560BCU02. Application. The bus connection unit 560BCU02 is designed to.
ABB AG
RTU560 Remote Terminal Unit Data Sheet Bus Connection Unit 560BCU02
Application
Characteristics
The bus connection unit 560BCU02 is designed to make the RTU560 System Bus Signals accessible to the outside on the communication sub-rack 23TP22 or the 560MPR01 if a 560CMU05 subrack is used.
The bus connection 560BCU02 may be used in the 23TP22/560MPR01. The board is mounted to the plug-in terminal strips of the existing slots. This gives the chance to use two RTU560 boards at these slots.
ALARM (ALR) and WARNING (WRN) are signalled to the outside with relay contacts.
The power comes from the RTU560 boards and a 24V cable.
An external minute impulse may be connected via an optocoupler. The filtered internal minute impulse is outputted as 24V impulse.
The signals ALARM and WARNING are distributed with relay contacts. On signalling ALARM the signal WARNING is activated also.
The 560BCU02 can be used in either the 23TP22 or the 560MPR01. With this board two RTU560 communication boards are usable within the 23TP22 or 560MPR01.
ALARM and WARNING are supervised from a watchdog. They are activated if the communication modules do not respond within 30 seconds. At the isolated minute impulse input TSI, an external minute impulse can be connected to the RTU560 boards. This minute impulse is evaluated from the time master function. The internal filtered minute impulse is available at the minute impulse output TSO.
Abb. 1: Bloch diagram 560BCU02
Doc-No.: 1KGT 150 404 V001 1
1
ABB AG Bus Connection Unit 560BCU02
RTU560
Technical Data In addition to the general technical data of the RTU560, the following applies:
Minute impulse input
Power supply
TSI:
Supply:
plug-in terminal strip 2-pole isolated, 24 V input
5V/app. 80mA 24V/app. 60mA
Minute impulse output
Mechanics
TSO:
PCB:
100 x 55 mm
Weight:
app. 0,2kg
plug-in terminal strip 2-pole 24V output.
Signal outputs Alarm-/Warning: plug-in terminal strip Output:
2-pole each
Relay contact:
active closed Warning set also with Alarm ≤1A / ≤60VDC / ≤30W
Connection Type Connectors:
2 plug-in terminal strips 18 pole each
Additionals Extension of the 24V feeder about 80cm to the 24V connection on the 560MPR01
Watchdog
Environmental Conditions
Supervision time: 30 sec.
Temperature: Relative humidity:
0 ... 70 C 5 ... 95 % (non condensing)
Ordering Information 560BCU02R0001 1KGT 007 900 R0001