Power Flow Redistribution in Croatian Power System Network using ...

20 downloads 0 Views 572KB Size Report
Electricity market deregulation has given a significant role to PST's. PST .... 3. Phase angle regulation in Croatian power system. Because of the role of electricity ...
Power Flow Redistribution in Croatian Power System Network using PhaseShifting Transformer

Ivica Pavić Faculty of Electrical Engineering and Computing Zagreb, CROATIA Sejid Tešnjak Faculty of Electrical Engineering and Computing Zagreb, CROATIA Tomislav Špoljarić Technical Polytechnic in Zagreb, CROATIA

1. Introduction Transformer, observed as an element of the power system, is usually used to transport electric power between two different voltage levels. One of these voltage leves can be regulated by magnitude, and this method of regulation is called voltage magnitude regulation. Besides the voltage magnitude, the voltage phase angle can be regulated. This method of regulation is called phase angle regulation, and is used when there is a need for regulating not only the voltage magnitude, but also the phase angle between two different voltage levels. Transformers, who have the ability to control the phase angle between primary and secondary side are called phase-shifting transformers (PST). By using voltage magitude regulation, the reactive power flows can be controled. However, phase angle regulation can be used if the active power flows are to be controlled. Electricity market deregulation has given a significant role to PST's. PST, as an element of a power system, can be used to control power flows, therefore the power system containing such elements can provide its maximum efficiency. The use of PST's in the power system can also solve major problems that come together with deregulation of electric market, like power transit or uneven loading. The transmission network is used to transport power from producer to consumer, who have a concealed contract in which is stated that producer produces a certain amount of electrical energy and consumer buys this energy. Hence, the contractual path of the electricity is straight from producer to consumer. However, the physical path is a group of parallel paths, some of which lead through regions (countries) that are not involved in the contract. In a situation like this, uncontrolled power flows can occur in the transmission system of a region involved in the contract and overload its lines, when regions or paths not involved, are to be avoided. As for the uneven loading, it is necessary to state that the distribution of the power flow between two parallel lines is dictated by their impedances. The line with the smallest reactance carries the largest part of the load. In most situations, one of the two lines will be operating well below its nominal rating because otherwise the parallel line would be overloaded. Solution to problems like these is using the active power control. This is where the PST's have a significant role, because a phase angle regulation can be used to redirect active power flows and manage the loading of transmission paths, thus the losses in transmission network are minimal and the efficiency of such network is enhanced.

2. Voltage phase angle regulation 2.1. Principles od phase angle regulation Active power flow along a transmission line or transformer is determined mainly by the angle difference of the terminal voltages. It is also inversely proportional to the transmission line or transformer reactance which is placed between these two sides. Controling of active power flows can be made mainly by changing voltage phase angles and line reactances. Altering the voltage magnitudes affects significantly the reactive power flows and therefore it is not effective for active power flow control. Reactance can be altered by placing a series capacitor along the line to compensate the inductance of the line. Besides increased power flow, switching the capacitors at an appropriate time can be used to dampen oscillations. Flexible alternating current transmission systems (FACTS devices) can be used to alter the total line reactance very dinamically. The most common used method for effective active power flow control is a change of voltage phase angles. Because of their proportionality, the active power flow through the transmission line can be increased by adding the angle shift to the existing phase angle. This angle shift is controllable within certain limits. According to the angle between phase and adding voltage there are two types of phase angle regulation:  phase angle and voltage magnitude regulation – an angle between phase and adding voltage varies between 0 and 90 degrees  phase angle regulation only – an angle between voltages is 90 degrees Principles of both types of phase angle regulation, along with voltage magnitude regulation are shown in fig. 2.1.

Figure 2.1. Basic principles of regulation: a) voltage magnitude regulation; b) phase angle and voltage magnitude regulation; c) phase angle regulation only When a phase angle and voltage magnitude regulation is used, not only does a phase angle of a secondary voltage alter in comparison to the primary side, but there is an altering in magnitude of secondary voltage compared to the primary voltage also. This type of regulation can be obtained by connecting the end of one regulation winding in a series with previous phase, i.e. phase C voltage is added to the phase A voltage, as shown in fig. 2.1. Second type of phase angle regulation (phase angle regulation only) is a method of regulating the phase angle shift of a secondary voltage, where magnitudes of both voltages are equal.

2.2. Mathematical modelling of PST A per-unit model of ideal transformer with tap changing is used to describe the phase angle regulation [1]. This model is shown in fig. 2.2.

Figure 2.2. Basic equivalent circuit of a PST for coupling between primary and secondary coils with both primary and secondary off-nominal turns ratio of

and , in p.u.

To describe the phase shift, the model of a transformer has to be provided with a complex turns ratio. Besides, the invariance of the product

representing the apparent power across

the ideal transformer requires the distinction to be made between the turns ratio for current and voltage:

The circuit shown in fig. 2.2 has a turns ratio of . Solving equations for terminal currents of the modified circuit one can get next relations:

Therefore, the matrix of a general single phase admittance of a phase-shifting transformer model described above is:

The network described in fig. 2.1 is not bilinear, as can be seen in an asymmetrical diagonal form in an admittance matrix described above. Hence, the equivalent circuit of a single phase shifting transformer is of limited value and the best way to describe this transformer is analytically by its admittance matrix.

2.3. General classification of phase-shifting transformers Phase-shifting transformers can be classified by these characteristics: -

direct PST's are based on one 3-phase core. The phase shift is obtained by connecting the windings in an appropriate manner.

-

indirect PST's are based on a construction with two separate cores. One variable tap exciter (often called the booster) is used to regulate the magnitude of a quadrature voltage. Then the one series transformer is used to inject the quadrature voltage in an appropriate phase.

-

asymmetrical PST's create an output voltage with altered phase and magnitude in comparison with an input voltage.

-

symmetrical PST's create an output voltage with altered phase compared to the input voltage. The magnitude of an output voltage remains unaltered.

The combination of the first two types with the two last types described above results in 4 main categories of PST's: direct asymmetrical, direct symmetrical, indirect asymmetrical and indirect symmetrical PST's [2,3].

3. Phase angle regulation in Croatian power system Because of the role of electricity trade and transit between Southeast and Western Europe, a need for a phase angle regulation in Croatian power system appeared. A results of preliminary analysis have shown that the small change in phase angle has a significant impact on power flow between 400, 220 and 110 kV levels and, depending on a shift, energy exchange is expected in both directions. A PST was installed in TS Žerjavinec, where the operation of a phase angle regulation was expected to be most effective in satisfying the needs for controlling the trade and transit. Main task for this PST is controlling and redirecting power flows on 400, 220 and 110 kV voltage levels. Selection of a PST in TS Žerjavinec included observing the needs and thus searching for a most economical solution, not requiring significant increase in investment and spatial projects changing. 400 MVA autotransformer, with the ratio of transformation 400/231 kV and the possibility to alter both magnitude and phase angle, was selected. Voltage magnitude or phase angle regulation can be selected in the unloaded condition only. For the turns ratio lesser than two, it is better to choose the autotransformer [4]. It is easier, cheaper and has less losses. From the perspective of efficiency and investment, it has more advantages than two-winding transformer. The type of phase angle regulation was on-load tap changing with three-phase tap changer, where regulating winding has 25 possible tap positions with the regulation step of 16 bends, having overall 192 bends and is made in neutral point. Made in this way, a PST has a wanted impact on both HV and LV levels of the trasformer. However, this type of phase angle regulation is nonlinear, and regulation range is asymmetric, varying from -4.48° (negative phase angle shift) to +6.76° (positive phase angle shift) in the loaded condition. Voltage magnitude regulation selected for this transformer is also on-load tap changing, because of its flexibility and efficiency. For the possibility of adjusting both levels, a regulation in neutral point is selected. Autotransformer scheme is shown in fig. 3.1, and regulating winding is shown in fig. 3.2. By changing the position of three-phase switch shown in fig. 3.1 in the unloaded condition phase angle regulation can be selected instead of a voltage magnitude regulation.

B

A UA mA

C

UB

UC mB

mC three-phase switch which selects a voltage magnitude or phase angle regulation in the unloaded condition

magnitude regulation

regulating winding

phase angle regulation

x

y

z

a

b

c

x

Figure 3.1. Autotrasformer scheme with voltage magnitude and phase angle regulation

Figure 3.2. Regulating winding scheme for PST in TS Žerjavinec When operating with a regulating winding, one can affect the turns ratio of both sides of the transformer, the HV and the LV side. The advantage of such operation is a possibility to alter voltages according to needs, whether it is positive or negative energy exchange (upper or lower switch position regarding the turns ratio). The type of regulating winding is reversible.

3.1. Voltage magnitude regulation in TS Žerjavinec Described autotransformer has the ability to alter voltage magnitude if a proper position of a three-phase switch is selected, as shown in fig. 3.1. When the tap changer switch is in upper position (the "u" designation on the fig. 3.2), number of windings is increased, the turns ratio is lowered, and the decreasing of the HV side voltage, or increasing of the LV side voltage is provided, depending on the type of transformation. Tap changer positions are from 13 to 25,

respectively, as shown in fig. 3.2. If the tap changer switch is in lower position, number of windings is decreased, the turns ratio is increased, thus the increasing of the HV side voltage, or decreasing of the LV side voltage is provided. Tap changer positions are from 1 to 13, respectively, as shown in fig. 3.2. According to this, positions 1 and 25 are ending positions, and position 13 is a neutral point position. When a descending transformation type is used, and a tap changer switch is in position 25 (designation "u"), the voltage magnitude is 91% of the HV side nominal voltage. If a tap changer switch is in position 1 (designation "d"), and a regulating winding is in a reversed state, with descending type of transformation, HV voltage magnitude is 115,5% of the nominal HV voltage magnitude. In ascending transformation type autotransformer is adjusting the voltage on a LV side. Tap changer position 25 therefore fits the LV voltage magnitude level on 109,9% of the nominal LV voltage magnitude, and a position 1 fits the level of 86,6% of the nominal LV voltage magnitude.

Figure 3.3. Autotransformer scheme (phase A only) and phasor diagram, when a regulating winding is set to alter voltage magnitude, with the tap changer switch set on upper position

A

EA

EA

UA EmA

UmA

EmA

UA -ErA UmA

three-phase switch 1

tap changer switch

d

ErA 13

C

B

Figure 3.4. Autotransformer scheme (phase A only) and phasor diagram, when a regulating winding is set to alter voltage magnitude, with the tap changer switch set on lower position Designations on the schemes and diagrams are:  E A – electromotive force inducting in the non-regulating HV winding of phase A  E mA – electromotive force inducting in the non-regulating LV winding of phase A  E rA – electromotive force inducting in the regulating winding of phase A  E rC – electromotive force inducting in the regulating winding of phase C  U A – voltage potential of the phase A terminal towards the earthing point (HV terminal)  U mA – voltage potential of the phase A terminal towards the earthing point (LV terminal)

3.2. Phase angle regulation in TS Žerjavinec By changing the position of three-phase switch shown in fig. 3.1, phase angle regulation can be selected instead of a voltage magnitude regulation. If a phase A is observed, regulating winding voltage of phase C is added to the phase A voltage. Resulting voltage is such that the voltage on the LV side of the transformer is moved to an angle φ, which is not angle due to load, but an angle shift due to phase angle regulation. If a tap changer switch is set on lower position (tap changer position of regulating winding is between 1 and 13) the angle will be negative. Autotransformer scheme for one phase and a phasor diagram are shown in fig. 3.6, when operating in negative phase angle shift mode.

Figure 3.5. Autotransformer scheme (phase A only) and phasor diagram, when a regulating winding is set to alter negative phase angle shift Setting the same switch on upper position (tap changer position is between 13 and 25) results in the positive phase angle. Autotransformer scheme for one phase and a phasor diagram are shown in fig. 3.6, respectively.

Figure 3.6. Autotransformer scheme (phase A only) and phasor diagram, when a regulating winding is set to alter positive phase angle shift The advantages of a described PST are lower price compared to the PST with booster and regulating winding used for both types of regulation, which can provide descending and ascending transformation type depending on the regulating side of the autotransformer, HV side or LV side. The disadvantages include impossibility to alter the turns ratio when using the phase angle regulation and nonlinearity of neutral point position. When altering the positive phase shift to maximum (tap changer on position 25), the turns ratio matches the HV voltage of 416 kV (104% of U 1n ), if a descending transformation is observed. If, for some reasons the HV side voltage is much lower, phase angle regulation can be temporarily switched to voltage magnitude regulation. Nonlinearity of the neutral point position is manifested on the range of voltage magnitude regulation: from 15,5% to -9% with descending transformation type and from -13,4% to +9,9% with ascending transformation type.

4. Simulation results 4.1. Features of Croatian Transmission Network Geographical location and shape of Croatia influence the main features of the Croatian transmission network (fig. 4.1). One of the most important power corridors Heviz-ŽerjavinecMelina-Divača-Redipuglia connects Central and Eastern European power system with Italy, a

major importer of electric energy in the region. Other corridor Mladost-ErnestinovoŽerjavinec represents the East-West connection between Eastern Europe (Bulgaria, Romania) and Western Europe (Slovenia, Italy). These two corridors are of great importance to the Southeast part of UCTE grid. Installed capacity of hydro and thermal power plants in Croatian power system is approximately the same, but their geographical distribution is not uniformed. Majority of hydro power plants are located in Southern part of the network, while thermal power plants are located in Central and Western part. This distribution of power plants has a major impact on the power flows in Croatian power system, but also in adjacent power systems. In the years of wet hydrology, majority of production is located in Southern part of Croatian power system, thus there is a large power flow through the 400 kV line Konjsko-Velebit-Melina. Another main characteristic of Croatian transmission system is a continuous power transit through interconnection lines Heviz-Žerjavinec and Mladost-Ernestinovo in direction EastWest. Based on previous considerations it can easily be concluded that Transformer Station (TS) Žerjavinec with transformation levels 400/220 kV and 400/110 kV has a very important role in Croatian power system [5,6].

Figure 4.1. 400 kV and 220 kV transmission network of Croatian and adjacent power systems 4.2. Numerical examples Effect of phase-shifting transformer 400/220 kV installed in TS Žerjavinec was analyzed for a real situation in Croatian power system as it was this winter. The total consumption of Croatian power system was in that case 2850 MW, which is very close to the maximum load of about 3100 MW. The own production was 2150 MW and the rest (about 760 MW) has been imported from Eastern Europe through Hungary, Serbia and Bosnia and Herzegovina. The difference between total consumption and production with imports was the power losses in Croatian network (about 60 MW). In the observed case, the transit from Southeast Europe to Italy, which closes over the Croatian transmission network was about 600 MW. For the analysis of power flows and the impact of voltage angle regulation in TS Žerjavinec, the entire Croatian power system and 400 kV and 220 kV parts of adjacent power systems were modeled. The active power flows of the network in the immediate vicinity of TS Žerjavinec are shown in fig. 4.2. In this case, phase-shifting transformer was used for voltage magnitude regulation and its tap changer was in the middle position (13), which means the nominal turns ratio. This initial case, which is the basis for all further analysis is marked as Case 0. In order to determine the impact of voltage angle control, the transformer is transferred in voltage phase angle regulation mode and its tap changer is set at the upper end position (25) which corresponds to a positive angle of the 6.76° in unloaded condition. This variant is marked as Case 1 and the results of load flow calculation are shown in fig. 4.3. In the Case 2 the transformer tap changer is set at the lower end position (1) which corresponds to a negative angle of the 4.48° in unloaded condition and results are shown in fig. 4.4. From the given results it can be concluded that changing of transformer’s turns ratio redistributes active power flows between 400 kV network and 220 kV and 110 kV network. In the Case 1, when tap changer is set at the upper end position, active power flow through phase-shifting transformer is increased for about 140 MW in direction from 400 kV bus to 220 kV bus, compared to the Case 0. Unlike the previous case, in the Case 2, when tap changer is set at the lower end position active power flow through phase-shifting transformer from 400 kV bus to 220 kV bus is decreased for about 100 MW compared to the Case 0. Based on the obtained results, it can be concluded that the voltage angle change of 1° in the unloaded condition causes a change of active power flow through the phase-shifting transformer to approximately 20 MW.

If the active power losses are compared for all three analyzed cases, it can be seen that changing of transformer’s turns ratio does not affect significantly the amount of losses. In the Case 0, without the voltage phase angle shift, the total active power losses in Croatian transmission network are 62.8 MW and in the other two cases (Case 1, Case2) total active power losses are 63.6 MW and 64.2 MW, respectively. Since the changing of phase-shifting transformer’s turns ratio also affects the reactive power flows in the surrounding network, active power losses are increased. To reduce these losses, turns ratio of the other transformers should be coordinated with phase-shifting transformer’s turns ratio. It is the task of voltage magnitude and reactive power optimization but it is not a subject of this papers.

Figure 4.2. Active power flow for Case 0, TAP position 13 (angle 0°) Heviz 400 kV

Hungary

Ernestinovo 400 kV

Serbia

182

Cirkovce

260

220 kV

266 Slovenia

257

214

400 MVA

Bosnia and Herzegovina

98

Žerjavinec

159

700 MW 2x300 MVA

400 kV

NE Krško

220 kV

110 kV

400 kV

238 3x300 MVA

350

57

95 220

110 kV Network (Zagreb)

3x150 MVA

Mraclin

Tumbri 400 kV

Eastern Croatia

220 kV

342

West Croatia

32

25 Bosnia and Herzegovina

Southern Croatia

Figure 4.3. Active power flow for Case 1, TAP position 25 (angle +6.76°)

Figure 4.4. Active power flow for Case 2, TAP position 1 (angle -4.48°)

5. Conclusion Phase-shifting transformers can be effectively used in electric energy transport, when used for redirection of active power flows. PST in TS Žerjavinec has proven useful in controling the active power flows in corridors placed in Southeast part of UCTE grid, thus guarding transmission assets from unscheduled use and unwanted overload. Employing the economical aspect, technical advantages and disadvantages, the autotransformer selected to operate in given conditions has proven to be the efficient solution in Croatian power system. Its possibilites to alter voltage magnitude and phase angle shift have met the needed requirements, and the advantages exceed the disadvantages of this installed autotransformer. References [1] J. Arrilaga, C. P. Arnold, "Computer Analysis of Power Systems", John Wiley & Sons Ltd, England, September 1994. [2] J.Verboomen, D. Van Hertem, P. H. Schavemaker, W. L. Kling, R. Belmans, "Phase Shifting Transformers: Principles and Applications", IEEE, June 2005. [3] J.H. Harlow et al., "Electric power transformer engineering", CRC Press LLC, USA, 2004.

[4] T. Kelemen, B. Ćućić, "Three-phase autotransformer 400 MVA, 400/231/(10,5) kV with voltage regulation in neutral point for TS Žerjavinec", Končar - Electrical Engineering Institute, Zagreb, February 2003. [5] S. Tešnjak, I. Pavić, "Load flow calculation with phase-shifting transformer 400/220 kV in TS Žerjavinec", FER, Zagreb, March 2003. [6] G. Jerbić, "Application of Phase-shifting Transformers in Croatian Power Supply System ", Energija – Journal of Energy, vol. 56 (2007), no. 02/07, HEP d.d. – Energija, Zagreb, May 2007., pp 216-231