Instructions

21 downloads 12831 Views 63KB Size Report
115 VAC. Enclosure. NEMA 4x, 5" x 7" polycar- bonate. Relays. SPST. Relay Rating ... connect to relay outputs, as shown in the Connections diagram. Note that ...
FS20 Dual Flow Switch Instructions Installation

Designed to be used with a variety of SeaMetrics meters, the FS20 signals when flow reaches critical setpoints. Two setpoints are provided, a low and a high setting. When flow falls below the low or rises above the high, SPDT relay contacts close to actuate whatever alarms or controls are connected to them. Setting is by means of DIP switches, and setpoints are in pulses per minute. Output lights give visual indication that flow limit has been reached.

Mounting. To gain access to the mounting screw holes, remove the front clear cover. Mounting screw holes are at the four corners, under the cover screws. Mark the centers of these holes, using the box or the enclosed template, and drill. Finally, insert screws through the corner holes and tighten.

DIS CO NT INU ED

General Information

Specifications Power Enclosure

Relays Relay Rating

Setpoint Range

Setpoint Hysteresis Sensor Power

Terminal Access. Terminals are on the back side of the printed circuit board. Remove the front clear cover, then remove the four front plate screws. Turn the printed circuit board over to reach the terminals. Connect Flow Meter. Bring the flow meter input cable into the unit through the appropraite strain relief, then connect following the Connections diagram. Either twowire (dry contact) or three-wire (solid state) flow meter sensors can be used.

115 VAC NEMA 4x, 5" x 7" polycarbonate SPST 5 A resistive at 115 VAC 5 A at 24 VDC 1 - 33,000 pulses/ minute 6% 25 mA at 12 VDC nominal

Connect Alarm Relay(s). Bring alarm output cable(s) into the unit through the appropriate strain reliefs and connect to relay outputs, as shown in the Connections diagram. Note that depending on setting, relays may energize when the unit is first powered up. If this presents a hazard, disconnect any devices on the other end of the cable(s) until settings have been made and tested.

Features

Power switch and indicator

Low Flow Setting

High Flow Setting

OFF ON OFF ON

L O W

INPUT

Input Indicator

OFF

1 2 4 8 16 32 64 128

Setting equals the sum of the switches 256 turned "ON". 512 1024 2048 4096 8192 16384 32768

F L O W

FS20

FLOW SWITCH

LOW FLOW

ON

1 2 4 8 16 32 64 128

H I G H

Setting equals the sum of the switches 256 turned "ON". 512 1024 2048 4096 8192 16384 32768

F L O W

HIGH FLOW

MANUAL

Cover screws and box mounting screw holes

MANUAL

Output Indicators

INC. KENT, WA

Internal 10 Amp replaceable fuse Meter input strain relief

Power input cord (6’ length)

Low flow relay output

High flow relay output

PUB 19128-1000 Page 1 of 2

FS20 Connections Diagram

DRY CONTACT TYPE METER (MR,WPR)

GND SIGNAL

SOLID STATE TYPE METER (ME,IP,WT)

DIS CO NT INU ED

GND SIGNAL +12 VDC

Hot Neutral Ground

EXTERNALLY-PACED METERING PUMP

NO NC N G

NO NC N G

PUMP+

GND SIGNAL

110 VAC Input

Normally Open Normally Closed Common Unused

High Flow Relay

Unused Common Normally Closed Normally Open

SOLID STATE TYPE METER (ME,IP,WT)

+12 VDC

Low Flow Relay

Setting

See example diagram for method of setting. Note that Low Flow energizes the relay when flow drops below the set point, and High Flow energizes when it rises above the set point.

Connect Power. If using the power cord provided, wait to plug it in until after the front panel has been replaced. Terminal connection is only necessary for conduit installations. Remove the power cord provided and connect power, following the Connections diagram. Do not energize the circuit until the front panel has been replaced.

Example: The meter produces 50 pulses per gallon. Low-flow relay output is desired at 20 gallons per minute. 50 pulses/gallon X 20 gallons per minute = 1,000 pulses/minute Set Low Flow to 1,000.

Set Trip Points. The DIP switches under the front clear cover are used to set trip point frequencies. Example

Replace Front Panel. Reverse the removal procedure.

OFF

1000 Pulses per minute

Determine Trip Points. Trip point frequencies are in pulses per minute. To calculate, multiply the pulses per gallon provided by the meter (“K-factor”) by the gallons per minute at which the alarm output is desired.

2 of 2

20419 80th Ave. So., Kent WA. 98032 USA Phone: 253-872-0284 Fax: 253-872-0285 www.seametrics.com 1-800-975-8153

L O W

F L O W

ON

1 2 4 8 16 32 64 128

256 512 1024 2048 4096 8192 16384 32768

Setting equals the sum of the switches turned "ON".