential heating market: heat pump based heating systems that meet the demands of customers for less energy-gobbling systems and the demands of legislators for greater efficiency. The result: heating systems that are far more energy efficient than conventional fossil fuel solutions. This combination of advanced technology and renewable energy – air – as a fuel* places Daikin’s role as technological leader in the service of preserving our environment. Add to this the famous Daikin reliability, flexibility, safety, low installation cost and the total comfort of its heating systems, and you know why Daikin is fast becoming a ‘hot’ brand in the heating industry. *Daikin’s heating systems also use a small amount of electricity (about 1/4 of the heating energy)

CO O L IN G ONLY COOL SOLUTIONS FOR YOUR INDUSTRY You place high demands concerning what’s best for your business. We at Daikin have also been delivering state-of-the-art cooling appliances for decades. Whether you are looking for optimal energy-efficiency or for extreme precision for your industrial or process cooling, Daikin caters to your every cooling need. This unique dedication to technology and reliability makes Daikin your obvious choice.

9

ENVIRONMENTAL AWARENESS EU recognises heatpumps The approval of the Renewable Energy Directive by the European Parliament in December 2008 saw Daikin’s efforts rewarded for designing energy-efficient air-to-water and air-to-air heat pumps. In its quest for ever more energy-efficient heating products, Daikin develops heat pumps that meet all the user’s needs and consume considerably less primary energy than its fossil-fuel based competitors. For the first time, the Directive recognises also aerothermal and hydrothermal energy as renewable energy sources. With the recognition by the EU of the outside air, ground and (surface, lake or well) water as renewable energy sources, much is expected of the member states’ promotion of heat pump technologies using these renewable energy sources. Alongside with solar panels and wind turbines, heat pumps may also be considered for subsidies, promotion campaigns and tax benefits. The goal of the EU is to increase the share of renewable energy in Europe to 20% by 2020.” The urgency of the EU’s 20/20/20 objectives – reducing carbon emissions and energy consumption by 20% and increasing the share of renewable energy by 20%, all by 2020 – and the fact that heat pumps can contribute directly to meeting these ambitious objectives, present a major opportunity for heat pumps.

AEROTHERMAL HEAT PUMP

HYDROTHERMAL HEAT PUMP

GEOTHERMAL HEAT PUMP

ENERGY EFFICIENT EQUIPMENT Many product innovations stem from Daikin environmental awareness. Inverter control reduces unit start up time and varies compressor output to match precise system load requirements. Also, when linked with Daikin DC compressor motors, it allows Daikin equipment to achieve the highest COP ratings in the market. Similarly, advanced computerised control packages ensure optimum system efficiency at all times and allow remote monitoring via the internet. REDUCING WASTE Daikin was the first European air conditioning manufacturer to gain ISO14001 environmental certification and all Daikin plants and subsidiaries are now similarly certified. The company’s zero waste policy ensures that many of its manufacturing by products can be recycled, reused or recovered. RECYCLING MATERIALS Daikin recycles materials as a matter of course. For instance, the sludge recovered from pre treated waste water is used in cement manufacture. The recycling of other types of waste is also supported by investment in returnable packaging.

10

ECO-LABEL Over the past ten years, the "Flower" has become a European-wide symbol for products, providing simple and accurate guidance to consumers. All products bearing the "Flower" have been checked by independent bodies for complying with strict ecological and performance criteria. There are currently twenty-six different product groups, and already more than 250 licences have been awarded for several hundred products. The EU Eco-label is administered by the European Eco-labelling Board (EUEB) and receives the support of the European Commission, all Member States of the European Union and the European Economic Area (EEA). The Eco-labelling Board includes representatives such as industry, environment protection groups and consumer organisations. Heat-pumps have recently been added as a product group and Daikin is the first company to obtain the Eco-label for its Daikin Altherma air to water heat pumps. The EU awards a heat pump with an Eco-label when they evaluate it to be more energy efficient compared to the average of heat pumps without Eco-label. In being awarded the EU Eco-label, Daikin Altherma was assessed in a range of categories: heating and cooling efficiency, refrigerant global warming potential (GWP), noise, absence of RoHS substances, training, documentation, availability of spare parts and detailed information at point of sale. Daikin Altherma represents the culmination of Daikin’s decades-long experience with heat pump technology. It efficiently extracts the low-level heat in the ambient air and raises it to temperatures capable of comfortably heating a house and providing domestic hot water in outdoor temperatures down to -20º C. In doing so, Daikin Altherma makes use of aerothermal energy, a renewable energy source. The heat pump technology employed is highly efficient (3 to 5 kWh of heat for every 1 kWh of electricity consumed). Daikin Europe N.V. obtained an Eco-Label for the following Daikin Altherma products valid for application with outlet temperature 35°C.

B/31/1

Following models received the ECO-LABEL: ERHQ006B-EKHBH008B, ERHQ007B-EKHBH008B, ERHQ008B-EKHBH008B, ERHQ011B-EKHBH016B, ERHQ014B-EKHBH016B, ERHQ016B-EKHBH016B, ERHQ006B-EKHBX008B, ERHQ007B-EKHBX008B, ERHQ008B-EKHBX008B, ERHQ011B-EKHBX016B, ERHQ014B-EKHBX016B, ERHQ016B-EKHBX016B.

WE CARE ICONS A NUMBER OF ICONS ARE HIGHLIGHTED IN GREEN TO INDICATE PRODUCT FEATURES THAT HAVE AN IMPACT ON REDUCING ENERGY CONSUMPTION. Energy efficiency

Energy saving during standby mode

Econo mode

Two area intelligent eye

Movement sensor

Night set mode

Fan only

Auto-cleaning function

Inverter technology



ENERGY LABELLING Energy labelling is part of a European Climate Change program, targeting energy efficiency as one method of reducing CO2 emissions. The European Commission determines that improved awareness will enable users to purchase the most ecologically economic unit for their needs.

Energy efficiency class of the unit in cooling mode:

WHAT? The label provides information on air conditioning unit energy consumption. Units with cooling capacities up to 12kW are classified by energy consumption in categories from ‘A’ to ‘G’ and colour coded accordingly. The most energy efficient ‘A’ category units are indicated by a dark green arrow and the least efficient ‘G’ category units, by a red arrow. Thus users can compare the efficiencies of equal types of unit from different brands. WHAT IS LISTED ON THE LABEL Manufacturer’s name and logo and type of indoor and outdoor units (*).

Energy efficiency class of the unit in heating mode:

A

EER > 3.20

 COP > 3.60

B

3.20 ≥ EER > 3.00

 3.60 ≥ COP > 3.40

C

3.00 ≥ EER > 2.80

 3.40 ≥ COP > 3.20

D

2.80 ≥ EER > 2.60

 3.20 ≥ COP > 2.80

E

2.60 ≥ EER > 2.40

 2.80 ≥ COP > 2.60

F

2.40 ≥ EER > 2.20

 2.60 ≥ COP > 2.40

G

2.20 ≥ EER



INDICATED ANNUAL ENERGY CONSUMPTION Approximate annual energy consumed is indicated, based on a standard residential model. Annual consumption is calculated by multiplying total power input by an average of 500 hr/year IN COOLING MODE AT FULL LOAD. Annual energy consumption cost is calculated by multiplying this figure by user’s electricity tariff.

Energy Manufacturer Outside unit Inside unit More efficient

A B C D E

COOLING OUTPUT Is the unit’s cooling capacity in kW operating in cooling mode at full load. Users should select a unit with a rated output sufficient for their cooling/ heating requirements. Oversized units can increase on/off cycling, shortening service life and undersized units will not provide adequate cooling or heating. Output figures can be obtained from the manufacturer or local dealer. ENERGY EFFICIENCY RATIO (EER) Is the unit’s cooling output divided by the total electrical power input required to deliver it – the higher the EER, the greater the energy efficiency. TYPE Indicates whether the unit is a cooling only or cooling/heating model. Cooling mode indicates whether the unit is water or air cooled. HEAT OUTPUT Is the heating capacity of the unit in kW, operating in heating mode at full load.

2.40 ≥ COP

F G Less efficient Annual energy consumption, kWh in cooling mode (Actual consumption will depend on how the apliance is used and climate)

Cooling output Energy efficiency ratio

kW

Full load (the higher the better)

Type

Cooling only Cooling + Heating Air cooled Water cooled

Heat output

kW

Heating performance A: higher

G: lower

Noise (dB(A) re 1 pW)

Further information is contained in product brochures

* For multi models, Daikin indicates a single outdoor unit with a maximum of 2 wall mounted indoor units. 

Air-conditioner Energy Label Directive 2002/31/EC

SEASONAL EFFICIENCY With European legislation* pressing energy users to drastically cut energy consumption, improve energy efficiency of buildings and homes, and meet the Commission’s 20/20/20 targets, industry is looking at more appropriate ways to evaluate efficiency. Thus, the new EuP Eco-Design Directive aims at reducing the environmental impact of products in the EU. To that end it will introduce a new calculation method for measuring performance – seasonal efficiency – in replacement of the current method of nominal efficiency, which has its limitations. NOMINAL EFFICIENCY UP FOR IMPROVEMENT Measuring environmental performance is not new to Europe. Such measurements are used to set minimum requirements for manufacturers and to provide consumers with information on air conditioner performance so they can make intelligent choices when purchasing. The measurement method currently in place is that of nominal efficiency, a method, however, with limitations that result in a significant gap between rated and actual performance.

Temperature distribution curve Occurrence

r Temperature

r Current point for COP Current point for EER Heating Cooling

SEASONAL EFFICIENCY IN LINE WITH REAL-LIFE PERFORMANCE To correct this situation, a more complex measurement – seasonal efficiency – is being developed in the EuP Directive. The major differences between seasonal and nominal calculation are: › The use of several rating temperatures for cooling and heating instead of one nominal temperature, better reflecting actual performance over an entire season › Integration of operation at partial capacity instead of full capacity. › Adoption of the seasonal efficiency calculation method will result in a better estimation of the reallife performance of a unit since the majority of systems operate at partial load most of the time.

Daikin has identified the Sky Air® as the product range with the strongest potential environmental impact. Indeed, light commercial applications are responsible for the biggest energy use on a yearly basis, and this due to the high sales volume and the high number of running hours per year.

NOMINAL

In addition, the new seasonal efficiency calculation will take into consideration the power consumed by devices in auxiliary modes (when the compressor is off ). Seen over a year, energy consumption in these modes can be substantial.

TOTAL

Annual energy consumption

Yearly total energy consumption (MWh) 100% 80% 60% 40% 20%

In this view, Daikin has decided to tackle first the light commercial segment, by already applying Eco-Design principle on the Sky Air® range.

0% Residential

*EPB (Energy Performance of Buildings) Directive 2002/91/EC, EuP (Energy Using Products) Eco-Design Directive



Light commercial

DAIKIN SOLUTIONS TO R-22 PHASE OUT Due to significant developments in heat pump technology, older systems of air conditioning run less efficiently than those available today. Furthermore the use of R-22 will be soon banned in Europe. To upgrade R-22 systems as cost effective as possible: Daikin developed solutions for its commercial range. Thanks to this new technology, it is possible to use existing R22-piping. WHAT IS R-22 AND WHY IS IT PHASED-OUT IN EUROPE? R-22 is a hydrochlorofluorocarbon (HCFC) which was commonly used in air conditioning systems. When R-22 is released into the air, the ultraviolet rays of the sun cause it to decompose and chlorine is released in the stratosphere. Chlorine reacts with ozone, reducing the amount of the ozone. Due to ozone layer depletion, harmful ultraviolet rays reach the surface of the earth giving rise to a number of health and environmental issues. The international community therefore, signed the Montreal Protocol to phase out ozone depletion materials by 2030. The European Union however, decided to ban R-22 already in 2015.

WHEN WILL R-22 BE BANNED IN EUROPE?

2004

2005

2006



2010

2009

2011



2014

2015

Ban on the use of R-22 in new air conditioning equipment

1

Ban on the use of virgin R-22

Ban on the use

for service & maintenance

of all R-22 for service & maintenance

Only reclaimed & recycled1

Recycled: re-use of R-22 following a basic cleaning process by the same undertaking that carried out the recovery (can be done by installer) Reclaimed: reprocessed R-22 in order to meet the equivalent performance of virgin R-22 (by specialized company)

R-22 allowed

WHAT IS THE IMPACT ON AN R-22 INSTALLATION? The R-22 phase-out regulation will impact on all currently operating R-22 systems, although reliable R-22 equipment does not need to be replaced immediately because maintenance can be carried out with recycled or reclaimed R-22 until January 1st, 2015. However, as currently not enough R-22 is reclaimed to cover the demand, supply shortages and price increases are expected. If there is no reclaimed R-22 available certain repairs (for example: compressor change) are no longer possible and considerable air conditioning system downtime can occur. It is therefore worthwhile to consider a replacement system before 2015, especially for air conditioning systems with a large impact on the daily running of the business. DAIKIN SOLUTIONS TO R-22 PHASE-OUT For Sky Air®, re-use technology is already available on the Super Inverter and will also be available on the new Seasonal Inverter. Thanks to this technology these units can be installed using existing R-22 piping. The newly developed VRV®III-Q solution allows retaining existing R-22 piping and in some cases even the indoor units and controllers. 14

URURU AIR PURIFIER

Humidification and air purification in one MCK75JVM-K

There are many substances in the air you breathe such as allergen, bacteria, virus and tobacco smoke, which causes your health to suffer. Above all things, dryness is especially a big issue during wintertime. Daikin Ururu Air Purifier moisturizes the air inside your home and relieves the effects of dry air. Just fill the 4l tank occasionally and it will humidify your room with a maximum volume of 600ml/h. This useful and innovative function stems from the incorporation of a slim line water tank and combined water wheel and vaporisation filter assembly.

¾ ¾

Humidification thanks to the slim water tank Air purification

Daikin has already received great praise for its air purifiers: the Daikin TüV award confirms the efficiency of this unit.

MCK75JVM-K MODEL Type Power supply Dimensions Colour Weight Dust collecting method Deodorising method Air filter Air purifying operation Power input Sound pressure level (1) Air flow rate Applicable room area (2) Humidifying operation Power input Sound pressure level (1) Air flow rate Humidification (3) Water tank capacity

MCK75JVM-K

Height x Width x Depth mm kg

kW dBA m3/h m2 kW dBA m3/h ml/h l

Turbo 0.081 50 450 Turbo 0.084 50 450 600

Humidifying air purifier 1~/220-240/220-230V/50/60Hz 590x395x268 Black (Panel colour: silver) 11 Plasma ionizer + Electrostatic dust collection filter Flash streamer + Titanium apatite photocatalytic filter + Deodorising catalyst Polypropylene net with catechin H M L 0.035 0.018 0.011 43 36 26 330 240 150 46 H M L 0.037 0.020 0.013 43 36 26 330 240 150 470 370 290 4

Silent 0.008 17 60 Silent 0.012 23 120 240

(1) Sound pressure levels are the average of values measured at 1m away from the front, left, right and top of the unit. (This is equal to the value in an anechoic chamber) (2) The applicable room area is appropriate when the unit is operating in turbo mode. Applicable room area indicates the space where a certain amount of dust particles can be removed in 30 minutes. (3) Humidification amount changes in accordance with indoor and outdoor temperature and humidity. Measurement condition: 20°C in temperature, 30% in humidity.

16

humid air air Vaporization filter

HOW DOES THE HUMIDIFICATION FUNCTION WORK? Water in the tank flows into the receiver tray housing the water wheel, which lifts the water as it rotates and releases it onto the filter. Air blown onto the filter, absorbs its moisture and discharges it into the room as humidification. MCK75JVM-K

Electrostatic dust collection filter Positively charged dust and pollen are adsorbed by the negatively charged filter. Flash Streamer High-speed electrons are generated by the Flash Streamer. These electrons powerfully break down odours and formaldehyde.

Titanium Apatite Photocatalytic Filter Odour, bacteria and viruses are adsorbed and decomposed.

Dirty air

Deodorising catalyst Odours are adsorbed and broken down before the air is returned into the room.

Purified Air

Pre-filter (with catechin) Removes large dust particles and pet hairs.

Flash Streamer unit

Plasma ionizer Dust and pollen are positively charged and sent to the electrostatic filter.

Daikin Ururu Air Purifier also removes efficiently allergens (e.g. pollen, house dust mites, dust, etc.), bacteria and viruses. Additionally, it has a high deodorizing efficiency; it eliminates efficiently tobacco smoke whilst decomposing other smells. It quickly collects particles and breaks them down rapidly. Its quiet operation makes it ideal for quiet nights. The unit includes seven pleated filters (one for immediate use and 6 spares). 17

PHOTOCATALYTIC AIR PURIFIER

MC707VM-W MC707VM-S

PURE AIR FOR FREE AND HEALTHY BREATHING › stylish design › improved performance › unprecedented comfort › super quiet operation › easy to maintain › portable › no installation

THREE TIMES PURIFICATION, A GOOD DEED FOR YOUR HEALTH Pollen, dust and pet hair are just some of the potential causes of allergies, asthma and respiratory problems. A Daikin air purifier cleans the air and relieves you of these troubles thanks to a three-part operation: › allergen removal › virus and bacteria removal › odour removal

TÜV NORD Systems GmbH & Co. KG

ar nt o c Ac

en d a e Te s t rd

Volu rd

y i In yg in d o o r A i r H tan gt o T ÜV N OR D S

Suitable for Allergic People House dust and indoor allergen retention Test object: Air purifier and humidifier SEGB-2540/08

Daikin has already received great praise for its air purifiers: a UK allergy certificate and the Daikin TüV award confirm the efficiency of our units.

MC707VM- W/S MODEL Power supply Dimensions Colour Weight Mode (50Hz) Power input Sound pressure level Sound power level Air flow rate Dust collecting method Deodorising

Bacteria filtering method Filter

MC707VM-W/S 1~/ 220-240/220-230V/ 50/60Hz 533x425x213 (W) = White + Sparkling silver or (S) = Sparkling silver + Metallic ocean blue 8.7

Height x Width x Depth mm kg

kW dBA dBA m3/h Method Deodorising performance (%) Regenerate method Dust Form collection and Function deodorisation Lifetime Bio-Antibody filter Pre-filter

Turbo 0.055 47 62 420

H M L 0.023 0.014 0.010 38 31 24 52 40 39 285 180 120 Plasma ionizer (electrostatic dust collection) + Electrostatic dust collection filter Flash Streamer + Titanium apatite photocatalytic filter + Deodorising catalyst 95 The Flash Streamer activates the photocatalytic reaction Bio-Antibody filter + Flash Streamer + Titanium apatite photocatalytic filter Pleated filter Deodorisation + disinfection + dust collection + adjuvant removal 1 filter/1 year New Catechin pre-filter

18

Silent 0.008 16 31 60

MC707VM-W

MC707VM-S

Pre-filter (with catechin) Removes large dust particles and pet hairs.

Bio-antibody filter Airborne viruses are captured and removed.

Plasma ionizer Dust and pollen are positively charged and sent to the electrostatic filter.

Dirty air

Flash Streamer unit Flash Streamer Electrostatic dust collection filter Deodorising catalyst Positively charged dust and High-speed electrons are Odours are adsorbed pollen are adsorbed by the generated by the Flash and broken down negatively charged filter. Streamer. These electrons before the air is returned powerfully break down odours into the room. Front and formaldehyde.

Purified air Back Titanium Apatite Photocatalytic Filter Odour, bacteria and viruses are adsorbed and decomposed.

19

People are becoming more and more aware of the cost of heating. Traditional heating systems and boilers use fossil fuels, making them an expensive and not sustainable option for the environment. Nobody wants to waste their money. Since approximately two thirds of the heat generated by the Daikin heat pump systems, is free of charge, the perfect solution is just around the corner. Moreover, since heat pumps consume less energy than traditional heating systems, they also generate less CO 2 emissions. Air to water and air to air heat pumps use energy from renewable sources: the ambient air. These energy sources are renewable and inexhaustible. Of course, heat pumps also need energy to function (mostly electricity), but increasingly this electricity can also be generated from renewable energy sources (solar energy, wind energy, hydropower, biomass) It is no surprise that people throughout Europe are becoming aware of new heating technology. In less than a decade practically all properly insulated buildings from Italy to Norway will be heated with heat pumps. Millions of heat pumps have already been installed in residential and commercial applications. So… why wait? 95% of our air conditioning equipment can heat and/or cool and thus are heat pumps. The products in this chapter are optimised heating solutions as their primary scope and purpose is heating.

OPTIMISED HEATING SOLUTIONS NEW NEW NEW NEW

NEW NEW NEW

AIR TO WATER HEAT PUMPS Daikin Altherma Low Temperature (LT) EKHBH(X)-B ER(L/H)Q-B(V3/W1) E(D/B)(L/H)Q-B(V3/W1) Options Daikin Altherma High Temperature (HT) EKHBRD-A(V1/Y1) ER(R/S)Q-A(V1/Y1) Options Daikin heat pump convector FWXV-A Daikin Altherma High Tempeature Series for apartment buildings EKHVMYD-AAV1 EMRQ-AAY1

22 22 24 24 25 26 28 30 30 31 32 32 33 33 33

AIR TO AIR HEAT PUMPS FTXL-G / RXL-G

34 34

VRV® HEAT PUMPS OPTIMISED FOR HEATING RWEYQ-PR RTSYQ-P

36 36 37

21

DAIKIN ALTHERMA - LOW TEMPERATURE (LT)

HOW DOES THE DAIKIN ALTHERMA AIR TO WATER HEAT PUMP WORK? Daikin Altherma LT Split 1A / OUTDOOR UNIT :

1B / INDOOR UNIT :

AN EFFICIENT USE OF ENERGY FROM THE AIR

THE HEART OF THE DAIKIN ALTHERMA SYSTEM

Daikin Altherma uses a natural source of energy. The outdoor unit extracts heat from the outside air and raises its temperature to a level high enough to supply heating. This heat is then transferred to the indoor unit through refrigerant pipes (thus, the additional advantage is that the pipes can never freeze). The compact outdoor unit is easily installed and, as no drilling or excavation work is required, it can also be installed in flats and apartments.

The indoor unit heats the water that circulates through low temperature radiators, floor heating systems or fan coil units and also provides domestic hot water. If you opt for the combination of heating and cooling, then the indoor unit can also decrease the water temperature to distribute a refreshing coolness.

3 / DOMESTIC HOT WATER TANK : FOR LOW ENERGY CONSUMPTION As for your domestic hot water, Daikin Altherma is just as clever. The unique lay-out and special placement of the system components maximise energy efficiency. The water inside the storage tank is primarily warmed up by thermal energy from the outside air, thanks to a heat exchanger connected to the heat pump. However, an additional electrical heating element in the domestic water tank

5 / Solar collector

can take care of extra heat required in the shower, tub or sink. At necessary intervals the water is automatically heated to 70°C to prevent the risk of bacteria growth. With Daikin Altherma you can enjoy delightfully warm and perfectly safe water at all times. Depending on the daily consumption of hot water, Daikin Altherma domestic hot water tanks are available in different sizes.

Solar pump station

Fan coil unit (field supply) Low temperature radiator (field supply)

4 / Solar kit

1A / Outdoor unit

3 / Domestic hot water tank

1B / Indoor unit

22

Under floor heating system

Daikin Altherma LT Monobloc 2 / MONOBLOC OUTDOOR UNIT: ALL IN ONE In addition to Daikin Altherma outdoor and indoor unit systems, Daikin has introduced a monobloc version in which all hydraulic parts are located within the outdoor unit.

In this new system the water pipes, rather than refrigerant lines, run indoors from the outdoor unit, making installation much quicker and easier for the installer.

4 / SOLAR KIT  optional

6 / ROOM THERMOSTAT  optional

The solar kit provides the transfer of solar heat to the Daikin Altherma hot water tank via an external heat exchanger. In contrast to tanks with two heat exchangers, this system allows the entire content of the tank to be efficiently heated with solar heat and, if necessary, with heat pump energy.

With the wired or wireless room thermostat, the ideal temperature can be easily, quickly and conveniently regulated. An external sensor (EKRTETS) can be placed between the under floor heating and the floor, as an option to the wireless room thermostat. It allows for more precise measurement and can regulate the comfort level of your customer even more optimally and energy efficiently. *EKRTW for wired wall-mounting and EKRTR for the wireless type.

5 / SOLAR COLLECTOR  optional The high-efficiency collectors transfer all the short-wave solar radiation into heat as a result of their highly selective coating. The collectors can be mounted on the roof tiles.

5 / Solar collector

6 / Room thermostat

3 / Domestic hot water tank

2 / Monobloc outdoor unit 23

DAIKIN ALTHERMA - LOW TEMPERATURE (LT) TECHNICAL DATA  SPLIT ECOLABEL Daikin is the first manufacturer to receive the Eco-label for heat pumps! Daikin Altherma LT with under floor heating received the EU ECO-LABEL* because of its higher energy efficiency and less global warming impact than other heat pump products in its class.

B/31/1

NEW

* Following models received the ECO-LABEL: ERHQ006B-EKHBH008B, ERHQ007B-EKHBH008B, ERHQ008B-EKHBH008B, ERHQ011B-EKHBH016B, ERHQ014B-EKHBH016B, ERHQ016B-EKHBH016B, ERHQ006B-EKHBX008B, ERHQ007B-EKHBX008B, ERHQ008B-EKHBX008B, ERHQ011B-EKHBX016B, ERHQ014B-EKHBX016B, ERHQ016B-EKHBX016B.

INDOOR UNIT EKHBH008B*** Function Dimensions Colour Material Weight Leaving water temperature range

HxWxD

mm

Heating Cooling

kg °C °C

NEW

/ / / / / /

EKHBH016B***

Reversible 922x502x361

48 15~55

-

5~22

EKHBH(X)016B3V3 EKHBH(X)016B6V3 EKHBH(X)016B6WN EKHBH(X)016B6T1 EKHBH(X)016B9WN EKHBH(X)016B9T1

EKHBX016B***

Reversible Heating only 922x502x361 922x502x361 Pure white (RAL 9010) Epoxy polyester painted galvanised steel 46 15~50

FACTORY MOUNTED HEATER EKHBH(X)008B3V3 EKHBH(X)008B6V3 EKHBH(X)008B6WN EKHBH(X)008B6T1 EKHBH(X)008B9WN EKHBH(X)008B9T1

EKHBX008B***

Heating only 922x502x361

-

5~22

kW

Capacity steps

Power supply

3 6 6 6 9 9

1 2 2 2 2 2

1~/230V/50Hz 1~/230VV/50Hz 3~/400VV/50Hz 3~/230VV/50Hz 3~/400VV/50Hz 3~/230VV/50Hz

OUTDOOR UNIT With bottom plate heater

ERLQ006BV3

ERLQ007BV3

ERLQ008BV3

Without bottom plate heater Dimensions HxWxD Heating Nominal capacity Cooling Heating Nominal power input Cooling COP EER Heating Operation range Cooling Domestic water Heating Sound power level Cooling Heating Sound pressure level Cooling Weight Refrigerant charge R-410A Power supply Recommended fuses

ERHQ006BV3

ERHQ007BV3

ERHQ008BV3

mm kW kW kW kW

735x825x300 6.84 8.16 1.58 2.78 4.34 2.94 -20~25 10~43 -20~43

5.75 7.20 1.26 2.27 4.56 3.17

°CDB °CDB °CDB dBA dBA dBA dBA kg kg

8.43 8.37 2.08 2.97 4.05 2.82

61

62 63

48 48

49 50 56 1.7 1~/230V/50Hz 20

A

Measuring conditions: Heating Ta DB/WB 7°C/6°C - LWC 35°C (DT=5°C) - Cooling Ta 35°C - LWE18°C (DT=5°C)

(Single phase)

(Three phase)

With bottom plate heater

ERLQ011BV3

ERLQ014BV3

ERLQ016BV3

ERLQ011BW1

ERLQ014BW1

ERLQ016BW1

Without bottom plate heater Dimensions HxWxD Heating Nominal capacity Cooling Heating Nominal power input Cooling COP EER Heating Operation range Cooling Domestic hot water Heating Sound power level Cooling Heating Sound pressure level Cooling Sound pressure level - Heating night quiet Cooling Weight Refrigerant charge R-410A Power supply Recommended fuses

ERHQ011BV3

ERHQ014BV3

ERHQ016BV3

ERHQ011BW1

ERHQ014BW1

ERHQ016BW1

16.0 17.8 3.83 6.77 4.18 2.63

11.32 15.05 2.54 4.44 4.46 3.39

mm kW kW kW kW

°CDB °CDB °CDB dBA dBA dBA dBA dBA dBA kg kg

1,170x900x320 14.0 17.3 3.17 5.78 4.42 2.99 -20~35 10~46 -20~43

11.2 13.9 2.46 3.79 4.55 3.67

64 64 49 50

66 51 52 42 45

66 69 53 54 43 46

103 3.7 1~/230V/50Hz 32

A

Measuring conditions: Heating Ta DB/WB 7°C/6°C - LWC 35°C (DT=5°C) - Cooling Ta 35°C - LWE18°C (DT=5°C) * 108 kg for ERHQ011-016BW1 / 110 kg for ERLQ011-016BW1

24

1,345x900x320 14.50 16.06 3.33 5.33 4.35 3.01 -20~35 10~46 -20~43 64

64

66 51

50

52 42 45 108 / 110* 2.95 3N~/400V/50Hz 20

16.05 16.76 3.73 6.06 4.30 2.76

66 69 52 54 43 46

TECHNICAL DATA  MONOBLOC

NEW

OUTDOOR UNIT HEATING ONLY SINGLE PHASE

REVERSIBLE

With bottom plate heater

EDLQ011B6V3

EDLQ014B6V3

EDLQ016B6V3

EBLQ011B6V3

EBLQ014B6V3

EBLQ016B6V3

Without bottom plate heater

EDHQ011B6V3

EDHQ014B6V3

EDHQ016B6V3

EBHQ011B6V3

EBHQ014B6V3

EBHQ016B6V3

16.00 3.79 4.22 -

11.20 12.85 2.47 3.78 4.54 3.39

Dimensions

HxWxD Heating Cooling Heating Nominal power input Cooling COP EER Heating Operation range Cooling Domestic water Heating Sound power level Cooling Heating Sound pressure level Cooling Weight Refrigerant charge R-410A Power supply Recommended fuses Nominal capacity

mm kW kW kW kW

°CDB °CDB °CDB dBA dBA dBA dBA kg kg

1,418x1,435x382 14.00 3.20 4.37 -15~35 (1) -15~43

11.20 2.47 4.54 64

1,418x1,435x382 14.00 15.99 3.20 5.65 4.37 2.83 -15~35 (1) 10~46 -15~43

66

64 65

51 -

180 2.95 1~/230V/50Hz 32

A

52 -

66 51

50

52 180 2.95 1~/230V/50Hz 32

16.00 16.73 3.79 6.28 4.22 2.66

66 69 52 54

Measuring conditions: Heating Ta DB/WB 7°C/6°C - LWC 35°C (DT=5°C) - Cooling Ta 35°C - LWE18°C (DT=5°C) (1) E(D/B)L* models can reach -20°C / E(D/B)L*6W1 models can reach -25°C but without capacity guarantee HEATING ONLY THREE PHASE Dimensions

EDLQ011B6W1

EDLQ014B6W1

EDLQ016B6W1

EBLQ011B6W1

EBLQ014B6W1

EBLQ016B6W1

Without bottom plate heater

EDHQ011B6W1

EDHQ014B6W1

EDHQ016B6W1

EBHQ011B6W1

EBHQ014B6W1

EBHQ016B6W1

11.20 2.51

1,418x1,435x382 14.00 3.22

16.00 3.72

11.20 12.85 2.51 3.78 4.46 3.39

HxWxD Heating Cooling Heating Nominal power input Cooling COP EER Heating Operation range Cooling Domestic water Heating Sound power level Cooling Heating Sound pressure level Cooling Weight Refrigerant charge R-410A Power supply Recommended fuses Nominal capacity

REVERSIBLE

With bottom plate heater mm kW kW kW kW

4.46 °CDB °CDB °CDB dBA dBA dBA dBA kg kg

49 -

A

4.35 -15~35 (1) -15~43 (1) -

4.30 -

51 180 2.95 3N~/400V/50Hz 20

53 -

-

Measuring conditions: Heating Ta DB/WB 7°C/6°C - LWC 35°C (DT=5°C) - Cooling Ta 35°C - LWE18°C (DT=5°C) (1) E(D/B)L* models can reach -20°C / E(D/B)L*6W1 models can reach -25°C but without capacity guarantee

25

64 65 49 50

1,418x1,435x382 14.00 15.99 3.22 5.32 4.35 3.01 -15~35 (1) 10~46 -15~43 (1) 64 66 51 52 180 2.95 3N~/400V/50Hz 20

16.00 16.73 3.72 6.06 4.30 2.76

66 69 53 54

DAIKIN ALTHERMA - LOW TEMPERATURE (LT) TECHNICAL DATA  OPTIONS DOMESTIC HOT WATER TANK Water volume Max.water temperature Height Diameter Booster heater Power supply Material inside tank Material outside casing Colour Empty weight

l °C mm mm kW

EKHWS150B3V3

EKHWS200B3V3

EKHWS300B3V3

EKHWS200B3Z2

EKHWS300B3Z2

150

200

200

300

900

1,150

300 85 1,600 580 3

1,150

1,600

1~/230V/50Hz

kg

37

45

2~/400V/50Hz Stainless steel (DIN 1.4521) Epoxy-coated mild steel Neutral white 59

45

59

EKHWE150A3V3 EKHWE200A3V3 EKHWE300A3V3 EKHWE200A3Z2 EKHWE300A3Z2 EKHWET150A3V3 Mounting Water volume Max.water temperature Height Diameter Booster heater Power supply Material inside tank Material outside casing Colour Empty weight

l °C mm mm kW

kg

150

200

1,205

1,580 545

Floor 300 75 1,572 660 3

200

300

1,580 545

1,572 660

1~/230V/50Hz 2~/400V/50Hz Enamel coated steel acc. DIN4753TL2 Epoxy coated steel Neutral white (RAL 9010) 104 140 104 140

80

Wall 150 75 1,205 545 3 1~/230V/50Hz Enamel coated steel acc. DIN4753TL2 Epoxy coated steel Neutral white (RAL 9010) 82

SOLAR KIT EKSOLHWAV1 Dimensions

HxWxD Pressure drop Max.inlet temp Heat exchanger Heat exchange capacity Max. Ambient temperature Min. Weight Sound pressure level Power supply Power supply intake

mm kPA °C W/K °C °C kg dBA

770x305x270 21.5 110 1,400 35 1 8 27 1~/220-240V/50Hz Indoor unit

ROOM THERMOSTAT

EKRTW

EKRTW

EKRTW thermostat - receiver (wireless)

NEW

Dimensions Temperature setpoint range Clock Regualtion function

HxWxD Heating Cooling

mm °C °C

87x125x34 4~37 4~37 yes proportional band

EKRTR Thermostat

Receiver

Temperature sensor EKRTETS (option)

87x125x34 4~37 4~37 yes proportional band

170x50x28 -

3m wire length -

PUMP STATION EKSRDS1A with controller EKSR3PA Mounting method Dimensions Height x Width x Depth mm Power supply Control Solar panel temperature sensor Storage tank sensor Return flow sensor Feed temperature and flow sensor (option)

On wall 332x230x145 230V / 50 Hz Digital temperature difference controller with plain text Pt1000 PTC PTC Voltage signal (3,5V DC)

26

NEW

SOLAR COLLECTOR Position Dimensions HxWxD Outer surface Absorber surface Weight Water content Absorber Coating Glazing Heat insulation Max. pressure drop at 100l/h Allowed roof angle Max. standstill temperature Max. operating pressure

mm m² m² kg l

mbar °C bar

EKSV26P

EKSH26P

Vertical 2,000x1,300x85

Horizontal 1,300x2,000x85 2.60 2.36 42

1.7 2.1 harp-shaped copper pipe register with laser-welded highly selective coated aluminum plate micro-therm (absorption max. 96%, emission ca. 5% +/- 2%) Single pane safety glass, transmission +/- 92% mineral wool, 50mm 3 0.5 15° to 80° 200 6

The collectors are standstill resistant over a long period and are tested for thermal shock. Minimum collector yield over 525kWh/m² at 40% covering proportion, location Würzburg, Germany.

27

DAIKIN ALTHERMA - HIGH TEMPERATURE (HT)

1  AIR TO WATER HEAT PUMP A / OUTDOOR UNIT: AN EFFICIENT USE OF ENERGY FROM THE AIR The outdoor unit extracts heat from the ambient outdoor air. This heat is transferred to the indoor unit via refrigerant piping. B / INDOOR UNIT: THE HEART OF THE DAIKIN ALTHERMA SYSTEM The indoor unit receives the heat from the outdoor unit and further increases the temperature, allowing water temperatures up to 80°C for heating through radiators (field supply) and for domestic hot water use. Daikin’s unique cascade compressor approach to the heat pumps (one in the outdoor unit/one in the indoor unit) means optimum comfort at even the coldest outdoor temperatures, without the need for an electric back up heater.

2  DOMESTIC HOT WATER TANK: FOR LOW ENERGY CONSUMPTION Daikin Altherma’s high water temperature is ideal for heating domestic hot water without the need for an additional electric heater. Rapid heating of domestic hot water also means smaller boilers are needed. For a family of approximately 4 people, the standard tank (EKHTS200A) is the best solution. Should you require more hot water, a larger tank is also available.

28

HEATING AND DOMESTIC HOT WATER WITH SOLAR ENERGY The Daikin Altherma high temperature heating system can optionally use solar energy for hot water production. If the solar energy is not required immediately, the purpose-built hot water tank (EKHWP) can store large quantities of heated water for up to a day for later use as domestic hot water or for heating. Solar collector

Indoor unit and Domestic hot water tank

3  USER INTERFACE With Daikin Altherma’s user interface, the ideal temperature can be easily, quickly and conveniently regulated. It allows for more precise measurement and can regulate your comfort even more optimally and energy efficiently.

29

DAIKIN ALTHERMA - HIGH TEMPERATURE (HT) TECHNICAL DATA  SPLIT INDOOR UNIT SINGLE PHASE EKHBRD011AV1 Function Dimensions HxWxD Leaving water temperature range Heating Material Colour Sound pressure level 1 Sound pressure level 2 Weight Type Refrigerant Charge Power supply Recommended fuses

Heating only 705x600x695 25~80 Precoated sheet metal Metallic grey 45 46 144.25 R-134a 3.2 1~/220-240V/50Hz 25

mm °C

dBA dBA kg

EKHBRD014AV1

43

kg A

THREE PHASE EKHBRD016AV1

46

EKHBRD011AY1

43

EKHBRD014AY1 Heating only 705x600x695 25~80 Precoated sheet metal Metallic grey 45 46 147.25 R-134a 3.2 3~/380-415V/50Hz 16

EKHBRD016AY1

46

1

Measuring conditions: Entering Water: 55°C, Leaving Water: 65°C; 1m in front of unit; integrated design (+ tank) 2 Measuring conditions: Entering Water: 70°C, Leaving Water: 80°C; 1m in front of unit; integrated design (+ tank)

OUTDOOR UNIT SINGLE PHASE

THREE PHASE

WITH BOTTOM PLATE HEATER3

ERRQ011AV1

ERRQ014AV1

ERRQ016AV1

ERRQ011AY1

ERRQ014AY1

ERRQ016AY1

WITHOUT BOTTOM PLATE HEATER3

ERSQ011AV1

ERSQ014AV1

ERSQ016AV1

ERSQ011AY1

ERSQ014AY1

ERSQ016AY1

Dimensions Nominal capacity Nominal power input 1 COP 1 Nominal power input 2 COP 2 Operation range Sound power level Sound pressure level Weight Refrigerant charge Power supply Recommended fuses

HxWxD Heating Heating

mm kW kW

Heating

kW

Heating Domestic water Heating Heating

°C °C dBA dBA kg kg

R-410A

1,345x900x320 14 4.66 3.00 5.65 2.48 -20~20 -20~35 69 53 120 4.5 1~/230V/50Hz 25

11 3.57 3.08 4.40 2.50

68 52

A

1

16 5.57 2.88 6.65 2.41

11 3.57 3.08 4.40 2.50

71 55

68 52

Measuring conditions: Entering Water: 55°C, Leaving Water: 65°C, T = 10°C; ambient conditions: 7°CDB/6°CWB 2 Measering conditions: Entering Water: 70°C, Leaving Water: 80°C, T = 10°C; ambient conditions: 7°CDB/6°CWB 3 Bottom plate heater = anti freeze protection for cold climates

30

1,345x900x320 14 4.66 3.00 5.65 2.48 -20~20 -20~35 69 53 120 4.5 3~/400V/50Hz 16

16 5.57 2.88 6.65 2.41

71 55

TECHNICAL DATA  OPTIONS NEW

DOMESTIC HOT WATER TANK EKHTS200A Water volume Max. water temperature Dimensions Dimensions - integrated on indoor unit Material outside casing Colour Empty weight Tank Domestic hot water heat exchanger

NEW

HxWxD HxWxD

l °C mm mm

EKHTS260A

200

260 75

1,335x600x695 2,010x600x695

1,610x600x695 2,285x600x695 Precoated sheet metal Metallic grey

kg Material Material Volume l Heat exchanger surface m²

70

78 Stainless steel (DIN 1.4521) Duplex steel LDX 2101 7.5 1.56

DOMESTIC HOT WATER TANK WITH SOLAR CONNECTION EKHWP300A Mounting method Casing colour Casing material Water volume Maximum water temperature Dimensions HxWxD Empty weight Material Volume Domestic hot water heat Maximum operation pressure exchanger Heat exchanger surface Average specific thermal output Material Volume Charging exchanger Heat exchanger surface Average specific thermal output Material Volume Auxiallary solar heating exchanger Heat exchanger surface Average specific thermal output

NEW

EKHWP500A Floor standing Dusty grey - RAL 7037 Impact resistant polypropylene

l °C mm kg

300

500 85

1,590x595x615 67

1,590x790x790 100 Stainless steel 1.4404

l bar m² W/K

5.7 2,795

l m² W/K

12.3 2.5 1,235

l m² W/K

-

27.8

28.4 6 5.9 2,860 Stainless steel 1.4404 17.4 3.7 1,809 Stainless steel 1.4404 5 1.0 313

PUMP STATION EKSRPS3 Mounting method Dimensions HxWxD Power supply Max. electric power consumption Control Solar panel temperature sensor Storage tank sensor Feed temperature and flow sensor (option)

NEW

On side of tank 815x230x142 230V / 50 Hz 245 Digital temperature difference controller with plain text Pt1000 PTC Voltage signal (3,5V DC)

mm W

SOLAR COLLECTOR Position Dimensions HxWxD Outer surface Absorber surface Weight Water content Absorber Coating Glazing Heat insulation Max. pressure drop at 100l/h Allowed roof angle Max. standstill temperature Max. operating pressure

mm m² m² kg l

mbar °C bar

EKSV26P

EKSH26P

Vertical 2,000x1,300x85

Horizontal 1,300x2,000x85 2.60 2.36 42

1.7 2.1 harp-shaped copper pipe register with laser-welded highly selective coated aluminum plate micro-therm (absorption max. 96%, emission ca. 5% +/- 2%) Single pane safety glass, transmission +/- 92% mineral wool, 50mm 3 0.5 15° to 80° 200 6

The collectors are standstill resistant over a long period and are tested for thermal shock. Minimum collector yield over 525kWh/m² at 40% covering proportion, location Würzburg, Germany.

31

NE

W DAIKIN

HEAT PUMP CONVECTOR FOR LOW TEMPERATURE APPLICATIONS

Daikin’s heat pump convector with interlink function addresses a common heating efficiency problem. In well-insulated new residences, a combination of under floor heating and low temperature radiators is one of the most efficient heating solutions on the market. This solution, however, is not perfect. The low leaving water temperatures important for efficiency are adequate for under floor heating, but the room radiators (in e.g. bedrooms) then need to be oversized in order to emit the proper levels of heat at these low water temperatures. To address this issue, a heat pump convector solution with an interlink function is introduced. The heat pump convector is able to emit the required levels of heat at low leaving water temperatures, while retaining a modest size. Instead of the leaving water circuit being switched on and off via a thermostat in a single master room, each convector can be directly wired to the Daikin Altherma indoor unit, the system’s intelligence centre. This allows all rooms to have heat when required, regardless of the state of the other rooms.

HEATING & COOLING INDOOR UNITS Capacity Dimensions Weight Air flow rate Sound pressure Refrigerant Power supply Piping connections

Heating Cooling Cooling HxWxD

45°C1 7°C2 18°C3

H/M/L

kW kW kW mm kg m³/h dBA

FWXV15AVEB*

FWXV20AVEB*

1.5 1.2 0.3

2.0 1.7 0.4 600x700x210 14

3.8 26/19/