Service Manual - Appliance Factory Parts

68 downloads 4017 Views 3MB Size Report
Wall Mounted. Mini-Split System. Air Conditioning/Heat Pump. Service Manual. B /A-HMC09AS. B/A-HMC12AS, B/A-HMH12AS. B/A-HMC18AS, B/A-HMH18AS.
®

Wall Mounted Mini-Split System Air Conditioning/Heat Pump Service Manual B/A-HMC09AS B/A-HMC12AS, B/A-HMH12AS B/A-HMC18AS, B/A-HMH18AS B/A-HMC24AS, B/A-HMH24AS

Before servicing the unit, read the “safety precautions” in this manual. Only for authorized service personnel.

Contents Functions...................................................................................................................................... 3 Product Specifications ................................................................................................................ 5 Dimensions................................................................................................................................... 7 Refrigeration Cycle Diagram..................................................................................................... 10 Wiring Diagram .......................................................................................................................... 12 Operation Details ....................................................................................................................... 15 Display Function ........................................................................................................................ 22 Self-diagnosis Function ............................................................................................................ 22 Installation .................................................................................................................................. 23 Operation .................................................................................................................................... 38 Disassembly of the Parts(Indoor Unit)..................................................................................... 40 Cycle Troubleshooting Guide ................................................................................................... 46 Electronic Control Device ......................................................................................................... 56 Schematic Diagram.................................................................................................................... 59 Exploded View and Replacement Parts List............................................................................ 60

-2-

Functions Indoor Unit Operation ON/OFF by Remote controller Sensing the Room Temperature • Room temperature sensor (THERMISTOR) Room temperature control • Maintains the room temperature in accordance with the Setting Temp. Starting Current Control • Indoor fan is delayed for 5 seconds at the starting. Time Delay Safety Control • Restarting is inhibited for approx. 3 minutes. Indoor Fan Speed Control • High, Med, Low and Auto Operation indication Lamps (LED) --- Lights up in operation --- Lights up in Sleep Mode --- Lights up in Timer Mode --- Lights up in Defrost Mode or Hot Start Mode (only Heating Model) OUT --- Lights up during compressor running (only Cooling Model) DOOR

Healthy Dehumidification Mode • Intermittent operation of fan at low speed Sleep Mode Auto Control • The fan is switched to low(Cooling), med(Heating) speed. • The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours. Auto Air Control by the unit electronic control • The fan is switched to intermittent or irregular operation. • The fan speed is automatically switched from high to low speed. Chaos Swing • The louver can be set at the desired position or swing up and down automatically.

Defrost control(Heating) • Both the indoor and outdoor fan stops during defrosting. • Hot start will be operated after defrosting ends. Hot-start Control (Heating) • The indoor fan stops until the indoor pipe temperature will be reached at 28°C(82°F).

-3-

Remote Controller Operation ON/OFF

Operation Mode Selection Cooling Operation Mode.( (Cooling (Heating model only) model only)

)

Healthy Dehumidification Operation Mode.(

Auto Operation Mode.( ) Heating Operation Mode.(

) )

Fan Speed Selection (Low)

(Med)

(High)

(CHAOS)

Room, Temperature Display : (High: 39°C(98°F)

LOW : 12°C(54°F)

Temperature Setting TEMPERATURE

LOW

Down to 18°C(64°F) Heating Up to 30°C(86°F)

HIGH

Cooling

JET COOL

Selecting °C / °F °C / °F

Setting the Time or Timer

Timer Selection ON

OFF

Timer Setting SET

: OFF, ON, OFF

ON

Timer Cancel CANCEL

: Cancel Sleep Mode, Timer ON or Timer OFF

Sleep Operation : 1, 2, 3, 4, 5, 6, 7, Off Timer Chaos Swing

Fan Operation Mode : Fan Operates without cooling or heating. Horizontal Airflow Direction Control Button(Option)

Reset

-4-

Down to 16°C(60°F) Up to 30°C(86°F)

Product Specifications(Cooling Only) Items Unit Power Supply ø, V, Hz Cooling Capacity BTU/h Input W Running Current A COMP. Locked Rotor AMP. A E.E.R BTU/hW Air Circulation m3/min(cfm) Moisture Removal l/h(pts/hr) Noise Level Indoor, High dB(A) (Sound Med dB(A) Pressure, 1m) Low dB(A) Outdoor, Max dB(A) Features Temperature Control Air Deflection Steps, Fan/Cool Airflow Direction Control(up&down) Airflow Direction Control(left&right) Remocon Type Setting Temperature Range, Cooling Mode Temperature Increment Auto Operation(electronic control) Self Diagnosis Timer Sleep Operation Healthy Dehumidification Mode Restart Delay minutes Refrigerant(R-22) Charge g(oz) Power cord AWG #: P*mm2 Fuse or breaker Capacity A Connecting Cable AWG #: P*mm2 Connecting Tube Liquid Side mm(in) (ø. Socket Flare) Gas Side mm(in) Length, std m(ft) Additional Drain Hose(Outer Dia.) mm(in) Dimensions Indoor mm (WxHxD) in Outdoor mm in Net Weight Indoor kg(lbs) Outdoor kg(lbs)

B/A-HMC09AS B/A-HMC12AS B/A-HMC18AS 1, 115V, 60 1, 115, 60 1, 230/208, 60 9,000 12,000 18,000/17,800 940 1,290 1,900/1,870 8.5 11.7 8.5/9.0 46 58 47 9.6 9.3 9.5/9.5 7.1(250) 9.4(330) 13(460) 1.2(2.6) 1.4(3) 2.5(5.3) 38 41 44 36 39 41 35 37 38 48 48 55 Thermistor Thermistor Thermistor 4-way 4-way 4-way 3/3 3/3 3/3 Auto Auto Auto Manual Manual Manual Wireless LCD Wireless LCD Wireless LCD 64~86°F 64~86°F 64~86°F 2°F 2°F 2°F Yes Yes Yes Yes Yes Yes 24hr, On/Off 24hr, On/Off 24hr, On/Off Yes Yes Yes Yes Yes Yes 3 3 3 630(22.2) 730(25.8) 1,250(44.1) 14:3*2.5 14:3*2.5 14:3*2.5 15A 20A 20A 16:4*0.75 18:4*0.75 18:4*0.75 6.35(1/4) 6.35(1/4) 6.35(1/4) 12.7(1/2) 12.7(1/2) 15.88(5/8) 7.62(25) 7.62(25) 7.62(25) 15.5(5/8) 15.5(5/8) 15.5(5/8) 802*262*165 888*287*170 1,080*314*181 31.6*10.3*6.5 35.0*11.3*6.7 42.5*12.4*7.1 770*540*245 770*540*245 870*655*320 30.3*21.3*9.6 30.3*21.3*9.6 34.3*25.8*12.6 7(15.4) 9.5(20.9) 13(28.7) 32(70.5) 32(70.5) 61(134.5)

* Design and Specifications subject to change without prior notice for product improvement.

-5-

B/A-HMC24AS 1, 230/208, 60 23,000/22,600 2,550/2,500 11.5/12.0 67 9.0/9.0 15(530) 3.1(6.6) 49 45 40 57 Thermistor 4-way 3/3 Auto Manual Wireless LCD 64~86°F 2°F Yes Yes 24hr, On/Off Yes Yes 3 2,000(70.5) 14:3*2.5 25A 18:4*0.75 9.52(3/8) 15.88(5/8) 7.62(25) 15.5(5/8) 1,080*314*181 42.5*12.4*7.1 870*655*320 34.3*25.8*12.6 13(28.7) 62(136.7)

Product Specifications(Cooling & Heating) Items Power Supply Cooling Capacity Heating Capacity Input Running Current COMP. Locked Rotor AMP. E.E.R C.O.P Air Circulation Moisture Removal Noise Level (Sound Pressure, 1m)

Cooling Heating Cooling Heating Cooling Heating

Unit ø, V, Hz BTU/h BTU/h W W A A A A BTU/hW m3/min(cfm) l/h(pts/hr) dB(A) dB(A) dB(A) dB(A)

Indoor, High Med Low Outdoor, Max Features Temperature Control Air Deflection Steps, Fan/Cool/Heat Airflow Direction Control(up&down) Airflow Direction Control(left&right) Remocon Type Setting Temperature Range, Cooling Mode Heating Mode Temperature Increment Auto Operation(electronic control) Self Diagnosis Timer Sleep Operation Healthy Dehumidification Mode Restart Delay minutes Defrost Control Hot Start Refrigerant(R-22) Charge g(oz) Power cord AWG #: P*mm2 Fuse or breaker Capacity A Connecting Cable AWG #: P*mm2 Connecting Tube Liquid Side mm(in) (ø. Socket Flare) Gas Side mm(in) Length, std m(ft) Additional Drain Hose(Outer Dia.) mm(in) Dimensions Indoor mm (WxHxD) in Outdoor mm in Net Weight Indoor kg(lbs) Outdoor kg(lbs)

B/A-HMH12AS 1, 115, 60 12,000 12,000 1,290 1,290 11.7 11.7 58 58 9.3 2.75 9.4(330) 1.4(3) 41 39 37 48 Thermistor 4-way 3/3/3 Auto Manual Wireless LCD 64~86°F 60~86°F 2°F Yes Yes 24hr, On/Off Yes Yes 3 Yes Yes 840(29.6) 14:3*2.5 20A 18:4*0.75 6.35(1/4) 12.7(1/2) 7.62(25) 15.5(5/8) 888*287*170 35.0*11.3*6.7 770*540*245 30.3*21.3*9.6 9.5(20.9) 33(72.8)

B/A-HMH18AS 1, 230/208, 60 18,000/17,800 19,000/18,700 1,900/1,870 1,900/1,870 8.5/9.0 8.5/9.0 42 42 9.5/9.5 2.9/2.9 13(460) 2.5(5) 44 41 38 55 Thermistor 4-way 3/3/3 Auto Manual Wireless LCD 64~86°F 60~86°F 2°F Yes Yes 24hr, On/Off Yes Yes 3 Yes Yes 1350(47.6) 14:3*2.5 20A 18:4*0.75 6.35(1/4) 15.88(5/8) 7.62(25) 15.5(5/8) 1080*314*181 42.5*12.4*7.1 870*655*320 34.3*25.8*12.6 13(28.7) 62(136.7)

* Design and Specifications subject to change without prior notice for product improvement.

-6-

B/A-HMH24AS 1, 230/208, 60 23,000/22,600 23,000/22,600 2,550/2,500 2,550/2,500 11.5/12.0 11.5/12.0 67 67 9.0/9.0 2.6/2.6 15(530) 3.1(6.6) 47 44 40 58 Thermistor 4-way 3/3/3 Auto Manual Wireless LCD 64~86°F 60~86°F 2°F Yes Yes 24hr, On/Off Yes Yes 3 Yes Yes 1900(67.0) 14:3*2.5 25A 18:4*0.75 9.52(3/8) 15.88(5/8) 7.62(25) 15.5(5/8) 108*314*181 42.5*12.4*7.1 870*655*320 34.3*25.8*12.6 13(28.7) 63(138.9)

Dimensions (1) Indoor Unit

D W

H

Installation plate

Tubing hole cover

Tubing hole cover

MODEL DIM

9K

12K

18K, 24K

W

mm(inch)

802(31.6")

888(35.0")

1,080(42.5")

H

mm(inch)

262(10.3")

287(11.3")

314(12.4")

D

mm(inch)

165(6.5")

170(6.7")

181(7.1")

-7-

(2) Outdoor Unit 1. 9K, 12K L2

D

L1

W

H

L3

L5

Gas side (3-way valve)

L4

Liquid side (2-way valve)

DIM

MODEL unit

9K, 12K

W

mm(inch)

770(30.3)

H

mm(inch)

540(21.3)

D

mm(inch)

245(9.6)

L1

mm(inch)

287(11.3)

L2

mm(inch)

64(2.5)

L3

mm(inch)

518(20.4)

L4

mm(inch)

10(0.4)

L5

mm(inch)

100(3.9)

-8-

2. 18K, 24K

L1 L9

H

L3

L2

D

W

L4

L10

Gas side 3-way valve

L6

L5

L7

MODEL

Liquid side 3-way valve

L8

18K, 24K

DIM W

mm(inch)

870(34.3)

H

mm(inch)

655(25.8)

D

mm(inch)

320(12.6)

L1

mm(inch)

370(14.6)

L2

mm(inch)

25(1.0)

L3

mm(inch)

630(24.8)

L4

mm(inch)

25(1.0)

L5

mm(inch)

546(21.5)

L6

mm(inch)

162(6.4)

L7

mm(inch)

162(6.4)

L8

mm(inch)

54(2.1)

L9

mm(inch)

74.5(2.9)

L10

mm(inch)

79(3.1)

-9-

Refrigeration Cycle Diagram • Cooling Only Models INDOOR UNIT

OUTDOOR UNIT

LIQUID SIDE

CAPILLARY TUBE

HEAT EXCHANGER (EVAPORATOR)

HEAT EXCHANGER (CONDENSER)

COMPRESSOR

GAS SIDE

Pipe size(Diameter:ø)

Piping length

Elevation

MODEL Gas

Liquid

Rated

Max

Rated

Max

9K, 12K (Cooling Only)

1/2"

1/4"

7.62m(25ft)

15m(50ft)

5m(16ft)

8m(26ft)

18K (Cooling Only)

5/8"

1/4"

7.62m(25ft)

15m(50ft)

5m(16ft)

8m(26ft)

24K (Cooling Only)

5/8"

3/8"

7.62m(25ft)

15m(50ft)

5m(16ft)

8m(26ft)

For installation over rated, *a proper quantity of refrigerant should be added for each 3.3ft(1m). a proper quantity of refrigerant 9k, 12k

0.7 Oz (20g)

18k, 24k

1.4 Oz (40g)

Ex) 18K: When installed at a distance of 50ft(15m), 10.6Oz(295g) of refrigerant should be added. (50-25) 1.4 3.3 = 10.6 Oz (295g) of refrigerant to add

Unit precharged for 25ft. line sets.

- 10 -

• Cooling & Heating Models OUTDOOR UNIT

INDOOR UNIT

LIQUID SIDE

CAPILLARY TUBE

HEAT EXCHANGER (EVAPORATOR)

CHECK VALVE

HEAT EXCHANGER (CONDENSER)

GAS SIDE REVERSING VALVE COOLING HEATING

COMPRESSOR

Pipe size(Diameter:ø) MODEL

Piping length

Elevation

Gas

Liquid

Rated

Max

Rated

Max

9K, 12K (Cooling & Heating)

1/2"

1/4"

7.62m(25ft)

15m(50ft)

5m(16ft)

8m(26ft)

18K (Cooling & Heating)

5/8"

1/4"

7.62m(25ft)

15m(50ft)

5m(16ft)

8m(26ft)

24K (Cooling & Heating)

5/8"

3/8"

7.62m(25ft)

15m(50ft)

5m(16ft)

8m(26ft)

For installation over rated, *a proper quantity of refrigerant should be added for each 3.3ft (1m). a proper quantity of refrigerant 9k, 12k

0.7 Oz (20g)

18k, 24k

1.4 Oz (40g)

Ex) 18K: When installed at a distance of 50ft(15m), 10.6Oz(295g) of refrigerant should be added. (50-25) 1.4 3.3 = 10.6 Oz (295g) of refrigerant to add

Unit precharged for 25ft. line sets.

- 11 -

Wiring Diagram (1) Indoor Unit

BLDC MOTOR

CN-UP/DOWN

CN-MOTOR

CN-DC/DC

MAIN P.C.B

INDOOR WIRING DIAGRAM

- 12 -

BL BK BR RD

4 3 2 1 PILLAR TERMINAL

3854AR7074A

TO OUTDOOR UNIT

STEP MOTOR

CN-DISP

DISPLAY P.C.B

(ROOM) THERMISTOR (PIPE)

CN-TH

1. 9K, 12K, 18K, 24K(Cooling Only Models, Cooling & Heating Models)

(2) Outdoor Unit • Cooling Only Models 1. 9K, 12K MAIN P.C.B

CN-TRANS

YL T/B 1

RD

ZNR

BR MOTOR

FUSE 3.15A

RD

BL BL

TRANSFORMER

BL

BK BK

RY-COMP 4

CN-POWER

F

CAPACITOR

3

BL

CN-DC/DC

RD BR BK BL

C

BR H

FUSE 2.5A

BL BR

(N)

TERMINAL BLOCK

YL BR

(L)

G

R S C

COMP. O.L.P

TO INDOOR UNIT POWER INPUT

OUTDOOR WIRING DIAGRAM

3854A30077Z

2. 18K

ZNR

MOTOR

FUSE 3.15A

BK

F

BR

C

3

4

CN-POWER CN-DC/DC

BR

BL

8

YL O.L.P S C BR

RD BR BK BL FUSE 2.5A

BL

1

R

BL BL BK

RY-COMP

H

CAPACITOR

BR

BR

CN-TRANS

T/B 1

BK

YL

TRANSFORMER

MAIN P.C.B OR(BR)

BR

6 4 BL 2

0

COMP.

TERMINAL BLOCK

BL RD

G

TO INDOOR UNIT

OUTDOOR WIRING DIAGRAM

3854AR7077J

POWER INPUT

3. 24K

ZNR

MOTOR

FUSE 3.15A

S C

0

BK

4

CN-POWER CN-DC/DC

BR

BL

RD BR BK BL FUSE 2.5A

BL

1

R

3

C

F

BR

YL

BL BL BK

RY-COMP

H

CAPACITOR

BR

BR

CN-TRANS

T/B 1

BK

YL

TRANSFORMER

MAIN P.C.B OR(BR)

8

BR

6 4 BL 2

COMP.

BL

TERMINAL BLOCK

RD

OUTDOOR WIRING DIAGRAM

- 13 -

G

TO INDOOR UNIT

3854AR7077L

POWER INPUT

• Cooling & Heating Models

BK

T/B 3

RD

BK

T/B 4

RD

RY-4WAY

MAIN P.C.B

BL

F

CN-FAN

WH T/B 1

MOTOR CAPACITOR

RY-FAN

YL

RY-HEATER

WH WH T/B 2

ZNR FUSE 3.15A

BL BL BK BK

RY-COMP 3

WH

C

CN-TRANS

RD

TRANSFORMER

4WAYVALVE

CN-4WAY

1. 9K, 12K

H

CRANK CASE HEATER

4

CN-POWER

BR

CN-DC/DC

RD BR BK BL

BL FUSE 2.5A

BL BR

YL S C

R

BR O.L.P

COMP.

(N)

TERMINAL BLOCK

RD

(L)

G

TO INDOOR UNIT POWER INPUT

OUTDOOR WIRING DIAGRAM

3854A30077W

F

R

C YL S C

0

8

ZNR FUSE 3.15A

BL BL BK BK

TRANSFORMER

WH T/B 4

RY-COMP 3

CRANK CASE HEATER

1 BR

RY-HEATER

WH

CN-TRANS

WH T/B 3

WH BL

MAIN P.C.B

RY-FAN

BK

BR

4

CN-POWER CN-DC/DC

BR

BL

H

CAPACITOR

MOTOR

RY-4WAY

RD

BK BK

YL

RD

T/B 2

CN-FAN

OR(BR)

T/B 1

RD BR BK BL FUSE 2.5A

BK

4WAYVALVE

CN-4WAY

2. 18K, 24K

BR

6 4 BL 2

BL

TERMINAL BLOCK

G

COMP. RD

TO INDOOR UNIT

OUTDOOR WIRING DIAGRAM

- 14 -

3854AR7077M

POWER INPUT

Operation Details (1) The function of main control 1. Time delay Safety Control • 3min.; The compressor operation is delayed for 3 minutes to balance the pressure of cycle. (Protection of compressor) • 5sec.; The indoor fan is delayed for 5 seconds, when operating initially, to prevent noises occurred by the vertical louver and wind. • 2min.; The reversing valve is delayed for 2 minutes to prevent the refrigerant-gas for abnormal noise when the heating operation is OFF or switched to the other operation mode while compressor is off. While compressor is running, it takes 3~5 seconds to switch.

2. Chaos Swing Mode • By the Chaos Swing key input, the upper/lower vane automatically operates with the Chaos Swing or they are fixed to the desired direction. • While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.

< Cooling Mode >

< Heating Mode >

CLOSED

CLOSED





OPEN

OPEN

3. Cooling Operation Mode • When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote control and the operation diagram is shown below. INTAKE AIR TEMP. SETTING TEMP. +1°F (Compressor ON) SETTING TEMP. -1°F (Compressor OFF)

INDOOR FAN SPEED COMPRESSOR ■ Protection

More than 3 minutes

More than 3 minutes

Setting fan speed

Low

Setting fan speed

Low

ON

OFF

ON

OFF

Setting fan speed ON

of the indoor heat exchanger from frosting

• Compressor and outdoor fan stop when indoor pipe temperature is below 0°C(32°F) and restart at the pipe temperature is above 7°C(45°F).

- 15 -

4. Auto Operation (Electronic control mode) • The operation procedure is shown below. (Cooling & Heating Model) Press Start/Stop Button

Select Auto Operation Mode Check the Room temperature

Operation mode Indoor fan speed Setting temperature

are decided automatically by the unit electronic control.

Intake-air temperature

below 70°F

Operation Mode

Heating

Over 70°F

~

below 76°F

Over 76°F

Soft Dry

Cooling

❋ If initial mode is decided, that mode is continued without the room temperature changing. ■ Auto

Operation for Cooling

Operation Condition

When Auto Operation initial start

When pressing room temperature setting button during Auto Operation

Intake-air Temperature

Setting Temperature

Over 78°F

77°F

Over 76°F~below 78°F

Intake air -1°C

Over 72°F~below 76°F

Intake air -0.5°C

Over 68°F~below 72°F

Intake air temperature

below 64°F

64°F

Over 64°F~below 86°F

Electronic control

below 64°F

64°F

over 86°F

86°F

Fan Speed

Air Direction Control

Controlled by the electronic control

In this mode, when pressing the vertical air direction control button, vertical louver swings up and down automatically.

INTAKE AIR TEMP. SETTING TEMP. +1°F (Compressor OFF) SETTING TEMP. -1°F (Compressor ON)

INDOOR FAN SPEED COMPRESSOR

The electronic control operation ON

OFF

- 16 -

ON

OFF

■ Auto

Operation for Dehumidification(only Heating Model)

• The Setting temperature will be same that of the auto operation for cooling. - Compressor ON temperature; Setting temperature +2°F - Compressor OFF temperature; Setting temperture -1°F

■ Auto

Intake-air temp.

below 68°F

Over 68°F~below 70°F

over 86°F

Setting temp.

68°F

Intake air temperature +1°F

86°F

Operation for Heating(only Heating Model)

- Compressor ON temperature; Setting temperature - Compressor OFF temperature; Setting temperature +6°F ■ Vertical

louver auto operation : During Auto Operation, pressing the chaos swing button makes the horizontal louvers swing up and down automatically. If you want to stop auto-swing, press chaos swing button again.

- 17 -

5. Healthy Dehumidification • When the dehumidification operation input by the remote control is received, the intake air temperature is detected and the setting temp is automatically set according to the intake air temperature. 26°C ≤ Intake Air Temp ➲ 25°C 24°C ≤ Intake Intake Air Temp