Models BMPlus 3000/5000/7000

70 downloads 2645 Views 5MB Size Report
off-the-shelf heat/cool thermostat, EWC Controls once again proves to be ... thermostat allowing for individual zone ..... Wiring for manual activation of “One Zone”.
Models BMPlus 3000/5000/7000 Patent Pending

Leave this bulletin on the job site for future reference!

The main module controls three zones using motorized dampers and may be expanded up to 5, or 7 zones, using 1 or 2 XM2 Expansion Modules. Compatible Controls 2 stage conventional or dual fuel heat pumps, without the need for dual fuel HVAC kits. Also single or two-stage gas, oil, & Systems hydronic heating systems, with single or two stage air conditioning. Constant or variable speed fan systems.

Zone Capacity

Not compatible with 2 speed / 2 stage compressor heat pumps. (3 stage heat pumps).

Compatible Thermostats

Compatible with most 1 stage conventional 4 or 5 wire heat/cool mechanical or digital thermostats that operate on 24vac. Battery powered or power robbing thermostats that draw less than 20 ma of current. Zone 1 will accept most 2 stage heat conventional thermostats. Heat pump thermostats are not required, but a select type can be used on zone 1 only, if desired. See page 4 & 5.

Automatic Heat/Cool Changeover

The BMPlus Zone system features automatic changeover from any thermostat allowing for individual zone comfort from the HVAC system.

Status LED

The STATUS LED pulses as a steady heart beat to indicate active Microprocessor status.

System LEDs

On board LED’s illuminate to indicate HVAC system mode, system status, active and inactive zone identification. See page 10 for details.

Damper LEDs

LEDs labeled Zone 1 thru Zone 7 indicate which dampers are energized open.

Operating Power

All modules operate on 24vac power supplied from a separate transformer. A single 40va transformer can power up to 5 zones with a total of 5 ND/URD dampers directly connected. See page 9 for details.

TB-215

J1

CONTROL 19

ZONE3 MOTOR

26

46

5

34

47

52

2 ND STAGE TIMER OAS R2

R 40

47

SAS

R 41

DIFFERENTIAL

R5 U3

C7 C8

CPU RESET

R 42

SAS

R 43

OAS

C9

OAS

R 44 R 45

D15 D16

D1

M6 M4 M2 M1

U2 R6

K3

ZONE1 MOTOR D4

D3

F1

+

+

C1

C2

24 VAC T’FORMER

OFF

R 25 R 26 R 27

K7

C14

R 59 R 60

U6

R 61

D19 D20 R 62 R 63

LED 1

STATUS

LED 2

OAS

LED 3

SAS

LED 4

ZONE 3

LED 5

ZONE 2

LED 6

ZONE 1

R 28 LED 7

R 29 R 30

Y2

R 32 R 33

LED 9

Y1

D9

R 67 R 68 R 69 R 70

EM

R 71

U8

ONE ZONE

R 72 R 73

EM

R 74 R 75

W1

B

W2

EM

R 77

BMPlus 3000

R 78 R 79

+

C W1 W2 Y R G

R 65

LED 11 C4

+

R 64

LED 10

R 34 C3

ZONE1 T STAT

R 66

U7

FAN

LED 8

R 31

K8

R 80

C W Y R G

R 57 R 58

Z1

R 22

D8

ZONE2 T STAT

R 56

R 19

R 24

D7

D17 D18

R 54 R 55

< > ON

HP < SYSTEM > GAS DF < HP > CONV ON < FAN DELAY > OFF 90s < PURGE > 120 s OAS < 2 ND STAGE > TIMER OFF < 50% RULE > ON OFF < SAS > ON GAS < FAN > HYDRONIC

SW 3

K 6 R 23

EWC

R 35

U5

R 21 D6

RC RH LINK

C13

C11 Y 1

R 20

SYSTEM

R 51

R 53

D5

G Y2 Y1 O W1 B W2 E RH RC

C W Y R G

R 49 R 50

R 52

K4

K5

ZONE3 T STAT

R 48

C12

TIMER RESET

R8 R9 R 10 R 11 R 12 R 13 R 14 R 15 R 16 R 17 R 18

R C

R 46 R 47

C10 U4

R7 D2

R 76

NORM SW 4

Contents

* BMPlus 3000 Control Panel * Supply Air Sensor * Technical Bulletin TB215 * Mounting Hardware

Thermal Circuit Breaker

The BMPlus module has a Thermal circuit breaker that protects the module(s) from shorts in the damper and thermostat field wiring. It will not protect against shorts in the HVAC system wiring.

CAUTION: When the circuit breaker is tripped it will get quite hot. To reset the breaker: Shut off power to the panel. Find and repair the short. Restore the 24VAC power.

Watch Dog Circuit

The processor has a built-in feature that monitors the processor performance and resets the system if an error occurs in operations or due to power failures.

Indoor Fan Control

Any zone can activate the indoor fan and only the dampers in zones calling for continuous fan operation will open. Continuous fan operation will only occur when there are no active or pending, heat or cool demands.

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 P/N 090375A0215 19 October 2004 REV. F

R 36 R 37 R 38 R 39

2 ND STAGE HEAT

K2

M6 M4 M2 M1

D10 D11 D12 D13

33 40

R4

C6

U1

ZONE2 MOTOR

110

R3

K1

26

19

HIGH TEMP LIMIT

C5

D14

SYSTEM 150

160 12 170 5

LOW TEMP LIMIT

R1

140

130

49 120

40 37

12

M6 M4 M2 M1

43

40

33

D 21

The advanced BMPlus Zone Control System allows you to easily upgrade an inefficient single zone HVAC system, into a Multi-zone, Energy savings, Comfort producing, HVAC system. The robust and superior design, intuitive firmware, simple setup options, and easy to understand wiring, makes the BMPlus Zoning system the Contractors dream. Combined with EWC motorized dampers and practically any off-the-shelf heat/cool thermostat, EWC Controls once again proves to be the innovative leader in the residential & light commercial Forced Air Zoning industry.

Copyright C 2003 EWC Controls All Rights Reserved

E-Mail- [email protected]

1

BMPlus 3000 FIRMWARE/HARDWARE FEATURES Indoor Fan Control During Heating

Built-In Timer Settings

A dip switch is provided to enable automatic fan operation in heat mode. Useful for straight electric heat or hydronic heat applications. NOTE: Fan mode is automatically set when Heat Pump is selected. The panel has built-in delay timers that insure safe & reliable operation.

*Opposite Mode Delay Timer *2nd Stage Delay Timer

20 minutes, fixed.

*Supply Air Limit Delay Timer

3 minutes, fixed.

5 to 47 minutes, Adjustable

*Short Cycle Timer

When the system is satisfied, the panel will not resume the same mode for a minimum of 3 minutes.

*Changeover Timer

A built-in timer prevents the system from rapidly switching between heating and cooling modes. At the end of a call, a 4 minute timer is started and the panel will not switch to the opposing mode until the timer has expired.

*Opposite Mode Delay Timer *2nd Stage Timer / OAS 12

26

33 40

47 5 2nd STAGE Timer / OAS

5 to 47 minutes or 5 to 47 degrees F.

A 20 minute delay must expire, or the active zone(s) must satisfy, before the panel will honor a thermostat demand to changeover to the opposite mode of system operation.

The 2nd STAGE TIMER sets the amount of continuous call time in 1st stage, before second stage heat or cool is energized. NOTE: The potentiometer also serves as the 2nd stage Heat Outside Air Changeover Setting. The BMPlus 3000 can inhibit 2nd stage heat based on Time or Outside Air Temperature. NOTE: An Optional OAS Sensor is required to use the OAS feature. NOTE: 2nd stage cool delay defaults to 15 minutes, if OAS is chosen to inhibit 2nd stage Heat.

*Supply Air Limit Delay Timer

2

40

43

46 49

37

34 52 LOW TEMP LIMIT

The Adjustable Cooling Limit potentiometer sets the supply air temperature at which the cooling is cycled off and the fan continues to run, allowing the coil to warm up.

*Short Cycle Timer 3 minutes, fixed. *Changeover Timer 4 minutes, fixed.

19

Cooling and Heating Limit Controls

The time delay of 3 minutes must expire before the BMPlus 3000 will re-energize heat or cool mode. This occurs when the processor detects the supply air temperature is higher or lower than the Heat/Cool limit settings.

130

140

150 160

120

170 110 HIGH TEMP LIMIT

The Adjustable Heating Limit potentiometer sets the 1st stage heat supply air temperature, at which the heating is cycled off and the fan continues to run, allowing the heat exchanger or coil to cool down.

The Adjustable 2nd stage heat differential potentiometer sets the 2nd stage heat supply air temperature, at 40 12 which the heating is cycled off and the 5 47 fan continues to run, allowing the heat 2nd STAGE HEAT DIFFERENTIAL exchanger or coil to cool down. NOTE: Allows the supply air sensor to Example: be installed in the supply air plenum, Hi Temp. limit=130 regardless of the coil/heat exchanger plus 2nd stg T= 40 configuration. Allows the installer to New limit = 170* F. fine tune virtually any 2 stage heating system! 19

26

33

Timer Reset BUTTON

TIMER RESET

CPU Reset BUTTON

SYSTEM RESET

Emergency Heat Switch EM

NORM

Momentarily pressing the TIMER RESET button will clear any Active Time Delay except the 15 minute fixed cool delay in “OAS” mode. This enables you to test and certify the installation faster. NOTE: Do not use sharp objects to press the button. Use your finger tip or the eraser head of a pencil. Press & Hold the SYSTEM RESET button for 5 seconds. That will reset the Main & Expansion modules on a BMPlus Zoning System. NOTE: A 3 minute startup delay occurs whenever the CPU Reset button is pushed, upon any initial power up, or when a power failure has occurred.

An On-Board Switch is provided that allows the user to set the system to the Emergency heat mode. This switch is shown in the NORMAL position. NOTE: An Emergency terminal is also provided at zone 1 terminal block, allowing an optional / illuminated Remote Emergency Switch (Part # RES), or a multi-function Heat Pump Thermostat, to be connected to the BMPlus 3000 Zone Control.

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362

E-Mail- [email protected]

Selecting the Options Using the DIP Switches ***FS = Factory Settings

RECORD YOUR OWN DIP SWITCH SETTINGS HERE

ON

1

Programming and setting up the BMPlus 3000 to control your HVAC system is very easy! Look below for an explanation of each dip switch function and choose your settings. Some functions may not apply to your application. Then use a pencil to mark/record your settings. If the settings get changed later on, you will have a record of the original settings.

2 3 4 5 6 7 8

HP < SYSTEM > GAS FS DF < HP > CONV FS ON < FAN DELAY > OFF FS 90S < PURGE > 120S FS OAS < 2nd STAGE > TIMER FS FS OFF < 50%RULE > ON FS OFF < SAS > ON FS GAS < FAN > HYDRONIC

HP < SYSTEM > GAS Choose the type of HVAC system you want to control. Select HP, if your system is any type of heat pump. Select GAS, if your system is a standard Gas or Oil furnace. Also applies to straight electric furnaces or hydronic (hot water coil) heating systems.

DF < HP > CONV Choose the type of Heat Pump you want to control. Select DF, if your system is a dual fuel heat pump with gas or oil furnace backup heat. Select CONV, if your system is a conventional heat pump with electric resistance backup heat. Also applies to Ground source/Geothermal heat pumps.

ON < FAN DELAY > OFF Select ON, if you want the indoor blower forced ON at the end of a heat/cool call to assist the zone purge cycle. Selecting OFF will allow the HVAC system to operate the indoor blower, without interference from the BMPlus.

90S < PURGE > 120S Select 90S or 120S, if you want the zone dampers to hold position for 90 seconds or 120 seconds at the end of any heat/cool call. This allows the HVAC system to purge the remaining hot/cold air, into the zone(s) that were calling for it.

OAS < 2nd STAGE > TIMER Select OAS, if you want to delay 2nd stage heat based on the outside air temperature sensor. Select TIMER, if you want to delay 2nd stage heat & cool based on the adjustable on-board timer. NOTE: 2nd stage cool defaults to a 15 minute delay, when OAS is chosen. NOTE: An optional Outside Air Sensor (OAS) is required to use the OAS feature.

OFF < 50%RULE > ON Select OFF, if you do not want to inhibit 2nd stage heat/cool based on the total number of zones calling. Select ON, if you want to inhibit 2nd stage heat/cool based on the total number of zones calling. More than half the total zones must be calling for the same mode, or 2nd stage will not activate. NOTE: If HP has been selected at dip switch 1, Y2 is not available. If DF or OAS has been selected, the 50% rule will apply to cooling operations only. 2nd stage heat will not be affected by this setting. The 50% rule will always dominate the 2nd stage timer unless Emergency mode is active. IMPORTANT NOTE: The BMPlus 3000 Zone Control System allows a 2 stage heating thermostat to be wired to Zone 1 only! Energizing this terminal results in over-ride of any stage 2 heating delay. The BMPlus will remain in 2nd stage mode until that terminal is de-energized. If this occurs in dual fuel mode or emergency mode, the BMPlus will stay in 2nd stage until the heating demand is satisfied. On the next demand for heat, the BMPlus will attempt to activate 1st stage heat unless, Emergency Mode is still active, or the outdoor temperature is low and OAS / DF has been selected. This comfort over-ride feature provides true versatility to your zoning system, and gives the homeowner a level of comfort control over the system.

OFF < SAS > ON

Select OFF, if you do not want to use the supply air sensor included with the BMPlus Zone Control system. Select ON, if you intend to use the included supply air sensor. Refer to the data sheet included with the supply air sensor for details.

GAS < FAN > HYDRONIC Select GAS, if your HVAC system is a gas or oil forced air furnace. Select HYDRONIC, if your HVAC system has a hot water coil, or straight electric heat with no indoor blower support. Useful when you need the indoor blower to run automatically in heat mode, just like it does in cool mode. NOTE: When you select HP on dip switch #1, the indoor fan mode is automatically set for you. EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362

E-Mail- [email protected]

3

INSTALLATION INSTRUCTIONS and THERMOSTAT WIRING Installation should be performed by qualified personnel only. Follow local & national electrical & mechanical codes. Use multi-conductor 18 awg solid copper conductors. Wire number to number or letter to letter on each control.

EMERGENCY MODE Use the optional/Illuminated Remote Emergency Switch to activate Emergency heat, or use the OnBoard Emergency Heat Switch, or use a multi-function Heat Pump Thermostat.

WARNING: THESE PANELS ARE DESIGNED FOR USE WITH 24VAC. DO NOT USE OTHER VOLTAGES! USE CAUTION TO AVOID ELECTRIC SHOCK OR EQUIPMENT DAMAGE. Mount the panel housing in a suitable/convenient location. Mounting hardware is provided. Use the knockouts provided on the panel housing as entryways into the housing. Strain relief fittings can be used if desired. Use care and do not damage the circuit board when making wire connections. NOTE: The 24 vac power required to operate a BMPlus system must be supplied by a separate transformer. WARNING! DO NOT use the 24 vac power supply from the HVAC manufacturer’s equipment. NOTE: Unlike previous zone control systems, the BMPlus 3000 supplies power to all connected expansion modules. There is no need to power up the expansion modules separately or by jumping power from one module to another. This improved design simplifies the installation wiring and reduces the possibility of polarity reversal. Line

A single 24vac, 40va Voltage UL Listed transformer PROVIDE can power the BMPlus MEANS OF DISCONNECT 3000 Main module with one damper on each zone. A total of three zones and three dampers. See page 8 for more load and TRANSFORMER 24vac, 40 - 100va transformer data.

BMPlus 3000 Main Module

W

Y

R

G

C W1 W2 Y R G EM

Optional EMERGENCY SWITCH

ONE ZONE

LED Figure 4

POWER WIRING

ZONE THERMOSTAT #1

ZONE 1 T'STAT

Wiring for heat pump application using a standard heat/cool thermostat in Zone1, with an Optional Remote Emergency Switch. Part# RES.

HEAT PUMP THERMOSTATS

24 VAC T’FORMER

ZONE 1 T'STAT

R C

WHITE-RODGERS 1F94-371 ZONE THERMOSTAT #1

R - Hot C - Common

UL LISTED

Figure 2 BMPlus 3000 Power wiring

C

E W1 W2 Y1

R

G E2

*

C W1

Regardless of the type of HVAC system you intend to control, you only need to use regular Heat/Cool Thermostats on all zones. Use standard 4 or 5 wire mechanical or digital electronic thermostats that are simple to wire and easy to program. * Common wire may not be required on your thermostats.

4

THERMOSTAT WIRING

W2 Y R G

ZONE THERMOSTAT 1 and up

ZONE 2 T’STAT

C W Y R G

Figure 3

C

W

Y

R

G

*

EM ONE ZONE

Program thermostat for * Add “Heat Pump 3 mode”. jumper wire as shown. Set the “E2/P” switch to E2.

Figure 5 Zone 1 will accept White Rodgers Model 1F93-380 and 1F95-377 Multi-Mode thermostats. White Rodgers Model 1F94-371 and CTC Model 43403 are also compatible with the BMPlus 3000.

Typical heat/cool Thermostat wiring for Zones 1 thru 7.

A Honeywell T-8011 programmable or T-8411 nonprogrammable can also be used. All of these versatile thermostats can be set up in Conventional mode, and still allow use of the Heat pump features. (i.e. Emergency Mode)

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362

E-Mail- [email protected]

THERMOSTAT WIRING CONTINUED HEAT PUMP THERMOSTATS

ZONE 1 T'STAT

WIRING FOR “ONE ZONE” MODE

HONEYWELL T8011 ZONE 1 T'STAT

ZONE THERMOSTAT #1 C

C

E W1 W2 Y

*

R

G

L

*

W2

Y

Y

R

R

G

G

EM

EM

ONE ZONE

Add field jumper wire E to W1. * Remove jumper wire * between Factory Y & W1.

Figure 7

G

ZONE THERMOSTAT 1 and up Rc

G

Rh

Optional ONE ZONE SWITCH

Wiring for manual activation of “One Zone” mode using a standard heat/cool thermostat in Zone1. An Optional, Illuminated One Zone Mode Switch, Part# “VAC” is required.

WIRING FOR “ONE ZONE” MODE

WIRING FOR RADIANT FLOOR HEAT

Y

R

LED

Figure 6 Zone 1 will accept heat pump style thermostats with a constant 24vac output during emergency mode, and separable W1 and Y terminals. These thermostats can be field configured to conventional heat / cool operation.

C

Y

W1 W2

ZONE 2 T’STAT

W

C

W1

ONE ZONE

ZONE THERMOSTAT #1

ZONE 1 T'STAT

Commercial Grade Thermostat ZONE THERMOSTAT #1 C W1 W2 Y

R

G UNOCC / OCC

W

C

C W Y R G

W1 W2 Y R G EM ONE ZONE To Radiant floor / Baseboard heat zone valve or pump relay

Figure 8

Figure 9

Wiring a split circuit thermostat to operate a Radiant floor heating or Baseboard heating Hydronic system. The BMPlus 3000 controls the cooling only, in this type of configuration.

Wiring for automatic activation of “One Zone” mode using a commercial grade thermostat in Zone 1. Program or wire the thermostat to Energize (close contact) the One Zone Terminal and setback the temperature when the building is Unoccupied....When the building is Occupied, the thermostat will de-energize (open contact) the One Zone Terminal.

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362

E-Mail- [email protected]

5

SYSTEM WIRING Single Transformer Gas/Oil Systems 1 or 2 Stage Heat

Typical gas / oil system with A/C. A jumper wire between Rc and Rh is provided. There is no need to install a jumper.

GAS/OIL Furnace 1or2 STAGE OUTDOOR CONDENSING UNIT

Y C

G

G

Y2

Y2

Y1

Y1

W1

W1

W2

W2

C

C

R

R

Conventional 1 stage Heat Pump with O or B Type Reversing Valve **

BMPlus3000 HEAT PUMP 1 STAGE

RH RC

C R

RC/RH LINK

Y

Y

G

G

C

C

R

R

T

T

OIL BURNER

T

PRIMARY CONTROL

T

CIRCULATOR RELAY OR HOT WATER ZONE VALVE CONNECTION

G Y2 Y1 O

RC/RH LINK

T

Figure 11 Two transformer Oil or Hydronic / A/C system.

* Note: Your Air Handler may include a W terminal. That means it may have it’s own isolation circuit. If you can confirm this, simply connect the W1/B terminal to the W terminal on the air handler. Do not cut the Rc / Rh jumper. Wire up your Oil Burner, Circulator relay, or Hydronic Zone valve to the isolation contacts or wires provided in the air handler. The fan is controlled via time delay relay inside the air handler.

SYSTEM

G Y2 Y1 O

W2

Y

Y

G

G

C

C

R

R

W1/B W2/E

RH RC RC/RH LINK

Figure 12 Conventional Heat Pump System

Dual Fuel Heat Pump with O Type Reversing Valve **

Typical heat pump wiring with Gas/Oil furnace backup heat. No dual fuel kit is required. Select to activate via the adjustable Timer or Outside air temperature.

HEAT PUMP 1 STAGE

GAS/OIL Furnace 1or2 STAGE W1

X/W

Y O C R

Cut Rc/Rh Jumper

T

W1

* Connect either the O or the W1/B. In a typical O type system, there will not be a connection to the W1/B terminal!

W1/B W2/E

RH RC

BMPlus3000

*

SYSTEM

W*

*W

ISOLATION TERMINALS OR WIRES

6

W2

Y OorB

TYPICAL FAN CENTER TERMINAL BLOCK

Y C

Either One Not Both

W1

X/W

W1/B W2/E

Wiring diagram for a typical oil burner, hydronic zone / Air handler with A/C. Cut the Rc / Rh link on the BMPlus Panel for systems requiring isolation.

OUTDOOR CONDENSING UNIT

AIR HANDLER WITH 1 0R 2 STAGE ELECTRIC RESISTANCE BACKUP HEAT

SYSTEM

G Y2 Y1 O

Figure 10 Single transformer Gas / A/C system.

Two Transformer Systems

Typical heat pump system wiring with electric resistance backup heat. Wire up the reversing valve to either O or W1/B, depending on your type of system. Applies to air cooled or geothermal / ground source systems.

W2 Y

BMPlus3000

W1 W2 Y

O

O

G

G

C

C

R

R

SYSTEM

G Y2 Y1 O W1/B W2/E

RH RC RC/RH LINK

Figure 13 Single stage heat pump and 1or 2 stage furnace. **Note that a Conventional & Dual fuel heat pump wire up more or less the same. The difference is how 2nd stage heat operates. In a Conventional system, the indoor fan & the compressor continues to run when 2nd stage energizes. In a Dual Fuel system, the indoor fan & the compressor shuts down when 2nd stage energizes. The BMPlus 3000 will perform these functions automatically. All you have to do is set the dip switches to the correct settings. Select DF or CONV at dip switch #2. Choose to activate 2nd stage heat by TIMER or by OUTSIDE AIR TEMPERATURE. (Optional Sensor required) You can also use a 2 stage heat thermostat at Zone 1 that will over-ride the delays if the thermostat demands it. When the thermostat 2nd stage heat demand is satisfied, the BMPlus 3000 will stage down, unless DF/OAS has been selected and the outdoor temperature is lower than the OAS changeover setting. In that case the system will continue in FUEL mode, until the heating demand is fully satisfied.

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362

E-Mail- [email protected]

SYSTEM WIRING CONTINUED Single Transformer Gas w/A/C 2 stage heat 2 stage cool

2 STAGE OUTDOOR CONDENSING UNIT

Y2 Y1 C

Typical 2 stage gas furnace with 2 stage A/C. Constant or variable speed systems can be connected and controlled. Choose time or outside air to delay 2nd stage.

2 STAGE GAS FURNACE G

G

Y2 Y1

Y2 Y1

W1

W1

W2

W2

C R

C R

BMPlus3000 SYSTEM

G Y2 Y1 O W1/B W2/E

RH RC

HVAC system with OEM Voltage Control Circuitry Some HVAC manufacturers are designing HVAC Systems with 5 - 18 vdc control circuits. Standard 24 vac thermostats will not work on these systems. These systems can only be controlled with their own thermostat. But the SYSTEM connections on a BMPlus 3000 are all dry contacts! Virtually any HVAC low voltage control circuit can be connected and controlled. All you have to do is ask the manufacturer which numbered terminal corresponds to the standard terminals. Theoretical diagram only shown below.

BMPlus3000

OEM Geothermal Heat Pump

SYSTEM G

RC/RH LINK

Y2 Y1 O W1/B W2/E

5 Note that you can route a Common lead back to the “System” terminal block, but it should never be connected! Use it as a TEST point while troubleshooting. It should be marked as such and, remain capped off when not in use!

Figure 14 Single transformer 2 Stage Heat / AC system Warning: All of the wiring diagrams provided are general in nature and may not perfectly match your particular application, due to differences in HVAC Mfr’s design and terminal designations and functions! Variations on these diagrams and other System or Thermostat applications are available by contacting the EWC Technical Support Hotline.

4 3 2

RH RC

1 RC/RH LINK

Figure 15 OEM system with 5 - 18 vdc control circuit.

ENHANCED FEATURES AND FUNCTIONS MODULE TO MODULE FACTORY POWER WIRING

SHORTED ZONE FEATURE FIRMWARE

The BMPlus 3000 includes Factory Power Wiring on all expanded systems. The 24 vac power to the expansion modules is fed through the bus cable. This simplifies your wiring and minimizes the chances of reversing polarity.

The BMPlus 3000 Zone Control System includes the Shorted Zone Feature. This feature allows the BMPlus to ignore demands from a zone thermostat that is putting out simultaneous demands for heat & cool. A condition most likely due to a short in the field wiring, incorrect wiring, or a defective thermostat. The BMPlus will honor any legitimate demands from any other zone(s), except the shorted zone. When the problem is identified and repaired, the BMPlus 3000 will automatically recognize that zone.

DUAL FUEL COMPATIBLE

The BMPlus 3000 is compatible with Dual Fuel Heat Pumps. Dual Fuel kits are not required. Select staging based on Adjustable Time Delay or an Optional Outside Air temperature Sensor. The intelligent firmware does the rest. * 5 TO 47 MINUTE 2ND STAGE TIME DELAY SETTINGS

*SECOND STAGE 50% ZONE RULE

* 5 to 47 DEGREE F. OUTSIDE AIR CHANGEOVER

* STATUS LED’s ARE INCLUDED ON ALL MODULES

* W2 AUTOMATIC OVERRIDE VIA ZONE 1 THERMOSTAT *ONE ZONE MODE CAPABILITY * 2ND STAGE HEAT ADJUSTABLE LIMIT CONTROL

* SIMPLIFIED WIRING AND SYSTEM SETUP

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362

E-Mail- [email protected]

7

DAMPER WIRING AND CONFIGURATION Note: All zone dampers default to the "OPEN" position after a purge delay has occurred. Dampers also default “OPEN” during changeover & short cycle delays, and when all zone demands are satisfied, and no signals are detected from the thermostats.

2 Wire Spring Return Motor Wiring EWC Controls Spring Return Motor Wiring MA-ESR

REFERENCE THESE DIAGRAMS PRIOR TO INSTALLATION AND POWER WIRING. DOING SO WILL SAVE TIME AND LABOR LATER ON.

M6 M4 M2 M1

{

Either one Not both

NC NO C M M

ZONE MODULE DAMPER MOTOR TERMINAL BLOCK DESIGNATION & FUNCTION ZONE MOTOR

Terminal M6 Terminal M4 Terminal M2 Terminal M1

24vac to Close a damper(s)

M6 M4 M2 M1

24vac to Open a damper(s) Constant 24vac HOT Common 24vac

Auxilary SPDT End Switch Dry Contacts Rated for 24vac only

A Spring Open Damper is wired to M1 & M6 . A Spring Close Damper is wired to M1 & M4 Figure 19

Multiple MA-ND & MA-URD Damper Wiring on a Single Zone

. Figure 16

All Models MA-ND & MA-URD Damper Wiring

1 4 6

ZONE MOTOR

M6 M4 M2 M1

M6 M4 M2 M1

1 4 6

1 4 6

ZONE MOTOR

Figure 17

All Models SMDL & BMDL Damper Wiring

1 4 6

Patented Optical Damper Motor Actuators

Patented Optical Damper Motor Actuators or new Min/Max Actuators

1 2 4

ZONE MOTOR

Patented Optical Damper Motor Actuators Figure 18

M6 M4 M2 M1

Figure 20

On all these dampers and most older style dampers, including competitor’s dampers, always wire up number to number. Contact EWC Controls Technical Support when you are on the job site for assistance with damper wiring. Do not overload your transformer!

8

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362

E-Mail- [email protected]

DAMPER WIRING CONTINUED If you need to connect numerous dampers to a single zone, or you are using dampers of unknown current draw, Isolation relays and separate power supplies will be required. Parallel as many dampers as you want as long the total current load of the motor actuators does not exceed the VA rating of the transformer. Other factors should also be considered, such as the full load amp rating of the isolating relay contacts, voltage drops from long wire runs and feeder conductor sizing to junction points. NOTE: Some older style dampers and competitor’s dampers cannot be paralleled and must be isolated or wired in tandem. Contact EWC Controls Technical Support for assistance.

1 4 6

Variations on this diagram and other damper solutions are available.

NO

ZONE MOTOR

3

M6 M4 M2 M1

1 4 6

1 4 6

TYPICAL FEEDER CONDUCTOR

TYPICAL JUNCTION POINT

C

1

NC

2

COIL 24 vac

H

1 4 6

One relay coil=One motor. Don’t overload your power transformer, by connecting too many relays.

R1 Isolation Relay SPDT action with 24 vac coil Relay is shown de-energized. All dampers are closed. L1

C

Multiple Damper Wiring on a Single Zone, using a Separate Transformer and an Isolating Relay. Maximum of 4 dampers per 40 va transformer.

To Line Voltage Provide over current protection

L2 Separate 24 vac Transformer

Figure 21

BMPlus 3000, 5000, 7000, Recommended Power Solutions Number of Dampers Directly Connected

1-3

4-5

6-7

3 40va 40va 50va 5 40va 40va 60va 7 40va 50va 75va

Use class 2 UL Listed 1585 inherently current limiting transformers only!

Spring Types @ 8 - 10 va per damper

Number of Zones

Number of Zones

ND / URD’s @ 3.5 - 5 va per damper

Number of Dampers Directly Connected

1-3

4-5

6-7

3 40va 50va 75va 5 50va 60va 75va 7 50va 60va 100va

Non-inherently current limiting transformers must have field provided over-current protection on the secondary 24 vac output. The table values provided pertain to genuine ULTRAZONE Dampers and Competitors typical 24 vac Spring loaded dampers. Included in these VA load ratings are the correct number of thermostats, the BMPlus Zone System, and a 5% field factor. Spring loaded dampers draw higher currents & require more power.

T E S T I N G D A M P E R MOTORS ND / URD / SMD / BMD Dampers - Connect 24vac common to terminal 1 and 24vac hot to terminal 4. Damper should Open. Remove 24vac hot from terminal 4 and apply to terminal 6. Damper should Close RDN / SMDL / BMDL Dampers - Connect 24vac common to terminal 1 and 24vac hot to terminals 2 and 4. Damper should Open. Remove 24vac hot from terminal 4. Damper should Close. SR / ESR Power Close / Spring Open Dampers - Connect 24vac common & hot to the two motor (M) terminals. Damper should Close. Remove 24 vac hot. Damper should Open. SR / ESR Power Open / Spring Close Dampers - Connect 24vac common & hot to the two motor (M) terminals. Damper should Open. Remove 24vac hot. Damper should Close. EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362

E-Mail- [email protected]

9

LED’S BMPlus 3000 LED’s

The BMPlus 3000 is equipped with 11 LED’s which indicate system operation and status. Familiarize yourself with the LED’s definitions, in order to quickly determine the system status and mode of operation.

RED

STATUS

The STATUS LED pulses as a steady heart beat to indicate proper Microprocessor system status.

RED

OAS

OAS LED illuminates solid to indicate that the Outdoor Temperature has fallen below the chosen set point. LED will blink rapidly to indicate a malfunctioning Outdoor Air Sensor.

RED

SAS

SAS LED illuminates solid to indicate that the Supply Temperature has exceeded the chosen set point on either the HIGH TEMP LIMIT or the LOW TEMP LIMIT. LED will blink rapidly to indicate a malfunctioning Supply Air Sensor.

RED

ZONE 3

ZONE 3 LED will illuminate solid to indicate that damper(s) is energized open, and the Zone is active.

RED

ZONE 2

ZONE 2 LED will illuminate solid to indicate that damper(s) is energized open, and the Zone is active.

RED

ZONE 1

ZONE 1 LED will illuminate solid to indicate that damper(s) is energized open, and the Zone is active.

RED

FAN

FAN LED will illuminate solid to indicate a demand for fan operation, during COOLING, HEATING, PURGE, or CONTINUOUS FAN.

RED

Y2

Y2 LED illuminates solid to indicate 2nd stage of COOLING is energized.

RED

Y1

Y1 LED illuminates solid to indicate 1st stage of COOLING is energized in GAS/HYDRONIC or HEAT PUMP mode. Y1 LED illuminates solid to indicate 1st stage HEATING in HEAT PUMP MODE.

RED

W1/B

W1/B LED illuminates solid to indicate 1st stage of HEATING is energized in Gas/Hydronic mode. W1/B LED illuminates solid to indicate ‘B’ reversing valve is energized in HEAT PUMP operation.

RED

W2/E

W2/E LED illuminates solid to indicate 2nd stage of HEATING is energized in GAS/HYDRONIC or HEAT PUMP mode. W2/E LED illuminates solid to indicate EMERGENCY HEAT is energized in HEAT PUMP mode.

The BMPlus Zone Control System is not compatible with 2 speed / 2 stage compressor Heat Pumps. (3 stage heat pumps).

NOTES:

10

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362

E-Mail- [email protected]

BMPlus 3000 3 Zone Main Module

Rugged 10 pin Expansion Header Protective header cap not shown for clarity

User Friendly Adjustable Potentiometers

J1

CONTROL Rugged Damper Motor Terminal Blocks

19

ZONE3 MOTOR

26

5

R2

SAS

R 41

DIFFERENTIAL

R4

D 21

U3

C7 C8

CPU RESET

R 42

SAS

R 43

OAS

C9

R5

OAS

R 44 R 45

U2

D4

R 10 R 11 R 12 R 13 R 14 R 15 R 16 R 17 R 18

+

+

C1

C2

C13

R 35

OFF

R 58 C14

R 59 R 60

U6

R 61

D19 D20

Z1

R 19

R 62 R 63

LED 1

STATUS

LED 2

OAS

LED 3

SAS

LED 4

ZONE 3

R 22

K 6 R 23 R 24 R 25 D7

R 26 R 27

K7 R 29 R 30

D8

ZONE 1

LED 8

R 31

K8

LED 9

R 32

R 80

R 33 D9

R 69 R 70

U8 R 73

EM

R 74

Y1

R 75

W1

B

W2

EM

R 77

BMPlus 3000

R 78 R 79

+

ONE ZONE

R 72

Y2

Multi Functional Zone 1 Thermostat Terminal Block

EM

R 71

LED 11 C4

+

FAN

R 67 R 68

LED 10

R 34 C3

R 66

U7

ZONE 2

LED 7

C W1 W2 Y R G

R 65

LED 6 R 28

ZONE1 T STAT

R 64

LED 5

Rugged Thermostat Terminal Blocks

C W Y R G

R 57

R 21 D6

ZONE2 T STAT

R 56

< > ON

HP < SYSTEM > GAS DF < HP > CONV ON < FAN DELAY > OFF 90s < PURGE > 120 s OAS < 2 ND STAGE > TIMER OFF < 50% RULE > ON OFF < SAS > ON GAS < FAN > HYDRONIC

K4

D17 D18

R 54 R 55

U5

R 20

EWC

R 51

R 53

D5

G Y2 Y1 O W1 B W2 E RH RC

R 50

C11 Y 1

SW 3

K5

C W Y R G

R 49

R 52

R C

ZONE3 T STAT

R 48

TIMER RESET

R8

F1

C10

C12

K 3 R9

D3

R 46 R 47

U4

R7 D2

Outdoor Air Sensor Connections

D15 D16

R6

RC RH LINK

On-Board System Rc/Rh Link

R 40

47

K2

SYSTEM

Isolated HVAC System Terminal Block

40

R 36 R 37 R 38 R 39

D1

M6 M4 M2 M1

M6 M4 M2 M1

D10 D11 D12 D13

33

2 ND STAGE HEAT

R3 C6

U1

ZONE2 MOTOR

26

19

HIGH TEMP LIMIT

C5

K1

24 VAC T’FORMER Polarized Power Input Terminals

52

150

160 12 170 5

110

LOW TEMP LIMIT

R1

ZONE1 MOTOR

Easy Setup 8 switch Bank

34

47

140

130

49 120

2 ND STAGE TIMER OAS

Timer Reset Button

Thermal Circuit Breaker

46

40 37

12

M6 M4 M2 M1

43

40

33

Supply Air Sensor Connections

D14

SYSTEM

R 76

NORM SW 4

Figure 22

System Status LED’s

On-Board Emergency Switch

The BMPlus 3000 Zone Control System includes Module to Module Factory Wiring. We power up the Expansion Modules for you. The XM2 Expansion module includes a Status LED and Damper Status LED’s. See page 11 and 12 for drawing representations of a 5 and 7 zone system and appropriate dip switch settings. All you have to do is: 1. Set the dip switches to your specific application. 2. Connect your thermostats, dampers and system wiring. 3. Power up the Main Module 4. Check System Operation. EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362

E-Mail- [email protected]

11

Setting the XM2 Expansion Panel DIP Switches Each expansion module has a 2 position DIP switch. Factory set to insure the main module recognizes each expansion module in the proper sequence.

BMPlus 5000

K1

D M P R

M6 M4 M2 M1

R2 C2 D1

R 17

R3 R4

R 19

R 21

R 23

D5

D7

R8

A 01 A 02

C W Y R G

T S T A T

C W Y R G

T S T A T

Y1

D M P R

R5

K2

M6 M4 M2 M1

R9 U4

R6

D2 D3

R 18

D8

R 20

R 22

D4

D6

R7

Z1

J1

U2

EWC

DIP switch settings for 1st Expansion panel. Zones 4 & 5

R 24 R 25 R 26 R 27 R 28 R 29 R 30

J1

CONTROL

Protective header caps not shown for clarity

26

19

ZONE3 MOTOR

43

40

33

46

5

34

47

52

2 ND STAGE

TIMER

OAS R2

40

R 40

47

SAS

R 41

R4

R 42

SAS

R 43

OAS

C9

R5

D 21

U3

C7 C8

OAS

R 44 R 45

D15 D16

U2

K2 R6

D2

D4

R 10 R 11 R 12 R 13 R 14 R 15 R 16 R 17 R 18

F1

24 VAC T’FORMER

+

+

C1

C2

OFF

K 6 R 23

R 58 C14

R 59 R 60

U6

R 61

D19 D20 R 62 R 63

STATUS

R 25 R 26 R 27

K7

OAS

LED 3

SAS

LED 4

ZONE 3

R 29 R 30

ZONE 2 ZONE 1

LED 7

FAN

LED 8

K8

LED 9

R 32 R 33 D9

R 34 C3

R 67 R 68 R 69 R 70

ONE ZONE

R 72

Y2

R 73

EM

R 74

Y1

R 75

LED 10

W1

B

W2

EM

R 77

BMPlus 3000

R 78 R 79

+

EM

R 71

U8

LED 11 C4

+

R 66

U7

LED 5

R 31

C W1 W2 Y R G

R 65

LED 6 R 28

ZONE1 T STAT

R 64

LED 2

R 24

R 80

C W Y R G

R 57

Z1

R 22

D8

ZONE2 T STAT

R 56

R 19 LED 1

D7

D17 D18

R 54 R 55

R 21 D6

EWC

R 35

< > ON

HP < SYSTEM > GAS DF < HP > CONV ON < FAN DELAY > OFF 90s < PURGE > 120 s OAS < 2 ND STAGE > TIMER OFF < 50% RULE > ON OFF < SAS > ON GAS < FAN > HYDRONIC

R 20

RC RH LINK

C13

U5

D5

G Y2 Y1 O W1 B W2 E RH RC

R 51

R 53

K4

SYSTEM

R 50

C11 Y 1

SW 3

K5

C W Y R G

R 49

R 52

R C

ZONE3 T STAT

R 48

TIMER RESET

R8

D3

C10

C12

K 3 R9

ZONE1 MOTOR

R 46 R 47

U4

R7

24 vac transformer

R 36 R 37 R 38 R 39

D1

M6 M4 M2 M1

M6 M4 M2 M1

33

DIFFERENTIAL

CPU RESET

U1

26

19

D10 D11 D12 D13

2 ND STAGE HEAT

R3 C6

K1

ZONE2 MOTOR

150

HIGH TEMP LIMIT

C5

D14

SYSTEM 160 12 170 5

110

LOW TEMP LIMIT

R1

140

130

49 120

40 37

12

M6 M4 M2 M1

To Line Voltage

U3

+ R1

FACTORY SUPPLIED POWER & DATA POLARIZED BUS CABLE

Provide Over-Current Protection

R 10 R 11 R 12 R 13 R 14 R 15 R 16

C3

STATUS

U1

C1

R 76

NORM SW 4

Figure 23 12

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362

E-Mail- [email protected]

BMPlus 7000

Setting the XM2 Expansion Panel DIP Switches Each expansion panel has a 2 position DIP switch. Factory set to insure the main module recognizes each expansion module in the proper sequence.

U3

+

K1

D M P R

R1

M6 M4 M2 M1

R2 C2 D1

Protective header caps not shown for clarity

R 17

R3

R 19

R 21

R 23

D5

D7

R8

A 01 A 02

R4

C W Y R G

T S T A T

C W Y R G

T S T A T

C W Y R G

T S T A T

C W Y R G

T S T A T

Y1

D M P R

R5

K2

M6 M4 M2 M1

R9 U4

D2 D3

R 18

D8

R6

J1

K1

D6

D4

R 22

U2

EWC

D M P R

R 20

R7

Z1

R 10 R 11 R 12 R 13 R 14 R 15 R 16

C3

U3

+ R1

M6 M4 M2 M1

R2 C2 D1

R 17

R3 R4

R 19

R 21

R 23

D5

D7

R8

A 01 A 02

DIP switch settings for 2nd Expansion panel. Zones 6 & 7

R 28 R 29 R 30

R 24 R 25 R 26 R 27

STATUS

U1

C1

FACTORY SUPPLIED POWER & DATA POLARIZED BUS CABLE

R 10 R 11 R 12 R 13 R 14 R 15 R 16

C3

STATUS

U1

C1

Y1

D M P R

R5

K2

M6 M4 M2 M1

R9 U4

D2 D3

R 18

D8

R6

R 20

R 22

D4

D6

R7

Z1

J1

U2

EWC

R 24 R 25 R 26 R 27

R 28 R 29 R 30

DIP switch settings for 1st Expansion panel. Zones 4 & 5

J1

CONTROL 26

19

ZONE3 MOTOR

52

2 ND STAGE

TIMER

130

OAS R2

150

40

R5

D 21

U3

C7 C8

R 42

SAS

R 43

OAS OAS

R 44 R 45

D15 D16

D1

U2 R6

R8

D4

D3

+ C1

24 VAC T’FORMER

+ C2

R 53

LED 1

STATUS OAS

LED 3

SAS

LED 4

ZONE 3

R 24

R 26 R 27

K7

R 58 C14

R 59 R 60

U6

R 61

D 19 D20

R 29 R 30

R 32

ZONE 2 ZONE 1

LED 7

FAN

LED 8

Y2

LED 9

Y1

R 80

R 33 D9

R 69 R 70

ONE ZONE

R 72 R 73

EM

R 74 R 75

W1

B

W2

EM

R 77

BMPlus 3000

R 78 R 79

+

EM

R 71

U8

LED 10

C4

+

R 67 R 68

LED 11

R 34 C3

C W1 W2 Y R G

R 65 R 66

U7

LED 6

R 31

K8

ZONE1 T STAT

R 64

LED 5

R 28

D8

C W Y R G

R 57

R 62 R 63

LED 2 R 22

R 25 D7

ZONE2 T STAT

Z1

K 6 R 23

EWC

R 55

R 21 D6

D17 D 18

R 54

R 56

R 19

R 20

RC RH LINK

R 35

< > ON

HP < SYSTEM > GAS DF < HP > CONV ON < FAN DELAY > OFF 90s < PURGE > 120 s OAS < 2 ND STAGE > TIMER OFF < 50% RULE > ON OFF < SAS > ON GAS < FAN > HYDRONIC

D5

G Y2 Y1 O W1 B W2 E RH RC

C13

U5

OFF

K4

SYSTEM

R 51

C11 Y 1

SW 3

K5

C W Y R G

R 49 R 50

R 52

R C

ZONE3 T STAT

R 48

C12

R 10 R 11 R 12 R 13 R 14 R 15 R 16 R 17 R 18

F1

C10

TIMER RESET

K 3 R9

ZONE1 MOTOR

R 46 R 47

U4

R7 D2

24 vac transformer

SAS

R 41

C9

K2

M6 M4 M2 M1

R 36 R 37 R 38 R 39 R 40

DIFFERENTIAL

CPU RESET

U1

33

47

R4

C6

D 10 D11 D12 D13

2 ND STAGE HEAT

R3

K1

26

19

HIGH TEMP LIMIT

C5

D14

SYSTEM 160 12 170 5

110

LOW TEMP LIMIT

R1

140

49 120

34

47

M6 M4 M2 M1

To Line Voltage

46

40 37

5

ZONE2 MOTOR

Provide Over-Current Protection

40

33

12

M6 M4 M2 M1

43

R 76

NORM SW 4

Figure 24

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362

E-Mail- [email protected]

13

To Line Voltage

2 STAGE GAS FURNACE

G

O

Y

W2

C

G

O

Y

W2

W1

C

R

W1

R

M6 M4 M2 M1

M6 M4 M2 M1

M6 M4 M2 M1

R C

J1

ZONE3 MOTOR

ZONE2 MOTOR

ZONE1 MOTOR

SYSTEM

24 VAC T’FORMER

G Y2 Y1 O W1 B W2 E RH RC R 80

RC RH LINK

F1

BMPlus 3000 Wiring Diagram Dual Fuel Heat Pump

43

LOW TEMP LIMIT R5

HIGH TEMP LIMIT

140

CONTROL 130

R3

110

49 120

46

52

C6

CPU RESET

TIMER RESET

C11 Y 1

< > ON

SYSTEM 26

DIFFERENTIAL

19

R4 C7 C8

U4

U3

C9

U2

OAS U7

U6

U5

C12

LED 2

SAS

U8

40

33

C14

C10

47

C13

2 ND STAGE HEAT

5

160 12 170

Z1

LED 3

ZONE 2

ZONE 3

STATUS

LED 5

B

ZONE 1 Y2

FAN LED 8

W1

Y1 EM

D 10 D11 D12 D13

R 35

R 73

R 75

R 74

R 78 R 79

R 77

R 76

BMPlus 3000

W2

LED 9

+

C4

LED 11

LED 10

LED 7

LED 6

LED 4

LED 1

HP < SYSTEM > GAS DF < HP > CONV ON < FAN DELAY > OFF 90s < PURGE > 120 s OAS < 2 ND STAGE > TIMER OFF < 50% RULE > ON OFF < SAS > ON GAS < FAN > HYDRONIC

OFF

150

R 36 R 37 R 38 R 39

SW 4

ZONE1 T STAT

ZONE2 T STAT

ZONE3 T STAT

D14

R 72

R 71

R 70

R 69

R 68

R 67

R 66

R 65

R 64

R 62 R 63

R 61

R 60

R 59

R 58

R 57

R 56

R 55

R 54

R 53

R 52

R 51

R 50

R 49

R 48

R 46 R 47

R 45

R 44

R 43

R 42

R 41

R 40

2nd Stage Heat Activates via Outdoor air Temperature, On-Board or Remote Emergency Switch

26 40

34

C5

U1

R6 R7

SW 3

R8 R9 R 10 R 11 R 12 R 13 R 14 R 15 R 16 R 17 R 18

R2

K1

K2

C2

+

D3

K3

D2

D1

47

40 37

33

2 ND STAGE OAS TIMER

19 12 5 R1

D4

+ C1

K4

R 19

R 22

R 21

R 20

K5

D5

D6

R 23 R 24 R 25

K6

D7

R 26 R 27 R 28

R 30

R 29

K7

D8

R 31 R 32

C3

R 34

R 33

K8

D9

+

OUTDOOR AIR SENSOR

ON-BOARD

SUPPLY AIR SENSOR

SAS

SAS

OAS

OAS

D15 D16

C W Y R G D17 D 18

C W Y R G D 19 D20

EM

C W1 W2 Y R G

EM

ONE ZONE

NORM

E-Mail- [email protected]

All wiring should be done to local and national codes and ordinances. Use color-coded, multi-conductor wire. Wire number to number or letter to letter on each control.

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362

WARNING: THESE PANELS ARE DESIGNED FOR USE WITH 24VAC. DO NOT USE OTHER VOLTAGES! USE CAUTION TO AVOID ELECTRIC SHOCK OR EQUIPMENT DAMAGE.

EWC

D 21

OUTDOOR HEAT PUMP

X/W

Y O C R

24 vac transformer 40va

ND / URD DAMPERS

1 4 6 1 4 6 1 4 6

ZONE THERMOSTAT 3

C W Y R G

ZONE THERMOSTAT 2

C W Y R G

ZONE THERMOSTAT 1

OFF

ON

C W Y R G

32 4

EMERGENCY MODE

OPTIONAL REMOTE

Y C

OUTDOOR CONDENSING UNIT

24 vac transformer 40 va

G

Y1

W1

W2

C

R

G

Y1

W1

W2

C

R

2 STAGE GAS FURNACE

To Line Voltage

ND / URD DAMPERS

1 4 6

1 4 6

1 4 6

F1

R1

5

12

26

R2

U1

C5

R8

R7

C2

C1

C3

R 34

R 33

R 32

52

OFF

< > ON

C11 Y 1

TIMER RESET

R5

HIGH TEMP LIMIT

CPU RESET

R3

110

140

C7 C8

R4

STATUS

ZONE 2

LED 5

+

C4

LED 11

LED 10

LED 9

LED 8

LED 7

EM

B

U8

U7

U6

U5

C13

C14

C10

D 10 D11 D12 D13

R 78 R 79

R 77

R 76

R 75

R 74

R 73

R 35

BMPlus 3000

W2

W1

Y1

Y2

FAN

ZONE 1

ZONE 3

LED 6

SAS

LED 4

OAS

U4

C12

U2

U3

C9

47

40

33

2 ND STAGE HEAT

LED 3

LED 2

LED 1

Z1

26

DIFFERENTIAL

19

160 12 170 5

150

HP < SYSTEM > GAS DF < HP > CONV ON < FAN DELAY > OFF 90s < PURGE > 120 s OAS < 2 ND STAGE > TIMER OFF < 50% RULE > ON OFF < SAS > ON GAS < FAN > HYDRONIC

C6

+

130

49 120

46

SYSTEM

SW 4

ZONE1 T STAT

ZONE2 T STAT

NORM

EM

ONE ZONE

EM

C W1 W2 Y R G

D 19 D20

C W Y R G

D17 D 18

C W Y R G

D15 D16

OAS

OAS

SAS

SAS

SUPPLY AIR SENSOR

W W2 Y R G

ZONE THERMOSTAT 1

C W Y R G

ZONE THERMOSTAT 2

C W Y R G

ZONE THERMOSTAT 3

E-Mail- [email protected]

All wiring should be done to local and national codes and ordinances. Use color-coded, multi-conductor wire. Wire number to number or letter to letter on each control.

R 72

R 71

R 70

R 69

R 68

R 67

R 66

R 65

R 64

R 62 R 63

R 61

R 60

R 59

R 58

R 57

R 56

R 55

R 54

R 53

R 52

R 51

R 50

R 49

R 48

R 46 R 47

R 45

R 44

R 43

R 42

R 36 R 37 R 38 R 39

ZONE3 T STAT

D14

R 41

R 40

WARNING: THESE PANELS ARE DESIGNED FOR USE WITH 24VAC. DO NOT USE OTHER VOLTAGES! USE CAUTION TO AVOID ELECTRIC SHOCK OR EQUIPMENT DAMAGE.

D9

R 30 R 31

K8

D8

R 29

R 28

R 26 R 27

K7

D7

R 25

R 23 R 24

R 22

R 21

K6

D6

R 19

SW 3

R 20

K5

D5

K4

+

D3

R 10 R 11 R 12 R 13 R 14 R 15 R 16 R 17 R 18

K 3 R9

K2

43

LOW TEMP LIMIT

R6

34

K1

D2

D1

47

+

D4

40

40 37

33

2 ND STAGE OAS TIMER

19

CONTROL

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362

EWC

R 80

RC RH LINK

SYSTEM

24 VAC T’FORMER

ZONE1 MOTOR

ZONE2 MOTOR

G Y2 Y1 O W1 B W2 E RH RC

C

R

M6 M4 M2 M1

M6 M4 M2 M1

M6 M4 M2 M1

ZONE3 MOTOR

J1

2nd Stage Heat Activates via Adjustable Timer or Zone 1 Thermostat

2 STAGE GAS HEAT WITH A/C

BMPlus 3000 Wiring Diagram

D 21

T R O U B L E S H O O T I NG SYMPTOM

SOLUTIONS

LED’S are responding properly but HVAC system is malfunctioning.

Check HVAC system wiring for proper connections. Check HVAC system wiring for shorts/miswiring. Check HVAC System. Refer to Technical Bulletin for correct Setup/Wiring/Dip Switch settings.

LED’s are not responding properly and HVAC system is malfunctioning.

Check HVAC system wiring for shorts/miswiring. Check HVAC system wiring for proper connections. Check HVAC thermostat for proper connections. Refer to Technical Bulletin for correct Setup/Wiring/Dip Switch settings.

LED’s illuminate and HVAC system functions normally but dampers do not respond.

Check damper motor wiring for proper connections. Check damper motor 24vac transformer voltage/fuse/BMPluscircuit breaker. Check damper motor wiring for shorts/miswiring. Refer to Technical Bulletin for correct Setup/Wiring. REFER TO THE DAMPER MOTOR TESTING PAGE 8

LED’s do not illuminate and HVAC system does not respond.

Check HVAC/BMPlus system transformer supply voltage. Check HVAC/BMPlus system 24vac transformer voltage/fuse/BMPlus circuit breaker. Check HVAC/BMPlus system wiring for shorts/miswiring.

CHECK YOUR WIRING DETECTING 24vac SHORTS

SYMPTOMS: Module(s) appear to be dead!

HVAC system not responding and BMPLUS 3000 LED’s are off. Dampers not responding and THE BMPLUS 3000 LED’s are off.

If 24vac short has occurred, 24vac will be present at the BMPlus 3000 Module Input terminals R & C; but 24vac will not be present at the Thermostat R&C.

ISOLATING 24vac SHORTS

Disconnect the wire(s) from the ‘R’ terminals on the BMPlus 3000 thermostat terminal blocks , and the “M2/M4/M6’’ terminals on the BMPlus 3000 damper motor terminal blocks. Restore power. If the short is no longer present, Ohm out the thermostat and damper field wiring for shorts/misconnections. Replace or repair wires as necessary. Restore power. Module(s) will resume operation.

F1 circuit breaker protects the BMPlus 3000 and reacts to a short in the damper motor or thermostat component and field wiring.

SOLUTIONS: Remove 24vac power from BMPlus 3000 and allow circuit breaker to cool! Find and repair short(s) in damper and/or thermostat field wiring. Restore 24 vac power.

TESTING THERMOSTATS During a demand for heating, the thermostat should apply a 24vac hot signal to the W and or W2 terminals. During a demand for cooling, the thermostat should apply a 24vac hot signal to the Y and G terminals. During a continuous fan demand, the thermostat should apply a 24vac hot signal to the G terminal. Check to make sure that the thermostat Rc and Rh terminals are connected together, unless your application requires separation of these circuits. Use the (C) Common terminal provided at each thermostat terminal block to wire up full 24 vac hard-wired thermostats. You should reference the (C) Common terminal when troubleshooting incoming thermostat demand signals, even if no wire is connected there.

TECHNICAL SUPPORT EWC Controls provides superior toll free Troubleshooting Support for the BMPlus 3000 when you are on the job site! Call 1-800-446-3110 Monday - Friday 8am to 5pm EST Otherwise call 1-732-446-3110 for information on the BMPlus 3000 and other ULTRA-ZONE products.. When calling for Technical Support, please have a multi-meter, pocket screwdriver, and wire cutter/stripper handy.

16

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362

E-Mail- [email protected]