109 IAG/IUG/IEG/CEG/LEG Series - Rocker http://airpax.sensata.com/ IAG/IUG/IEG/CEG/LEG Series - Rocker 110 ROCkER CIRCUIT PROTECTORS IAG/IUG/IEG/CEG/LEG
IAG/IUG/IEG/CEG/LEG
IAG/IUG/IEG/CEG/LEG Magnetic Circuit Protectors
Introduction
|
105
Single & Multi-Pole
|
106
Rocker, Sealed Toggle
|
109
Configurations
|
114
Operating Characteristics
|
116
Delay Curves
|
117
Specifications
|
121
Decision Tables
|
123
IAG/IUG/IEG/CEG/LEG
IAG/IUG/IEG/CEG/LEG Series Hydraulic Magnetic Circuit Protectors
SINGLE POLE CIRCUIT PROTECTOR
1.687 [42.85]
.240 [6.10] ON 32º 32º OFF
INTRODUCTION The Airpax™ IAG/IUG/IEG/CEG/LEG magnetic circuit protectors provide low-cost power switching, reliable circuit protection and accurate circuit control for equipment in the international marketplace.
.690 [17.53]
2.075 [52.71] MAX.
equipment, vending and amusement machines, military applications and wherever precision operation is required. Temperature differences which affect fuses and other thermal devices are not a concern.
Single Pole Mounting Detail +.010 -.000
.590 [15.00] MAX.
.625 +.25 -.00
2X 6 – 32 THREAD .140 [3.56] DEEP M3 ISO THD. OPTIONAL
15.88
IEG models meet IEC spacing requirements which is mandatory for equipment that must comply with IEC specifications 601 and 950 and VDE specifications 0804 and 0805. In addition, they are UL Recognized as supplementary protectors per UL STD. 1077, CSA Certified as supplementary protectors per CSA C22.2–No. 235, VDE Approved to VDE 0642 (EN60934), CCC Approved and CE Compliant. IAG models are for those applications where the unit’s inherent attributes are desired, but compliance with the various standards is not required. Designed using the latest in sensitive hydraulic magnetic technology, the IAG/IUG/IEG/CEG/LEG line adapts itself to many applications and environments. They’re ideal for data processing and business machines, medical instrumentation, broadcast
One important feature of this protector line is a “trip free” action, which means the circuit will trip in the presence of an overload even though the handle is held in the ON position. The delay mechanism senses the fault and the contacts open. The IAG/IUG/IEG/CEG/LEG is available in a wide variety of configurations including series, series with auxiliary switch, shunt and relay with a choice of delays and ratings in either DC, 50/60Hz or 400Hz versions. Handles come in seven different colors and international markings are standard. Single or multipole versions are available, with a variety of pole arrangements to meet your specifications. Four pole models require a double toggle handle. Units with a handle per pole come in one through six pole assemblies.
1.660 [42.16]
2X
1.050 [26.67]
O N
2.000 [50.80]
O F F
1.220 [31.00]
0.156 [3.96]
.1.660 [42.16]
.750 [19.05]
.168 [4.27]
LEG Type Units Require Screw Terminals
.230 [5.84]
1.530 [38.86]
Note: Tolerance ±.015 [.38] unless noted. Dimensions in brackets [ ] are millimeters.
105
IAG/IUG/IEG/CEG/LEG Series - Introduction
http://airpax.sensata.com/
http://airpax.sensata.com/
IAG/IUG/IEG/CEG/LEG Series - Single Pole
106
MULTI-POLE CIRCUIT PROTECTORS (IAGH/IUGH/IEGH/CEGH/LEGH)
Two Pole Protectors An assembly consisting of two single pole units, having their trip mechanisms internally coupled and with a single toggle handle, forms the IEG11 with quick-connect D.I.N.-style terminals. Individual poles may differ in ratings, delays and internal connections. An auxiliary switch may be included in either or both poles, allowing you to mix SELV and hazardous voltages. Rugged screw-type terminals can be provided, in which case the designation would be IEG66. The IEGH offers a toggle handle for each pole. LEG type units are avavailable only in one or two pole configurations.
The IAGH/IUGH/IEGH/CEGH/LEGH two, three and four pole models are available with a handle per pole.
all units simultaneously. A single toggle handle operates all three poles for quick and convenient control, or if preferred, a handle per pole is available. The four pole construction consists of four single pole units assembled with an internal mechanical interlock which actuates all units simultaneously. A double toggle handle operates all four poles. The individual poles need not have identical characteristics and any series trip pole may have an auxiliary switch. If screw-type terminals are required, the breaker designation will be IEG666 for a three pole version and IEG6666 for a four pole version.
Three Pole and Four Pole Protectors The three pole construction consists of three single pole units assembled with an internal mechanical interlock which actuates
LEGH type units are available only in two pole models. IAGH/IUGH/IEGH/CEGH/LEGH Protectors 1.687 [42.85]
Two Pole*
.240 [6.10]
32º OFF
.690 [17.53]
LEG Type Units Require Screw Terminals O F F
O N
O N
O F F
O N
O F F
O N
O F F
[5.84]
O N
O F F
O N
O F F
O N
O F F
O N
O F F
O N
O F F
O N
O F F
O N
O F F
O N
O F F
O N
O F F
O N
O F F
O N
O F F
O N
O F F
O N
O F F
O N
O F F
O N
O F F
O N
O F F
O N
O F F
O N
O F F
1.515 [38.48] 1.515 [38.48]
.168 [4.27]
MAX. MAX.
2.265 [57.53] MAX. 2.265 [57.53] MAX.
3.015 [76.58] MAX. 3.015 [76.58] MAX.
2X 2X
+.010 -.000
.625
Three Pole*
Two Pole
Four Pole*
+.25 +.010 -.00 -.000 15.87
.625 +.25
-.001.660 15.87[42.16]
OFF
1.515 [38.48] MAX.
.690 [17.53]
3.015 [76.58] MAX.
2.265 [57.53] MAX.
Two Pole*
.230 [5.84]
2X
Three Pole*
Four Pole*
+.010
.625 -.000 [15.88+.25 -.00 [
.156 [3.96]
.750 [19.05]
.750 .750 [19.05] [19.05]
.750 [19.05]
.750 .750 [19.05] [19.05]
LEG/LEGH Barriers (required) In order to meet UL listing requirements, the LEG/LEGH two pole model requires barriers. Available with a standard straight barrier or an optional “Z” type barrier. Standard Barrier
1.660 [42.17]
4X
1.530 [38.86]
1.050 1.660 [26.67] [42.16] 1.050 [26.67] 4X .156 [3.96] 4X
(Optional: Handle may be located in Pole 1 instead of Pole 2)
LEG Type Units Require Screw Terminals
1.530 [38.86]
1.660 [42.16]
1.220 2.000 [31.00] 1.660 [50.80] [42.16] 1.220 [31.00] .168 [4.27]
.230
32º
2.075 [52.71] MAX.
2.000 [50.80]
NOTE: We recommend machining slots into your panel for 2 or more poles. This eliminates the need to dissemble/reassemble the handle ties to be able to insert the handles thru indvidiually drilled holes. LEG type units are only available in one or two poles.
Four Pole*
Three Pole*
ON 32º
2X
4X 6 – 32 THREAD .140 [3.56] DEEP M3 ISO THD. OPTIONAL 4X 6 – 32 THREAD .140 [3.56] DEEP M3 ISO THD. OPTIONAL
Panel Mounting Detail: Tolerance for Mtg. ±.005 [.13] unless noted.
IAG/IUG/IEG /CEG/LEG 1.687 [42.85]
.240 [6.10]
.590 [15.00] MAX. .590 [15.00] MAX.
32º
Protector poles are numbered consecutively when viewed from the terminal side, with the ON position up, starting with Pole #1 on the left side and proceeding to the right.
IAG/IUG/IEG/CEG/LEG Multi-Pole Circuit Breakers
2X
ON
2.075 [52.70] MAX.
.750 .750 .750 [19.05] [19.05] [19.05] .750 .750 .750 [19.05] [19.05] [19.05]
*See Two Pole Mounting Detail for hole sizes and locations.
Optional “Z” Barrier
1.050 [26.68]
.156 [3.96]
.750 [19.05]
Panel Mounting Detail: Tolerance for Mtg. ±.005 [.13] unless noted. *See Single Pole Mounting Detail for hole sizes and locations. LEG type units are only available in one or two poles.
107
IAG/IUG/IEG/CEG/LEG
MULTI-POLE CIRCUIT PROTECTORS (IAG/IUG/IEG/CEG/LEG)
IAG/IUG/IEG/CEG/LEG Series - Multi-Pole
.750 .750 [19.05] [19.05]
.750 .750 .750 [19.05] [19.05] [19.05]
Note: Tolerance ± .015 [.38] unless noted. Dimensions in brackets [ ] are millimeters. Note: Tolerance ± .015 [.38] unless noted. Dimensions in brackets [ ] are millimeters.
http://airpax.sensata.com/
http://airpax.sensata.com/
IAG/IUG/IEG/CEG/LEG Series - Multi-Pole
108
IAG/IUG/IEG/CEG/LEG
Rocker CIRCUIT Protectors (IAGX/IAGZX/IUGX/IUGZX/IEGX/IEGZX/CEGX/CEGZX/LEGZX)
Rocker CIRCUIT Protectors (IAGBX/IUGBX/IEGBX/CEGBX/LEGBX)
The IAGX/IUGX/IEGX/CEGX and IAGZX/IUGZX/IEGZX/CEGZX/ LEGZX styles offer two attractive rocker actuator versions of our popular IAG/IUG/IEG/CEG/LEG family. Designed with the operator in mind, each features handles with a concave surface and aesthetic appearance for front panel applications.
The IAGZX/IUGZX/IEGZX/CEGZX/LEGZX style adds our “EZ” options of contrasting dual color rocker actuators, affording a clear visual indication of the handle position and integrated handle guards, to help prevent accidental turn-on and turn-off of the unit. Available with a black rocker and white, red or green indicator color for either ON or OFF indication.
Both are available with rocker handle styles in a choice of five single colors: black, red, grey, orange or white.
IAGX/IUGX/IEGX/CEGX
The innovative new design of our IEG BX style circuit breaker features a flat front rocker that not only satisfies your aesthetic needs, it guards against accidental actuation while providing the highest degree of circuit protection and quality. Only Airpax offers this new standard in user interface, providing additional peace of mind that guards alone can’t supply.
Available on a variety of versions with a full range of agency approvals, the new IEG BX style circuit breakers meet or exceed all current performance specifications, including interrupting capacities up to 50,000 amperes. Various guard options offer additional and increasing levels of actuation protection performance. The two shot mold on the flat rocker surface provides a clean, crisp legend that can withstand demanding use.
IAGBX/IUGBX/IEGBX/CEGBX/LEGBX Single Pole 6 – 32 THD. (TYP.) M3 ISO THD. OPTIONAL .750 [19.05]
1.687 [42.85]
Three Pole
Four Pole
1.515 [38.48] MAX.
2.265 [57.53] MAX.
3.015 [76.58] MAX.
(Optional: Handle may be located in Pole 2 instead of Pole 1)
2.206 [56.03]
1.220 [30.99]
2.000 [50.80]
Two Pole
1.972 [50.09]
ON
ON
1.660 [42.16]
OFF
OFF
OFF
OFF
ON
.735
[±.13]
Mounting Detail Single, Two & Three Pole
Four Pole* Panel Mounting Detail: Tolerance for Mtg. ±.005 [.13] unless noted. *See Single Pole Mounting Detail for hole sizes and locations.
1.660 [42.16] 1.260 [32.00]
.200 [5.08]
.750 [19.05]
2.000 [50.80]
1.220 [30.99]
2.470 MAX. [62.74] 1.687 [42.85]
.420 REF. [10.67]
.750 [19.05]
Two Pole*
6 – 32 THD. (TYP.) M3 ISO THD. OPTIONAL
.125 [3.18]
1.515 [38.48]
PUSH TO RESET
.750 [19.05]
Three Pole
2.000 [50.80] 1.530 [38.86]
2.165 [54.98] OPTIONAL HANDLE GUARDS (SEE DETAIL “A”)
.430 [10.92]
Single, Two & Three Pole 2X .156 [3.96]
1.660 [42.16]
OFF
6-32 THD. MOUNTING M3 ISO THD. OPTIONAL
.750 [19.05]
2X ÿ .156 [3.96]
O OFF
1.660 [42.16]
ON OFF
1.660 [42.16]
ON OFF
ON
.750 [19.05]
OF
2.217 [56.31]
Panel Mounting Detail: Tolerance for Mtg. ±.005 [.13] unless noted.
1.239 [31.47]
ON I
ON I
O OFF
1.260 [32.00]
.200 [5.08]
ON
PUSH TO RESET
HANDLE HANDLE POSITION "OFF" POSITION "ON" GUARD WITH NO ACTUATE GUARD WITH NO ACTUATE OFF FEATURE OFF FEATURE (SIXTH DECISION, X) (SIXTH DECISION, X)
1.239 [31.47]
.314 [7.98]
2.265 Max. [57.53]
1.220 [30.99]
ON I
ON I
1.530 [38.86]
IAGZX/IUGZX/IEGZX/CEGZX/LEGZX Single Pole*
HANDLE POSITION "ON" WITH GUARD (SIXTH DECISION, G)
HANDLE (SEE NOTE) POSITION "OFF" WITH GUARD (SIXTH DECISION, G)
.125 [3.18]
1.687 [42.85]
1.510 [38.35]
2X .156 [3.96]
O OFF
ACTUATION ACCESS
.387 REF. [9.84]
±.005
[18.67] (HANDLE WIDTH)
O OFF
OFF
2.378 MAX [60.40]
.490 [12.45] MAX.
2.470 [62.74] MAX.
ON
ON
ON I
ON I
ON I O OFF
SINGLE POLE
HANDLE POSITION "OFF" WITHOUT GUARD
HANDLE POSITION "ON" WITHOUT GUARD
DETAIL "A"
1.660 [42.16]
* LEG type units are only available in one or two poles. OPTIONAL GUARD (SEE DETAIL “A”)
1.260 [32.00]
.200 [5.08]
.750 [19.05]
NOTE: ACCESS IS LIMITED TO A DEVICE SMALLER THAN THE UNDERWRITERS LABORATORY "ARTICULATED PROBE" DEFINED IN UL-489 FIG. 11.1.7.2.1.
Panel Mounting Detail MOUNTING DETAIL TOLERANCE: ±.005 [.13] UNLESS NOTED
Detail “A” Note: Tolerance ± .015 [.38] unless noted. Dimensions in brackets [ ] are millimeters.
109
IAG/IUG/IEG/CEG/LEG Series - Rocker
http://airpax.sensata.com/
http://airpax.sensata.com/
IAG/IUG/IEG/CEG/LEG Series - Rocker
110
IAG/IUG/IEG/CEG/LEG
SEALED TOGGLE CIRCUIT PROTECTORS (IAGN/IUGN)
SNAP-IN CIRCUIT PROTECTORS (IEGS/IEGHS/CEGS/CEGHS/lEGS/LEGHS)
The IAGN/IUGN family is a sealed toggle version of the IAG/ IUG family. The silicone rubber seal around the handle assures panel seal integrity and makes this style a natural for harsh environments.
The Snap-In version of the IEG brings mounting simplification and international spacing together in a package that is aesthetically enhanced. The IEGS securely snaps into a rectangular cut-out, eliminating the need for panel mounting hardware and the associated costs. The face plate of the IEGS is a clean, black matte and it satisfies the increasing demand for front panel components that are designed with ergonomic considerations.
This sealed toggle family is available in one to three poles with ratings of .050 to 50 amperes.
Single Pole
Two Pole
KEYWAY .060 [1.52] – .065 [1.65] WIDE .030 [.76] – .035 [.89] DEEP .750 [19.05]
6 – 32 MTG. SCREW FOR HIGH SHOCK MTG.
.130 [3.30]
LOCKWASHER
ON
.240 [6.09]
2.000 [50.80]
1.220 [30.99]
±3º
32º
1.220 [30.99]
2.000 [50.80]
1/2 – 32 HEX NUT
OFF
2.075 [52.70] MAX.
.656 [16.66]
1.488 [37.80]
.744 [18.90] ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
2.598 [65.99]
.690 [17.53]
.750 [19.05]
Note: A: Flush face plate is optional. See decision tables, sixth decision. B:Tolerance ± .031 [.79] Angles: ±5° unless noted. Dimensions in brackets [ ] are millimeters.
Panel Cutout Detail Panel Thickness: (See Table)
Optional Handle
2.976 [75.59]
2.232 [56.69]
(Optional: Handle may be located in Pole 2 instead of Pole 1)
RUBBER “O” RING .625 [15.88]
1.687 [42.85]
32º
±3º OFF 13º
2.256 [57.30] MAX.
2.265 [57.53] MAX.
ON
13º
The IEGS is UL Recognized, CSA Certified and VDE approved.
IEGHS/CEGHS/LEGHS Circuit Protectors (Note B) (Multi-Pole-IEGH Handles Per Pole) (Omit H for Single Pole)
Three Pole
1.515 [38.48] MAX.
The IEGS is offered in either flush or beveled versions, in 1, 2, 3 or 4 pole packages, and with a handle per pole or per unit.
Mounting Detail Single Pole .156 [3.96]
DIM. “C” (SEE TABLE)
Three Pole*
Two Pole*
.750 [19.05]
.750 [19.05]
.750 [19.05]
DIM. “A” (SEE TABLE)
.127 [3.23]
.515 [13.08] .656 [16.66]
DIMENSIONS “A”, “B”, “C”
Panel Mounting Detail: Tolerance for Mtg. ±.005 [.13] unless noted.
*See Single Pole Mounting Detail for hole sizes and locations.
Note: Tolerance ± .015 [.38] unless noted. Dimensions in brackets [ ] are millimeters.
Number of Poles
Dimension “A”, inches [ mm ]
Dimension “B”, inches [ mm ]
1 pole
.750 [19.05] max
.755 [19.18] min
2 pole
1.515 [38.48] max
1.520 [38.61] min
3 pole
2.265 [57.53] max
2.270 [57.66] min
4 pole
3.015 [76.58] max
3.020 [76.71] min Panel Thickness
111
IAG/IUG/IEG/CEG/LEG Series - Sealed Toggle
DIM. “B” (SEE TABLE)
http://airpax.sensata.com/
http://airpax.sensata.com/
Dimension “C”, inches [ mm ] 2.180 ± .005 [55.37 ± .13]
2.186 ± .011 [55.52 ± .28]
.040 to .059 [1.02 to 1.50]
.060 to .100 [1.52 to 2.54]
IAG/IUG/IEG/CEG/LEG Series - Snap-In
112
1.687 [42.85]
.240 [6.09]
.960 [24.38]
ON
1.700 [43.18]
2.450 [62.23]
3.190 [81.03]
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
32º
2.000 [50.80]
32º
1.220 [30.99]
2.598 [65.99]
OFF
2.075 [52.70] MAX.
.690 [17.53]
DIM. “B” (SEE TABLE)
Panel Cutout Detail Panel Thickness: (See Table)
DIM. “C” (SEE TABLE) DIM. “A” (SEE TABLE)
.130 [3.30]
DIMENSIONS “A”, “B”, “C” Number of Poles
Dimension “A”, inches [ mm ]
Dimension “B”, inches [ mm ]
1 pole
.750 [19.05] max
.780 ± .015 [19.81 ± .381]
2 pole
1.515 [38.48] max
1.540 ± .015 [39.12 ± .381]
3 pole
2.265 [57.53] max
2.290 ± .015 [58.17 ± .381]
4 pole
3.015 [76.58] max
3.040 ± .015 [77.22 ± .381] Panel Thickness
Dimension “C”, inches [ mm ] 2.180 ± .005 [55.37 ± .13]
2.186 ± .011 [55.52 ± .28]
.040 to .059 [1.02 to 1.50]
.060 to .100 [1.52 to 2.54]
Shunt Trip The shunt trip is designed for controlling two separate loads with one assembly. The control is established by providing overload protection for the critical load. When the current through this load becomes excessive and reaches the trip point, the protector will open and remove power from both loads simultaneously. The total current rating of both loads must not exceed the maximum contact rating. Auxiliary Switch (Applies to Series Trip Only) This is furnished as an integral part of a series pole in single or multi-pole assemblies. Isolated electrically from the protector’s circuit, the switch works in unison with the power contacts and provides indication at a remote location of the protector’s on-off status. Auxiliary switch contacts actuate simultaneously with the main protector contacts, and will open regardless of whether the protector contacts are opened manually or electrically. For auxiliary switch ratings below 6Vac or 5Vdc, an auxiliary switch with gold contacts designated as REG is available. Gold contacts are not recommended for load current above 100 milliamps.
Main Terminal TYPES Optional Handle Guard .780 [19.82]
Amp Rating
Push-On
.05 to 30
X
.230
.230 [5.84]
Series Trip The most popular configuration for magnetic protectors is the series trip where the sensing coil and contacts are in series with the load being protected. The handle position conveniently indicates circuit status. In addition to providing conventional overcurrent protection, it’s simultaneously used as an on-off switch.
M4 Screw
X
X
30.1 to 50
[5.84]
1.530 [38.86]
10-32 Screw X
1.530 [38.86]
Series
Optional flat screw terminal
Switch Only
2.52 MAX. [64.00] (See Note A)
.230 [5.84]
1.380 [35.05] Shunt
1.530 [38.86]
Standard Auxiliary Switch
VDE Auxiliary Switch .469 [11.91]
.441 [11.20] 1.059 .764 [26.90][ 19.04]
1.083 [27.51] .848 [21.53]
2.438 MAX. [61.93] (See Note A)
.110 [2.79]
8-32 Screw
IAG/IUG/IEG/CEG/LEG
CONFIGURATIONS
IEGS/CEGS/LEGS Circuit Protectors (Note B) (Add H for multiple handles per unit, IEGHS)
M5 Screw
–IREC4 –IREG4
.187 [4.75]
2.454 MAX. [62.33] (See Note A)
.260 [6.60]
.250 [6.35] –IREC5
X
1.560 [39.62]
Series with Auxiliary Switch C
.734 [18.64]
113
IAG/IUG/IEG/CEG/LEG Series - Snap-In
Note: A: Tolerance ± .015 [.38] unless noted. Dimensions in brackets [ ] are millimeters. B: Bevelled face plate is standard.
http://airpax.sensata.com/
Note: A: Terminal protrusion dimensions are referenced from back mounting panel. B: Main terminals are male push-on type .250 [6.35] wide x 0.31 [.79] thick x .375 [9.53] long or 8-32 x .187 [4.75] screw type. Metric screw terminals are M4 x 5mm (30A). On VDE approved builds with screw terminals, external tooth lockwashers are supplied. On VDE approved builds with push-on terminals a soldered connection is required above 25 amperes.
http://airpax.sensata.com/
NO NC BREAKER IN OFF POSITION
IAG/IUG/IEG/CEG/LEG Series - Configurations
114
2.52 MAX. [64.00] (See Note A)
1.380 [35.05]
Current Ratings (Amps)
1.530 [38.86]
Relay
2.52 MAX. [64.00] (See Note A)
1.380 [35.05]
Dual Coil By combining two electrically independent coils on a common magnetic circuit, it is possible to provide contact opening when either an over-current or trip voltage is applied to the respective coils. One coil will be a current trip coil with standard specifications. The second, or dual coil, can be used to provide a control function permitting contact opening from a remote interlock or other transducer functions. Standard coils are 6, 12, 24, 48, 120 and 240 volts. Tripping is instantaneous and must be removed (usually selfinterrupting) after trip.
Inrush Pulse Tolerance The following table provides a comparison of inrush pulse tolerance with and without the inertial delay feature for each of the 50/60Hz delays. Pulse tolerance is defined as a single pulse of half sine wave peak current amplitude of 8 milliseconds duration that will not trip the circuit breaker. The table at left provides a guide to determine if the inertia delay feature is required. Consult factory for further assistance.
Impedance
.620 [15.75]
.230 [5.84]
1.530 [38.86]
Dual Coil
DC (ohms)
AC, 50/60Hz (ohms)
AC, 400Hz (ohms)
51, 52, 53, 59
61, 62, 63, 69
41, 42, 43, 49
0.200
36.6
34.2
74.2
1.00
1.38
1.47
2.85
2.00
0.31
0.25
0.64
5.00
0.053
0.051
0.100
10.0
0.016
0.013
0.027
20.0
0.006
0.005
0.008
30.0
0.0027
0.0026
0.004
50.0
0.0019
0.0018
—
INRUSH PULSE TOLERANCE Delay
DCR and Impedance based on 100% rated current applied and stabalized for a minimum of one hour. Tolerance .05-2.5 amperes ± 20%: 2.6 -20 amperes ± 25%, 21-50 amperes ± 50%. Consult factory for special values and for coil impedance of delays not shown.
Pulse Tolerance
61, 62, 63, 71, 72, 73
10 times rated current (approx)
61F, 62F, 63F, 71F, 72F, 73F
12 times rated current (approx)
64, 65, 66
25 times rated current (approx)
Percentage of Rated Current vs Trip Time in Seconds at +25°C (Vertical Mount) .230 [5.84]
2.52 MAX. [64.00] (See Note A)
.620 [15.75] 1.380 [35.05]
Voltage Trip Sometimes called “dump circuits” or “panic trip circuits,” these units make it possible to open main power contacts with lower power inputs from one or more sources. This configuration is becoming increasingly more important for sensitive circuitry and denser packaging in automation systems. Available in series, shunt or relay configurations.
OPERATING CHARACTERISTICS
TYPICAL RESISTANCE / IMPEDANCE .230 [5.84]
IAG/IUG/IEG/CEG/LEG
Relay Trip This permits the overload sensing coil to be placed in a circuit which is electrically isolated from the trip contacts. The coil may be actuated by sensors monitoring pressure, flow, temperature, speed, etc. Other typical applications include crowbar, interlock and emergency /rapid shutdown circuitry. Trip may be accomplished by voltage or current, which must be removed after trip.
1.530 [38.86]
Dual Coil
Optional Barriers (IEG Only) .571 [14.50]
2.000 [50.80]
Note: Tolerance ± .015 [.38] unless noted. Dimensions in brackets [ ] are millimeters.
Delay
100%
125%
150%
200%
400%
600%
800%
1000%
41
No Trip
May Trip
.500 to 8.0
.150 to 1.9
.020 to .40
.006 to .25
.004 to .1
.004 to .05
42
No Trip
May Trip
5 to 70
2.2 to 25
.40 to 5.0
.012 to 2
.006 to .2
.006 to .15
43
No Trip
May Trip
35 to 350
12 to 120
1.5 to 20
.012 to 2.2
.01 to .22
.01 to .1
49
No Trip
May Trip
.100 Max
.050 Max
.020 Max
.020 Max
.020 Max
.020 Max
51*
No Trip
.500 to 6.5
.300 to 3.0
.100 to 1.2
.031 to .500
.011 to .25
.004 to .1
.004 to .08
52*
No Trip
2 to 60
1.8 to 30
1 to 10
.15 to 2.0
.04 to 1
.008 to .5
.006 to .1
53*
No Trip
80 to 700
40 to 400
15 to 150
2 to 20
.23 to 9
.018 to .55
.012 to .2
59*
No Trip
.120 Max
.050 Max
.050 Max
.022 Max
.017 Max
.017 Max
.017 Max
61*
No Trip
.700 to 12
.35 to 7.0
.130 to 3.0
.030 to 1
.015 to .3
.01 to .15
.008 to .1
62*
No Trip
10 to 120
6 to 60
2 to 20
.2 to 3.0
.02 to 2
.015 to .8
.01 to .25
63*
No Trip
50 to 700
30 to 400
10 to 150
1.5 to 20
.4 to 10
.013 to .85
.013 to .5
64
No Trip
.7 to 12
.35 to 7
.13 to 3
.030 to 1
.017 to .3
.01 to .16
.008 to .1
65
No Trip
10 to 120
6 to 60
2 to 20
.2 to 3
.02 to 2
.017 to .76
.01 to. 6
66
No Trip
50 to 700
30 to 400
10 to 150
1.5 to 20
.4 to 10
.014 to 5
.014 to 3
69*
No Trip
.120 Max
.100 Max
.050 Max
.022 Max
.017 Max
.017 Max
.017 Max
71**
No Trip
.440 to 10
.300 to 7
.100 to 3.0
.03 to 1
.012 to .3
.004 to .15
.004 to .1
72**
No Trip
1.8 to 100
1.7 to 60
1 to 20
.15 to 3
.04 to 2
.008 to .79
.006 to .28
73**
No Trip
50 to 600
30 to 400
10 to 150
1.8 to 20
.22 to 10
.018 to .88
.011 to .50
79**
No Trip
.120 Max
.100 Max
.050 Max
.023 Max
.016 Max
.015 Max
.015 Max
*CEG type units are available only with 51, 52, ,53 and 59 delays LEG type units are available only with 61, 62, 63 and 69 delays **135% minimum trip point for delays 71, 72, 73 and 79
115
IAG/IUG/IEG/CEG/LEG Series - Configurations
http://airpax.sensata.com/
http://airpax.sensata.com/
IAG/IUG/IEG/CEG/LEG Series - Operating Characteristics
116
DELAY CURVES (IAG/IUG/IEG/CEG)
400Hz, DC, 50/60Hz Delay Curves (typ) A choice of delays is offered for DC, 50/60Hz and 400Hz applications. Delays 49, 59 and 69 provide fast acting, instantaneous trip and are often used to protect sensitive electronic equipment (not recommended where known inrush exists). Delays 41, 51 and 61 have a short delay for general purpose applications. Delays 42, 52 and 62 are long enough to start certain types of motors and most transformer and capacitor loads. Delays 43, 53 and 63 are long delays for special motor applications at 400Hz, DC and 60Hz. CEG type units are only available in 51, 52, 53 and 59 delay curves. LEG type units are only available in 61, 62, 63 and 69 delay curves.
DC Delay Curves (typ)
1
1
.1
.1
.01
.01
.01
.01
600
1000
700
800
900
1000
100 150 200 125
300
400
500
600
700
800
900
1000
DELAY 63
DELAY 69
100
.01
0
100 150 200 125
300
400
500
600
700
800
900
1000
PERCENT OF RATED CURRENT
IAG/IUG/IEG/CEG/LEG Series - Delay Curves
TIME IN SECONDS
1
400
500
600
700
800
900
1000
.1
.01
.01
.001 0
100 150 200 125
300
400
500
600
700
800
900
1000
PERCENT OF RATED CURRENT
http://airpax.sensata.com/
.001
0
PERCENT OF RATED CURRENT
DELAY 52
1000
100 150 200 125
300
400
500
600
700
800
900
1000
900
1000
PERCENT OF RATED CURRENT
DELAY 59
100
10
1
.1
.001
300
10
MAY TRIP
10
.1
100 150 200 125
10000
1000
100
1
0
10000
1000
10
.001
PERCENT OF RATED CURRENT
10000
TIME IN SECONDS
TIME IN SECONDS
0
PERCENT OF RATED CURRENT
100
.001
.001
MAY TRIP MAY
500
TIME IN SECONDS
400
MAY TRIP
300
MAY TRIP
10000
100 150 200 125
MAY TRIP
10
.1
0
DELAY 53
100 TIME IN SECONDS
10
1
1000
.1
.001
117
100
10
1
DELAY 51
1000
TIME IN SECONDS
100
10
DELAY 62
MAY TRIP
1000
TIME IN SECONDS
100 TIME IN SECONDS
DELAY 61
MAY TRIP
1000
10000
10000
10000
MAY TRIP
10000
IAG/IUG/IEG/CEG/LEG
DELAY CURVES (IAG/IUG/IEG/CEG/LEG)
1
.1
.01
0
100 150 200 125
300
400
500
600
700
PERCENT OF RATED CURRENT
http://airpax.sensata.com/
800
900
1000
.001
0
100 150 200 125
300
400
500
600
700
800
PERCENT OF RATED CURRENT
IAG/IUG/IEG/CEG/LEG Series - Delay Curves
118
IAG/IUG/IEG/CEG/LEG DELAY CURVES (IAG/IUG/IEG)
DELAY CURVES (IAG/IUG/IEG)
Multi-frequency - DC, 50/60Hz Delay Curves (typ)
400Hz Delay Curves (typ)
0
100 150 200 135
300
400
500
600
700
800
900
.01
.001 100 150 200 135
300
400
500
600
700
800
900
1000
DELAY 79
100
1
01
.01
400
500
600
700
800
900
1000
PERCENT OF RATED CURRENT
IAG/IUG/IEG/CEG/LEG Series - Delay Curves
001
0
500
600
700
800
900
1000
100 150 200 135
300
400
500
600
700
800
900
1000
http://airpax.sensata.com/
.001
.001
MAY TRIP
0
PERCENT OF RATED CURRENT
DELAY 42
100 150 200 125
300
400
500
600
700
800
900
1000
900
1000
PERCENT OF RATED CURRENT
DELAY 49
1000
100
10
1
01
300
400
10
.1
100 150 200 135
300
10000
1000
100
10
100 150 200 125
10000
1
0
0
PERCENT OF RATED CURRENT
1
001
TIME IN SECONDS
.01
TIME IN SECONDS
TIME IN SECONDS
1
1
01
MAY TRIP
MAY TRIP
10
1
.1
1000
100
10
.1
0
DELAY 43
100
1
PERCENT OF RATED CURRENT
DELAY 73
1000
MAY TRIP
10
10000
1000
TIME IN SECONDS
10
1000
10000
119
100
001
001
DELAY 41
1000
TIME IN SECONDS
01
100
DELAY 72
TIME IN SECONDS
TIME IN SECONDS
100
1000
MAY TRIP
DELAY 71
MAY TRIP
TIME IN SECONDS
1000
10000
10000
1
MAY TRIP
10000
MAY TRIP
10000
.1
.01
0
100 150 200 125
300
400
500
600
700
PERCENT OF RATED CURRENT
http://airpax.sensata.com/
800
900
1000
.001
0
100 150 200 125
300
400
500
600
700
800
PERCENT OF RATED CURRENT
IAG/IUG/IEG/CEG/LEG Series - Delay Curves
120
Trip Free Will trip open on overload, even when forcibly held in the ON position. This prevents the operator from damaging the circuit by holding on the protector. Trip Indication The operating handle moves positively to the OFF position on overload. Ambient Operation IAG/IUG/IEG/CEG/LEG protectors operate in temperatures between –40° C to +85° C. Insulation Resistance Not less than 100 megohms at 500 volts DC. Dielectric Strength IAG/IUG/IEG/CEG/LEG protectors withstand 3750Vac, 60Hz for 60 seconds between all electrically isolated terminals, except auxiliary switch terminals shall withstand 600Vac, 60Hz for REG and REC types. Four terminal dual coil and relay construction (not offered in the IEG) will withstand 1500Vac. Endurance Operating as a switch, the operating life exceeds 10,000 operations at a rate of 6 per minute when tested as follows: 6000 OPS @ rated current plus 4000 OPS @ at no load. Electrical Characteristics .050-50 amperes; 80Vdc Max., 240Vac Max., 50/60Hz and .050-30 amperes: 250Vac Max., 400Hz. Units above 30 amps are not suitable for across-the-line motor starting. Auxiliary Switch When supplied shall be SPDT configuration. Non VDE approved switches have a maximum UL rating of 10.0 amperes, 250 volts, 60Hz; 3.0 amperes, 50 volts DC, 1 amperes, 80 volts DC (REC) type or 0.1 amperes, 125 volts, 60Hz. (REG type). VDE approved switches have a maximum UL rating of 10.0 amperes, 250 volts, 60Hz, 1 amperes, 80 volts DC (REG type); or 0.1 amperes, 125 volts, 60Hz (REG type); or 0.1 amperes, 125 volts, 60Hz (REG type). Moisture Resistance Meets all the requirements of MIL-PRF-55629 when tested in accordance with Method 106 of MIL-STD-202. Salt Spray (Corrosion) Meets the requirements of MIL-PRF-55629 when tested in accordance with Method 101 of MIL-STD-202. Shock Circuit protectors shall not trip when tested per MIL-STD-202, Method 213, Test Condition I with 100% rated current applied to delayed units, except 90% current in plane 4 (i.e., handle down). Instantaneous units shall have 80% rated current applied in all planes. Construction Series, shunt, relay and series with auxiliary switch available in various delays and combinations.
121
IAG/IUG/IEG/CEG/LEG Series - Delay Curves
AGENCY APPROVALS Vibration Circuit protector shall not trip when vibrated per MIL-STD-202, Method 204, Test Condition A with 100% rated current applied to delayed units and 80% rated current to instantaneous units. VDE Approval IEG is VDE approved under VDE 0642 (EN60934). The IEG has 8mm creepage and clearance between the main circuit and the following areas: A. Operator accessible area around the handle. B. The mounting inserts or brackets. C. The auxiliary switch circuit. D. Between poles. Care must be taken to maintain spacings at the terminals when wired. The VDE approval for standard terminals is not for use with bare wire. A crimp type lug is required. In addition, all VDE approved units will be in compliance with specific CE Directives. These units will be marked as CE Compliant. UL1500 (Marine Ignition Protected) IDG/IDGH is approved for Marine Ignition Protection UL489A Listed The CEG is dimensionally the same as the popular IEG, but provides UL listing to UL489A. Available in one to three poles, in series, series with auxiliary switch, shunt, dual coil and voltage trip configurations. As a circuit breaker, the CEG provides communication equipment manufacturers with a UL listed circuit breaker in a very compact package that meets the stringent environmental requirements of today’s marketplace. This makes the CEG ideal for switching, transmission and wireless applications. UL489 Listed The LEG is dimensionally the same as the popular IEG, but provides UL listing to UL489. Available with one or two poles, in series, series with auxiliary switch, shunt and three-terminal dual coil configurations. As a circuit breaker, the LEG provides equipment manufacturers with a UL listed magnetic hydaulic circuit breaker in the most compact package available on the market. Approximate Weight Per Pole (1 to 6 poles available) Ounces
Grams
2.2
62.4
RECOMMENDED TORQUE SPECIFICATIONS
IAG/IUG/IEG Supplementary Protectors Frequency (Hz)
Phase
Minimum Poles
UL/CSA
TüV
UL1077 & CSA
TüV
80
DC
—
1
.02 to 50
.10 to 30
U2, 7500
4000
125
50/60
1
1
.02 to 50
—
U2, 3000
—
125
50/60
1
1
.02 to 30
—
C1, 5000(3)
—
125
50/60
1
1
.02 to 50
—
U3, 1000
—
125 / 250
50/60
1
2
.02 to 50
—
U1, 3000
—
125 / 250
50/60
1
1
2/1 - 30/15
—
C2, 5000(1)
—
240
50/60
1&3
1
.02 to 50
—
U1, 2000
—
240
50/60
1&3
1
.02 to 50
—
C2, 5000(1)
—
250
50/60
1
1
.02 to 2
—
U2, 5000
—
250
50/60
1&3
1
.02 to 30
.10 to 50
U1, 2000
2000
250
50/60
1&3
1
.02 to 30
—
C2, 3500(2)
—
250 (4)
50/60
1&3
1
.02 to 30
—
C1, 3500(2)
—
250 (4)
50/60
1&3
1
.02 to 30
—
U1, 1000
—
250 (5)
50/60
1
2
.02 to 50
—
U3, 1000
—
250 (5)
50/60
3
3
.02 to 50
—
U3, 1000
—
277
50/60
1
1
.02 to 30
—
U2, 2000
—
277
50/60
1
1
.02 to 30
—
C2, 5000(2)
—
250
400
1&3
1
.02 to 30
—
U2, 1500
—
250
400
3
—
.02 to 30
—
U3, 200
—
Phase
Minimum Poles
UL/CSA
TüV
UL1077 & CSA
TüV
IDG Supplementary Protectors Max Voltage
Frequency (Hz)
48
DC
—
1
.02-50
—
U2, 5000
—
65
DC
—
1
.02-50
—
U2, 3000
—
125
50/60
1
1
.02-50
—
U2, 2000
—
125/250
50/60
1
2
.02-50
—
U2, 1500
—
250
50/60
1&3
1
.02-30
—
U1, 1000
—
CEG Communications Equipment Circuit Breakers Max Voltage
Frequency (Hz)
Phase
Minimum Poles
UL/CSA
TüV
UL489A
TüV
80
DC
—
1
.05-50
—
5000
—
Max Voltage
Frequency (Hz)
Phase
Minimum Poles
UL/CSA
TüV
UL489
TüV
125
50/60
1
1
.05-30
.10-30
5000
2000
120/240
50/60
1
2
1-30
.10-30
5000
2000
LEG Circuit Breakers
Torque (in-lbs)
6-32 Mounting Inserts
6 to 8
M3 Mounting Screws
4 to 5
8-32 Screw Terminals
10 to 12
M4 Terminal Screws
10 to 12
10-32 Screw Terminals
14 to 15
The family of protectors has been evaluated for end use application for use groups (UG) A, B, C and D
M5 Screw Terminals
14 to 15
The maximum voltage ratings for which the protectors have been tested are shown in the chart
30 to 35
Where applicable, mechanical support must be provide to the terminals when applying torque
http://airpax.sensata.com/
Short Circuit Rating (SC), Amps
Max Voltage
Component
1/2 - 32 Mounting Bushing
Rated Current (Amps)
IAG/IUG/IEG/CEG/LEG
SPECIFICATIONS
Notes:
(1) With 125 A max. series fuse; (2) With 80 A max. series fuse; (3) With 50 A max. circuit breaker; (4) With blocked vent construction; (5) Non-standard construction. “Fit for further use” approval
General notes: All supplementary protectors are of the overcurrent (OC) type The terminals (FW) are suitable for factory wiring only (0) The current is the amperage range that the protectors have been tested The tripping current (TC) for all of the protectors is “1” (in the range of 125% to 135% of ampere rating except for the 400Hz protectors which is “2” (more than 135% of ampere rating) The overload rating (OL) - designates whether the protector has been tested for general use or motor starting applications.
http://airpax.sensata.com/
0 – tested at 1.5 times amp rating for general use 1 – tested at 6 times AC rating or 10 times DC rating for motor starting The short circuit current rating (SC) – The short circuit rating in amperes following a letter and number designating the test conditions and any calibration following the short circuit test is defined below: C – Indicates short circuit test was conducted with series overcurrent protection U – Indicates short circuit test was conducted without series overcurrent protection 1 – Indicates a recalibration was not conducted as part of the short circuit testing 2 – Indicates a recalibration was performed as part of the short circuit testing 3 – Indicates recalibration was performed along with the dielectric and voltage withstand for “Suitable for Further Use” rating
IAG/IUG/IEG/CEG/LEG Series - Delay Curves
122
IMG** CMG++ IMGH** CMGH++
One toggle handle per unit, marine ignition protection One toggle handle per pole marine ignition protection One toggle handle per unit mid-trip indication One toggle handle per pole mid-trip indication
*UL Recognized, CSA Certified **UL Recognized, CSA Certified, VDE Approved *** UL Recognized UL1500 + UL489A Listed CSA Certified ++ UL489AListed CSA Certified VDE Approved
To determine the ordering number for your particular IAG/IUG/IEG/CEG unit, simply follow the steps shown. You may use this number to place an order or as a reference for further questions you may have.
C. IEG, IEGH, IEGS, IEGHS, IEGX and IEGZX circuit protectors are designed to meet 8mm creepage and clearance requirements for installation Category III, Pollution Degree 3, Case A as measured in IEC 664. Intended for use in equipment designed to comply with IEC 601 and 950 and VDE 0804 and 0805.
3
Third Decision
IAG/IUG/IEG/CEG Series - Decision Tables
Barriers*
LINE
.250
15.0
X
Rocker w/ standard mounting*
.500
20.0
-C
277V (50/60Hz only) (See note 3)
ZX
ZX Rocker w/ integral mounting*
.750
30.0
-G
Handle guard, (available in ZX, BX and snap-in versions only)
BX
BX Rocker w/ integral mounting
N
Sealed toggle w/bushing mounting**
Note: Add "F" for flat screw terminals * Not available on mid-trip units ** Available only on IAG, IUG units
1.00
35.0*
2.50
40.0*
-L
Handle lock
5.00
50.0*
-M
Handle in opposite pole (2 pole only)
-Q
APG style “FAT” handle
7.50
Poles and Terminals
7
Seventh Decision
Push-on Terminals
Screw Terminals
1
6
Single pole
11
66
Two pole
111
666
Three pole
Color
Unmarked
Marked ON-OFF I-O
1111
6666
Four pole
Black
-00
-01 (STD)
Yellow
-10
-11
Red
-20
-21
Blue
-30
-31
Green
-40
-41
Orange
-60
-61
White
-90
-91
2
3
5
Toggle Handle
7
ON
4
Fourth Decision
Face plate sides flush with protector (see note 4) Handle guard with no actuation feature (BX rocker only) (Not available with mid-trip indication)
IAG/IUG/IEG/CEG/LEG
INDICATION “ON” MOUNTING/INDICATOR CODE: J, K, L
LINE LOAD
OFF
O
OFF
ON
ON
FIG. 2
LOAD LINE
LOAD LINE
O
ON
FIG. 3
OFF
FIG. 5
FIG. 4
LOAD LINE ON
OFF
FIG. 6
O OFF
MOUNTING/INDICATOR CODE: M, N, P, R
LOAD LINE
See alternate 7th decision below for X, ZX & BZ rocker handles.
ON
LINE
O
O
OFF
FIG. 2
FIG. 3
OFF
LOAD ON
O
FIG. 6
MARKING DETAIL “C” (SEE TABLE)
Frequency and Delay Switch only 400Hz short delay
-1REC4
Series w/ auxiliary switch * .110 quick connect
-42
400Hz long delay
-43
400Hz motor start
Rocker Handle Color, Indicator Color and Marking Selection (See Notes)
Series w/ auxiliary switch * .187 quick connect
-49
400Hz 150% instant trip
IAGX, IUGX, IEGX, IAGZX, IUGZX, IEGZX, CUGZX, CEGZX Rocker Handle (Single Rocker Color)
-51
DC short delay*
Series w/ auxiliary switch (gold contacts)* .110 quick connect
-52
DC long delay*
-53
DC motor start*
Rocker Handle Color
Series w/ alarm switch, electrical trip, .110 Q.C. terminals
-59
DC 125% instant trip*
-61
50/60Hz short delay
Series w/ alarm switch, electrical trip, .110 Q.C. terminals (mid-trip only)
-62
50/60Hz long delay
-63
50/60Hz motor start
-64
50/60Hz short delay
-65
50/60Hz long delay
-66
50/60Hz motor start
-69
7
Seventh Decision
Vertical Mounting
Horizontal Mounting On-Off Fig.4
I-O Fig.5
On-Off I-O Fig.6
Indicating Color
Marking Color
Indicates:
Unmarked
On-Off Fig.1
I-O Fig.2
On-Off I-O Fig.3
Black
N/A
White
N/A
-00
-01
-02
-03
-04
-05
-06
Red
N/A
White
N/A
-20
-21
-22
-23
-24
-25
-26
Grey
N/A
Black
N/A
-40
-41
-42
-43
-44
-45
-46
Orange
N/A
Black
N/A
-50
-51
-52
-53
-54
-55
-56
White
N/A
Black
N/A
-90
-91
-92
-93
-94
-95
-96
White
White
On
-A0
-A1
-A2
-A3
-A4
-A5
-A6
Black
Red
White
On
-B0
-B1
-B2
-B3
-B4
-B5
-B6
50/60Hz 125% instant trip
Black
Green
White
On
-C0
-C1
-C2
-C3
-C4
-C5
-C6
-71
DC/60Hz short delay
Black
White
White
Off
-F0
-F1
-F2
-F3
-F4
-F5
-F6
-72
DC/60Hz long delay
Black
Red
White
Off
-G0
-G1
-G2
-G3
-G4
-G5
-G6
Black
Green
White
Off
-H0
-H1
-H2
-H3
-H4
-H5
-H6
Black
White
White
On
-J0
-J1
-J2
-J3
-J4
-J5
-J6
Black
Red
White
On
-K0
-K1
-K2
-K3
-K4
-K5
-K6
Black
Green
White
On
-L0
-L1
-L2
-L3
-L4
-L5
-L6
-79
DC/60Hz motor start DC/60 Hz 135% instant trip
For addition of inertial delay, add an ìFî to any delay numeral. * CEG types are only available with DC ratings
V = VDE and CCC Approved The shaded areas denote VDE and CCC (if applicable) approval options. This approval requires the addition of a V at the end of the part number. The V will be added to any part number formed entirely from shaded decisions. If non-shaded areas are selected, the unit will not be VDE or CCC Approved, but other approvals still apply.
http://airpax.sensata.com/
Marking Detail
A
IAGZX, IUGZX, IEGZX, CUGZX, CEGZX Rocker Handle (Dual Rocker Color) Black
-73
C = CCC Approved
ROCKER HANDLE COLOR
INDICATION “OFF”
-41
* Only one auxiliary switch is normally supplied on two or three pole units. Switch is located in the right-hand pole (viewed from terminal end) unless otherwise specified.
ON
FIG. 6
ON I
SW
Relay
OFF
FIG. 5
FIG. 4
LOAD
LOAD LINE
ON
LINE
Series
-4
FIG. 3
ON
MARKING DETAIL “B” (SEE TABLE)
Switch only
Shunt
OFF
LINE
FIG. 1
-1
-3
FIG. 2
LOAD LINE
LINE
O
OFF
INDICATING COLOR
-X
-0
-1REC5
ON
O
OFF
OFF
Notes: 1. One or more descriptions may be used as required. 2. When this is not used, table one may be substituted and U.S. thread will be supplied. Unit will be rated at 250V (50/60Hz only.) 3. VDE approved at 250VAC 4. IEGS standard face plate has beveled sides(see pg.90) * Not available on snap-in units
Handle Color and Marking Selection
4
LOAD LINE
INDICATION “OFF” MOUNTING/INDICATOR CODE: F, G, H
MARKING DETAIL “A” (SEE TABLE)
-S
Second Decision
LINE
INDICATION “ON” MOUNTING/INDICATOR CODE: A, B, C
FIG. 1
* IDG/IDGH is rated for 30 amps max.
Internal Configuration
This approval requires the addition of a C at the end of the part number. The unit will not be VDE Approved.
123
Metric thread mounting inserts and terminals
-B
Handle marking color is white on black, red, blue & green handles and black on white, yellow and orange handles.
-1RLS4
B. When “A” (metric thread mounting) is specified in the sixth decision in combination with screw terminal option in the second decision, metric screw terminals are supplied.
-A
Toggle w/ snap-in mounting
1
-1RS4
A. It is recommended that power leads be soldered to circuit protectors having push-on type terminals for current trip ratings above 20 amperes.
10.0
OFF
INDICATING COLOR
S
Example: IEG 1 - 1REC4 - 61 - 20.0 - 01 - V
-1REG4
Notes:
.100
*Not available in toggle seal handle type.
When specifying a circuit protector for AC motor start or high inrush applications, the peak amplitude and surge duration should be specified for factory assistance in rating selection. For example, the following is the code for a single pole, IEG quick-connect type terminal, series unit with auxiliary switch, designed for operation in a 50/60Hz circuit. It has a short time delay, a rating of 20 amperes, a black marked handle and is VDE approved.
Standard toggle/mounting, no designation required
2
ROCKER HANDLE COLOR
Standard hardware. No designation required.
Standard ratings listed. For other ratings, please contact the factory.
O
IDGH***
One toggle handle per pole
ON
Optional OFF
Handle and Mounting Options
One toggle handle per unit
INDICATING COLOR
ON
O
The coding given permits a self-assigning part number but with certain limitations. Special applications may require a factory-assigned part number. Typical examples are units with mixed ratings, combinations of styles, or constructions not listed in the third decision table. With these, it is suggested that order entry be by description and/or drawings and a part number will be established. Additionally, it is standard policy to establish a factory-assigned part number whenever a descriptive drawing exists to provide cross reference, traceability and manufacturing control.
IAG IUG* IEG** CUG+ CEG++ IAGH IUGH* IEGH** CUGH+ CEGH++ IDG***
ROCKER HANDLE COLOR
Sixth Decision
O
Description
6
Fifth Decision Rated Current
Select Type and Terminal Type
The ordering code for IAG/IUG/IEG/CEG/IDG circuit protectors may be determined by following the decision steps in the tables shown here.
5
First Decision
O
IAG / IUG / IEG / CEG Decision Tables
1
A
B
IAGBX, IUGBX, IEGBX, CUGBX, CEGBX Rocker Handle (Dual Rocker Color) Black
White
White
Off
-M0
N/A
-M2
-M3
N/A
-M5
-M6
Black
Red
Red
Off
-N0
N/A
-N2
-N3
N/A
-N5
-N6
Black
Green
Green
Off
-P0
N/A
-P2
-P3
N/A
-P5
-P6
Black
Yellow
Yellow
Off
-R0
N/A
-R2
-R3
N/A
-R5
-R6
C
Notes: A. Bezels of IAGBX, IUGBX, IEGBX, CUGBX, CEGBX are black. B. Consult factory for other marking options.
http://airpax.sensata.com/
IAG/IUG/IEG/CEG Series - Decision Tables
124
Description
Type LEG
Handle and Mounting Options
LMG
One toggle handle per unit One toggle handle per unit mid-trip indication
LEGH
One toggle handle per pole
LMGH
One toggle handle per pole mid-trip indication
For example, use: .100 or 2.00 or 10.0
Standard toggle/mounting, no designation required
Handle guard, (available in ZX, BX and snap-in versions only)
Toggle w/ snap-in mounting
-L
Handle lock
ZX
ZX Rocker w/ integral mounting*
-S
Face plate sides flush with breaker
BX Rocker w/ integral mounting
Note: Add "F" for flat screw terminals * Not available on mid-trip units
LINE
LOAD
-X*
Handle guard with no actuation feature (BX rocker only)
-Z
"Z" Barriers
LINE
INDICATION “ON” MOUNTING/INDICATOR CODE: A, B, C
ON
LINE
ON
OFF
OFF
FIG. 2
LOAD LINE
LINE
O
O
OFF
FIG. 1
INDICATION “OFF” MOUNTING/INDICATOR CODE: F, G, H
FIG. 3
ON
LOAD
LOAD LINE OFF
FIG. 5
FIG. 4
ON
FIG. 6
MARKING DETAIL “A” (SEE TABLE)
INDICATING COLOR
2
7
Second Decision Poles and Terminals
OFF LINE ON
Seventh Decision
Push-on Terminals
Screw Terminals
1
6
Single pole
11
66
Two pole
Toggle Handle
Example:
LEG
1
6 - 1REC4 - 61 - 20.0 - 01 - V
2
3
4
5
7
LINE
Color
Unmarked
Marked ON-OFF I-O
Black
-00
-01 (STD)
Yellow
-10
-11
Red
-20
-21
Blue
-30
-31
Green
-40
-41
Orange
-60
-61
White
-90
-91
4
Internal Configuration -61
50/60Hz short delay
-1REC4
Series w/ auxiliary switch * .110 quick connect
-62
50/60Hz long delay
-63
50/60Hz motor start
Series w/ auxiliary switch * .187 quick connect
-69
50/60Hz 125% instant trip
-1RLS4
-3
Series w/ alarm switch*, electrical trip, .110 Q.C. terminals Series w/ alarm switch*, electrical trip, mid-trip only, .110 Q.C. terminals Shunt
* Only one auxiliary switch is normally supplied on two pole units. Switch is located in the right-hand pole (viewed from terminal end) unless otherwise specified.
LOAD LINE
O
ON
ON
FIG. 2
FIG. 3
OFF
FIG. 4
LOAD LINE
FIG. 5
LOAD LINE ON
OFF
FIG. 6
MARKING DETAIL “B” (SEE TABLE)
ON I O OFF
LINE
INDICATION “OFF”
MOUNTING/INDICATOR CODE: M, N, P, R
LOAD
ON
LINE
O
O
OFF
FIG. 2
FIG. 3
LINE OFF
LOAD ON
O
FIG. 6
MARKING DETAIL “C” (SEE TABLE)
Frequency and Delay
Series
Series w/ auxiliary switch* (gold contacts) .110 quick connect
OFF
Fourth Decision
-1
-1REC5
O
ON
FIG. 1
See alternate 7th decision below for ZX & BZ rocker handles.
Third Decision
OFF
LOAD
Handle marking color is white on black, red, blue & green handles and black on white, yellow and orange handles.
3
ROCKER HANDLE COLOR
INDICATION “ON” MOUNTING/INDICATOR CODE: J, K, L
Handle Color and Marking Selection
*Not available in toggle seal handle type.
-1RS4
For addition of inertial delay, add an “F” to any delay numeral. * CEG types are only available with DC ratings
V = VDE Approved The shaded areas denote VDE Approval options. This approval requires the addition of a V at the end of the part number. The V will be added to any part number formed entirely from shaded decisions. If non-shaded areas are selected, the unit will not be VDE Approved, but other approvals still apply.
C = CCC Approved This approval requires the addition of a C at the end of the part number. The unit will not be VDE Approved.
Notes: A. When “A” (metric thread mounting) is specified in the sixth decision in combination with screw terminal option in the second decision, metric screw terminals are supplied.
7
Seventh Decision Rocker Handle Color, Indicator Color and Marking Selection (See Note) LEGZX Rocker Handle (Single Rocker Color)
Vertical Mounting
Horizontal Mounting
I-O Fig.2
On-Off I-O Fig.3
On-Off Fig.4
I-O Fig.5
On-Off I-O Fig.6
-01
-02
-03
-04
-05
-06
-21
-22
-23
-24
-25
-26
-40
-41
-42
-43
-44
-45
-46
N/A
-50
-51
-52
-53
-54
-55
-56
N/A
-90
-91
-92
-93
-94
-95
-96
Rocker Handle Color
Indicating Color
Marking Color
Indicates:
Unmarked
On-Off Fig.1
Black
N/A
White
N/A
-00
Red
N/A
White
N/A
-20
Grey
N/A
Black
N/A
Orange
N/A
Black
White
N/A
Black
Marking Detail
A
LEGZX Rocker Handle (Dual Rocker Color) Black
White
White
On
-A0
-A1
-A2
-A3
-A4
-A5
-A6
Black
Red
White
On
-B0
-B1
-B2
-B3
-B4
-B5
-B6
Black
Green
White
On
-C0
-C1
-C2
-C3
-C4
-C5
-C6
Black
White
White
Off
-F0
-F1
-F2
-F3
-F4
-F5
-F6
Black
Red
White
Off
-G0
-G1
-G2
-G3
-G4
-G5
-G6
Black
Green
White
Off
-H0
-H1
-H2
-H3
-H4
-H5
-H6
Black
White
White
On
-J0
-J1
-J2
-J3
-J4
-J5
-J6
Black
Red
White
On
-K0
-K1
-K2
-K3
-K4
-K5
-K6
Black
Green
White
On
-L0
-L1
-L2
-L3
-L4
-L5
-L6
A
B
LEGBX Rocker Handle (Dual Rocker Color)
B. LEG, LEGH, LEGS, LEGHS, LEGZX and LEGBX circuit breakers are designed to meet 8mm creepage and clearance requirements for installation Category III, Pollution Degree 3, Case A as measured in IEC 664. Intended for use in equipment designed to comply with IEC 601 and 950 and VDE 0804 and 0805.
LEG Series - Decision Tables
Metric thread mounting inserts and terminals
-G
OFF
INDICATING COLOR
Notes: 1. One or more descriptions may be used as required. 2. When this is not used, table one may be substituted and U.S. thread will be supplied. Unit will be rated at 250V (50/60Hz only.) 3. LEGS standard face plate has beveled sides(see pg. 90) * Not available on mid-trip units
-1REG4
125
-A
S
BX
Note: All types are UL489 listed, CUL certified
Standard hardware. No designation required.
Use three numbers to print required current value between .100 amps minimum and 30.0 amps maximum.
O
To determine the ordering number for your particular LEG unit, simply follow the steps shown. You may use this number to place an order or as a reference for further questions you may have.
ROCKER HANDLE COLOR
OFF
Select Type and Terminal
When specifying a circuit breaker for AC motor start or high inrush applications, the peak amplitude and surge duration should be specified for factory assistance in rating selection. For example, the following is the code for a single pole, LEG screw type terminal, series unit with auxiliary switch, designed for operation in a 50/60Hz circuit. It has a short time delay, a rating of 20 amperes, a black marked handle and is VDE approved.
ON
Optional
O
The coding given permits a self-assigning part number but with certain limitations. Special applications may require a factory-assigned part number. Typical examples are units with mixed ratings, combinations of styles, or constructions not listed in the third decision table. With these, it is suggested that order entry be by description and/or drawings and a part number will be established. Additionally, it is standard policy to establish a factoryassigned part number whenever a descriptive drawing exists to provide cross reference, traceability and manufacturing control.
INDICATING COLOR
ON
O
The ordering code for LEG circuit breakers may be determined by following the decision steps in the tables shown here.
Rated Current
First Decision
ROCKER HANDLE COLOR
Sixth Decision
O
LEG DECISION TABLES
1
6
Fifth Decision
IAG/IUG/IEG/CEG/LEG
5
Black
White
White
Off
-M0
N/A
-M2
-M3
N/A
N/A
-M6
Black
Red
Red
Off
-N0
N/A
-N2
-N3
N/A
N/A
-N6
Black
Green
Green
Off
-P0
N/A
-P2
-P3
N/A
N/A
-P6
Black
Yellow
Yellow
Off
-R0
N/A
-R2
-R3
N/A
N/A
-R6
C
Notes:A. Bezels of LEGBX are black. B. Consult factory for other marking options.
http://airpax.sensata.com/
http://airpax.sensata.com/
LEG Series - Decision Tables
126
This document is generated from the AIRPAX™ full-line catalog #2455005000 printed in USA, January 2011
BUSINESS CENTERS Sensata Technologies 807 Woods Road Cambridge, MD 21613, USA Phone: +1 410-228-1500 Brands: Airpax™
Sensata Technologies Holland B.V. Kolthofsingel 8 7602 EM Almelo, The Netherslands Phone: +31 546 87 95 55 Brands: Klixon™, Sensata Technologies™
Sensata Technologies Inc. 529 Pleasant Street Attleboro, MA 02703, USA Phone: +1 508-236-3287 Brands: Klixon™, Sensata Technologies™
Sensata Technologies China Co., Ltd. Novel Plaza, 8th Floor 128 Nanjing Road West Shaghai, 20003 People’s Republic of China Phone: +86 21 23061500 Brands: Klixon™, Sensata Technologies™
Sensata Technologies 4467 White Bear Lake Parkway St. Paul, MN 55110, USA Phone: +1 800-553-6418 Brands: Dimensions™
Sensata Technologies Japan Ltd. 305, Tanagashira Oyama-cho, Sunto-gun, Shizuoka-ken Japan, 410-1396 Phone: +81 550 78 1211 Brands: Klixon™, Sensata Technologies™ Sensata Technologies Nihon-Airpax 6-3, Chi Yoda 5 Chome Saitama-Ken Japan, 350-0214 Phone: +81 492 83 7575 Brands: Airpax™
Sensata Technologies Korea Ltd. 29F, Trade Tower 159-1 SamSung-Dong, KangNam-Ku, Seoul 135-729, Korea Phone: +81-2-551-2918 Brands: Klixon™, Sensata Technologies™
Important Notice: Sensata Technologies (Sensata) reserves the right to make changes to or discontinue any product or service identified in this publication without notice. Sensata advises its customers to obtain the latest version of the relevant information to verify, before placing any orders, that the information being relied upon is current. Sensata assumes no responsibility for infringement of patents or rights of others based on Sensata applications assistance or product specifications since Sensata does not possess full access concerning the use or application of customers’ products. Sensata also assumes no responsibility for customers’ product designs.
http://airpax.sensata.com/