Manual water inlet: press the key Inlet to start water supply solenoid valve, which
will ... necessary to repair or replace it. ..... or equal to W87+5 , P4 is turned off. ...
the buzzer will make a sound, thus the system resets, and it rovers to the.
Control Cabinet for Solar Hot Water Project
Instruction Manual
Read the manual before usage
Contents 1
Function Introduction
3
Technical Parameters
5
Application Method
17
Connection Method
18
Attentions
19
Maintenance Guide
19
Control Cabinet Accessories
22
Packing List
HKG-IV Type Control Cabinet Function Introduction I.Full-automatic type: (all the following functions are automatic) Water temperature display: both water temperature display of large tank and that of collector and pipeline range between 0 and 99 and the display accuracy is 1 . Water level display: water level display of large tank ranges between grade 0 and grade 4. Water tank display: running conditions of two water tanks are displayed on separate screens. Collector display: running conditions of two groups of collector are displayed on separate screens. Temperature-controlled water inlet: in case tank temperature is 5 higher than the set temperature and water level is lower than grade 4, solenoid valve will be started. Timed water inlet: under timed water inlet state, if the set time is reached, solenoid valve will be started. Constant-level water inlet: in case tank water level is lower than water inlet level, solenoid valve will be started. Dry burning-resistant function: in case electric heating conditions are met but water level is Lower than grade 1, solenoid valve will be started. Timed electric heating: under timed electric heating state, if the set time is reached, solenoid valve will be started. Intelligent electric heating: Intelligent turns on after the key is pressed and then intelligent electric heating function will be started. Anti-freezing electric heating: in case tank temperature is lower than the set temperature and water level is higher than grade 1, electric heating will be started. Circulation of temperature difference: inspect difference in temperatures of collector and water tank. In case the temperature difference is greater than the set value, circulation pump will be started. Anti-pipe-explosion circulation: in case collector temperature is higher than 95 , circulation Pump will run in accordance with the set time period. Timed circulation at constant temperature: within the set time, if pipeline temperature is 5 lower than the set temperature, circulation pump will be started; if the set temperature is reached, circulation pump will be shut down. Timed pipeline circulation: under timed water use state, if tank water level is higher than grade 1, the circulation will be enabled and circulation pump will be shut down after 10 minutes. Anti-freezing circulation: inspect the pipeline temperature and conduct circulation to prevent pipeline being frost-damaged. Separate anti-freezing control function: in case the temperature of anti-freezing sensor is lower than the starting temperature, anti-freezing circulation pump (ribbon heater) will be started to prevent header being frost-damaged. Timed water use: under timed water use state, if the set time is reached, water pump will be Started. Earth leakage protection: leakage circuit breaker is set in power supply line. In case the phase line has the operable leakage current to ground, power supply will be cut off automatically. Power-off anti-pipe-explosion function: in case of energizing after power off, to prevent pipe explosion of collector, when collector temperature is greater than or equal to 90 and temperature difference between collector and water tank is greater than or equal to 30 , all circulation functions of heat collecting temperature difference will be disabled.
01
HKG-IV Type Control Cabinet II. Operable type: (all the following functions can be manually operated) Water level setting: standing level of water tank is set between grade 2 and grade 4 and is grade 4 by default. Tank temperature setting: water temperature of water tank is set between 0 45
and 99
and is
by default. Pipeline holding temperature: water temperature is set between 0
and 99
and is 40
by
Default. Function key
Set
: press this key to view the above parameters and conduct auxiliary setting.
Function key
OK
: under parameter setting state, press this key to confirm the parameter
value and return to the previous level. Function key Cancel : under parameter setting state, press this key to exit setting state and return to the previous level. and Function keys Function key
Inspection
: press them to adjust the setting values. : press this key to view current operating state of control panel.
Manual water inlet: press the key
Inlet
to start water supply solenoid valve, which will
automatically shut down when the set water level is reached, and press this key again under inlet state to stop water supply immediately. Timed water inlet: press the key Timed Water Inlet to enable control function of timed water inlet and press this key again to cancel such function. Manual electric heating: when the key Electric Heating met, electric heating function will be enabled. Intelligent electric heating: press the key Intelligent
is pressed, if heating conditions are
to enable control function of intelligent
electric heating and press this key again to cancel such function. Timed electric heating: press the key Timed Electric Heating
to enable control function of
electric heating and press this key again to cancel such function. Pipeline circulation: press the key Pipeline Circulation to enable control function of manual pipeline circulation and press this key again to cancel such function. Timed water use: press the key Timed Water Use to enable control function of timed water use and press this key again to cancel such function. Clock timing: to set hour and minute of real-time clock. Reset function: if user wants to restore system factory default settings, user can operate the key Reset
and then the system will automatically revert to factory default state.
02
HKG-IV Type Control Cabinet III. Back-up control type When the system is in debugging stage, functions in this part can be used for assisting the debugging. Or in case automatic control system has a failure, functions in this part can be temporarily enabled so as to ensure normal output of hot water. If transfer switch inside the cabinet is in auto mode, corresponding buttons will be shielded. To enable functions in this part, it is necessary to turn transfer switch to be manual mode (the display panel has no display at this time). As required, operators must have taken usage training and specific person must be on duty. Temperature difference circulation button 1: rotate this button to manual mode to start temperature different circulation pump 1. Temperature difference 2/ discharge button: rotate this button to manual mode to start temperature different circulation pump 2 or discharge solenoid valve. System inlet button: rotate this button to manual mode to start water inlet solenoid valve 1. Pipeline circulation button: rotate this button to manual mode to start pipeline circulation pump. Anti-freezing circulation button: rotate this button to manual mode to start anti-freezing circulation pump or ribbon heater. Water use / water inlet button 2: rotate this button to manual mode to start water use pump or water inlet solenoid valve 2. Auxiliary heating button 1: rotate this button to manual mode to enable electric heating 1. Auxiliary heating button 2: rotate this button to manual mode to enable electric heating 2.
IV. Leakage test Leakage circuit breaker is the main switch of control cabinet. Before use of this control cabinet, first open the control cabinet, switch on leakage circuit breaker and press test button T of the leakage circuit breaker, and then the leakage circuit breaker should automatically trip, which proves the leakage circuit breaker is normal. If the leakage circuit breaker fails to automatically trip, it is necessary to repair or replace it. (Such operations must be conducted by professional installation or maintenance personnel!)
Technical Parameters List of technical parameters Ambient temperature Relative temperature
Remarks
0-40 80% (40 )
Power supply configuration
380VAC/50Hz
Three-phase four-wire system
Electric leakage protection
Residual operating current is 50, 75 and 100mA
Depending on electric thermal power
Electric thermal power
2 45kW
Customized in accordance with user's requirements
Power of water pump
1kW/220VAC
Customized in accordance with user's requirements
Performance standards: GB50171-1992 and GB4706.1-2005
03
HKG-IV Type Control Cabinet Function Description
Tank 1
Tank 12
Water temperature Water level
Timed
Collector 1
Collector 2
Water discharge at Water Temperature constant temperature temperature difference circulation
Timed circulation Parameter sequence number
Intelligent Timed water inlet
Control Panel No.
Clock
Pipeline circulation Timed water use
Anti-freezing circulation
Screen Structure Diagram
I. Water tank display
Tank 1
Tank 2
Water temperature
Timed
Water level
Running conditions of two water tanks are displayed on upper left area of the screen. For single-tank system, Tank 1 is normally on; for dual-tank system, water temperatures, water levels and electric heating conditions of Tank 1 and Tank 2 are displayed on separate screens.
Intelligent
II. Collector display The upper right area is collector display area. For single-collector system, Collector 1 is normally on; for dual-collector system, water temperatures and collection circulating conditions of two groups of collectors Collector 1 and Collector 2 are displayed on separate screens.
04
Collector 1
Water temperature
Parameter sequence number
Temperature difference circulation
Collector 2 Timed water discharge
HKG-IV Type Control Cabinet III. Basic display The lower left area of the screen is basic display area, including control panel number display and clock display.
Control Clock
panel No.
IV. Water inlet/ anti-freezing/ pipeline/ water use display The lower right area displays temperatures and running conditions of pipeline circulation and anti-freezing circulation separately.
Pipeline circulation Timed water use
Timed water inlet
Anti-freezing circulation
V. Split-screen display Continuously press Inspection to simultaneously switch for displaying temperatures, water levels and devices' running conditions of tank 1 / 2 or collector 1 / collector 2 or pipeline / anti-freezing circulation.
Application Method I. Parameter setting Auto
Stop Manual
Open control cabinet, switch on leakage circuit breaker and all small high-breaking capacity breakers. Rotate the internal Transfer Switch to Auto mode to automatically control partial energization works.
It defaults to using the key Shift Up under setting state while the key Shift Down is used under non-device state. When various devices are in flickering duration, corresponding operations can be carried out only after corresponding keys are pressed to send commands, otherwise they will keep flickering.
Heat-collecting method
Inspection
Electric Timed electric Set heating 2 Intelligent 2 heating 2 Water inlet
Timed water inlet
Timed electric Electric heating 1 Intelligent 1 heating 1 Timed water use
Pipeline circulation
Press Control panel No.
Set
setting state, with
to directly access user Control Panel No.
normally on display and display.
05
-
in
in flickered
HKG-IV Type Control Cabinet After access to setting state, press OK to enter parameter sequence number setting of this panel, with Control Panel No. and - returning to normal display (or press Cancel to return to the previous level).
Parameter sequence number
After access to parameter sequence number setting state of a master control panel, Parameter Sequence Number is normally on, and 88 on it displays sequence number of the parameter in a flickering manner. During flickering of 88 (defaulting to the minimum sequence number of corresponding level), Shift Up is used for directly inputting parameter sequence number, or left/right arrow keys are used for adjusting parameter sequence number. After OK is pressed, parameter setting state of this panel will be accessed and 88 will display the input sequence number of the parameter (or Cancel can be pressed for returning to the previous level). After access to parameter setting state, 88:88 on the lower left area displays the original contents of parameter in a flickering manner. You can directly input target value of the parameter or use left/right arrow keys to adjust such values, and press OK to memorize parameter value, restore the normal display and return to the previous level.
Auditory tone cue: auditory tone cue sounding like toot can be heard when a key is pressed every time (the sound is similar to prompt tone of calculator). Details of all parameter sequence numbers and all parameters are shown in the parameters list on page 19 of this Specifications. Management-level Set Parameters in the parameters list shall be set by professional installation personnel or personnel specified by our company so as to ensure their correctness. II. Control function 1. Heat-collecting function The heat-collecting system has the following five system modes. Temperature-difference circulation
Constant-temperature water release
Note: (1) The upper left icon is normally on, and the three arrows in it chase one another when the temperature-difference circulation pump is started. (2) The lower left icon is normally on, and the water drops flicker when the discharge solenoid valve is started.
06
HKG-IV Type Control Cabinet Mode 1 Water tank 1
P3
L1
DCF1
T6
T3 T1 P1 DJR1
T4
Temperature-difference circulation: when the water level of water tank 1 L1 is greater than or equal to 1, if the temperature difference T3 T1 is greater than or equal to W83 , P1 will be started; if the temperature difference is less than or equal to W84 , P1 will be shut down. (After the temperature-difference circulation is started, it will be forced to stop after T60 minutes when the temperature-difference is less than W83 .) Anti-pipe-explosion circulation: when the water level of water tank 1 L1 is equal to or less than 1, if the temperature of heat collector T3 is greater than 95 , the circulation pump P1 will be stopped for T61 minutes after each T60 minutes' circulation, and it circulates round again and again. W83: Starting temperature-difference of temperature-difference circulation
T1: Temperature of water tank 1
W84: Stopping temperature-difference of temperature-difference circulation
L1: Water level of water tank 1 T3: Temperature of heat collector
T60: Duration of heat-collecting circulation
P1: Circulation pump
T61: Stop duration of heat-collecting circulation
Mode 2
Water tank 1
Water tank 2
L1
L2
T3
P3
T6
P1 T2
T1
T4
T5
DCF1
DJR1
P2 DJR2
Temperature-difference circulation: when the water level of water tank 1 L1 is greater than or equal to 1, if the temperature difference T3-T1 is greater than or equal to W83 , P1 will be started; when the temperature difference is less than or equal to W84 , P1 will be shut down. (After temperature-difference circulation is started, it will be forced to stop after T60 minutes when the temperature difference is less than W83 .)
07
HKG-IV Type Control Cabinet Inter-water tanks temperature-difference circulation: when water level of water tank 1 L1 is greater than or equal to 1 and the water level of water tank 2 L2 is greater than or equal to 1, if T1-T2 is greater than or equal to W83 , P2 will be started; when the temperature difference is less than and equal to W84 , P2 will be shut down. Anti-freezing circulation between two water tanks: when water level of water tank 1 L1 is greater than or equal to 1 or when water level of water tank 2 L2 is greater than or equal to 1, when the temperature of anti-freezing sensor T5 is less than W87, P2 will be started, when the temperature of anti-freezing sensor T5 is greater than or equal to W87+5 , P2 will be shut down. Anti-pipe-explosion circulation: when water level of water tank 1 L1 is greater than or equal to 1, if the temperature of heat collector T3 is greater than 95 , the circulation pump P1 will be stopped for T61 minutes after each T60 minutes' circulation, and it circulates round again and again. T1: Temperature of water tank 1
T3: Temperature of heat collector
T2: Temperature of water tank 2
T5: Temperature of anti-freezing sensor
L1: Water level of water tank 1
P1: Circulation pump
L2: Water level of water tank 2
P2: Circulation pump
W87: Anti-freezing starting temperature
W83: Starting temperature difference of temperature-difference circulation W84: Stopping temperature difference of temperature-difference circulation T60: Duration of heat-collecting circulation T61 Stop duration of heat-collecting circulation
Mode 3 Water tank 1
DCF1
T6
L1
T3
P1 T4 L2 T1 P2 DJR1
T5
08
P3
HKG-IV Type Control Cabinet Temperature-difference circulation 1: when the water level of water tank 1 L1 is greater than or equal to 1, if the temperature difference T3-T1 is greater than or equal to W83 , P1 will be started; when the temperature difference is less than or equal to W84 , P1 will be shut down. (After the temperature-difference circulation is started, it will be forced to stop after T60 minutes when the temperature-difference is less than W83 .) Temperature-difference circulation 2: when the water level of water tank 1 L1 is greater than or equal to 1, if the temperature difference L2-T1 is greater than or equal to W93 , P2 will be started; when the temperature difference is less than or equal to W94 , P2 will be shut down. (After the temperature-difference circulation is started, it will be forced to stop after T63 minutes when the temperature-difference is less than W93 .) Anti-pipe-explosion circulation 1: when the water level of water tank 1 L1 is greater or equal to 1, if the temperature of heat collector 1 T3 is greater than 95 , the circulation pump P1 will be stopped for T61 minutes after each T60 minutes' circulation, and it circulates round again and again. Anti-pipe-explosion circulation 2: when the water level of water tank 1 L1 is greater or equal to 1, if the temperature of heat collector 2 L2 is greater than 95 , the circulation pump P2 will be stopped for T64 minutes after each T63 minutes' circulation, and it circulates round again and again. T1: Temperature of water tank 1
P1: Circulation pump
L1: Water level of water tank 1 T3: Temperature of heat collector 1
P2: Circulation pump
L2: Temperature of heat collector 2
T61: Stop duration of heat-collecting 1 circulation
T60: Duration of heat-collecting 1 circulation
T63: Duration of heat-collecting 2 circulation T64: Stop duration of heat-collecting 2 circulation W83: Starting temperature difference of temperature-difference circulation W84: Stopping temperature difference of temperature-difference circulation
Mode 4 T6
Water tank 1
DCF1 DCF2
L1
T3
P3
P1 DJR1
T4
09
HKG-IV Type Control Cabinet Temperature-difference circulation: when the water level of water tank 1 L1 is greater than or equal to 1, if the temperature difference T3 T1 is greater than or equal to W83 , P1 will be started; if the temperature difference is less than or equal to W84 , P1 will be shut down. (After the temperature-difference circulation is started, it will be forced to stop after T60 minutes when the temperature-difference is less than W83 .) Constant-temperature water release: when the water level of water tank 1 L1 is less than 3, if the temperature of heat collector T3 is greater than or equal to W81, enable DCF2; if the temperature heat-collector T3 is less than or equal to stopping temperature W82 , shut down DCF2, or the water level of water tank 1 L1 is equal to 4, turn it off after the time delay of 30 minutes. Anti-pipe-explosion circulation 1: when the water level of water tank 1 L1 is greater of equal to 1, if the temperature of heat collector T3 is greater than 95 , the circulation pump P1 will be stopped for T61 minutes after each T60 minutes' circulation, and it circulates round again and again. T1: Temperature of water tank 1
P1: Circulation pump
L1: Water level of water tank 1
DCF2: Discharge solenoid valve
T3: Temperature of heat collector
W81:Starting temperature of constant-temperature water release T61: Stop duration of heat-collecting 1 circulation
T60: Duration of heat-collecting 1 circulation W82: Stopping temperature of constant water-release
W83: Starting temperature difference of temperature-difference circulation W84:Stopping temperature difference of temperature-difference circulation
Mode 5 (Constant-temperature water supply) P3 Water tank 2
Water tank 1
T3
DCF2
L1
T6
L2
P1 T1
T4
DJR1
T5
P2
T2 DJR2
DCF1
Temperature-difference circulation: when the water level of water tank 1 L1 is greater than or equal to 1, if the temperature difference T3 T1 is greater than or equal to W83 , P1 will be started; if the temperature difference is less than or equal to W84
, P1 will be shut down. (After the temperature-difference circulation is started,
it will be forced to stop after T60 minutes when the temperature-difference is less than W83 .) Inter-water tanks temperature-difference circulation: when water level of water tank 1 L1 is greater than or equal to 1 and the water level of water tank 2 L2 is greater than or
10
HKG-IV Type Control Cabinet equal to 1, if T1-T2 is less than or equal to temperature difference is less than or equal to
W83 W84
, P2 will be started; when the , or the temperature of water tank
2 T2 is greater than or equal to W95, P2 will be shut down. Anti-freezing circulation between two water tanks: when water level of water tank 1 L1 is greater than or equal to 1 or when water level of water tank 2 L2 is greater than or equal to 1, when the temperature of anti-freezing sensor T5 is less than W87, P2 will be started, when the temperature of anti-freezing sensor T5 is greater than or equal to W87+5 , P2 will be shut down. Anti-pipe-explosion circulation 1: when the water level of water tank 1 L1 is greater or equal to 1, if the temperature of heat collector T3 is greater than 95 , the circulation pump P1 will be stopped for T61 minutes after each T60 minutes' circulation, and it circulates round again and again. Automatic water replenishing A. Water replenishing at constant water level: when the water level of water tank 2 L2 is lower than water level 3 and the temperature of water tank 1 T1 is less than 60 , DCF1 will be started to replenish water until the temperature of water tank 2 T2 is greater or equal to W95+3 or the water level of water tank 2 reaches water level 4. B. Temperature-controlled water replenishing: when the water temperature in water tank 2 T2 is greater or equal to W95+3, and the water level of water tank 2 L2 is less than 4, DCF2 will be started to replenish water; when the water level of water tank 2 L2 reaches water level 4 or the temperature of water tank 2 is less than or equal to =W95, DCF2 will be shut down to stop water replenishing. C. Water replenishing at low water level: when the water level of water tank 2 L2 is less than water level 2, DCF1 will be started for forced water replenishing, and stop water replenishing when water level of water tank 2 L2 is greater or equal to water level 3. D. Manual water inlet and cutting-off of water supply: press water inlet key so that it flickers; when the water level of water tank 2 L2 is less than set water level of water tank H77 , DCF1 will be started for water inlet, and turn it off 30 seconds later when set water level is reached. Another pressing water inlet key during water inlet will shut it down. E. Overheating protection: when the temperature of heat collector T3 is greater than 95 , it's not allowed to turn on DCF1, and water inlet is not supported by the system. T1: Temperature of water tank 1
T3: Temperature of heat collector
T2: Temperature of water tank 2
T5: Temperature of anti-freezing sensor
P1: Circulation pump 1 L1: Water level of water tank 1 DCF1: Solenoid valve 1 P2: Circulation pump 2 L2: Water level of water tank 2 DCF2: Solenoid valve 2 H77: Set water level of water tank W87: Starting temperature of anti-freezing W83: Starting temperature difference of temperature-difference circulation W84: Stopping temperature difference of temperature-difference circulation W95: Set water temperature of water tank 2
11
HKG-IV Type Control Cabinet 2. Water inlet function Note: 1. It is required to ensure that evacuated collector tube is not a torrid empty tube when turning on the machine for trial or starting various water inlet functions so as to avoid explosion of tube. 2. T1 and L1 represent the water temperature and water level of single-water-tank project, while T2 and L2 represent that of double-water-tank project.3. The water inlet channel is only applicable to Mode 1 and Mode 4. Timed water inlet
When the system is in water inlet state, drops will flicker.
water
Manual water inlet and cutting-off of water supply: press water inlet key so that it flickers; when the water level of water tank L1 (L2) is less than set water level of water tank H77 , DCF1 will be started for water inlet, and turn it off 30 seconds after set water level is reached. Another pressing water inlet key during water inlet will turn it off. Temperature-controlled water inlet: when water level of water tank L1 (L2) is less than 4, if the temperature of water tank T1 (T2) is greater or equal to set water temperature of water tank W85 (W95) + 5, DCF1 will be started for water inlet, and immediately turn it off when the temperature of water tank is less than or equal to W85 (W95), or turn it off 30 seconds after the water level of water tank L1 (L2) reaches water level 4. Timed water inlet: starting/stopping time/ stopping water level of five timed water inlets (T00/T01/H71, T02/T03/H72, T04/T05/H73, T06/T07/H74 and T08/T09/H75): time can range from 00:00 to 23:59, and water level can range form 1 to 4. Press the timed water inlet key, it will be in timed water inlet state, and timed water inlet is lit, CDF1 will be started for water inlet if the water level of water tank L1 (L2) is less than H71 when it comes to the time of timed water inlet T00, and DCF1 will be shut down 30 seconds after the water level of water tank Lk1 (L2) is greater or equal to H71; or immediately DCF1 will be shut down when it comes to T01, and the other 4 water inlets shall be operated in the same way. Constant-level water inlet: when the water level of water tank L1 (L2) is lower than the water level of constant-water-level water inlet H76, immediately DCF1 will be started for water inlet, when the water level of water tank L1 (L2) is greater or equal to the set stopping water level of water tank H77 , shut down DCF1 30 seconds later. Overheating protection: when the temperature of heat collector T3 or L2 (L2 is the temperature of heat collector 3 under Mode 3) is greater than 95 , it's not allowed to turn on DCF1, and water inlet is not supported by the system.
12
HKG-IV Type Control Cabinet 3. Pipeline circulation function Note: 1. T1 and L1 represent the water temperature and water level of pipeline circulation of single-water-tank project, while T2 and L2 represent that of double-water-tank project. 2. When the pipeline circulation pump is started, the three arrows in the right triangle will chase one another; 3. The function of timed pipeline circulation is removed in Mode 5 (constant-temperature water supply).
Manual pipeline circulation: press the Heat-collecting method
Inspection
Electric Intelligent 2 Timed electric Set heating 2 heating 2 Water inlet
Timed water inlet
Timed electric Electric heating 1 Intelligent 1 heating 1 Timed water use
Pipeline circulation
Pipeline circulation
Pipeline circulation
key so that it flickers, if the water level of water tank L1 (L2) is greater or equal to 1, and the temperature of water tank T1 (T2) is greater than the maintaining temperature of pipeline W86. P3 will be shut down when the temperature of pipeline T6 is less than the maintaining temperature of pipeline W86 . Or immediately stop circulation by pressing pipeline circulation key again during circulation. (When timed water-use state is started, water pump P6 and P3 are operated simultaneously.)
Timed constant-temperature circulation: within the set period T32-T33 and T34-T35, if water level of water tank L1 (L2) is greater or equal to 1, and the temperature of water tank T1 (T2) is greater than the maintaining temperature of pipeline W86. P3 will be started when the temperature of pipeline T6 is less than maintaining temperature of pipeline W86
-5. After circulation, P3 will be shut down, when the temperature of
pipeline T6 is greater than or equal to
maintaining temperature of pipeline
. (It will
automatically be turned off after the longest circulation duration of T100) Timed pipeline circulation: starting time of the 5 timed circulation (T40, T42, T44, T46 and T48), and the time can range from 00:00 to 23:59. Press is in timed water use state, and
Timed water use
timed water use
so that it
is lit. P3 will be started for
circulation if the water level of water tank L1 (L2) is greater than or equal to 1 when it comes to T40, and the circulation will stop after T100 minutes; the other 4 timed circulations shall be operated in the same way. (When timed water use state is started, timed constant-temperature circulation is removed) Anti-freezing circulation: P3 will be started for circulation when the water level of water tank L1 (L2) is greater than or equal to 1, and the temperature of pipeline T6 is less than W87. P3 will be shut down to stop circulation when the temperature of pipeline T6 is greater than or equal to W87+5. (When timed water-use state is started, water-use pump P6 and P3 are operated simultaneously.)
13
HKG-IV Type Control Cabinet 4. Electric heating function of water tank 1 Intelligent
Timed
Heat-collecting method
Inspection
Electric Intelligent 2 Timed electric Set heating 2 heating 2 Timed water inlet
Water inlet
Timed electric Electric heating 1 Intelligent 1 heating 1 Pipeline circulation
Timed water use
Heat-collecting method
Inspection
Electric Intelligent 2 Timed electric Set heating 2 heating 2 Timed water inlet
Water inlet
Timed electric Electric heating 1 Intelligent 1 heating 1 Pipeline circulation
Timed water use
Heat-collecting method
Inspection
Electric Intelligent 2 Timed electric Set heating 2 heating 2 Water inlet
Timed water inlet
Timed electric Electric heating 1 Intelligent 1 heating 1 Timed water use
Pipeline circulation
Note: When electric heating is started, three stroke segment points under the electric heating symbol are displayed circularly at different time.
Manual electric heating: is lit after the electric heating 1 key is pressed, DJR1 will be started for heating if the water level of water tank 1 L1 is greater than or equal to 1, and the temperature of water tank 1 T1 is less than the set temperature W85 -5, and DJR1 will be shut down to stop heating when the temperature of water tank 1 T1 is greater than or equal to the set temperature W85 . Timed electric heating: (starting/stopping time of 5 timed electric heating are respectively T10/T11, T12/T13, T14/T15, T16/T17 and T18/T19). After the timed electric heating 1 key is pressed, it is in timed electric heating state, timed and are lit. DJR1 will be started for heating if the water level of water tank 1 L1 is greater than or equal to 1 and the temperature of water tank 1 T1 is less than the set temperature W85 -5 when it comes to T10. DJR1 will be shut down to stop heating when the temperature of water tank 1 T1 is greater than or equal to the set temperature W85 ; or immediately DJR1 will be shut down when it comes to T11, and the other four timed electric heating are operated in the same way. Intelligent heating: after the Intelligent key is pressed, Intelligent is lit, thus electric heating function is started. When it comes to the clock-controlled set intelligent heating time T54, DJR1 will be started when the temperature of water tank is less than 25 within 2 hours (If the water level is lower than level 1, turn on water inlet first until the water level is higher than level 1, then turn on electric heating), DJR1 will be shut down when it reaches 30 ; DJR1 will be started when the temperature of water tank is lower than 35 within 2 to 4 hours, and DJR1 will be shut down when it reaches 40 ; from the forth to the sixth hour, DJR1 will be started when the temperature of water tank is lower than the set temperature W85 , and DJR1 will be shut down when it reaches the set temperature W85 , this function of the current day is removed, but the Intelligent is still lit. When it is pressed again, the Intelligent indication is off, thus intelligent electric heating function is turned off.
14
HKG-IV Type Control Cabinet Anti-freezing heating: if the temperature of water tank 1 T1 is less than anti-freezing starting temperature W87+5 , and the water level of water tank is greater than or equal to 1, DJR1 will be started for heating, when T1 is greater than or equal to W87+10 , DJR1 will be shut down to stop heating. When there is no water, start dry burningresistant water inlet, thus ensuring certain temperature to resist freezing. Dry burning-resistant function: when the temperature condition of electric heating is met and the water level of water tank L1 is lower than level 1, DCF1 will be started automatically, and stop water inlet 30 seconds after the water level is greater than or equal to level 1, and then reDJR1 will be started. (When the water level L1 is greater or equal to 1 in Mode 5, reDJR1 will be started after 30 seconds.) 5. Electric heating function of water tank 2 Electric heating control method is the same as the electric heating function of water tank 1. Parameters needing to be set: starting/stopping time of timed electric heating (T20/T21, T22/T23, T24/T25, T26/T27 and T28/T29), starting time of T55 intelligent electric heating and the set temperature of water tank 2 W95 (45 by default) Sensors include: water tank 2, water temperature T2, and water level L2 Actuator includes: DJR2 6. Anti-freezing control function
Anti-freezing circulation
Anti-freezing of heat-collecting 1: when the temperature of antifreezing sensor T4 is less than anti-freezing starting temperature W87, circulation pump P4 is started, (the three arrows of the triangle symbol of anti-freezing circulation chase one another), when T4 is greater than or equal to W87+5 , P4 is turned off. Anti-freezing of heat-collecting 2: when the temperature of antifreezing sensor T5 is less than the anti-freezing starting temperature W87, circulation pump P5 is started, (the three arrows of the triangle symbol of anti-freezing circulation chase one another), when T5 is greater than or equal to W87+5 , circulation pump P5 is turned off.
7. Timed water-use function
Timed water use
Note: The timed water-use method is only applicable to Mode 1 to Mode 4
Timed water use: starting/stopping time of five timed water uses: (T40/T41, T42/T43, T44/T45, T46/T47 and T48/T49). Press the water use
key, the
timed water use
timed
is lit, and it will be in timed
water use state; when it comes to the timed water-use time T40, water pump P6 is started and water drops flicker, and water pump P6 is turned off at T41; the other 4 water uses shall be operated in the same way.
15
HKG-IV Type Control Cabinet 8. Function of anti-explosion switching-off In case of the recovery of power supply after power outage, when the temperature of heat collector is greater than or equal to 90
and the
temperature difference between heat collector and water tank is greater than 30 , all function of heat-collecting temperature-difference circulation is invalidated; when the temperature of heat-collector is less than 90 or the temperature difference is less than or equal to 25 ,the function of heat-collecting temperature-difference circulation is recovered. The first position of toggle switch SW2 on the main control panel
SW2
is in ON state by default, it has the function of anti-explosion switchingoff, meanwhile, the green indicator light is always off; when the first position of toggle switch SW2 is in ON state, the function of antiexplosion switching-off is invalidated, meanwhile, the green indicator light LED2 is flickers. 9. Memory function It can memorize all equipment parameters and operation state. 10. Error code display of sensor No. 1
Name Temperature of water tank 1 T1
Error code E1
2
Water level of water tank 1 L1
E7
3
Temperature of water tank 2 T2
E2
4
Water level of water tank 2 L2
E8
5
Temperature T3
E3
6
Temperature T4
E4
7
Temperature T5
E5
8
Temperature T6
E6
11. Reset function Setting of toggle switch: the fourth position of toggle switch SW1 on the main control panel is the switch for reset setting, when the duration that it stays in ON state is more than 5 seconds, dial it to non-ON state, the buzzer will make a sound, thus the system resets, and it rovers to the factory default. The factory defaults at other positions of the toggle switch have already been set, and laypeople are not allowed to touch it .
16
HKG-IV Type Control Cabinet Connection method Sensor input connection RVVP3 x0.12mm2 three-core shielding line is adopted in sensor connection. After the wires of all sensors are threaded through slots, they shall be connected to the corresponding position on the terminals successively according to connection instructions. Shielding lines of each signal wire shall be connected to the shielding position of water tank sensor. The connection method of Mode 1, 2, 4 and 5 are shown in Figure A, and that of Mode 3 is shown in Figure B. Red Yellow Blue Red Yellow Blue Red Yellow Blue Red Yellow Blue
Red Yellow Blue Ground Red Yellow Blue Ground
Red Yellow Blue Red Yellow Blue Red Yellow Blue Red Yellow Blue
Yellow
Blue Red Red Yellow Blue Ground
Power supply input connection All power wires on control and display system shall be connected to leakage breaker QF7, if there are two electric heating, the power wire of electric heating 2 shall be connected to leakage breaker -QF8. Water pump output connection The power of each water pump (solenoid valve) is greater or equal to 1kW, and only on
and
null
line are needed to be connected. It is required to use RVV2x1.0mm2
line for connection, RVV3x1.0mm2 line shall be used for the water pump with earth wire, so as to connect the earth line to the earthing bolt on the right side of control cabinet. When electrically-operated valve is connected, the power of it is less than or equal to 1kW, switch it on for connecting on and switch it off for connecting off . The neutral wire shall be connected to null , and RVV3x1.0mm2 cable shall be adopted. The connecting terminal on temperature controller is the connecting position specially prepared for the electric-heating water tank having dry burning-resistant function, and the positions can be exchanged. If anti-parching function of the water tank is not used, but electric heating function is in application, it is required to short circuit these two terminals with the power wires over RVV1.0mm2, otherwise the electric heating function can not be started. On Null Off On Null Off On Null Off On Null Off On Null Off
On Null Off
Constant-temperature Temperature-difference water-release valve of Water inlet Pipeline Anti-freezing temperature-difference solenoid valve1 circulation pump circulation pump circulation pump 1 circulation pump 2
Temperature Water inlet solenoid Temperature controller of valve 2 of timed water controller of electric heating 1 electric heating 2 pump
17
HKG-IV Type Control Cabinet Electric heating output connection Electric heating load line shall be strictly matched with the power of each phase, which will be shown by taking the four-wire-and-three-phase power supply as the example: Total electric heating power (Unit: kW)
3 1 36 16
Single-phase wire diameter (Unit:mm2) Total electric heating power (Unit: kW) Single-phase wire diameter (Unit:mm2)
4.5 1.5 45 25
6 2.5 54 35
9 4 70 50
18 6 80 70
24 10 90 95
30 16 108 120
Attentions The control cabinet shall be installed in dry and waterproof room. The inner container of the control cabinet and water tank of water heating project must be connected to earth reliably, thus it can be put into application. The stainless binding post on control cabinet and water tank shall be connected to ground reliably. It shall be avoided to lead the sensor signal line and the load power line together within one pipeline to room, so as to prevent disorder operation of control cabinet resulted from electromagnetic interference. Lightning protection device must be provided in large water-heating project, and the height of lightning rod shall be H=2+R/1.5 (unit: m), and the water-heating project must be located within the effective protection area of lightning rod, as shown in the following figure. R Lightning Schematic Diagram
Lightning rod
H The dash area refers to effective protection area
It is required to inspect the safety protection measures on water-heating project regularly. It is strictly prohibited to change the connection of the circuits in control cabinet. There must be professional electrician in charge of the installation of control cabinet.
18
HKG-IV Type Control Cabinet Maintenance Guide Phenomenon
Causes
Troubleshooting method
Fuse is broken
Replace the fuse Check leakage breaker and lead, then connect the power Call professional to maintain
The power is not connected
Panel of control cabinet does not display
Leakage breaker trips
Water temperature is displayed abnormally
Internal contact is bad Sensor is wired wrongly or short circuited The sensor does not work
Call professional to maintain
The instrument is faulted
Call professional to maintain
The temperature is set too low
Reconnect according to instructions Replace sensor Reset the temperature
Replace electric heater The electric heater does not work The contactor does not work Call professional to maintain or on-line contact is bad Call professional to maintain The instrument is faulted Select high-lift pump and start up Water pressure is low
Electrical heating cannot be started
It does not fill water automatically
The instrument is faulted
Call professional to maintain
Control Cabinet Accessories I. HYC-WA3 water level and temperature sensor 1. Installation method: First, pass the sensor through bushing and tee joint, and insert it into the large water tank carefully from water nozzle of sensor (to prevent temperature probe being broken) to make all water level probes of sensor drop into tank naturally, then fix the bushing and tee joint and screw down the nut to fix sensor, thus ensuring total face-up of sensor. Drain pipe
Water nozzle
Nylon nut
This face up Tee joint Sensor
Water level probe
One-inch tee joint One-to-four bushing
Water temperature probe
One-inch nozzle
Engineering tank Installation Diagram
19
HKG-IV Type Control Cabinet Sensor signal wire shall adopt RVVP3x0.12mm2 three-core shielding line. During installation, connect the signal wires and outgoing lines of sensor correspondingly according to red , yellow , blue and shielding line , and adopt insulation and waterproof measures at connection part (see the figure below).
Shielding line
Red wire
Blue wire
Schematic Diagram of Outgoing Line of Sensor
Yellow wire
Diagram of Outgoing Line of Sensor
2. Attentions Pipe joint must be sealed well,free from seepage and leakage. Sensor must be wired correctly with colors connected correspondingly as per requirements, or else error in action may be incurred. Sensor must be connected in strictaccordance with the diagram, with thebend vertically down and vent pipe up. Sensor wire introduced from roof to indoor must have three-core shielding line adopted. II. Temperature sensor 1. Installation method (1) Wrap the parts of sensor close to pipes with adhesive tape and perform heat preservation at the outermost. Sensor Adhesive tape and insulating layer
Pipeline
Tee joint
(2) Put sensor into blind pipe.
Sensor
Blind pipe
Pipeline
Connect pipeline here
2. Connection method: Connect red, yellow and blue shielding nets correspondingly. Red
Yellow Blue
20
HKG-IV Type Control Cabinet Parameter Table Hereinbelow are parameters set for supervisory level Parameter Software Meaning code SN T00 Start-up time of the first timed water inlet 0 T01 Stop time of the first timed water inlet 1 T02 Start-up time of the second timed water inlet 2 T03 Stop time of the second timed water inlet 3 T04 Start-up time of the third timed water inlet 4 T05 Stop time of the third timed water inlet 5 T06 Start-up time of the fourth timed water inlet 6 T07 Stop time of the fourth timed water inlet 7 T08 Start-up time of the fifth timed water inlet 8 T09 Stop time of the fifth timed water inlet 9 T10 Start-up time of the first timed electric heating 10 T11 Stop time of the first timed electric heating 11 T12 Start-up time of the second timed electric heating 12 T13 Stop time of the second timed electric heating 13 T14 Start-up time of the third timed electric heating 14 T15 Stop time of the third timed electric heating 15 T16 Start-up time of the fourth timed electric heating 16 T17 Stop time of the fourth timed electric heating 17 T18 Start-up time of the fifth timed electric heating 18 T19 Stop time of the fifth timed electric heating 19 T20 Start-up time of the first timed electric heating (tank 2) 20 T21 Stop time of the first timed electric heating (tank 2) 21 T22 Start-up time of the second timed electric heating (tank 2) 22 T23 Stop time of the second timed electric heating (tank 2) 23 T24 Start-up time of the third timed electric heating (tank 2) 24 T25 Stop time of the third timed electric heating (tank 2) 25 T26 Start-up time of the fourth timed electric heating (tank 2) 26 T27 Stop time of the fourth timed electric eating (tank 2) 27 T28 Start-up time of the fifth timed electric heating (tank 2) 28 T29 Stop time of the fifth timed electric heating (tank 2) 29 T50 Start-up time for timing cycle of heat collecting 1 30 T51 Stop time for timing cycle of heat collecting 1 31 T52 Start-up time for timing cycle of heat collecting 2 32 T53 Stop time for timing cycle of heat collecting 2 33 T54 Start-up time of intelligent electric heating 1 34 T55 Start-up time of intelligent electric 35 H71 Standing level of the first timed water inlet 36 H72 Standing level of the second timed water inlet 37 H73 Standing level of the third timed water inlet 38 H74 Standing level of the fourth timed water inlet 39 H75 Standing level of the fifth timed water inlet 40 H76 Inlet level of constant level 41 T60 Cycle time of heat collecting 1 42 T61 Cycle stop time of heat collecting 1 43 T63 Cycle time of heat collecting 2 44 T64 Cycle stop time of heat collecting 2 45 W81 Start-up temperature of drainage at constant temperature (heat collecting 1) 46 W82 Stop temperature of drainage at constant temperature (heat collecting 1) 47 W83 Start-up temperature difference of temperature difference circulation (heat collecting 1) 48 W84 Stop temperature difference of temperature difference circulation (heat collecting 1) 49
21
Set range 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 1 1 1 1 1 0 00 00 00 00 00 00 00 00
23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 4 4 4 4 4 3 99 99 99 99 99 99 99 99
59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59
Default
Level
00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 08 00 19 00 00 00 00 00 12 00 12 00 Equal to H77 Equal to H77 Equal to H77 Equal to H77 Equal to H77 0 level 10min 20min 10min 20min 50 45 10 2
Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision Supervision
HKG-IV Type Control Cabinet 50 51 52 53 54 55
W87 W91 W92 W93 W94
Start-up temperature of anti-freezing Start-up temperature of drainage at constant temperature (heat collecting 2) Stop temperature of drainage at constant temperature (heat collecting 2) Start-up temperature of temperature difference circulation (heat collecting 2) Stop temperature of temperature difference circulation (heat collecting 2) T100 Duration of timed circulation at constant temperature Hereinbelow are parameters set for user level Parameter Software SN code
Meaning
0 T32 Start-up time of the first timed circulation at constant temperature 1 T33 Stop time of the first timed circulation at constant temperature 2 T34 Start-up time of the second timed circulation at constant temperature 3 T35 Stop time of the second timed circulation at constant temperature 4 T40 Start-up time of the first timed water use 5 T41 Stop time of the first timed water use 6 T42 Start-up time of the second timed water use 7 T43 Stop time of the second timed water use 8 T44 Start-up time of the third timed water use 9 T45 Stop time of the third timed water use 10 T46 Start-up time of the fourth timed water use 11 T47 Stop time of the fourth timed water use 12 T48 Start-up time of the fifth timed water use 13 T49 Stop time of the fifth timed water use 14 W85 Set water temperature of tank (tank 1) 15 W86 Holding temperature of pipelines 16 W95 Set water temperature of tank (tank 2) 17 H77 Set standing level of tank 18 T99 Timing clock The shaded area refers to system reserved parameters
00 00 00 00 00 00
99 99 99 99 99 99
8 50 45 10 2 10min
Supervision Supervision Supervision Supervision Supervision Supervision
Set range
Default
Level
00 00 23 59 00 00 23 59 00 00 23 59 00 00 23 59 00 00 23 59 00 00 23 59 00 00 23 59 00 00 23 59 00 00 23 59 00 00 23 59 00 00 23 59 00 00 23 59 00 00 23 59 00 00 23 59 00 99 00 99 00 99 2 4( H76+1) 00 00-23 59
00 01 23 59 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 45 40 45 4 level Factory settings
User User User User User User User User User User User User User User User User User User User
Packing List Name and specifications
Quantity
Host machine of HKG-IV control cabinet
1 set
Water temperature and level sensor Temperature sensor Copper blind pipe
Remarks
Configure 1, 2, 1, 1 and 2 for mode I, mode II, mode III, mode IV and mode V respectively; Such sensor will be unnecessary when embedded sensor is configured for large tank. Configure 3, 4, 5, 3 and 4 for mode I, mode II, mode III, mode IV and mode V respectively;
Three-core shielding line
100m
Instruction book
1
Cable ties
40pieces
Shrinkable tube
18pieces
3 20mm
Keys
1set
Keys to case
22
Including quality certificate and warranty card
Announcements: Himin Solar Co., Ltd reserves to change the product design and the specification but have no notice of right. Himin Solar Co., Ltd reserves the final explanation rights to the instruction. All data has been reviewed carefully. Himin Solar Co., Ltd won't be reponsible to any outcome resulted from publish mistake. Version No.: 2010-06-15