Journal of Electrical Engineering & Technology Vol. 4, No. 3, pp. 337~345, 2009 337
Optimum Allocation of Reactive Power in Real-Time Operation under Deregulated Electricity Market Mahdi Rajabzadeh† and Masoud A. Golkar* Abstract – Deregulation in power industry has made the reactive power ancillary service management a critical task to power system operators from both technical and economic perspectives. Reactive power management in power systems is a complex combinatorial optimization problem involving nonlinear functions with multiple local minima and nonlinear constraints. This paper proposes a practical market-based reactive power ancillary service management scheme to tackle the challenge. In this paper a new model for voltage security and reactive power management is presented. The proposed model minimizes reactive support cost as an economic aspect and insures the voltage security as a technical constraint. For modeling validation study, two optimization algorithm, a genetic algorithm (GA) and particle swarm optimization (PSO) method are used to solve the problem of optimum allocation of reactive power in power systems under open market environment and the results are compared. As a case study, the IEEE-30 bus power system is used. Results show that the algorithm is well competent for optimal allocation of reactive power under practical constraints and price based conditions. Keywords: Ancillary Services, Deregulation, Reactive power Market, Voltage Stability criteria
1. Introduction The primary objective of ISO is to match the electricity supply with demand. At the same time, ISO must control generation to the extent necessary to maintain reliability, optimize transmission efficiency, and maintain stability of participants, such as GenCo, TransCo and Discos is to maximize theirs own profit [1]. Reactive power management and control is a significant factor to support the system security and reliability. In a deregulated electricity market, active power has generally become a commodity, and reactive power has been treated as an ancillary service. And many of the deregulated electricity markets have established financial compensation mechanisms for reactive power services [2]. Adequate provision for reactive power is essential in power systems in order to ensure secure and reliable operation of power systems. Reactive power is tightly related to bus voltages throughout a power network, and hence reactive power services have a significant effect on system security. Insufficient reactive power supply can result in voltage collapse, which has been one of the reasons for some recent major blackouts [3]. Reactive power is supplied by several different sources, including transmission equipment (such as capacitors, reactors, Static VAR Compensators (SVCs) and static compensators), generators, and synchronous condensers. Reactive power does not travel over long distances at high line loadings due to significant losses on the wires. Thus, reactive †
Corresponding Author : K.N.Toosi University of Technology, Tehran, Iran. (
[email protected]) * K.N.Toosi University of Technology, Tehran, Iran. (
[email protected]) Received 12 March 2009; Accepted 9 July 2009
power usually must be procured from suppliers near where it is needed. This factor limits the geographic scope of the reactive power market and, thus, the number of suppliers that can provide reactive power and the amount of competition at any place and time, at least in the short term before other suppliers can enter the market [4]. This paper focuses on and challenges the issues related to reactive power ancillary service procurement and pricing in competitive power market environments. Most existent plans for reactive power purchasing have two common aims; one of them is to create propellant in reactive generators in order to participate in reactive power market and appropriate coordination between economical and technical problems [5, 6]. Early attempt of this approach similar to real power spot price theory can be found in [7]. But this model can not create a transparent competition between reactive generators and there is no attention to voltage stability. Li and David proposed a modified AC OPF model for reactive power wheeling rates analysis [8]. Bhattacharya and Zhong constructed a reactive bid curve of generator in [9] and further develop a competitive market mechanism based on it in [10]. However, as pointed out in [11], the application of marginal reactive price is not very practical due to its volatile and erratic behaviors. With these considerations cost-based reactive power pricing and management methods were proposed in [11, 12]. However, there are two drawbacks in their proposed approaches, namely technical signals but not economic signals are used to determine generators’ reactive power obligation and only reactive power amount, without considering the effects of the loading location on the costs, is used to charge reactive loads. As a result economic effectiveness is deteriorated [13]. In [6, 14-16] the real power market consequences are supposed to be steady and then the optimal
338
Optimum Allocation of Reactive Power in Real-Time Operation under Deregulated Electricity Market
reactive power flow is done, also all the reactive capacities are obliged to participate in market. Generators need reactive power in order to generate real power but this model pay money to generators in all operation conditions. Such a structure has many differences to competitive one. A model for simulation of voltage stability can be found in [17] but it did not discuss the determination of operating point by the use of voltage stability margin, also there is no warranty for the preservation of voltage stability. A model was proposed in [18] which minimize the active and reactive power generation cost simultaneously, since the active power generation cost is much bigger than reactive power generation cost, therefore the act of reactive generators will be neglected. There is no attention to voltage stability in this paper too. This paper proposed a new model for the optimal allocation of the reactive power reserves in real-time operation. In the proposed method, the management of the reactive power reserves is proposed as an optimization problem. The main objective of the optimization is to minimize reactive support cost as well as to decrease the active power losses by rescheduling the reactive power injection of the reactive power supports. In this approach, the voltage stability margin is incorporated in to the power flow equations to maintain the power system in a secure operating state where a sudden load variation or even a contingency occurs. Optimal reactive power dispatch is obtained with the objective of minimizing reactive support cost. Then, a pricing structure including compensation to reactive sources and charge of reactive consumers is established with both technical feasibility and economic equitability taken into account. In this paper ISO, as a facilitator of reactive service, assures the total compensations to reactive suppliers equal to the revenues from the reactive power consumer. Based on analysis of generators’ production cost of reactive power, a segmented bidding model of generators’ reactive power generation is exerted [19]. The proposed method specifies the active and reactive power of generators and the reactive power of static VAR compensators and the variation of transformers tap changer as well as their cost. In this paper both active and reactive power flow is accomplished while optimization. Each reactive power supports proposes its reactive power capacity and its cost by a clear function so there are a transparent competition between reactive generators. The optimization problem is solved with both genetic algorithm (GA) and particle swarm optimization (PSO) method. Finally, the simulation results on a IEEE-30 bus power system are presented.
is Significant in three aspects. In long-term reactive power planning, system security is important in long-term voltage stability and the main goal is to determine the amount and placement of reactive resources to achieve voltage stability. Another is short-term reactive power planning and management. In this case it is supposed that the reactive resources are denoted thus the optimal allocation of reactive reserves in short-term is significant. And the last is reactive power management in Real-Time Operation. In which the reactive power capacity is available and the optimal uses of reactive resources for voltage stabilization in real-time operation is important. By the inspection of reactive power market models, it is observable that the reactive power market structure should be able to prepare the necessary conditions for the independent reactive power generators to participate in the market and also should have the ability to adjust energy treaties when there is reactive power resources shortage or even utility technical constraints. The designed model should prepare the competition possibility for energy treaties stabilization. Reactive power market structure should consider the utility voltage stability in a proper manner and achieving an optimal point as a reactive power market consequence can not assure utility stability operation in realtime operation.
3. Problem Formulation In the deregulated electricity market, concentration is on optimal reactive power purchasing in order to minimize management costs. Reactive power management in realtime operation is considered in this part. Active power generation quantity and situation, transmission system configuration and also the location of reactive power resources have the significant role in voltage stability. A new model for the optimal allocation of reactive power is proposed which considers the voltage stability restriction in the realtime operation besides voltage magnitude constraints.
3.1 Objective Function The following objective function is formulated where Q gi , Q shj
and
Q gi are ξ
purchased reactive power of generators at
th
bus i , static VAR compensators at bus jth and purchased reactive power of generators at bus i with the load increase respectively; ΔP gi is the active power participation of generators at bus ith which compensate utility losses and
2. Favorite Reactive Power Market Model The main subjects related with the reactive power management are: maintaining an adequate security level, defining correct economic signals, providing a simple and transparent structure, ensuring market equity, and avoiding additional charges on the final energy price. Reactive power planning and management in deregulated electricity market
ΔT
is the change of transformation ratio. ξ
Min J (Q g , Q sh , Q g , Δ P g , Δ T +
NT
∑ C Tk ( Δ T k )
k =1
+
NG
ξ
)=
NG i =1
∑ τ gqi λ gi (Q gi ) + MCP i =1
N sh
∑ λ gi (Q gi ) + ∑ C shj (Q shj ) + j =1
NG
.( ∑ ( P i =1
0 gi
+
ND
(1)
0 Δ P gi ) − ∑ P dl ) l =1
In Eqn. (1) P0gi and P0dl are the active power outputs of generator i and the power consumption of consumer l
Mahdi Rajabzadeh and Masoud A. Golkar
respectively which are obtained from electricity market; τ gqi is the adjustment coefficient of reactive power cost increase while increasing in load; MCP is the market clearing price in which electricity is purchased in order to compensate the active power losses. N G , N sh , N T and N D are the number of generator units, static VAR compensators, transformers and loads respectively. λ gi (Q gi) and
C shj (Q shj ) are the costs of reactive power support from the point of view of each generator or static VAR compensator respectively which their computational methods are discussed in subsequent part. C Tk (ΔT k ) is the cost function of adjustable ratio transformer k, the fourth term is the cost of reactive power support while increasing in load and the final term represents the active power loss, which is procured at market clearing price.
339
Suppose that one generator unit gets p 0 active power by bidding, when the generator operates in area 0-K-N-B-C, the active power will not decrease when the reactive power increases, so the reactive power cost mainly included investment cost. When the generator operates in area C-B-A, it has to reduce its active power in order to increase reactive power, so the reactive power cost should include investment cost and reduced active power income. When operates in area 0-K-H-F-E, the generator is in leading phase, so the reactive power cost should include investment cost and operation fare for leading phase. In the same way, when the generator operates in area D-F-E, the reactive power cost must include investment cost, opportunity cost and operation fare for leading phase.
A. Reactive Power Bidding Model of Generators ISO operates the market of reactive power ancillary service according to the quoted price for reactive power of each generator unit and coordinates the reactive compensation devices and transformers belonged to power Grid Company to procure the needed reactive power. Because ISO cannot know exactly the reactive power generation cost of generator units, based on general characters of reactive power generation cost, the reactive power segmented bidding model of generator units is used there, that is to say, generator units join the reactive power market by bidding. The reactive power generation costs of generator units are composed of investment cost, opportunity cost and operation and maintenance cost. The investment cost is reactive power capacity cost of generator units, and the opportunity cost equals to the reduced active power income because of the increased reactive power. The operation and maintenance cost aims mainly that when generator operates in leading phase, the temperature of the stator head increases, and the range of steady stability decreases, so the operators should strengthen the management of equipments, and this part of expenses should be compensated. When generators in operating, the constraints of the stator winding temperature, the excitation winding temperature, the power of prime move, the temperature of stator head in leading phase and the stability in parallel compose the operation limit diagram of generator units, as shown in Fig. 1. The operation point of generator is limited within the area of A-N-H-D.
Fig. 2. Reactive power bidding curve of generator units Based on above analysis, the reactive power-bidding curve of generator units is as in Fig. 2; and the corresponding reactive power-bidding model is shown in Eqn. (2). Q , Q , Q , Q in Fig. 2 correspond to the corremax
min
1
2
sponding value in Fig. 1. λ q 0 Compensated the reactive power investment cost of generator, corresponding to the capacity price of reactive power, to encourage generator traders to invest reactive power and ensure system having enough reactive power resources. ( λ q1 − λ q 0 ) compensates the expenditure for generator in leading phase. Beeline L1 compensates the investment cost and opportunity cost of reactive power, and L 2 compensates the investment cost and opportunity cost of reactive power and operation in leading phase. ⎧λ q1 + (a′ Q gi + b′) Q min ≤ Q gi ≤ Q1
( )
λ gi Q gi
⎪ ⎪⎪λ q1 =⎨ ⎪λ q 0 ⎪ + (a Q gi + b) ⎩⎪λ q 0
Q1 ≤ Q gi ≤ 0 0 ≤ Q gi ≤ Q 2
(2)
Q 2 ≤ Q gi ≤ Q max
The bidding model can encourage generator traders to join bidding of reactive power and make them reclaim their cost reasonably and take part in reactive power market positively, in order to make system get enough reactive power resources and satisfy the demand of reactive power load and provide voltage support. For a given unit, λ q0 should have a fixed value, because the investment cost of reactive power is lower oppositely, λ q0 can be prescribed Fig. 1. Operation limit diagram of generator
maximal value to prevent gamble behaviors of generator
Optimum Allocation of Reactive Power in Real-Time Operation under Deregulated Electricity Market
340
traders and ensure the stability of reactive power market. Under the condition of invariable active power, reactive power's regulation of generator is an effective way to regulate voltage, which need not have extra expenditure, so describing λ q0 as a lesser value is not only accord with the characters of reactive power's generation but also can make system procure more reactive power from generator units; not only can make generator units reclaim their cost of reactive power but also decrease expenditure of reactive power ancillary services effectively, and accordingly decrease the reactive power expenditure that users bear, utilize resources adequately, to realize maximal social benefits [1]. B. Cost of reactive compensators The charge for using reactive compensators is assumed proportional to the amount of the reactive power purchased and can be expressed as: (3) C shj Qshj = r shji Qshji
( )
Where r shji and Q shj are the reactive cost and the amount purchased, respectively, at location j. The production cost of a compensator is assumed as its capital investment return, which can be expressed as its depreciation rate. For example, if the investment cost of a reactive compensator is 36000 $/MVAR, and its average working rate and life span are 3/4 and 35 years, respectively, the cost or depreciation rate of the compensator can be calculated as:
r shj =
36000 3 35 × 365 × 24 × 4
= 0 . 15655
for the isolated system operator to be aware of stability condition and distance to instability margin. In order to make decision the favorite criteria is the one which gives the exact distance to instability margin to the operator. Voltage Stability Criteria is able to estimate the exact distance to instability margin by the use of the direction of increase in power generation and consumption. It is supposed in this paper that the amount of power generation and consumption are increased proportional to the primary amount of them. In this approach, the voltage stability margin is incorporated in to the power flow equations to maintain the power system in a secure operating state where a sudden load variation or even a contingency occurs. Various OPF based approaches to include voltage stability criteria as a security constraint are discussed in [20] in detail. Referring to [21], one way to ensure of voltage stability in power system operation is to dispatch the active and reactive power in such a way that sufficient safety margin exist to the collapse point. Beyond the collapse point, the power flow equations have no feasible solution. The voltage stability margin is usually measured in per unit MW and defined as the minimum distance from current operating point to the collapse point. This concept is graphically depicted in Fig. 3.
($ / MVAR)
3.2 Constraints In order to accommodate the market solution with actual power system condition, the operational constrains of the power system should be included into the model provided for reactive power procurement. The constraints of mentioned market are as follows: A. Constraint of Power Balance
(P
0 gi
)
+ ΔP gi − P 0di =
( )
N bus
∑ V i V j Y i , j ⋅ cos(θ i , j + δ j − δ i ) j
N bus
Q gi + Q shi − tan ϕ di ⋅ P 0di = − ∑ V i V j Y i , j ⋅ sin(θ i , j + δ j − δ i ) 0
j
(4) (5)
Where V i and δ i represent the voltage magnitude and angle at node i. Y i, j and θ i, j are the magnitude and angle of the admittance connecting bus i to bus j. ϕ 0 is the di phase angle of the load at bus i. B. Voltage Stability Criteria Since, increase in power generation and consumption, conduct the system to instability margin so it is important
Fig. 3. Pictorial definition of voltage stability margins and loading factor In this figure, ξ is the loading factor of the system and 0 P total stands for the present operating point of the system and VSM measures the voltage stability margin. The VSM always refers to the theoretical stability margin because no capacity or voltage constraints of the network are involved in its calculation. Instead, practical voltage stability margin (PVSM) is widely used as practical implementation of the concept of voltage stability in power systems. PVSM is defined as the maximum load that can be added to the current operating point while no capacity or security limits are violated. In other words this figure shows that increase in 0 does not make volttotal power by the amount of ξ ⋅ P total age collapse in the system. Consequently, it can be incorporate into the power flow equations and OPF formulation as following:
(P
0 gi
+
ΔP + k gi
gi
⋅ξ ⋅
P
0 total
)−(P
0 di
+
k
di
⋅ξ ⋅
P
0 total
)=
N
∑V V Y j
bus
ξ
ξ
i
j
i, j
θ +δ −δ ) (6)
⋅ cos(
i, j
ξ
ξ
j
i
Mahdi Rajabzadeh and Masoud A. Golkar
ξ
(ϕ ) ⋅ ( P + k
N
)= −
∑V V Y
δ −δ ) (7) In Eqn. (6) and (7) parameters which are shown by superscript (ξ) are the amount gained after increase in load. In order to simulate sudden load variation or increase in power generation and consumption, different directions can be selected to determine distribution coefficients. These coefficients are proposed by Eqn. (8) to (10). 0 Pdi (8) k di = 0 Ptotal Q
gi
Q
+
shi
− tan
0
0
di
di
di
⋅ξ ⋅
P
0
total
bus
ξ
ξ
i
j
j
i, j
θ
⋅ sin(
i, j
+
ξ
ξ
j
i
allocation of reactive power in power systems under open market environment. For verifying the validity of the proposed model, it is tested on IEEE-30 bus system. The programs were run on a 3.2 GHz, Pentium-IV, with 512 MB RAM PC. • Parameters for the GA algorithm: Population Size = 32 Maximum Iterations = 200 Crossover rate=0.8 Mutation rate=0.01 Crossover parameter=0.5 • Parameters for the PSO algorithm: Population Size = 32 Learning factors: C1 = C 2 = 2.0
0
k gi =
P gi + ΔP gi 0 Ptotal
(9)
ND
0 0 Ptotal = ∑ P di
(10)
i =1
C. Active and Reactive Power generation/consumption capacity Generation and absorption capacity of reactive power and active power output of generators is limited as fallow: (11)
P gi ≤ P gi ≤ P gi + ΔP gi min
0
min
(12)
0
Pdj ≤ Pdj ≤ P dj min
max
Q gi ≤ Q gi ≤ Q gi
ξ
min
max
; Q gi ≤ Q gi ≤ Q gi
min
max
(14)
Q shi ≤ Q shi ≤ Q shi Where
P 0gi
and
0
P dj
(13)
are the quantities of active power
obtained through execution of the auction-based electricity market. The generators are allowed to offer some extra part of active power, namely ΔP gi for compensation of the transmission losses.
max
Q gi
and
min
Q gi
are the maximum ca-
pacity of reactive power generation/absorption of generators at bus i respectively.
max
V i ≤V i ≤V i
; V imin ≤V ξi ≤V imax
(15)
E. Constraint of Transformer Ratio (16) ≤T k≤T k max and T k are the minimal and maximal
T
min k
Weighting factor: ω max = 0.9,ω min = 0.4 Maximum Iterations = 200 The IEEE-30-bus power system consists of 41 branches, 6 generator-buses and 22 load-buses, of which four branches are under load-tap-setting transformer branches and four static VAR compensators [22]. It is shown in appendix. The categories, sites and limits of control variables are listed as follow: 1. Continuous AVR values of generator 1, 2, 5, 8, 11 and 13, the upper and lower limit is set to 0.9pu and 1.1pu. Each generator unit proposes its bidding curve formulated with Eqn.(2). The reactive power bidding curve parameters of generator units are proposed in Table 1. Reactive power values are expressed in p.u. And the price of the losses is 10$/Pu (MW). 2. Discrete tap of transformers in lines 6-9, 6-10, 4-12 and 27-28, the upper and lower limit is set to 0.9pu and 1.1pu, which have 20 tap positions. 3. There are four static VAR compensators installed at bus 10, 15, 18 and 24 with maximal values of output of 0.25pu. It is assumed that the first two have presented the reactive power prices as 25$/p.u (MVAR) and the last two 15$/p.u (MVAR). Table 1. Reactive power-bidding curve parameters of generators
D. Bus Voltage Limits min
341
max
Where T min k allowable range of ratio of Tap Changer respectively.
4. Results and Discussion A genetic algorithm (GA) and particle swarm optimization (PSO) method are implemented in MATLAB programming language 7.6 to solve the problem of optimum
Gen. Bus No.
λ
q1
λ
q0
a′
b′
a
b
Q
1
Q
2
1
3.6
2.8
-15
-1.2
8
-1.2
-0.08 0.15
2
3.4
2.6
-15
-1.8
9
-0.9
-0.12
5
3.6
2.8
-15
-1.2
8
-0.96 -0.08 0.12
8
3.4
2.6
-14
-1.68
9
-0.9
-0.12
0.1
11
3.8
3
-16
-1.6
7
-0.35
-0.1
0.05
13
3.8
3
-16
-1.6
7
-0.35
-0.1
0.05
0.1
Optimum Allocation of Reactive Power in Real-Time Operation under Deregulated Electricity Market
342
Table 4. Final tap positions of transformers (P.U.)
4.1 Optimal allocation of reactive power: In this case each generator unit proposes its reactive power bidding curve and it is assumed that the voltage stability criteria has not considered. Therefore the loading factor ξ and τgqi in Eqn.(1) is equal to zero. Table 2 shows final allocation of generator’s active power and compares the results of both optimization methods. Final amount of reactive power of generators and static VAR compensators is showed in Table 3. Final tap position of transformers is obvious in Table 4. Consequently, Table V compares two methods and shows total active power of generators, active power losses and its cost, total reactive power obtained from reactive sources and their costs, there is also total costs obtained from optimization methods. As it is obvious from Table 5 the PSO algorithm has achieved better consequences in compare with GA, the former has smaller power loss and more important it gained better cost amount as total cost. Therefore, the PSO method is used in following section to achieve more accurate results. Table 2. Final allocation of generator’s active power (P.U.) variables
Lower Upper Final state (GA) limit limits
Final state (PSO)
P g1
0.5
2
1.864
1.926
P g2
0.1
1
0.1
0.1
P g5
0.1
1
0.196
0.343
P g8
0.1
1
0.248
0.196
P g11
0.1
1
0.243
0.159
P
0.1
1
0.243
0.159
variables
Lower limit
Upper limit
Final state Final state (GA) (PSO)
T
6−9
0.9
1.1
1.1
1.04
T
6−10
0.9
1.1
0.96
1.05
T
4−12
0.9
1.1
1.05
0.9
27− 28
0.9
1.1
0.9
1.01
T
4.2 Reactive power market consequences with emphasis on voltage stability criteria: In this case the optimal allocation of reactive power is investigated with emphasis on voltage stability criteria. As it was declared before, in this paper, it is supposed that the amount of power generation and consumption are varied proportional to the primary amount of them. Reactive power market consequences by the assumption of τ gqi = 0.5 for the different amount of loading factor ξ from 0.0 to 0.2 are proposed. Fig. 4 shows the cost of reactive, cost of loss and total cost which are obtained from PSO method. It is observed that by increase in voltage stability criteria the reactive power cost increases. The process of reactive power variation of generators and static VAR compensators are showed in Fig. 5 and Fig. 6 respectively. These figures confirm that the proposed model tries to prepare reactive power from the cheapest resources. Reactive Power Cost
Cost of Loss
Total Cost
140
Cost ($)
120 g 13
100 80 60 40
Table 3. Final allocation of reactive power of generators and SVCs (P.U.)
20 0 0
variables
Lower limit
Upper limit
Final state (GA)
Final state (PSO)
Q g1
-0.2
1
0.15
0.208
Qg 2
-0.2
0.5
0.1
0.142
Q g5
-0.2
1
0.12
0.133
Q g8
-0.2
0.5
0.1
0.139
Q g11
-0.2
0.5
0.146
0.05
Q g13
-0.2
0.5
0.146
0.05
Q sh10
0
0.25
0.032
0.039
Q sh15
0
0.25
0.026
0.041
Q sh18
0
0.25
0.121
0.094
Qsh24
0
0.25
0.097
0.087
0.05
0.1
0.15
0.2
Loading Factor (p.u.)
Fig. 4. Variation of cost function by increase in voltage stability criteria
Reactive Power of Generators (p.u.)
Qg1
Qg2
Qg5
Qg8
Qg11
Qg13
0.45 0.4 0.35 0.3 0.25 0.2 0.15 0.1 0.05 0 0
0.05
0.1
0.15
0.2
Loading Factor (p.u.)
Fig. 5. Reactive power variation of generators by increase in voltage stability criteria
Mahdi Rajabzadeh and Masoud A. Golkar
343
Table 5. comparisons of optimal results for two methods N
Reactive Power of SVCs (p.u.)
Qsh10
N
G
Active
∑ λ gi (Q gi ) ∑ C shj (Q shj ) Power j =1 sh
GA
2.894
1.038
0.0499
18.144
4.72
Total Losses Cost Cost 69.01892.482
PSO
2.883
0.983
0.0491
18.097
4.715
67.97491.356
Method ∑ P
Qsh15
gi
( pu )
∑Q
Qsh18
g & sh
( pu )
P Loss
{pu)
i =1
($)
($)
Appendix
Qsh24
0.14
Table A.1. Bus data of IEEE-30 bus power system
0.12 0.1 0.08 0.06 0.04 0.02 0 0
0.05
0.1
0.15
0.2
Loading Factor (p.u.)
Fig. 6. Reactive power variation of SVCs by increase in voltage stability criteria
5. Conclusion In this paper an approach was presented for optimal allocation of reactive power in deregulated electricity market. The proposed model minimizes reactive support cost as an economic aspect and insures the voltage security as a technical constraint. In this approach, the voltage stability margin is incorporated in to the power flow equations to maintain the power system in a secure operating state where a sudden load variation or even a contingency occurs. Based on analysis of generators’ production cost of reactive power, a segmented bidding model of generators’ reactive power generation is exerted. The proposed method specifies the active and reactive power of generators and the reactive power of static VAR compensators and the variation of transformers tap changer as well as their cost. In this paper both active and reactive power flow is accomplished while optimization. Each reactive power supports proposes its reactive power capacity and its cost by a clear function so there are a transparent competition between reactive generators. Finally, a genetic algorithm (GA) and particle swarm optimization (PSO) method are compared to solve the problem. The performance of the proposed model is validated on IEEE-30 bus system. Results demonstrate that the algorithm is well competent in achieving the near optimal allocation of reactive power under practical constraints and price based conditions.
Acknowledgements This work was supported by the K. N. Toosi University of technology, Tehran, Iran.
Bus No
Pd
Qd
Bs
Gs
BaseKV
1
0
0
0
0
132
2
21.7
12.7
0
0
132
3
2.4
1.2
0
0
132
4
7.6
1.6
0
0
132
5
94.2
19
0
0
132
6
0
0
0
0
132
7
22.8
10.9
0
0
132
8
30
30
0
0
132
9
0
0
0
0
1
10
5.8
2
19
0
33
11
0
0
0
0
11
12
11.2
7.5
0
0
33
13
0
0
0
0
11
14
6.2
1.6
0
0
33
15
8.2
2.5
0
0
33
16
3.5
1.8
0
0
33
17
9
5.8
0
0
33
18
3.2
0.9
0
0
33
19
9.5
3.4
0
0
33
20
2.2
0.7
0
0
33
21
17.5
11.2
0
0
33
22
0
0
0
0
33
23
3.2
1.6
0
0
33
24
8.7
6.7
4.3
0
33
25
0
0
0
0
33
26
3.5
2.3
0
0
33
27
0
0
0
0
33
28
0
0
0
0
132
29
2.4
0.9
0
0
33
30
10.6
1.9
0
0
33
Optimum Allocation of Reactive Power in Real-Time Operation under Deregulated Electricity Market
344
Table A.2. Branch data of IEEE-30 bus power system From Bus
To Bus
b (p.u.)
x (p.u.)
r (p.u.)
1
2
0.0528
0.0575
0.0192
1
3
0.0408
0.1652
0.0452
2
4
0.0368
0.1737
0.057
3
4
0.0084
0.0379
0.0132
2
5
0.0418
0.1983
0.0472
2
6
0.0374
0.1763
0.0581
4
6
0.009
0.0414
0.0119
5
7
0.0204
0.116
0.046
6
7
0.017
0.082
0.0267
6
8
0.009
0.042
0.012
6
9
0
0.208
0
6
10
0
0.556
0
9
11
0
0.208
0
9
10
0
0.11
0
4
12
0
0.256
0
12
13
0
0.14
0
12
14
0
0.2559
0.1231
12
15
0
0.1304
0.0662
12
16
0
0.1987
0.0945
14
15
0
0.1997
0.221
16
17
0
0.1923
0.0524
15
18
0
0.2185
0.1073
18
19
0
0.1292
0.0639
19
20
0
0.068
0.034
10
20
0
0.209
0.0936
10
17
0
0.0845
0.0324
10
21
0
0.0749
0.0348
10
22
0
0.1499
0.0727
21
22
0
0.0236
0.0116
15
23
0
0.202
0.1
22
24
0
0.179
0.115
23
24
0
0.27
0.132
24
25
0
0.3292
0.1885
25
26
0
0.38
0.2544
25
27
0
0.2087
0.1093
28
27
0
0.396
0
27
29
0
0.4153
0.2198
27
30
0
0.6027
0.3202
29
30
0
0.4533
0.2399
8
28
0.0428
0.2
0.0636
Fig. A.1. IEEE 30-bus power system.
References [1]
Nidul Sinha, Loi Lei Lai and Palash Kumar Ghosh, “GA Based Algorithm for Optimum Allocation of Reactive Power under Deregulated Environment,” IEEE DRPT2008 Conference, April 2008 Nanjing China. [2] S.K. Parida, S.N. Singh and S.C. Srivastava, “Voltage Security Constrained Localized Reactive Power Market,” 0-7803-9525-5/06/$20.00 ©2006 IEEE. [3] El-Samahy, K. Bhattacharya, and C. A. Cañizares, “A Unified Framework for Reactive Power Management in Deregulated Electricity Markets,” IEEE, PSCE 2006, pp. 901-907. [4] Alex D. Papalexopoulos, George A. Angelidis, “Reactive Power Management and Pricing in the California Market,” IEEE MELECON, Benalmádena (Malaga), Spain, May 2006, pp. 902-905. [5] Lamont JW, Fu J. , “Cost analysis of reactive power support,” IEEE Trans Power Syst. 1999;14(3):890– 896. [6] X.J. Lin, C.W. Yu and C.Y. Chung, “Pricing of reactive Power Support Ancillary Services,” IEE proc.Gener. Transm. Distrib., vol. 152, no. 5, September2005, pp. 616-622. [7] Baughman ML, Siddiqi SN., “Real time pricing of reactive power: theory and case study results,” IEEE Trans Power Syst 1991; 6(1):23–9. [8] Li YZ, David AK., “Wheeling rates of reactive power flow under marginal cost pricing,” IEEE Trans. Power Syst. 1994; 9(3):1263–9 [9] Bhattacharya K, Zhong J., “Reactive power as an ancillary service,” IEEE Trans Power Syst 2001; 16(2):294–300. [10] Zhong J, Bhattacharya K., “Toward a competitive market for reactive power,” IEEE Trans Power Syst 2002;17(4):1206–15.
Mahdi Rajabzadeh and Masoud A. Golkar
[11] Hao S., “A reactive power management proposal for transmission operators,” IEEE Trans Power Syst 2003; 18(4):1374–80. [12] Silva EL, Hedgecock JJ, Mello JCO, Luz JCF., “Practical cost-based approach for the voltage ancillary service,” IEEE Trans Power Syst 2001; 16(4): 806-12. [13] X.J. Lin, C.W. Yu, A.K. David, C.Y. Chung, H. Wu, N. Xu, “A novel market-based reactive power management scheme,” ELSEVIER Electrical Power and Energy Systems 28 (2006) 127-132. [14] R.S. Salgado, and M.R. Irving, “Framework for Analysis of reactive Power Dispatch in Energy Pools,” IEE Proc.-Gener. Transm. Distrib., vol. 151, no. 2, March 2004, pp. 1047-1052. [15] Wen-Chen Chu, Bin-Kwie Chen and chung Liao, “Allocation the Cost of Reactive Power purchased in an Ancillary Service Markets by Modified Y-Bus Matrix Method,” IEEE Transaction on Power Systems, vol. 19, no. 1, February 2004, pp. 174-179. [16] Julian Barquin Gil, and et al, “Reactive Power Pricing: a Conceptual Framework Remuneration and charging Procedure,” IEEE Transaction on Power Systems, vol. 15, no. 2, May 2000, pp. 483-489. [17] X.J. Lin and A.K, David and C.W. Yu, “Reactive Power optimization with Voltage stability consideration in Power Market Systems,” IEE proc.-Gener. Transm. Distrib., vol. 150, no. 3, July 2003, pp. 305310. [18] M.J. Rider and V.L. Paucar, “Application of Nonlinear Reactive Power Pricing Model for Competitive Electric Markets,” IEE proc.-Gener. Transm. Distrib. vol. 151, no. 3, May 2004, pp. 407-414. [19] Li Gengyin, Zhou Ming, Yang Juan, and Sun Liying, “Research on Procurement Strategy of Reactive Power as Auxiliary Service in Power Markets,” IEEE International Conference on Electric Utility Deregulation, Restructuring and Power Technologies (DRPT2004), pp. 349-354, April 2004. [20] W. Rosehart, C. Cafiizares, and V. H. Quintana, “Optimal Power Flow Incorporating Voltage Collapse Constraints,” Proc. of the 1999 IEEE/PES Summer Meeting, Edmonton, Alberta, July 1999, pp. 820-825. [21] B. Mozafari, T.amraee, A. M. Ranjbar, M. Mirjafari, and A. R. Shirani, “Optimal Reactive Power Dispatch in a Joint Active / Reactive Market Model,” IEEE, International Conference on Power System Technology, 2006. [22] Q. H. Wu, Y. J. Cao, and J. Y. Wen, “Optimal reactive power dispatch using an adaptive genetic algorithm,” Int. J. Elect. Power Energy Syst., vol. 20, pp. 563-569, Aug. 1998.
345
Mahdi Rajabzadeh He was born in Masal in Iran, in 1983. He received his BSc degree from Guilan University, Iran in 2005 and is a MSc student in K. N. Toosi University of Technology, Tehran, Iran. He has worked on power system restoration and system security as his important researches. And now he is studying on reactive power pricing and management in deregulated environment. mahdi_rajabzadeh@ee. kntu.ac.ir
Masoud AliAkbar Golkar He was born in Tehran Iran in 1954. He received his BSc degree from Sharif University of Technology Tehran-Iran in 1977, MSc from The Oklahoma State University USA in 1979 and his PhD degree from the Imperial College of Science, Technology, and Medicine (The University of London, UK) in 1986, all in Electrical Engineering (Power Systems). His employment experience included working as an Associate Professor at The K N Toosi University, Tehran, Advisor to Tehran Electricity Board, Head of research group at Electric Power Research Center in Tehran .Now he is an Associate Professor at K N Toosi University of Technology in Tehran, Iran. Golkar@eetd. kntu.ac.ir