inspection or brush exchange over a long time because of brushless construction
switch ... Type Revolving-field type AC Generator (Brushless). Excitation ...
AVK/Mitsubishi Diesel Generators from 5-44kVA. AVK/Mitsubishi Diesel ...
Engine Specifications. Alternator. Compact Version. kVA. Cos φ. 0.8. Engine.
Range.
systems in off-grid renewable energy installations, in ... an off-grid system designed as part of the Open- ... The general structure of the diesel engine model is.
above, the fuel consumption, exhaust emissions, mass, volume and acquisition costs of four arrangements are estimated and ..... are defined as ηx, power factors as P.F.x, active power as Px ... the minimum power rating for each generator set.
Shell Rimula R6 LM. (SL1407). SAE 10W-40. X00065012 ..... (-40 °F). Refer to
Variant B. Variant A: Storage with filled media circuits under normal conditions. 1.
Abstract: This paper deals with the numerical modeling of a diesel generator set used as .... voltage) and the load connection is typically at least 10-15 seconds.
Heavy-Duty Engine - Rugged 4-cycle industrial diesel delivers reliable power,
low ... operator interface to the generator set, manual and remote start/stop
control ...
Va multumim pentru achizitionarea unui generator diesel KIPOR. Acest manual
de ... Nu alimentati cu combustibil in timp ce motorul functioneaza. Curatati cu o ...
Generator Set Specifications. Governor Regulation Class. ISO 8528 G2. Voltage
Regulation, No Load to Full Load. +/- 1%. Random Voltage Variation. +/- 1%.
Jan 3, 2012 ... Product identification numbers determine service parts. Record the product ...
Record the controller description from the generator set operation ...
Residential/Commercial Generator Sets ... Product identification numbers
determine service parts. ... Record the controller description from the generator
set.
Controller Identification. Record the controller description from the generator set
operation manual, spec sheet, or sales invoice. Controller Description ...
CAT C15-500_EN [email protected]. Date: 11 November 2013. Technical data
Diesel Generator Set. CAT C15- ... CBK 3pol manual, fixed mount rear. 800 A / 50
...
www.avesco.ch. Ref: CAT C18-605_EN [email protected]. Date: 11 November
2013. Technical data Diesel Generator Set. CAT C18-605. Output Ratings with ...
powered by Cummins B Series engines, are rated at 1500 RPM and conform to ...
suitable for 50 Hz, 3 phase, 4 wire system, conforming to BS .... 6BTAA 5.9G1-I.
BHP ... 120 x 1. 185 x 1 or 95 x 2. 240 x 1 or 120 x 2. (Al Armoured 3 1/2 core).
2 Joint Graduate Program in Bioinformatics, University of Arkansas at Little ... Student 2007, Office Professional 2007, Office Small Business 2007, Office ...
conditions, and operation and maintenance (O&M) .... for participation, testing methodology, and the ... labeling thresholds and testing methodology is still ..... Since a range of possible emissions reductions from application of each technology is
Introduction to Generators technical guide - Diesel Generator Sets ...
V10 ELECTRICITY GENERATION PLANT - PRESENTATION. CONTENTS. 1.
INTRODUCTION. 2 ... Extract from ISO8528-1:1993 Section 13 – Power Ratings ...
ELECTRICAL GRADUATE ENGINEERS’ TRAINING DAY PREPARED AND PRESENTED BY ANDREW WILLIAMS VOLUME TWO - PARTICULAR SPECIFICATION
V10
ELECTRICITY GENERATION PLANT - PRESENTATION
CONTENTS 1
INTRODUCTION
2
GENERATOR BASICS
3
INSTALLATION CONSIDERATIONS
4
SPACE PLANNING
5
COOLING and AIRFLOW
6
NOISE / VIBRATION
7
EXHAUST FLUE
8
FUEL SUPPLY
9
CONTROL SYSTEMS
10
OTHER ITEMS
ELECTRICAL GRADUATE ENGINEERS’ TRAINING DAY PREPARED AND PRESENTED BY ANDREW WILLIAMS
1 – INTRODUCTION Presentation by – Andrew Williams of Excel Power Ltd
Excel generator range from 22kVA to in excess of 3300kVA
ELECTRICAL GRADUATE ENGINEERS’ TRAINING DAY PREPARED AND PRESENTED BY ANDREW WILLIAMS
2 – GENERATOR BASICS Generator Definition -
Conversion of fossil fuel energy into electrical energy
Diesel Fuel Input
Heat Compression Ignition (diesel) Engine
Noise / Vibration Exhaust
AC Alternator
Heat
Electrical Output Engine Alternator
ELECTRICAL GRADUATE ENGINEERS’ TRAINING DAY PREPARED AND PRESENTED BY ANDREW WILLIAMS
Radiator
Local control panel
Engine Alternator
Alternator Terminal Box
ELECTRICAL GRADUATE ENGINEERS’ TRAINING DAY PREPARED AND PRESENTED BY ANDREW WILLIAMS
2000A – GENERATOR BASICS Application -
Source of standby power in the event of loss of mains power.
Power Output – Voltage Output –
kVA / kWe Low, Medium or High Voltage
Duty Rating –
ISO8528-1 Continuous (COP), Prime (PRP) or Standby (LTP) – see next slide
Step Load Restriction -
Turbo-charged engines have limited step load capability. Varies significantly dependant on engine manufacturer. Expect approx 50% on large units.
Load Considerations -
Harmonics – UPS loads, motor starting. Electronic engine speed governing.
Extract from ISO8528-1:1993 Section 13 – Power Ratings
ELECTRICAL GRADUATE ENGINEERS’ TRAINING DAY PREPARED AND PRESENTED BY ANDREW WILLIAMS
Extract from ISO8528-5 – Performance Class
Volts Drop
Volts Recovery Time
Steady State Frequency Band
Steady State Voltage Deviation
Governing Type
Frequency Drop
Freq Recovery Time
G1
-15%
10s
3.5%
-25%
10
2.5%
5%
G2
-10%
5s
2%
-20%
6
1.5%
2.5%
G3
-7%
3s
2%
-15%
4
0.5%
1%
Freq Recovery Tolerance
Important note - Different engines have different load characteristics – One 1000kW engine may accept 700kW in a single step and comply with G2 Another will only accept 500kW and still comply with G2 Therefore it is important to state what initial load step is required and what performance is required.
ELECTRICAL GRADUATE ENGINEERS’ TRAINING DAY PREPARED AND PRESENTED BY ANDREW WILLIAMS
3 – INSTALLATION CONSIDERATIONS Space Planning -
Large and heavy mechanical devices.
Cooling and airflow -
Significant amount of heat is rejected.
Noise / Vibration -
Unsilenced generator noise range is 85 to 115dB(A)
Exhaust Flue -
Combustion exhaust at around 500°C with noxious gases.
Fuel Supply -
Local day tanks and bulk storage tanks.
ELECTRICAL GRADUATE ENGINEERS’ TRAINING DAY PREPARED AND PRESENTED BY ANDREW WILLIAMS
4 – SPACE PLANNING
Consider -
Large and heavy mechanical devices. Installation route Plant replacement strategy Maintenance access Emergency escape routes
Typical Plant room installation – side elevation
ELECTRICAL GRADUATE ENGINEERS’ TRAINING DAY PREPARED AND PRESENTED BY ANDREW WILLIAMS
4b – SPACE PLANNING Continued…
Space Planning -
Typical sizes – Open generator sets (mm) 100kVA – 2260 L 500kVA – 3820 L 1000kVA – 4360 L 2000kVA – 6000 L 3300kVA – 6650 L
x x x x x
850 W 1250 W 1800 W 2325 W 2600 W
x x x x x
1560 H – 820kg 2165 H – 5050kg 2450 H – 8519kg 3240 H – 13800kg 3300 H – 21900kg
Typical outdoor canopy / container type installation – side elevation
ELECTRICAL GRADUATE ENGINEERS’ TRAINING DAY PREPARED AND PRESENTED BY ANDREW WILLIAMS
5 – Cooling and Airflow Cooling -
Engine jacket water removes some heat from the engine and is rejected by the radiator with an engine driven fan. This also collects the radiated heat from the engine and alternator and discharges it through the radiator.
Alternatively -
Remote radiator cooling – 65% of the full airflow is typically still required to deal with the radiated heat from the engine.
Aspiration air -
The engine also uses air in the combustion process. This is then discharged at high temperature via the exhaust flue.
ELECTRICAL GRADUATE ENGINEERS’ TRAINING DAY PREPARED AND PRESENTED BY ANDREW WILLIAMS
6 – Noise and Vibration
Noise -
Difficulty in reducing noise levels while maintaining adequate airflow to prevent overheating. 80 to 85dB(A) at 1m – standard ‘export’ type unit 75dB(A) at 1m – standard ‘UK’ type unit 55 – 65dB(A) at 1m – City centre / sensitive installations
Plant Room – Installations designs
The building structure itself must be of sufficient integrity. Various types of acoustic louvres and splitter attenuators are used to reduce the external noise to acceptable levels. Room within a room may be necessary for very low noise levels.
External –
Outdoor enclosed generators have similar requirements but the structure of the enclosure is designed and supplied by Excel Power.
Vibration -
Reciprocating engines vibrate and care must be taken to avoid rigid links between the set and the building or enclosure structure.
ELECTRICAL GRADUATE ENGINEERS’ TRAINING DAY PREPARED AND PRESENTED BY ANDREW WILLIAMS
ELECTRICAL GRADUATE ENGINEERS’ TRAINING DAY PREPARED AND PRESENTED BY ANDREW WILLIAMS
7 – Exhaust Flue
Flexible Bellows -
Prevents vibration from the engine being transmitted into the flue and building structure.
Silencers -
Fitted into exhaust run to prevent noise breakout at flue termination. Most load dependant noise difference.
Flue Route -
Double skinned stainless steel tube normally installed within a building riser or on an external face of the building, if planning allows.
Flue Termination -
Dependant on local planners but normally above roof line.
ELECTRICAL GRADUATE ENGINEERS’ TRAINING DAY PREPARED AND PRESENTED BY ANDREW WILLIAMS
8 – Fuel Supply
Fuel Consumption -
Approximately 200litres/hour per 1000kVA but is non-linear on part loads.
Local Daytank -
4 to 8 hours depending on set size with pumps to automatically refill.
Bulk Storage Tanks -
No maximum capacity limit – depends on the criticality of the installation.
ELECTRICAL GRADUATE ENGINEERS’ TRAINING DAY PREPARED AND PRESENTED BY ANDREW WILLIAMS
9 – Control Systems
2 Wire Start -
The Excel Generator starts on receipt of a signal.
Automatic Mains -
Excel Equipment monitors the mains and responds accordingly.
Synchronising -
Between various generators or with mains power (no-break return).
Changeover Panel -
ATS. Contactors, MCCB’s or ACBs to change between mains and generator supply.
ELECTRICAL GRADUATE ENGINEERS’ TRAINING DAY PREPARED AND PRESENTED BY ANDREW WILLIAMS