LG Room Air Conditioner - Appliance Factory Parts

0 downloads 171 Views 4MB Size Report
LG Room. Air Conditioner. SERVICE MANUAL. LG. MODEL: WG1805RY6,RAD-183A. WG2405RY6,RAD-243A. CAUTION website http://www.
website http://www.lgservice.com

LG

LG Room Air Conditioner SERVICE MANUAL MODEL: WG1805RY6,RAD-183A WG2405RY6,RAD-243A

CAUTION • BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL. • ONLY FOR AUTHORIZED SERVICE PERSONNEL.

Air Conditioner Service Manual

TABLE OF CONTENTS Safety Precautions..........................................................................................................................................3 Dimensions .....................................................................................................................................................5 Symbols Used in this Manual .....................................................................................................................5 Outside Dimensions ...................................................................................................................................5 Product Specifications ..................................................................................................................................6 Installation .......................................................................................................................................................7 Select the Best Location ...........................................................................................................................7 Installation Check .......................................................................................................................................7 How to Secure the Drain Pipe ....................................................................................................................7 Window Requirements ...............................................................................................................................8 Installation Kits Contents............................................................................................................................8 Suggested Tool Requirements ...................................................................................................................9 Cabinet Installation...................................................................................................................................10 Operation ......................................................................................................................................................12 Features ...................................................................................................................................................12 Control Locations Function of Controls ....................................................................................................12 Disassembly ..................................................................................................................................................14 Mechanical Parts......................................................................................................................................14 Air Handling Parts ....................................................................................................................................15 Electrical Parts .........................................................................................................................................16 Refrigerating Cycle...................................................................................................................................18 Schematic Diagram.......................................................................................................................................21 Electronic Control Device .........................................................................................................................21 Wiring Diagram.........................................................................................................................................22 Components Lation ..................................................................................................................................23 Troubleshooting Guide .................................................................................................................................24 Piping System ..........................................................................................................................................24 Troubleshooting Guide .............................................................................................................................25 Room Air Conditioner Voltage Limits........................................................................................................31 Exploded View ..............................................................................................................................................34 Replacement Parts List ................................................................................................................................36

2 Room Air Conditioner

Safety Precautions

Safety Precautions To prevent injury to the user or other people and property damage, the following instructions must be followed. ■ Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.

WARNING

This symbol indicates the possibility of death or serious injury.

CAUTION

This symbol indicates the possibility of injury or damage to property only.

■ Meanings of symbols used in this manual are as shown below.

Be sure not to do. Be sure to follow the instruction.

WARNING ■ Installation Do not use damaged power cord plugs, or a loose socket. • There is risk of fire or electric shock.

Always use the power plug and socket with the ground terminal. • There is risk of electric shock.

Service Manual 3

Safety Precautions

Do not modify or extend the power cord.

• There is risk or fire or electric shock.

Do not install, remove, or re-install the unit by yourself. • There is risk of fire, electric shock, explosion, or injury.

Be cautious when unpacking and installing the product. • Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator.

Do not store or use flammable gas or combustibles near the air conditioner. • There is risk of fire or failure of product.

Sharp edges

Gasolin

Be sure the installation area does not deteriorate with age. • If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.

4 Room Air Conditioner

Dimensions

Dimensions Symbols Used in this Manual This symbol alerts you to the risk of electric shock. This symbol alerts you to hazards that could cause harm to the air conditioner. NOTICE

This symbol indicates special notes.

Outside Dimensions 660

428

675 (770)

Model 18K Btu

24K Btu

Dimension W

mm(inch)

660(26")

660(26")

H

mm(inch)

428(16 27/32")

428(16 27/32")

D

mm(inch)

675(26 9/18")

675(269/18")

Service Manual 5

Specfications

Product Specifications Table -1

MODELS

ITEMS

WG2405RY7

WG1805RY6

POWER SUPPLY

1Ø, 208/230V, 60Hz

COOLING CAPACITY

17,500/18,000

23,500/23,800

INPUT

1,800/1,850

2,760/2,800

9.7

8.5

RUNNING CURRENT REFRIGERANT (R-22) CHARGE(g) OPERATING TEMPERATURE

720g(25.4oz)

830g(29.3oz)

INDOOR(°C)

27(DB),19(WB)

OUTDOOR(°C)

35(DB),24(WB)

EVAPORATOR

2 ROW 15 STACKS LOUVERED-FIN TYP

CONDENSER

2 ROW 19 STACKS,LOUVERED-FIN TYPE L-BENDING TYPE

FAN, INDOOR

TURBO

FAN, OUTDOOR

PROPELLER TYPE FAN WITH SLINGER-RING

FAN SPEEDS, FAN/COOLING

3/3

FAN MOTOR

6 POLES

OPERATION CONTROL

WIRELESS REMOCN

ROOM TEMP. CONTROL

THERMISTOR

AIR DIRECTION CONTROL

VERTICAL LOUVER(RIGHT & LEFT) HORIZONTAL LOUVER(UP & DOWN)

CONSTRUCTION PROTECTOR

SLIDE IN-OUT CHASSIS COMPRESSOR

INTERNAL OVERLOAD PROTECTOR

FAN MOTOR

INTERNAL THERMAL PROTECTOR

POWER CORD

3 WIRE WITH GROUNDING CORD-CONNECTED TYPE(ATTATCHMENT PLUG:OPTION)

DRAIN SYSTEM NET WEIGHT

DRAIN PIPE OR SPLASHED BY FAN SLINGER (lbs/kg)

OUTSIDE DIMENSION

(inch)

(W x H x D)

(mm)

6 Room Air Conditioner

130/60 26 x 16 27/32 x 26 9/16 660 x 428 x 675

147.7/67 26 x16 27/32 x 30 5/16 660 x 428 x 675

Specfications

Product Specifications Table -1

MODELS

ITEMS POWER SUPPLY

RAD-183A 1Ø, 208/230V, 60Hz

COOLING CAPACITY

17,500/18,000

INPUT

1,800/1,850

RUNNING CURRENT

9.7

REFRIGERANT (R-22) CHARGE(g)

720g(25.4oz)

OPERATING

INDOOR(°C)

27(DB),19(WB)

OUTDOOR(°C)

35(DB),24(WB)

TEMPERATURE EVAPORATOR

2 ROW 15 STACKS LOUVERED-FIN TYP

CONDENSER

2 ROW 19 STACKS,LOUVERED-FIN TYPE L-BENDING TYPE

FAN, INDOOR

TURBO

FAN, OUTDOOR

PROPELLER TYPE FAN WITH SLINGER-RING

FAN SPEEDS, FAN/COOLING FAN MOTOR

3/3 6 POLES

OPERATION CONTROL

WIRELESS REMOCN

ROOM TEMP. CONTROL

THERMISTOR

AIR DIRECTION CONTROL

VERTICAL LOUVER(RIGHT & LEFT) HORIZONTAL LOUVER(UP & DOWN)

CONSTRUCTION PROTECTOR

SLIDE IN-OUT CHASSIS COMPRESSOR

INTERNAL OVERLOAD PROTECTOR

FAN MOTOR

INTERNAL THERMAL PROTECTOR

POWER CORD

3 WIRE WITH GROUNDING CORD-CONNECTED TYPE(ATTATCHMENT PLUG:OPTION)

DRAIN SYSTEM NET WEIGHT

DRAIN PIPE OR SPLASHED BY FAN SLINGER (lbs/kg)

OUTSIDE DIMENSION

(inch)

(W x H x D)

(mm)

7 Room Air Conditioner

130/60 26 x 16 27/32 x 26 9/16 660 x 428 x 675

Specfications

Product Specifications Table -1

MODELS

ITEMS POWER SUPPLY

RAD-243A 1Ø, 208/230V, 60Hz

COOLING CAPACITY

23,500/23,000

INPUT

2,760/2,710

RUNNING CURRENT

8.5

REFRIGERANT (R-22) CHARGE(g)

835g(29.3oz)

OPERATING

INDOOR(°C)

27(DB),19(WB)

OUTDOOR(°C)

35(DB),24(WB)

TEMPERATURE EVAPORATOR

2 ROW 15 STACKS LOUVERED-FIN TYP

CONDENSER

2 ROW 19 STACKS,LOUVERED-FIN TYPE L-BENDING TYPE

FAN, INDOOR

TURBO

FAN, OUTDOOR

PROPELLER TYPE FAN WITH SLINGER-RING

FAN SPEEDS, FAN/COOLING FAN MOTOR

3/3 6 POLES

OPERATION CONTROL

WIRELESS REMOCN

ROOM TEMP. CONTROL

THERMISTOR

AIR DIRECTION CONTROL

VERTICAL LOUVER(RIGHT & LEFT) HORIZONTAL LOUVER(UP & DOWN)

CONSTRUCTION PROTECTOR

SLIDE IN-OUT CHASSIS COMPRESSOR

INTERNAL OVERLOAD PROTECTOR

FAN MOTOR

INTERNAL THERMAL PROTECTOR

POWER CORD

3 WIRE WITH GROUNDING CORD-CONNECTED TYPE(ATTATCHMENT PLUG:OPTION)

DRAIN SYSTEM NET WEIGHT

DRAIN PIPE OR SPLASHED BY FAN SLINGER (lbs/kg)

OUTSIDE DIMENSION

(inch)

(W x H x D)

(mm)

7 Room Air Conditioner

130/60 26 x 16 27/32 x 26 9/16 660 x 428 x 675

Installation

Installation Select the Best Location

CAUTION: All side louvers of the cabinet must remain exposed to the outside of the structure.

AWNING COOLED AIR

75~15cm

1.To prevent vibration and noise, make sure the unit is installed securely and firmly. 2.Install the unit where the sunlight does not shine directly on the unit. 3.The outside of the cabinet must extend outward for at least 30cm and there should be no obstacles, such as a fence or wall, within 50cm from the back of the cabinet because it will prevent heat radiation of the condenser. Restriction of outside air will greatly reduce the cooling efficiency of the air conditioner.

FENCE

HEAT RADIATION

ABOUT 10~15mm Over 50cm

Figure 1

4.Install the unit a little slanted so the back is slightly lower than the front (about 10~15mm). This will help force condensed water to the outside. 5.Install the unit from the bottom about 75~150cm above the floor level.

Installation Check The setting conditions must be checked prior to initial starting. The following items are especially important checking points when the installation is finished. 1. Grounding wire (Green or Green and Yellow) is provided in the power cord. The green wire must be grounded. 2. Connect to a single-outlet 15A circuit. (or 20A circuit for Electric Heater Model) 3. To avoid vibration or noise, make sure the air conditioner is installed securely. 4 Avoid placing furniture or draperies in front of the air inlet and outlet.

How to Secure the Drain Pipe In humid weather, excess water may cause the BASE PAN to overflow. To drain the water, remove the DRAIN CAP and secure the DRAIN PIPE to the rear hole of the BASE PAN. Press the drain pipe into the hole by pushing down and away from Drain pipe the fins to avoid injury.

Drain cap

Optional 1. Install the drain pan over the corner of the cabinet where you removed the CABINET plug with 4 (or 2) screws. 2. Connect the drain hose to the outlet located at the bottom of the drain pan. You can purchase the drain hose or tubing locally to satisfy your particular DRAIN PAN needs. (Drain hose is not supplied). 3. Select the most appropriate connection from among the following figures (by considering the hole of the unit) to fit drain pan to your own unit.

SCREW

Fig. 1

Fig. 2

DRAIN HOSE

Fig. 3

Fig. 4

Service Manual 8

Installation

Window Requirements NOTICE

All supporting parts should be secured to firm

wood, masonry, or metal.

26" to 41"

1. This unit is designed for installation in standard double hung windows with actual opening widths from 26" to 41". The top and bottom window sashes must open sufficiently to allow a clear vertical opening of 18" from the bottom of the upper sash to the window stool. 2. The stool offset (height between the stool and sill) must be less than 1 1/4".

18" min

Stool

Offset Less than 1 1/4" Sill Exterior

Interior wall 26" min. (Without frame curtain)

Installation Kits Contents Foam strip (Plain-Back)

Foam-PE (Adhesive-Backed)

Foam-PE (Adhesive-Backed)

Left frame curtain

Drain joint pipe

Frame guide(2) Window locking bracket Right frame curtain Sill bracket(2)

Type A (14)

Support bracket(2)

Type B (7)

9 Room Air Conditioner

Type C (5)

Type D (2)

Carriage Bolt (2)

Lock Nut (4)

Installation

Suggested Tool Requirements PREPARATION OF CHASSIS Shipping screws

1. Remove the screws which fasten the cabinet at both sides and at the back.

Figure 2

2. Slide the unit out from the cabinet by gripping the base pan handle and pulling forward while bracing the cabinet. 3. Cut the window sash seal to the proper length. Peel off the backing and attach the Foam-PE to the underside of the window sash.

Figure 3

4. Remove the backing from Foam-PE with 3 holes and attach it to the bottom of the Top retainer bar.

Top retainer bar

5. Attach the Top retainer bar on the top of the cabinet with 3 screws (Type A).

Foam-PE 6. Insert the Frame guides into the bottom of the cabinet.

Foam-PE

Figure 4

Top retainer bar

7. Insert the Frame Curtain into the Top retainer bar and Frame guides.

8. Fasten the curtains to the unit with 10 screws (Type A) at both sides.

Screw (Type A)

Screw(Type A) Frame guide

Figure 5

Service Manual 10

Installation

Cabinet Installation 1. Open the window. Mark a line on the center of the window stool between the side window stop moldings. Loosely attach the sill bracket to the support bracket using the carriage bolt and the lock nut.

Sill Bracket

Support Bracket Lock nut

Carriage Bolt (M-Screw)

Figure 6

2. Attach the sill bracket to the window sill using the screws (Type B). Carefully place the cabinet on the window stool and align the center mark on the bottom front with the center line marked window stool.

Machine screw(Type D) and lock nut

Cabinet Track hole

Outer edge of window sill

Support Bracket

Screw(Type B) Sill bracket

Carriage bolt and lock nut

Figure 7

3. Using the M-screw and the lock nut, attach the support bracket to the cabinet track hole. Use the first track hole after the sill bracket on the outer edge of the window sill. Tighten the carriage bolt and the lock nut. Be sure the cabinet slants outward.

CAUTION: Do not drill a hole in the bottom pan. The unit is designed to operate with approximately 1/2" of water in bottom pan.

Top retainer bar

Window stool Front angle

Window sash

4. Pull the bottom window sash down behind the Top retainer bar until they meet. NOTICE

1. Do not pull the window sash down so tightly that the movement of Frame curtain is restricted. Attach the cabinet to the window stool by driving the screws (Type B) through the cabinet into window stool. 2. The cabinet should be installed with a very slight tilt downward toward the outside.

Figure 8

Top retainer bar

Foam-PE Cabinet Frame curtain Foam-PE Figure 9

Sash track

Front Angle Screw(Type B)

11 Room Air Conditioner

Figure 10

Installation 5. Pull each Frame curtain fully to each window sash track, and pull the bottom window sash down behind the Top retainer bar until it meets.

Screw(Type C)

6. Attach each Frame curtain the window sash by using screws (Type C.) (See Fig. 11)

Figure 11

7. Slide the unit into the cabinet.(See Fig. 12)

CAUTION: For security purpose, reinstall screws(Type A) at cabinet's sides. Power Cord Screw

Screw (Type A) Figure 12

8. Cut the Foam-strip to the proper length and insert between the upper window sash and the lower window sash.(See Fig. 13)

Foam-Strip

Figure 13

9. Attach the Window locking bracket with a screw (Type C.) (See Fig. 14)

Window locking bracket

Figure 14

10. Attach the front grille to the cabinet by inserting the tabs on the grille into the tabs on the front of the cabinet. Push the grille in until it snaps into place.(See Fig.15) 11. Lift the inlet grille and secure it with a screw (Type A) through the front grille.(See Fig. 15)

Figure 15

12. Window installation of room air conditioner is now completed. See ELECTRICAL DATA for attaching power cord to electrical outlet.

Figure 16

Service Manual 12

Operation

Operation Features • Designed for COOLING ONLY. • Powerful and whispering cooling. • Slide-in and slide-out chassis for the simple installation and service. • Side air-intake, side cooled-air discharge.

• Built-in adjustable THERMOSTAT • Washable one-touch filter • Compact size • Reliable and efficient rotary compressor

Control Locations Function of Controls 1. Cooling Only Model • VENTILATION The ventilation lever must be in the CLOSE position in order to maintain the best cooling conditions. When a fresh air is necessary in the room, set the ventilation lever OPEN position. The damper is opened and room air is exhausted.

CLOSE

VENT

OPEN

NOTICE Before using the ventilation feature,

make the lever, as shown. First, pull down part to horizontal line with part . • THERMOSTAT Thermostat will automatically control the temperature of the room. Select a higher number for a cooler temperature in the room. The temperature is selected by positioning the knob to the desired position. The 5 or 6 position is a normal setting for average conditions. • OPERATION OFF

: Turns the air conditioner off.

MED FAN LOW FAN

: Permits the medium fan speed operation without cooling. : Permits the low fan speed operation without cooling.

HIGH COOL : Permits cooling with the high fan speed operation. MED COOL : Permits cooling with the medium fan speed operation. LOW COOL : Permits cooling with the low fan speed operation. • AUTO SWING ON

: Air swing is operated while OPERATION knob is set to the COOL position.

OFF : Stops the operation of air swing.

13 Room Air Conditioner

Thermostat

Operation Auto Swing

5 4

6

Off

3

On

Off Med Fan

High Cool

Low Fan

Med Cool

7

2

8 1

9

Low Cool

Operation 2. Cooling Only Model with Remote Control and Touch Type DISPLAY

REMOTE CONTROL

WG2405RY6, WG2405RY6

WG2405RY6 WG2405RY6

3

2

Power

1

8 Temp

5

6 1

Fan Speed

4 Timer

Mode

Energy Saver

Auto Swing

2

3

4

5

7 6

7

PRECAUTION: The Remote Control unit will not function properly if bright light strikes the sensor window of the air conditioner or if there are obstacles between the Remote Control unit and the air conditioner. POWER BUTTON Operation starts, when this button is pressed and stops when you press the button again. OPERATION MODE SELECTION BUTTON Select Cooling, or Fan or Dehumid mode with button. (Dehumid mode is not to all models.) ON/OFF TIMER BUTTON Set the time of starting and stopping operation. The timer is set by 1 hour. FAN SPEED SELECTOR Select the fan speed in three steps. - High [F3] ➔ Low[F1] ➔ Med[F2] ➔ High[F3]... . ROOM TEMPERATURE SETTING BUTTON Control the room temperature within a range of 60°F to 86°F by 1°F. 6 ENERGY SAVER(Available In some models)

The fan stops when the compressor stops cooling. Approximately every 3 minutes the fan will turn on and check the room air to determine if cooling is needed. 7 AUTO SWING BUTTON

Control the horizontal air direcion by air swing system.

AUTO RESTART In case the power comes on again after a power failure, the unit runs as previous setting operation.(Available in some models)

Service Manual 14

Disassembly

Disassembly — Before the following disassembly, CONTROL BOX set to OFF and disconnect the power cord.

Mechanical Parts 1. Front Grille 1. Open the lnlet grille upward . 2. Remove the screw that fastens the front grille. 3. Pull the front grille from the right side. 4. Remove the front grille. 5. Re-install the component by referring to the removal procedure, above.(See Figure 17) NOTICE

Mark " "of inlet grille means opening d irection.

2. Cabinet 1. After disassembling the FRONT GRILLE, remove the 2 screws that fasten the cabinet at both sides. 2. Remove the 2 screws that fasten the cabinet at back. 3. Pull the base pan forward. (See Figure 18) 4. Remove the cabinet. 5. Re-install the component by referring to the removal procedure, above.

Figure 17

3. Control Box 1. Remove the front grille. (Refer to section 17) 2. Remove the cabinet. (Refer to section 18) 3. Remove the 2 screws that fasten the control box cover. 4. Remove two housings that connect compressor wire and motor wire in the control box. 5. Discharge the capacitor by placing a 20,000 ohm resistor across the capacitor terminals. 6. Remove the 2 screws that fasten the control box. 7. Pull the control box forward completely. 8. Re-install the components by referring to the removal procedure, above. (See Figure 19) (Refer to the circuit diagram found on page 23 in this manual and on the control box.)

Figure 18

Figure 19

15 Room Air Conditioner

Disassembly

Air Handling Parts 4. Cover (at the top) 1. Remove the front grille. (Refer to section 17) 2. Remove the cabinet. (Refer to section 18) 3. Remove 11 screws which fasten the brace and covers. 4. Remove the covers and the brace. (See Fig. 20) 5. Re-install the components by referring to the removal procedure, above.

Figure 20

5. Blower 1. Remove the cover. (Refer to section 20) 2. Remove the 3 screws which fasten the evaporator at the left side and the top side. 3. Move the evaporator sideward carefully. 4. Remove the orifice from the air guide carefully. 5. Remove the clamp which secures the blower with plier. (See Fig. 21) 6. Remove the blower with plier or your hand without touching blades. (See Fig. 22) 7. Re-install the components by referring to the removal procedure, above.

6. Fan

Figure 21

Figure 22

1. Remove the cabinet. (Refer to section 18) 2. Remove the brace and shroud cover. (Refer to section 20) 3. Remove the 5 screws which fasten the condenser. 4. Move the condenser sideways carefully. 5. Remove the clamp which secures the fan. 6. Remove the fan. (See Figure 23) 7. Re-install the components by referring to the removal procedure, above. Figure 23

Service Manual 16

Disassembly 6. Shroud 1. Remove the fan. (Refer to section 21) 2. Remove the screw that fastens the shroud. 3. Remove the shroud. (See Figure 24) 4. Re-install the component by referring to the removal procedure, above.

Figure 24

Electrical Parts 7. Motor 1. Remove the cabinet. (Refer to section 18) 2. Remove the cover control and disconnect a wire housing in control box. (Refer to section 19) 3. Remove the blower. (Refer to section 21) 4. Remove the fan. (Refer to section 22) 5. Remove the 4 screws which fasten the motor. (See Figure. 25) 6. Remove the motor. 7. Re-install the components by referring to the removal procedure, above.

Figure 25

8. Compressor 1. Remove the cabinet. (Refer to section 18) 2. Discharge the refrigerant system using FreonTM Recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM . Leave the valve in place after servicing the system. 3. Disconnect the 3 leads from the compressor. 4. After purging the unit completely, unbrace the suction and discharge tubes at the compressor connections. 5. Remove the 3 nuts and the 3 washers which fasten the compressor. 6. Remove the compressor. (See Figure 26) 7. Re-instill the components by referring to the removal procedure, above.

17 Room Air Conditioner

Figure 26

Disassembly 9. Capacitor 1. Remove the control box. (Refer to section 19) 2. Remove the knobs and the screw that fasten control panel from control box. 3. Remove the screw that located in the front. 4. Open the bottom side of control box. 5. Remove the screw and the clamp that fastens the capacitor. 6. Disconnect all the leads of capacitor terminals. 7. Re-install the components by referring to the removal procedure, above. (See Figure 27) Figure 27

10. Power Cord 1. Remove the control box. (Refer to section 19) 2. Open the control box. (Refer to section 25) 3. Disconnect the grounding screw from the control box. 4. Disconnect the 2 receptacles. 5. Remove a screw which fastens the clip cord. (See Figure 28) 6. Remove the power cord. 7. Re-install the component by referring to the above removal procedure, above. (Use only one ground-marked hole for ground connection.) 8. If the supply cord of this appliance is damaged, it must be replaced by the special cord. (The special cord means the cord that has the same specification marked on the supply cord attached at the unit.)

Figure 28

11. Thermistor 1. Remove the control box. (Refer to section 19) 2. Unfold the control box. (Refer to section 25) 3. Disconnect the themistor terminals from main P.W.B Assembly. 4. Remove the thermistor. 6. Re-install the components by refereing to the above removal procedure above. (See Figure 29)

Figure 29

12. Synchronous Motor 1. Remove the control box. (Refer to section 19) 2. Unfold the control box. (Refer to section 25) 3. Remove the crankshaft. 4. Disconnect all the leads of the synchronous motor. 5. Remove the 2 screws which fasten the synchronous motor. (See Figure. 30) 6. Re-install the components by referring to the above removal procedure above. Figure 30

Service Manual 18

Disassembly

Refrigerating Cycle CAUTION: Discharge the refrigerant system using a FreonTM Recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system. 13. Condenser 1. Remove the cabinet. (Refer to section 18) 2. Remove the 4 screws that fasten the brace.(Refer to section 20) 3. Remove the 5 screws that fasten the condenser and shroud. 4. After discharging the refrigerant completely, unbraze the interconnecting tube at the condenser connections. 5. Remove the condenser. 6. Re-install the component by referring to notes. (See Figure 31)

14. evaporator

Figure 31

1. Remove the cabinet. (Refer to section 18) 2. Remove the 2 screws that fasten the evaporator. 3. Move the evaporator sideways carefully. (Refer to section 20) 4. After discharging the refrigerant completely, unbraze the interconnecting tube at the evaporator connections. 5. Remove the evaporator. 6. Re-install the component by referring to notes. (See Figure 32)

15. Capillary Tube 1. Remove the cabinet. (Refer to section 18) 2. After discharging the refrigerant completely, unbraze the interconnecting tube at the capillary tube.(See caution above) 3. Remove the capillary tube. 4. Re-install the component by referring to notes.

19 Room Air Conditioner

Figure 32

Disassembly NOTICE

— Replacement of the refrigeration cycle. 1. When replacing the refrigeration cycle, be sure to Discharge the refrigerant system using a FreonTM recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system. 2. After discharging the unit completely, remove the desired component, and unbraze the pinch-off tubes. 3. Braze service valves into the pinch-off tube ports, leaving the valves open. 4. Braze the pinch-off tubes with Service valves. 5. Evacuate as follows. 1) Connect the vacuum pump, as illustrated figure 33A. 2) Start the vacuum pump, slowly open manifold valves A and B with two full turns counterclockwise and leave the valves open. The vacuum pump is now pulling through valves A and B up to valve C by means of the manifold and entire system.

CAUTION: If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclockwise. This will keep oil from foaming and being drawn into the vacuum pump.

6. Recharge as follows : 1) Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened. 2) Connect the charging cylinder as shown in figure 33B. With valve C open, discharge the hose at the manifold connection. 3) Open valve A and allow the proper charge to enter the system. Valve B is still closed. 4) If more charge is required, the high-side will not take it. Close valve A. 5) With the unit running, open valve B and add the balance of the charge. a. Do not add the liquid refrigerant to the Lowside. b. Watch the Low-side gauge; allow pressure to rise to 30 lbs (0.2Mp). c. Turn off valve B and allow pressure to drop. d. Repeat steps b. and c. until the balance of the charge is in the system. 6) When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos brazing rod and braze pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leakage of the pinch-off connection.

3) Operate the vacuum pump vaccum for 20 to 30 minutes, until 600 microns of vaccum is obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump. 4) Remove the hose from the vacuum pump and place it on the charging cylinder. See figure 33B. Open valve C. Discharge the line at the manifold connection. 5) The system is now ready for final charging.

Service Manual 20

Disassembly Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pin-off tool capable of making a leak-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve.

COMPOUND GAUGE

CONDENSER (HIGH PRESSURE SIDE)

MANIFOLD GAUGE

A

B CAPILLARY TUBE

SEE INSETS BELOW EVAPORATOR (LOW PRESSURE SIDE)

COMPRESSOR

LOW

HI

A B

B

A

EXTERNAL VACUUM PUMP CHARGING CYLINDER

C

Figure 33A-Pulling Vacuum

21 Room Air Conditioner

Figure 33B-Charging

MAIN POWER

FAN

COMP

HERM

C

CAPACITOR

FAN MOTOR

S/V4WAY

SYNC MOTOR

PIPE-TH

ROOM-TH

1

3

1

1

3

1

CN-BK

CN-BL

CN-RD

CN-4WAY

250V/T3.15A

FUSE

G4A-1A-E-LG

RY-COMP

12V

CN-SYNC

CN-WOR

3

2

4

3

4

3

1

2

1

2

SMW250-04

CN-TH1

R01J

TVR14271

ZNR01J

120 1/2W

0.1/275V

C01J

RY-HI

RY-MED

RY-LOW

RY-4WAY

RY-SYNC

RY-COMP

2

1

4

7

POWER TRANS

RY-HI

RY-MED

RY-LOW

RY-4WAY

RY-SYNC

10 7

1000 35V

D04D + C01D

D05D

ULN2004A

IC01M

8

9

D02D~D05D 1N4004

D03D

D02D

12V

1

2

3

14

16

15

4

5

6

13

12

11

OR2H

12.1K 1%

12.1K 1%

0K

OR1H

R22H

R21H

R03H

5V

0.1 50V

I

1000 16V

C03D

7812 C02D

O +

12.1K 1%

6.2K 1%

IC01D

R01H

R02H

COMP

7805

IC02D

0.01 50V

C04D

O

12V

LED out3

Buzzer

Receiver

HI

MED

ION

HVB

LOW

4WAY

SYNC

220 10V

1M

R01B

20

36

21

35

22

34

I

C05D +

33

32

31

30

29

28

27

26

25

24

23

Option2 LED out2

OSC01B

Option1 5V

37

5V

0.01 50V

17

16

MICOM

18

5V

38

R02E 20

R12F 20K

39

40

TMP87CH47U

19

C06D

R01E 1K

LED out1

VAref KEY0

Room TH KEY1

Osc out VDD

Pipe TH LED out0

VSS SLIDE SW

14

42

15

41

/Reset SEG-f

44

43

1

2

3

4

5

6

7

8

9

10

11

C01L 680pF

4

3

2

SDA

Rx

+

1

3

Vcc 8

1K

R01L

ULN2004A

IC01G

C01F R01F 0.001 10K

SEG-c

SEG-b

SEG-a

Digit0 (Scan0)

Digit1 (Scan1)

Digit2 (Scan2)

Digit3 (Scan3)

1

2

3.6V

7 A1 WP 6 SCL GND SDA 5 A2

A0

24LC01BT

EEPROM

1uF 50V

C02A

20K

R01A

Digit4 (Scan4)

SCL

C02F R02F 0.001 10K

12

Tx

C01A 0.01 50V

13

TEST SEG-e

Osc in SEG-g

RT8.00MG

SEG-d

5V

1

20K

20K

16

7 8

6

5

9

10

11

12

14 13

15

4

1K

R04P

R03P

R02P

3

2

IC01A

5V

S7136

12V

5V

R07G

R06G

R05G

R04G

R03G

R02G

R01G

CN-DISP

150

150

150

150

150

150

150

5V

16

15

12

11

10

9

8

7

6

14

13

1

17

SW3

A/SWING

D03F

ENERGY SAVER

SW7

TEMP UP

D07F

AIR PURIFIER

A/RESTART

CN-DISP

2

3

6

7

8

9

10

11

12

5 4

17

1

5V

Q04G A101S

2 16

COOL

SW2

SW5

PKM13EPY -4002

BZ01E

E/SAVER

FAN

TIMER

DRY/HEAT

DEFROST

D02F

TIMER

D05F

TEMP DOWN

A101S

Q03G

3 15

d

c

b

Vcc

GND

RECEIVER

Vout

g

7 f 8

SW1

SW4

Digit1 a

1 e

2

3

4

5

D01F

FAN

D04F

MODE

A101S

Q02G

4

d

c

e

f

Digit0

SW8

+

5V C22L 220 10V

5

d

g

a

6

13

88 SEGMENT

e

g

a

b

D08F

10

f

SW6

ON/OFF

D06F

AUTO SWING

14

A101S

Q01G

c

b

5V

Schematic Diagram

Schematic Diagram

Electronic Control Device

Service Manual 22

Schematic Diagram

Wiring Diagram • MODEL : WG1805RY6 / WG2405RY6

POWER INPUT WH(BL)

BK(BR) (Plain) GN/YL(GN)

BK BL RD OR(BR) YL

RD

H

PTC

COMP.

BK RD BL

R S C

BL

3854AR2330P WIRING DIAGRAM

23 Room Air Conditioner

BR BR

RY-SYNC

ZNR

RY-COMP 4 3

OLP

CN-DISP

RY-HI

RY-MID

CN-SYNC

OR(BR) BK RD

MAIN P.W.B ASM

C BK

CN-WORK

GN/YL (GN) CAPACITOR F

THERMISTOR CN-TH1

RY-LO

MOTOR

BK BL RD OR(BR) YL

DISPLAY P.W.B ASM

(Ribbed)

TRANS FORMER FUSE 250V/T2A (115V/T2A)

SYNC MOTOR

Schematic Diagram

Components Location Main P.W.B Assembly

Display P.W.B Assembly

Service Manual 24

Troubleshooting Guide

Troubleshooting Guide Piping System

CONDENSER COIL FAN

CAPILLARY TUBE

MOTOR COMPRESSOR

BLOWER

EVAPORATOR COIL

Figure 34 is a brief description of the important components and their function in what is called the refrigeration system. This will help you to understand the refrigeration cycle and the flow of the refrigerant in the cooling cycle.

ROOM AIR CONITIONER CYCLE OF REFRIGERATION

EVAPORATOR COILS

CONDENSER COILS

COMPLETE LIQUID BOIL OFF POINT COOLED AIR

SUCTION LINE COOL LOW PRESSURE VAPOR

VAPOR INLET HOT DISCHARGED AIR

ROOM AIR HEAT LOAD

MOTOR

OUTSIDE COOLING AIR FOR REFRIGERANT PASS THROUGH

COMPRESSOR OIL

LIQUID PRESSURE DROP

LIQUID OUTLET (LIQUID REFRIGERANT) CAPILLARY TUBE

HIGH PRESSURE VAPOR LIQUID REFRIGERANT LOW PRESSURE VAPOR

Figure 34

25 Room Air Conditioner

Troubleshooting Guide

Troubleshooting Guide In general, possible trouble is classified in two kinds. The one is called Starting Failure which is caused from an electrical defect, and the other is ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application.

Unit runs but poor cooling. Ineffective Cooling

Check cold air circulation for smooth flow.

Check outdoor coil (heat exchanger) & the fan operation.

Dirty indoor coil (Heat exchanger)

Check gas leakage.

Malfunction of fan

Repair gas leak.

Check heat load increase.

Unexpected residue

Overloaded circuit

Clogged of air filter.

Replacement of unit if the unit is beyond repair.

Check inside gas pressure.

Obstruction at air outlet Adjusting of refrigerant charged. Stop of auto air-swing

Malfunction of compressor. Correct above trouble

Check clogging in refrigeration circuit.

Repair clogging in refrigeration circuit.

Replacement of compressor.

Satisfactory operation with temperature difference of inlet & outlet air ; 44~50°F(7~10°C)

Service Manual 26

Troubleshooting Guide

Fails to Start

Check of power source.

Check circuit breaker and fuse.

Check of control switch setting.

Gas leakage of feeler bulb of thermostat

Check of control switch.

Compressor only fails to start.

Fan only fails to start.

Improper wiring. Drop of power voltage. Improper thermostat setting. Defect of fan motor capacitor.

Defect of compressor capacitor. Loose terminal connection. Capacitor check.

Irregular motor resistance ( ). Irregular motor insulation ( ).

Improper wiring. Replacement Replacement of fan motor.

Irregular motor resistance (

)

Irregular motor insulation (

)

Regular but fails to start.

Replacement of compressor (locking of rotor, metal). Replacement of compressor (Motor damaged)

27 Room Air Conditioner

Troubleshooting Guide Electrical Parts Troubleshooting Guide Possible Trouble 1

The unit does not operate.

Is the Trans output power AC 220V?

NO

• Check the Fuse. • Check the wiring diagram.

YES

Is the Trans output power about AC 14V?

NO

YES

Is output Voltage of IC01D DC 12V?

Is shorted the Trans. output?

YES

NO

NO

• Check the Main PCB pattern.

• Exchange the Trans. • Exchange D02D~D05D. • Exchange IC01D.

YES

Is output Voltage of IC02D DC 5V?

NO

• Exchange IC02D.

YES

Is the reset circuit all right? (The No.16 of Micom is 5V.)

NO

• Exchange IC01A, C02A.

YES Is the connection between Main and Display all right?

NO

• Connect connector exactly.

NO

• Check the PCB pattern.

YES

Is the voltage No.20 of Micom DC 5V? YES Exchange Main PCB Ass'y.

Service Manual 28

Troubleshooting Guide Possible Trouble 2

The compressor does not operate.

Is setting Temp. set lower than Room Temp.-0.5°C?

NO

• Select the setting Temp. to lower Number.

YES

Is the voltage No.10 of IC01M 0V?

NO

Is the voltage N0.7 of IC01M DC 5V? YES

YES • Check the RY-COMP. • Check the wiring Diagram.

• Exchange IC01M.

NO

Is the Unit for 3 minutes delay?

NO

YES • Wait 3 Minutes.

• Exchange MAIN PCB Ass'y.

Possible Trouble 3

The compressor always operate.

Is the wire connection of RY-COMP all right? YES • Check the RY-COMP.

29 Room Air Conditioner

NO

• Connect LEAD Wire to RY-COMP again.

Troubleshooting Guide Possible Trouble 4

FAN does not operate.

Is the voltage NO.1 or 4 of IC01M DC 5V?

NO

• Exchange IC01M.

YES

Is the voltage NO.13 or 16 of IC01M 0V?

NO

• Exchange IC01M.

YES • Check the RY-Hi or RY-Lo. • Check the wiring diagram.

Possible Trouble 5

Auto Swing does not operate.

Is the voltage NO.6 of IC01M DC 5V?

NO

• Exchange Micom.

YES

Is the voltage NO.11 of IC01M 0V?

NO

• Exchange IC01M.

YES • Check the RY-SYNC. • Check the connectionn of CN-SYNC. • Check the PCB pattern.

Service Manual 30

Troubleshooting Guide Possible Trouble 6

Remote controller does not operate.

Is the voltage of Battery about over 2.3V?

NO

• Exchange the battery.

YES Is the voltage No.16 of CN-DISP on Main PCB Ass'y DC 5V?

NO

• Check the PCB pattern.

YES NO

Is the connection of CN-DISP all right?

• Connect connector to CN-DISP exactly.

YES • Exchange Receiver Ass'y.

Possible Trouble 7

It displays abnormally on display PCB Ass'y.

Is the IC01G all right?

NO

• Exchange IC01G.

YES NO Is the connection of CN-DISP all right?

NO

• Connect connector to CN-DISP exactly.

YES Does the Q01G~Q04G operate normally on main PCB Ass'y? YES • Exchange the display PCB Ass'y.

31 Room Air Conditioner

NO

• Exchange Q01G-Q04G.

Troubleshooting Guide

Room Air Conditioner Voltage Limits NAME PLATE RATING 208~230±10% 115±10% COMPLAINT Fan motor will not run.

MINIMUM 187V 104V CAUSE

MAXIMUM 253V 126V REMEDY

No power

Check voltage at outlet. Correct if necessary.

Power supply cord

Check voltage to rotary switch. If none, check power supply cord. Replace cord if circuit is open.

Rotary switch

Check switch continuity. Refer to wiring diagram for terminal identification. Replace switch if defective.

Wire disconnected or connection loose

Connect wire. Refer to wiring diagram for terminal identification. Repair or replace loose terminal.

Capacitor (Discharge capacitor before testing.)

Test capacitor. Replace if not within ±10% of manufacturer's rating. Replace if shorted, open, or damaged.

Will not rotate

Fan blade hitting shroud or blower wheel hitting scroll. Realign assembly. Units using slinger ring for condenser fan must have 1 /4 to 5/16 inch clearance to the base. If it hits the base, shim up the bottom of the fan motor with mounting screw(s). Check fan motor bearings; if motor shaft will not rotate, replace the motor.

Fan motor runs intermittently

Revolves on overload.

Check voltage. If not within limits, call an electrician. Test capacitor. Check bearings. Does the fan blade rotate freely? If not, replace fan motor. Pay attention to any change from high speed to low speed. If the speed does not change, replace the motor.

Fan motor noise.

Compressor will not run, but fan motor runs.

Fan

If cracked, out of balance, or partially missing, replace it.

Turbo

If cracked, out of balance, or partially missing, replace it.

Loose clamper

Tighten it.

Worn bearings

If knocking sounds continue when running or loose, replace the motor. If the motor hums or noise appears to be internal while running, replace motor.

Voltage

Check voltage. If not within limits, call an electrician.

Wiring

Check the wire connections, if loose, repair or replace the terminal. If wires are off, refer to wiring diagram for identification, and replace. Check wire locations. If not per wiring diagram, correct.

Rotary

Check for continuity, refer to the wiring diagram for terminal identification. Replace the switch if circuit is open.

Service Manual 32

Troubleshooting Guide COMPLAINT Compressor will not run, but fan motor runs.

Compressor cycles on overload.

Compressor cycles on overload.

Compressor cycles on overload.

Insufficient cooling or heating

Excessive noise

CAUSE

REMEDY

Thermostat

Check the position of knob If not at the coldest setting, advance the knob to this setting and restart unit. Check continuity of the thermostat. Replace thermostat if circuit is open.

Thermistor

Check the TEMP control. If not at the lowest number, set TEMP control to this setting and restart the unit. Check the continuity of the thermistor. Replace the thermistor if the circuit is open.

Capacitor (Discharge capacitor before servicing.)

Check the capacitor. Replace if not within ±10% of manufacturers rating. Replace if shorted, open, or damaged.

Compressor

Check the compressor for open circuit or ground. If open or grounded, replace the compressor.

Overload

Check the compressor overload, if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool it, and retest.)

Voltage

Check the voltage. If not within limits, call an electrician.

Overload

Check overload, if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.)

Fan motor

If not running, determine the cause. Replace if required.

Condenser air flow restriction

Remove the cabinet. inspect the interior surface of the condenser; if restricted, clean carefully with a vacuum cleaner (do not damage fins) or brush. Clean the interior base before reassembling.

Condenser fins (damaged)

If condenser fins are closed over a large area on the coil surface, head pressures will increase, causing the compressor to overload. Straighten the fins or replace the coil.

Capacitor

Test capacitor.

Wiring

Check the terminals. If loose, repair or replace.

Refrigerating system

Check the system for a restriction.

Air filter

If restricted, clean of replace.

Exhaust damper door

Close if open.

Unit undersized

Determine if the unit is properly sized for the area to be cooled.

Turbo or fan

Check the set screw or clamp. If loose or missing, correct. If the turbo or fan is hitting air guide, rearrange the air handling parts.

Copper tubing

Remove the cabinet carefully and rearrange tubing not to contact cabinet, compressor, shroud, and barrier.

33 Room Air Conditioner

Troubleshooting Guide COMPLAINT Compressor cycles on overload. Insufficient cooling or heating

Excessive noise.

CAUSE Capacitor Wiring Refrigerating system Air filter Exhaust damper door Unit undersized Turbo or fan

Copper tubing

Auto air-swing fails.

Rotary switch. Wiring Synchronous motor.

REMEDY Test capacitor. Check the terminals. If loose, repair or replace. Check the system for a restriction. If restricted, clean of replace. Close if open. Determine if the unit is properly sized for the area to be cooled. Check the set screw or clamp. If loose or missing, correct. If the blower or fan is hitting air guide, rearrange the air handling parts. Remove the cabinet and carefully rearrange tubing not to contact cabinet, compressor, shroud, and barrier. Set the knob to HIGH COOL or LOW COOL while rocker switch is ON. Check terminals. If loose, repair or replace. Check the synchronous motor for open circuit.

Service Manual 34

Exploded View

Exploded View Cooling Model 135500

554030

554031

148000

130910

W48602 559011

149980

352380

349600

130410 346811

135515

554160

359012 354210

550140

349480

147582 W48602

W52106-1

W52106-2

349001 552111

352115 352113 352111 135312 35211A 159830

249950

135314

269300

W0CZZ 137215 266002 147581-2

146812

266003

149410

147581-1

264100

Room Air Conditioner

135510

Exploded View

Exploded View Cooling Model 135500

554030

554031

148000

130910

W48602 559011

149980

352380

349600

130410 346811

135515

554160

359012 354210

550140

349480

W52106-2

147582 W48602

W52106-1

349001 552111 267110

352113 352111 249950

135312 567480

35211A W0CZZ

159830 268711-1

135314 237200 238310

135510 146812

147581-2 268711-2 147581-1

Room Air Conditioner

264110

Replacement Parts List R: Service Parts LOCATION NO.

DESCRIPTION

PART NO. WG1805RY6

REMARK

130410

BASE ASSEMBLY,SINGLE

3041A30001H

R

130910

CABINET ASSEMBLY,SINGLE

3091AR6056P

R

135312

GRILLE ASSEMBLY,FRONT(SINGLE)

3531A11002B

R

135303

GRILLE,INLET

3530A10189A

R

135500

COVER ASSEMBLY,CONTROL(SINGLE)

3551A30015A

R

146812

MOTOR ASSEMBLY,SYNC.

2H01102J

R

147581-1

LOUVER,HORIZONTAL

5990A20032A

R

147581-2

LOUVER,HORIZONTAL

5990A20033A

R

-

R

147582

LOUVER,VERTICAL

148000

BRACE

4800AR7271A

R

149980

SHROUD

4998AR1597B

R

152302

FILTER ASSY,A/C

5231AR6159A

R

237200

PANEL,CONTROL

3720AR6163A

R

238310

ESCUTCHEON

3831A20060E

R

249950

CONTROL BOX ASSEMBLY,SINGLE

4995A20613P

R

263230

THERMISTOR ASSEMBLY

6323A20003D

R

264110

POWER CORD ASSEMBLY

6411A20056P

R

267110

REMOTE CONTROLLER ASSEMBLY

6711A20034S

R

268712

PWB(PCB) ASSEMBLY,DISPLAY

6871A20611A

R

268714

PWB(PCB) ASSEMBLY,MAIN(AC)

6871A10193J

R

346811

MOTOR ASSEMBLY,SINGLE

4681A20081T

R

349001

DAMPER,VENTILATION

4900AR7265A

R

349480

ORIFICE

4948A20016A

R

349600

MOUNT,MOTOR

4960AR1596A

R

352111

TUBE ASSEMBLY,CONDENSER OUT

5211AR7059A

R

352113

TUBE ASSEMBLY,DISCHARGE SINGLE

5211A25040B

R

35211A

TUBE ASSEMBLY,SUCTION SINGLE

5211A10247P

R

352390

AIR GUIDE ASSEMBLY

5239A20001W

R

354210

EVAPORATOR ASSEMBLY,FIRST

5421A20248B

R

359012

FAN ASSEMBLY,TURBO

5900A20027A

R

552101

TUBE,CAPILLARY

5210A24956H

R

554031

CONDENSER ASSEMBLY,BENT

5403A20062F

R

554160

COMPRESSOR SET

2520UCBJ002

R

559010

FAN ASSEMBLY,AXIAL

5900AR1508B

R

W0CZZ

CAPACITOR,DRAWING

6120AR2194F

R

3H02932C

R

W52106-1

TUBE,EVAPORATOR

5210A21083B

R

W52106-2

TUBE,EVAPORATOR

5210A21083C

R

W48602

CLAMP,SPRING

NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request. (GCSC WEBSITE http://biz.LGservice.com)

36 Room Air Conditioner

LOCATION No. 130410 130910 135312 135303 135515 146812 147581-1 147581-2 147582 148000 149980 159830 237200 238310 249950 567480 264110 267110 268711-1 268711-2 346811 349001 349480 349600 352111 352113 35211A 352380 354210 359012 554031 554160 559011 W0CZZ 268711-2 W52106-1 W52106-2 135500 W48602 554030 552111 346811 135510 749740 731273

Replacement Parts List DESCRIPTION BASE ASSEMBLY,SINGLE CABINET ASSEMBLY,SINGLE GRILLE ASSEMBLY,FRONT(SINGLE) GRILLE,INLET COVER ASSEMBLY, CONTROLINDOOR) MOTOR ASSEMBLY,SYNC. LOUVER,HORIZONTAL LOUVER,HORIZONTAL LOUVER,VERTICAL BRACE SHROUD FILTER ASSEMBLY,A/C PANEL,CONTROL ESCUTCHEON CONTROL BOX ASSEMBLY,SINGLE THERMISTOR POWER CORD ASSEMBLY REMOTE CONTROLLER ASSY PWB(PCB) ASSY,DISPLY PWB(PCB) ASSY,MAIN MOTOR ASSEMBLY,SINGLE DAMPER,VENTILATION ORIFICE MOUNT MOTOR TUBE ASSEMBLY,CONDENSER OUT TUBE ASSEMBLY,DISCHARGE SINGLE TUBE ASSEMBLY, SUCTION SINGLE AIR GUIDE ASSEMBLY EVAPORATOR ASSEMBLY,FIRST FAN,TURBO CONDENSER ASSEMBLY,BEND COMPRESSOR FAN ASSEMBLY, AXIAL CAPACITOR, DRAWING CLAMP, SPRING TUBE, EVAPORATOR TUBE, EVAPORATOR COVER CLAMP,SPRING CONDENSER ASSEMBLY,FIRST TUBE,BENDING MOTOR,AC COVER ASSEMBLY, CONTROL(SINGLE) GUIDE Install Part Assembly,Single

PART NO WG2405RY7 3041A30001F 3091AR6056P 3531A11002B 3530A10189A 3551A30001A 2H01102J 5990A20032A 5990A20033A 4758AR6157A 4800AR7271A 4998AR1597B 5231AR6159A 3720AR6163A MDD36626101 4995A20613M 6323A20003S 6411A20056Q 6711A20034S 6871A20611A 6871A10193J 4681A20081W 4900AR7265A 4948A20016A 4960AR1596A 5211AR7059E 5211A21526J 5211A10094P 5239A20001W 5421A20248F 5900A20027A 5403A20062F 5416A20045B 5900AR1508B 0CZZA20001X 6871A10193J 5210A30144U 5210A30144V 3550AR6173A 3H02932C 5403A20062E 5210A24956J 4681A20081W 3551A30015A 2H00858D 3127AR3403U

REMARK R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R

Replacement Parts List PART NO

LOCATION NO

DESCRIPTION

130410 130910 135312 135303 135500 146812 147581-1 147581-2 147582 148000 149980 152302 237200 238310 249950 263230 264110 267110

BASE ASSEMBLY,SINGLE CABINET ASSY,SINGLE GRILLE ASSY,FRONT(SINGLE) GRILLE ASSY,INLET COVER,CONTROL(INDOOR) MOTOR ASSEMBLY,SYNC LOUVER,HORIZONTAL LOUVER,HORIZONTAL LOUVER,VERTICAL BRACE SHROUD FILTER ASSY,A/C PANEL,CONTROL ESCUTCHEON CONTROL BOX ASSEMBLY,SINGLE THERMISTOR ASSEMBLY POWER CORD ASSEMBLY REMOTE CONTROLLER

3041A30001H 3091AR6056P AEB30969401 3530AR1604A 3551A30015A 2H01102J 4758AR7264A 4758AR7278A 4758AR6157A 4800AR7271A 4998AR1597B 5231AR6159A 3720AR6163A 3831A20032L 4995A20613Y 6323A20003D 6411A20056P 6711A20035A

R R R R R R R R R R R R R R R R R R

PWB(PCB) ASSEMBLY,DISPLAY

6871A20611A

R

6871A10193N 4681A20081T 4900AR7265A 4948A20016A 4960AR1596A 5211AR7059A 5211A25040B 5211A10247P 5239A20001W 5421A20248G 5900A20027A 5210A33036P 5403A20062F 2520UCBJ002 5900AR1508B 6120AR2194F 3H02932C 5210A21083B 5210A21083C

R R R R R R R R R R R R R R R R R R R

268712 268714 346811 349001 349480 349600 352111 352113 35211A 352390 354210 359012 552101 554031 554160 559010 W0CZZ W48602 W52106-1 W52106-2

PWB(PCB) ASSEMBLY,MAIN MOTOR ASSEMBLY,SINGLE DAMPER,VENTILAYION ORIFICE MOUNT,MOTOR TUBE ASSEMBLY,CONDENSER OUT TUBE ASSEMBLY,DISCHARGER SINGLE TUBE ASSEMBLY,SUCTION SINGLE AIR GUIDE ASSEMBLY EVAPORATOR ASSEMBLY,FIRST FAN,TURBO TUBE, CAPILLARY CONDENSER ASSEMBLY,BENT COMPRESSOR FAN ASSEMBLY,AXIAL CAPACITOR CLAMP,SPRING TUBE,EVAPORATOR TUBE,EVAPORATOR

37 Room Air Conditioner

RAD-183A

Remark

LOCATION No. 130410 130910 135312 135314 135510 146812 147581-1 147581-2 147582 148000 149980 159830 137215 238310 249950 567480 264110 267110 268711-1 268711-2 346811 349001 349480 349600 552113 352113 35211A 749750 354210 359012 552102 554031 554160 559011 W0CZZ W48602 325115-1 325115-2 550140 135500 135515

Replacement Parts List DESCRIPTION BASE ASSEMBLY,SINGLE CABINET ASSY,SINGLE Grille ASSY,Front(SINGLE) Grille ASSY,Inlet COVER,CONTROL(INDOOR) Motor Assembly,SYNC LOUVER,HORIZONTAL LOUVER,HORIZONTAL LOUVER,VERTICAL BRACE SHROUD FILTER ASSY,A/C PANEL,CONTROL ESCUTCHEON CONTROL BOX ASSEMBLY,SINGLE Thermistor ASSEMBLY POWER CORD ASSEMBLY REMOTE CONTROLLER PWB(PCB) ASSEMBLY,DISPLAY PWB(PCB) ASSEMBLY,MAIN MOTOR ASSEMBLY,SINGLE DAMPER,VENTILAYION ORIFICE MOUNT,MOTOR TUBE ASSEMBLY,CONDENSER OUT TUBE ASSEMBLY,DISCHARGER SINGLE TUBE ASSEMBLY,SUCTION SINGLE AIR GUID EASSEMBLY EVAPORATOR ASSEMBLY,FIRST FAN,TURBO Tube,Bending CONDENSER ASSEMBLY,BEND COMPRESSOR FAN ASSEMBLY,AXIAL CAPACITOR CLAMP,SPRING TUBE,EVAPORATOR TUBE,EVAPORATOR ISOLATOR, COMP COVER COVER ASSEMBLY, TOP(INDOOR)

PART NO(2006) REMARK RAD-243A 3041A30001F R 3091AR6056P R AEB30969401 R 3530AR1604A R 3550AR7046D R 2H01102J R 4758AR7264A R 4758AR7278A R 4758AR6157A R 4800AR7271A R 4998AR1597B R 5231AR6159A R 3720AR6163A R 3831A20032L R ABQ32895801 R 6323A20003S R 6411A20056Q R 6711A20035A R 6871A20611A R 6871A10193N R 4681A20081W R 4900AR7265A R 4948A20016A R 4960AR1596A R 5211AR7059E R 5211A21526J R 5211A10094P R 5239A20001W R 5421A20248F R 5900A20027A R 5210A24956J R 5403A20062F R 5416A20045B R 5900AR1508B R 0CF1042856A R 3H02932C R 5210A30144U R 5210A30144V R 4022A30008A R 3550AR6173A R 3551A30001A R

P/No.: 3828A20887A

JULY, 2007 Printed in China