Residential Plans Examiner Review Form - Air Conditioning ...

6 downloads 158 Views 181KB Size Report
HVAC DUCT DISTRIBUTION SYSTEM DESIGN(IRC M1601.1). HVAC LOAD CALCULATION (IRC M1401.3). Building Plan #. Contractor. Home Address ( Street ...
Residential Plans Examiner Review Form for HVAC System Design (Loads, Equipment, Ducts)

Form RPER 1.01 8 Mar 10

County, Town, Municipality, Jurisdiction Header Information REQUIRED ATTACHMENTS1

Contractor Mechanical License # Building Plan #

ATTACHED

Manual J1 Form (and supporting worksheets):

Yes

No

or MJ1AE Form2 (and supporting worksheets): OEM performance data (heating, cooling, blower): Manual D Friction Rate Worksheet: Duct distribution system sketch:

Yes Yes Yes Yes

No No No No

Home Address (Street or Lot#, Block, Subdivision)

HVAC LOAD CALCULATION (IRC M1401.3) Design Conditions

Building Construction Information Building

Winter Design Conditions

°F

Outdoor temperature

Orientation (Front door faces) North, East, West, South, Northeast, Northwest, Southeast, Southwest

°F Btu

Indoor temperature Total heat loss

Sq Ft

Conditioned floor area

Summer Design Conditions

°F °F

Outdoor temperature Indoor temperature

∆ Gr @

Grains difference

Number of bedrooms

Windows

% Rh Btu Btu Btu

Sensible heat gain Latent heat gain Total heat gain

HVAC EQUIPMENT SELECTION

Number of occupants

Ft

Eave overhang depth Internal shade Blinds, drapes, etc

Number of skylights

(IRC M1401.3)

Heating Equipment Data

Cooling Equipment Data

Equipment type

Blower Data

Equipment type

Furnace, Heat pump, Boiler, etc.

Air Conditioner, Heat pump, etc

Model

Model

Btu

Heating output capacity

Heat pumps - capacity at winter design outdoor conditions

Auxiliary heat output capacity

Btu

Heating CFM

CFM

Cooling CFM

CFM

Btu Btu Btu

Sensible cooling capacity Latent cooling capacity Total cooling capacity

HVAC DUCT DISTRIBUTION SYSTEM DESIGN (IRC M1601.1) CFM

Longest supply duct:

Ft

External Static Pressure (ESP)

IWC

Longest return duct:

Ft

Component Pressure Losses (CPL)

IWC

Total Effective Length (TEL)

Ft

Available Static Pressure (ASP)

IWC

Design airflow

Friction Rate:

IWC

Duct Materials Used (circle) Trunk Duct: Duct board, Flex, Sheet metal, Lined sheet metal, Other (specify) Branch Duct: Duct board, Flex, Sheet metal, Lined sheet metal, Other (specify)

Friction Rate = (ASP × 100) ÷ TEL

ASP = ESP - CPL

I declare the load calculation, equipment selection, and duct system design were rigorously performed based on the building plan listed above, I understand the claims made on these forms will be subject to review and verification. Contractor's Printed Name

Date

Contractor's Signature

Reserved for use by County, Town, Municipality, or Authority having jurisdiction. 1 2

The AHJ shall have the discretion to accept Required Attachments printed from approved ACCA software vendors, see list on page 2 of instructions. If abridged version of Manual J is used for load calculation, then verify residence meets requirements, see Abridged Edition Checklist on page 13 of instructions.