R410A ˘ˇˆ ˙ SERVICE MANUAL Indoor Unit 4-way Air Discharge Cassette Type MMU-AP0091H, AP0121H, AP0151H, MMU-AP0181H, AP0241H, AP0271H,
FILE NO. A05-004-1 Revised: Jan./2006
SERVICE MANUAL R410A System air conditioner The indoor units in the Super Heat Recovery Multi System are common to those used in the Super Modular Multi System air conditioner. Therefore refer to the service manuals A03-009, A03-010, and A03-011 separately issued.
Heat Recovery Type Indoor Unit
Outdoor Unit
4-way Air Discharge Cassette Type
MMU-AP0091H, AP0121H, AP0151H, MMU-AP0181H, AP0241H, AP0271H, MMU-AP0301H, AP0361H, AP0481H MMU-AP0561H 2-way Air Discharge Cassette Type
MMU-AP0071WH, AP0091WH, AP0121WH, MMU-AP0151WH, AP0181WH, AP0241WH, MMU-AP0271WH, AP0301WH, AP0481WH* * CHINA market only
1-way Air Discharge Cassette Type
MMU-AP0071YH, AP0091YH, AP0121YH, MMU-AP0151SH, AP0181SH, AP0241SH, MMU-AP0152SH, AP0182SH, AP0242SH
Inverter Unit
MMY-MAP0802FT8 MMY-MAP1002FT8 MMY-MAP1202FT8
Flow Selector Unit (FS unit) RBM-Y1122FE RBM-Y1802FE RBM-Y2802FE
Concealed Duct Standard Type
MMD-AP0071BH, AP0091BH, AP0121BH, AP0151BH, MMD-AP0181BH, AP0241BH, AP0271BH, AP0301BH, MMD-AP0361BH, AP0481BH, AP0561BH Concealed Duct High Static Pressure Type
MMD-AP0181H, AP0241H, AP0271H, MMD-AP0361H, AP0481H Slim Duct Type
MMD-AP0071SPH, AP0091SPH, AP0121SPH, MMD-AP0151SPH, AP0181SPH Under Ceiling Type
MMC-AP0151H, AP0181H, AP0241H, MMC-AP0271H, AP0361H, AP0481H High Wall Type
MMK-AP0071H, AP0091H, AP0121H, MMK-AP0151H, AP0181H, AP0241H, MMK-AP0072H, AP0092H, AP0122H Floor Standing Cabinet Type
MML-AP0071H, AP0091H, AP0121H, MML-AP0151H, AP0181H, AP0241H Floor Standing Concealed Type
MML-AP0071BH, AP0091BH, AP0121BH, MML-AP0151BH, AP0181BH, AP0241BH Floor Standing Type
MMF-AP0151H, AP0181H, AP0241H,AP0271H, MMF-AP0361H, AP0481H, AP0561H
PRINTED IN JAPAN, Jan., 2006 ToMo
WARNINGS ON REFRIGERANT LEAKAGE Important
Check of Concentration Limit The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit. The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A is almost non-existent. With the recent increase in the number of high concentration buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared with conventional individual air conditioners. If a single unit of the multi conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can occur). In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device. The concentration is as given below. Total amount of refrigerant (kg) Min. volume of the indoor unit installed room (m³) ≤ Concentration limit (kg/m³)
NOTE 2 : The standards for minimum room volume are as follows. (1) No partition (shaded portion)
(2) When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door). Outdoor unit Refrigerant piping Indoor unit
(3) If an indoor unit is installed in each partitioned room and the refrigerant tubing is interconnected, the smallest room of course becomes the object. But when a mechanical ventilation is installed interlocked with a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next smallest room becomes the object. Refrigerant piping
Outdoor unit
The concentration limit of R410A which is used in multi air conditioners is 0.3kg/m³. NOTE 1 : If there are 2 or more refrigerating systems in a single refrigerating device, the amounts of refrigerant should be as charged in each independent device.
e.g., charged amount (10kg)
Outdoor unit e.g., charged amount (15kg)
Very small room
Indoor unit Small room
Medium room
Large room
Mechanical ventilation device - Gas leak detector
NOTE 3 : The minimum indoor floor area compared with the amount of refrigerant is roughly as follows: (When the ceiling is 2.7m high) 40 m² 35
Room A Room B Room C Room D Room E Room F Indoor unit
For the amount of charge in this example: The possible amount of leaked refrigerant gas in rooms A, B and C is 10kg. The possible amount of leaked refrigerant gas in rooms D, E and F is 15kg.
Min. indoor floor area
30 25
Range below the density limit of 0.3 kg/m³ (countermeasures not needed)
20 15 10
Range above the density limit of 0.3 kg/m³ (countermeasures needed)
5 0
10 20 30 Total amount of refrigerant
kg
CONTENTS SAFETY CAUTION ............................................................................................ 4 1. OUTLINE ................................................................................................... 9 2. WIRING DIAGRAM ................................................................................. 14 3. PARTS RATING ...................................................................................... 30 4. REFRIGERANT PIPING SYSTEMATIC DRAWING ............................... 48 5. SYSTEM REFRIGERANT CYCLE DRAWING ....................................... 53 6. CONTROL OUTLINE .............................................................................. 60 7. APPLIED CONTROL .............................................................................. 71 8. TEST OPERATION ................................................................................. 86 9. TROUBLESHOOTING .......................................................................... 116 10. CONFIGURATION OF CONTROL CIRCUIT ........................................ 174 11. BACKUP OPERATIONS (EMERGENCY OPERATION)....................... 188 12. OIL LEVEL JUDGMENT DISPLAY ....................................................... 190 13. REFRIGERANT RECOVERY WHEN REPLACING THE COMPRESSOR ........................................... 191 14. LEAKAGE/CLOGGING OF OIL-EQUALIZATION CIRCUIT ................. 197 15. REPLACING COMPRESSOR............................................................... 199 16. REPLACING PROCEDURE OF PARTS ............................................... 206 17. P.C. BOARD .......................................................................................... 217
NOTE Ensure power is isolated from the unit when replacing the high performance filter or when opening the service panel.
SAFETY CAUTION The important contents concerned to the safety are described on the product itself and on this Service Manual. Please read this Service Manual after understanding the described items thoroughly in the following contents (Indications/Illustrated marks), and keep them.
[Explanation of indications] Indication
Explanation
DANGER
Indicates contents assumed that an imminent danger causing a death or serious injury of the repair engineers and the third parties when an incorrect work has been executed.
WARNING
Indicates possibilities assumed that a danger causing a death or serious injury of the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
CAUTION
Indicates contents assumed that an injury or property damage (∗) may be caused on the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
∗ Property damage : Enlarged damage concerned to property, furniture, and domestic animal/pet
[Explanation of illustrated marks] Mark
Explanation Indicates prohibited items (Forbidden items to do) The sentences near an illustrated mark describe the concrete prohibited contents. Indicates mandatory items (Compulsory items to do) The sentences near an illustrated mark describe the concrete mandatory contents. Indicates cautions (including danger/warning) The sentences or illustration near or in an illustrated mark describe the concrete cautious contents.
[Confirmation of warning label on the main unit] Confirm that labels are indicated on the specified positions (Refer to the Parts disassembly diagram (Outdoor unit).) If removing the label during parts replace, stick it as the original.
DANGER
Turn off breaker.
Execute discharge between terminals.
Turn “OFF” the breaker before removing the front panel and cabinet, otherwise an electric shock is caused by high voltage resulted in a death or injury. During operation, a high voltage with 400V or higher of circuit (∗) at secondary circuit of the highvoltage transformer is applied. If touching a high voltage with the naked hands or body, an electric shock is caused even if using an electric insulator. ∗ : For details, refer to the electric wiring diagram. When removing the front panel or cabinet, execute short-circuit and discharge between highvoltage capacitor terminals. If discharge is not executed, an electric shock is caused by high voltage resulted in a death or injury. After turning off the breaker, high voltage also keeps to apply to the high-voltage capacitor. Do not turn on the breaker under condition that the front panel and cabinet are removed. An electric shock is caused by high voltage resulted in a death or injury.
Prohibition
4
WARNING
Check earth wires.
Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of the main unit, otherwise an electric shock is caused when a leak occurs. If the earth wire is not correctly connected, contact an electric engineer for rework. Do not modify the products. Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury.
Prohibition of modification.
Use specified parts.
Do not bring a child close to the equipment.
For spare parts, use those specified (∗ ∗). If unspecified parts are used, a fire or electric shock may be caused. ∗: For details, refer to the parts list. Before troubleshooting or repair work, do not bring a third party (a child, etc.) except the repair engineers close to the equipment. It causes an injury with tools or disassembled parts. Please inform the users so that the third party (a child, etc.) does not approach the equipment. Connect the cut-off lead cables with crimp contact, etc, put the closed end side upward and then apply a water-cut method, otherwise a leak or production of fire is caused at the users’ side.
Insulating measures
No fire
When repairing the refrigerating cycle, take the following measures. 1) Be attentive to fire around the cycle. When using a gas stove, etc, be sure to put out fire before work; otherwise the oil mixed with refrigerant gas may catch fire. 2) Do not use a welder in the closed room. When using it without ventilation, carbon monoxide poisoning may be caused. 3) Do not bring inflammables close to the refrigerant cycle, otherwise fire of the welder may catch the inflammables. Check the used refrigerant name and use tools and materials of the parts which match with it. For the products which use R410A refrigerant, the refrigerant name is indicated at a position on the outdoor unit where is easy to see. To prevent miss-charging, the route of the service port is changed from one of the former R22. For an air conditioner which uses R410A, never use other refrigerant than R410A. For an air conditioner which uses other refrigerant (R22, etc.), never use R410A. If different types of refrigerant are mixed, abnormal high pressure generates in the refrigerating cycle and an injury due to breakage may be caused.
Refrigerant
Do not charge refrigerant additionally. If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over the specified standard amount is charged and an abnormal high pressure is applied to the inside of the refrigerating cycle resulted in cause of breakage or injury. Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute vacuuming, and then newly recharge the specified amount of liquid refrigerant. In this time, never charge the refrigerant over the specified amount. When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant or air other than R410A into the specified refrigerant. If air or others is mixed with the refrigerant, abnormal high pressure generates in the refrigerating cycle resulted in cause of injury due to breakage. After installation work, check the refrigerant gas does not leak. If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous. Never recover the refrigerant into the outdoor unit. When the equipment is moved or repaired, be sure to recover the refrigerant with recovering device. The refrigerant cannot be recovered in the outdoor unit; otherwise a serious accident such as breakage or injury is caused.
Assembly/Cabling
After repair work, surely assemble the disassembled parts, and connect and lead the removed cables as before. Perform the work so that the cabinet or panel does not catch the inner cables. If incorrect assembly or incorrect cable connection was done, a disaster such as a leak or fire is caused at user’s side.
5
WARNING
Insulator check
Ventilation
After the work has finished, be sure to use an insulation tester set (500V mugger) to Ω or more between the charge section and the non-charge check the resistance is 2MΩ metal section (Earth position). If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side. When the refrigerant gas leaks during work, execute ventilation. If the refrigerant gas touches to a fire, poisonous gas generates. A case of leakage of the refrigerant and the closed room full with gas is dangerous because a shortage of oxygen occurs. Be sure to execute ventilation. When checking the circuit inevitably under condition of the power-ON, use rubber gloves and others not to touch to the charging section. If touching to the charging section, an electric shock may be caused.
Be attentive to electric shock
When the refrigerant gas leaks, find up the leaked position and repair it surely. If the leaked position cannot be found up and the repair work is interrupted, pump-down and tighten the service valve, otherwise the refrigerant gas may leak into the room. The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
Compulsion
When installing equipment which includes a large amount of charged refrigerant such as a multi air conditioner in a sub-room, it is necessary that the density does not the limit even if the refrigerant leaks. If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is caused. For the installation/moving/reinstallation work, follow to the Installation Manual. If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric shock or fire is caused. After repair work has finished, check there is no trouble. If check is not executed, a fire, electric shock or injury may be caused. For a check, turn off the power breaker.
Check after rerair
Check after reinstallation
After repair work (installation of front panel and cabinet) has finished, execute a test run to check there is no generation of smoke or abnormal sound. If check is not executed, a fire or an electric shock is caused. Before test run, install the front panel and cabinet. Check the following items after reinstallation. 1) The earth wire is correctly connected. 2) The power cord is not caught in the product. 3) There is no inclination or unsteadiness and the installation is stable. If check is not executed, a fire, an electric shock or an injury is caused.
CAUTION
Put on gloves
Cooling check
∗) during repair work. Be sure to put on gloves (∗ If not putting on gloves, an injury may be caused with the parts, etc. (∗) Heavy gloves such as work gloves When the power was turned on, start to work after the equipment has been sufficiently cooled. As temperature of the compressor pipes and others became high due to cooling/heating operation, a burn may be caused.
6
• New Refrigerant (R410A) This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer.
1. Safety Caution Concerned to New Refrigerant The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant, the refrigerating oil has been also changed. Therefore, be sure that water, dust, the former refrigerant or the former refrigerating oil is not mixed into the refrigerating cycle of the air conditioner with new refrigerant during installation work or service work. If an incorrect work or incorrect service is performed, there is a possibility to cause a serious accident. Use the tools and materials exclusive to R410A to purpose a safe work.
4. Tools (1) Required Tools for R410A Mixing of different types of oil may cause generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types. 1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22)) 2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22) 3) Tools commonly used for R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
2. Cautions on Installation/Service (1) Do not mix the other refrigerant or refrigerating oil. For the tools exclusive to R410A, shapes of all the joints including the service port differ from those of the former refrigerant in order to prevent mixture of them. (2) As the use pressure of the new refrigerant is high, use material thickness of the pipe and tools which are specified for R410A. (3) In the installation time, use clean pipe materials and work with great attention so that water and others do not mix in because pipes are affected by impurities such as water, oxide scales, oil, etc. Use the clean pipes. Be sure to brazing with flowing nitrogen gas. (Never use gas other than nitrogen gas.) (4) For the earth protection, use a vacuum pump for air purge. (5) R410A refrigerant is azeotropic mixture type refrigerant. Therefore use liquid type to charge the refrigerant. (If using gas for charging, composition of the refrigerant changes and then characteristics of the air conditioner change.)
Tools whose specifications are changed for R410A and their interchangeability R410A air conditioner installation No.
Usage
Used tool
Conventional air conditioner installation
Existence of Whether convenWhether new equipment new equipment tional equipment can can be used with for R410A be used conventional refrigerant
Flare tool
Pipe flaring
Yes
*(Note 1)
Yes
Copper pipe gauge for adjusting projection margin
Flaring by conventional flare tool
Yes
*(Note 1)
*(Note 1)
Torque wrench
Connection of flare nut
Yes
No
No
Gauge manifold
Evacuating, refrigerant charge, run check, etc.
Yes
No
No
Charge hose
7
3. Pipe Materials
Vacuum pump adapter
Vacuum evacuating
Yes
No
Yes
For the refrigerant pipes, copper pipe and joints are mainly used. It is necessary to select the most appropriate pipes to conform to the standard. Use clean material in which impurities adhere inside of pipe or joint to a minimum.
Electronic balance for refrigerant charging
Refrigerant charge
Yes
Yes
Yes
Refrigerant cylinder
Refrigerant charge
Yes
No
No
Leakage detector
Gas leakage check
Yes
No
Yes
Charging cylinder
Refrigerant charge
(Note 2)
No
No
(1) Copper pipe
The pipe thickness, flare finishing size, flare nut and others differ according to a refrigerant type. When using a long copper pipe for R410A, it is recommended to select “Copper or copper-base pipe without seam” and one with bonded oil amount 40mg/10m or less. Also do not use crushed, deformed, discolored (especially inside) pipes. (Impurities cause clogging of expansion valves and capillary tubes.)
Use the flare nuts which are attached to the air conditioner unit.
(2) Joint The flare joint and socket joint are used for joints of the copper pipe. The joints are rarely used for installation of the air conditioner. However clear impurities when using them.
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary. (Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.) In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools. (1) Vacuum pump Use vacuum pump by attaching vacuum pump adapter. (2) Torque wrench (3) Pipe cutter (4) Reamer (5) Pipe bender (6) Level vial
(7) Screwdriver (+, –) (8) Spanner or Monkey wrench (9) Hole core drill (10) Hexagon wrench (Opposite side 4mm) (11) Tape measure (12) Metal saw
Also prepare the following equipments for other installation method and run check. (1) Clamp meter (3) Insulation resistance tester (Megger) (2) Thermometer (4) Electroscope (Volt meter)
5. Recharge of Refrigerant When recharge of the refrigerant is required, charge the new refrigerant with the specified amount in the procedure as described below. Recover the refrigerant and check there is no refrigerant in the equipment.
Leave it as it is for 1 to 2 minutes and check the indicator of the compound gauge does not return.
Connect the charge hose to the packed valve service ports at gas side, liquid side, and balance side of the outdoor unit.
Set the refrigerant cylinder on the electronic balance, connect the charge hose to connecting ports of the cylinder and the electronic gauge, and then charge the liquid refrigerant from the service port at liquid side. (Shield with the gauge manifold so that refrigerant does not flow to gas side.)
Connect the charge hose to vacuum pump adaptor.
Open the packed valves of the balance pipe fully at liquid and gas sides, and then return the valve at gas side a little to the closed side.
Open fully PMV of the outdoor unit. • Turn on power of the outdoor unit. • Short CN30 on I/F P.C. board of the outdoor unit. • Turn off power of the outdoor unit within 2 minutes after shorting CN30.
(Charge the refrigerant as below.)
LowHighpressure gauge pressure gauge Connected to indoor unit
Valve fully closed (gas side) Main Center unit pipe
Open fully the handle on the Low side of the gauge manifold, and then turn on the power of vacuum pump for vacuuming.
Brazed
Fully tightened
When the pressure has lowered until indication of the compound gauge pointed –0.1MPa (–76cmHg), open fully the handle Low and turn off the power of vacuum pump.
Q R
Q R
Service port Ø6.4 Copper pipe
VL
VH Gauge manifold
Reducing valve
Service port Valve fully closed (liquid side) Fully tightened
Never charge the refrigerant over the specified amount. Do not charge the additional refrigerant. If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over the specified standard amount is charged and an abnormal high pressure is applied to the inside of the refrigerating cycle resulted in cause of breakage or injury.
Nitrogen gas Ø6.4 Copper pipe
Valve fully closed (balance) Connected to other terminal units
4mm-hexagonal wrench is required.
Set the equipment so that liquid refrigerant can be charged. When using a cylinder with siphon pipe, liquid can be charged without inverting the cylinder. [ Cylinder with siphon ]
[ Cylinder without siphon ]
Gauge manifold
Gauge manifold OUTDOOR unit
Electronic balance
6. Environmental concern
Refrigerant cylinder
Refrigerant cylinder
Siphon OUTDOOR unit
Electronic balance
R410A refrigerant is consisted with HFC mixed refrigerant. Therefore if the refrigerant gas is charged, the composition of the charged refrigerant changes and characteristics of the equipment changes.
Use “Vacuum pump method” for an air purge (Discharge of air in the connecting pipe) in installation time. • Do not discharge flon gas into the air to protect the earth environment. • Using the vacuum pump method, clear the remaining air (Nitrogen, etc.) in the unit. If the air remains, the pressure in the refrigerating cycle becomes abnormally high and an injury could occur through failure of the product.
8
1. OUTLINE “Super Heat Recovery Multi System” is a multi air conditioning system which enables each indoor unit in a refrigerant line to independently select cooling or heating operation. As it is able to operate simultaneously in cooling and heating modes, further heat recovery becomes possible. This system is most suitable for a building etc. where cool and hot air are mixed, such as a building where there are large temperature differences between rooms, caused by the influence of daylight or where used in a server room and permanent cooling is required. Heating and cooling operation are automatically selected in individual unit; You can save time for operation. For example, when heating is required for early morning and cooling for daytime, a Flow Selector Unit provides automatically a smooth selection of heating or cooling operation. Therefore you can obtain a comfortable room environment without feeling somewhat out of place and moreover you can save time to select heat/cool operation.
INFORMATION The Super Heat Recovery Multi system is different from that of the conventional Multi air conditioner in several ways such as the heating and cooling operations are mixed and only a part of the air conditioning system operates in cooling function. For this reason, the following table explains the operation modes of this air conditioner. The following table explains the representation of the operation modes within this Manual.
Operation mode Operation mode
Outline
1. All Cooling
All indoor units are under cooling operation only. Outdoor heat exchanger (Main heat exchanger) is used as condenser.
2. All Heating
All indoor units are under heating operation only. Outdoor heat exchanger (Main heat exchanger) is used as evaporator.
3. Simultaneous operation
MIU for simultaneous operation
3-1. Mainly cooling, partly heating operation
Indoor units are under heating/cooling simultaneous operation with subjective cooling operation Outdoor heat exchanger (Sub heat exchanger) is used as condenser.
3-2. Mainly heating, partly cooling operation
Indoor units are under heating/cooling simultaneous operation with subjective heating operation Outdoor heat exchanger (Main heat exchanger) is used as evaporator.
4. Defrost
Using the reversing operation of the 4-way valve, ice on the outdoor heat exchanger is dissolved within single cooling cycle.
9
1-1. Component Multi Using High-efficiency Refrigerant R410A 1. Outdoor units Inverter unit Corresponding HP
Appearance 8 HP
10 HP
12 HP
MAP0802FT8
MAP1002FT8
MAP1202FT8
Cooling capacity (kW)
22.4
28.0
33.5
Heating capacity (kW)
25.0
31.5
37.5
13
16
20
Model name
Heat pump
MMY-
No. of connectable indoor units
2. Combination of outdoor units Corresponding HP Combined Model
MMY-
Cooling capacity (kW) Heating capacity (kW) Combined outdoor units No. of connectable indoor units
16 HP
18 HP
20 HP
24 HP
26 HP
28 HP
30 HP
AP1602FT8
AP1802FT8
AP2002FT8
AP2402FT8
AP2602FT8
AP2802FT8
AP3002FT8
45.0
50.4
56.0
68.0
73.0
78.5
84.0
50.0
56.5
63.0
76.5
81.5
88.0
95.0
8 HP
10 HP
10 HP
8 HP
10 HP
10 HP
10 HP
8 HP
8 HP
10 HP
8 HP
8 HP
10 HP
10 HP
—
—
—
8 HP
8 HP
8 HP
10 HP
27
30
33
40
43
47
48
3. Branching joints and headers Model name RBM-BY53FE
Y-shape branching joint (∗3)
4-branching header (∗4)
8-branching header (∗4)
T-branch joint
∗1 ∗2 ∗3 ∗4 ∗5 ∗6
Usage Indoor unit capacity code (∗1)
Total below 6.4
RBM-BY103FE Indoor unit capacity code (∗1)
Total below 14.2
RBM-BY53E
Indoor unit capacity code (∗1)
Total below 6.4
RBM-BY103E
Indoor unit capacity code (∗1)
Total below 14.2
RBM-BY203FE Indoor unit capacity code (∗1)
Total below 25.2
RBM-BY303FE Indoor unit capacity code (∗1)
Total below 25.2
RBM-BY203E
Indoor unit capacity code (∗1)
Total below 25.2
RBM-BY303E
Indoor unit capacity code (∗1)
Total below 25.2
RBM-1043FE
Indoor unit capacity code (∗1)
Total below 14.2
RBM-2043FE
Indoor unit capacity code (∗1)
Total below 25.2
RBM-1043E
Indoor unit capacity code (∗1)
Total below 14.2
RBM-2043E
Indoor unit capacity code (∗1)
Total below 25.2
RBM-1083FE
Indoor unit capacity code (∗1)
Total below 14.2
RBM-2083FE
Indoor unit capacity code (∗1)
Total below 25.2
Appearance For 3 piping For 2 piping (∗5) For 3 piping For 2 piping (∗5) For 3 piping For 2 piping (∗5) For 3 piping
RBM-1083E
Indoor unit capacity code (∗1)
Total below 14.2
RBM-2083E
Indoor unit capacity code (∗1)
Total below 25.2
BT13-FE
The following 3 types of T joint pipes are supplied as 1 set. • Balance pipe (Ø9.5) × 1 • Liquid side (Corresponded dia. Ø12.7 to Ø19.1) × 1 • Suction gas side (Corresponded dia. Ø22.2 to Ø34.9) × 1 • Discharge gas side (Corresponded dia. Ø19.1 to Ø22.2) × 1
For 2 piping (∗5)
“Capacity code” can be obtained from page 11, 12. (Capacity code is not actual capacity) If the total capacity code value of indoor unit exceeds that of the outdoor unit, apply capacity code of the outdoor unit. When using a Y-shape branching joint for 1st branching, select according to the capacity code of the outdoor unit. Max. 6.0 capacity code in total can be connected. This is used for branching to “cooling only” indoor unit. Model names for outdoor described in this guide are shortened because of the space constraint.
10
4. Flow selector units (FS unit) Model name
Usage
RBM-Y1121FE
Capacity rank for indoor unit : Type 007 to 030
RBM-Y1801FE
Capacity rank for indoor unit : Type 036 to 056
RBM-Y2802FE
Capacity rank for indoor unit : Type 018 to 096
Appearance
* Accessory part (Sold separately): Connection cable kit (RBC-CBK15FE), up to 15m.
5. Indoor units Type
Appearance
Model name MMU-AP0091H
4-way Air Discharge Cassette Type
2-way Air Discharge Cassette Type
1-way Air Discharge Cassette Type
Concealed Duct Standard Type
Capacity rank Capacity code 009 type
1
Cooling capacity (kW)
Heating capacity (kW)
2.8
3.2
MMU-AP0121H
012 type
1.25
3.6
4.0
MMU-AP0151H,
015 type
1.7
4.5
5.0
MMU-AP0181H
018 type
2
5.6
6.3
MMU-AP0241H
024 type
2.5
7.1
8.0
MMU-AP0271H
027 type
3
8.0
9.0
MMU-AP0301H
030 type
3.2
9.0
10.0
MMU-AP0361H
036 type
4
11.2
12.5
MMU-AP0481H
048 type
5
14.0
16.0
MMU-AP0561H
056 type
6
16.0
18.0
MMU-AP0071WH
007 type
0.8
2.2
2.5
MMU-AP0091WH
009 type
1
2.8
3.2
MMU-AP0121WH
012 type
1.25
3.6
4.0
MMU-AP0151WH
015 type
1.7
4.5
5.0
MMU-AP0181WH
018 type
2
5.6
6.3
MMU-AP0241WH
024 type
2.5
7.1
8.0
MMU-AP0271WH
027 type
3
8.0
9.0
MMU-AP0301WH
030 type
3.2
9.0
10.0
MMU-AP0481WH (CHINA only)
048 type
5
14.0
16.0
MMU-AP0071YH
007 type
0.8
2.2
2.5
MMU-AP0091YH
009 type
1
2.8
3.2
MMU-AP0121YH
012 type
1.25
3.6
4.0
MMU-AP0151SH
015 type
1.7
4.5
5.0
MMU-AP0181SH
018 type
2
5.6
6.3
MMU-AP0241SH
024 type
2.5
7.1
8.0
MMU-AP0152SH
015 type
1.7
4.5
5.0
MMU-AP0182SH
018 type
2
5.6
6.3
MMU-AP0242SH
024 type
2.5
7.1
8.0
MMD-AP0071BH
007 type
0.8
2.2
2.5
MMD-AP0091BH
009 type
1
2.8
3.2
MMD-AP0121BH
012 type
1.25
3.6
4.0
MMD-AP0151BH
015 type
1.7
4.5
5.0
MMD-AP0181BH
018 type
2
5.6
6.3
MMD-AP0241BH
024 type
2.5
7.1
8.0
MMD-AP0271BH
027 type
3
8.0
9.0
MMD-AP0301BH
030 type
3.2
9.0
10.0
MMD-AP0361BH
036 type
4
11.2
12.5
MMD-AP0481BH
048 type
5
14.0
16.0
MMD-AP0561BH
056 type
6
16.0
18.0
11
Type
Concealed Duct High Static Pressure Type
Slim Duct Type
Under Ceiling Type
High Wall Type
Floor Standing Cabinet Type
Floor Standing Concealed Type
Floor Standing Type
Appearance
Model name
Capacity rank Capacity code
Cooling capacity (kW)
Heating capacity (kW)
MMD-AP0181H
018 type
2
5.6
6.3
MMD-AP0241H
024 type
2.5
7.1
8.0
MMD-AP0271H
027 type
3
8.0
9.0
MMD-AP0361H
036 type
4
11.2
12.5
MMD-AP0481H
048 type
5
14.0
16.0
MMD-AP0071SPH
007 type
0.8
2.2
2.5
MMD-AP0091SPH
009 type
1
2.8
3.2
MMD-AP0121SPH
012 type
1.25
3.6
1.0
MMD-AP0151SPH
015 type
1.7
4.5
5.0
MMD-AP0181SPH
018 type
2
5.6
6.3
MMC-AP0151H
015 type
1.7
4.5
5.0
MMC-AP0181H
018 type
2
5.6
6.3
MMC-AP0241H
024 type
2.5
7.1
8.0
MMC-AP0271H
027 type
3
8.0
9.0
MMC-AP0361H
036 type
4
11.2
12.5
MMC-AP0481H
048 type
5
14.0
16.0
MMK-AP0071H
007 type
0.8
2.2
2.5
MMK-AP0091H
009 type
1
2.8
3.2
MMK-AP0121H
012 type
1.25
3.6
4.0
MMK-AP0151H
015 type
1.7
4.5
5.0
MMK-AP0181H
018 type
2
5.6
6.3
MMK-AP0241H
024 type
2.5
7.1
8.0
MMK-AP0072H
007 type
0.8
2.2
2.5
MMK-AP0092H
009 type
1
2.8
3.2
MMK-AP0122H
012 type
1.25
3.6
4.0
MML-AP0071H
007 type
0.8
2.2
2.5
MML-AP0091H
009 type
1
2.8
3.2
MML-AP0121H
012 type
1.25
3.6
4.0
MML-AP0151H
015 type
1.7
4.5
5.0
MML-AP0181H
018 type
2
5.6
6.3
MML-AP0241H
024 type
2.5
7.1
8.0
MML-AP0071BH
007 type
0.8
2.2
2.5
MML-AP0091BH
009 type
1
2.8
3.2
MML-AP0121BH
012 type
1.25
3.6
4.0
MML-AP0151BH
015 type
1.7
4.5
5.0
MML-AP0181BH
018 type
2
5.6
6.3
MML-AP0241BH
024 type
2.5
7.1
8.0
MMF-AP0151H
015 type
1.7
4.5
5.0
MMF-AP0181H
018 type
2
5.6
6.3
MMF-AP0241H
024 type
2.5
7.1
8.0
MMF-AP0271H
027 type
3
8.0
9.0
MMF-AP0361H
036 type
4
11.2
12.5
MMF-AP0481H
048 type
5
14.0
16.0
MMF-AP0561H
056 type
6
16.0
18.0
12
n Remote controllers Name
Wired remote controller
Simple wired remote controller
Weekly timer
CODE No.
SuMoTuWeTh Fr Sa
SET DATA SETTING TEST
TEST
UNIT No.
SETTING R.C.
H
No.
PROGRAM1
˚C ˚F
PROGRAM2
ERROR
PROGRAM3
TEMP.
Appearance
ON / OFF WEEKLY TIMER
FILTER RESET TEST
Model name
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
UNIT
RBC-AMT31E
RBC-AS21E
RBC-EXW21E
Wireless remote controller kit
Name Receiver section
ADR
Receiver section mounted separately ADR
Receiver section
ADR
Appearance
Model name
RBC-AX2U (W)-E
RBC-AX22CE
TCB-AX21E
Type
4-way Air Discharge Cassette type
Under Ceiling type 1-way Air Discharge Cassette type (MMU-AP✽✽✽2SH Series)
Separate sensor type
Name
Central remote controller
ZONE ALL ZONE GROUP
CODE No. 1234 SET DATA SETTING
R.C.
UNIT No.
TEST
No.
Appearance GROUP SELECT
ZONE
CL
SET
Model name
TCB-SC642TLE
Type
64 system center controller
13
1 CN304 (GRY) 2 3 RED
Motor drive circuit
RY303
~
1 1
Fuse T3.15A 250V~
+
Power supply circuit
P301
CN66 1 (WHI) 2 CN44 1 (BLN) 2
CN50 (WHI)
1 2 3 4 5
Earth screw
1 2
Parts name Fan motor Indoor temp sensor Temp sensor Temp sensor Temp sensor Louver motor Drain pump motor Float switch Drain control relay Pulse Motor Valve
CN60 (WHI)
CN81 (BLK)
CN40 (BLU)
CN41 (BLU)
1 2 3 4 5 6
1 2 3 4 5
1 2 1 2
1 2 3 1 2 3
CN61 (YEL) T10 1 2 3 4 5 6
(Option)
(Fandrive)
Power supply Single phase 220-240V 50Hz 220V 60Hz
Symbol FM TA TC1 TCJ TC2 LM1, LM2 DM FS RY302 PMV
CN32 (WHI)
CN309 (YEL)
CN104 (YEL)
1 1 2 2
CN102 (RED)
1 1 2 2
CN101 (BLK)
1 1 2 2
CN100 (BRN)
1 1 2 2 3 3
CN80 (GRN)
1 2 PNL 3
CN73 (RED)
1 EXCT 2
CN20 CN70 (BLU) (WHI)
1 2 3 4 5
1 2 3 1 2 3
BLK
R(L) S(N)
Closed end connector
~
DC20V DC15V DC12V DC7V
BLU BLU
14
RED WHI
Indoor unit
3 3
Indoor control P.C. board MCC-1402
BLK
Flow selector unit earth screw
3 1 CN34 3 2 1 (RED)
RY302
Fuse T6.3A 250V~
BLK
1 2 3 4 5 CN33 1 2 3 4 5 (WHI)
1 2 3 4 5 6 CN82 1 2 3 4 5 6 (BLU)
CN67 (BLK) 2 2
WHI
FS
TR
1.
indicates the terminal block, letter at inside indicates the terminal number. 2. A dotted line and broken line indicate the wiring at site. 3. indicates the control P.C. board.
U1 U2
CN01 1 2 Network adaptor (WHI) 1 2 (Option)
A B BLK
WHI
U1 U2 Outdoor unit WHI
BLK CN1 (WHI)
Color identification RED WHI YEL BLU BRN
: RED : WHITE : YELLOW : BLUE : BROWN
BLK GRY PNK ORN GRN
: BLACK : GRAY : PINK : ORANGE : GREEN
WHI
BLK CN001 (WHI)
1 2 1 2
1 2 1 2
Wired remote controller
Adaptor for wireless remote controller
3 3 2 2 1 1 CN02 (BLU)
Network adaptor P.C. board
MCC-1401
1 2 CN03 1 2 (RED) X Y
TA TCJ TC2
TC1
1 Filter input 2
2. WIRING DIAGRAM
1 1 2 2 3 3
DM
1 2 3 4 5 1 2 3 4 5
2-1. Indoor Unit
5 4 3 2 1 CN334 1 2 3 4 5 CN333 5 4 3 2 1 (BLU) 1 2 3 4 5 (WHI)
1 2 3 4 5 1 2 3 4 5
2-1-1. 4-way Air Discharge Cassette Type
1 2 3 4 5 1 2 3 4 5
6 4 3 1 2 5 6 4 3 1 2 5 CN68 (BLU)
LM1
LM2
FM
Model: MMU-AP0091H, AP0121H, AP0151H, AP0181H, AP0241H, MMU-AP0271H, AP0301H, AP0361H, AP0481H, AP0561H
PMV
RC
LM
1 2 1 2
DM YEL
BLU
ORN
BLK
RED FAN 9 8 7 6 5 4 3 2 1 CN083(WHI) 9 8 7 6 5 4 3 2 1
9
H
Color indication
M
L
PMV
6 4 3 1 2 5 6 4 3 1 2 5
FS
DP
LM
FS
1 2 3 (BLU) 1 2 3 (GRN) 1 2 3 (RED) 1 2 3 CN068 1 2 3 CN033 1 2 3 CN030
PMV
1 2 3 4 5 6 (BLU) 1 2 3 4 5 6 CN082
UL
RY007
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
P301
(BLK)
RY002
RY001
RY006
1
CN304 (GRY) 2
RY005
Fuse T5.0A
15 CN066 1 (WHI) 2
Power supply circuit
CN044 1 (BRW) 2
CN040 CN041 (BLU) (BLU)
Indoor unit Earth screw R(L) S(N)
1 2 3 1 2 3 BLK
BLU BLU
1 2 1 2
CN050 (WHI)
CN075 (WHI)
CN074 (WHI)
1 2 3 4 5
1 2 3 1 2 3
BLK
Flow selector unit earth screw TR
CN102 (RED)
1 1 2 2
CN101 (BLK)
1 1 2 2
CN100 (BRW)
1 1 2 2 3 3
CN080 (GRN)
1 2 PNL 3
CN073 (RED)
1 EXCT 2
CN070 (WHI)
1 1 2 2
CN081 (BLK)
1 2 3 4 5
Indoor control P.C. board
1 1 2 2 3 3
1 1 2 2 CN067 250V~ (BLK) 3 3
Closed end connector
1 1 2 2
RY004
3
CN039 (YEL)
CN104 (YEL)
1 2 3 4 5 6 1 2 3 4 5 6
CN061 (YEL)
1 2 3 4 5 6
A B X Y
Network CN01 1 2 adaptor (WHI) 1 2 (Option)
3 3 2 1 1
U1 U2 CN1 (WHI)
Outdoor unit
1 2 1 2 Remote controller
1 2
1 2 3 4 5 6
TCJ TC2
Option
1 2 3 4 5 6 CN02 1 2 3 4 5 6 (YEL)
Line Filter
U1 U2
CN060 (WHI)
Fan drive
Sub P.C. board MCC-1520
Power supply Single phase 220-240V 50Hz 220V 60Hz
CN032 (WHI)
TA
CN02 (BLU)
1 1 2 2 MCC-1401
1 2 3 4 5 6 CN01 1 2 3 4 5 6 (WHI)
TR
CN03 (RED)
1.
indicates the terminal block, letter at inside indicates the terminal number. 2. A dotted line and broken line indicate the wiring at site. 3. indicates the control P.C. board.
Symbol FM RC TR LM TA TC1,TC2,TCJ RY001 RY002 RY004 RY005~007 FS DM PMV
Parts name Fan motor Running capacitor Transformer Louver motor Indoor temp sensor Temp sensor Louver control relay Drain control relay Heater control relay Fan motor control relay Float switch Drain pump motor Pulse Motor Valve
TC1
Filter
2-1-2. 2-way Air Discharge Cassette Type
1 2 RED 3 4 5 6 7
Model: MMU-AP0071WH, AP0091WH, AP0121WH, AP0151WH, AP0181WH, MMU-AP0241WH, AP0271WH, AP0301WH, AP0481WH
FM
WHI
1 2 3 4 5 6 7
YEL
BLU
BLK
ORN
1 2 3 1 2 3
H
M
L
FS
2 1 2 1
2 1 2 1
DP
LM
6 4 3 1 2 5 6 4 3 1 2 5 FS
1 2 3 (BLU) 1 2 3 (GRN) 1 2 3 (RED) 1 2 3 CN068 1 2 3 CN033 1 2 3 CN030
FAN 9 8 7 6 5 4 3 2 1 CN083(WHI) 9 8 7 6 5 4 3 2 1
Color indication
PMV LM
RED
RC
DM
PMV
1 2 3 4 5 6 (BLU) 1 2 3 4 5 6 CN082
UL
RY007 CN301 (BLK)
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
RY002
RY001
RY006
Heater
1
CN304 (GRY) 2
RY005
3 3 1 1 2 2 CN067 Fuse (BLK) T5.0A 3 3
16 CN066 1 (WHI) 2
Power supply circuit CN044 CN040 CN041 (BRW) (BLU) (BLU)
1 2 1 2
WHI
RED
TR Flow selector unit earth screw
1 2 1 2
1 2 3 1 3
1 1 2 2
CN101 (BLK)
1 2
CN100 (BRW)
1 1 2 2 3 3
CN080 (GRN)
1 2 PNL 3
CN073 (RED)
1 EXCT 2
CN070 (WHI)
1 1 Filter 2 2
CN081 (BLK)
1 2 3 4 5
1 2 3 4 5
1 2 3 1 2 3
Network CN01 1 2 adaptor (WHI) 1 2 (Option)
1 1 2 2
BLK
BLK
BLU
BLU
WHI
U1 U2
1 2 3 4 5 6 1 2 3 4 5 6
CN061 (YEL)
1 2 3 4 5 6
A B X Y AI-NET central control terminal
Power supply Single phase 220-240V 50Hz 220V 60Hz
CN060 (WHI)
1 2
1 2 3 4 5 6
Fan drive
CN03 (RED)
Sub P.C. board MCC-1520
1 2 3 4 5 6 CN01 1 2 3 4 5 6 (WHI)
Network adaptor P.C. board
TR
3 2 1 CN02 3 2 1 (BLU)
U1 U2 CN1 (WHI)
Outdoor unit
CN032 (WHI)
TCJ
TC1
Option
MCC-1401
Line Filter
BLU
CN075 (WHI)
CN074 (WHI)
TA
1 2 3 4 5 6 CN02 1 2 3 4 5 6 (YEL) BLU
Indoor unit Earth screw R(L) S(N)
CN050 (WHI)
BLU
Closed end connector
CN102 (RED)
Indoor control P.C. board
1 1
CN309 (YEL) 2 2
RED
1 1 2 2
RY004
3
AC IN
CN104 (YEL)
1 2 1 2 Remote controller
1.
indicates the terminal block, letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site. 3.
indicates the control P.C. board.
Symbol FM RC TR LM TA TC1,TCJ RY001 RY002 RY004 RY005~007 FS DM PMV
Parts name Fan motor Running capacitor Power transformer Louver motor Indoor temp sensor Temp sensor Louver motor control relay Drain pump control relay Heater control relay Fan motor control relay Float switch Drain pump motor Pulse Motor Valve
2-1-3. 1-way Air Discharge Cassette Type (Compact type)
FM
1 2 3 4 5 6
Model: MMU-AP0071YH, AP0091YH, AP0121YH
1 2 3 4 5 6
RC
1 PMV
LM 3 4 5 6
DM 1 2 1 2
H
M
L
LM
DM
RED BLK ORN BLU YEL FAN 7 5 3 1 CN083 9 (WHI) 9 7 5 3 1
CN068 1 (BLU) 1
FS
1 1
3 3
6 4 3 1 2 5 6 4 3 1 2 5
FS
3 CN033 3 (GRN)
1 1
PMV 1 2 3 4 5 6 CN082 1 2 3 4 5 6 (BLU)
3 CN030 3 (RED)
UL
RY007 P301 BLK
RY002 RY004
RY001
RY006
1 (GRY) CN304
3
RY005
1 1
Control P.C. board for Indoor unit MCC-1403
(YEL) CN309
3 3 AC IN 1 1
FUSE (BLK) CN067
Power supply circuit
BLU
CN050 (WHI)
1 2 3 RC 1 3
TR
Network adapter (Option)
CN01(WHI)
1 2 1 2
Flow selector unit earth screw
CN074 1 (WHI) 1
1 2 3 4 5
1 2 1 2 3 3 2 1 1
3 3
1 2 3 4 5 6 1 2 3 4 5 6
CN101 (BLK)
1 1 2 2
CN100 (BRW)
1 1 2 3 3
CN080 (GRN)
1 2 PNL 3
CN073 (RED)
1 EXCT 2
CN070 (WHI)
1 2
CN081 (BLK)
1 2 3 4 5
U1 U2
A
B
X Y
U1 U2 Outdoor unit
1. 1 2 1 2 CN1
Remote controller
CN060 (WHI)
1 2 3 4 5 6
1 2
1 2 3 4 5 6
Fan drive
Option
Sub P.C. board MCC-1520
TR
1 2 1 2
R(L) S(N)
CN032 (WHI)
1 2 3 4 5 6 CN01 1 2 3 4 5 6 (WHI)
CN02 (BLU) CN03(RED)
Power supply single phase 220-240V 50Hz 220V 60Hz
1 1 2 2
1 2 3 4 5 6 CN02 1 2 3 4 5 6 (YEL)
Line Filter Closed-end connector
CN102 (RED)
CN061 (YEL)
CN075 (WHI)
BLK
1 2 1 2
EMG
CN041 (BLU)
BLK
CN040 (BLU)
BLU
17
CN066 (WHI) 1 2 CN044 (BRW) 1 2
Indoor unit earth screw
1 1 2 2
T5.0A 250V~
3 3
MCC-1401
indicates the terminal bolock, letter. Letter at inside indicates the terminal number. 2. A dotted line and broken line indicate the wiring at side. 3. indicates the control P.C. board.
TA
CN104 (YEL)
Symbol FM RC TR LM TA TC1,TC2,TCJ RY001 RY002 RY005~007 FS DM PMV
TCJ
TC2
TC1
Filter
Color indication RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
Parts name Fan motor Running capacitor Transformer Louver motor Indoor temp sensor Temp sensor Louver control relay Drain control relay Fan motor control relay Float switch Drain pump motor Pulse motor valve
Model: MMU-AP0151SH, AP0181SH, AP0241SH
FM
1 2 3 4 5 6
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY: GRAY PNK : PINK ORN: ORANGE BRN : BRWN GRN: GREEN
PMV
FM
CN68 (BLU) 1 1 DP
CN334 5 4 1 (WHI) 5 4 3 2 1
RY302
CN304 (GRY) RED WHI
CN67 (BLK)
TR 1 1 2 3 3
WHI
Power supply single phase 220-240V 50Hz 220V 60Hz
5 CN333 5 (WHI)
1 2 3 4 5 6 CN82 1 2 3 4 5 6 (BLU)
RY303
1 1 3 3
A B
Outdoor unit Wired remote controller
BLK
CN01 CN02 (WHI) (BLU) CN03 (RED)
MCC-1401 1 2 1 2 CN001(WHI)
Adapter for wireless remote controller
AI-NET
1 2 1 2
X Y
Network adapter (Option)
BLU BLK
BLK
FS
1 2 3 4 5 CN33 1 2 3 4 5 (WHI)
1 2 1 2
1 2
1 2
CN112 (WHI)
CN111 (WHI)
CN110 (WHI)
Fuse T3.15A 250V~
3
18 U1 U2 A B
U1 U2
1 2 1 2
WHI
WHI Closed-end connector
R(L) S(N)
3 3
CN71
(CHK)
CN72
(DISP)
DC20V DC15V DC12V DC7V
Power supply circuit
Fuse T6.3A 250V~
1 2
CN66 (WHI)
1 2 1 2
CN40 (BLU)
1 1 2 3 3
CN41 (BLU)
Control P.C. board for indoor unit MCC-1402
CN309 (YEL) 1 1
3 3
CN50 (WHI)
CN061 (YEL)
CN32 (WHI)
CN60 (WHI)
CN81 (BLK)
CN20 (BLU)
1 2 3 4 5
1 2 3 4 5 6
1 2 Fan drive
1 2 3 4 5 6
1 2 3 4 5
1 2 3 4 5
T10
1.
1 3 1 2 3
Option
indicates the terminal bolock letter. Letter at inside indicates the terminal number. 2. A dotted line and broken line indicate the wiring at side 3. indicates a control P.C. board.
GRL
CN34 (RED)
CN104 (YEL)
1 1 2 2
CN102 (RED)
1 1 2 2
CN101 (BLK)
1 1 2 2
CN100 (BRW)
P301
BLK BLU
Indoor unit earth screw
1 1
1
BLK
RED
1 2 3 4 5 1 2 3 4 5
Motor drive circuit
3 3
Flow selector unit earth screw
LM
High ceiling setup 6 4 3 1 2 5 6 4 3 1 2 5
TA
TCJ
TC2
1 1 3 3
CN80 (GRN)
1 2 PNL 3
CN73 (RED)
1 EXCT 2
CN70 (WHI)
1 2
Filter
TC1
2-1-4. 1-way Air Discharge Cassette Type
Color indication
Parts name Fan motor Indoor temp sensor Temp sensor Temp sensor Temp sensor Louver motor Drain pump motor Float switsh Drain control relay Pulse motor valve Transformer
Model: MMU-AP0152SH, AP0182SH, AP0242SH
Symbol FM TA TC1 TCJ TC2 LM DP FS RY302 PMV TR
6 4 3 1 2 5 6 4 3 1 2 5
1 2 3 1 2 3 CN68 (BLU)
1 1 2 2 3 3
DM
CN333 1 (WHI) 1
5 4 2 1 5 4 3 2 1
1 1
WHI 1 3 1 2 2
3 1 CN34 3 2 1 (RED)
CN33
1 2 3 4 5 (WHI)
Indoor control P.C. board ~
Fuse T3.15A
+
250V~
250V~
3 3
BLK
1 2 3 4 5 6 CN82 1 2 3 4 5 6 (BLU)
Motor drive circuit
Fuse T6.3A
CN67 (BLK) 2 2
5 5
CN334 (WHI)
RY302
1 CN304 (GRY) 2 3 RED
3 3
FS
~
Power supply circuit
DC20V DC15V DC12V DC7V
P301
WHI
CN44 1 (BRW) 2
R(L) S(N)
Closed end connector
Flow selector unit earth screw
Earth screw
CN40 (BLU)
CN41 (BLU)
1 2 1 2
1 2 3 1 2 3
BLU BLU
Indoor unit
WHI
Indoor unit power supply Single phase 220-240V 50Hz 220V 60Hz
CN50 (WHI)
CN309 (YEL)
1 2 3 1 2 3
TR
U1 U2
A B BLK
WHI
Outdoor unit
BLK CN1 (WHI)
T10 1 2 3 4 5 6
CN32 (WHI)
CN60 (WHI)
CN81 (BLK)
1 2
1 2 3 4 5 6
1 2 3 4 5
(Fan drive)
(Signal output)
WHI
Network CN01 1 2 adaptor (WHI) 1 2 (Option)
3 3 2 2 1 1
WHI
U1 U2
1 2 3 4 5
CN61 (YEL)
1 1 2 2
CN102 (RED)
1 1 2 2
CN101 (BLK)
1 1 2 2
CN100 (BRN)
1 1 2 2 3 3
CN80 (GRN)
1 2 PNL 3
CN73 (RED)
1 EXCT 2
CN20 CN70 (BLU) (WHI)
1 2 3 4 5
BLK
Reactor
RED
BLK
19
CN66 1 (WHI) 2
CN104 (YEL)
CN02 (BLU)
Network adaptor P.C. board
1 2 CN03 1 2 (RED)
BLK
X Y
CN001 (WHI)
1 2 1 2
1 2 1 2
Wired remote controller
Adaputor for wired remote controller
1.
indicates the terminal block, letter at inside indicates the terminal number. 2. A dotted line and broken line indicate the wiring at site. 3. indicates the control P.C. board.
Color identification RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BRW : BROWN
Symbol FM TA TC1,TC2,TCJ DM FS RY302 PMV
BLK GRY PNK ORN GRN
: BLACK : GRAY : PINK : ORANGE : GREEN
Parts name Fan motor Indoor temp sensor Indoor temp sensor Drain pump motor Float switch Drain pump control relay Pulse Motor Valve
1 2
TA TCJ TC2
TC1
2-1-5. Concealed Duct Standard Type
PMV
1 1
Model: MMD-AP0071BH, AP0091BH, AP0121BH, AP0151BH, AP0181BH, AP0241BH MMD-AP0271BH, AP0301BH, AP0361BH, AP0481BH, AP0561BH
FM
5 5 4 4
8
(BLK)
RY007
P301
1
CN304 (GRY) 2
H
RY004
M
L
DP
LM
1 2 3 (BLU) 1 2 3 (GRN) 1 2 3 CN068 1 2 3 CN033
1 2 3 1 2 3 FS CN030 (RED)
UL
RY002
RY006
1 2 1 2
1 2 1 2
1 2 1 2
TC1
1 2 3 CN100 1 2 3 (BRN)
CN104 CN102 CN101 (YEL) (RED) (BLK)
RY001
3
1 1 CN309 2 2 (YEL) 3 3
Power supply circuit
CN066 (WHI) CN044 CN040 CN041 (BRW) (BLU) (BLU)
1 2
20
TR
1 2 1 2
EMG
OC
CN050 (WHI)
1 2 3 1 3
1 2 3 1 2 3
Network adaptor (Option) MCC-1401 CN01 1 2 (WHI) 1 2
A B
U1 U2 CN1 (WHI)
CN02 (BLU)
Outdoor unit
CN081 (BLK)
1 2 3 4 5
CN082 (BLU)
6 5 4 3 2 1
WHI
43F1
43F1 3
RC BLU
F1
WHI RED
1 2 3 4 1 2 3 4 GRY FM
F2
F3 BLK
WHI RED GRY
Closed end connector
A
5
4
CN032 (WHI)
CN060 (WHI)
6 5 4 3 2 1
5 2 1 3 4 6
5 2 1 3 4 6
PMV
1 2 3 4 5 6 CN02 1 2 3 4 5 6 (YEL)
F4
1. indicates the terminal block, letter at inside indicates the terminal number. 2. A dotted line and broken line indicate the wiring at site. 3. indicates the control P.C. board. 4. When attaching a drain pump, exchange CN030 connector with the connector of the float switch. 5. A part is connected to the terminal block. When exchanging to the outside static pressure necessary at the local site, check the terminal No. and lead color of the fan motor in the below diagram, and then exchange the lead wire indicated by the arrow mark ( ).
BRN
RED RED 6
YEL
Power supply Single phase 220-240V 50Hz 220V 60Hz
1 Filter 2
TR
X Y
Remote controller
Indoor unit Earth screw
CN070 (WHI)
1 2 3 4 5 6 1 2 3 4 5 6 1 2 1 2 3 4 5 6 Option 1 2 3 4 5 6 T10 Fan drive
1 2 CN03 1 2 (RED)
1 2 1 2
Closed end connector
S(N)
1 EXCT 2
1 2 3 4 5 6 CN01 1 2 3 4 5 6 (WHI)
ORN
WHI
F
CN073 (RED)
Sub P.C. board MCC-1520
3 3 2 1 1
RED
CN075 CN061 (WHI) (YEL)
CN074 (WHI)
1 2 3 4 5
RC
U1 U2
Flow selector unit earth screw
T10A,250V~
1 2 PNL 3
Fuse T5.0A
1 2
RED
CN080 (GRN)
Indoor control P.C. board RY005
CN067 (BLK)
1 1 2 2 3 3
R(L)
TC2
RED
7
43F1
FAN 9 8 7 6 4 2 CN083(WHI) 9 8 7 6 5 4 3 2 1
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
TCJ
Wired for MMD-AP0481 only (BRN Wire)
BLU ORN BRN
BLK WHI GRY RED
Motor over heating protection switch
49F
Sold separately
Symbol FM RC TR TA TC1,TC2,TCJ RY005~007 RY001 RY002 PMV F 43F1 DM FS
Parts name Fan motor Running capacitor Transformer Indoor temp sensor Temp sensor Fan motor control relay Louver motor control relay Drain control relay Pulse Motor Valve Fuse Fan motor control relay Drain pump motor Float switch
2-1-6. Concealed Duct High Static Pressure Type
WHI
Color indication
TA
DP
Model: MMD-AP0181H, AP0241H, AP0271H, AP0361H, AP0481H
(Option) Spark killer
1 2 3 4 5 1 2 3 4 5 FS
1 1 2 2 3 3
DM
CN304 1 (GRY) 2
RED WHI
BLK
RY303
Indoor control P.C. board ~
Earth screw
21
RED WHI
R(L) S(N)
CN66 (WHI)
BLU 1 1 BLU
CN40 (BLU)
2 2
Closed end terminal
Power supply single phase 200-240V 50Hz 200V 60Hz
Fuse T6.3A 250V~ P301
1 2
Flow selector unit earth screw
Indoor unit
BLK
1 1 2 BLK 3 3
Fuse T3.15A
+
Power supply circuit
~
CN41 (BLU)
CN309 (YEL)
1 2 3 1 2 3
CN50 (WHI)
CN61 (YEL)
1 2 3 4 5
TR
U1 U2 A B BLK
WHI
Outdoor unit
BLK CN1 (WHI)
1 2 1 2
Wired remote controller
WHI
CN60 (WHI)
CN81 (BLK)
1 2 3 4 5 6
1 2
1 2 3 4 5 6
1 2 3 4 5
T10
Fandrive
Option
BLK
1 1 2 2
CN101 (BLK)
1 1 2 2
CN100 (BRW)
1 1 2 2 3 3
TA TCJ
CN80 (GRN)
1 2 PNL 3
CN73 (RED)
1 EXCT 2
CN70 (WHI)
1 FILTER 2
TC1
CN20 (BLU)
1 2 3 4 5
Color identification
Network adaptor P.C. board
BLK GRY PNK ORN GRN
: BLACK : GRAY : PINK : ORANGE : GREEN
1 2 CN03 1 2 (RED) X Y
indicates the terminal block, letter at inside indicates the terminal number. 2. A dotted line and broken line indicate the wiring at site. Adaptor for wireless 3. indicates the control P.C. board. remote controller
CN102 (RED)
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BRW : BROWN
CN001 (WHI)
1 2 1 2
1 1 2 2
GRL
Network CN01 1 2 adaptor (WHI) 1 2 (Option)
CN02 (BLU)
CN104 (YEL)
TC2
DC20V DC15V DC12V DC7V
CN32 (WHI)
3 3 2 2 1 1
WHI
U1 U2
1 3 CN34 1 2 3 (RED)
Motor drive circuit
1 1 3 3
1 2 3 4 5 CN33 1 2 3 4 5 (WHI)
RY302
3 CN67 (BLK) 2 2
1 2 3 4 5 6 CN82 1 2 3 4 5 6 (BLU)
5 4 1 CN334 1 2 3 4 5 CN333 5 4 3 2 1 (WHI) 1 2 3 4 5 (WHI)
CN68 (BLU)
1.
Sold separately
Symbol FM TA TC,TC2,TCJ LM RY302 DM FS
Parts name Fan motor Indoor temp sensor Temp sensor Louver motor Drain control relay Drain pump motor Float switch
2-1-7. Under Ceiling Type
LM
6 4 3 1 2 5 6 4 3 1 2 5
Model: MMC-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481H
PMV
FM
1 2 3 1 2 3 CN334 5 4 2 1 (WHI) 5 4 3 2 1 1
CN68 (BLU)
CN333 1 (WHI) 1
3 3
TA
TCJ
TC2
TC1
1 1 2 2
1 1 2 2
1 1 2 2
1 3 1 2 3
6 4 3 1 2 5 6 4 3 1 2 5 5 5
RY302
1 2 3 4 5 6 1 2 3 4 5 6
1 2 3 4 5
CN82 (BLU)
CN33 (WHI)
1 1
3 3
CN34 (RED)
CN104 CN102 CN101 (YEL) (RED) (BLK)
3 Motor drive circuit
1 1 3 3 CN304 (GRY) 1 1
WHI
3 3 CN67 (BLK)
CN080 (GRN)
RY303
LM
RED
CN100 (BRW) CN103 (GRN)
FUSE
FUSE
T6.3A 250V~
T3.15A 250V~
Control P.C. board for Indoor unit MCC-1402 Power supply circuit
DC20V DC15V DC12V DC7V
1 2 1 2 3
CN73 (RED)
1 2 EXCT
CN70 (WHI)
1 2
22
P301 BLK Flow selector unit earth screw
1 2 CN66 (WHI)
RED Closed-end connector WHI
CN40 (BLU)
CN41 (BLU)
1 2 1 2
1 2 3 1 3
1 1
3 CN309 3 (YEL)
CN50 (WHI)
CN61 (YEL)
1 2 3 4 5
1 2 3 4 5 6
CN32 (WHI)
CN60 (WHI)
CN81 (BLK)
CN20 (BLU)
1 2
1 2 3 4 5 6
1 2 3 4 5
1 2 3 4 5
Fandrive
Option
BLU BLU
R(L) S(N)
BLK BLK
Power supply single phase 220-240V 50Hz 220V 60Hz
GRY
TR
GRY
Indoor unit
BLK
U1 U2
A
B
X
Y
Earth screw
WHI
3 3 2 1 1
1 2 1 2
CN03(RED) WHI
U1 U2 Outdoor unit
BLK WHI
1 2 1 2 CN1 (WHI)
BLK
1 2 1 2 CN001 (WHI)
Wired remote Adaptor for controller wireless remote controller
1.
CN01(WHI) CN02 (BLU)
1 2 1 2
Network adaptor (Option) MCC-1401
Color indication RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
indicates the terminal bolock. Letter at inside indicates the terminal number. 2. A dotted line and broken line indicate the wiring at side. 3. indicates the control P.C. board. Symbol FM TA TC1,TC2,TCJ PMV LM RY303
Parts name Fan motor Indoor temp sensor Temp sensor Pulse motor valve Louver motor Louver control relay
2-1-8. High Wall Type
PMV
1 1
Model: MMK-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241H
FM
5 5 4 4
BLK
RED
5 4 3 2 1
S HBS CN22
1 2 3 4 5
6 5 4 3 2 1 6 5 4 3 2 1
6 5 4 3 6 5 4 3
1 1
CN82 (BLU)
6 5 4 3 2 6 5 4 3 2 1
CN33 (WHI)
CN210 (WHI)
CN44 CN40 (BRW) (BLU)
DC 15V
1 2 3 4 5 1 2 3 4 5
1 2 3 4 5
Flow selector unit (Sold separately)
Power supply circuit
CN213 (WHI)
Infrared rays receive and indication parts (MCC-861)
(MCC-1510) Control P.C.board for indoor unit
(BRW)
CN101 (BLU)
BLK 1 1 2 2 BLK
Heat exchanger sensor (TC2)
CN103 (GRN)
1 2
CN102 (YEL)
BLK 1 1 BLK 2 2
Heat exchanger sensor (TCJ)
BLK 1 1 BLK 2 2
Thermo sensor (TA)
CN104 CN80 (WHI) (GRN)
CN61 (YEL)
CN60 (WHI)
1 2
1 2 3 4 5 6 1 2 3 4 5 6
1 2 3 4 5 6
1 2 3
Option
PNL/EMG
1 2 3 4
HA
BLK 3 3 2 WHI 1 1
Heat exchanger sensor (TC1)
CN32 (WHI) Fan drive
BLU 1 1 2 2 BLU
BLK 1 1 2 BLK 3 3
DC 7V
1 2 3 4 5 6 7 8 9 10 1 2 3 4 7 8 9 10
9 7 6 5 4 3 2 11 10 9 8 7 6 5 4 3 2 1
CN41 (BLU)
DC 0V CN100 DC 12V
GRY ORN RED BLU
3 3
WHI BRW YEL GRY PNK
RED
CN309 1 (YEL) 1 GRN & YEL
WHI
CN81 (BLK)
WHI BRW YEL
5 CN67 (BLK)
GRN & YEL
23
GRN & YEL
Outdoor unit 1 2
F301 Fuse T3. 15A 250V~
1 1
WHI 3 3
Power Supply Single phase 220-240V 50Hz 220V 60Hz
indicates the terminal block, letter at inside indicates the terminal number. 2. A dotted line and broken line indicate the wiring at site. 3. indicates the control P.C. board.
F
CN50 (WHI) Heat exchanger
1.
Fan motor YEL YEL YEL YEL WHI
:
Louver motor
Pulse motor valve
RED
GRN
BROWN RED WHITE YELLOW BLUE BLACK GRAY PINK ORANGE GREEN & YELLOW GREEN
BLU YEL WHI BLK
: : : : : : : : : :
RED BRW BLU ORN YEL WHI
BRW RED WHI YEL BLU BLK GRY PNK ORN GRN & YEL
TF
WHI
BLK
1 2 1 2 CN1(WHI)
Wierd remote controller (Sold separately)
Model: MMK-AP0072H, AP0092H, AP0122H
Color identification
RC
6 4 3 1 2 5 6 4 3 1 2 5 RED BLK ORN BLU YEL FAN 7 5 3 1 CN083 9 (WHI) 9 7 5 3 1 H
M
L
CN068 (BLU) 1
DP 3
LM 1
PMV 1 2 3 4 5 6 CN082 1 2 3 4 5 6 (BLU)
CN033 3 (GRN)
UL
RY007 P301 (BLK)
RY002 RY004 (GRY) CN304
3 3
RY005
1 1
AC IN
RED
Control P.C. board for Indoor unit MCC-1403
(YEL) CN309
3 3 1 1
1 1 2 2
CN102 (RED)
1 1 2 2
CN101 (BLK)
1 1 2 2
CN100 (BRN)
1 1 2 2
CN080 (GRN)
1 2 PNL 3
CN073 (RED)
1 EXCT 2
CN070 (WHI)
1 2
CN081 (BLK)
1 2 3 4 5
FUSE
24
CN066 (WHI) 1 1 2 2 Power supply circuit CN050 (WHI)
1 2 3 RC 1 3
TR
Network adapter (Option)
3 3 2 1 1
CN032 (WHI)
CN060 (WHI)
3 3
1 2 3 4 5 6 1 2 3 4 5 6
1 2 3 4 5 6 T10
1 2
1 2 3 4 5 6
Fan drive
Option
1 2 3 4 5 6 1 2 3 4 5 6
CN02 (YEL)
Sub P.C. board MCC-1520
CN01(WHI)
Flow selector unit earth screw Line filter
CN02 (BLU)
1 2 3 4 5 6 1 2 3 4 5 6
CN01 (WHI)
CN03(RED)
U1 U2
A
B
X Y
U1 U2 Outdoor unit
1 2 1 2 CN1
TR
1 2 1 2
R(L) S(N) Power supply single phase 220-240V 50Hz 220V 60Hz
CN074 1 (WHI) 1
1 2 3 4 5
1 2 1 2
CN061 (YEL)
CN075 (WHI)
BLK
BLU
BLU
1 2 1 2
CN041 (BLU)
BLK
CN040 (BLU)
Indoor unit earth screw
TCJ
TC2
TC1
T5.0A 250V~
3 3 WHI CN067 (BLK)
RED Closed-end connector WHI
TA
CN104 (YEL) RY001
RY006
1 1
FS 1 3 CN030 1 2 3 (RED)
MCC-1401
1. Remote controller
indicates the terminal block. Letter at inside indicates the terminal number. 2. A dotted line and broken line indicate the wiring at side. 3. indicates the control P.C. board.
Symbol FM RC TR TA TC1,TC2,TCJ RY001 RY002 RY004 RY005~007 PMV
Filter
Color indication RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
Parts name Fan motor Running capacitor Transformer Indoor temp sensor Temp sensor Louver control relay Drain control relay Heater control relay Fan motor control relay Pulse motor valve
2-1-9. Floor Standing Cabinet Type
FM
PMV
2 3 4 5 6
Model: MML-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241H
2 3 4 5 6
WHI RED
RC
2 4 5 6 3
FM WHI
GRN
RED
PMV
2 4 5 6 3
6 4 3 1 2 5 6 4 3 1 2 5
RC
RED BLK ORN BLU YEL FAN 7 5 3 1 CN083 9 (WHI) 9 7 5 3 1
RED BLK ORN BLU YEL FAN 7 5 3 1 CN068 1 CN083 9 (WHI) 9 (BLU) 1 7 5 3 1 H
For AP0071BH,AP0091BH,AP0121BH
M
L
3 3
1 1
3 CN033 3 (GRN)
1 3 1 2 3 CN030 (RED)
UL
RY007 R301 (BLK)
RY002 RY004
RY006
1 3
(GRY) CN304 RY005
1 1 3 3 AC IN 1 1
RY001
Control P.C. board for undoor unit MCC-1403
(YEL) CN309 FUSE
3 3
1 2 1 2
1 2 3 4 5 6 1 2 3 4 5 6 PMV 1 1 2 2
CN102 (RED)
1 1 2 2
CN101 (BLK)
1 1 2 2
CN100 (BRW)
1 1 2 3 3
CN080 (GRN)
1 2 PNL 3
CN073 (RED)
1 EXCT 2
CN070 (WHI)
1 2
CN081 (BLK)
1 2 3 4 5
T5.0A 250V~
(BLK) CN067
CN066 (WHI) CN044 (BRW)
EMG
25
CN082 (BLU) CN104 (YEL)
Power supply circuit
CN040 (BLU)
CN041 (BLU)
CN050 (WHI)
1 2 1 2
1 2 3 1 3
1 2 3 4 5
CN075 (WHI) CN074 1 (WHI) 1
3 3
1 2 3 4 5 6 1 2 3 4 5 6
CN061 (YEL)
1 2 3 4 5 6
CN032 (WHI)
CN060 (WHI)
1 2
1 2 3 4 5 6
Fan drive
Option
Sub P.C. board MCC-1520
WHI
RED
1 2 3 4 5 6 CN01 1 2 3 4 5 6 (WHI)
1 2 1 2
TR
Network adaptor (Option)
TR
CN01(WHI)
Flow selector unit earth screw RED
U1 U2
R(L) S(N) Power supply single phase 220-240V 50Hz 220V 60Hz
B
X
Y
3 3 2 1 1
CN02 (BLU)
1 1 2 2 CN03 (RED)
CN03(RED)
Closed-end connector
MCC-1401
WHI
Indoor unit earth screw
A
U1 U2
1 2 1 2 Outdoor unit CN1 Remote controller
1.
indicates the terminal block. Letter at inside indicates the terminal number. 2. A dotted line and broken line indicate the wiring at side. 3. indicates the control P.C. board.
Color indication RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
Symbol FM RC TR TA TC1,TC2,TCJ RY001 RY002 RY004 RY005~007 PMV
TCJ
TC2
Filter
1 2 3 4 5 6 CN02 1 2 3 4 5 6 (YEL) 1 2 1 2
TA
Parts name Fan motor Running capacitor Transformer Indoor temp sensor Temp sensor Louver control relay Drain control relay Heater control reley Fan motor control relay Pulse motor valve
TC1
2-1-10. Floor Standing Concealed Type
FM
1 3 2 4 5 6
Model: MML-AP0071BH, AP0091BH, AP0121BH, AP0151BH, AP0181BH, AP0241BH
GRN
1 3 2 4 5 6
FM
BRW
3 4 5 6 7
PMV
LM 2 1 2 1
M
H
L
6 4 3 1 2 5 6 4 3 1 2 5 LM
RED BLK ORN BLU YEL FAN 7 5 3 1 CN083 9 (WHI) 9 7 5 3 1
CN068 (BLU) 1
DP
1 1
3
FS
3 CN033 3 (GRN)
PMV 1 2 3 4 5 6 CN082 1 2 3 4 5 6 (BLU)
1 3 CN030 1 2 3 (RED)
UL
RY007 P301 (BLK)
RY002 RY004
RY001
RY006
1 (GRY) CN304
3
RY005
1 1
FUSE
CN066 (WHI) 1 2 CN044 (BRW) 1 2
Power supply circuit CN050 (WHI)
1 2 3 RC 1 3
CN075 (WHI) CN074 1 (WHI) 1
1 2 3 4 5
BLK
BLU
1 2 1 2
CN041 (BLU)
BLK
CN040 (BLU)
BLU
WHI
26
RED
(BLK) CN067
EMG
1 2 1 2 TR
Indoor unit earth screw
CN102 (RED)
1 1 2 2
CN101 (BLK)
1 1 2 2
Network adaptor (Option)
3 3 2 1 1
Line filter
1 2 3 4 5 6 1 2 3 4 5 6
1 2 3 4 5 6
CN02 (BLU)
TCJ
TC2
1 1
TC1
3 3 1 2 PNL 3
CN073 (RED)
1 EXCT 2
CN070 (WHI)
1 Filter 2
CN081 (BLK)
1 2 3 4 5
CN032 (WHI)
CN060 (WHI)
1 2
1 2 3 4 5 6
Fan drive
Option
1 2 3 4 5 6 CN02 (YEL) 1 2 3 4 5 6
Sub P.C. board MCC-1520
CN01(WHI)
1 2 1 2
3 3
CN061 (YEL)
TA
CN080 (GRN)
T5.0A 250V~
3 3
Flow selector unit earth screw
1 1 2 2
CN100 (BRW)
Control P.C. board for Indoor unit MCC-1403
(YEL) CN309
3 3 AC IN 1 1
CN104 (YEL)
1 2 3 4 5 6 CN01 1 2 3 4 5 6 (WHI)
Color indication RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
CN03(RED) Closed-end connector
U1 U2
A
B
Power supply single phase 220-240V 50Hz 220V 60Hz
X Y
U1 U2 Outdoor unit
1 2 1 2 CN1
TR
1 2 1 2
R(L) S(N)
MCC-1401
Remote controller
1.
indicates the terminal block, letter. Letter at inside indicates the terminal number. 2. A dotted line and broken line indicate the wiring at side. 3. indicates the control P.C. board.
Symbol FM RC TR LM TA TC1,TC2,TCJ RY001 RY002 RY005~007 PMV
Parts name Fan motor Running capacitor Transformer Louver motor Indoor temp sensor Temp sensor Louver control relay Drain control relay Fan motor control relay Pulse motor valve
2-1-11. Floor Standing Type
RC 3 4 5 6 7 8
Model: MMF-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481H, AP0561H
1 1
1 3
: RED : WHITE : YELLOW : BLUE : BLACK : GRAY : PINK : ORANGE : BRWN : GREEN
5 4 1 CN334 5 4 3 2 1 (WHI)
1 1
3 3
5 CN333 5 (WHI)
1 3 1 2 3
(External static pressure setup)
1 2 3 4 5 6 CN82 1 2 3 4 5 6 (BLU)
Drain pump type ("SPH" Type) CN68 (BLU) 1 1
CN34 (RED)
CN33
1 2 1 2
1 2
1 2
CN112 (WHI)
CN111 (WHI)
CN110 (WHI)
1 2 3 4 5 (WHI)
CN71
(CHK)
CN72
(DISP)
FS
1 3 1 2 3
RY302
DM 3 3
Motor drive circuit
1 CN304 (GRY)
3
RED WHI
Fuse T3.15A 250V~
Fuse T6.3A 250V~ 1 1
Power supply circuit
3 3
27
CN67 (BLK) P301
BLK 1 2
Flow Selector unit
Indoor unit
R(L) S(N)
Earth screw
Earth screw
Power supply 220-240V~, 50Hz 220V~, 60Hz
CN309 (YEL)
1 2 1 2
1 2 3 1 3
1
3
1. U1 U2
U1 U2
A
A
B
Outdoor unit
Wired remote controller
CN102 (RED)
1 1 2 2
CN101 (BLK)
1 1 2 2
TC2
1 1 3 3
CN73 (RED)
1 EXCT 2
CN70 (WHI)
1 2
CN60 (WHI)
CN81 (BLK)
CN20 (BLU)
1 2 3 4 5
1 2 3 4 5 6
1 2 Fan drive
1 2 3 4 5 6 Option
1 2 3 4 5
1 2 3 4 5
Parts name Fan motor Indoor temp sensor Temp sensor Drain control relay Pulse motor valve Drain pump motor Float switch
TCJ
1 2 PNL 3
CN32 (WHI)
Symbol FM TA TC1,TC2,TCJ RY302 PMV DM FS
TA
CN80 (GRN)
CN61 (YEL)
indicates the terminal bolock. Letter at inside indicates the terminal number. 2. A dotted line and broken line indicate the wiring at side 3. indicate a control P.C. board.
B
1 1 2 2
CN50 (WHI)
BLK
CN41 (BLU)
BLU
RED
CN40 (BLU)
BLU BLK
WHI
Closed-end connector
CN66 (WHI)
CN44 1 (BRW) 2
CN104 (YEL)
CN100 (BRW)
Control P.C. board for undoor unit MCC-1402
DC20V DC15V DC12V DC7V
CN34 (RED)
TC1
2-1-12. Slim Duct Type
6 4 3 1 2 5 6 4 3 1 2 5
Model: MMD-AP0071SPH, AP0091SPH, AP0121SPH, AP0151SPH, AP0181SPH
RED WHI YEL BLU BLK GRY PNK ORN BRN GRN
Drain pump type ("SPH" Type)
FM
CN68 (BLU) Color indication
Non Drain pump type ("SH" Type)
PMV
Non Drain pump type ("SH" Type)
CN311(BLU) SV41
BLU
4 3 2 4 3 2 1
4 3 1 4 3 2 1
4 3 2 1 4 3 2 1
4 3 2 1 4 3 2 1
4 3 2 1 4 3 2 1
5 4 3 2 1 5 4 3 2 1
4 3 2 1 4 3 2 1
CN302 (RED)
CN500 (WHI)
CN501 (RED)
CN508 (RED)
CN509 (BLK)
CN510 (WHI)
CN513 (BLU)
CN512 (BLU)
1 1
3 3
CN306 (WHI)
1 1
3 3
CN308 (BLU) CN502 (WHI) CN503 (PNK)
RY500
1 1
Interface Control P.C. Board MCC-1429
7 7 CR503
RY503
CN504 (WHI) ON
CN522 (BLK)
SW30
3 3 CR502
RY502
CR504
RY504
CN505 (GRN)
1 1
4 3 SV51 BLU 2 2 BLU 1 1 CN312(WHI) BLU 3 3 SV2 BLU 1 1 CN324(RED)BLU 3 3 SV3A BLU 1 1 CN313(YEL) BLU 3 3 SV3B BLU 1 1 CN314(BLK) BLU 3 3 SV3C BLU 1 1 CN322(WHI) BLU 4 4 SV11 BLU 3 3 2 1 CN319(WHI) BLU 1 1 SV12 BLU 3 3
CN507 (YEL)
CN310(WHI)
CR507
RY507
CR508
1 2 3 (Srvice) 4 5 6
RY508
ON 1 2 3 4
ON 1 2 3 4
ON 1 2 3 4
ON 1 2 3 4
SW11
SW12
SW13
SW14
ON 1 2 3 4
ON 1 2 3 4
SW06
SW07
ON 1
ON 1 2 3 4
CN515 (GRN)
ON 1 2 3 4
SW09
SW08
CN516 (RED)
SW10
CN31 CN523 (YEL)
CN800 CR509
CR513
CR514
1 2 3 4 5 6 7 8 9
RY509
RY513
RY514
CN32
D600 D601 D602 D603 D604 SW01
SW02
RY510
1 1 3 3 1 1 3 3 1 1
BLU(BLK)
BLU(BLK)
1 1
YEL
5 4 3 2 1
CR511
CR521
CR519
Accumulator heater
SV 3D
SV 3E
ORN ORN
BLK (PNK)
CN305(RED) 7 7
BLU
3 CN317 4 3 2 1 3 (BLU) 2 1
BLK (PNK)
1 2 3 4 CN323 1 1 2 3 4 (WHI) 1
2 CN321 2 (RED)
BLK BLK BLK BLK
1 1
T6.3A FUSE
5 5
4WV1
CN25 3 (WHI) 3
TO (BLK)
YEL
1 1 2 2 3 3 BLK WHI CM1 RED YEL BLU
BLU
TK1 (BLK) TK2 (BLU)
Interface control P.C. board (I/F) MCC-1429
OCR
L1 L2 L3 N Comp. IPDU No.1 MCC-1502
5 4 3 2 1 5 4 3 2 1
1 2 3 4 5 1 2 3 4 5
CN06 (WHI)
CN18 (RED)
CN26 (BLU)
BLU
RED 3 3
1 1
CN17 (BLK)
IPDU P.C. Board (1) MCC-1502 CN11
W V U
CN10 CN09 CN22 CN23
TL (WHI) BLK
BLK WHI RED
CN03 L1 CN02 L2 CN01 L3
CN15 CN13
CN20 WHI
Reactor
Noise filter P.C. board MCC-1366
Option board
PTC Themistor RED
CN21
BLU
RED
BLU
WHI
CN402 Transformer WHI CN401 RED CN600(WHI) 5 5 4 4 3 3 2 2 1 1
CN01
CN17
CN02
CN18
WHI BLK BLK GRY GRY GRY
CN04 CN20 CN22(WHI) CN23(BLU) 3 3
1 1
Mg-SW 1 2
RED RED
CN19
CN03
1 1
CN25 3 (WHI) 3
L1
U1 U2 U3 U4 U5 U6 Fan IPDU MCC-896 Connecting terminal
Power supply terminal
1 1
BLK
1
MGSW
1 2 3 4 5 1 2 3 4 5
RED OCR 2
3
4
4
5
6
6
A1 A2
3 3
1 1
Parts layout
Power supply for fan MCC-1439
RED
1 1
+ – + – BLK HVC1 HVC2
1 1 CN26 (BLU)
3
Noise filter P.C. board MCC-1366
GRY
3 3
CN21 WHI
TK4 (GRN)
Earth screw
: RED : WHITE : YELLOW : BLUE : BLACK : GRAY : PINK : ORANGE : BRWN : VIOLET
CN504
BLU
Comp1
RED WHI YEL BLU BLK GRY PNK ORN BRN VLT
5 5
CN501 (RED) CN505(RED)
TK3 (BLU)
Comp2
Color indication
1 1
YEL
TE1 (BLK)
1 2 3 4 CN400 3 1 1 2 3 4 (WHI) CN325 (YEL) BLK BLK Option 3 1 3 1 ORN ORN 3 3
CN503 (WHI)
BLU(BLK) BLU(BLK)
3 3
Power supply P.C. board for FAN MCC-1439
TS2
BLK
T6.3A FUSE
CN500 (WHI)
PNK RED BLU WHI BLK
CR 510
5 4 3 2 1
3 3
CN506(BLK) CN502 (BLU)
1 2 3 4 5
RED WHI BLK GRY
CR 518
5 4 3 2 1
BLU(BLK) BLU(BLK)
BLU
WHI
BLK
5 4 3 2 1
1 1
BLK WHI BLU RED PNK
TS1 (GRY)
BLU(BLK)
4 3 2 1
3 3
TD2 (RED)
3 3
YEL
CN01 (WHI)
RY519
RY521
CN307(WHI)
4-way valve coil Compressor case thermo. Pipe temp. sensor (Inlet) Pipe temp. sensor (Outlet) Heat exchange temp. sensor Air temp. sensor Oil temp. sensor Liquid temp. sensor Case heater, 230V, 26W Fan motor (DC) Low pressure sensor High pressure sensor High pressure switch Magnetic switch Overcurrent relay High voltage capacitor
3 3
– +
W
L1 L2 L3 N
RY517
2-way valve coil
BLU(BLK)
BLK 2 2 BLK 1 1 BLK 2 2 BLK 1 1 BLK 2 2 BLK 1 1 BLK 2 2 BLK 1 1 BLU(BLK) 3 3 1 1
V
FAN IPDU P.C. Board MCC-896, 897
BLU(BLK)
CN511 (GRN)
RY516
Parts name Compressor Pulse motor valve
1 1
TD1 (YEL)
GRY
1 1 T Heater 2
Symbol CM1, CM2 PMV1, PMV2, PMV3 SV2, SV41, SV42, SV51, SV3A, SV3B, SV3C, SV3D, SV3E, SV61, SSV11, SV12 4WV1 COMP1, COMP2 TS1, TS2 TD1, TD2 TE1 TO TK1, TK2, TK3, TK4 TL HEATER1, HEATER2, ACCUM HEATER FM PS PD 63H1, 63H2 MG-SW OCR HVC1, HVC2
3 3
BLU(BLK)
4 3 2 1
T6.3A FUSE CR517
1 1
BLU(BLK)
BLK 2 2 BLK 1 1
CN100 (BLK)
RY511
U 3 3
CN521 (WHI)
SW03
CN802 Flash RY518
CR516
CN30
SW04 SW05 SW06
RED
1 1 Heater 1 CN315(BLU) 3 3 BRW
RY506
BRN
28
CN316(WHI) 3 3 BRW
CN514 (BLK)
CR506
RED
WHI
RED BLK
RED BLK WHI
RED BRN BLU ORN YEL WHI
RED BRN BLU ORN YEL WHI
RED BRN BLU ORN YEL WHI
6 5 4 3 2 1 6 5 4 3 2 1
CN301 (WHI)
3 3
BLU 5 5 BLU
6 5 4 3 2 1 6 5 4 3 2 1
CN300 (WHI)
1 1 BLU
PNK RED BLU WHI BLK
SV42
6 5 4 3 2 1 6 5 4 3 2 1
5
CR500
63H2
BLU
Central remote controller
BLU
63H1
Comp. IPDU No.2 MCC-1502
Power Supply 3phase 380-415V 50Hz
L2 L3 N
RED WHI BLK
BLK WHI CM2 RED YEL BLU
W V U
5 4 3 2 1 5 4 3 2 1
5 4 3 2 1 5 4 3 2 1
CN06 (WHI)
CN18 (RED)
RED
U1 U2 U3 U4
BLU
Option Board
BLK WHI BLU RED PNK
U5 U6
Outdoor unit
Option Board
BLK
U1 U2
Indoor unit
Option Board
YEL YEL
SV61
Option Board
BLK WHI BLU RED PNK
BLU
3 2 1 3 2 1
CN01 CN03 (BLU) (WHI)
PMV3
Option Board
BLK WHI BLU RED PNK
CN309(WHI)
WHI WHI
BLU BLU
2 1 2 1 7
PMV2
Pressure Sensor PD
3 3
IPDU Board (2) MCC-1502
CN11 CN10 CN09 CN22 CN23
CN15 CN13 YEL BLU
1 1
CN17 (BLK)
CN03 L1 CN02 L2 CN01 L3
CN08 WHI
BLK WHI RED
CN07 WHI
GRY Reactor
1. The two-dot chain line indicates wiring at the local site, and the dashed line indicates accessories sold separately and service wires, respectively. 2. , , and indicate the terminal board and the numerals indicate the terminal numbers. 3. indicates P.C. board. * Be sure to fix the electric parts cover surely with two screws. (Otherwise water enters into the box resulting in malfunction.)
2-2. Outdoor Unit
PMV1
U1 U2 U3 U4 U5 U6
Pressure Sensor PS
Model: MMY-MAP0801FT8, MAP1001FT8, MAP1201FT8
–
+ FM
1 2 1 2
Supplied wire (Power supply)
Earth screw
SVD SVD
1 1
29
1 1
3 3
CN01 (RED)
COM SVD SVS SVDD SVSS BRW BLU YEL WHI ORN
1 1
3 3
5 5
7 7
CN10 (WHI)
Control P.C. board MCC-1431 CN02 (GRN)
9 9
Control P.C. board for indoor unit
3 3
CN67 (BLK)
1 2 3 4 5 CN81 1 2 3 4 5 (BLK)
R(L) S(N)
1 2 3 4 5 1 2 3 4 5
Power supply single phase 220-240V 50Hz Supplied wire (Control wiring)
Indoor unit earth screw
2-3. Flow Selector Unit (FS Unit)
Indoor unit
RBM-Y1802FE only RBM-Y2802FE RBM-Y2802FE only only
SVS SVS SVS SVSS SVDD
Model: RBM-Y1122FE, Y1802FE, Y2802FE
Flow Selector unit
3. PARTS RATING 3-1. Indoor Unit 4-way Air Discharge Cassette Type Model
MMU-AP
0091H
0121H
0151H
0181H
Fan motor
0241H
0271H
Drain pump motor
ADP-1409
Float switch
FS-0218-102
TA sensor
Lead wire length : 155mm
TC1 sensor
Ø4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Red)
Pulse motor
EDM-MD12TF-3
Pulse motor valve
EDM-B25YGTF
EDM-B40YGTF
Louver motor (panel) Model
0301H
SWF-230-60-1
MP24GA MMU-AP
0361H
0481H
Fan motor
0561H
SWF-200-90-1
Drain pump motor
ADP-1409
Float switch
FS-0218-102
TA sensor
Lead wire length : 155mm
TC1 sensor
Ø4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Red)
Pulse motor
EDM-MD12TF-3
Pulse motor valve
EDM-B60YGTF-1
Louver motor (panel)
MP24GA
2-way Air Discharge Cassette Type Model
MMU-AP
0071WH
Fan motor Running capacitor for fan motor
0091WH
0121WH
0151WH
AF-230-53-4G
AF-230-39-4B
AC 400V, 1.0µF
AC 450V, 2.0µF
Drain pump motor
PJD-05230TF-1
Float switch
FS-0208-608
Control P.C. board transformer
TT-13
Pulse motor
EDM-MD12TF-3
Pulse motor valve
EDM-B25YGTF
TA sensor
EDM-B40YGTF
Lead wire length : 268mm
TC1 sensor
Ø4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Red)
Model
MMU-AP
Fan motor Running capacitor for fan motor
0241WH
0271WH
0301WH
AF-200-53-4F
0481WH AF-200-92-4B
AC 450V, 2.5µF
Drain pump motor
AC 450V, 3.5µF
AC 500V, 5µF
PJD-05230TF-1
Float switch
FS-0208-608
Control P.C. board transformer
TT-13
Pulse motor Pulse motor valve
0181WH
EDM-MD12TF-3 EDM-B40YGTF
TA sensor
Lead wire length : 268mm
TC1 sensor
Ø4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Red)
30
EDM-B60YGTF-1
1-way Air Discharge Cassette (Compact type) Type Model
MMU-AP
0071YH
0091YH
Fan motor
0121YH
AF-200-22-4N-1
Running capacitor for fan motor
AC 400V, 1µF
Drain pump motor
PJD-05230TF-1
Float switch
FS-0208-602
Control P.C. board transformer
TT-13
Pulse motor
EDM-MD12TF-3
Pulse motor valve
EDM-B25YGTF
TA sensor
Lead wire length : 818mm
TC1 sensor
Ø4 size lead wire length : 1200mm Vinyl tube (Blue)
TCJ sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Red)
Model
MMU-AP
0151SH
Fan motor
0181SH
0241SH
0152SH
0182SH
AF-200-34-4D
Running capacitor for fan motor
SWF-280-60-1
AC 450V, 1.5µF
Drain pump motor Float switch Control P.C. board transformer
0242SH
AC 500V, 2.5µF
—
PJD-05230TF-2
ADP-1409
FS-0208-603
FS-0218-103
TT-13
—
Pulse motor
EDM-MD12TF-3
Pulse motor valve
EDM-B40YGTF
TA sensor
EDM-B40YGTF-3 Lead wire length : 155mm Vinyl tube
TC1 sensor
Ø4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Red)
Concealed Duct Standard Type Model
MMD-AP
0071BH
0091BH
Fan motor
0121BH
0151BH
Drain pump motor
ADP-1409
Float switch
FS-0218-102
Pulse motor
EDM-MD12TF-3
Pulse motor valve
EDM-B25YGTF
TA sensor
EDM-B40YGTF Lead wire length : 618mm
TC1 sensor
Ø4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Red)
Model Fan motor
MMD-AP
0241BH
0271BH
0301BH
0361BH
ICF-280-120-1
0481BH ICF-280-120-2
Drain pump motor
ADP-1409
Float switch
FS-0218-102
Pulse motor Pulse motor valve
0181BH
ICF-280-120-2
EDM-MD12TF-3 EDM-B40YGTF
EDM-B60YGTF-1
TA sensor
Lead wire length : 618mm
TC1 sensor
Ø4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Red)
31
0561BH
Concealed Duct High Static Pressure Type Model
MMD-AP
Fan motor
0181H
0241H
0271H
0361H
0481H
STF-200-160-4B
STF-200-160-4A
STF-200-260-4C
STF-200-260-4B
AC 500V, 4µF
AC 400V, 8µF
AC 450V, 6µF
AC 400V, 8µF
Running capacitor for fan motor Drain pump motor
ADP-1409
Float switch
FS-0218-102-6
Pulse motor
EDM-MD12TF-3
Pulse motor valve
EDM-B40YGTF
TA sensor
EDM-B60YGTF-1
Lead wire length : 1200mm
TC1 sensor
Ø4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Red)
Slim Duct Type Model
MMD-AP
0071SPH(SH)
0091SPH(SH)
0121SPH(SH)
Fan motor
0151SPH(SH)
Pulse motor
EDM-MD12TF-3
Pulse motor valve
EDM-B25YGTF
EDM-B40YGTF
Drain pump motor ∗
ADP-1409
Float switch ∗
FS-0218-102
TA sensor
Lead wire length : 1558mm
TC1 sensor
Ø4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Red)
∗
0181SPH(SH)
SWF-280-60-1
“SPH” series only.
Under Ceiling Type Model
MMC-AP
0151H
Fan motor
0181H
0241H
SWF-280-60-1
0271H
Louver motor
MP24GA1
Pulse motor
EDM-MD12TF-3
Pulse motor valve
0361H
SWF-280-60-2
EDM-B40YGTF
TA sensor
0481H
SWF-280-120-2
EDM-B60YGTF-1 Lead wire length : 155mm Vinyl tube
TC1 sensor
Ø4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Red)
High Wall Type Model
MMK-AP
0071H
0091H
0121H
Fan motor Louver motor
0151H
0181H
TA sensor
0072H
0092H
ICF-280-120-3
ICF-340-30 or MF-340-30
MT8-3-6
MP24Z
Pulse motor Pulse motor valve
0241H
0122H
EDM-MD12TF-3 EDM-B25YGTF
EDM-B40YGTF
EDM-B25YGTF-3
Lead wire length : 818mm Vinyl tube
Lead wire length : 318mm Vinyl tube
TC1 sensor
Ø4 size lead wire length : 1200mm Vinyl tube (Blue)
Ø4 size lead wire length : 600mm Vinyl tube (Blue)
TC2 sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Black)
Ø6 size lead wire length : 800mm Vinyl tube (Black)
TCJ sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Red)
Ø6 size lead wire length : 800mm Vinyl tube (Red)
32
Floor Standing Cabinet Type Model
MML-AP
0071H
0091H
0121H
0151H
0181H
0241H
Fan motor
AF-200-19-4F
AF-200-45-4F
AF200-70-4K
Running capacitor for fan motor
AC450V, 1.2µF
AC400V, 1.8µF
AC450V, 2µF
Transformer
TT13
Pulse motor
EDM-MD12TF-3
Pulse motor valve
EDM-B25YGTF
EDM-B40YGTF
TA sensor
Lead wire length : 818mm Vinyl tube
TC1 sensor
Ø4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Red)
Floor Standing Concealed Type Model
MML-AP
0071BH
0091BH
0121BH
Fan motor
AF-200-19-4G
Running capacitor for fan motor
AC450V, 1.5µF
0151BH
AC450V, 1µF TT-13
Pulse motor
EDM-MD12TF-3 EDM-B25YGTF
TA sensor
0241BH
AF-200-70-4K
Transformer
Pulse motor valve
0181BH
AC450V, 2µF
EDM-B40YGTF Lead wire length : 818mm Vinyl tube
TC1 sensor
Ø4 size lead wire length : 2000mm Vinyl tube (Blue)
TC2 sensor
Ø6 size lead wire length : 2000mm Vinyl tube (Black)
TCJ sensor
Ø6 size lead wire length : 2000mm Vinyl tube (Red)
Floor Standing Type Model
MMF-AP
0151H
0181H
0241H
0271H
Fan motor
AF-200-37R
AF-200-63T
Running capacitor for fan motor
AC500V, 3µF
AC500V, 3.5µF
Transformer
TT-13
Pulse motor
EDM-MD12TF-3
Pulse motor valve
0481H
AF-200-110M-1
EDM-B40YGTF
Louver motor TA sensor
0361H
AF-200-160H-1 AC500V, 4µF
EDM-B60YGTF-1 MT8-3-9
Lead wire length : 1200mm Vinyl tube
TC1 sensor
Ø4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensor
Ø6 size lead wire length : 2000mm Vinyl tube (Black)
TCJ sensor
Ø6 size lead wire length : 1200mm Vinyl tube (Red)
33
0561H
3-2. Outdoor Unit Model
MMY-
Compressor
MAP0802FT8
MAP1002FT8
DA421A3FB-23M
MAP1202FT8
Output: : 3.75kW × 2
4-way valve coil (Heat pump only)
LB64046
AC220-240V 50Hz
Pulse motor valve coil
VPV-MOAJ524C0
HAM-MD12TF-3
2-way valve coil
VPV
SV2, SV3A, SV3B, SV3C, SV3D, SV3E SV41, SV42, SV5, SV6, SV11, SV12
VPV-122DQ1
SV2, SV3C, SV3D, SV3E, SV6, SV12
VPV-303DQ1
SV3A, SV41, SV42, SV5
VPV-603DQ2
SV3B
VPV-1204DQ50
SV11
DC12V
AC220–240V 50Hz
2-way valve
High-pressure SW
ACB-JB215
OFF : 3.73MPa, ON : 2.9MPa
Pressure sensor (For high pressure) 150XA4-H3
0.5 to 3.5V / 0 to 0.98MPa
Pressure sensor (For low pressure)
150XA4-L1
0.5 to 4.3V / 0 to 3.73MPa
Fan motor
MF-230-600-2
DC280V, 600W
Case heater
AC240V, 29W × 3
Compressor case thermo.
US-622KXTMQO-SS
OFF : 125°C, ON : 90°C × 2
3-3. Outdoor Control Unit Heat Recovery Model Model
MAP0802FT8
MMY-
MAP1002FT8
Power supply terminal block
JXO-3004
AC600V / 30A, 4P
Communication line terminal block
JXO-B2H
AC30V (or DC42V) / 1A, 6P
MAP1202FT8
Inductor
CH-44FK
1.45mH / 25A
Smoothing condenser (For compressor)
400LRSN 1500M
1500µF / 400V
Power supply transformer
TT-01-03T
AC230V, 350mA
FKX-240NK-4810US
0.48mH / 30A (MCC-1366 P.C. board)
FKX-220NK-6310US
0.63mH / 25A (MCC-1366 P.C. board)
IPDU-4T62DA1E
6.2kW
P.C. board (Noise filter) Line filter (AC)
MCC-1366
P.C. board (Control board) P.C. board (IPDU for compressor)
MCC-1429
P.C. board (Power supply board)
MCC-1502
MCC-1439
P.C. board (IPDU for fan)
IPDU-2D16DA1
800W
Power complex module
6MBR25UA120
25A/1200V (MCC-1502 P.C. board)
MCC-896, MCC-897
Pipe temp. sensor (TD)
—
–30°C to 135°C (Ambient temp. range)
Pipe temp. sensor (TS)
—
–20°C to 80°C (Ambient temp. range)
Heat exchanger temp. sensor (TE)
—
–20°C to 80°C (Ambient temp. range)
Outside temp. sensor (TO)
—
–20°C to 80°C (Ambient temp. range)
Oil temp. sensor (TK)
—
–30°C to 135°C (Ambient temp. range)
Liquid temp. sensor (TL)
—
–20°C to 80°C (Ambient temp. range)
Smoothing capacitor (For fan)
400LRSN1000M
1000µF / 400V
Magnet SW
FC-2S
400V / 38A
Thermistor
ZPROYCE101A500
100Ω, 13A, 500V
3-4. Flow Selector Unit (FS Unit) Model
RBM-Y1122FE
RBM-Y1802FE
P.C. board (Control board)
MCC-1431
2-way valve coil
VPV
AC220-240V 50Hz
VPV-122DQ1
SVSS, SVDD
VPV-1204DQ50
SVS, SVD
2-way valve
34
RBM-Y2802FE
TE sensor
TS2 sensor Check joint (Low pressure)
Low pressure sensor
SV2 valve SV42 valve SV3D valve
SV3E valve
35
SV3C valve
SV11 valve
SV41 valve SV5 valve
SV6 valve SV3A valve
TK1, TK2 sensor
TS1 sensor
High pressure SW1
SV12 valve TD1 sensor
PMV 4-way valve
High pressure SW2
SV3B valve
TD2 sensor
TL sensor Check joint (High pressure)
TK3 sensor TK4 sensor
High pressure sensor Check joint (Liquid pipe)
Front side
Rear side
3-5. Parts Layout in Outdoor Unit
TO sensor
3-6. Name of Each Part
[Concealed Duct Type]
Earth screw Situated inside the electric parts box.
2-way discharge/3-way discharge 2-way discharge or 3-way discharge can be selected according to the shape or arrangement of the room. For details, consult with the dealer from which you have purchased the air conditioner.
Air filter Filters dust and other trash. (Air filter is situated in the air grille.)
Clip To open/close the air inlet grille.
Air inlet grille
Main remote controller RBC-AMT31E
Air outlet/Air outlet louver Select air flow direction in cooling or heating operation.
Air filter Filter dust and other trash. (Air filter is situated in the air inlet grille.)
Air inlet
Air filter Filters dust and other trash. (Air filter is situated in the air grille.)
R.C.
H
No.
TEMP.
FILTER RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
Air outlet/Air outlet louver Select air flow direction in cooling or heating operation. Earth screw Situated inside the electric parts box.
Earth screw Situated inside the electric parts box. Air outlet/Air outlet louver Select air flow direction in cooling or heating operation.
Air outlet Discharge duct connection.
Drain pan
[Slim Duct Type]
Earth screw Situated in the electric parts box.
˚C
SETTING
Air inlet grille
Air filter Filters dust and other trash. (Air filter is situated in the air inlet grille.)
Air filter Filters dust and other trash. (Air filter is situated in the air inlet grille.)
MMU-AP0152SH, AP0182SH, AP0242SH Button Button to open/close suction port
Air filter Filters dust and other trash. (Air filter is situated in the air grille) Air inlet grille. Earth screw Situated inside the electric box.
Air outlet/Air outlet louver Select air flow direction in cooling or heating operation mode.
Air filter Filters dust and other trash. (Provided on the suction port.)
Air outlet Discharge duct connection.
[Under Ceiling Type] Button Button to open/close the inlet grille.
Air filter Air filter is situated in the air grille. (Filters dust and other trash.)
Air inlet grille
ERROR
PROGRAM2 PROGRAM3
WEEKLY TIMER
Air inlet Suction duct connection.
Earth screw Earth screws situated in the electric parts box.
Air filter (Air filter is not supplied on certain models within the series.) TEST
SuMoTuWeTh Fr Sa PROGRAM1
UNIT
Air inlet Suction duct connection.
Wireless remote controller kit TCB-AX21E2 RBC-AX22CE2 RBC-AX21U(W)-E2
36
[1-way Air Discharge Cassette Type] MMU-AP0071YH to AP0121YH MMU-AP0151SH to AP0241SH
Air inlet Air filter is situated in the air grille.
[Concealed Duct, High Static Pressure Type]
UNIT No.
Air outlet/Air outlet louver Select air flow direction in cooling or heating operation.
Sub-remote controller RBC-AS21E2
Center panel
Earth screw Earth screws are situated inside the electric parts box.
CODE No. SET DATA SETTING TEST
[2-way Air Discharge Cassette Type] Earth screw Situated inside the electric parts box.
Air outlet flange Discharge duct connection.
Weekly timer RBC-EXW21E2
Sold Separately Parts
[4-way Air Discharge Cassette Type]
[High Wall Type] MMK-AP0071H to AP0241H Air inlet grille
Air filter Filters dust and other trash. (Air filter is situated in the air inlet grille.)
Air inlet grille
Earth screw Situated inside the electric parts box. Air outlet/Air outlet louver Change the direction of the air to be discharged according to cool/heat mode. Earth screw Situated inside the electric parts box.
Air outlet/Air outlet louver Change the direction of the air to be discharged according to cool/heat mode.
MMK-AP0072H to AP0122H Air inlet grille
Air filter Filters dust and other trash. (Air filter is situated in the air inlet grille.)
Earth screw Situated inside the electric parts box.
Air outlet/Air outlet louver Change the direction of the air to be discharged according to cool/heat mode.
Central remote controller TCB-SC642TLE2
3-6-1. Indoor Unit
ZONE ALL ZONE GROUP
CODE No. 1234 SET DATA SETTING
R.C.
UNIT No.
TEST
No.
GROUP SELECT
ZONE
CL
SET
3-7. Parts Name of Remote Controller
[Floor Standing Cabinet Type] Air outlet/Air outlet louver Changes the direction of the air flow.
Earth screw Situated inside the electric parts box.
Air filter Filters dust and other trash. (Situated inside the air grille.)
Display section In the illustration, all of the indicators are displayed for the purpose of explanation. In normal operation, only the icons relevant to the mode of operation would be displayed. • When turning on the power breaker switch for the first time, [SET DATA] flashes on the display part of the remote controller. While this display is flashing, the system is performing a self-check function. Wait until this check has been completed and the [SET DATA] display has disappeared before using the remote controller.
2 3 4 5 6 15 1
Air outlet port
Drain pan (With drain filter) This accessory is installed at the local site.
Air inlet grille
Front panel (Lower side)
Air filter Filters dust and other trash. (Situated inside the suction port.)
1
37
Horizontal louver/Air outlet port Changes the direction of the air flow.
Vertical louver The air can automatically be discharged rightward/leftward at stated periods.
Air inlet grille
Air filter Filters dust and other trash.
Earth screw Situated inside the electric parts box.
3 4
H
SET DATA display
12
6 7
13
Timer time display
Timer SETIN setup display
Filter display ” is displayed, clean the air filter.
14
VENT
SET
CL
Operation section
UNIT
Louver position display (for 4-Way Air Discharge Cassette Type and Under Ceiling Type model only) Louver swing display Indicates the movement of the louver.
10
Setpoint temperature display The selected set up temp. is displayed.
11
10
Remote controller sensor display Displayed while the sensor of the remote controller is used.
16 11 13 12 14 PRE-HEAT display
Operation ready display
No function display Displayed when the selected function is not available.
15
Fan mode display The selected Fan mode is displayed. (AUTO) (HIGH) (MED.) (LOW) In the Concealed Duct High Static Pressure type models, [HIGH] only is displayed for the air speed.
16
Mode select control display Displayed when pushing “Operation mode select ” button while the operation mode is fixed to heating or cooling by the system manager of the air conditioner.
TEST run display
Displays louver position.
9
Refrigerant pipe access for connection
SWING/FIX
Displayed when cooling or heating operation is impossible because the outdoor temperature goes outside the operating range.
Displayed during a test run.
8
Power source aperture
MODE
TIME
Displayed when the heating or defrost operation is carried out. While this indication is displayed, the indoor fan stops or the runs in LOW fan speed.
By pressing the Timer Set button, the display of the timer is shown in the following order: → [OFF] repeat OFF timer → [OFF] → No display. [ON]
Air outlet (Discharge) Hot air is discharged when cooling operation is performed. Cold air is discharged when heating operation is performed.
Fixing leg
CHECK display
If “FILTER
Air inlet Situated at front, rear, left, and right sides.
FAN
17
No.
Operation mode select display
Displays the selected delay time. (When a malfunction occurs, a check code is displayed in place of the time display.)
Drain pan Water accumulated in the drain pan is drained through the drain pipe.
3-6-2. Outdoor Unit
FILTER RESET TEST
ON / OFF
TIMER SET
UNIT No.
R.C.
Will be displayed when a error condition occurs or a protection device operates.
5
Fixing metal holder (Right and left)
TEMP.
SET DATA SETTING TEST
The selected operation mode is displayed. Fixing metal holder
No.
CODE No.
Displayed during initialization of controller.
2 [Floor Standing Type]
Display section
UNIT No.
R.C.
H
78 9
Air inlet grille
[Floor Standing Concealed Type]
Earth screw Situated inside the electric parts box.
CODE No. SET DATA SETTING TEST
17
Central control display Displayed when using the remote controller with a central control remote controller, etc. If the remote controller is prohibited on fan the flashes when operating the centralcontrol side, ON / OFF
MODE
, , / buttons and following the function is not accepted. (The different settings available on the remote controller when in use with a central controller, can be referred to in the owners manual of the central controller.)
3-8. Correct Usage
Operation section Push each button to select the desired operation. This remote controller can operate up to a maximum 8 indoor units. • The remote controller can memorize user settings and can be recalled and activated by a single press of ON / OFF button. the
Preparation
1 7 TEMP.
10 2 5
FILTER RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
When the product is operated for the first time, or after the SET DATA value has been changed, the procedure below should be followed. The remote controller can memorize user settings and can be recalled and acti ON / OFF button. vated by a single push of the
UNIT
8 9 4 6
Power the system by switching the electrical isolation device on and by pushing the ON/OFF button on the remote controller. • When the power is switched on, a partition line is shown on the remote controller display. • The remote controller performs a self-check function for approximately 1 minute during which user input will not be accepted.
REQUIREMENT ON / OFF • While using the air conditioner, operate it only with button without turning off the main power switch and the leak breaker. • Do not turn off the earth leakage breaker while the air conditioner is in use. • When the air conditioner has not been operated for a period of time, ensure the earth leakage breaker is turned on for 12 or more hours prior to the start up of operation.
3 1
38
2 3 4
5
Timer set button Used for setting the timer function. Check button The CHECK button is used for the check operation. During normal operation, do not use this button. Fan button When an after-market fan device is connected to the system, this button activates the device. is displayed on the remote controller • If when pushing the FAN button, a fan is not connected.
7
8
ON / OFF
9
Operation select button Selects the desired operation mode.
10
FILTER RESET TEST
button
Push to cycle between ON and OFF mode. When the unit is OFF, the Operation Lamp and the display will turn OFF.
Set up temperature button Adjusts the temperature set point for the room. Set the desired temperature by pressing the or .
1 2
3
” display.
:
Select the desired indoor unit by pressing the unit button. SWING/FIX
:
Press the button to set the louver into Auto mode. • This function is not available on the Concealed Duct Standard Type, High Static Pressure Type, Floor standing Cabinet Type, Floor Standing Concealed Type, or Slim Duct Type.
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
3
1 2
UNIT
ON / OFF
Push button. The operation lamp goes on, and the operation starts. MODE
Select an operation mode with the button. One push of the button, and the display changes in the order shown on the right. • “DRY mode” function is not available on the Concealed Duct High Static Pressure Type.
AUTO
HEAT
DRY
COOL
FAN
(Dehumidity)
AUTO
HIGH
MED.
LOW
Select air volume with FAN button. One push of the button, and the display changes in the order shown on the right. • When air volume is “AUTO ”, air volume differs according to the temperature difference between the set temperature and the room temperature. ” is displayed and the air volume is LOW. • In DRY mode, “AUTO
Unit and Auto louver buttons UNIT
ON / OFF
4
Operation lamp Lit during normal product operation. Flashes to indicate malfunction or incorrect timer setting.
Filter reset button Resets the “FILTER
6
TEMP.
Fan mode select button Selects the desired air speed. The Concealed Duct High Static Pressure type models cannot be operated.
• In heating operation, if the room temperature is not heated sufficiently with volume “LOW select “MED. ” or “HIGH ” operation.
OPTION : Remote controller sensor The temperature sensor in the indoor unit measures the room temperature. The remote controller can also measure the room temperature. For details of this feature, contact the dealer from whom you purchased the product.
” operation,
• The temperature which the temperature sensor detects is one near the air inlet of the indoor unit. Therefore it slightly differs from the room temperature according to the installation status. The setup value is a criterion of the room temperature. (Automatic air speed cannot be selected in FAN mode.) • Air volume of function is not available on “Concealed Duct High Static Pressure Type” air speed “HIGH ” only is displayed.
4
Determine the set up temperature by pushing the “TEMP.
Stop Push
ON / OFF
button.
The operation lamp goes off, and the operation stops.
” or “TEMP.
” button.
REQUIREMENT
How to set up the air direction Push SWING/FIX button.
[In Cooling operation] • The operation starts after approximately 1 minute.
[In Heating operation] • In heating operation, the fan operation may continue for approximately 30 seconds after the air conditioner has stopped. • The indoor fan continues in preheat operation for 3 to 5 minutes, and then blows out the hot air. symbol is displayed on the remote controller.) ( • When the temperature of the room has reached the set point temperature and after the unit has stopped, the air speed is lowered and the air volume is greatly reduced. is displayed. • In defrost mode, the fan stops so that cool air is not discharged. PRE-DEF symbol
[In Automatic operation] • Using the difference between the set point temperature and the room temperature, the heating and cooling operations are automatically performed.
1
Every push of the button, the air direction changes.
In Heating operation Set the air outlet louver downward. If directing it upward, the hot air may not reach the floor. Initial setup
In Cooling / Dry operation Set the air outlet louver upward. If directing it downward, dew condensation may fall on or near the air discharge port. Initial setup
How to start louvre swinging
3-9. Adjustment of Wind Direction
2
To increase the cooling or heating effect, be sure to make proper use of the discharge louver for cooling or heating operation. As the characteristics of the air, cool air collects at lower levels, and hot air collects at higher levels.
39
CAUTION
Push SWING/FIX button. Set the louver direction to the lowest position, and then push SWING/FIX again. • [SWING ] is displayed and the air direction automatically changes upward/downward. In cases where one remote controller controls the multiple indoor units, each indoor unit can be selected and its air direction can be set up.
TEMP.
FILTER RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
UNIT
Set the louver so that air blows out horizontally. If cooling operation is performed with the louver blowing air downwards, the air outlet or surface of the louver will be wet with dew, which may drip.
How to stop louver swinging
3 4-way Air Discharge Cassette Type • While the air conditioner stops, the discharge louver directs downward automatically. state, the louver is directed upward. • When the heating operation is in PREHEAT/DEFROST The rotation of the louver starts after PREHEAT/DEFROST status cleared , is displayed status. on the remote controller even if the heating operation is in PREHEAT/DEFROST
[In Cooling operation] Use the discharge louver with horizontal set point.
[In Heating operation] Use the discharge louver with downward set point.
4
1, 2, 3
4
SWING/FIX
Push button again while the louver is operating. • The louver stops at a position when you push SWING/FIX . If pushing SWING/FIX again, the air direction descends from the highest position. * In COOL/DRY operation, the louver does not stop at the lowest position. If stopping the louver as it directs downward during operation, it stops after moving to the 3rd position from the highest position.
In FAN operation
In all modes
Series of operation Initial setup
Display when stopping the swing
UNIT UNIT
• Push to set up the air direction individually in each indoor unit. Then the indoor unit No. in a group control is displayed. For the displayed indoor unit, set up the air direction. • If the unit No. is not displayed, all the indoor units are operated at the same time. UNIT pushed, the display is • Every time is exchanged as follows:
Fan/Heat operation
No display
Cool/Dry operation
Unit No. 1-1
Unit No. 1-4
Unit No. 1-2
Unit No. 1-3
2-way discharge or 3-way discharge can be selected according to the configuration of the room. For details, consult with the dealer from which you have purchased the air conditioner.
INFORMATION • If cooling operation has been selected while the louver is in a downward position, the cabinet or surface of the louver may become wet with dew. • If heating operation has been selected while the louver is in a horizontal position, the room temperature may not be even. • Never handle the louver directly with hands as a malfunction or injury may occur. Use the louver operation functions on the remote controller to change direction of the louver.
2-way Air Discharge Cassette Type [In Cooling operation] Use the air outlet louver with horizontal set point.
[In Heating operation]
Under Ceiling Type, 1-way Air Discharge Cassette Type (2SH Series) • When the air conditioner is stopped, the horizontal louver (Up/Down air direction adjustment plate) automatically directs upward. • When the air conditioner is in stand-by status waiting to heat, the horizontal louver (Up/Down air direction adjustment plate) directs upward. The swinging operation starts upon the heating operation starting, but “SWING ” is displayed on the remote controller even when in heating operation.
How to set up the air flow direction Push
SWING/FIX
button during operation.
1
Every pushing of the button, the air direction changes.
In Heating operation
In Cooling / Dry operation
Set the horizontal louver (Up/Down air direction adjustment plate) downward. If directing it upward, the hot air may not reach the floor.
Set the horizontal louver (Up/Down air direction adjustment plate) upward. If directing it downward, dew condensation may fall on or near the air discharge port.
Initial setup
Initial setup
Use the air outlet louver with downward set point.
How to start swinging
How to set up the air direction
1 2 40
3
SWING/FIX
Push button during operation. • [SWING ] is displayed and the air direction automatically changes upward/downward. In case when one remote controller controls multiple indoor units, each indoor unit can be selected and the air direction can be set up. SWING/FIX
Push button again during swinging of the air outlet louver. • The air outlet louver can be stopped at the required position.
TEMP.
2
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
TEMP.
SWING/FIX
Push button. Set the direction of the horizontal louver (Up/ Down air direction adjustment plate) to the lowest position and then push SWING/FIX button again. • [SWING ] is displayed and the air direction automatically changes upward/downward. In cases where one remote controller controls the multiple indoor units, each indoor unit can be selected and air flow direction set up.
UNIT
FILTER RESET TEST
UNIT
• To set up the air direction individually, push button to display each indoor unit No. in a group control. Then set the air direction on the displayed indoor unit. • If there is no display, all the indoor units can be operated collectively. UNIT button, the display will • Every pushing of the change as shown in the figure.
SET
CL
How to stop swinging
UNIT
3
1, 2 No display
3
Unit No. 1-1
Unit No. 1-4
Unit No. 1-2
Unit No. 1-3
1-way Air Discharge Cassette Type (1H Series)
Adjustment of air direction upward/downward [In Cooling operation] In cooling operation, use the air outlet louver in a position that will defuse cool air throughout the room.
[In Heating operation] In heating operation, use the air outlet louver in a downward position so that the air is directed to the floor.
Adjustment of air the direction rightward/leftward To change the discharge direction from the right or left position, set the vertical grille inside of the air outlet louver to the required direction.
4
SWING/FIX
Push button again during swinging of the horizontal louver. • The horizontal louvre can be stopped at the desired position. The air direction can be again set up from the uppermost position by pushing SWING/FIX button. * While the horizontal louver is set downward in cooling/drying operation, it does not stop. If stopping the horizontal louver which directs downward during swinging, it will stop after reaching the 3rd position from the upper position. UNIT
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
1, 2, 3 In FAN operation
No display
Unit No. 1-1
Unit No. 1-2
Unit No. 1-4
Unit No. 1-3
UNIT
4 In all modes
Series of operation Initial setup
Display when stopping the swing
Fan/Heat operation
UNIT
• Push to set up the air direction individually in each indoor unit. Then the indoor unit No. in a group control is displayed. For the displayed indoor unit, set up the air direction. • If the unit No. is not displayed, all the indoor units are operated at the same time. UNIT is pushed, the display is ex• Every time changed as follows:
Setup the air flow direction and swinging Refer to the description of the “2-way Air Discharge Cassette Type”.
FILTER RESET TEST
ON / OFF
Cool/Dry operation
Right/Left air direction adjustment
Floor Standing Cabinet Type
To change the air outlet direction to the right or left side, set the vertical louver located behind the horizontal louver to the desired direction.
[In Cooling operation]
INFORMATION • If cooling operation is performed with a donwards discharge, dew may form on the surface of the cabinet or the horizontal louver resulting in possible dripping. • If heating operation is performed with a horizontal discharge, the room temperature may not be equal i.e. there may be a large variance between one side of the room with the other.
In cooling operation, set the air outlet louver with a horizontal set point so that the cold air diffuses the whole room.
[In Heating operation] In heating operation, set the air outlet louver with a downwards set point so that the hot air blows towards the floor.
High Wall Type
Adjustment of air Flow direction Upwards/Downwards [In Cooling operation]
How to change the air outlet port
In cooling operation, use the horizontal louver with a horizontal set point so that the cold air diffuses the whole room.
Change the air outlet port using the following procedure.
1
[In Heating operation]
Remove the two fixing screws on the air outlet port. (The fixing screws are reused.)
In heating operation, use the horizontal louver with a downwards set point so that the hot air blows towards the floor.
41
REQUIREMENT • If cooling operation is performed with the louver set at a downwards position, dew may form on the surface of the cabinet or the horizontal louver resulting in possible dripping. • If heating operation is performed with the louver set in a horizontal position, the room temperature may not be equal i.e. there may be a large variance between one side of the room with the other. • Do not move the horizontal louver directly with your hands; otherwise a fault maybe caused. Select the direction of the SWING/FIX button on the remote controller. horizontal louver using the The horizontal louver will not stop immediately even if the switch is pushed. Note pushing the switch again when the required louver direction has been reached will stop the louver.
Adjustment of air Flow direction rightwards/leftwards To change the air outlet direction to the right or left side, set the vertical louver located behind the horizontal louver to the desired direction.
Setup of air direction and swinging 1H series: Refer to the description of “2-way Air Discharge Cassette Type”. 2H series: Refer to the description of “Under Ceiling Type, 1-way Air Discharge Cassette Type (2SH Series)”.
2
3 4
5
Remove the discharge port, by pushing up on the rear side, to a point where you can remove it from the rear clip.
Lift the air outlet port upwards and remove it.
Reverse the air outlet port and attach it to the main unit. Pay attention so that four claw hooks (two at rear and two at the lower sides) are hooked on the mounting position.
Be sure to tighten the air outlet port with the removed fixing screws so that the air outlet port does not come off.
3-10. Timer Operation
Floor Standing Type
Adjustment of air Flow direction upwards/downwards
The type of timer operation can be selected from the following three types. OFF timer : The operation stops when the time on the timer has reached the set time. Repeat OFF timer : The unit will stop, every time the set time period has elapsed. ON timer : The unit will start when the time on the timer has reached the set time.
[In Cooling operation] In cooling operation, move the louver with your hands so that the horizontal air outlet points in a direction so that the cold air diffuses the entire room.
Timer operation [In Heating operation] In heating operation, move the louver with your hands so that the horizontal air outlet points in a downward direction, towards the floor. TEMP.
ON / OFF
Adjustment of air Flow direction rightwards/leftwards [In case of using unsymmetrical air directions] Lift up the vertical louver lightly and direct it towards the desired direction once completed lower the louver back down. In this case, do not use the Swing function.
2
1
1
FILTER RESET TEST
[In case of automatic swing]
1
42
2
3
Push the button again whilst the vertical louver is moving will allow you to stop the louver in the desired position.
MODE
TIME
SWING/FIX
VENT
SET
CL
2
UNIT
34 TEMP.
FILTER RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
1
UNIT
2
1, 2
UNIT
Swing button • To set up the air flow the direction individuUNIT ally, push the button to display each indoor unit No. in a group control. Then set up the air flow direction to the desired indoor unit. • If there is no display, all the indoor units can be operated collectively. UNIT button, will change • Every push of the the display as shown in the figure.
FAN
In this case, do not use the swing function.
SWING/FIX
Push the button during operation. • [SWING ] is displayed and the air direction will automatically change rightwards/ leftwards. In cases where one remote controller controls multiple indoor units, it is possible to set each indoor unit individually, so that the air flow direction can be altered. SWING/FIX
TIMER SET
No display
3 Unit No. 1-1
Unit No. 1-4
Unit No. 1-2
• If cooling operation is performed with downward air outlet, dew may form on the surface of the cabinet or the horizontal louver, resulting in possible dripping of water. • If heating operation is performed with the horizontal air outlet actively moving, unevenness of the temperature may increase within the room. • Do not move the louver directly with your hands during swing operation; otherwise a fault may be caused. SWING/FIX button is pushed. The vertical louver does not stop immediately even if the SWING/FIX To adjust the stop position, push the button.
Push the
TIME
OFF
OFF
ON
(OFF timer)
(Repeat OFF timer)
(ON timer)
No display
buttons to select the “SET TIME”.
For every push of the button, the set time increases in the unit of 0.5 hr (30 minutes). The maximum set time is 72.0 hr. button, the set time decreases in the unit of 0.5 hr (30 minutes). For every push of the The minimum set time is 0.5 hr.
3
Unit No. 1-3
INFORMATION
Push the TIMER SET button. • The timer display (type) changes for every push of the button. • SET TIME and timer time displays flash.
Push the SET button. • The SETTING display disappears and the timer time display goes on. (When the ON timer is activated, the chosen time period will be displayed. Once the time has been reached, all displays except the ON light will disappear.)
Cancel of timer operation
4
Push the CL button. • TIMER display will disappear.
NOTICE • When the unit stops after the timer has reached the preset time, the Repeat OFF timer will resume the ON / OFF operation. However by pushing the button the repeat function will stop once the time on the timer has again reached its set time.
3-11. Installation
3-12. Maintenance
Installation location
Cleaning of air filter WARNING
• When [FILTER] is displayed on the remote controller, its is time to check and if necessary clean the filter. • Clogging of air filter decreases the cooling/heating effect.
• Select a location for installation that will be able to safely support the weight of the unit. If the installation location is not strong enough to support the unit and the unit falls, injury could result. CODE No. SET DATA SETTING TEST
CAUTION • Do not install the unit in a location where combustible gases could conceivably leak. Leaking gases that accumulate in the vicinity of the unit could be ignited by the unit.
UNIT No.
FILTER display Notifies that it is time to clean the air filter.
No.
TEMP.
REQUIREMENT • A location that permits the level installation of the unit • A location that provides enough space to service the unit safely • A location where water draining from the unit will not pose a problem
R.C.
H
FILTER reset
FILTER RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
UNIT
Push the FILTER switch after cleaning. The “FILTER” display will disappear.
Avoid the following types of locations :
43
• Locations where salt is present in large amounts (seaside areas), or where sulfuric gases are present in large amounts (hot springs areas) (If the unit is to be used in such areas, special maintenance is necessary.) • Locations that generate oils (including machine oils), steam, oily smoke, or corrosive gases • Locations where organic solvents are used • Locations in the vicinity of equipment that generates high frequency signals • Locations where the outdoor unit will blow in the direction of a neighbor's window • Locations where the noise of the outdoor unit will pose a problem • Locations with poor air circulation
Electric wiring
WARNING Be sure to turn off the main power supply prior to any maintenance. • Please do not intend to do the daily maintenance and/or Air Filter cleaning by yourself. Cleaning of the air filter and other parts of the unit involves dangerous work in high places, so be sure to have a qualified service person do it. Do not attempt it by yourself.
Daily maintenance • For daily maintenance including Air Filter cleaning, please use qualified service personnel, particularly for the following models; 4-way Air Discharge Cassette Type Concealed Duct Type Under Ceiling Type 2-way Air Discharge Cassette Type Slim Duct Type 1-way Air Discharge Cassette Type Concealed Duct, High Static Pressure Type
WARNING
NO GOOD
Ensure that the unit is correctly earthed.
NO GOOD
Grounding is necessary. If earthing is incomplete, an electric shock may be caused.
CAUTION
NO GOOD
Check that the circuit breaker is fitted. Attaching a earth leakage breaker is necessary. Otherwise, an electric shock may be caused.
Make sure that the correct capacity Fuses are used.
2-way Air Discharge Cassette Type
Using wire or copper wire may cause a fire or unit fault. Ensure that the power supply to the unit is exclusive and is the correct rated voltage.
4-way Air Discharge Cassette Type
1-way Air Discharge Cassette Type
NO GOOD
NO GOOD
To disconnect the appliance from the main power supply. This appliance must be connected to the main power supply by means of a circuit breaker or a switch with a contact separation of at least 3mm.
NO GOOD Concealed Duct Type
NO GOOD Under Ceiling Type
Slim Duct Type
Concealed Duct, High Static Pressure Type
Re-installing the air filter • Insert the upper portion of air filter confirming alignment with the right and left edges of the indoor unit until it is located. • Close the air inlet grille. If the FILTER lamp on the indoor unit is lit, push the FILTER button on the remote controller or the TEMPORARY button on the indoor unit to turn off the lamp.
High Wall Type (Model : 1H series) • Push the projection at the center of the air filter. • Undo the clip on the air filter, pull the air filter downwards while pushing it towards the main unit side.
(Model : 2H series)
Push the air filter, and pull it downward.
• Open the air inlet grille. Lift the air inlet grille up in to the horizontal position. • Take hold of the left and right handles of the air filter and lift it up slightly, then pull downwards to remove it from the filter holder.
Filter holder
Cleaning the air inlet grille 1. Remove the air inlet grille. Hold the two sides of the air inlet grille and open in an upwards direction. Move the center arm to the left and remove the grille. 2. Wash it with water using a soft sponge or towel. (Do not use metallic scrubbing brush or other hard brushes.) • Use of such hard objects will cause scratches on the surface of the grille, and the metal coating to peel off. • If very dirty, clean the air inlet grille with a neutral detergent for kitchen use, and rinse it off with water. 3. Wipe the air inlet grille and allow to dry. 4. Fit the left and right arms of the air inlet grille to the shafts on the two sides of the air conditioner and push in completely, then push in the center arm. 5. Check that the center arm has been completely inserted and then close the air inlet grille. • Push the arrow locations (Four) at the bottom of the air inlet grille to check whether the grill is completely closed.
Filter holder
Floor Standing Cabinet Type
44
• Gently push down the upper part of the suction port, and then pull towards you to remove it. • Take out the air filter inside of the suction port.
Floor Standing Concealed Type • Push down on the hook of the air filter on the front panel (Lower side). • Pull the air filter towards you to remove it. Front panel (Lower) Air filter knob
Floor Standing Type Removal / Attachment of air filter • Pull the air filter towards you. • To attach the air filter, insert it into the main body and push.
Cleaning of main unit / remote controller
CAUTION
NOTE • When cleaning the air filter, use a small brush or cleaning device. If the air filter is heavily stained use a neutral detergent mixed with warm water. • After washing the filter, rinse it out thoroughly and place in the shade to dry. Do not expose to direct sun light. • Once the air filter has dried, place the air filter back into the unit.
• Wipe them with a soft and dry cloth. • A cloth dampened with cold water may be used on the indoor unit if it is very dirty. • Never use a damp cloth on the main unit or remote controller. • Do not use or leave a chemically treated duster on the unit for long periods of time, as it may damage or alter the colour of the unit surface. • Do not use benzine, thinner, polishing powder, or similar solvents for cleaning. These may cause the plastic surface to crack or deform.
Thinner Polishing Benzene powder
Chemical floor-cloth
Do not use.
3-13. Air Conditioner Operations and Performance
If you do not plan to use the unit for more than 1 month 1. Operate the fan for 3 to 4 hours to dry the inside of the unit • Operate “FAN” mode. 2. Stop the air conditioner and turn off the main power supply or the circuit breaker.
Check before operation Wipe with a dry soft cloth
• Check whether earth wire is disconnected or out of place. • Check that air filter is installed to the indoor unit.
Heating capacity
WARNING Turn on the power supply 12 hours or more before starting the air conditioner.
• During heating operation the heat pump system operates by absorbing the heat from the outside air and discharging it into the room. Therefore if the outside temperature drops, the units heating capacity will decrease. • When the temperature of the outside air is low, it is recommended that you use other forms of heating in conjunction with the air conditioner.
Checks before operation 1. Check that the air filters are installed. 2. Check that the air outlet or inlet is not blocked. 3. Turn on the main power switch or the circuit breaker for the main power supply to the air conditioner. When the unit has not been turn on for a long period of time, ensure the unit is dry, as shown above and then operate in fan only mode for 3 to 4 hours.
Defrost operation during heating operation • If the outdoor unit has a build up of frost during the heating operation, the operation mode changes automatically to defrost mode to increase the heating effect (for approximatley 2 to 10 minutes). • During defrost operation, fans of the indoor and the outdoor units will stop.
Protection for 3 minutes
NOTE For an Air conditioning system which is operated regularly, cleaning and maintenance of the indoor/ outdoor units are strongly recommended. As a general rule, if an indoor unit is operated for about 8 hours daily, the indoor/outdoor units will need to be cleaned at least once every 3 MONTHS. This cleaning and maintenance shall be carried out by a qualified person. Failure to clean the indoor/outdoor units regularly will result in poor performance, icing, water leakage and even compressor failure.
• The outdoor unit will not operate for approximately 3 minutes after the air conditioner has been immediately restarted after being stop, or the power supply has been turned on. This is to protect the system.
Main power failure • If a power failure occurs during operation, all operations will stop. • When restarting the unit, push the ON/OFF button again.
Fan rotation of stopped unit
45
• When other indoor units within the same system are in operation, the fan on the indoor units that are on “stand-by” will rotate to protect the machine once per approximately 1 hour for several minutes.
HINTS FOR ECONOMICAL OPERATION
Protective device (High pressure switch)
Maintain room temperature at comfortable level Clean air filters The clogged air filter impairs the performance of the air conditioner. Gee, chilly
Never open doors and windows more than what is necessary
Control
To keep the cool or warm air in the room, never open doors and windows more than what is necessary.
Window curtains In cooling, close the curtains to avoid direct sunlight. In heating, close the curtains to keep the heat in.
Clean, please.
The high pressure switch will stop the unit automatically when excessive load is applied to the air conditioner. If the protective device operates, the operation lamp will stay lit but the operation will stop. When the protective device operates, check characters “ ” on the remote controller display. The protective device may operate in the following cases. • When suction or discharge port on the outdoor unit is blocked. • When strong wind blows continuously against the discharge port of the outdoor unit. • When dust or dirt is excessively adhered to the air filter of the indoor unit. • When the discharge port of the indoor unit is blocked.
Cooling/heating operation of a Heat Recovery Multi air conditioner • When the outdoor temperature goes out of the operating range, the cooling or heating modes may not be performed in order to protect the equipment. In this case, the “ ” light goes on.
Ensure uniform circulation of room air Adjust the air flow direction so that the air is evenly circulated throughout the room.
Ple
ase
clo
se
Characteristics of heating operation
Blows upward
Air flow adjustment
Cool and dry air Warm air
Blows downward
• Hot air will not be blown out immediately from the indoor unit. It will take between 3 to 5 minutes (depending on temperature conditions of the room and the outside) before the indoor heat exchanger warms up sufficiently, to allow hot air to be blown. • During operation, the indoor unit may stop if the outside temperature becomes to high. • When other indoor units are in heating operation, the fan operation of the indoor unit on fan only operation may be stopped temporarily to prevent hot air from being blown out.
Characteristics of cooling/heating simultaneous operation • If the outdoor temperature drops during operation, the fan of the outdoor unit may stop.
3-15. When the Following Symptoms are Found
Air conditioner operating conditions For specified performance, operate the air conditioner under the following temperature conditions: Cooling operation
Room temperature CAUTION Heating operation
Check the points described below before contacting your local service repair center.
Outdoor temperature : –10°C to 43°C (Dry-bulb temp.) Outdoor unit
• White misty cold air or water is blown out. • Sometimes, the noise “Pushu !” is heard.
• The fan on the outdoor unit automatically stops when performing a defrost operation. • Solenoid valve works when defrost operation starts and finishes.
Indoor unit
• “Swish” sound is sometimes heard.
• When the unit is in operation,a sound such as the movement of water from one area to another may be heard. This sound may become larger after a period of 2 to 3 minutes once the unit has begun operation. This is not a cause for concern, but is the movement of the refrigerant or the draining sound of the dehumidifier. • This is sound generated when the heat exchanger, etc. expands and contracts slightly due to the change of temperature. • Various odurs such as those from a carpet, clothes, cigarette, or cosmetics will adhere to the air conditioner. • Has the outdoor temperature gone out of its specified range specified range? • When the manager of the air conditioner has fixed the operation to either COOL or HEAT, but a request/demand contrary to this setup operation is requested. • When the fan operation is stopped to prevent the discharge of hot air. • Since refrigerant is flowed temporarily to prevent the stay of oil or refrigerant in the stand by indoor unit, the sound of flowing refrigerant, “Kyururu” or “Shaa” may be heard. When indoor unit operates in HEAT mode, and cold air in COOL mode white steam may be blown out. • Sound is generated when the expansion valve operates when power supply has been turned on.
Outdoor temperature : –15°C to 21°C (Dry-bulb temp.), –15°C to 15.5°C (Wet-bulb temp.) Room temperature
: 15°C to 28°C (Dry-bulb temp.)
• If the air conditioner is used outside of the above conditions, the units safety protection devices may operate. * Do not use “Super HRM” for other than personal usage where the ambient temperature may go down below –5°C. (For example, OA equipment/Electric device/Food/Animals and plants/Art object)
When outdoor temperature goes out of specified range, “ or ” mark is indicated on the Wired remote controller display and the required operation will stop. “ & ” : When in heating operation. “ ” : When in cooling operation.
Notice : • This indication is not failure. • When outdoor temperature goes back to specified range, “ or ” will disappear and the unit will begin normal operation. • The unit operation may stop if the next operation (request) cannot be fulfilled because it falls outside the specification for Super HRM. See below for the maximum cooling and heating specifications. (Outdoor temp. (DB) < –10°C : Cooling mode, > 21°C : Heating mode)
• Slight “Pishi!” sound is heard.
It is not a failure.
CAUTION
Cause
Symptom
: 21°C to 32°C (Dry-bulb temp.), 15°C to 24°C (Wet-bulb temp.)
Room relative humidity – less than 80 %. If the air conditioner operates in excess of this figure, the surface of the air conditioner may cause dewing.
• Discharge air smells. • “
” indication is lit.
• Sound or cool air is blown from the indoor unit.
DANGER If the unit position is to be changed and re-located to a new position ask your local dealer or installation specialist. Do not attempt to move the air conditioner yourself, as incorrect installation may cause electric shock or fire.
Do not install the air conditioner in the following places • Do not install the air conditioner in any place within 1 m from a TV, stereo or radio set. If the unit is installed in such places, noise transmitted from the air conditioner may affect the operation of these appliances. • Do not install the air conditioner near a high frequency appliance (sewing machine or massager for business use, etc.), as the air conditioner may malfunction. • Do not install the air conditioner in a humid or oily place, or in a place where steam, soot or corrosive gas maybe generated. • Do not install the air conditioner in a salty place such as a seaside area. • Do not install the air conditioner in a place where a great deal of machine oil is used. • Do not install the air conditioner in a place where it is usually exposed to strong change winds such as in a seaside area or on the roof / upper floor of a building. • Do not install the air conditioner in a place where sulfureous gas maybe generated such as in a spa. • Do not install the air conditioner in a vessel or mobile crane.
Be careful with noise or vibrations • Do not install the air conditioner in a place where the noise or the hot air created by the outdoor unit will come into contact with your neighbours. • Install the air conditioner on a solid and stable foundation as this will reduce the transmission of noise and vibration that is produced from the outdoor unit. • If one indoor unit is operating, some sound may be audible from other indoor units that are connected within the same system (even when not in operation)
Check again.
46
• When power of the air conditioner is turned on, “Ticktock” sound is heard.
3-14. Re-Installation
Operates or stops automatically.
• Is the timer “ON” or “OFF”?
Does not operate.
• • • • t Silen
Air is not cooled or warmed sufficiently.
It’s strange.
Is there a power failure to the unit? Has the power supply been turned off? Has the power fuse or breaker blown? Has the protective device operated? (The operation lamp goes on.) • Is the timer “ON”? (The operation lamp goes on.) • Has the outdoor temperature gone out of the specified range for the outdoor unit? • Is the suction port or discharge port of the outdoor unit obstructed? • Are there any doors or windows open? • Is the air filter clogged with dust? • Is the discharge louver of the indoor unit set at appropriate position? • Is the air selection set to “LOW” or “MED” and is the operation mode set to “FAN Only”? • Is the setup temp. the appropriate temperature? • Has the outdoor temperature gone out of the specified range?
When the following symptoms are found, stop the unit operation immediately, turn off the power supply, and contact the dealer from where you have purchased the air conditioner. • Activation of the power supply causing the unit to operate in an unstable fashion (power on, power off, power on, power off etc). • The main power fuse often blows out, or circuit breaker is often activated. • Foreign matters or water have entered the unit by mistake. • When the unit fails to operate after the protective device (circuit breaker) has been removed. Not recommended. • Other unexplained symptoms or unit abnormalities, that cannot be explained.
Confirmation and check When a error has occurred in the air conditioner, the check code and the indoor unit No. will appear on the display part of the remote controller. The check code is only displayed during while the unit is operating. If the display disappears, operate the air conditioner according to the following “Confirmation of error history” for confirmation.
CODE No.
UNIT No.
R.C.
Check code
No.
Indoor unit No. in which an error has occurred
Confirmation of error history When a error has occurred on the air conditioner, the error history can be confirmed with the following procedure. (Up to 4 errors can be stored in the memory of the remote controller.) The history can be confirmed from both operating status and stop status.
TEMP.
2 FILTER RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
UNIT
1
3 Procedure
Description
47
SET
TEST
When pushing the and buttons at the same time for 4 seconds or more, the following display will appear. If [Service check] is displayed, the mode enters into the change error history mode.
1
CODE No.
UNIT No.
• [01 : Order of error history] is displayed in CODE No. window.
R.C.
No.
• [Check code] is displayed in CHECK window. • [Indoor unit address in which the error has occurred] is displayed in UNIT No. For every push of the is displayed in order.
2
,
button used to set temperature, the trouble history stored in memory
The numbers in CODE No. indicate CODE No. [01] (latest) → [04] (oldest). CAUTION Do not push the
3
CL
button because all the error history of the indoor unit will be deleted.
After confirmation, push the
TEST
button to return to the normal display.
1. Check the error codes according to the above procedure. 2. Ask an authorized dealer or qualified service (maintenance) professional to repair or maintain the air conditioner. 3. More details of the service codes are explained in the Service Manual.
4. REFRIGERANT PIPING SYSTEMATIC DRAWING 4-1. Inverter Unit (8, 10, 12HP) Model: MMY-MAP0802FT8, MAP1002FT8, MAP1202FT8 Propeller fan
FM Fan motor Sensor (TE1)
(Right side)
Strainer Pulse motor valve
(Left side)
Solenoid valve (SV12) (PMV2)
Main heat exchanger
Strainer Strainer
Check valve
Sub heat exchanger (Right side) Sub heat exchanger (Left side)
(PMV3)
4-Way valve
Check valve Solenoid valve (SV11)
Solenoid valve (SV5)
High-pressure sensor Solenoid Capillary Check joint tube valve (SV6) Capillary tube Strainer
Sensor (TL)
Solenoid valve (SV3D)
Highpressure switch Sensor (TD1)
Sensor (TS2) Solenoid valve (SV2)
Oil separator
Check valve
Capillary tube
Compressor 1 (Inverter)
Check joint
Check valve
Check valve
Solenoid valve (SV3C)
Strainer Strainer
Solenoid valve (SV3E)
Check valve
Check valve
Capillary tube
Capillary tube
Solenoid valve (SV42) Highpressure switch Sensor (TD2)
Sensor (TK2) Oil tank
Sensor (TK4)
Capillary tube
Capillary tube
Strainer
Solenoid valve (SV3A) Strainer
Check valve
Solenoid valve (SV3B) Check valve
Service valve of balance pipe
Service valve at liquid side
Service valve at discharge gas side
Check joint
Capillary tube
Sensor (TK3)
Sensor (TK1)
Strainer
LowSensor pressure (TS1) sensor
Strainer
Capillary tube Solenoid valve (SV41)
Liquid tank
Capillary tube
Compressor 2 (Inverter)
(PMV1)
Sensor (TO)
Main heat exchanger
Service valve at suction gas side
48
Accumulator
4-2. Explanation of Functional Parts Functional part name Solenoid valve SV3A
(Connector CN313: Blue) Open : Allows oil to return to the outdoor unit via the balance pipe.
SV3C
(Connector CN314: Black) Open : Pressurizes the oil tank..
SV3D
(Connector CN323: White) Open : Supplies oil to the compressor from the oil separator.
SV3E
(Connector CN323: White) Open : Turns on during operation and balances oil between compressors.
SV2
(Hot gas bypass) (Connector CN312: White) 1) Low pressure release function 2) High pressure release function 3) Gas balance function during stop time
SV4 1 SV4 2
(Gas balance control for compressor start-up) (Connector CN311: Blue) 1) For gas balance start 2) High pressure release function 3) Low pressure release function
SV5
(Connector CN310: White) 1) Increase of No. of heating indoor units, Gas balance function in defrost time 2) Low-pressure balance function of discharge gas pipe during all cooling operation
SV6
(Connector CN309: White) 1) Liquid bypass function for discharge temp. release (Cooling bypass circuit)
SV11
(Connector CN322: White) 1) For shutdown discharge gas (During all cooling operation and defrost operation)
SV12
(Connector CN319: White) 1) Flow-rate control function of refrigerant to sub heat exchanger during simultaneous operation 2) Flow-rate control function of refrigerant to sub heat exchanger during defrost operation (Connector CN317: Blue) 1) Cooling/Heating selection 2) Reverse defrost 3) Main-/Sub-heat exchanger selection
PMV1, 2
(Connector CN300, 301: White) 1) Super heat control function during all heating operation and mainly heating, partly cooling operation 2) Under-cool adjustment function during all cooling operation 3) Divided flow control function during mainly cooling, partly heating operation
PMV3
(Connector CN302: Red) 1) For flow-rate control of sub heat exchanger during simultaneous operation (Control function of heating divided flow) 2) A function preventive high pressure up during all cooling or all heating operation
Oil separator Temp. sensor
(Connector CN324: Red) Closed : Allows oil to collect/remain in the oil tank. Open : Allows oil to exit the oil tank.
SV3B
4-way valve
Pulse motor valve
Functional outline
1) Prevention for early drop of oil level (Decrease of flow-out of discharge oil to cycle) 2) Reserve function of surplus oil TD1, TD2
(TD1: Connector CN502: White, TD2: Connector CN503: Pink) 1) Protection of compressor discharge temp. 2) Releasing of discharge temp.
TS1
(Connector CN504: White) 1) Controls super heat of PMV1 and 2 during all heating operation and simultaneous operation
TS2
(Connector CN522: Black) 1) Controls indoor oil recovery during all cooling operation and mainly cooling, partly heating operation 2) Detects overheat of cycle.
TE
(Connector CN505: Green) 1) Controls defrost during all heating operation and simultaneous operation. 2) Controls outdoor fan during all heating operation and simultaneous operation.
TK1, TK2, TK3, TK4,
TK1: Connector CN514: Black, TK3: Connector CN516: Red,
TK2: Connector CN515: Green, TK4: Connector CN523: Yellow
1) Judges oil level of compressor. TL
(Connector CN521: White) 1) Detects under-cool during all cooling operation and simultaneous operation.
TO
(Connector CN507: Yellow) 1) Detects external ambient temperature.
49
Functional part name Pressure High pressure sensor sensor
Low pressure sensor
Heater
Functional outline (Connector CN501: Red) 1) Detects high pressure and uses it to control the capacity of the compressor. 2) Detects high pressure during all cooling operation and uses it to control the fan when cooling with low outside air. 3) Detects under-cool of the indoor unit of which heating thermo.-ON during all heating operation and simultaneous operation. 4) Controls outdoor fan rpm during mainly cooling, part heating operation. (Connector CN500: White) 1) Detects low pressure and uses it to control capacity of the compressor during all cooling operation and simultaneous operation 2) Detects low pressure and uses it to controls super heat during all heating operation and simultaneous operation
Compressor case heater (Compressor 1 Connector CN316: White, Compressor 2 Connector CN315: Blue) 1) Prevents liquid accumulation in the compressor Accumulator case heater (Connector CN321: Red) 1) Prevents liquid accumulation to accumulator
Balance pipe
1) Oil balancing pipe between outdoor unit (This unit does not use this Balance pipe.)
Operation mode Operation mode
Outline
1. All Indoor Unit(s) Operating for Cooling
Only cooling operation without heating operation Outdoor heat exchanger (Main heat exchanger) is used as a condenser.
2. All Indoor Unit(s) Operating for Heating
Only heating operation without cooling operation Outdoor heat exchanger (Main heat exchanger) is used as an evaporator.
3. Simultaneous operation
MIU for simultaneous operation
3-1. Mainly cooling, partly heating operation
Cooling/heating simultaneous operation with subjective cooling operation Outdoor heat exchanger (Sub heat exchanger) is used as a condenser.
3-2. Mainly heating, partly cooling operation
Cooling/heating simultaneous operation with subjective heating operation Outdoor heat exchanger (Main heat exchanger) is used as an evaporator.
4. Defrost
Using the reversing operation of the 4-way valve, ice on the outdoor heat exchanger is dissolved within a single cooling cycle.
For details of operation mode, refer to page 53 to 59.
50
Configuration of outdoor unit heat exchanger
Flow Selector Unit (FS Unit) RBM-Y1122FE Discharge gas pipe
Liquid pipe
Propeller fan
Strainer
Strainer Capillary tube
Capillary tube
Fan motor
Check valve
Suction gas pipe
SVS
Capillary tube
SVD SVDD
SVSS Strainer
To indoor liquid side
Main heat exchanger
To indoor gas side
RBM-Y1802FE Wind
Wind
* RBM-Y1801FE has two “SVS” valves. Discharge gas pipe
Liquid pipe
Strainer
Sub heat exchanger
Sub heat exchanger
Strainer Capillary tube
Capillary tube Check valve
Suction gas pipe
Capillary tube
SVD
SVS SVS SVDD
SVSS Strainer
Front side (Right)
Rear side (Left)
To indoor liquid side
To indoor gas side
RBM-Y2802FE * RBM-Y2802FE has three “SVS” valves and two “SVD”. Discharge gas pipe
Liquid pipe
Strainer
Strainer Capillary tube
Capillary tube Check valve
Suction gas pipe
Capillary tube SVD
SVS SVS SVS SVDD
SVSS Strainer
To indoor liquid side
Functional part name Solenoid valve
To indoor gas side
Functional outline
SVD
(Discharge gas block valve) 1) High pressure gas circuit during heating operation
SVS
(Suction gas block valve) 1) Low pressure gas circuit during cooling operation
SVDD
(Pressure valve) 1) For pressurizing when No. of heating indoor units increases.
SVSS
(Reducing valve) 1) For recovery of refrigerant of the stopped indoor unit of which cooling thermo-OFF 2) For reducing pressure when a No. of heating indoor units decreases.
51
4-3. Indoor Unit
Liquid side Gas side
Strainer
Capillary tube
Air heat exchanger at indoor side
Pulse Motor Valve (PMV) Distributor Sensor (TC2)
Sensor (TCJ)
Fan Sensor (TC1) Sensor (TA)
M
Fan motor
(NOTE) MMU-AP0071YH to AP0121YH type air conditioners have no TC2 sensor.
Functional outline
Functional part name Pulse Motor Valve PMV
(Connector CN082 (6P): Blue) 1) Controls super heat in cooling operation 2) Controls under cool in heating operation 3) Recovers refrigerant oil in cooling operation 4) Recovers refrigerant oil in heating operation
Temp. sensor
1. TA
(Connector CN104 (2P): Yellow) 1) Detects indoor suction temperature
2. TC1
(Connector CN100 (3P): Brown) 1) Controls PMV super heat in cooling operation
3. TC2
(Connector CN101 (2P): Black) 1) Controls PMV under cool in heating operation
4. TCJ
(Connector CN102 (2P): Red) 1) Controls PMV super heat in cooling operation 2) [MMU-AP0071 to AP0121YH only] Controls PMV under cool in heating operation
52
5. SYSTEM REFRIGERANT CYCLE DRAWING 5-1. Refrigerant Piping Systematic Diagram in System Selection of operation mode For the selection of each operation mode, refer to the below table: “Stop Once” this means the system does not operate for 3 minutes after operation before update has stopped. After update All cooling operation (OFF)
All cooling operation (OFF)
Before update
Mainly cooling, partly Mainly heating, partly All heating operation heating cooperation cooling operation (ON) (ON) (ON) Operation continues (OFF à ON)
Mainly cooling, partly heating cooperation (ON)
Operation continues (ON à OFF)
Mainly heating, partly cooling operation (ON)
Stop Once (ON à OFF)
Operation continues (As ON)
All heating operation (ON)
Stop Once (ON à OFF)
Operation continues (As ON)
Operation continues (OFF à ON)
Stop Once (OFF à ON)
Operation continues (As ON)
Operation continues (As ON)
Operation continues (As ON)
Operation continues (As ON)
Note) Phrases in the parentheses of the table indicate the status of the 4-way valve.
ON-OFF list of Flow Selector Unit (FS Unit) valve Outline of control valve output of FS unit (Basic operation) Indoor operation mode
SVD (High pressure circuit valve)
SVDD (Pressure valve )
SVS (Low pressure circuit valve)
SVSS (Reducing valve )
1. Stop (Remote controller OFF)
OFF
OFF
OFF
ON
2. Cooling thermo-OFF
OFF
OFF
OFF
ON
3. Cooling thermo-ON
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
4. Heating thermo-OFF 5. Heating thermo-ON 6. “E04” error is being detected
53
5-2. All cooling operation (Operation of cooling only) In high outside temperature (10°C or more: Criterion) Header unit
Follower unit
FM
FM
TE1
*
Main heat exchanger
*
Sensor TO
SV12
PMV2
PMV1
PMV3
4-Way valve
*
Main heat exchanger
*
PMV3
OFF
4-Way valve
OFF
SV11 TS1
SV5
Pd sensor
TS2
Pd sensor SV6
TS1
SV2
SV6
TL
Pd sensor
TS2
Pd sensor SV2
OS
OS
SV3D
SV3D
SV41
Liquid tank
SV42
HP
HP SV3C TK3
TK1
SV42
HP
Accumulator
HP SV3C
TD1
TD2
Compressor 2 (Inverter)
Compressor 1 (Inverter)
TD1
SV41
Compressor 1 (Inverter)
Liquid tank
Sensor TO
PMV2
SV11 SV5
TL
Main heat exchanger
TK2
TK3
TK1
Oil tank SV3E
Accumulator
TD2
Compressor 2 (Inverter)
SV12 PMV1
Main heat exchanger
TE1
TK2 Oil tank
TK4
SV3E
SV3A
TK4
SV3A SV3B
SV3B
Suction gas pipe Discharge gas pipe Liquid pipe
SVS
FS unit
SVS
SVD SVDD SVSS
Indoor unit
SVS
SVD
ST
SVDD SVSS
ST
ST
PMV
TC1
SVD SVDD SVSS
ST
ST
PMV
TC2 TCJ
SVS
SVD
SVDD SVSS
ST
ST
PMV
TC1
TC2 TCJ
ST
PMV
TC2 TCJ
TC1
TC2 TCJ
TC1
Cooling Cooling High pressure gas or condensed liquid refrigerant
Cooling Stop Low pressure gas refrigerant (Refrigerant recovery line)
Low pressure gas refrigerant
High pressure refrigerant (Push-in circuit)
4-way valve SV4 (n) SV5 SV6 SV11 SV12
Outdoor unit OFF SV3A (Note 1) SV3B OFF SV3C Control SV3D ON SV3E OFF PMV1, 2
Outdoor fan
Control
PMV3
Flow selector/Indoor unit Cooling thermo.-ON Stop SVD OFF SVD SVS ON SVS SVDD OFF SVDD SVSS ON SVSS PMV Control PMV
OFF OFF OFF Control ON Control Close
(Note 1) SV4 on the stopped compressor is ON.
54
OFF OFF OFF ON Close
In low outside temperature (15°C or less: Criterion) Header unit
Follower unit
FM
FM TE1
*
Main heat exchanger
*
SV12
PMV2
PMV1
PMV3
4-Way valve
*
Main heat exchanger
*
PMV3
OFF
4-Way valve
OFF
SV11 TS1
SV5
Pd sensor
TS1
TS2
Pd sensor SV6
SV2
SV6
TL
Pd sensor
TS2
Pd sensor SV2 OS
OS SV3D
SV3D
SV41
Liquid tank
SV42
HP
HP SV3C TK3
TK1
SV42
HP
Accumulator
HP SV3C
TD1
TD2
Compressor 2 (Inverter)
Compressor 1 (Inverter)
TD1
SV41
Compressor 1 (Inverter)
Liquid tank
Sensor TO
PMV2
SV11 SV5
TL
Main heat exchanger
TK3
TK1
TK2
TK2
Oil tank
Oil tank
TK4
SV3E
Accumulator
TD2
Compressor 2 (Inverter)
SV12 PMV1
Main heat exchanger
TE1 Sensor TO
TK4
SV3E
SV3A
SV3A SV3B
SV3B
Suction gas pipe Discharge gas pipe Liquid pipe
SVS
SVS
SVD
FS unit
SVDD SVSS
Indoor unit
SVS
SVD
ST
SVDD SVSS
ST
ST
PMV
TC1
SVD SVDD SVSS
ST
ST
PMV
TC2 TCJ
SVS
SVD
SVDD SVSS
ST
ST
PMV
TC1
TC2 TCJ
Cooling
Cooling
ST
PMV
TC2 TCJ
TC1
Cooling
TC1
TC2 TCJ
Stop
High pressure gas or condensed liquid refrigerant
Low pressure gas refrigerant (Refrigerant recovery line)
Low pressure gas refrigerant
High pressure refrigerant (Push-in circuit)
4-way valve SV4 (n) SV5 SV6 SV11 SV12
Outdoor unit OFF SV3A (Note 1) SV3B ON SV3C Control SV3D OFF SV3E OFF PMV1, 2
Outdoor fan
Control
PMV3
Flow selector/Indoor unit Cooling thermo.-ON Stop SVD OFF SVD SVS ON SVS SVDD OFF SVDD SVSS ON SVSS PMV Control PMV
OFF OFF OFF Control ON Control Close
(Note 1) SV4 on the stopped compressor is ON.
55
OFF OFF OFF ON Close
5-3. All heating operation (Operation of heating only) Header unit
Follower unit
FM
FM
TE1
*
Main heat exchanger
*
Sensor TO
SV12
PMV2
PMV1
PMV3
4-Way valve
SV11
*
Main heat exchanger
*
PMV3
TS1
4-Way valve
SV11
Pd sensor
TS1
Pd sensor
TS2
Pd sensor
SV2
SV6
TL
SV2
OS
OS
SV3D
SV3D
SV41
Liquid tank
SV42
HP
HP SV3C TK3
TK1
SV42
HP
Accumulator
HP SV3C
TD1
TD2
Compressor 2 (Inverter)
Compressor 1 (Inverter)
TD1
SV41
Compressor 1 (Inverter)
Liquid tank
OFF
SV5
TS2
Pd sensor SV6
Sensor TO
PMV2
OFF
SV5
TL
Main heat exchanger
TK2
TK3
TK1
TK2
Oil tank
Oil tank
TK4
SV3E
Accumulator
TD2
Compressor 2 (Inverter)
SV12 PMV1
Main heat exchanger
TE1
TK4
SV3E
SV3A
SV3A SV3B
SV3B
Suction gas pipe Discharge gas pipe Liquid pipe
SVS
SVS
SVD
FS unit
SVDD SVSS
Indoor unit
SVS
SVD
ST
SVDD SVSS
ST
ST
PMV
TC1
ST
ST
SVDD SVSS
ST
ST
PMV
TC1
TC2 TCJ
Heating
SVD SVDD SVSS
PMV
TC2 TCJ
SVS
SVD
ST
PMV
TC2 TCJ
Heating
TC1
TC1
TC2 TCJ
Heating
Stop
High pressure gas or condensed liquid refrigerant
Low pressure gas refrigerant (Refrigerant recovery line)
Low pressure gas refrigerant
High pressure refrigerant (Push-in circuit)
4-way valve SV4 (n) SV5 SV6 SV11 SV12
Outdoor unit OFF SV3A (Note 1) SV3B OFF SV3C Control SV3D ON SV3E OFF PMV1, 2
Outdoor fan
Control
PMV3
OFF ON OFF Control ON Control
Heating thermo.-ON SVD ON SVS OFF SVDD OFF SVSS OFF PMV Control
Close
(Note 1) SV4 on the stopped compressor is ON.
56
Flow selector/Indoor unit Heating thermo.-OFF SVD ON SVS OFF SVDD OFF SVSS OFF PMV Close
Stop SVD SVS SVDD SVSS PMV
OFF OFF OFF ON Close
5-4. Mainly Cooling, Partly Heating Operation (Cooling/heating simultaneous operation with subjective cooling operation) Header unit
Follower unit
FM
FM
TE1
TE1 Sensor TO
Main heat exchanger
Main heat exchanger
Main heat exchanger
SV12
PMV2
PMV1
PMV2
Operating for condenser
Operating for condenser
PMV3
4-Way valve
SV11
PMV3
ON
TS1
SV5
Pd sensor
TS1
Pd sensor
SV5 TS2
Pd sensor
SV2
SV6
TL
SV2
OS
OS
SV3D
SV3D
SV41
Liquid tank
SV42
HP
HP SV3C TK3
TK1
SV42
HP
Accumulator
HP SV3C
TD1
TD2
Compressor 2 (Inverter)
Compressor 1 (Inverter)
TD1
SV41
Compressor 1 (Inverter)
Liquid tank
ON
SV11
Pd sensor
TS2
SV6
TL
4-Way valve
TK2
TK3
TK1
TK2
Oil tank SV3E
Accumulator
TD2
Compressor 2 (Inverter)
SV12 PMV1
Sensor TO
Main heat exchanger
Oil tank
TK4
TK4
SV3E
SV3A
SV3A SV3B
SV3B
Suction gas pipe Discharge gas pipe Liquid pipe
SVS
SVS
SVD
FS unit
SVDD SVSS
Indoor unit
SVS
SVD
ST
SVDD SVSS
ST
ST
PMV
TC1
ST
ST
SVDD SVSS
ST
ST
PMV
TC1
TC2 TCJ
Cooling
SVD SVDD SVSS
PMV
TC2 TCJ
SVS
SVD
TC1
TC2 TCJ
Cooling
ST
PMV
TC1
TC2 TCJ
Stop
Heating
High pressure gas or condensed liquid refrigerant
Low pressure gas refrigerant (Refrigerant recovery line)
Low pressure gas refrigerant
High pressure refrigerant (Push-in circuit)
4-way valve SV4 (n) SV5 SV6 SV11 SV12
Outdoor unit ON SV3A (Note 1) SV3B OFF SV3C Control SV3D ON SV3E Control PMV1, 2
Outdoor fan
Control
PMV3
OFF OFF OFF Control ON Close (Note 2)
Cooling thermo.-ON SVD OFF SVS ON SVDD OFF SVSS ON PMV Control
Flow selector/Indoor unit Heating thermo.-ON SVD ON SVS OFF SVDD OFF SVSS OFF PMV Control
Control
(Note 1) SV4 on the stopped compressor is ON.
(Note 2) May be controlled.
57
Stop SVD SVS SVDD SVSS PMV
OFF OFF OFF ON Close
5-5. Mainly Heating, Partly Cooling Operation (Cooling/heating simultaneous operation with subjective heating operation) Header unit
Follower unit
FM
FM
TE1
*
Main heat exchanger
*
Sensor TO
SV12
PMV2
PMV1
PMV3
4-Way valve
SV11
*
Main heat exchanger
*
PMV3
TS1
4-Way valve
SV11
Pd sensor
TS1
Pd sensor
TS2
Pd sensor
SV2
SV6
TL
SV2
OS
OS
SV3D
SV3D
SV41
Liquid tank
SV42
HP
HP SV3C TK3
TK1
SV42
HP
Accumulator
HP SV3C
TD1
TD2
Compressor 2 (Inverter)
Compressor 1 (Inverter)
TD1
SV41
Compressor 1 (Inverter)
Liquid tank
ON
SV5
TS2
Pd sensor SV6
Sensor TO
PMV2
ON
SV5
TL
Main heat exchanger
TK2
TK3
TK1
TK2
Oil tank SV3E
Accumulator
TD2
Compressor 2 (Inverter)
SV12 PMV1
Main heat exchanger
TE1
Oil tank
TK4
TK4
SV3E
SV3A
SV3A SV3B
SV3B
Suction gas pipe Discharge gas pipe Liquid pipe
SVS SVD SVDD SVSS
Indoor unit
ST
ST
ST
PMV
ST
SVDD SVSS
ST
ST
ST
PMV
TC1
TC2 TCJ
Heating
SVD SVDD SVSS
PMV
TC1
SVS
SVD SVDD SVSS
TC2 TCJ
ST
PMV
TC1
TC2 TCJ
Heating
TC1
TC2 TCJ
Stop
Cooling
High pressure gas or condensed liquid refrigerant
Low pressure gas refrigerant (Refrigerant recovery line)
Low pressure gas refrigerant
High pressure refrigerant (Push-in circuit)
Outdoor unit 4-way valve ON SV3A SV4 (n) (Note 1) SV3B SV5 OFF SV3C SV6 Control SV3D SV11 ON SV3E SV12 Close (Note 2) PMV1, 2 Outdoor fan
SVS
SVS
SVD
FS unit
Control
PMV3
OFF OFF OFF Control ON Control
Cooling thermo.-ON SVD OFF SVS ON SVDD OFF SVSS ON PMV Control
Flow selector/Indoor unit Heating thermo.-ON SVD ON SVS OFF SVDD OFF SVSS OFF PMV Control
Close (Note 2)
(Note 1) SV4 on the stopped compressor is ON.
(Note 2) May be controlled.
58
Stop SVD SVS SVDD SVSS PMV
OFF OFF OFF ON Close
5-6. Defrost Header unit
Follower unit
FM
FM
TE1
TE1 Sensor TO
Main heat exchanger
Main heat exchanger PMV1
PMV3
4-Way valve
PMV2
PMV3
OFF
SV11 SV5
TS1
4-Way valve
Pd sensor
SV5
SV6
TL
Pd sensor
TS1 TS2
Pd sensor
SV2
SV2
OS
OS
SV3D
SV3D
SV41
Liquid tank
SV42
HP
HP SV3C TK3
TK1
SV42
HP
Accumulator
HP SV3C
TD1
TD2
Compressor 2 (Inverter)
Compressor 1 (Inverter)
TD1
SV41
Compressor 1 (Inverter)
Liquid tank
OFF
SV11
Pd sensor
TS2
SV6
TL
Main heat exchanger
SV12
PMV2
TK2
TK3
TK1
TK2
Oil tank SV3E
Accumulator
TD2
Compressor 2 (Inverter)
SV12 PMV1
Sensor TO
Main heat exchanger
Oil tank
TK4
TK4
SV3E
SV3A
SV3A SV3B
SV3B
Suction gas pipe Discharge gas pipe Liquid pipe
SVS
SVS
SVD
FS unit
SVDD SVSS
Indoor unit
ST
ST
ST
SVD SVDD SVSS
ST
ST
PMV
TC1
SVS
SVD SVDD SVSS
PMV
TC2 TCJ
SVS
SVD
SVDD SVSS
ST
ST
PMV
TC1
TC2 TCJ
Cooling
Heating
ST
PMV
TC1
TC2 TCJ
TC2 TCJ
Heating
TC1
Stop
High pressure gas or condensed liquid refrigerant
Low pressure gas refrigerant (Refrigerant recovery line)
Low pressure gas refrigerant
High pressure refrigerant (Push-in circuit)
Defrost operation is carried out during all heating operation or Mainly heating, part cooling operation.
4-way valve SV4 (n) SV5 SV6 SV11 SV12 Outdoor fan
Outdoor unit OFF SV3A (Note 1) SV3B ON SV3C Control SV3D OFF SV3E Close PMV1, 2 Stop (Note 2) PMV3
Flow selector/Indoor unit Cooling thermo.-ON Others SVD OFF SVD SVS ON SVS SVDD OFF SVDD SVSS ON SVSS PMV Control PMV Fan Control Fan
OFF OFF OFF Control ON Control Control
(Note 1) SV4 on the stopped compressor is ON.
(Note 2) May be controlled.
59
OFF ON OFF ON Control Stop
6. CONTROL OUTLINE 6-1. Indoor Unit 6-1-1. Control Specifications No.
Item
Outline of specifications
1
Power supply is reset.
(1) Identification of outdoor unit When the power supply is reset, the outdoor units are individually identified and communication is established. (2) Check code clear When the power supply is reset, the check code is also reset. If an abnormal status is still present upon restart the check code will be displayed again on the remote controller.
2
Operation select
(1) Based upon the operation command received from the remote controller or central controller, the operation mode is selected.
Remarks
Remote controller command
Control outline
STOP
Stops air conditioner.
FAN
Fan only operation
COOL
Cooling operation
DRY
Dry operation ∗
HEAT
Heating operation
COOL/HEAT AUTO
COOL/HEAT AUTO operation
∗ Concealed Duct High Static Pressure type air conditioner cannot operate in drying mode.
Heating operation is automatically selected with difference between the set point temperature and room temperature. 3
Room temp. control
(1) Set point temperature adjustment range on remote controller (°C) Allcooling
All heating
Wired type
18 to 29°C
18 to 29°C
Wireless type
18 to 30°C
16 to 30°C
(2) The set point temperature in heating operation can be offset using item code (DN) 06. Setup data Setup temp. correction
0
2
4
6
+0°C
+2°C
+4°C
+6°C
Heating suction temperature shift
Setup at shipment Setup data
2
4
Automatic capacity control
(1) The difference between the temperature reading taken from the Ta (room) sensor and the Ts (set point) selected on the remote controller is used to determine the demand frequency to the outdoor unit.
5
Air volume control
(1) The remote controller is used to select the modes “HIGH (HH)”, “MED (M)”, “LOW (L)” or “AUTO”. (2) The difference between the temperature reading taken from the Ta (room) sensor and the Ts (set point) selected is used to control the air volume setting when in “AUTO” mode.
60
HH > H+ > H > L+ > L > LL
No. 6
Outline of specifications
Item Prevention of cold air discharge
(1) In all heating operation, the upper limit of the fan tap is set by one with higher temperature of TC2 sensor and TCJ sensor. • When B zone has continued for 6 minutes, the operation shifts to C zone. • In defrost time, the control point is set to +6°C. (˚C) 32
A zone: OFF B zone: Over 26˚C, below 28˚C, LOW C zone: Over 28˚C, below 30˚C, MED D zone: Over 30˚C, below 32˚C, HIGH E zone: Ultra HIGH
D
30
E
C
28 26 20
Freeze prevention control (Low temp. release)
• In D and E zones, priority is given to remote controller air speed setup. • In A and B zones, “ ” is displayed.
B
16
7
Remarks
A
(1) In all cooling operation, the air conditioner operates as described below based upon temp. detected by TC1, TC2 and TCJ sensors. To prevent the heat exchanger from freezing, the operation stops. • When “J” zone is detected for 5 minutes, the command frequency becomes “S0” to the outdoor unit. • In “K” zone, the timer count is interrupted, and held. • When “1 ” zone is detected, the timer is cleared and the operation returns to the normal operation. • When the command frequency became S0 with continuation of “J” zone, operation of the the indoor fan in LOW mode until it reaches the “1 ” zone. It is reset when the following conditions are satisfied. Reset conditions 1) TC1 > 12°C and TC2 > 12°C and TCJ > 12°C 2) 30 minutes passed after stop. TC1 (˚C)
a
P1
K
Q1 J
P1
10°C (5°C)
Q1
0°C
(2) In all cooling operation, the air conditioner operates as described below based upon temp. detected by TC2 and TCJ sensors. • When “M” zone is detected for 45 minutes, the command frequency becomes “S0” to the outdoor unit. • In “N” zone, the timer count is interrupted and held. • When shifting to “M” zone again, the timer count restarts and continues. • If “L” zone is detected, the timer is cleared and the operation returns to normal operation. Reset conditions 1) TC1 > 12°C and TC2 > 12°C and TCJ > 12°C 2) 30 minutes passed after stop. (˚C)
L
TC2, TCJ
P2 N Q2 M
61
P2
5°C
Q2
–2.0°C
∗ In a Model without TC2, TC2 is not judged.
No.
Item
Outline of specifications
Remarks
8
Recovery control for cooling refrigerant and oil
(1) The indoor unit which stops operation, thermostat is OFF, or operates in FAN mode opens PMV of the indoor unit by the specified opening degree when cooling refrigerant or oil recovery signal is received from the outdoor unit. (2) Drain pump of 4-way air discharge cassette type and concealed duct type operate during recovery control mode.
• Recovery operation is usually executed every 2 hours.
9
Recovery control for heating refrigerant and oil
The indoor unit which stops operation, thermostat is OFF, or operates in FAN mode performs the following controls when the heating refrigerant/Oil recovery signal is received from the outdoor unit. 1) Opens PMV of the indoor unit by the specified opening degree. 2) Stops the fan. 3) Only 4-way Air Discharge Cassette type air conditioner rotates the indoor fan with intermittent operation for approximately 1 minute after recovery control. 4) Only 4-way Air Discharge Cassette type air conditioner rotates the indoor fan with intermittent operation for approximately 1 minute after recovery control as the outdoor unit. 5) After recovery control, drain pump of 4-way air discharge cassette type and concealed duct type will operate.
• In the indoor unit which thermostat is OFF, or operates in FAN mode, “ ” lamp goes on. • Recovery operation is usually executed every 1 hour.
10
Short intermittent operation compensation control
(1) For 5 minutes after the operation has started, the operation is continued even if entering thermostat-OFF condition. (2) However, if the thermostat has been turned off by changing the set up temp., the thermostat is OFF with even the above condition. The protective control has priority.
11
Drain pump control
(1) During “COOL” operation (including DRY operation), the drain pump operates. (2) While the drain pump operates, if the float switch works, the drain pump continues operation and a check code is displayed. (3) While the drain pump stops, if the float switch works, turn off the capacity demand command, stop the operation, and operate the drain pump. If the float switch continues operating for approx. 5 minutes, the operation stops and the check code is displayed. (4) In heating operation, if humidifier “provided” is judged, compressor “ON”, compressor “ON”, fan “ON”, and MAX (TC2, TCJ) > 33°C, the drain pump operates.
12
Elimination of remaining heat
(1) When the air conditioner stops in the “HEAT” mode, drive the indoor fan with “LOW” mode for approx. 30 seconds.
13
Auto louver control
(1) When the louver signal has been received from the remote controller, the louver operates if the indoor fan is operating. (2) In 4-way Air Discharge Cassette type, the discharge louver automatically directs downward if the operation stops. (3) In 4-way Air Discharge Cassette type, the discharge louver directs upward if the heating operation is being prepared.
14
Filter sign display (None in wireless type) ∗ Provided in the separately laid type TCB-AX21E.
(1) The operation time of the indoor fan is integrated and stored in memory, and the filter exchange signal is sent to the remote controller to display on the remote controller LCD after the specified time. (2) When the filter reset signal is received form the remote controller, time of the integrated timer is cleared. In this time, if the specified time has passed, the measured time is reset and LCD display disappears.
62
Check code [P10]
No.
Item
15
“ ” and “ ” display (Operation and heating stand-by)
Outline of specifications .......... Display on remote controller (1) • “P05” is one of displays of power wire missing. • “P05” of power cable is detected. • “COOL/DRY” operation cannot be performed because the other indoor unit is under “HEAT” operation. • “HEAT” operation cannot be performed because COOL priority is set (Outdoor I/F P.C. board SW11 1-bit is ON) and the other indoor unit is under “COOL/DRY” operation. • “FAN” operation cannot be performed because the system performs “Heat oil/Refrigerant recovery” operation. • There is a unit in which indoor overflow “P10” is detected. • There is a unit in which interlock alarm “P23” is detected. (2) The above indoor units unavailable to operate waits under condition of thermostat OFF.
Remarks • “
” goes on.
• “
” goes on.
.................. Display on remote controller (1) • HEAT thermostat is OFF. • During HEAT operation, the fan rotates with lower air speed than one specified in order to prevent discharge of cold draft or stops. (including case that defrost operation is being performed) • “HEAT” operation cannot be performed because COOL priority is set (Outdoor I/F P.C. board SW11 bit 1 is ON) and the other indoor unit is under “COOL/DRY” operation. (2) “HEAT standby” is displayed until the above conditions are released.
16
Selection of central control mode
(1) The contents which can be changed on the remote controller at indoor unit side can be selected by setup at the central controller side. (2) In case of operation from TCC-LINK central controller (TCB-SC642TLE, etc.) [Central control mode 1] : Cannot operate [Central control mode 2] : Cannot operate, stop, select mode, set up temp. [Central control mode 3] : Cannot select mode, set up temp. [Central control mode 4] : Cannot select mode (3) RBC-AMT21E (Wired remote controller) CENTRAL” While mode is the central control mode, “ lights on the display part of the remote controller.
63
If operation is performed from the remote controller “CENTRAL CONTROL” mode, the status is notified with receiving sound.
6-2. Outdoor Unit 6-2-1. Operation Start/Operation End The compressor, solenoid valve, pulse motor valve (PMV), outdoor fan, etc. are controlled by a command from the indoor controller. The follower outdoor unit starts/stops by a command from the header outdoor unit. No. 1
Item Pulse Motor Valve (PMV) control
Operation explanation and applied data, etc. (1) PMV control (using two PMV, 1 and 2) • Each PMV is controlled between 90 to 1000 pulses during operation. • In cooling operation, PMV opening is dependent upon detected readings from the TL sensor and Pd pressure sensor (sub-cool control). • In heating operation, PMV opening is dependent upon detected readings from the TS and TD sensors and the Ps pressure sensor (super-heat control). • Each PMV will be fully closed when the system is in ‘Standby’ or ‘No demand’ modes and when a malfunction in the system has occurred.
Remarks • During heating operation, PMV2 is 0 pulses and PMV may be controlled with only PMV 1, with a minimum of 45 pulses.
PMV opening
1000 PMV 2 550 500 90 45
PMV 1 Min.
Med.
Max.
(2) PMV3 control 1) PMV3 (Pulse Motor Valve 3) is controlled between 0 to 500 pulses during mainly cooling, part heating or mainly heating, part cooling operation. 2) PMV3 opening is controlled according to the demand capacity difference (HP) between the cooling capacity and the total heating capacity. 3) The PMV will be fully closed when the system is in ‘Standby’ or ‘No demand’ modes and when a malfunction in the system has occurred.
2
Outdoor fan control
(1) Fan control in all cooling operation 1) The outdoor fan speed/mode is determined by the detected Pd pressure value. 2) When cooling operation has started, the outdoor fan speed of the master unit is controlled using the detected Pd pressure value. (2) Fan control in all heating operation 1) The outdoor fan speed/mode is determined by the detected TE sensor value. 2) If a TE value > 25°C has been continuously detected for 5 minutes, the operation may stop. 3) After start up, this control is not available during the specified time after a defrost operation. 4) This operation may start and stop repeatedly when the system is undercharged. (3) Fan control for mainly cooling, part heating operation The outdoor fan speed (mode) is controlled according to the target of the Pd (Discharge pressure).
64
When TE temp. (ambient temperature) exceeds 25°C, Heating operation stops.
• The maximum fan speed differs depending on the outdoor HP.
No.
Item
Operation explanation and applied data, etc.
Remarks
3
Capacity control
1) The capacity request command received from the indoor controller determines the inverter frequency control of the outdoor unit. 2) The two compressors in each outdoor unit swap starting order on successive operation.
• Min. frequency: 26Hz
4
Oil level detection control
1) Measurement of sensors TK1 to TK4 is used to determine whether the correct amount of oil is present in the compressor case. 2) A comparison of measurements taken from TK1/TK2 with that of TK3/TK4 is used to judge whether there is sufficient oil in the compressor case. If there is insufficient oil in the compressor case, the system switches to the oil equalizing control method. 3) This control is performed during compressor operation.
• The detection is performed when one or both compressors are operated. • Adequate oil level (Standard) 1) The oil level of compressor 1 is adequate when TK1 - TK3 > 15°C 2) The oil level of compressor 2 is adequate when TK2 - TK3 > 15°C
(SV2)
Oil separator
(SV3D) OFF
(SV42)
(SV41)
(SV3C) (TD2)
OFF
Compressor 2
Compressor 1
(TD1) (TK3)
(TK1)
(TK2) Oil tank
ON (SV3E)
(TK4)
(SV3A) OFF
Balance pipe Packed valve
(SV3B)
65
No. 5
6
7
Item Oil short protective control
Refrigerant/Oil recovery control
Defrost control (Reverse cycle defrost method)
Operation explanation and applied data, etc. This control is provided to prevent oil shortage occurring in the compressors of each outdoor unit. The control is achieved by ON/OFF operation of the solenoid valves SV3A, SV3B, SV3C and SV3D. (1) Oil-short protective control The oil shortage protection control function stops the outdoor unit, if an oil shortage continues for 30 minutes, after 2 minutes, 30 seconds the outdoor unit restarts. If this function is activated on 3 successive occasions, an error check code (H07) is generated and the outdoor unit is stopped. (1) During cooling operation, this function is executed to regularly to recover the refrigerant/oil from the indoor units and connecting pipe-work back to the outdoor unit. This function is also performed to prevent stagnated refrigerant accumulating in the outdoor heat exchanger during low ambient cooling. The control is managed by the header outdoor unit. 1) Control conditions • Cooling oil recovery operation is executed approximately every 2 hours. 2) Contents of control • The recovery period lasts for approximately 2 or 3 minutes though this is dependant on the system capacity. (2) Refrigerant recovery control in heating room This function is executed regularly to recover the liquid refrigerant from the indoor unit. It is also used to recover oil present in the outdoor heat exchanger during the heating overload operation (except during defrost operation). The control is managed by the header outdoor unit. 1) Heating operation oil, recovery control is executed approximately every hour. 2) The period of recovery lasts for approximately 2 to 10 minutes though this is dependent upon the load condition. (3) Control for refrigerating / whilst oil recovery in simultaneous operation. This function is executed to recover the refrigerating oil accumulated in the low-pressure gas inter-unit piping. (regardless of all cooling operation/all heating operation). 1) Control condition • When the combined time of the compressor-ON has reached 95 minutes in simultaneous operation. 2) Control contents When the conditions have been satisfied, upon changing the indoor unit mode from heating to cooling, (stop the indoor fan) the oil is recovered for a period between 2 minutes 30 seconds to 10 minutes. The indoor unit in cooling operation continues operation. (1) Defrost start condition The defrost function is initiated when the measurement temperature taken from the TE sensor is lower than -2°C for a period of 25 minutes after compressor initial start up and 55 minutes after subsequent start ups. (2) Contents of control • If the outdoor units are combined, the minimum duration for the defrost operation is 2 minutes. (3) Defrost stop condition • The outdoor fan speed and compressor inverter frequency are determined by the measurement of Pd pressure during defrost operation.
66
Remarks
• Oil accumulated in the oil separator is returned to the compressor.
• Control for refrigerant/ oil recovery is performed approximately every 2 hours. • Recovery lasts for approximately 2 or 3 minutes though this is dependent upon the system capacity.
• Heating operation, oil recovery is executed approximately every hour. • Recovery lasts for approximately 2 to 10 minutes though this is dependent upon the load condition.
• During the defrost operation, all solenoid 4-way valves are OFF and all compressors are operating.
No.
Item
Operation explanation and applied data, etc.
8
Release valve control
(1) SV2 gas balance control In order to decrease the starting load on the compressor, SV2 valve is opened during the time the compressor is ‘OFF’, and the gas is balanced. (2) SV2 high pressure release control This function limits the pressure level during the low frequency operation of the inverter. (3) SV2 low pressure release control This function is used to prevent rapid pressure drop during transient operation of the unit. This is performed by the header unit only. The function is performed when required, except during ‘No demand’ status or when the system is in ‘Standby’. (4) SV41, SV42 valves 1) SV41, 42 low-pressure release control This function is used to prevent pressure dropping to low. The function is performed during defrost operation, heat start up, all cooling operation, or mainly cooling or part heating operation. • Control contents (Defrost/heating start pattern) Turn on SV41 and SV42 when PS pressure ≤ 0.1MPa, and turn off SV41 and SV42 when PS pressure ≥ 0.15MPa. • Control contents (All cooling operation, Mainly cooling, part heating operation) Turn on SV41 and SV42 when PS pressure ≤ 0.14MPa and Pd pressure ≤ 1.8MPa, and turn off SV41 and SV42 when PS pressure ≥ 0.24MPa and Pd pressure ≥ 2.2MPa 2) High pressure release control This function is for gas bypass control which emergently prevents the high pressure cut. Turn on SV41 and SV42 when Pd pressure ≥ 3.5MPa, and turn off SV41 and SV42 when Pd pressure ≤ 3.45MPa. (5) SV6 valve 1) Cooling bypass control This function is a liquid refrigerant bypass control to suppress the rise of the discharge temperature or the inside temperature of the compressor. Turn on SV6 valve when the discharge temperature (TD1 or TD2) becomes 96°C or higher and turns off when it drops below 84°C by bypassing liquid refrigerant. (6) PMV3 1) High pressure release control (All heating operation) This function suppresses the rise of high pressure during the inverter low frequency operation when in all heating operation mode. Set up PMV3 opening to 45 pulses when Pd pressure = 3.45MPa. 2) High pressure release control (All cooling operation) Set up PMV3 opening to 60 pulses when Pd pressure = 3.5MPa.
9
Frequency release control
(1) High pressure release control This function is to correct the operation command of the compressor and suppress the rise of high pressure. 1) Control contents The operation frequency is decreased by 1 step when Pd pressure ≥ 3.4MPa. It is decreased by 1 step every 10 seconds until Pd pressure drops below 3.4MPa. 2) Release condition • When Pd pressure ≤ 3.2MPa • When refrigerant recovery control starts in all heating mode • During defrost operation, stop, thermo OFF
67
Remarks
No.
Item
Operation explanation and applied data, etc.
10
Compressor stop due to high pressure release
Each compressor is stopped should the Pd pressure sensor reach a value of 3.5 MPa. This control is performed by the header unit and any follower units.
11
Case heater control
Heating is provided for both the compressor case and accumulator. When the compressor in any outdoor unit is stopped, the heater is switched on to prevent accumulation of refrigerant. After installation of a system, it should be powered for the specified period of time prior to operating a test run to prevent damage to the system. If the system has not been powered for a prolonged period of time, it is important to apply power for the specified period of time before resuming operation. This function is often performed in conjunction with the compressor winding heating control. When this occurs, a noise may be heard which is not an indication of a malfunction. (1) Contents of control • The function is performed during when the compressor is off. • When the TO sensor temp measures 28°C or higher the heater turns off and turns on when it change:measures 25°C or lower • The heater remains ‘ON’ for 10 minutes after the compressor has changed mode from Off to On.
12
IPDU control
The IPDU controls the inverter compressor by communicating a command frequency that controls the compressor speed, depending on any active releases. The main controls of the IPDU P.C. board are: (1) Current release control Feedback from the AC input current sensor (CT) is used to prevent the inverter input current exceeding its specified limit (2) Heat sink temperature detection control • Feedback from the thermistor (TH) on the compressor driving module is used to prevent the IGBT from overheating. The highest value is taken from IPDU 1 and IPDU 2 TH sensors. (3) Over-current protective control • When an over-current condition is detected by the IPDU, the compressor is stopped. (4) Compressor case thermo control • The compressor stops when the compressor case thermostat is activated. • Whenever this condition occurs, a 1 count is added to the system error count. • After a period of 2 minutes and 30 seconds, the compressor is reactivated and the error count cleared if the operation continues without further error for a period of 10 minutes or more. • If the error count reaches 4, the check code [H04] is displayed (for compressor 1) and [H14] (for compressor 2).
13
High pressure prevention control
(1) High pressure SW control • The high pressure switch is connected to the IPDU board and is in the normally closed condition. • When the high pressure switch is activated, the compressor is stopped. • Whenever this condition occurs, a 1 count is added to the system error count. • After a period of 2 minutes and 30 seconds, the drive to the compressor is reactivated and the error count is cleared if the operation continues with further error for a period of 10 minutes or more. • If the error count reaches 4, the check code [P04] is displayed.
68
Remarks
• A TH sensor is provided in each two IPDU.
• The case thermostat is normally closed and connected to interface P.C. board.
Other cautions 1. Cooling operation in low ambient temperatures 1) The indoor unit freeze prevention control system (TC sensor) may decrease the command frequency to the outdoor unit when low coil temperatures are detected. 2) The cooling capacity control may decrease the command frequency to the outdoor unit when low ambient temperature is detected. 3) When the discharge temperature sensor value reaches 60°C or below, the frequency may be increased above the required demand from the indoor unit.
2. PMV (Pulse Motor Valve) for outdoor unit 1) When the system power is turned on an audible “clicking” sound is omitted due to the PMV initialising, this is a normal condition. When the outdoor unit is situated near other sources of noise, this sound may not be noticeable. 2) Do not remove the driving part (head) of the PMV during operation as it may cause the PMV to malfunction. 3) When transporting or replacing the outdoor unit, never keep the driving part (head) removed from the PMV body as the valve will be closed and may result in damage or failure due to sealed liquid compression. 4) When refitting the driving part (head) to the body of the PMV, apply pressure until a “click” sound can be heard, complete the process by resetting the power to the system.
Release control list Release item
Operation
High pressure release
SV2 ON, SV41, SV42 ON PMV3=45 pulses (All heating operation), 60 pulses (All cooling operation) Operation frequency limit
Low pressure release
SV2 ON, SV41, SV42 ON, Operation frequency limit
Discharge temp. release
SV6 ON, Operation frequency limit
Current release
Operation frequency limit
Heat sink release
Outdoor fan speed up, Operation frequency limit
69
Oil equation control schematic diagram
Header outdoor unit (MMY-MAP1202FT8)
Follower outdoor unit (MMY-MAP1202FT8)
Unit to send oil
Unit to received oil FM
FM
TE1
*
Main heat exchanger
*
Sensor TO
SV12
PMV2
PMV1
PMV3
4-Way valve
*
Main heat exchanger
*
PMV3
OFF
4-Way valve
OFF
SV11 TS1
SV5
Pd sensor
TS2
Pd sensor SV6
TS1
Pd sensor
SV2
TL
Pd sensor
TS2
SV6
SV2 OS
OS SV3D
SV3D
SV41
Liquid tank
SV42
HP
HP
TK3
TK1
SV42
HP SV3C
TD1
TD2
Compressor 1 (Inverter)
TD1
SV41
HP
Accumulator
Compressor 2 (Inverter)
SV3C
Compressor 1 (Inverter)
Liquid tank
Sensor TO
PMV2
SV11 SV5
TL
Main heat exchanger
TK3
TK1
TK2 Oil tank
SV3E
TD2
Compressor 2 (Inverter)
SV12 PMV1
Main heat exchanger
TE1
TK2 Oil tank
TK4
SV3E
TK4
SV3A
SV3A SV3B
SV3B
70
Accumulator
7. APPLIED CONTROL 7-1. Indoor Unit 7-1-1. Setup of Selecting Function in Indoor Unit (Be sure to Execute Setup by a Wired Remote Controller) Execute the setup operation while the unit stops.
TEMP.
3 5 6
FILTER RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
4
UNIT
1
1
Push
SET
,
2
CL
, and
TEST
buttons simultaneously for 4 seconds or more.
The firstly displayed unit No. indicates the master indoor unit address in the group control. In this time, the fan of the selected indoor unit is turned on.
2 3 4
Every pushing UNIT button, the indoor unit numbers in the group control are successively displayed. In this time, the fan of the selected indoor unit only is turned on. Specify the item code (DN) using the setup temperature Select the setup data using the timer time
and
and
buttons.
buttons.
(When selecting the DN code to “33”, change the temperature indication of the unit from “°C” to “°F” on the remote controller.)
5
Push SET button. (OK if display goes on.) • To change the selected indoor unit, return to procedure . • To change the item to be set up, return to procedure .
3
6
Pushing
TEST
2
button returns the status to normal stop status.
71
Table: Function selecting item code (DN) (Items necessary to perform the applied control at the local site are described.) DN
Description
Item
0001 : 150H 0003 : 5000H
At shipment
01
Filter display delay timer
0000 : None 0002 : 2500H 0004 : 10000H
02
Dirty state of filter
0000 : Standard 0001 : High degree of dirt (Half of standard time)
0000 : Standard
03
Central control address
0001 : No.1 unit 0099 : Unfixed
0064 : No.64 unit
0099 : Unfixed
04
Specific indoor unit priority
0000 : No priority
0001 : Priority
0000 : No priority
06
Heating temp shift
0000 : No shift 0002 : +2°C
0001 : +1°C 0010 : +10°C (Up to +6 recommended)
0002 : +2°C (Floor type 0000: 0°C)
to
to
According to type
0d
Existence of [AUTO] mode
0000 : Provided 0001 : Not provided (Automatic selection from connected outdoor unit)
0001 : Not provided
0E
Follows operation mode of the header unit
0000 : Does not follow 0001 : Follows
0000 : Not provided
0F
Cooling only
0000 : Heat pump 0001 : Cooling only (No display of [AUTO] [HEAT])
0000 : Heat pump
10
Type
0000 : (1-way air discharge cassette) 0001 : (4-way air discharge cassette) to 0037
According to model type
11
Indoor unit capacity
0000 : Unfixed
0001 to 0034
According to capacity type
12
Line address
0001 : No.1 unit
to
0030 : No.30 unit
0099 : Unfixed
13
Indoor unit address
0001 : No.1 unit
to
0064 : No.64 unit
0099 : Unfixed
14
Group address
0000 : Individual 0002 : Follower unit of group
0001 : Header unit of group
0099 : Unfixed
19
Louver type (Adjustment of air direction)
0000 : Not provided 0001 : Swing only 0004 : [4-way Air Discharge Cassette type] and [Under Ceiling type]
1E
Temp difference of 0000 : 0 deg to 0010 : 10 deg [AUTO] mode (For setup temperature, reversal of COOL/HEAT by ± (Data value)/2) selection COOL → HEAT, HEAT →COOL
0003 : 3 deg (Ts±1.5)
28
Automatic restart of power failure
0000 : None
0000 : None
29
Operation condition of humidifier
0000 : Usual 0001 : Condition ignored (Detection control for heat exchanger temperature)
0000 : Usual
2A
Selection of option/ error input (CN70)
0000 : Filter input 0002 : None
0001 : Alarm input (Air washer, etc.)
0002 : None
2E
HA terminal (CN61) select
0000 : Usual
0001 : Leaving-ON prevention control
0000 : Usual (HA terminal)
30
Automatic elevating grille
0000 : Unavailable
0001 : Available
0000 : Unavailable
31
Ventilating fan control
0000 : Unavailable
0001 : Available
0000 : Unavailable
32
TA sensor selection
0000 : Body TA sensor
0001 : Remote controller sensor
0000 : Body TA sensor
33
Temperature unit select
0000 : °C (at factory shipment) 0001 : °F
40
Drain pump control
0000 : None 0002 : None
5d
High ceiling selection [4-way Air Discharge Cassette type] and [Under Ceiling type] (Air volume selection) 0000 : Standard filter 0001 : Super-long life filter 0003 : High efficiency filter
0001 : Restart
According to type
0000 : °C 0001 : Pump ON 0003 : Pump OFF
0003 : Pump OFF 0000 : Standard
[Concealed Duct Standard type] 0000 : Standard static pressure (40Pa) 0001 : High static pressure 1 (70Pa) 0003 : High static pressure 2 (100Pa) 0005 : Correspond to quiet sound 0006 : Low static pressure (20Pa) 60
Timer set (Wired remote controller)
0000 : Available (Operable) 0001 : Unavailable (Operation prohibited)
0000 : Available
62
Anti-ceiling smudging control
0000 : Clear
4- way Air Discharge Cassette type only
72
TYPE Item code [10] Setup data
Type
Abbreviated Model name
0000
1-way Air Discharge Cassette
MMU-AP XXX SH
0001
4-way Air Discharge Cassette
MMU-AP XXX H
0002
2-way Air Discharge Cassette
MMU-AP XXX WH
0003
1-way Air Discharge Cassette (Compact type)
MMU-AP XXX YH
0004
Concealed Duct Standard
MMD-AP XXX BH
0005
Slim Duct
MMD-AP XXX SPH, SH
0006
Concealed Duct High Static Pressure
MMD-AP XXX H
0007
Under Ceiling
MMC-AP XXX H
0008
High Wall
MMK-AP XXX H
0010
Floor Standing Cabinet
MML-AP XXX H
0011
Floor Standing Concealed
MML-AP XXX BH
0013
Floor Standing
MMF-AP XXX H
~
—
Indoor unit capacity Item code [11] Setup data
Model
0001
007
0003
009
0005
012
0007
015
0009
018
0011
024
0012
027
0013
030
0015
036
0017
048
0018
056
0021
072
0023
096
~
—
73
7-1-2. How to Set Up the Cooling Only Indoor Unit When connecting an indoor unit for use in cooling only. A flow selector unit is not connected. It is necessary to setup the unit. Perform setup as per the following procedure. Setup of the indoor unit is performed by use of a wired remote controller. If a wired remote controller is not used, for setup purposes a wired controller must be temporarily connected. When using the air conditioner with a wireless remote controller, select “Cooling Only” on the wireless remote controller after the below setup. Use of the wireless remote controller can be referred to in the manual supplied with the wireless remote controller. Change the setup during off status. CODE No.
UNIT No.
R.C.
No.
TEMP.
4 1 6 Procedure
FILTER RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
3 2 5
UNIT
Description SET
CL
TEST
Push + + buttons simultaneously for 4 seconds or more and display part will flashes as shown in the figure.
CODE No. SETTING
1
UNIT No.
Check that the displayed item code is [10].
R.C.
TEST
No.
• If the item code displayed is not [10], push button to erase the display and restart the operation from the first step. TEST button, the operation of the remote (After pushing the controller will not function for a short period.) (* The display changes according to the indoor unit model.) In group control, the firstly displayed indoor unit No. becomes the header unit.
2
Each pushing of the [UNIT] button, changes the indoor unit number within the group. Select the indoor unit that requires setup. The indoor unit selected can be confirmed at this time as the louver and fan will operate.
3
Use Use
and
buttons of the set temperature to specify the item code [0F].
and
4
buttons on the timer time to select the setup data [0001]. CODE No.
Setup data
0000
0001
Cooling Only setup
Heat pump
Cooling Only
UNIT No.
∗∗ ∗∗ R.C.
Push
SET
No.
button at this time, if the display changes from flashing to lit this confirms setup is complete.
• To change the setup of a different indoor unit other than the selected unit restart operation from Procedure
5
• In a group control, setup change of all the indoor units in the group is necessary. To change the setup of the group other than the selected one, restart operation from Procedure CAUTION • Pushing
Cooling Only and Heat pump cannot be connected in the same group.
CL
button clears the set up contents which has been previously set.
• In this case, restart from Procedure 2 . When the setup has completed, push
6
TEST
button. (The setup is determined.)
TEST
Pushing the button deletes the display and returns to the normal stop TEST button has been pushed, the operation of status. (For some time after the remote controller will not function for a short period.)
74
2.
2.
7-1-3. Setting When Connecting Multiple Indoor Units to a FS unit Cautions to connection of indoor unit • When connecting multiple indoor units to a single FS unit, it is necessary to set up the Item code. This should be done after the addressing of the units. • When connecting multiple indoor units to a single FS unit, only group control is available. Remote controllers cannot be connected to individual units. FS unit Piping
Indoor unit
Control wiring between indoor unit and FS unit
Remote controller Group control
n Usage/Features It is not possible to group control indoor units that are connected to more than one FS unit. Piping
FS unit
Indoor units off of a single FS unit cannot be individually controlled.
FS unit
FS unit
Piping
Indoor unit
Control wiring between indoor unit and FS unit Remote controller
Piping
Indoor unit
Control wiring between indoor unit and FS unit
NG
Remote controller
Group control
NG
How to set up Item code
1
VENT
TEST
Push + buttons simultaneously for 4 seconds or more. • is displayed in the UNIT No. window. • At this time, the fans of all the indoor units in the group control start the fan operation.
CODE No. SET DATA SETTING UNIT No.
R.C.
2 3 4 5
Using the set temperature buttons , select the Item code “- ”.
/
2
Change SET DATA to “ ” using the timer / . buttons Push
SET
5 4
button.
TEST
Push button. This confirms the setup has finished.
75
No.
TEMP.
FILTER RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
UNIT
1 3
n In case of not setting 01 to Item code “0E” When more than one indoor unit has been set up as a group to one FS unit and you have forgotten to set 01 on Item code “0E” on all the indoor units, the following may occur: 1) When AUTO operation is selected on the remote controller and cooling operation and heating operation are required, hot air may be discharged from the cooling operation unit or cool air may be discharged from the heating operation unit (or fan stops). However in case of 2 , “L18” error code is output and the air conditioner stops.
1 High-pressure gas
FS unit
High-pressure gas
High-pressure gas
Suction gas pipe Highpressure
Discharge gas gas pipe
SVS
Highpressure gas
SVSS SVDD
Liquid
Liquid
Highpressure gas
Highpressure gas Liquid
SVD
Liquid pipe
Liquid Indoor unit SVD SVDD SVS SVSS
Control wiring between indoor unit and FS unit
ON OFF OFF OFF
Heating operation
Cooling operation
Cooling operation
Hot air
Hot air
Hot air
Low-pressure gas
Low-pressure gas
Low-pressure gas
2 FS unit Suction gas pipe Discharge gas pipe
Lowpressure gas
SVS SVSS SVDD
Liquid
Liquid pipe Liquid SVD SVDD SVS SVSS
Liquid
Liquid
SVD
Indoor unit Control wiring between indoor unit and FS unit
OFF OFF ON ON
Cooling operation
Heating operation
Heating operation
Cool air
Cool air
Cool air
2) When the cooling thermostat of the indoor unit that is connected to the FS unit has been off, the refrigerant will not flow and cooling air may not discharge evenly if the thermostats of the other cooling operation units are on.
3 FS unit Suction gas pipe SVS SVSS
Discharge gas pipe
SVDD
SVD
Liquid pipe
Indoor unit SVD SVDD SVS SVSS
OFF OFF OFF ON
Control wiring between indoor unit and FS unit
Cooling operation Thermo OFF
76
Cooling operation Thermo ON
Cooling operation Thermo ON
7-1-4. Applied Control in Indoor Unit n Remote location ON/OFF control box (TCB-IFCB-4E) [Wiring and setup] • Use the exclusive connector for connection with the indoor control P.C. board. • In a group control, the system can operate when connecting with any indoor unit (Control P.C. board) in the group. However when taking out the operation/error signal from the other unit, it is necessary to take out from each unit individually.
(1) Control items 1) Start/Stop input signal : Operation start/stop in unit 2) Operation signal : Output during normal operation 3) Error signal : Output during alarm (Serial communication error or indoor/outdoor protective device) operation
(2) Wiring diagram using remote control interface (TCB-IFCB-4E) Input Output
IFCB-4E : No voltage ON/OFF serial signal No voltage contact for operation, error display Contact capacity: Below Max. AC240V 0.5A
Indoor control P.C. board
Start/Stop input COM (GND) Remote controller prohibition/clear input Operation signal output COM (+12V) Error signal output
Remote location ON/OFF control box (TCB-IFCB-4E)
1 2 3 4 5 6
1 2 3 4
ON/OFF serial signal input COM
CN06
1 2 3 4 5 6
CN61 T10 (YEL)
Operation signal output
CN13
Error signal output
Power supply 220–240V, ~50Hz
77
n Ventilating fan control from remote controller [Function] • The start/stop operation can be operated from the wired remote controller when air to air heat exchanger or ventilating fan is installed in the system. • The fan can be operated even if the indoor unit is not operating. • Use a fan which can receive the no-voltage A contact as an outside input signal. • In a group control, the units are collectively operated and they can not be individually operated.
(1) Operation Handle a wired remote controller in the following procedure. ∗ Use the wired remote controller during stop of the system. ∗ Be sure to set up the wired remote controller to the header unit. (Same in group control) ∗ In a group control, if the wired remote controller is set up to the header unit, both header and follower units are simultaneously operable.
1 2 3 4
SET
CL
TEST
Push concurrently + + buttons for 4 seconds or more. The unit No. displayed firstly indicates the header indoor unit address in the group control. In this time, the fan of the selected indoor unit turns on. UNIT
Every pushing button, the indoor unit numbers in group control are displayed successively. In this time, the fan of the selected indoor unit only turns on. Using the setup temp
or
Using the timer time or The setup data are as follows: Setup data
button, specify the item code
button, select the setup data. (At shipment: )
Handling of operation of air to air heat exchanger or ventilating fan
5
Unavailable (At shipment) Available
SET
Push button. (OK if display goes on.) • To change the selected indoor unit, go to the procedure ). • To change the item to be set up, go to the procedure ).
3
6
!.
Pushing
TEST
2
returns the status to the usual stop status.
(2) Wiring Relay (DC12V, procured locally) CN32 1 1 FAN DRIVE (2P WHI) 2 2
Outside control input of fan To terminal
Indoor control P.C. board Note) Determine the cable length between the indoor control P.C. board and the relay within 2m.
78
4-way Air Discharge Cassette type 1-way Air Discharge Cassette type (2 series) Concealed Duct Standard type model : Slim Duct type Under Ceiling type High Wall type Corresponds up to a relay in which rated current of the operation coil is approx. 75mA Other type models: Correspond up to a relay in which rated current of the operation coil is approx. 16mA (Does not correspond to a terminal block type relay on the market.)
n Leaving-ON prevention control [Function] • This function controls the indoor units individually. It is connected with cable to the control P.C. board of the indoor unit. • In a group control, it is connected with cable to the indoor unit (Control P.C. board), and the item code - is set to the connected indoor unit. • It is used when the start operation from outside if unnecessary but the stop operation is necessary. • Using a card switch box, card lock, etc, the forgotten-OFF of the indoor unit can be protected. • When inserting a card, start/stop operation from the remote controller is allowed. • When taking out a card, the system stops if the indoor unit is operating and start/stop operation from the remote controller is forbidden.
(1) Control items 1) Outside contact ON : The start/stop operation from the remote controller is allowed. (Status that card is inserted in the card switch box) 2) Outside contact OFF : If the indoor unit is operating, it is stopped forcedly. (Start/Stop prohibited to remote controller) (Status that card is taken out from the card switch box) ∗ When the card switch box does not perform the above contact operation, convert it using a relay with b contact.
(2) Operation Handle the wired remote controller switch in the following procedure. ∗ Use the wired remote controller switch during stop of the system.
1 2 3 4 5
Push concurrently
SET
CL
+
Using the setup temp
or
Using the timer time Push Push
SET
TEST
+
or
TEST
buttons for 4 seconds or more. button, specify the item code
-.
button, set to the setup data.
button. button. (The status returns to the usual stop status.)
(3) Wiring
Relay (procured locally) CN61 T10 1 1 (YEL) 2 2 3 4 5 6
3 4 5 6
* In the figure, the contact indicates a status that the card is taken out.
Indoor control P.C. board
Power supply Outside contact (Card switch box, etc: Procured locally)
Note) Determine the cable length between the indoor control P.C. board and the relay within 2m.
n Demand control from indoor unit When the relay is turned on, a forced thermostat-OFF operation starts. • Wiring example CN73
Relay (procured locally) Note) Determine the cable length between the indoor or outdoor control P.C. board and the relay within 2m.
1 1
EXCT 2 2 (2P plug: RED)
Relay coil signal
Indoor control P.C. board
79
7-2. Outdoor Unit 7-2-1. Applied Control in Outdoor Unit The following functions become available by setting the switches on the outdoor interface P.C. board. Function
No. 1
Outdoor fan high static pressure shift
Switch No.
Bit
SW10
2
Interface P.C. board of outdoor unit
Switch position detail
SW10 Bit 2
For setup of outdoor fan high static pressure shift
7-2-1-1. Outdoor fan High Static Pressure Shift n Usage/Features This function is set when connecting a duct to the discharge port of the outdoor unit.
n Setup Turn “Bit 2” of the dip switch [SW10] on the interface P.C. board of the outdoor unit to ON.
n Specifications The outdoor fan high static pressure shift function increases the fan speed on the outdoor unit to enable a discharge duct to be installed on the discharge port - the design of the ducting should be such that a static pressure of 35 Pa is not exceeded. This function should be executed where the discharge ducting static pressure exceeds 15 Pa. 45Pa or more : For detail of adjustment, consult with the sales subsidiary. The discharged air volume from each outdoor unit is shown in the table below: Capacity rank (MMY-MAP) Standard air volume of outdoor unit (m³/min.)
80
0801 type
1001, 1201 type
165
175
7-2-2. Applied Control in Outdoor Unit The following functions are available by using a separately supplied P.C. board. Set up the switches on the outdoor unit (U1). No.
Function
Switch No.
Bit
Connector No.
Used control P.C. board
1
Power peak-cut control (Standard)
SW07
1
CN513
TCB-PCDM2E
2
Power peak-cut control (Expansion)
SW07
1,2
CN513
TCB-PCDM2E
3
Snowfall fan control
—
—
CN509
TCB-PCMO2E
4
External master ON/OFF control
—
—
CN512
TCB-PCMO2E
5
Night operation control
—
—
CN508
TCB-PCMO2E
6
Operation mode selection control
—
—
CN510
TCB-PCMO2E
Connector position detail
Outdoor unit interface P.C. board
CN508 Red
CN509 Black
CN510 White
CN513 Blue
CN511 Green
Switch position detail
SW07
81
Bit 1
For power peak-cut control selection
Bit 2
For power peak-cut control (expansion) selection
7-2-2-1. Power Peak-cut Control (Standard) Operation
Header outdoor unit interface P.C. board SW07 Set up Bit 1.
CN513 (BLU)
The upper limit capacity of the outdoor unit is restricted based on the demand request signal from outside. L1 : Display lamp during power peak-cut control SW1 : Power peak-cut ON switch (ON during demand, OFF in normal time) ∗1 SW2 : Power peak-cut OFF switch (OFF during demand, ON in normal time) ∗1
(Setup to header unit only)
Connection cable Power peak-cut control board
PJ17 (4P WHI)
*1 Input signals of SW1 and SW2 are acceptable even if they are longer then pulse input (100mm.sec.) or serially made. However do not turn on SW1 and SW2 simultaneously. ∗ Be sure to prepare a contact for each terminal.
DC 1.2V
OFF
ON
SW2
SW1
Operation
Relay contact capacity of “operation” port
L1
In case of serial signal
In case of pulse signal
Below AC240V 0.5A (COSØ = 100%) Below DC24V 1A (Non-inductive load) Note) When connecting non-inductive load such as relay coil to L1 load, insert the noise surge absorber CR (In case of AC) or counter electromotive-proof diode (In case of DC) into the bypass circuit.
Display
Power supply Max. AC240V
Power peak-cut control board: TCB-PCDM2E Outdoor unit destination to be connected becomes the header outdoor unit (U1).
Procured locally
Setup when Power peak-cut control requested Power peak-cut control board (TCB-PCDM2E)
Outdoor unit interface P.C. board
SW1
SW2
L1
SW07: Bit 1 OFF
SW07: Bit 1 ON
Power peak-cut ON signal is input.
ON
OFF
ON
0% (Forced stop)
Capacity 60% (Upper limit restriction)
Power peak-cut OFF signal is input.
OFF
ON
OFF
100% (Normal operation)
100% (Normal operation)
Setup positions of header outdoor unit interface P.C. board
Connector position detail CN513 Blue
Switch position detail
OFF
Operation stop to 100%
ON
ON 60% to 100%
SW07 Bit 1
82
7-2-2-2. Power Peak-cut Control (Expansion) Header outdoor unit interface P.C. board
Operation SW07 Set up Bit 1. ON Bit 2.
CN513 (BLU)
(Setup to Header unit only)
Connection cable Power peak-cut control board
*1
PJ17 (4P WHI)
Input signals of SW1 and SW2 are acceptable even if they are upper than pulse input (100mm. sec.) or serially made. ∗ Be sure to prepare a contact for each terminal.
DC 1.2V OFF
ON
SW2
SW1
The upper limit capacity of the outdoor unit is restricted based on the demand request signal from outside. L1 : Display lamp during Power peak-cut control SW1 : Power peak-cut ON switch ∗1 SW2 : Power peak-cut OFF switch ∗1
Operation
Display
L1 Power supply MAX AC240V
Relay contact capacity of “operation” port Below AC240V 1A (COSØ = 100%) Below DC24V 2A (Non-inductive load) Note) When connecting non-inductive load such as relay coil to L1 load, insert the noise surge absorber CR (In case of AC) or counter electromotive-proof diode (In case of DC) into the bypass circuit. Power peak-cut control board: TCB-PCDM2E Outdoor unit destination to be connected becomes the header outdoor unit (U1).
Procured locally
Setup at power peak-cut control (expansion) request Outside power peak-cut request SW1
Display lamp
Power Peak-cut request Outdoor wire interface P.C. board (SW07/ Bit 2 ON)
SW2
L1
OFF
OFF
OFF
ON
OFF
ON
80% (Upper limit restriction)
85% (Upper limit restriction)
OFF
ON
ON
60% (Upper limit restriction)
75% (Upper limit restriction)
ON
ON
ON
Setup positions of header outdoor unit interface P.C. board
SW07 : Bit 1 OFF
SW07 : Bit 1 ON
100% (Normal operation)
100% (Normal operation)
0% (Forced stop)
60% (Upper limit restriction)
Connector position detail CN513 Blue
Switch position detail
Bit 1
SW07 Bit 2
83
OFF Operation stop to 60%, 80%, 100% ON
ON 60% to 60%, 75%, 85%, 100%
ON
Power peak-cut (expansion) ON
7-2-2-3. Snowfall Fan Control Header outdoor unit interface P.C. board
Operation The outdoor unit fan operates when a Snowfall signal is received. Input signal
Terminal
Operation
CN509 (4P BLK)
ON Connection cable External master ON/OFF control board
PJ17
OFF COOL (SMC)
(4P WHI)
ON OFF
HEAT COOL
COM
Snowfall fan control (Operates outdoor unit fan.)
Usual operation (Releases control.)
The control contents are accepted during leading and trailing of the input signal. (The status of leading and trailing should be held for 100mm. sec. or more.) External master ON/OFF control board : TCB-PCMO 2E Outdoor unit destination to be connected becomes the header outdoor unit (U1).
SMC
SMC: Snowfall detection switch Procured locally (Snow sensor)
7-2-2-4. External master ON/OFF control Header outdoor unit interface P.C. board
Operation The outdoor unit starts or stops the system. Input signal
Terminal CN512 (4P BLU) Connection cable External master ON/OFF control board
PJ17
COOL (SMC)
ON
Heat (SMH)
ON
Operation
Starts collectively indoor units. OFF
(4P WHI)
Stops collectively indoor units. OFF
The control contents are accepted during trailing of the input signal. (The status of trailing should be held for 100mm. sec. or more.) HEAT COOL
COM
SMC
NOTES 1) Do not turn on COOL and HEAT terminals concurrently. 2) Be sure to prepare a contact for each terminal. Outside signal: No voltage pulse contact External master ON/OFF control board : TCB-PCMO 2E Outdoor unit destination to be connected becomes the header outdoor unit (U1).
SMH
Procured locally
SMC: Input signal for start. SMH: Input signal for stop.
84
7-2-2-5. Night Operation Control
Header outdoor unit interface P.C. board
CN508 (4P RED)
Operation Reduce emitted noise during night by resting the compressor and fan speed. Terminal ON
Night (sound reduction) operation control
Connection cable External master ON/OFF control board
PJ17
(4P WHI)
COOL (SMC)
Operation
Input signal
OFF ON
Usual operation
OFF
HEAT COOL
COM
The control contents are accepted during leading and trailing of the input signal. (The status of leading and trailing should be held for 100mm. sec. or more.) Capacity criterion during night operation control Capacity during control indicates values as described in the following table.
Procured locally
Capacity
Night operation sound reduction dB (A)
COOL
HEAT
1201 type
50
Approx. 55%
Approx. 45%
1001 type
50
Approx. 65%
Approx. 55%
0801 type
50
Approx. 80%
Approx. 70%
SMC
SMC : Input signal for night operation. External master ON/OFF control board : TCB-PCMO 2E Outdoor unit destination to be connected becomes the header outdoor unit (U1).
(Against Max. capacity)
7-2-2-6. Operation Mode Selection Control Header outdoor unit interface P.C. board
CN510 (4P WHI) Connection cable External master ON/OFF control board
PJ17
HEAT COOL
(4P WHI)
COM
SMC SMH
Operation This control can be operated with the operation mode which is permitted by SMC or SMH. The indoor unit operating by operation mode without permission is as follows: 1) Display on remote controller (Mode select controlled)” goes on. “ 2) Indoor fan In FAN mode: Fan normally operates. In COOL mode: Fan normally operates. In HEAT mode: Fan operates with ultra low speed. * Be sure to prepare a contact for each contact terminal. Outside signal: No voltage serial contact SMC: COOL mode designated input switch SMH: HEAT mode designated input switch External master ON/OFF control board : TCB-PCMO 2E Outdoor unit destination to be connected becomes the header outdoor unit (U1).
Procured locally
85
8. TEST OPERATION
2. In case that a central control system is connected (Before address setup)
8-1. Procedure and Summary of Test Operation A test operation is executed in the following procedure. When a trouble or an error occurs in each step, remove causes of a trouble or an error referring to the section “9. Troubleshooting”.
Central control units
Check the basic items, mainly the installation work. Be sure to enter the check results in the check list 1 and 2.
Check before test operation
Check the main power supply is turned on.
U1 U2 U3 U4
4
Other refrigerant line
It is the check after the power has been turned on. Check the refrigerant circuit system is normally turned on.
2
5
Header unit (A)
U3 U4
Other refrigerant line
3 Follower unit (B)
U3 U4
Follower unit (C)
U3 U4
U3 U4
Outdoor unit
Start the address setup in the outdoor/indoor units. (NOTE) The operation does not start by only power-ON.
Set up the addresses.
U1 U2
U1 U2
1
U5 U6
U1 U2
U5 U6
U1 U2
To indoor unit 3-phase 380-415V Leak interception
6
6
END
Main switch
8-2. Check Items before Test Operation
U1 U2
Main check items for electric wiring
86
The communication system differs from that of R22 or R407 refrigerant “Modular Multi system” air conditioner. Check again cautious points on wiring.
2
4
Follower unit (B)
U3 U4
1
Follower unit (C)
U3 U4
No. U1 U2
U5 U6
U1 U2
U5 U6
U1 U2
5
5
Main switch U1 U2
Indoor unit
A B
U1 U2
U1 U2
A B
A B
U1 U2
A B
Remote controller
Main check items
Are indoor and outdoor communication lines of the header unit connected to U1/U2 terminals?
Is the relay connector between U1/U2 terminal and U3/U4 terminal removed? (Set up at shipment from the factory)
Is the communication line between each outdoor units connected to U5/U6 terminal?
Is the terminal resistance (SW30-2) on the interface P.C. board of the header unit turned on? (Set up at shipment from the factory)
Is the end terminal of the shield cable grounded?
Note)
A B
A B
Remote controller
Remote controller
Remote controller
A B
Main check items
Are indoor and outdoor communication lines of the header unit connected to U1/U2 terminals?
Is the relay connector between U1/U2 terminal and U3/U4 terminal removed? (Set up at shipment from the factory) (Before address setup, remove the relay connector.)
Is the communication line between outdoor and indoor units connected to U5/U6 terminal?
Is the communication line of the central control system connected to the header unit U3/U4 terminals of each refrigerant line? (The communication line of the central control system may be connected to the communication lines of the indoor/outdoor communication lines.)
Is the terminal resistance (SW30-2) on the interface P.C. board of the header unit turned on? (Set up at shipment from the factory) (After address setup, turn off SW30-2 of the header unit except the smallest unit after check of trial operation.)
Is the end terminal of the shield cable grounded?
When the refrigerant line and the central control system of the custom air conditioner are connected: → Are TCC-LINK adaptors correctly connected? → When the digital inverter air conditioner operates with group operation, twin, or triple operation, are the adopters connected to the header unit of the indoor unit?
1-phase 230V Leak interception
Main switch
A B
Check
U5 U6
Earth
3-phase 380-415V Leak interception
U1 U2
U3 U4
Outdoor unit
1. In case that a center control system is not connected:
U1 U2
1-phase 230V Leak interception
3
Main switch Header unit (A)
U1 U2
Indoor unit
Prior to the test operation, check the following items so that there is no trouble in the installation work.
No.
U5 U6
Earth
Carry out a test operation. Check air blowing and cooling/heating operation in the indoor unit.
Test operation
U5 U6
Check
The above figure does not show all the electric cables. For details, refer to the installation manuals for outdoor unit, indoor unit, remote controller, or optional devices.
Note)
The above figure does not show all the electric cables. For details, refer to the installation manuals for outdoor unit, indoor unit, remote controller, or optional devices.
3. Connection check between Flow Selector Unit (FS Unit) and indoor unit
Check list 2 Calculate the additional amount of refrigerant from the following:
1
Remote controller
Indoor unit
A
B
B
Earth terminal
Control wiring
N
3
CN01
L
B
N
Earth terminal
Earth terminal
A
B Control wiring
CN81
CN02 Power line
A
Earth terminal
FS unit
CN81 L
U1/U2
Earth terminal
B
B
Control FS unit wiring
Earth terminal
FS unit
CN81
CN02 Power line
A
A U1/U2
CN01
L
CN02
N
Earth terminal
Power line
Earth terminal
Earth terminal
No.
Note)
Pull Box
2
Pull Box
(A) (B) Firstly enter the total length for each liquid pipe in the following table and then calculate the additional amount of refrigerant by pipe length.
Additional amount of refrigerant by pipe length Pipe dia at liquid side
4
Main check items Are indoor/outdoor communication lines connected to U1/U2 terminals? Is the signal line of the FS unit connected to connector CN81? Is the power supply cable of the FS unit connected to R (L) and S (N) terminals? Is the power supply cable of the FS unit connected to the closed end connector? When the indoor unit is a Wall type (1 Series) or Concealed Duct High Static Pressure type?
Standard amount of refrigerant kg/m
Total pipe length at each liquid side
Additional amount of refrigerant pipe dia at each liquid side kg
Ø6.4
0.025 ×
=
kg
Ø9.5
0.055 ×
=
kg
Ø12.7
0.105 ×
=
kg
Ø15.9
0.160 ×
=
kg
Ø19.0
0.250 ×
=
kg
Ø22.2
0.350 ×
=
kg
Check
Additional amount of refrigerant by pipe length (A)
The above figure does not cover all the electric wirings. For details, refer to the Installation Manual of Flow selector unit.
kg
Next, refer to the following table for the corrective amount of refrigerant (B) by system capacity.
87
Corrective amount of refrigerant by system capacity
Check list 1 • Using the “Check list 1”, check there is no trouble in the installation work. Is capacity of the leak breaker appropriate?
Corrective amount of 1.3 + refrigerant by system capacity
CN01
Power supply Single phase 220-240V, 50Hz Earth leakage breaker Power switch
Additional amount Actual liquid Additional amount of = × × of refrigerant (B) pipe length refrigerant per liquid pipe 1m
A
Remote controller
Indoor unit
U1/U2
Remote controller
Indoor unit
Outdoor total capacity XXXX A
Is the diameter of the power cable correctly wired?
Is the control communication line correctly wired?
Normal type
Header unit (A) Follower unit (B) Follower unit (C)
XXXX A XXXX A XXXX A
Indoor unit XXXX A
Header unit (A) Follower unit (B) Follower unit (C)
XXXX mm² XXXX mm² XXXX mm²
Indoor unit XXXX mm²
Indoor –outdoor connection terminals (U1, U2) Outdoor–outdoor connection terminals (U5, U6) Central control system connection terminals (U3, U4)
XXXX XXXX XXXX
Is the power of the indoor units supplied collectively? Is the earth grounded
System horse power HP Unit 1
Unit 2
Unit 3
Corrective amount of refrigerant (B) kg
8
8
2.0
10
10
2.5
12
12
16
8
18
10
8
0
20
10
10
2.0
3.0 8
–1.5
24
8
8
8
–4.5
Is the insulation good? (10MΩ or more)
XXXX MΩ or more
26
10
8
8
–3.0
Is the main power voltage correct? (Within 200V ± 10%)
XXXX V
28
10
10
8
–1.5
30
10
10
10
0
Is the diameter of the connecting pipe correct? Is the branch kit correct?
Finally add the additional amount of refrigerant by pipe length (A) to the corrective amount of refrigerant by system capacity (B). This is the final additional amount of refrigerant. If the result is indicated as a negative, do not add any refrigerant. Do not add the refrigerant (= 0kg).
Does the indoor unit condensate drain adequately? Is the thermal insulation of pipes good? (Connecting pipes, Branch kit) For both indoor and outdoor units, ensure air is not short-circuited from discharge to inlet ports. After pressure test, check that the pipework and indoor units have been vacuumed and the correct amount of additional gas has been charged. Are valves of all the outdoor units fully opened? Suction gas side XXXX Header unit (A) XXXX Follower unit (B) XXXX Follower unit (C)
• Check the additional amount of refrigerant.
Discharge gas side XXXX XXXX XXXX
Liquid side XXXX XXXX XXXX
Balance side XXXX XXXX XXXX
Additional amount of refrigerant Additional amount of refrigerant by pipe length (A)
kg
Corrective amount of refrigerant by system HP (B)
kg
Additional amount of refrigerant
kg
8-3. Check at Main Power-ON
8-4. Address Setup
After turning on the main power of the indoor units and outdoor unit in the refrigerant line to be executed with a test operation, check the following items in outdoor and each indoor unit.
After power-ON, set up the indoor address from the interface P.C. board of the outdoor unit.
(After turning on the main power, be sure to check in order of indoor unit → outdoor unit.) If the power supply of the outdoor unit has been firstly turned on, [E19] appears on the 7-segment display on the interface P.C. board until the power supply of the indoor unit is turned on. However it is not an error.
Check on outdoor unit 1. Check that all the rotary switches, SW01, SW02, and SW03 on the interface P.C. board of the outdoor unit are set up to “1”. 2. If other error code is displayed on 7-segment [B], remove the cause of trouble referring to “9. Troubleshooting”. 3. Check that [L08] is displayed on 7-segment display [B] on the interface P.C. board of the outdoor unit. (L08: Indoor address unset up) (If the address setup operation has already finished in service time, etc, the above check code is not displayed, and only [U1] is displayed on 7-segment display [A].) 7-segment display [A]
7-segment display [B]
Interface P.C. board
(The address setup operation cannot be performed by power-ON only. )
8-4-1. Cautions 1. It requires approx. 5 minutes usually for 1 line to automatically set up address. However in some cases, it may require maximum 10 minutes. 2. It is unnecessary to operate the air conditioner for address setup. 3. Manual address setup is also available besides automatic setup. Automatic address: Setup from SW15 on the interface P.C. board of the outdoor unit Manual address: Setup from the weird remote controller. (For details, refer to section “8-4-3. Address setup procedure”)
8-4-2. Address Setup and Check Procedure Procedure
Item
Operation and check contents
88
1
Indoor unit power-ON
Turn on power of indoor unit in refrigerant line to which address is set up.
2
Outdoor unit power-ON
Turn on power of all the outdoor units in refrigerant line to which address is set up.
3
7-segment display check
Check that [L08] is displayed on 7-segment display [B] on the interface P.C. board of the outdoor unit in the system to which address is set up.
4
Address setup start
Confirm the corresponding items in “8-4-3 Address setup procedure”, and then set up address according to the operation procedure. (Be sure that the setup operation may differ in group control or central control.) Note) Address cannot be set up if switches are not operated.
5
Display check after setup
• After address setup, [U1] [ ] are displayed in 7-segment display section. • If an error code is displayed in 7-segment display [B], remove the cause of trouble referring to “9. Troubleshooting”. Using 7-segment display function, check the system information of the scheduled system. (This check is executed on the interface P.C. board of the outdoor unit.)
SW01
SW02
SW03 Rotary switch setup
Check on indoor unit 1. Display check on remote controller (In case of wired remote controller) Check that a frame as shown in the following left figure is displayed on LC display section of the remote controller.
TEMP.
FILTER RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
UNIT
Normal status (Power and operation stop)
System information check after setup
SW01
7-segment display
SW02 SW03
[A]
[B]
System capacity
1
2
3
[No. of HP]
[HP]
No. of connected outdoor unit
1
3
3
[Connected No. of units]
[ P]
No. of connected indoor units
1
4
3
[Connected No. of units]
After the above checks, return rotary switches SW01, SW02, SW03 to 1/1/1.
NO GOOD
GOOD
6
TEMP.
FILTER RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
Interface P.C. board
7-segment display [A]
Push-switch SW04
Push-switch SW05
Push-switch SW15
UNIT
7-segment display [B]
Abnormal status (Power is not normally turned on.)
If a frame is not displayed as shown in the above right figure, the power of the remote controller is not normally turned on. Therefore check the following items. • Check power supply of indoor unit. • Check wiring between indoor unit and remote controller. • Check whether there is cutoff of cable around the indoor control P.C. board or not, and check connection failure of connectors. • Check failure of transformer for the indoor microcomputer. • Check indoor control P.C. board failure.
SW01 SW02 SW03 Rotary switches
8-4-3. Address Setup Procedure
REQUIREMENT
In this air conditioner, it is required to set up address to the indoor unit before starting operation. Set up the address according to the following setup procedure. CAUTION 1. Set up address after wiring work. 2. It requires maximum 10 minutes (Usually, approx. 5 minutes) to set up automatically an address to 1 line. 3. To set up an address automatically, the setup at outdoor side is necessary. (Address setup cannot be performed by power-ON only.) 4. To set up an address, it is unnecessary to operate the air conditioner. 5. Manual address setup is also available besides automatic setup. Automatic address : Setup from SW15 on the interface P.C. board of the header unit Manual address : Setup from the wired remote controller ∗ It is temporarily necessary to set the indoor unit and wired to 1 : 1. (In group operation and in time without remote controller)
Cabling systematic diagram
Outdoor
SW11
89
(Example)
In case of central control in a single refrigerant line
In case of central control over refrigerant lines
Address setup procedure
To procedure 1
To procedure 2
Cable systematic diagram Outdoor
Central remote controller
Outdoor
Indoor
Indoor
Indoor
Remote controller
Remote controller
Remote controller
Central remote controller
Indoor
Address setup procedure 1 1. Turn on power of indoor/outdoor units. (In order of indoor → Outdoor) 2. After approx. 1 minute, check that U. 1. L08 (U. 1. flash) is displayed in 7-segment display section on the interface P.C. board of the outdoor unit. 3. Push SW15 to start the setup of the automatic addressing. (Max. 10 minutes for 1 line (Usually, approx. 5 minutes)) 4. When the count Auto 1 → Auto 2 → Auto 3 is displayed in 7-segment display section, and it changes from U. 1. - - - (U. 1. flash) to U. 1. - - - (U. 1. light) , the setup finished. 5. When performing an automatic address setup on a single refrigerant line with central control, connect relay connected between [U1, U2] and [U3, U4] terminals in the header unit.
Outdoor
Outdoor
Indoor
Indoor
Indoor
Remote controller
Remote controller
Remote controller
Central remote controller
Indoor
Header unit interface P.C. board SW04 SW05 SW15
3 2, 4
D600 D601 D602 D603 D604 SW01 SW02 SW03 1
1
1
5 U1 U2 U3 U4 U5 U6 For internal wiring of For internal wiring between For wiring between central control indoor and outdoor units system outdoor
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1
SW13 2 3
4
1
× × × × × × × × × × × × × ×
× ¡
×
¡
×
¡
×
¡
×
¡
×
¡
×
¡
SW14 2 3
× × ¡ ¡
× ×
¡ ¡
× ×
¡ ¡
× ×
× × × × ¡ ¡ ¡ ¡
× × × ×
¡ ¡
4
× × × × × × × × ¡ ¡ ¡ ¡ ¡ ¡
SW12
ON ON 1 2 3 4 1 2 3 4
Be careful not to duplicate addresses with the other refrigerant line.
Line address
Indoor
Header unit interface P.C. board
SW13
SW14
ON ON ON 1 1 2 3 4 1 2 3 4
SW07 SW08
SW09
SW10
(¡: Switch ON, × : Switch OFF)
Line address switch on outdoor interface P.C. board
(However, go to the procedure 1 when the central control is performed in a single refrigerant line.)
Indoor
ON ON ON ON 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
SW06
Without central control : To the address setup procedure 1 With central control : To the address setup procedure 2
Indoor
Remote controller
Address setup procedure 2
Note)
Outdoor
Indoor
1. Using SW13 and 14 on the interface P.C. board of the outdoor unit in each system, set up the address for each system. (At shipment from factory: Set to Address 1)
Automatic Address Setup
Group control over multiple refrigerant lines
(Example)
• When a group control is performed over the multiple refrigerant lines, be sure to turn on the power supplies of all the indoor units connected in a group at the time of address setup. • If turning on the power for each refrigerant line to set up address, a header indoor unit is set for each line. Therefore, an alarm code “L03” (Duplicated header indoor units) is output in operation after address setup. In this case, change the group address from the wired remote controller for only one header unit is set up.
Line address
1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
SW13 2 3
4
1
× ×
×
¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡
¡
×
¡
×
¡
×
¡
×
¡
×
¡
×
¡
SW14 2 3
4
¡ ¡
¡ ¡
× ×
¡ ¡
× ×
¡ ¡
× ×
¡ ¡
¡ ¡
× × × ×
¡ ¡ ¡ ¡
× × × ×
× × × × × × × ×
¡ ¡ ¡ ¡
: Is not used for setup of system address. (Do not change setup.) 2. Check that the relay connectors between [U1, U2] and [U3, U4] terminals are not connected in all the outdoor units to which the central control is connected. (At shipment from factory: Connector not connected) 3. Turn on power of indoor/outdoor. (In order of indoor → outdoor) 4. After approx. 1 minute, check that 7-segment display is U.1.L08 (U.1. flash) on the interface P.C. board of the outdoor unit. 5. Push SW15 to start the setup of automatic addressing. (Max. 10 minutes for 1 line (Usually, approx. 5 minutes)) 6. When the count Auto 1 → Auto 2 → Auto 3 is displayed in 7-segment display section, and it changes from U. 1. - - - (U. 1. flash) to U. 1. - - - (U. 1. light) , the setup finished. 7. Procedure 4. to 6. are repeated in other refrigerant lines.
2
U1 U2 U3 U4 U5 U6 For internal wiring of For internal wiring between For wiring between central control indoor and outdoor units system outdoor
8. How to set up the terminal resistance When all the address setups have finished in the same refrigerant circuit system, put the terminal resistance in the same central control line into one. • Remain only SW30-2 of the header outdoor unit with address 1 as ON. (With end terminal resistance) • Set up SW30-2 of the other header outdoor units to OFF. (Without terminal resistance) 9. Connect the relay connector between [U1, U2] and [U3, U4] of the header unit for each refrigerant line. 10. Then set up the central control address. (For the central control address setup, refer to the Installation manual of the central control devices.) 1 Follower unit
U3 U4
U5 U6
SW30
ON ON ON ON 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
SW11
SW12
ON ON 1 2 3 4 1 2 3 4
SW06
U1 U2
U5 U6
U1 U2
U3 U4
U5 U6
U1 U2
SW09
SW10
U1 U2
U5 U6
U1 U2
A B
2
(Wiring example in 2 lines)
3
#1
#2
Outdoor
Outdoor
Indoor Indoor Indoor
Indoor Indoor
Header unit U3 U4
U1 U2
Line address Indoor address Group address
U1 U2
A B
1 2 2
1 1 1 Remote controller
A B
1 3 2
2 1 2
Remote controller
Remote controller
Individual
5
Follower
90
Header unit
Follower unit
U3 U4
U3 U4
1 2
U1 U2
After address setup
OFF
U5 U6
U1 U2
OFF
U5 U6
U1 U2
OFF
U5 U6
U1 U2
U1 U2
Individual : 0000 Header unit : 0001 Follower unit : 0002
U1 U2
A B
A B
A B
Remote controller
Remote controller
Remote controller
U1 U2
A B
9
Remote controller
Group
Follower unit
Header unit
Follower unit
Header unit
Setup at shipment from factory
1
(Setup is unnecessary.)
2
(Setup is unnecessary.)
3
1
ON
(Setup is unnecessary.)
OFF after address setup
(Setup is unnecessary.)
OFF after address setup
ON
Connect short after address setup
Open
Connect short after address setup
Open
Connect short after address setup
Open
SW30-2 Terminal-end resistance of indoor/outdoor communi cation line/central control communication line
Relay connector
8
} In case of group control
A B
Header unit
Using the setup temp. set ! to the item code. Using the timer time the indoor address.
Operation procedure
1®2®3®4®5®6® 7 ® 8 ® 9 ® 10 ® 11 End
R.C.
2 1 1
2 2 2
3 1 0
Note Never connect a relay connector until address setup for all the refrigerant lines has been completed ; otherwise address cannot be correctly set up.
buttons, set up
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
buttons,
11
Push TEST button. Setup operation finished. (Status returns to normal stop status.)
ON / OFF
TIMER SET
/
Push SET button. (OK when display goes on.)
Item code TEMP.
FILTER RESET TEST
buttons,
10
No.
Data
2, 5, 8 4, 7, 10 11
/
Using the timer time / buttons, set Individual = , Header unit = , Follower unit = .
CODE No.
Indoor side (Automatic setup) 1 2 0
/
Using the setup temp. set " to the item code.
UNIT No.
1 1 0
buttons,
Using the timer time / buttons, set up the line address. (Match it with the line address on the interface P.C. board of the outdoor unit in the identical refrigerant line.)
SET DATA SETTING
Refrigerant line address Indoor unit address Group address
buttons
Push SET button. (OK when display goes on.) (Group address)
Group address
Relay connector
U1 U2
Individual
OFF
U5 U6
TEST
7
ON SW30
Relay connector U1 U2
SW13, 14 (Refrigerant line address)
U1 U2
1 2
ON SW30
6
In the above example, under condition of no inter-unit wire of the remote controller, set the address after individual connecting of the wired remote controller.
Header unit U3 U4
1 2
ON SW30
OFF
U5 U6
U3 U4
1 2
ON SW30
Relay connector
Outdoor interface P.C. board
Header unit Follower unit U3 U4
1 2
ON SW30
Remote controller
Group
/
+
Push SET button. (OK when display goes on.) (Indoor address)
2 2 2
Header Remote controller
Using the setup temp. set to the item code.
CL
4
U5 U6 Relay connector
U1 U2
A B
Turn on the power.
SW14
ON ON ON 1 1 2 3 4 1 2 3 4
SW07 SW08
Relay connector
A B
Push simultaneously SET + for 4 seconds or more. LCD changes to flashing. (Line address)
3
U3 U4
Before address setup During setup of address U1 U2
SW13
1
Arrange one indoor unit and one remote controller set to 1 by 1.
SW30
Header unit Follower unit
U3 U4
Manual address setup from remote controller In case to decide an address of the indoor unit prior to finish of indoor wiring work and unpracticed outdoor wiring work (Manual setup from remote controller)
ON 1 2
2
Header unit
U1 U2
Header unit interface P.C. board
3, 6, 9
UNIT
1
Note 1) When setting the line address from the remote controller, do not use address 29 and 30. The address 29 and 30 cannot be set up in the outdoor unit. Therefore if they are incorrectly set up, a check code [E04] (Indoor/outdoor communication circuit error) is output.
• To confirm all the unit numbers from an arbitrary wired remote controller; (Operation while the air conditioner stops) The indoor unit No. and position in the same refrigerant line can be confirmed. An outdoor unit is selected, the indoor unit numbers in the same refrigerant line are successively displayed, and then its indoor unit fan is turned on.
1 Confirmation of indoor unit address and position by using the remote controller [Confirmation of indoor unit address and the position] 1. When you want to know the indoor address though position of the indoor unit itself can be recognized;
2 3
(Operation while the air conditioner operates)
1 2
If it stops, push
ON / OFF
button. CODE No.
UNIT
Push button. The unit No. 1-1 is displayed on the LCD. (Disappears after several seconds) The displayed unit No indicates the line address and indoor address. (If there is other indoor unit connected to the same remote controller (Group control unit), other unit No. is displayed every pushing UNIT button.)
UNIT No.
TEMP.
1
Operate FILTER RESET TEST
4
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
UNIT
2
TEST
Push the timer time + buttons simultaneously for 4 seconds or more. Firstly, the line 1, item code )+ (Address Change) is displayed. (Select outdoor unit.) Using UNIT + SWING/FIX buttons, select the line address. CODE No.
Using SET button, determine the selected line address. • The indoor unit address, which is connected to the refrigerant pipe of the selected outdoor unit is displayed and the fan is turned on. Every pushing UNIT button, the indoor unit numbers in the identical pipe are successively displayed. • Only fan of the selected indoor unit operates.
[To select another line address]
5 6
2
Push CL button to return to procedure ). • The indoor address of another line can be successively confirmed. Push
TEST
SET DATA SETTING UNIT No.
R.C.
TEMP.
1
91
CODE No. SET DATA SETTING UNIT No.
• Unit No. is displayed. • The fans of all the indoor units in a group control are turned on.
2
3
1 2
TEST
Push + buttons simultaneously for 4 seconds or more.
Every pushing UNIT button, the indoor unit numbers in the group control are successively displayed. • The firstly displayed unit No. indicates the address of the header unit. • Only fan of the selected indoor unit is turned on. Push TEST button to finish the procedure. All the indoor units in group control stop.
R.C.
FILTER RESET TEST
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
CL
MODE
SWING/FIX
VENT
SET
CL
UNIT
2 4 5
Operation procedure
1®2®3® 4 ® 5 ® 6 End
button to finish the procedure.
Push simultaneously SET + CL + TEST buttons for 4 seconds or more. (The firstly displayed unit No. indicates the header unit in group control.) In group control, select an indoor unit No. to be changed by (The fan of the selected indoor unit is turned on.) Using the setup temp. to the item code.
/
buttons, set
UNIT
4 5 6
2
button.
!
CODE No. SET DATA SETTING
Using the timer time / buttons, change the displayed setup data to a data which you want to change. Push
SET
button.
Using the UNIT button, select the unit No. to be changed at the next time. Repeat the procedure to and change the indoor address so that it is not duplicated.
4 6
Operation procedure
1®2®3
UNIT
UNIT No.
ON / OFF
SET
3
No.
TEMP.
1 3 End
FAN
TIME
Change of indoor address from wired remote controller • To change the indoor address in individual operation (Wired remote controller : Indoor unit = 1 : 1) or group control (When the setup operation with automatic address has finished, this change is available.) (Operation while air conditioner stops)
• To confirm the unit numbers in a group control; (Operation while the air conditioner stops) The indoor unit numbers in a group control are successively displayed, and the corresponding indoor fan is turned on. (Operation while the air conditioner stops)
1
TIMER SET
Change of indoor address from remote controller
2. When you want to know position of the indoor unit using the address
VENT
FILTER RESET TEST
ON / OFF
6 3
Operation procedure
1®2
No.
End
7 8
After the above change, push confirm the changed contents. If it is acceptable, push confirmation.
TEST
UNIT
R.C.
No.
TEMP.
3 5 8 1
FILTER RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
UNIT
button to
button to finish
Operation procedure
1®2®3®4® 5 ® 6 ® 7 ® 8 End
4 2, 6, 7
• To change all the indoor addresses from an arbitrary wired remote controller; (When the setup operation with automatic address has finished, this change is available.) Contents : Using an arbitrary wired remote controller, the indoor unit address can be changed for each same refrigerant line ∗ Change the address in the address check/change mode. (Operation while air conditioner stops)
1 2 3
4 5 6
Clearance of address (Return to status (Address undecided) at shipment from factory) Method 1 An address is individually cleared from a wired remote controller. “0099” is set up to line address, indoor address, and group address data from the remote controller. (For the setup procedure, refer to the abovementioned address setup from the remote controller.)
TEST
Push the timer time + buttons simultaneously for 4 seconds or more. Firstly, the line 1, item code AC (Address Change) is displayed. Using
UNIT
+
SWING/FIX
Method 2
buttons, select the line address.
Push SET button. • The indoor unit address, which is connected to the refrigerant pipe of the selected outdoor unit is displayed and the fan is turned on. First the current indoor address is displayed on the setup data. (Line address is not displayed.) The indoor address of the setup data moves up/down by the timer time Change the setup data to a new address. Push
SET
/
Clear the indoor addresses in the same refrigerant line from the outdoor unit. 1. Turn off the power of the refrigerant line to be returned to the status at shipment, and change the header unit to the following status. 1) Remove the relay connector between [U1U2] and [U3U4]. (If it has been already removed, leave it as it is.) 2) Turn on SW30-2 on the interface P.C. board of the header unit if it is OFF. (If it has been already ON, leave it as it is.)
buttons. Central control device
button to determine the setup data.
U1 U2 U3 U4
UNIT
Every pushing button, the indoor unit numbers in the identical pipe are successively displayed. Only fan of the selected indoor unit operates. Repeat the procedure to and change all the indoor addresses so that they are not duplicated.
Header unit
4 6
7 92
8
U1 U2
Push SET button. (All the displays on LCD go on.) Push
TEST
Follower unit
U3 U4
U5 U6
Header Center unit
U3 U4
U1 U2
Follower unit
U3 U4
U5 U6
U1 U2
U5 U6
Header Center unit
U3 U4
U1 U2
U5 U6
U3 U4
U1 U2
U5 U6
button to finish the procedure. U1 U2
U1 U2
U1 U2
A B
A B
A B
Remote controller
Remote controller
Remote controller
U1 U2 A B
U1 U2 A B
Remote controller
Unit of which address is to be returned to the initial status
CODE No.
CODE No.
SET DATA SETTING
SET DATA SETTING UNIT No.
R.C.
No.
TEMP.
1
FILTER RESET TEST
3
UNIT No.
R.C.
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
UNIT
2
Cancel of line selection
Here, if the unit No is not called up, the outdoor unit in this line does not exist. Push CL button, and then select a line according to procedure .
2
No.
TEMP.
ON / OFF
4 8
FILTER RESET TEST
2. Turn on the indoor/outdoor power of which address is to be cleared. After approx. 1 minute, check that “U.1. - - -” is displayed, and then execute the following operation on the interface P.C. board of the header unit of which address is to be cleared in the refrigerant line.
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
UNIT
5, 7 To finish the set Operation procedure
1®2®3®4® 5 ® 6 ® 7 ® 8 End
6
SW01
SW02
SW03
SW04
Address which can be cleared
2
1
2
After checking that “A.d.buS” is displayed on 7-degment display, and then push SW04 for 5 seconds or more.
Line + Indoor + Group address
2
2
2
After checking that “A.d.nEt” is displayed on 7-degment display, and then push SW04 for 5 seconds or more.
Central address
3. After “A.d. c.L.” has been displayed on 7-degment display, return SW01/SW02/SW03 to 1/1/1. 4. When the address clearing has correctly finished, “U.1.L08” is displayed on 7-degment display after a while. If “A.d. n.G.” is displayed on 7-degment display, there is a possibility which is connected with the other refrigerant line. Check again the relay connector between [U1U2] and [U3U4] terminals. NOTE) Be careful that the other refrigerant line address may be also cleared if clearing operation is not correctly executed. 5. After clearing of the address, set up an address again.
In case of increase the address-undefined indoor units (Extension, etc.) If set up the indoor address of which address is undefined accompanied with extension of indoor units, replacement of P.C. board, etc, follow to the methods below.
8-4-4. Check after Address Setup When Central Control System is Connected When the central control system is connected, check the following setup has finished after address setup.
Method 1 Set up an address individually from a wired remote controller. (Line address, Indoor address, Group address, Central address) For the setup method, refer to the above “Manual address setup from remote controller”.
Central control units U1 U2 U3 U4
Method 2
Line address = 2
Set up an address from the outdoor unit. ∗ Leave the address of the unit of which address has been already set up as it is. Set up an address only to the unit of which address is undefined. The addresses are allocated from the low number.
Other refrigerant line
Line address = 1
Center unit Header unit(A) (A)
U3 U4
3
5
Header unit (A)
4
Other refrigerant line
2 Follower unit (B)
U3 U4
Follower unit (C)
U3 U4
U3 U4
1 Outdoor unit U1 U2
Setup procedure
U5 U6
U1 U2
U5 U6
U1 U2
U5 U6
U1 U2
U5 U6
Earth
Arrange the outdoor header units in the refrigerant line to which indoor units are added. (Figure below) 1. Remove the relay connector between [U1U2] and [U3U4]. 2. Turn on SW30-2 on the interface P.C. board at outdoor header unit side if it is OFF. ∗ Turn off the power, and then execute the operation.
5
3-phase 380–415V, 50Hz Leak interception
Main switch
Central control device U1 U2 U3 U4
Header unit
Follower unit
U3 U4
93
U1 U2
Header Center unit
U3 U4
U5 U6
U1 U2
Follower unit
U3 U4
U5 U6
U1 U2
U5 U6
U1 U2
U1 U2
Header Center unit
U3 U4
U5 U6
U1 U2
U5 U6
U1 U2
U1 U2
A B
A B
A B
Remote controller
Remote controller
Remote controller
U1 U2 A B
U1 U2
A B
A B
A B
U1 U2
Remote controller
Remote controller
Remote controller
A B
1-phase 220–240V, 50Hz Leak interception
Main switch
U1 U2
U1 U2
Indoor unit
U3 U4
U1 U2 A B
Main check items
Remote controller
Check
1) Is relay connector of the header unit connected after address setup? Added indoor unit
Relay connector 2) Is relay connector of the follower unit removed?
3. Turn on the indoor/outdoor power of which address is to be set up. After approx. 1 minute, check that “U.1. - - -” is displayed on 7-segment display. 4. Execute the following operation on the interface P.C. board of the header unit. SW01
SW02
SW03
2
14
2
Terminal resistance
SW04 After checking that “ ” is displayed on 7-segment display, and then push SW04 for 5 seconds or more.
“AUTO1” → “AUTO2” → “AUTO3” → … → “AUTO9” … is counted and displayed on 7-degment display. • Return the SW01, 02, 03 setup as before. 5. When “U.1. - - -” is displayed on 7-segment display, the setup operation finished. Turn off the indoor/outdoor power. 6. Return the following setup as before. • Relay connector • SW30-2
Line address
Note)
3) Is the end resistance (SW30-2) of the header unit with the least refrigerant line address number (in the central control line) turned on? (Setup is unnecessary for follower unit.) 4) Are the terminal resistance (SW30-2) of the header units except for the line of which central control refrigerant line address is the smallest, turned off? (Setup is unnecessary for follower unit.) 5) Are not addresses in the line address (SW13, SW14) duplicated in each refrigerant line?
The above table does not describe all the electric cablings. For details, refer to each installation manual for outdoor unit, indoor unit, remote controller, and optional devices.
8-5. Troubleshooting in Test Operation If the phenomena appear, such as a check code is output or the remote controller is not accepted in power-ON after cabling work or in address setup operation, the following causes are considered.
8-5-1. A check Code is Displayed on the Remote Controller Check code Outdoor unit displayed on 7-segment remote controller display E04
E19-00
Cause
Countermeasures
Outdoor power is formerly turned on.
Turn on the power again. (In order of Indoor → Outdoor)
There is none of outdoor terminator resistor, or there Check SW30 bit 2 of the outdoor unit. are two or more resistances. No connection between multiple refrigerant lines: (After address setup) SW30 bit 20N Connection between multiple refrigerant lines: SW30 bit 2 of the connected outdoor unit is turned on only in one line. After address was decided, all the indoor units do not correctly response after power-ON in outdoor unit.
ON 1 2
SW30 L08
E08-XX
E07
E06
Check and modifies disconnection of indoor/outdoor communication line.(Communication line between outdoor unit and the leading indoor unit) Check influence of communication noise.
Address setup error Set up address again. • Only line addresses of the connected indoor units are undefined. • The outdoor line address and the line addresses in all indoor units do not match. • The indoor addresses are duplicated. (Units except those displaying E04 are duplicated.) • A header unit is not set up in a group. (Except group displaying E04) Duplication of indoor addresses. (Address No in which sub-code of the check code are duplicated)
Set up address again.
There is none of outdoor terminal resistance, or there are two or more resistances. (After address setup, when terminal resistance setup is changed after power-ON.)
Check SW30 bit 2 of the outdoor unit. No connection between multiple refrigerant lines: SW30 bit 20N Connection between multiple refrigerant lines: SW30 bit 2 of the connected outdoor unit is turned on only in one line.
ON 1 2
SW30
Transmission circuit error at interface side (P.C. board failure)
Replace the interface P.C. board.
After address setup, communication from all the indoor units interrupted under condition that a normal operation can be performed.
Check and correct disconnection of indoor/outdoor communication line.(Communication line between outdoor unit and the leading indoor unit) Check influence of communication noise.
Exceeded No of connected indoor units or exceeded capacity.
Adjust No of connected indoor units or capacity.
E16
E16-XX
E25
E25
Duplication of outdoor addresses. (Only when outdoor address was manually set up)
Do not use a manual setup for outdoor address.
L04
L04
Duplication of outdoor line addresses • Line address setup error, occurred after connection between U1, U2 and U3, U4 connectors
Modify line address setup of the outdoor unit between lines. (Set up SW 13 and 14 on the interface P.C. board.)
L05 (∗)
L06
Duplicated of indoor units with priority
The Heat Recovery Multi is not set up on priority.
L06 (∗) L08
There are two or more indoor units set up with priority. L08
Address setup error • Only indoor addresses of all the connected indoor units are undefined.
(∗) [L05]: Displayed on the indoor unit set up with priority [L06]: Displayed on the indoor unit except one set up with priority
94
Set up address again.
8-5-2. Operation from remote controller is not accepted and a check code is displayed on 7-segment display of the interface P.C. board of the outdoor unit. Remote controller status
7-segment display of outdoor unit
No response
L08
E19-00
Cause
Countermeasures
Line addresses and indoor addresses of all the connected indoor units are unset.
Set up addresses.
There is no outdoor unit of group control.
Set up group address.
Indoor unit power is not turned on.
Turn on the power again. (In order of indoor → outdoor)
Indoor/outdoor communication line is not correctly connected to the outdoor unit. (Fig. 1) (Indoor/outdoor cannot communicate before address setup.)
Correct wiring.
There is none of outdoor terminator resistor, or there are two or more resistances. (Before address setup)
Check SW30 bit 2 of the outdoor unit. No connection between multiple refrigerant lines: SW30 bit 2 0N Connection between multiple refrigerant lines: SW30 bit 2 of the connected outdoor unit is turned on only in one line.
ON 1 2
SW30
E20-01
Address setup is performed with connecting indoor/outdoor communication line between outdoor units. (Fig. 3)
Correct wiring.
Address setup is performed under condition of connecting between multiple refrigerant lines. (Fig. 3)
Correct wiring.
8-5-3. There is no display of a check code on 7-segment display on the interface P.C. board of the outdoor unit though there is indoor unit which does not accept the operation from the remote controller. Remote controller status
7-segment display of outdoor unit
No response
None
No display on remote controller (No line is output.)
None
Countermeasures
Cause Communication line is not connected between indoor and outdoor.
Modify wiring.
Line and indoor addresses are unset. (Unit which does not response to remote controller)
Set up address.
The power of the header unit of the group is not turned on in indoor group control. (Unit which does not response to remote controller)
Turn on the power.
Group address is set up to follower unit in the individual control. (Unit which does not response to remote controller)
Set [0] to group address in case of individual control.
The power is not turned on. (Unit which is not displayed on remote controller)
Turn on the power.
Remote controller is not connected with cable. (Unit which is not displayed on remote controller)
Correct wiring.
Miscabling of remote controller (Unit which is not displayed on remote controller)
Correct wiring.
Remote controller communication circuit error (Unit which is not displayed on remote controller) If 230V is incorrectly applied to the remote controller terminal, the remote controller communication circuit fails.
Remove FASTON terminal connected to remote controller terminals (A/B), and check the voltage. If voltage is not applied, replace P.C. board. (15 to 18V usually)
8-5-4. In check for No. of connected outdoor units and connected Indoor units after address setup, diminished No. of connected units displayed. (There are outdoor/indoor units which do not operate in a test operation.) Status
Cause
Number of connected outdoor units is short.
Miswiring of communication line between outdoor units or unconnected cable (Fig. 4) (Address setup operation has finished without recognition of miswired follower unit.)
After modification of wiring, set up address again and check No. of the connected outdoor units.
Countermeasures
Number of connected indoor units is short.
Miswiring of communication line between indoor units or unconnected cable (Fig. 5) (Address setup operation has finished without recognition of miswired indoor unit.)
After modification of wiring, set up address again and check No. of the connected indoor units.
Number of outdoor units connected to group is short in group operation from remote controller.
Remote controller is not connected with wire. Miscabling of remote controller
Using the main remote controller connected to a group, start a test operation, specify the unit which does not operate (Unit unconnected to group), and then check wiring.
Remote controller communication circuit error If 230V is incorrectly applied to the remote controller terminal, the remote controller communication circuit fails.
Using the main remote controller connected to a group, start a test operation, specify the unit which does not operate (Unit unconnected to group). Remove Fasten receptacle connected to remote controller terminals (A/B), and check the voltage. If voltage is not applied, replace P.C. board. (15 to18V in normal time)
95
Incorrect wiring example (Fig. 1) Remote controller status
Header unit 7-segment display
No response
E19-00
Incorrect example
Header unit
Header unit
U3/U4
U5/U6
Indoorunit
Indoorunit
Indoorunit
Indoorunit
(Fig. 2) Remote controller status
Header unit 7-segment display
No response
E19-02
Incorrect example U5/U6 Header unit
Follower unit
U1/U2 Indoorunit
(Fig. 3) Remote controller status
Header unit 7-segment display
No response
E20-01
Incorrect example
Header unit
Follower unit
Header unit
Follower unit
Header unit
Follower unit
U1/U2
U1/U2
U1/U2
U5/U6
Line 1
Line 2 U1/U2
Indoorunit
Indoorunit
Indoorunit
(Fig. 4) Status
Incorrect example
Number of connected outdoor units is short. Header unit
Follower unit
Header unit
U1/U2
U3/U4
U3/U4
Follower unit
Indoorunit
U1/U2 U1/U2 U3/U4 U5/U6
(Fig. 5) Status
Incorrect example
Number of connected outdoor units is short. Header unit
Header unit
U1/U2
U1/U2
Indoorunit
A/B Indoorunit
Indoorunit
96
Follower unit
U5/U6
U1/U2 Indoorunit
Header unit
Indoorunit
Indoorunit
U1/U2 U3/U4
8-6. Test Operation Check 8-6-1. Fan Operation Check START
Push [START/STOP] button.
When an error code has been displayed on the remote controller, refer to Section 8-5-1.
Select the operation mode [FAN].
Is air discharged from the discharge port of the indoor unit?
NO
Check indoor fan, fan motor and fan circuit. (Ensure power has been isolated before removing any covers.)
NO
Check for items in contact with fan. (Ensure power has been isolated before removing any covers.)
YES Is there any abnormal noise? YES Normal Check all indoor units in turn.
8-6-2. Cooling/Heating Test Operation Check The cooling/heating test operation check can be performed on both remote controller and outdoor interface P.C. board.
1. Test operation start/stop operation Test operation from remote controller Wired remote controller
1
When pushing TEST button for 4 seconds or more, [TEST] is displayed in the display section and the mode enters the test operation mode.
TEST
2 3
4 5
Push
ON / OFF
TEMP.
1, 5
FILTER RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
UNIT
3
button.
Using MODE button, select an operation mode either [COOL] or [HEAT]. • Do not use any other operation modes, only [COOL] or [HEAT]. • Temperature adjustment is unavailable during test operation. • Errors are detected as usual. When the test operation has finished, push The same display as that in procedure 1 appears.
ON / OFF
97
TEST
button to stop the operation.
Push TEST button to clear the test operation mode. [TEST] display disappears and the status returns to the normal stop status.
2, 4
Wireless remote controller (Except 4-way Air Discharge Cassette type, Under Ceiling type and 1-way Air Discharge Cassette type (2 Series))
1 2
3 4
Remove the screw which fixes the name plate to the receiver part on the wireless remote controller. Remove the nameplate of the receiver section by inserting a minus screwdriver, into the notch at the bottom of the plate, and set the Dip switch to [TEST RUN ON]. ON / OFF Execute a test operation with button on the wireless remote controller. • , , and LED flash during test operation. • Under status of [TEST RUN ON], the temperature adjustment from the wireless remote controller is not available. Ensure that this is not used for normal operation as equipment damage may occur.
Use either COOL or HEAT operation mode for a test operation. Receiver unit Note) The outdoor unit does not operate for approx. 3 minutes. Spacer After power-ON and after operation has stopped. M4 × 25 screw (2 pieces)
After the test operation finished, stop the air conditioner using the wireless remote controller, and return the Dip switch to its original setting. (A 60-minute timing function is designed into the sensor section in order to prevent a continuous test operation.)
Notch
Nameplate
Small screw
Wireless remote controller (4-way Air Discharge Cassette type)
1
2 3
4 5
Turn OFF the power to the air conditioner. Remove the adjust corner cap and the attached with sensor section from the ceiling panel. For removal method, follow to the installation instructions attached to the ceiling panel. (Be careful to handling the sensor section because cables are connected to the sensor.) Remove the sensor cover from the adjust corner cap. (1 screw) Change Bit [1: TEST] of the switch [S003] on the sensor P.C. board from OFF to ON. Mount the sensor cover and attach the adjust corner cap with sensors to the ceiling panel. Turn on power of the air conditioner. Push ON / OFF button of the wireless remote controller, and select an operation mode [COOL] or [HEAT] with MODE button. (All the display lamps of the wireless remote controller sensor section flash during the test operation.) • Do not use operation mode other than [COOL] or [HEAT]. • Errors are detected as usual. S003
When the test operation has finished, push button to stop the operation.
ON / OFF
ON
Bit 1 : OFF 4
3
2
1 ON
Turn off the power to the air conditioner. Sensor cover Change Bit [1] of the switch [S003] on the sensor P.C. board from ON to OFF. Adjust corner cap Attach the adjust corner cap with sensors to the ceiling panel.
Sensor P.C. board
Test operation from outdoor unit Refer to “8-7-2. Function of Start/Stop the Indoor Unit from Outdoor Unit” in “8-7. Service Support Function”. NOTE) The test operation returns to normal operation after 60 minutes have passed.
98
In case of wireless remote controller (for Under Ceiling type and 1-way Air Discharge Cassette type (2 Series)) Procedure
Description Turn on power of the air conditioner.
1 2
The operation is not accepted for 5 minutes when power has been turned on at first time after installation, and 1 minute when power has been turned on at the next time and after. After the specified time has passed, perform a test operation. Push [Start/Stop] button and change the operation mode to [COOL] or [HEAT] with [Mode] button. Then change the fan speed to [High] using [Fan] button. Test cooling operation
Test heating operation
Set temperature to [18°C] using [Temperature set] button.
Set temperature to [30°C] using [Temperature set] button.
4
After checking the receiving sound “Pi”, immediately push [Temperature set] button to set to [19°C]
After checking the receiving sound “Pi”, immediately push [Temperature set] button to set to [29°C].
5
After checking the receiving sound “Pi”, immediately push [Temperature set] button to set to [18°C].
After checking the receiving sound “Pi”, immediately push [Temperature set] button to set to [30°C].
3
Then repeat the procedure
6
4→5→4→5.
After approx. 10 seconds, all the display lamps on the sensor part of wireless remote controller, [Operation] (Green), [Timer] (Green), and [Ready] (Yellow) flash and the air conditioner starts operation. If the lamps do not flash, repeat the procedure
7
2 and after.
After the test operation, push [Start/Stop] button to stop the operation.
Outline of test operation from the wireless remote controller Test cooling operation: Start → 18°C → 19°C → 18°C → 19°C → 18°C → 19°C → 18°C → (Test operation) → Stop Test heating operation: Start → 30°C → 29°C → 30°C → 29°C → 30°C → 29°C → 30°C → (Test operation) → Stop
Be sure to set the air speed to [High]
2
3, 4, 5, 6 2, 7
99
2. Test operation
START
Refer to “Test operation procedure” of indoor remote controller.
Test operation for one indoor unit YES
Operation start
NO
YES
The operation does not start approx. 3 minutes after power-ON or after operation stopped. (NOTE) After power-ON, it may require Max. 10 minutes to start the operation due to the initial communication of the system.
Is cold air or hot air discharged?
Check operation status of the compressor.
YES Check direction of the louver.
Is air circulation good? YES Test operation for all units in turn
Execute a test operation using “Function of start/stop the indoor unit from outdoor unit” in “Service support function”.
Operate all the indoor units at once.
(NOTE 1) Is the temperature difference between suction and discharge good?
NO
YES Is the operating voltage correct? (Rated voltage ±10%)
NO
YES
• Check power voltage of the main power supply. • Check cable size of the power supply.
(NOTE 2) Is the operating current normal?
NO
YES (NOTE 3) Is the operating pressure normal?
NO
YES Normal
100
• Check temperature load of the indoor room/ outdoor ambient. • Check pipe length and refrigerant charge amount. • Check operating Hz of compressor. • Check abnormal sound in the outdoor unit. (Abnormal sound, etc of compressor and others)
(NOTE 1) Criteria for judging difference between suction and discharge temperature 1. Cooling After operation for a minimum of 30 minutes in [COOL] mode, check the dry bulb temperature difference. Temperature difference: 8°C or more between suction and discharge air of the indoor unit. (In Max-Hz operation) 2. Heating After operation for a minimum of 30 minutes in [HEAT] mode, check the dry bulb temperature difference. Temperature difference: 15°C or more between suction and discharge air of the indoor unit. (In Max-Hz operation) ∗ The temperature difference may diminish in cases of systems in which the connected indoor capacity exceeds 100%, or with long pipe length, etc.
(NOTE 2) Criteria for operating current For a test operation (with all the indoor units operating), normal operating current is shown in the following table. Outdoor unit
8HP
10HP
12HP
Current value
18
21
22
(Unit: A)
(NOTE 3) Criteria for cycle status 1. Refrigerating cycle under standard condition The refrigerating cycle under standard cooling and heating condition is as follows:
Pressure
(MPa)
Pipe surface temp
Number of compressor rotations Air temp condition
(°C)
(rps) (DB/WB) (°C)
High Low Discharge Suction Indoor heat exchanger Outdoor heat exchanger Liquid temp Compressor Compressor Indoor Outdoor
(Pd) (Ps) (TD) (TS1) (TC) (TE1) (TL) 1 2
10HP MMY-MAP1002FT8 Cool standard Heat standard 3.1 2.9 0.8 0.7 86 90 6 3 8 46 43 1 36 36 79 75 79 75 27/19 20/– 35/– 7/6
∗ This compressor is driven with 4-pole motor. The value of the compressor frequency (Hz) measured by a clamp meter is two times the rotation count (rps) of the compressor. ∗ This data is the cycle data under condition of standard pipe length and two 4-way Air Discharge Cassette type air conditioners connected. Data changes according to installed pipe length, combination of indoor units or connected indoor capacity. ∗ For a compressor, the left side is 1 and the right side is 2 viewed front the front of the unit. Even if two compressors operate, the frequency difference may set as a measures against resonance. ∗ The temperature of indoor heat exchanger (TC) indicates TCJ sensor temperature in cooling time, and TC2 sensor temperature in heating time respectively.
2. Criteria for operating pressure General criteria is as follows: All cooling operaton
All heating operation
High pressure : 2.0 to 3.2MPa
Indoor
:18 to 32°C
Low pressure : 0.5 to 0.9MPa
Outdoor :25 to 35°C
High pressure : 2.5 to 3.3MPa
Indoor
Low pressure : 0.5 to 0.7MPa
Outdoor : 5 to 10°C
When all the units operate in cooling mode
:15 to 25°C When all the units operate in heating mode
Using the rotary switch on the outdoor unit I/F, the operating pressure, cycle temperature, and compressor rotation count can be checked on the 7-segment display. Refer to “Outdoor refrigerant circuit system data display” and “Indoor cycle data display” in Section 9. Troubleshooting.
101
8-7. Service Support Function 8-7-1. Function to Start/Stop (ON/OFF) Indoor Unit from Outdoor Unit The following functions enables the start and stop of the indoor units using the switches on the interface P.C. board of the header unit. No.
Function
Outline
1
All cooling test operation
Changes the mode of all the connected indoor units collectively to cooling test operation. Note) Control operation same as test operation for remote controller.
[Setup] Push SW04 for 2 seconds or more with SW01”2”, SW02”5”, SW03”1”. [Release] Return SW01, SW02, SW03 to “1”.
Section A [C ]
Section B [ –C]
2
All heating test operation
Changes the mode of all the connected indoor units collectively to heating test operation. Note) Control operation same as test operation for remote controller.
[Setup] Push SW04 for 2 seconds or more with SW01”2”, SW02”6”, SW03”1”. [Release] Return SW01, SW02, SW03 to “1”.
Section A [H ]
Section B [ –H]
3
Batch start
Starts all the connected indoor units collectively. Note) The contents follow the setup of remote controller.
[Setup] Push SW04 for 2 seconds or more with SW01”2”, SW02”7”, SW03”1”. [Release] Return SW01, SW02, SW03 to “1”.
Section A Section B [CH] [ 11] [ 11] is displayed on Section B for 5 seconds.
Batch stop
Stops all the connected indoor units collectively.
[Setup] Push SW05 for 2 seconds or more with SW01”2”, SW02”7”, SW03”1”. [Release] Return SW01, SW02, SW03 to “1”.
Section A Section B [CH] [ 00] [ 00] is displayed on Section B for 5 seconds.
Individual start
Starts the specified indoor unit. Notes) • Control operation same as test. • The other indoor units keep existing status.
[Setup] Push SW04 for 2 seconds or more set SW01 “16” and set SW02 and SW03 to address No. (1 to 64) to be started. [Release] Return SW01, SW02, SW03 to “1”.
Section A Section B [ ] [ ] Section A: Displays the corresponding indoor address. Section B: Displays [ 11] for 5 seconds from operation-ON.
Individual stop
Stops the specified indoor unit. Note) The other indoor units keep existing status.
[Setup] Push SW05 for 2 seconds or more set SW01 “16” and set SW02 and SW03 to address No. (1 to 64) to be stopped. [Release] Return SW01, SW02, SW03 to “1”.
Section A Section B [ ] [ ] Section A: Displays the corresponding indoor address. Section B: Displays [ 00] for 5 seconds from operation-OFF.
[Setup] Push SW04 for 10 seconds or more set SW01 “16” and set SW02 and SW03 to address No. (1 to 64) to be operated. [Release] Return SW01, SW02, SW03 to “1”.
Section A Section B [ ] [ ] Section A: Displays the corresponding indoor address. Section B: Displays [ FF] for 5 seconds from test operation-ON.
4
Individual test Operates the specified indoor unit. operation Note) The other indoor units keep existing status.
NOTE 1) This start/stop function only sends the command signals from the outdoor unit to the indoor unit, such as start, stop, operation mode, etc. Once it does not resend the signals even if the indoor unit does not follow the sent signals. NOTE 2) The above controls are not available when an error has caused the system to stop.
Setup/Release
Interface P.C. board
7-segment display
7-segment display [A] SW04
7-segment display [B] SW05
SW01 SW02 SW03 Rotary switch
102
1. All cooling test operation function This function is provided to change collectively the mode of all the indoor units connected to the same system for cooling test operation mode, using switches on the interface P.C. board of the header unit.
Operation procedure Power ON
Be sure to turn on power at the indoor side before power-ON of outdoor unit.
Set SW01 on the interface P.C. board of the header unit to [2], Sw02 to [5], and SW03 to [1] respectively. ([C ] is displayed on the 7-segment display [A].)
Push SW04 on the interface P.C. board of the header unit for 2 seconds or more.
Start
[TEST] is displayed on the remote controller of the indoor unit to be operated. Check that “ – C ” is displayed on the 7-segment display [A] [B] [B] on the interface P.C. board of the outdoor unit. [C ] [ –C]
Operation check
Return SW01, SW02, SW03 on the interface P.C. board of the outdoor unit to [1], [1], [1] respectively or push the push-switch SW05 for 2 seconds or more.
Stop/End
2. All heating test operation function This function is provided to change collectively the mode of all the indoor units connected to the same system for heating test operation mode, using switches on the interface P.C. board of the outdoor unit.
Operation procedure Power ON
Be sure to turn on power at the indoor side before power-ON of outdoor unit.
Set SW01 on the interface P.C. board of the header unit to [2], Sw02 to [6], and SW03 to [1] respectively. ([H ] is displayed on the 7-segment display [A].)
Push SW04 on the interface P.C. board of the header unit for 2 seconds or more.
Start
[TEST] is displayed on the remote controller of the indoor unit to be operated. Check that “ – H ” is displayed on the 7-segment display [A] [B] [B] on the interface P.C. board of the outdoor unit. [H ] [ –H]
Operation check
Return SW01, SW02, SW03 on the interface P.C. board of the outdoor unit to [1], [1], [1] respectively or push the push-switch SW05 for 2 seconds or more.
Stop/End
Interface P.C. board
7-segment display [A] SW04
7-segment display [B] SW05
SW01 SW02 SW03 Rotary switch
NOTE) The test operation returns to normal operation after 60 minutes.
103
3. Batch start/stop (ON/OFF) function This function is provided to start/stop collectively all the indoor units connected to the same system by using switches on the interface P.C. board of the outdoor unit.
Operation procedure
Power ON
Be sure to turn on power at the indoor side before power-ON of outdoor unit. If an error is already displayed under condition of SW01 [1], SW02 [1], SW03 [1], resolve the problem using the troubleshooting guide and then execute the test operation. If the operation is set “heat”, indoor unit which is set to “cool priority” will not operate or will be displayed. If the operation is set to “cool”, indoor unit which is set to “heat priority” will not operate or will be displayed.
Set up the operation mode of the remote controller. (If it is not set up, the operation continues in the current mode.) (FAN/COOL/HEAT)
Set on the interface P.C. board of the header unit SW01 to [2], Sw02 to [7], and SW03 to [1] respectively. ([CH ] is displayed on 7-segment display [A].)
Push SW04 on the interface P.C. board of the header unit for 2 seconds or more.
Start
The indoor unit to be started operates.
Push the push-switch SW05 on the interface P.C. board of the header unit for 2 seconds or more.
Stop
After test operation, return the rotary switches SW01, SW02, and SW03 on the interface P.C. board of the header unit to [1], [1], [1] respectively.
End
104
4. Individual start/stop (ON/OFF) individual test operation function This function is provided to start/stop (ON/OFF) individually each indoor unit connected to the same system by using switches on the interface P.C. board of the header unit. Set SW01 [16] and set SW02, SW03 to indoor address No. (1 to 64) to be started (Refer to the following table∗) - only the setup indoor unit starts operation. (In the rotary switches of the indoor unit which operates in a group by the remote controller, the follower unit cannot be individually started or stopped. In this case, [ – – ] is displayed on 7-segment display [B] on the interface P.C. board of the header unit.)
Operation procedure Power ON
Be sure to turn on power at the indoor side before power-ON of outdoor unit. If an error is already displayed under condition of SW01 [1], SW02 [1], SW03 [1], return the status to normal one according to troubleshooting and then execute a test operation. The unit which is not given with priority by heating priority control, cooling priority control, and selection of cooling or heating mode is not operated. In this case, or is displayed on the remote controller.
Set up the operation mode of the remote controller. (If it is not set up, the operation starts with the current mode.)
Match the rotary switch on the interface P.C. board of the header unit * with in the following table. (7-segment display) [A] [
[B] ]
Address display of corresponding indoor unit
[
]
[ 00] is displayed for 5 seconds after operation-ON.
Push the push-switch SW04 on the interface P.C. board of the header unit for 2 seconds or more. (If pushing this switch continuously for 10 seconds or more, the operation changes to the individual test operation.)
(7-segment display)
[A] [
]
[
[B] ]
Address display of [ 11] is displayed for corresponding indoor unit 5 seconds after operation-ON. (For individual test operation,[ FF] is displayed.)
Start
The indoor unit to be started operates.
*
Push the push-switch SW05 on the interface P.C. board of the header unit for 2 seconds or more.
SW01
SW02
SW03
16
1 to 16
1
Address 1 to Address 16
16
1 to 16
2
Address 17 to Address 32
16
1 to 16
3
Address 33 to Address 48
16
1 to 16
4
Address 49 to Address 64
(7-segment display) [A] [
[B] ]
Address display of corresponding indoor unit
[
Units to be operated
]
[ 00] is displayed for 5 seconds after operation-ON.
After test operation, return the display select switches SW01, SW02, and SW03 on the interface P.C. board of the header unit to [1], [1], [1] respectively. End
NOTE) The individual test operation returns to the normal operation after 60 minutes.
105
} } } }
individually
individually
individually
individually
In individual start/stop
8-7-2. Error Clearing Function 1. Clearing from the main remote controller [Error clearing in outdoor unit] Error of the outdoor unit is cleared by the unit of one refrigerant circuit system to which the indoor units operated by the remote controller. (Error of the indoor unit is not cleared.) For clearing errors, the service monitor function of the remote controller is used.
1 2
Change the mode to service monitor mode by pushing seconds or more. Using
/
CL
+
TEST
buttons simultaneously for 4
buttons, set “FF” to item code.
The display in Section A in the following figure is counted with interval of 5 seconds as “# ” → “" ” → “! ” → “ ” → “ ” → “ ”. When the count arrives “ ”, the error is cleared. ∗ However, counting from “# ” is repeated on the display.
3
When
TEST
button is pushed, the status returns to the normal status.
Operation procedure
1®2®3
The status returns to the normal status.
CODE No.
UNIT No.
Section A
R.C.
No.
TEMP.
3 FILTER RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
2
UNIT
1
[Error clearing in indoor unit] Error in the indoor unit is cleared by
ON / OFF
button on the remote controller.
(Only error of the indoor unit connected with operating remote controller is cleared.)
106
2. Clearing from the interface P.C. board Using the switches on the interface P.C. board, this function is to clear the currently detected error for each refrigerant circuit system without resetting the power supply. (→ Restart of error detection) Errors in both outdoor and indoor units are once cleared.
(7-segment display)
Set the rotary switches on the interface P.C. board of the header unit to the following setting.
[A]
[B]
[ E
SW01=[2] SW02=[16] SW03=[1]
]
[
]
Push the push-switch SW04 on the interface P.C. board of the header unit for 5 seconds or more.
(7-segment display)
[ C L] is displayed in 7-segment display [B] on the P.C. board (for 5 seconds), and the error is completely cleared.
[A] [ E
[B] ]
[
7-segment display [A] Interface P.C. board
Push switch SW04
CL ]
7-segment display [B] Push switch SW05
SW01 SW02 SW03
3. Clearing of error check code by power reset This function is provided to clear error in a refrigerant circuit system by resetting the power of all the outdoor and the indoor units. (→ Restart of error detection) As same as the clearing method on the interface P.C. board, errors of both the outdoor and the indoor units are once cleared.
Method 1. Be sure to reset power of both the outdoor and the indoor units. NOTE) After power reset, it requires usually 3 minutes to power-on due to the initial communication of the system. In same cases, it requires Max. 10 minutes.
107
8-7-3. Remote Controller Distinction Function This function is provided to distinguish the remote controller connected from the outdoor unit to the indoor unit for a refrigerant circuit system using switches on the interface P.C. board of the header unit.
Distinction procedure
Be sure turn on the power of the indoor unit prior to the power of the outdoor unit.
Power ON
Set the display select switches on the interface P.C. board of the header unit as follows: SW01 [2]
® ® [4] SW03 ® [1]
[
(7-segment display) [A] [B] A1 ] [ ]
SW02
Operation
Push the push-switch SW04 on the interface P.C. board of the header unit for 2 seconds or more.
(7-segment display) [
TEST
display of the connected remote controller flashes.
[A] A1 ]
[
[A] FF ]
Check the connected remote controller.
Push the push-switch SW05 on the interface P.C. board of the header unit for 2 seconds or more.
End Other end conditions: 1. 10 minutes passed for sending operation 2. SW01, SW02, or SW03 changed to other position.
Interface P.C. board
7-segment display [A] SW04
7-segment display [B] SW05
SW01 SW02 SW03 Rotary switch
108
8-7-4. Pulse Motor Valve (PMV) Forced Open/Close Function in Indoor Unit This function is provided to fully open or close forcibly the PMV for 2 minutes in all indoor units, using the switch operation on the interface P.C. board of the header unit. This function is also used to open the PMV fully when turning off the power and executing an operation, for example, vacuuming.
Operation [Open fully] Set the switch SW01 on the interface P.C. board of the header unit to [2], SW02 to [3], SW03 to [1] and push SW04 for 2 seconds or more. (Display shown on 7-segment display for 2 minutes as follows.) [P ] [ FF]
[Close fully] Set the switch on the interface P.C. board of the header unit SW01 to [2], SW02 to [3], SW03 to [1] and push SW05 for 2 seconds or more. (Display shown on 7-segment display for one minute as follows.) [P ] [ 00]
[Clear] After 2 minutes (1 minutes for “Close fully”) have passed when setup has finished, the PMV automatically returns to the normal operation.
8-7-5. Pulse Motor Valve (PMV) Forced Open Fully/Close fully Function in Outdoor Unit This function is provided to fully open or close fully the P.M.V. (PMV1/PMV2/PMV3) used in the outdoor unit for 2 minutes.
[Open fully]
[Operating method]
Short-circuit CN30 on the interface P.C. board of the header unit.
Select one of PMV1 or PMV2 to open. Turn SW12 bit 1 to OFF when handling (PMV1/PMV2), and turn it to ON when selecting PMV3.
[Close fully] Short-circuit CN31 on the interface P.C. board of the header unit.
Enlarged diagram of switch position
[Clear] After 2 minutes, the opening returns to the normal operation. Be sure to remove the short circuit after confirmation. SW12 I/F P.C. board
Bit 1 Check connector CN30
Check connector CN31
109
OFF PMV1, PMV2 ON PMV3
8-7-6. Solenoid Valve Forced Open/Close Function in Outdoor Unit This function is provided to forcibly open/close each solenoid valve mounted in the outdoor unit by use of the switches provided on the outdoor unit interface P.C. board. This function confirms the operation of each solenoid valve.
[Operation] 1. On the interface P.C. board set SW01 to [2], SW02 to [1] and SW03 to [3]. 2. Confirm [H, ] is displayed on the 7-segment display [B]. Push switch SW04 for 2 seconds or more. 3. Confirm [2] is displayed on the 7-segment display - this indicates that solenoid SV2 has been switched on. 4. Each solenoid can be operated by selecting the appropriate SW02 position as shown in the table below. (ON/OFF output pattern of each solenoid valve is as below.) NOTE 1) Be aware that there is a 5 second delay in the operation of the selected solenoid valve after SW02 has been set. NOTE 2) The mark [¡] in the table indicates the selected solenoid valve is forced on. NOTE 3) The mark [—] in the table indicates the selected solenoid mode will depend on the specifications of the air conditioner. NOTE 4) The mark [ ] in the table indicates the selected solenoid valve has been turned off. NOTE 5) The case heater relay output operates both compressor and accumulator heaters.
×
Operation pattern of solenoid valve
7-segment display [B]
SV2
SV5
1
[ ... 2 ...]
¡
—
—
—
—
—
—
—
—
—
—
¡
¡
2
[ ... 5 ...]
—
¡
—
—
—
—
—
—
—
—
—
¡
¡
3
[ ... 6 — ]
—
—
¡
—
—
—
—
—
—
—
—
¡
¡
4
[ ... 1 1 ]
—
—
—
¡
—
—
—
—
—
—
—
¡
¡
5
[ ... 1 2 ]
—
—
—
—
¡
—
—
—
—
—
—
¡
¡
6
[ ... 4 1 ]
—
—
—
—
—
¡
—
—
—
—
—
¡
¡
7
[ ... 4 2 ]
—
—
—
—
—
—
¡
—
—
—
—
¡
¡
8
[ ... 4 — ]
—
—
—
—
—
¡
¡
—
—
—
—
¡
¡
9
[ ... 3 A ]
—
—
—
—
—
—
—
¡
—
—
—
¡
¡
10
[ ... 3 b ]
—
—
—
—
—
—
—
—
¡
—
—
¡
¡
11
[ ... 3 C ]
—
—
—
—
—
—
—
—
—
¡
—
¡
¡
12
[ ... 3 d ]
—
—
—
—
—
—
—
—
—
—
¡
¡
¡
13
[ ... 3 E ]
—
—
—
—
—
—
—
—
—
—
—
×
¡
14
[ ... 3 — ]
—
—
—
—
—
—
—
¡
¡
¡
—
¡
¡
15
[ ... ... ... ]
—
—
—
—
—
—
—
—
—
—
—
¡
¡
16
[A L L]
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
SW02
Case heater SV6 SV11 SV12 SV41 SV42 SV3A SV3B SV3C SV3D SV3E
[Clear] Return settings on SW01, SW02, and SW03 to (1/1/1) on the Interface P.C. board. NOTE) Ensure this function is cleared to return the air conditioner to normal operation.
110
8-7-7. Fan Operation Check in Outdoor Unit This function is provided to check the fan operation on the interface P.C. board in the outdoor unit. The frequency of the fan speed can be controlled. Therefore utilize this function to check the operation or abnormal sound in the fan system. NOTE) Do not use this function during operation of the compressor. It may damage the compressor.
[Operation] 1. 2. 3. 4.
Set the switch on the interface P.C. board of the outdoor unit SW01 to [2], SW02 to [1], SW03 to [4]. When [F. d] is displayed in 7-segment display [A], keep pushing the switch SW04 for 2 seconds or more. From when fan step [ 31] is displayed in 7-segment display [B], the fan starts operation. (Max. step operation) After then, 7-segment display [B] and the fan step are changed by changing the setup number of the switches SW02 and SW03. (Output pattern of the fan is as follows.)
SW01
SW02
SW03
7-segment display [B]
Fan step
1
[ 31 ]
31
2
[ 30 ]
3
7-segment display [B]
Fan step
1
[ 15 ]
15
30
2
[ 14 ]
14
[ 29 ]
29
3
[ 13 ]
13
4
[ 28 ]
28
4
[ 12 ]
12
5
[ 27 ]
27
5
[ 11 ]
11
6
[ 26 ]
26
6
[ 10 ]
10
7
[ 25 ]
25
7
[
9 ]
9
[ 24 ]
24
[
8 ]
8
8 2
SW01
SW02
SW03
8
4
2
5
9
[ 23 ]
23
9
[
7 ]
7
10
[ 22 ]
22
10
[
6 ]
6
11
[ 21 ]
21
11
[
5 ]
5
12
[ 20 ]
20
12
[
4 ]
4
13
[ 19 ]
19
13
[
3 ]
3
14
[ 18 ]
18
14
[
2 ]
2
15
[ 17 ]
17
15
[
1 ]
1
16
[ 16 ]
16
16
[
0 ]
0
[Clear] This function is cleared by one of the following operations. 1. When SW01 setting number was changed to other number. 2. Push-switch SW05 was pushed for 2 seconds or more.
111
8-7-8. Abnormal Outdoor Unit Discrimination Method This function is provided to forcedly operate the fan of the outdoor unit in which an error occurred or the fan of the normal outdoor unit by the switch operation on the interface P.C. board in the header unit. To specify which one of the follower units connected to the system was faulty, use this function for the system stop due to a follower unit fault (Check code [E28]).
[Operation] In case to operate the fan in the erroneous outdoor unit only 1. Check all the switches, SW01, SW02, and SW03 on the interface P.C. board in the header unit are set to [1]. 7-segment display [A] [B]
Outdoor unit No.
Error code display
2. Push the push-switch SW04 for 2 seconds or more. 3. “E 1” is displayed on 7-segment display [A]. 4. The fan of the outdoor unit in which error occurred starts operation within approx. 10 seconds when “E 1” was displayed.
In case to operate the fans in all the normal outdoor units 1. 2. 3. 4.
Check all the switches, SW01, SW02, and SW03 on the interface P.C. board are set to [1/1/1]. Push the push-switches SW04 and SW05 at the same time for 2 seconds or more. “E 0” is displayed on 7-segment display [A]. The fans of all the normal outdoor units start operation with the Max. fan speed within approx. 10 seconds when “E 0” was displayed.
[Release] Push the push-switch SW05 on the interface P.C. board in the header unit for 2 seconds or more. The outdoor fan which was operated stops. * Check [U. 1] is displayed on 7-segment display [A], and then finish the work.
112
8-7-9. Manual Adjustment Function of Outside Temp (TO) Sensor This function is provided to fix TO sensor value manually by the switch operation on the interface P.C. board in the outdoor unit. When the unit stops abnormally due to TO sensor failure, etc, an emergent operation is available by set up the value manually to position near the current outside temperature.
[Operation] 1. Set the rotary switches on the interface P.C. board to numbers as follows. • SW01 [2] / SW02 [1] / SW03 [15] • 7-segment display: [t o] 2. Keep pushing the push-switch SW04 on the interface P.C. board for 1 second or more. The mode changes to the TO sensor value fix manual mode. 3. As shown in the following table, TO sensor value can be fixed by setting the rotary switch SW02 on the interface P.C. board. SW01 SW02 SW03 7-segment display [B] TO sensor value
SW01 SW02 SW03 7-segment display [B] TO sensor value
1
[
10
]
10°C
9
[
45
]
45°C
2
[
15
]
15°C
10
[
– 15
]
–15°C
3
[
20
]
20°C
11
[
– 10
]
–10°C
[
25
]
25°C
[ – 5
]
–5°C
4 2
12
15
2
15
5
[
30
]
30°C
13
[
0
]
0°C
6
[
35
]
35°C
14
[
2
]
2°C
7
[
40
]
40°C
15
[
5
]
5°C
8
[
43
]
43°C
16
[
7
]
7°C
NOTE) Emergent operation should be restricted to one day or so on. If operating TO sensor fixed with this function, the system control operation of the air conditioner may not become one based upon the specification of the product. Therefore an emergent operation should be restricted to a day or so on.
[Clear] Return numbers of SW01, SW02, and SW03 on the interface P.C. board in the header unit to [1/1/1] each.
Service support function list SW01 SW02 SW03 7-segment display [A] 1
[
J
C
]
Refrigerant circuit and control communication line check function (Cooling operation)
2
[
J
H
]
Refrigerant circuit and control communication line check function (Heating operation)
3
[
P
]
Indoor PMV forced full open function
[
A
]
Indoor remote controller discriminating function
5
[
C
]
Cooling test operation function
6
[
H
]
Heating test operation function
7
[
C
H
]
Indoor collective start/stop (ON/OFF) function
16
[
E
r
]
Error clear function
[
H
r
]
Solenoid valve forced open/close function
[
F
d
]
Fan forced operation function
[
t
o
]
Outside temp sensor manual adjustment function
4 2
1 to 16 4 to 5 15
16
1
1
3 2
Function contents
1
[ 0 1 ] to [ 1 6 ]
Indoor No. 1 to 16 unit
2
[ 1 7 ] to [ 3 2 ]
Indoor No.17 to 32 unit
3
[ 3 3 ] to [ 4 8 ]
Indoor No.33 to 48 unit
4
[ 4 9 ] to [ 6 4 ]
Indoor No.49 to 64 unit
1 to 16
Indoor individual start/stop (ON/OFF) function
113
8-7-10. Indoor Fan Operation Check Function This function is provided to check operation of single indoor unit without using communication with the remote controller or outdoor unit. This function can be used regardless operating or stopping of the system. However, if this function is used for a long time, a trouble of the air conditioner may be caused. Therefore using of this function should be restricted to several minutes.
[Operation] 1. Short-circuit CHK pin (CN71 on the indoor P.C. board). If short-circuiting DISP pin (CN72 on the indoor P.C. board) while short-circuiting CHK pin (CN71 on the indoor P.C. board), the indoor PMV only becomes the minimum opening (30 pulse). When opening DISP pin, it becomes the maximum opening again.
[Clear] Open CHK pin. If the system is operating, it stops once but automatically restart after several minutes. ∗ For the details of CHK pin (CN71 on indoor P.C. board) and DISP pin (CN72 on indoor P.C. board), refer to 11. Control circuit configuration, Indoor unit 2, Indoor P.C. board MCC-1402 and MCC-1403.
8-7-11. Indoor Fan Only Operating Mode When operating an air conditioner with indoor units and remote controller only in fan operation etc., this function can be used. A group operation is also available.
[Operation] 1) Short circuit DISP pin (CN72 on the indoor P.C. board). However, if CHK pin (CN71 on the indoor P.C. board) has been previously short circuited, this function is unavailable. 2) In a group operation, set up a group as usual. 3) While DISP pin is short circuited, all the sensor error judgment operation and communication with the outdoor unit are not performed. PMV is fixed to the Max. opening.
[Clear] Open DISP pin.
114
8-7-12. Monitor Function of Remote Controller Switch When using a remote controller with the model name RBC-ATM21E, the following monitor functions can be used.
Calling of display screen [Contents] The temperature or the operation status of the remote controller, indoor unit, or each sensor of the outdoor unit can be known by calling up the service monitor mode from the remote controller.
[Procedure]
2 3 4
Push CL + TEST buttons simultaneously for 4 seconds or more to call up the service monitor mode. The service monitor goes on, and temperature of the item code is firstly displayed.
Push UNIT button to change the item to one to be monitored. Then monitor the indoor unit and sensor temperature or operation status in the corresponding refrigerant line. Pushing display.
Indoor unit data (NOTE 2)
Item code
System data
CODE No.
UNIT No.
TEMP.
Push the temperature setup / buttons to select the item number (Item code) to be monitored. For displayed codes, refer to the table below.
TEST
button returns the display to the normal
4 1
FILTER RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
2 3
UNIT
Operation procedure
1®2®3®4
Returns to the normal display
Data name
Unit
00
Room temp (During control)
°C
01
Room temp (Remote controller)
°C
Display format
02
Indoor suction temp (TA)
°C
×1
03
Indoor coil temp (TCJ)
°C
×1
04
Indoor coil temp (TC2)
°C
×1
05
Indoor coil temp (TC1)
°C
×1
06
Indoor discharge temp (Tf) (NOTE 1)
°C
×1
08
Indoor PMV opening
pulse
× 1/10
0A
No. of connected indoor units
unit
0b
Total HP of connected indoor units
HP
0C
No. of connected indoor units
unit
0d
Total HP of outdoor units
HP
Item code
Outdoor unit individual data (NOTE 4, 5)
1
× 10
× 10
Data name
Unit
Display format
10
Compressor 1 discharge temp (Td1)
°C
×1
11
Compressor 2 discharge temp (Td2)
°C
×1
12
High-pressure sensor detention pressure (Pd)
MPa
× 100
13
Low-pressure sensor detention pressure (Ps)
MPa
× 100
14
Suction temp (TS)
°C
×1
15
Outdoor heat exchanger temp (TE)
°C
×1
16
Temp at liquid side (TL)
°C
×1
17
Outside ambient temp (TO)
°C
×1
18
Low-pressure saturation temp (TU)
°C
×1
19
Compressor 1 current (I1)
A
× 10
1A
Compressor 2 current (I2)
1b
PMV1 + 2 opening
1d
A
× 10
pulse
× 1/10
Compressor 1, 2 ON/OFF
—
(NOTE 3)
1E
Outdoor fan mode
—
0 to 31
1F
Outdoor unit HP
HP
×1
(NOTE 1) Only a part of indoor unit types is installed with the discharge temperature sensor. This temperature is not displayed for other types. (NOTE 2) When the units are connected to a group, data of the header indoor unit only can be displayed. (NOTE 3) 01 : Compressor 1 only is ON. 10 : Compressor 2 only is ON. 11 : Both compressor 1 and 2 are ON. (NOTE 4) The item codes are described as the example of the header unit. (NOTE 5) The upper digit of an item code represents the outdoor unit number. 1 : Header unit (A) 2 : Follower unit (B) 3 : Follower unit (C)
115
9. TROUBLESHOOTING 9-1. Troubleshooting Summary 1. Before troubleshooting 1) Applied models Super Heat Recovery Multi type models (Indoor unit: MMX-APXXX, Outdoor unit: MMY-MAPXXXFT8) 2) Required tools / measuring devices • Screwdrivers (Philips, Flat), spanner, longnose pliers, nipper, push pin for reset switch, etc. • Digital multimeter, thermometer, pressure gauge, etc. 3) Confirmation before check (The following items are not troubles.) No.
Operation
1
Compressor does not operate.
• • • •
2
Indoor fan does not work.
• Is cold draft prevention control operating at heating mode?
3
Outdoor fan does not rotate, or fan speed changes.
• Is it in low ambient cooling control? • Is a defrost operation being performed?
4
Indoor fan does not stop.
• Is the fan operating to remove residual heat after heating operation?
5
Start/stop operation on remote controller is unavailable.
• Is an auxiliary unit or remote controller being operated?
6
None
Check items Is it delayed for 3 minutes? (3 minutes after compressor-OFF) Is thermostat OFF? Is the fan operating or timer? Is the system initially communicating? Heating operation cannot be performed under the condition that the outside temperature is 21°C or higher. Cooling operation cannot be performed under the condition that the outside temperature is –5°C or lower.
• Are the wire connections on the indoor units and remote controllers correct?
2. Troubleshooting procedure When a fault has occurred, follow the procedure detailed below.
Trouble
Check the check display on the interface P.C. board of the header unit.
Check position or part in which trouble occurred.
NOTE) A malfunction of the microprocessor may be caused by power supply inconsistencies and external noise. If there are any noise sources, move remote controller and signal wires away from the noise sources or shield them.
116
9-2. Check Method If an trouble occurs, the error code can be retrieved from the main remote controller/central remote controller (LCD display) or the header unit interface P.C. board (7-segment display). Using this self diagnostic function, the trouble can be identified using the table below.
Check code list The following list shows all fault codes. • If check code is from indoor remote controller: See “Main remote controller display” in the list. • If check code is from outdoor unit: See “Outdoor 7-segment display” in the list. • If check code is from AI-NET central control remote controller: See “AI-NET central control display” in the list. • If check code is from indoor unit with wireless remote controller: See “Sensor display of receiving unit” in the list. IPDU: Intelligent Power Drive Unit ¡ : Lighting, : Flashing, l : Goes off ALT.: Flashing is alternately when there are two flashing LED. SIM: Simultaneous flashing when there are two flashing LED
¤
Check code Main remote controller display
Outdoor 7-segment display Auxiliary code
Wireless remote controller Sensor block display of receiving unit AI-NET central control display Operation Timer Ready Flash
E01
—
—
—
E02
—
—
—
l l l
l l l
Communication error between indoor and remote controller (Detected at remote controller side)
Remote controller
Remote controller transmission error
Remote controller
Communication error between indoor and remote controller (Detected at indoor side)
Indoor
¤ ¤ ¤
Communication circuit error between indoor/outdoor (Detected at indoor side)
Indoor
—
—
97
E04
—
—
04
l
l
No. of indoor units in which E06 sensor has been normally received
04
l
l
E07
—
l
l l l l
— E08
—
E08 Duplicated indoor addresses
96
E09
—
—
99
E10
—
—
CF
E12
01: Indoor/Outdoor communication E12 02: Communication between outdoor units
42
E15
E15
42
E16
00: Capacity over E16 01 ~: No. of connected units
—
Detecting device
¤ ¤ ¤
E03
E06
Check code name
¤ ¤ ¤ ¤
l l l
l
l
l
l
89
l
l
¤ ¤
Decrease of No. of indoor units
I/F
Communication circuit error between indoor/outdoor (Detected at outdoor side)
I/F
Duplicated indoor addresses Duplicated main remote controllers Communication error between indoor MCU
Indoor / I/F Remote controller Indoor
Automatic address start error
I/F
Indoor is nothing during automatic addressing
I/F
Capacity over / No. of connected indoor units
I/F
97, 99
¤
l
l
Communication error between indoor units
E19
00: Header is nothing E19 02: Two or more header units
96
l
l
¤
Outdoor header units quantity error
I/F
E20
E20
01: Outdoor of other line connected 02: Indoor of other line connected
42
l
l
Other line connected during automatic address
I/F
E23
E23
—
15
—
15
Duplicated follower outdoor addresses
I/F
E26
of outdoor units which E26 No. received signal normally
15
Decrease of No. of connected outdoor units
I/F
E28
E28 Detected outdoor unit number
d2
l l l l
I/F
E25
l l l l
Sending error in communication between outdoor units
E25
¤ ¤ ¤ ¤ ¤
Follower outdoor unit error
I/F
E31
01: 02: 03: E31 04: 05: 06: 07:
CF
l
l
¤
IPDU communication error
I/F
E18
—
—
IPDU1 error IPDU2 error IPDU1, 2 error Fan IPDU error IPDU + Fan IPDU error IPDU2 + Fan IPDU error All IPDU error
117
Indoor
Check code Main remote controller display
Outdoor 7-segment display Auxiliary code
Wireless remote controller Sensor block display of receiving unit AI-NET central control display Operation Timer Ready Flash
F01
—
—
0F
F02
—
—
0d
¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤
F03
—
—
93
F04
F04
—
19
F05
F05
—
A1
F06
F06
—
18
F07
F07
—
18
F08
F08
—
1b
F10
—
—
OC
F12
F12
—
A2
F13
F13
01: Comp. 1 side 02: Comp. 2 side
43
F15
F15
—
18
F16
F16
—
43
F23
F23
—
43
F24
F24
—
43
F29
—
—
12
F31
F31
—
1C
H01
01: Comp. 1 side H01 02: Comp. 2 side
IF
l
H02
H02
01: Comp. 1 side 02: Comp. 2 side
1d
l
H03
H03
01: Comp. 1 side 02: Comp. 2 side
17
l
H04
H04
—
44
H06
H06
—
20
H07
H07
—
d7
H08
01: 02: H08 03: 04:
H14
H14
H16
01: 02: H16 03: 04:
TK1 sensor error TK2 sensor error TK3 sensor error TK4 sensor error — TK1 oil circuit system error TK2 oil circuit system error TK3 oil circuit system error TK4 oil circuit system error
d4
l
44
l
d7
l
L03
—
—
96
L04
L04
—
96
L05
—
—
96
L06
L06 No. of indoor units with priority
l l l
96
¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤
—
—
99
L08
L08
—
99
L09
—
—
46
L10
L10
—
88
L17
L17
—
46
L18
L18
—
8A
L20
L20
—
98
L28
L28
—
46
L29
01: 02: 03: L29 04: 05: 06: 07:
IPDU1 error IPDU2 error IPDU3 error Fan IPDU error IPDU1 + Fan IPDU error IPDU2 + Fan IPDU error All IPDU error
CF
¤
¡
L30 Detected indoor address
b6
¤
¡
L31
—
—
—
Detecting device
ALT
Indoor TCJ sensor error
Indoor
ALT
Indoor TC2 sensor error
Indoor
ALT
Indoor TC1 sensor error
Indoor
ALT
TD1 sensor error
ALT
TD2 sensor error
I/F
ALT
TE1 sensor error
I/F
ALT
TL sensor error
I/F
ALT
TO sensor error
ALT
Indoor TA sensor error
¡
ALT
TS1 sensor error
I/F
¡
ALT
TH sensor error
IPDU
¡ ¡ ¡ ¡
ALT
Outdoor temp. sensor miscabling (TE, TL)
I/F
ALT
Outdoor pressure sensor miscabling (Pd, Ps)
I/F
ALT
Ps sensor error
I/F
ALT
Pd sensor error
¡ ¡ ¡ ¡ ¡
l
l ¡
SIM Indoor other error SIM Indoor EEPROM error
l
Compressor break down
l
Magnet switch error Overcurrent relay operation Compressor trouble (lock)
l
Current detect circuit system error
l l l
I/F
I/F Indoor
I/F Indoor I/F IPDU MG-SW Overcurrent relay IPDU IPDU
Comp 1 case thermo operation
I/F
Low pressure protective operation
I/F
Oil level down detective protection
I/F
l
Oil level detective temp sensor error
I/F
l
Comp 2 case thermo operation
I/F
l
Oil level detective circuit error Magnet switch error Overcurrent relay operation
¤ l ¤ ¤ ¡ ¤ ¤ l ¤ ¤ l ¤ ¤ l ¤ ¤ l ¤ ¤ l ¤ ¤ ¡ ¤ ¤ ¡ ¤ ¤ ¤ ¤ ¤ ¡ ¤ ¤ ¡ ¤
L07
L30
l l l
Check code name
SIM Indoor center unit duplicated
I/F MG-SW Overcurrent relay Indoor
SIM Outdoor line address duplicated
I/F
indoor units with priority SIM Duplicated (Displayed in indoor unit with priority)
I/F
indoor units with priority SIM Duplicated (Displayed in unit other than indoor unit with priority)
I/F
SIM Group line in individual indoor unit SIM Indoor group/Address unset SIM Indoor capacity unset
Indoor Indoor, I/F Indoor
SIM Outdoor capacity unset
I/F
SIM Inconsistency error of outdoor units
I/F
SIM FS unit error
FS unit
SIM Duplicated central control addresses
AI-NET, Indoor
SIM Over No. of connected outdoor units
I/F
¤
SIM No. of IPDU error
I/F
¤
SIM Indoor outside interlock
—
Extended I/C error
118
Indoor I/F
Check code Main remote controller display
Outdoor 7-segment display Auxiliary code
Wireless remote controller Sensor block display of receiving unit AI-NET central control display Operation Timer Ready Flash
P01
—
—
11
P03
P03
—
1E
P04
01: Comp. 1 side P04 02: Comp. 2 side
21
P05
P05
01: Phase-missing detection 02: Phase error
AF
P07
P07
01: Comp. 1 side 02: Comp. 2 side
IC
P10
P10 Detected indoor address
Ob
P12
—
—
11
P13
P13
—
47
P15
01: TS condition P15 02: TD condition
AE
P17
P17
P19
P19 Detected outdoor unit number
O8
P20
P20
22
—
[ [
C
[
3
D E
[
P22
1
[
P22
[
— 0
: IGBT short : Fan motor position detective circuit error : Fan motor trouble : TH sensor temp. error (Heat sink overheat) : TH sensor error : Vdc output error
bb
1A
¤ ¤ ¤ ¤
¤ ¤ l ¤ l ¤ l ¤ l ¤ ¤ ¤ ¤ ¤ ¤ ¤ l ¤ l ¤ l ¤ l ¤
¤
l
¤
¤ ¤ ¤
l
¤ ¤ ¤
l
¤ ¤ ¤ ¤ l l l
P26
P26
01: Comp. 1 side 02: Comp. 2 side
14
P29
P29
01: Comp. 1 side 02: Comp. 2 side
16
P31
P31
—
47
—
—
—
b7
By alarm device
—
—
—
97
—
—
—
99
l l
Check code name
Detecting device
ALT
Indoor fan motor error
ALT
Discharge temp. TD1 error
Indoor
ALT
High-pressure SW system operation
IPDU
ALT
Phase-missing detection /Phase error
I/F
ALT
Heat sink overheat error
I/F
IPDU, I/F
ALT
Indoor overflow error
Indoor
ALT
Indoor fan motor error
Indoor
ALT
Outdoor liquid back detection error
I/F
ALT
Gas leak detection
I/F
ALT
Discharge temp. TD2 error
I/F
ALT
4-way valve inverse error
I/F
ALT
High-pressure protective operation
I/F
ALT
Outdoor fan IPDU error
IPDU
ALT
G-TR short protection error
IPDU
ALT
Comp position detective circuit system error
IPDU
ALT
Other indoor unit error (Group terminal unit error)
Indoor
ALT
Error in indoor group
AI-NET
—
AI-NET communication system error
AI-NET
—
Duplicated network adapters
AI-NET
Error detected by TCC-LINK central control device Check code Central control device indication
Outdoor 7-segment display Auxiliary code
Wireless remote controller Sensor block display of receiving unit AI-NET central control display Operation Timer Ready Flash
Check code name
Detecting device
C05
—
—
—
—
Sending error in TCC-LINK central control device
TCC-LINK
C06
—
—
—
—
Receiving error in TCC-LINK central control device
TCC-LINK
C12
—
—
—
—
Batch alarm of general-purpose equipment General-purpose equipment control interface I/F
P30
Differs according to error contents of unit with occurrence of alarm —
—
(L20 is displayed.)
119
Group control branching unit error Duplicated central control addresses
TCC-LINK
New check code 1. Difference between the TCC LINK and AI-NET check code The displaying method of the check code changes in this model and onwards. AI-NET check code Used characters
Hexadecimal notation, 2 digits
Characteristics of code classification
Few classification of communication/ incorrect setup system
Block display
Indoor P.C. board, Outdoor P.C. board, Cycle, Communication
Display in wired remote controller
TCC Link Alphabet + Decimal notation, 2 digits
| | Many classification of communication/incorrect setup system | | | Communication/Incorrect setup (4 ways), Indoor protection, | Outdoor protection, Sensor, Compressor protection, etc. | | |→ Display Classification A
Unused
C
Central control system error
E
Communication system error
F
Each sensor error (Failure)
H
Compressor protective system error
Display on 7-segment in outdoor unit
J
Unused
• Unit No. and check code are displayed. • In a case of error with auxiliary code, the check code and the auxiliary code are displayed alternately.
L
Setup error, Other errors
P
Protective device operation
• [ ] is displayed. • [UNIT No.] + Check code + Operation lamp (Green) flash
Display on sensor part in wireless remote controller • Block display of combination of [
][
][
]
2. Special mention 1) If this model is connected to AI-NET by network adaptor, the different check codes are displayed on the main remote controller and AI-NET central control remote controller. Example) Indoor TA sensor error
AI-NETWORK BUS
Network adaptor
Indoorunit
OC
F10
AI-NET central control remote controller
Wired remote controller
2) The check code of the remote controller is displayed only while the air conditioner is operating (remote controller start button ON). When the air conditioner has stopped and the error has been cleared, the check code display on the remote controller also disappears. However, if the error continues after the unit has stopped, the check code is immediately displayed when the unit is restarted.
120
9-3. Troubleshooting by Check Display on Remote Controller In case of wired remote controller (RBC-AMT31E) 1. Confirmation and check When a trouble occurs in the air conditioner, the check code and the indoor unit No. are displayed on the of the remote controller. The check code is displayed while the air conditioner operates. If the display has disappeared, operate the air conditioner and check the error based upon the following “Confirmation of error history”.
CODE No.
UNIT No.
R.C.
Check code
No.
Indoor unit No. in which an error occurred
2. Confirmation of error history If a trouble occurs in the air conditioner, the error history can be found with the following procedure. (Up to 4 error histories are stored in the memory.) This history can be confirmed from either operating status or stop status.
TEMP.
2 FILTER RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
UNIT
1
3 Procedure
Description When pushing
SET
and
TEST
buttons simultaneously for 4 seconds or more, the below display appears.
If [Service Check] is displayed, the mode enters the error history mode.
1
• [01: Error history order] is displayed in code number window. UNIT No.
• [Indoor unit address with error] is displayed in UNIT No.
R.C.
Each successive push of the temp. set displayed in order.
2
/
The numbers in item code indicates item code [01] (most recent) to [04] (Oldest). CAUTION
After confirmation, push
TEST
button to return to the usual display.
121
No.
buttons, the error histories stored in the memory are
If [CL] button is pushed all of the error histories of the indoor unit will be deleted.
3
CODE No.
• [Check Code] is displayed in code number window.
In case of central remote controller (TCB-SC642TLE)
ZONE ALL ZONE GROUP
CODE No. 1234 SET DATA SETTING
R.C.
UNIT No.
TEST
No.
GROUP SELECT
ZONE
CL
SET
1. Confirmation and check When a trouble occurred on the air conditioner, the check code and the indoor unit No. are displayed on the display section of the remote controller. The check code is displayed while the air conditioner operates. If the display disappeared, operate the air conditioner and check the error based upon the following “Confirmation of error history”. Unit No display
Alarm display
UNIT No. Alternate flashing display R.C
No.
2. Confirmation of error history When a trouble occurred on the air conditioner, the error history can be confirmed with the following procedure. (Up to 4 error histories are stored in memory.) This history can be confirmed from either operating or stop. 1) Push
and
SET
buttons in succession for 4 seconds or more.
2) SERVICE CHECK
goes on and Item code 01 goes on.
3) When selecting (flash) the group number if there is the alarm history, the UNIT number and the latest alarm history are displayed alternately. * In this time, the temperature cannot be set up. 4) To confirm the alarm history other than the latest one, push temp. set code (01 to 04).
/
to select Item
GROUP
5) To confirm the alarm in the other group, push Do not push
CL
ZONE
and
to select the group number
button because all the alarm histories of the currently selected group are deleted.
6) To finish the service check, push
button.
Unit No display
Alarm display
UNIT No. Alternate flashing display R.C
No.
122
In case of AI-NET central remote controller 1. Operation for CHECK display When pushing the CHECK switch, the indoor unit No. (Network address No.) including the check data is displayed in the UNIT No. display section, and the check code is displayed in the set up temp. display section.
CHECK switch
ON MONITOR ZONE SET ALL
ON OFF
UNIT
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 MONITOR/SET ALL/ZONE
ZONE
UNIT
ZONE SET/ENTER SELECT
CENTER LOCKED MODE FAN ONLY COOL DRY HEAT AUTO
ON CENTER/LOCKED MODE OFF
TIMER ON
Push for 0.5 seconds to display CHECK code. Push for 3 seconds to reset indoor microprocessor. (While indoor microprocessor is locked by ALL STOP alarm) Push for 10 seconds to clear check data.
AUX. TYPE STANDBY TIMER No. FILTER FAN TEMP. CHECK AUTO 1 ˚C HIGH 2 MED. LOW LOUVER FIX MANUAL TEMP. FILTER RESET CHECK
FAN
RESET switch
LOUVER
Push the switch in the hole with pin. The remote controller resets initialized. (All data is cleared.)
2. Reading of CHECK monitor display
7 segment display Hexadecimal notation 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Decimal notation
Display on CHECK monitor Unit line No. (Network address No.)
MONITOR ZONE SET ALL
UNIT
ON OFF
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
CENTER LOCKED MODE FAN ONLY COOL DRY HEAT AUTO
AUX. TYPE STANDBY TIMER No. FILTER FAN TEMP. CHECK AUTO 1 ˚C HIGH 2 MED. LOW LOUVER FIX MANUAL
(Example) There is no check data.
Check code detected at first Check code detected at last
UNIT TEMP. CHECK
CHECK data
(Example) In No.1 unit, first the interconnection wire (bus communication line) of indoor/outdoor has failed. Next, the room temp. sensor is defective. For No.16 unit, the high pressure switch at the inverter unit side operates. UNIT
UNIT
UNIT
TEMP. CHECK 1
TEMP. CHECK 2
123
TEMP. CHECK 1
9-4. Check Code and Check Position Displayed on the Remote Controller and Outdoor Unit (7-Segment Display of Interface) Check code Detected Outdoor 7-segment display Main AI-NET position remote central control controller Check code remote controller Sub-code
Check code name
Status
Error detection condition
Check item (position)
• • • • •
Check remote controller inter-unit cable (A/B). Check disconnection, connector contact error. Check indoor power supply. Check indoor P.C. board error. Check remote controller address setup. (When two remote controllers operate) • Check remote controller P.C. board.
124
E01
—
—
—
Remote Communication error between Corresponding Communication interrupted unit only stops. between indoor P.C. board controller indoor and remote controller and remote controller. (Detected at remote controller side)
E02
—
—
—
Remote Remote controller sending error controller
E03
—
—
97
Indoor unit Communication error between indoor and remote controller (Detected at indoor side)
• Check remote controller and communication adapter wiring. Corresponding No communication from unit only stops. remote controller (including wireless) and communication adapter.
E04
—
—
4
Indoor unit Indoor/outdoor communication circuit error (Detected at indoor side)
Corresponding Indoor unit does not receive unit only stops. communication from outdoor unit.
E06
E06
No. of indoor units which received signal normally
4
I/F
Decreased number of indoor units
All stop
When signal is not sent for a certain period from the indoor unit which has been used to send signals, [E06] is normally displayed.
—
E07
—
—
I/F
Indoor/outdoor communication circuit error (Detected at outdoor side)
All stop
Transmission from outdoor to • Check outdoor terminator resistor setup (SW30-2). indoor cannot continue for 30 • Check the communication connection between indoor and outdoor. seconds.
E08
E08
96
Indoor I/F
Duplicated indoor addresses
All stop
Multiple indoor unit address setup are duplicated.
E09
—
—
99
E10
—
—
CF
Duplicated indoor addresses
Remote Duplicated master remote controller controllers
Indoor unit Communication error between indoor P.C. board assembly
Corresponding Signal could not be sent from • Check the communication wire of remote controller: Exchange remote controller. unit only stops. remote controller to indoor unit.
• • • •
Check power-ON order of indoor/outdoor. Check indoor address setup. Check inter-unit cabling between indoor and outdoor. Check outdoor end terminal resistance setup (SW30-2).
• • • • • •
Check the power supply of indoor unit. (Power-ON) Check connection of communication line between indoor and outdoor. Check connector connection for communication in indoor P.C. board. Check connector connection for communication in outdoor P.C. board. Check indoor P.C. board failure. Check outdoor P.C. board (I/F) failure.
• Check indoor address. • Check the change of remote controller connection (Group / individual) after setup of indoor address.
Corresponding In 2-remote controller control • Check remote controller setup. unit only stops. (including wireless), both are • Check remote controller P.C. board. setup as master (Header indoor unit stops and other indoor unit is operating.) Corresponding There is any trouble in power unit only stops. line.
• Indoor P.C. board failure
Check code Main Outdoor 7-segment display remote Sub-code controller Check code E12
E12
E15
E15
E16
E16
01: Indoor/outdoor communication 02: Between outdoors communication —
00: Capacity over 01 to: No. of connected units
Detected AI-NET central control position remote controller
Check code name
Status
Error detection condition
Check item (position)
42
I/F
Automatic address start error
All stop
• When indoor automatic address started, other refrigerant circuit system was setting automatic address. • When outdoor automatic address started, indoor automatic address was executed.
• Setup the address again after disconnecting communication connection with other refrigerant circuit system.
42
I/F
No corresponding indoor unit during automatic address
All stop
Indoor unit is not found when indoor automatic address • Check the communication line connection between indoor and outdoor. start was set up. • Check the electric power line error in indoor. • Check the noise of surrounding devices. • Power failure • Check indoor P.C. board error.
89
I/F
No. of connected indoor units / Capacity over
All stop
• Total capacity of indoor units exceeded 135% of total • Check the connection capacity of indoor unit. outdoor capacity. • Check the HP capacity of indoor unit. • No. of connected indoor units are more than 48 units. • Check the indoor/outdoor capacity setup • Check the No. of connected indoor units. [Note] If this code appears after backup setup of outdoor unit • Check the outdoor I/F P.C. board error trouble, set up “No. capacity-over detection”. Setup method of “No. capacity-over detection” Turn on SW09/Bit 2 on I/F P.C. board of outdoor header unit.
125
E18
—
—
97, 99
Indoor unit
Communication error between indoor header and follower units
Corresponding Regular communication between indoor header and unit only stops. follower units
E19
E19
00: No header unit 02: Two or more header units
96
I/F
Outdoor unit quantity error
All stop
• There are multiple outdoor units in 1 line. • There is none of outdoor unit in 1 line.
E20
E20
01: Connection of outdoor of other line 02: Connection of indoor of other line
42
I/F
Other line unit connected during automatic address
All stop
Unit of other line was connected when indoor automatic Separate the cable between lines according to automatic address started. address setup method in “Address setup”.
E23
E23
—
15
I/F
Communication sending error between outdoor units
All stop
Transmission of other outdoor unit was unavailable for 30 seconds or more.
In this model, only one outdoor unit is provided to one refrigerant line. Be sure to check there is no communication connection with outdoor unit in the other refrigerant line.
E25
E25
—
15
I/F
Duplicated outdoor follower address setup
All stop
Outdoor addresses manually set up are duplicated.
Note) Do not set up the outdoor address manually.
E26
E26
No. of normally received outdoor units
15
I/F
Decreased number of connected outdoor units
All stop
The signal was not returned for constant from the outdoor unit which was receiving signal.
In this model, only one outdoor unit is provided to one refrigerant line. Be sure to check there is no communication connection with outdoor unit in the other refrigerant line.
E28
E28
No. of detected outdoor units
d2
I/F
Outdoor follower unit error
All stop
Outdoor header unit received error code from outdoor follower unit.
• Check the check code of outdoor follower unit.
• Check cable of the remote controller. • Check power cabling of indoor. • Check P.C. board of indoor. The outdoor unit connected with communication cable between indoor and outdoor (U1.U2) is the outdoor unit. • Check connection of communication line between indoor and outdoor. • Check outdoor P.C. board(I/F) error.
Convenient functions Convenient functions When pushing SW04 for 1 second or more under condition that [E28] is displayed on 7-segment display of outdoor header unit, the fan of outdoor unit which stopped abnormally starts rotating. If pushing SW04 and SW05 simultaneously, the fan of normal outdoor unit operates. When pushing SW05 singly, the operation of fan is cleared.
Check code Outdoor 7-segment display Main remote controller Check code Sub-code 01: 02: 03: 04: 05: 06: 07:
IPDU1 error IPDU2 error IPDU1, 2 errors Fan IPDU error IPDU1 + Fan IPDU error IPDU2 + Fan IPDU error All IPDU error or communication error between IPDU and I/F P.C. board or outdoor I/F P.C. board error
AI-NET central control remote controller
Detected position
Check code name
I/F
IPDU communication error
Status
Error detection condition
All stop
Communication of each IPDU (P.C. board) in inverter box interrupted.
Check item (position)
126
E31
E31
F01
—
—
OF
Indoor unit Indoor TCJ sensor error
Corresponding • Resistance value of sensor is • Check connection/cabling of TCJ sensor connector. unit only stops infinite or zero. (Open/Short) • Check characteristics of TCJ sensor resistance value. • Check indoor P.C. board error.
F02
—
—
Od
Indoor unit Indoor TC2 sensor error
Corresponding • Resistance value of sensor is • Check connection/cabling of TC2 sensor connector. unit only stops. infinite or zero (Open/Short). • Check characteristics of TC2 sensor resistance value. • Check indoor P.C. board error.
F03
—
—
93
Indoor unit Indoor TC1 sensor error
Corresponding • Resistance value of sensor is • Check connection/cabling of TC1 sensor connector. unit only stops. infinite or zero (Open/Short). • Check characteristics of TC1 sensor resistance value. • Check indoor P.C. board error.
F04
F04
—
19
I/F
TD1 sensor error
All stop
• Resistance value of sensor is • Check connection of TD1 sensor connector. infinite or zero (Open/Short) • Check characteristics of TD1 sensor resistance value. • Check outdoor P.C. board (I/F) error.
F05
F05
—
A1
I/F
TD2 sensor error
All stop
• Resistance value of sensor is • Check connection of TD2 sensor connector. infinite or zero (Open/Short) • Check characteristics of TD2 sensor resistance value. • Check outdoor P.C. board (I/F) error.
F06
F06
—
18
I/F
TE1 sensor error
All stop
• Resistance value of sensor is • Check connection of TE1 sensor connector. infinite or zero (Open/Short). • Check characteristics of TE1 sensor resistance value. • Check outdoor P.C. board (I/F) error.
F07
F07
—
18
I/F
TL sensor error
All stop
• Resistance value of sensor is • Check connection of TL sensor connector. infinite or zero (Open/Short). • Check characteristics of TL sensor resistance value. • Check outdoor P.C. board (I/F) error.
F08
F08
—
1b
I/F
TO sensor error
All stop
• Resistance value of sensor is • Check connection of TO sensor connector. infinite or zero (Open/Short). • Check characteristics of TO sensor resistance value. • Check outdoor P.C. board (I/F) error.
F10
—
—
OC
Indoor
Indoor TA sensor error
F12
F12
A2
I/F
TS1, TS2 sensor error
01: TS1 02: TS2
CF
• Check connection of communication connector and disconnection between IPDU and I/F P.C. board. • Check outdoor P.C. board (I/F, IPDU, Fan IPDU) error. • Check external noise. • Check power supply P.C. board for fan error.
Corresponding • Resistance value of sensor is • Check connection/cabling of TA sensor connector. unit only stops. infinite or zero (Open/Short). • Check characteristics of TA sensor resistance value. • Check indoor P.C. board error. All stop
• Resistance value of sensor is • Check connection of TS1 or TS2 sensor connector. infinite or zero (Open/Short). • Check characteristics of TS1, TS2 sensor resistance value. • Check outdoor P.C. board (I/F) error.
Check code Outdoor 7-segment display Main remote controller Check code Sub-code F13
F13
F15
F15
F16
01: Compressor 1 side 02: Compressor 2 side
Detected AI-NET position central control remote controller IPDU
—
18
F16
—
F23
F23
F24
Status
Error detection condition
Check item (position)
TH sensor error
All stop
• Resistance value of sensor is • IGBT built-in temp sensor error infinite or zero (Open/Short). → Exchange IPDU P.C. board.
I/F
Outdoor temp sensor miscabling (TE1, TL)
All stop
• Check installation of TE1 sensor and TL sensor. During operation of compressor in HEAT mode, the • Check characteristics of TE1 and TL sensor resistance value. TE1 detection temp was higher • Check outdoor P.C. board (I/F) error. than that of TL by the specified value continued for 3 minutes or more.
43
I/F
Outdoor pressure sensor miscabling (Pd, Ps)
All stop
High-pressure Pd sensor and low-pressure Ps sensor were exchanged, or output voltages of both sensors are zero.
• • • • •
Check connection of high-pressure Pd sensor connector. Check connection of low-pressure Ps sensor connector. Check pressure sensors Pd and Ps error. Check outdoor P.C. board (I/F) error. Check compression error of compressor.
—
43
I/F
Ps sensor error
All stop
Output voltage of Ps sensor was zero.
• • • • • • •
Misconnection of Ps sensor and Pd sensor connectors Check connection of Ps sensor connector. Check Ps sensor error. Check compression error of compressor. Check 4-way valve error. Check outdoor P.C. board (I/F) error. Check SV4 circuit error.
F24
—
43
I/F
Pd sensor error
All stop
Output voltage of Pd sensor • Check connection of Pd sensor connector. was zero. (Sensor Open) • Check Pd sensor error. Pd > 4.15MPa during stop of • Check outdoor P.C. board (I/F) error. compressor
F29
—
—
12
Indoor
F31
F31
—
1C
I/F
Outdoor EEPROM error
All stop (*1)
H01
H01
01: Compressor 1 side 02: Compressor 2 side
1F
IPDU
Compressor breakdown
All stop
Inverter current detection circuit • Check power voltage. (AC220–240V ± 10%). detected over-current and • Check compressor error. stopped. • Check cause of abnormal overload operation. • Check outdoor P.C. board (IPDU) error.
H02
H02
01: Compressor 1 side 02: Compressor 2 side
1d
IPDU
Compressor error (lock) MG-SW error OCR operation
All stop
Over-current was detected several seconds after header compressor had started.
127
43
Check code name
(*1) All stop only in case of the header unit
Indoor other error
The follower unit continues operation.
Corresponding Indoor P.C. board did not unit only stops. operate normally.
• Check indoor P.C. board error (EEPROM error).
Outdoor P.C. board (I/F) did not • Check power voltage. operate normally. • Check power noise. • Check outdoor P.C. board (I/F) error.
• • • • •
Check compressor error. Check power voltage. (AC380–10%, 415V +10%). Check cable of compressor and phase-missing. Check connector/terminal connection on IPDU P.C. board. Check conduction of case heater. (Check activation error due to liquid stagnation in compressor.) • Check outdoor P.C. board (IPDU) error. • Check outdoor MG-SW or OCR.
MG-SW : Magnet Switch, OCR : Over-current Relay
Check code Outdoor 7-segment display Main remote controller Check code Sub-code H03
H04
H04
H06
H06
01: Compressor 1 side 02: Compressor 2 side
Detected position
Check code name
Status
Error detection condition
Check item (position)
• Check cabling of current detection circuit system. • Check outdoor P.C. board (IPDU) error.
17
IPDU
Current detection circuit system error
All stop
While header compressor stopped, current flowed more than the specified amount.
—
44
I/F
Compressor 1 case thermo operation
All stop
Compressor 1 case thermostat • Check compressor 1 case thermo circuit. (Connector, cable, P.C. board) performed protective operation. • Check full opening of service valve. (Gas and liquid side) • Check outdoor PMV clogging. (PMV1, 2, 3) • Check SV41 circuit leakage. • Check miscabling/misinstallation of SV41 and SV42. • Check valve open status of indoor PMV. • Check 4-way valve error. • Check refrigerant shortage. • Check SV5 leak. • Check SV11 circuit. (Wiring, OFF at one side only) • Check mispiping of discharge gas/suction gas main pipe. • Check Flow selector unit. Check leakage of SVD valve and SVS valve. (Check leakage of SVDD valve and SVSS.) Check mispiping of FS unit connecting pipe (Suction gas/Discharge gas), wiring between FS unit and indoor unit, and connection of connectors. Check miswiring of SVS/SVD valves.
—
20
I/F
Low-pressure protective operation
All stop
Low-pressure Ps detected • Check full opening of service valve. operation lower than 0.02MPa. (Discharge gas, suction gas and liquid side) • Check outdoor PMV clogging. (PMV1, 2) • Check SV2 circuit and SV4 circuit error. • Check low-pressure Ps sensor error. • Check indoor air filter clogging. • Check valve open of indoor PMV. • Check refrigerant pipe clogging. • Check outdoor fan operation. (All heating, mainly heating, part cooling operation) • Check refrigerant shortage. • Check clogging of circuit at auxiliary heat exchanger side. (PMV3, SV12, check valve) • Check 4-way valve error. (Reversal error) • Check mispiping of discharge gas/suction gas main pipe. • Check Flow selector unit. Check miswiring of discharge gas/suction gas pipe to FS unit. Check wiring between FS unit and indoor unit. Check miswiring of SVD/SVS valves, misinstallation of coil. Check opened status of SVS valve.
128
H03
AI-NET central control remote controller
Check code Outdoor 7-segment display Main remote controller Check code Sub-code H07
H07
—
Detected Check code name Status Error detection condition AI-NET position central control remote controller d7
I/F
Check item (position)
Protection for oil All stop The operating compressor Check all the outdoor units in the corresponding line. level drop detection detected oil shortage • Check full opening of service valve of balance pipe. continuously for 2 hours. • Check connection and installation of TK1, TK2, TK3, and TK4 sensors. • Check characteristics of TK1, TK2, TK3, and TK4 resistance values. • Check gas leak and oil leak in the same line. • Check refrigerant stagnation in compressor. • Check error of SV3A, SV3B, SV3C, SV3D, and SV3E valves. • Check clogging of oil separator oil return circuit. • Check clogging of oil-equation circuit. • Check TS1, TS2 sensors (Miswiring and misinstallation of TS1 and TS2) • Check leakage of SV6 circuit. • Check FS unit. Leakage of check valve of bypass between liquid pipe and discharge gas pipe Mispiping of discharge/suction gas connection Miswiring of SVD/SVS valve/Misinstallation of coil • Check whether there is no setup missing of indoor unit in all cooling operation mode
H08
H08
129 H14
H14
01: 02: 03: 04:
TK1 sensor error TK2 sensor error TK3 sensor error TK4 sensor error
—
d4
44
I/F
I/F
Oil level detective temp sensor error
Compressor 2 case thermo operation
All stop • Resistance value of sensor is infinite or zero. (Open/Short)
• Check connection of TK1 sensor connector. • Check characteristics of TK1 sensor resistance value. • Check outdoor P.C. board (I/F) error.
All stop • Resistance value of sensor is infinite or zero. (Open/Short)
• Check connection of TK2 sensor connector. • Check characteristics of TK2 sensor resistance value. • Check outdoor P.C. board (I/F) error.
All stop • Resistance value of sensor is infinite or zero. (Open/Short)
• Check connection of TK3 sensor connector. • Check characteristics of TK3 sensor resistance value. • Check outdoor P.C. board (I/F) error.
All stop • Resistance value of sensor is infinite or zero. (Open/Short)
• Check connection of TK4 sensor connector. • Check characteristics of TK4 sensor resistance value. • Check outdoor P.C. board (I/F) error.
All stop Compressor 2 case thermostat operated.
• • • • • • • • • • •
Check compressor 2 case thermo circuit. (Connector, cable, P.C. board) Check full opening of service valve. (Gas and liquid side) Check outdoor PMV clogging. (PMV1, 2) Check SV42 valve leak. Check miscabling/misinstallation of SV41 and SV42. Check valve opening of indoor PMV. Check 4-way valve error. Check refrigerant shortage. Check SV11 circuit. (Wiring, OFF at one side only) Check mispiping of discharge gas/suction gas main pipe. Check Flow selector unit. Check leakage of SVD valve and SVS valve. (Check leakage of SVDD valve and SVSS.) Check mispiping of FS unit connecting pipe (Suction gas/Discharge gas), wiring between FS unit and indoor unit, and connection of connectors. Check miswiring of SVS/SVD valves.
Check code Outdoor 7-segment display Main remote controller Check code Sub-code H16
H16
01: TK1 oil circuit system error 02: TK2 oil circuit system error 03: TK3 oil circuit system error 04: TK4 oil circuit system error
Detected AI-NET position central control remote controller d7
I/F
Status
Error detection condition
Oil level detective circuit system error MG-SW error OCR operation
All stop
Temperature change of TK1 could not be detected after compressor 1 started operation.
• • • • •
Temperature change of TK2 could not be detected after compressor 2 started operation.
• • • • •
Temperature change of TK3 could not be detected after compressor started operation.
• • • • •
Temperature change of TK4 could not be detected after compressor started operation, or the difference from other TK sensor changed for a constant time only within the specified range.
• • • • •
130
Check code name
Duplicated indoor center units
Corresponding There are multiple header unit only stops. units in a group.
Check item (position)
Check TK1 sensor coming-off. Check characteristics of TK1 sensor resistance value. Check TK1, TK2, TK3, and TK4 misconnection. Check operation error of SV3E valve. Check capillary clogging of oil-equation circuit and operation error of stop valve. • Check refrigerant stagnation in compressor. • Check MG-SW or OCR. Check TK2 sensor coming-off. Check characteristics of TK2 sensor resistance value. Check TK1, TK2, TK3, and TK4 misconnection. Check SV3E valve operation. Check capillary clogging of oil equalization circuit and check stop valve operation. • Check refrigerant stagnation in compressor shell. • Check MG-SW or OCR. Check TK3 sensor coming-off. Check characteristics of TK3 sensor resistance value. Check TK1, TK2, TK3, and TK4 misconnection. Check SV3E valve operation. Check capillary clogging of oil-equalization circuit and check valve operation. • Check refrigerant stagnation in compressor shell. • Check MG-SW or OCR. Check TK4 sensor coming-off. Check characteristics of TK4 sensor resistance value. Check TK1, TK2, TK3, and TK4 misconnection. Check SV3E valve operation. Check capillary clogging of oil-equalization circuit and check valve operation. • Check refrigerant stagnation in compressor shell. • Check MG-SW or OCR.
• Check indoor address. • Check the change of remote controller connection (Group/individual) after indoor address setup.
L03
—
—
96
Indoor
L04
L04
—
96
I/F
Duplicated outdoor line address
All stop
Line address setup is duplicated against the outdoor unit in different refrigerant pipe system.
L05
—
—
96
I/F
Duplicated indoor units with priority (Displayed on indoor unit with priority)
All stop
Indoor units with priority were • Check display of indoor unit with priority. duplicated.
• Check line address.
MG-SW : Magnet Switch, OCR : Over-current Relay
Check code Main Outdoor 7-segment display remote controller Check code Sub-code L06
L06
L07
—
L08
L08
No. of indoor units with priority
Detected AI-NET central control position remote controller
Check code name
Status
Duplicated indoor units with priority (Displayed on the unit other than indoor unit with priority)
All stop
—
99
Indoor
Group line in individual indoor unit.
Corresponding At least one indoor unit connected unit only stops. to a group existed in the individual indoor units.
• Check indoor address.
—
99
Indoor
Indoor group / address unset
Corresponding Address was not yet set up. unit only stops.
• Check indoor address.
Indoor capacity unset
Corresponding Indoor unit capacity was unset. unit only stops.
Set up indoor capacity. (DN=11)
—
46
Indoor
L10
L10
—
88
I/F
Outdoor capacity unset
L17
L17
—
I/F
Inconsistent models of outdoor units
L18
L18
8A
I/F
FS unit system error
L20
—
—
98
AI-NET, Indoor
L28
L28
—
46
L29
L29
CF
Corresponding indoor address
131 L30
L30
• Check display of indoor unit with priority and outdoor unit.
I/F
—
IPDU1 error IPDU2 error IPDU1, 2 errors Fan IPDU error IPDU1 + Fan IPDU error IPDU2 + Fan IPDU error All IPDU error or communication error between IPDU and I/F P.C. board, or outdoor I/F P.C. board error
Detected indoor address
All stop
Indoor units with priority were duplicated.
Check item (position)
96
L09
01: 02: 03: 04: 05: 06: 07:
Error detection condition
Note) After installation, this code is displayed when the power is first turned on.
Check model setup on outdoor I/F P.C. board A’ssy for service. On the I/F P.C. board for service, jumper line was not cut according to the model. 1 and 2 series outdoor units have been mixed.
Corresponding An indoor unit which is not unit only stops. connected with a FS unit is operating without setup of cooling only mode.
• Check outdoor units. • Check setup of remote controller (DN=[OFF]). • Check FS unit. Check pipe connection to FS unit. (Mispiping between discharge gas and suction gas) Check miswiring/misinstallation of SVS/SVD valves. • Check central control address. • Check network adaptor P.C. board. (In case of AI-NET)
Duplicated central control addresses
All stop
Duplicated central control addresses
I/F
Quantity over of connected outdoor units
All stop
There were more than four outdoor • Check No. of connected outdoor units. (Max. 4 units per 1 system) units. • Check communication line between outdoor units. • Check outdoor P.C. board (I/F) error.
I/F
IPDU quantity error
All stop
No. of IPDU units detected when power was turned on were less.
• Check model setup for outdoor I/F service P.C. board. • Check connection of UART communication connector. • Check IPDU, fan IPDU, and I/F P.C. board error. Note) UART: Universal Asynchronous Receiver Transmitter
b6
Indoor
Interlock in indoor unit from outside
Corresponding • Outside error input terminal unit only stops. Detected signal to (CN80) for more than 1 minute
n Outside device is connected to connector (CN80): 1) Check outside device error. 2) Check indoor P.C. board error. n Outside device is not connected to connector (CN80): 1) Check indoor P.C. board error.
—
L31
—
—
I/F
Extended IC (Integrated Circuit) error
Operation continues.
P.C. board (I/F) parts error
Check indoor (I/F) P.C. board.
Check code Outdoor 7-segment display Main remote controller Check code Sub-code
Detected AI-NET position central control remote controller
Check code name
Status
Error detection condition
Check item (position)
• Check the lock of fan motor (AC fan). • Check cabling.
132
P01
—
—
11
Indoor
Indoor fan motor error
Corresponding unit only stops.
P03
P03
—
1E
I/F
Discharge temp TD1 error
All stop
Discharge temp (TD1) exceeded 115°C.
• • • • • • • • • • •
Check full opening of outdoor service valves (Gas side, Liquid side). Check clogging of outdoor PMV. (PMV1,2) Check characteristics of TD1 sensor resistance value. Check refrigerant shortage. Check 4-way valve error. Check leakage of SV41 circuit. Check SV4 circuit. (Miswiring and misinstallation of SV41 and SV42) Check leakage of SV5 circuit. Check leakage of SV6 circuit. (Capillary clogging, valve operation error) Check mispiping of discharge gas/suction gas main pipe. Check Flow selector unit. Check leakage of SVD valve and SVS valve. (Check leakage of SVDD valve and SVSS.) Check mispiping of FS unit connecting pipe (Suction gas/Discharge gas), wiring between FS unit and indoor unit, and connection of connectors. Check miswiring of SVS/SVD valves.
P04
P04
01: Compressor 1 side 02: Compressor 2 side
21
I/F
Actuation of high-pressure SW
All stop
High-pressure SW actuated.
• • • • • • • • • • • • • • • • • • •
Check Pd pressure sensor error. Check full opening of outdoor service valves (Gas side, Liquid side). Check outdoor fan error. Check outdoor fan motor error. Check clogging of outdoor PMV. (PMV1,2) Check clogging of indoor/outdoor heat exchangers. Check short-circuiting of outdoor suction/discharge air. Check clogging of SV2 circuit. Check outdoor P.C. board (I/F) error. Check indoor fan system error. (Cause of air volume decrease) Check opening of indoor PMV. Check miscabling of communication line between indoor and outdoor. Check operation error of check valve of discharge pipe. Check SV4 valve circuit. Check SV5 valve circuit. Check refrigerant overcharge. Check mispiping of discharge gas/suction gas main pipe. Check circuit clogging at auxiliary heat exchanger side. (PMV3, SV12, check valve) Check FS unit. Check clogging of SVD valve and operation error. Check wiring inside of FS unit. (SVD/SVS coil miswiring, etc.) Check wiring between FS unit and indoor unit. (Miswiring, Disconnection, Wiring missing)
P05
P05
01: Power supply missing phase 02: Power supply phase order (reversed phase)
AF
I/F
Phase missing or reversed phase order
All stop
• Missing phase was detected • Check outdoor power line. when the power turned on. • Check outdoor P.C. board (I/F) error. • Reversed phase was detected when the power turned on.
Check code Detected Check code AI-NET Main Outdoor 7-segment display name central control position remote Sub-code remote controller controller Check code
Status
Error detection condition
Check item (position)
P07
P07
01: Compressor 1 side 02: Compressor 2 side
1C
IPDU I/F
Heat sink overheat error
All stop
IGBT built-in temp sensor (TH) • Check power voltage. was overheated. • Check outdoor fan system error. • Check clogging of heat sink cooling duct. • Check fixation between IGBT and heat sink. (Check screwing and contact.) • Check IPDU error.(IGBT built-in temp sensor (TH) error).
P10
P10
Indoor address with trouble
Ob
Indoor
Indoor overflow error
All stop
• Float switch operated. • Float switch circuit disconnected or the connector came off.
• • • • •
Check the float switch connector. Check operation of drain pump unit. Check the drain pump circuit. Check clogging of drain pipe. Check indoor P.C. board error.
Corresponding • The value of motor speed unit only stops. deviated from target value was detected for certain time. The standard ducted unit air conditioner utilizes a direct current (DC) indoor fan motor that features current • Over-current protection limiting protection. In the event power is not isolated prior to service, the protective control circuit will activate operated. and stop the unit operating. The check code “P12”will be displayed on the remote controller-once service work has been completed, this code can be cleared by switching off then on the electrical isolation device of the indoor unit and pressing the operation stop button on the remote controller to reset the system
• • • • •
Check connection of fan connector and wiring. Check fan motor error. Check indoor P.C. board error. Check influence of outside air control. Check indoor type code (DN=10) and the capacity code (DN=11).
• • • • • • •
Check full close operation of outdoor PMV (1, 2). Check Pd and Ps sensor error. Check clogging of SV2 circuit. Check clogging of 4-way valve error circuit. Check outdoor P.C. board (I/F) error. Check capillary clogging of oil return circuit from oil separator. Check TS1, TS2 sensor error.
Indoor fan motor error
—
—
11
Indoor
P13
P13
—
47
I/F
Outdoor liquid back detection error
All stop
In heating While the system is operating in HEAT mode, outdoor PMV of which opening degree was 100 pulse or less for a certain time.
P15
P15
01: TS condition
AE
I/F
Gas leak detection (TS1 condition)
All stop
• Check refrigerant shortage. Suction temp exceeded the judgment standard temp for 10 • Check full open of outdoor service valves (gas side, liquid side). minutes or more. • Check outdoor PMV clogging (PMV1, 2). TS error judgment standard • Check characteristics of TS1 sensor resistance value. • Check 4-way valve error. temperature • Check leakage of SV4 circuit. In cooling operation: 60°C or higher • Check leakage of SV5 circuit. • Check mispiping of discharge gas/suction gas main pipe. In heating operation: 40°C or higher • Check Flow selector unit. Check leakage of SVD valve and SVS valve. (Check leakage of SVDD valve and SVSS.) Check mispiping of FS unit connecting pipe (Suction gas/Discharge gas), wiring between FS unit and indoor unit, and connection of connectors. Check miswiring of SVS/SVD valves.
02: TD condition
AE
I/F
Gas leak detection (TD condition)
All stop
Discharge temperature TD1 or • Check refrigerant shortage. TD2 was continuously 108°C • Check outdoor PMV clogging (PMV1, 2). or higher for 10 minutes. • Check characteristics of TD1, TD2 sensor resistance value. • Check indoor air filter clogging. • Check pipe clogging. • Check SV4 circuit (Valve leakage, misinstallation) • Check mispiping of discharge gas/suction gas main pipe. • Check Flow selector unit. Check leakage of SVD valve and SVS valve. (Check leakage of SVDD valve and SVSS.) Check mispiping of FS unit connecting pipe (Suction gas/Discharge gas), wiring between FS unit and indoor unit, and connection of connectors. Check miswiring of SVS/SVD valves.
133
P12
Check code Outdoor 7-segment display Main remote controller Check code Sub-code
Detected AI-NET position central control remote controller
Check code name
Status
Error detection condition
Check item (position)
P17
—
bb
I/F
Discharge All stop Discharge temperature • Check full opening of outdoor service valves (gas side, liquid side). temp TD2 error (TD2) exceeded 115°C. • Check clogging of outdoor PMV (PMV1, 2). • Check characteristics of TD2 sensor resistance value. • Check 4-way valve error. • Check leakage of SV42 circuit. • Check SV4 circuit. (Miscabling and misinstallation of SV41 and SV42) • Check leakage of SV5 valve circuit. • Check SV6 circuit. (Clogging, Valve operation error) • Check mispiping of discharge gas/suction gas main pipe. • Check Flow selector unit. Check leakage of SVD valve and SVS valve. (Check leakage of SVDD valve and SVSS.) Check mispiping of FS unit connecting pipe (Suction gas/Discharge gas), wiring between FS unit and indoor unit, and connection of connectors. Check miswiring of SVS/SVD valves.
P19
P19
Detected outdoor unit No.
8
I/F
4-way valve operation error
• Error of 4-way valve error All stop When abnormal refrigerating cycle data • Check coil error and connector connection of 4-way valve. was detected in heating • Check characteristics of TS1/TE1 sensor resistance value. • Check characteristics of Pd, Ps pressure sensor output voltage. • Check misconnection of TE1 and TL sensors. • Check Flow selector unit. Check leakage of SVD valve and SVS valve. (Check leakage of SVDD valve and SVSS.) Check mispiping of FS unit connecting pipe (Suction gas/Discharge gas).
P20
P20
—
22
I/F
High-pressure protective operation
All stop Pd sensor detected 3.6MPa or more.
134
P17
• • • • • • • • • • • • • • • • • • •
Check Pd pressure sensor error. Check full opening of service valves (Gas side, Liquid side). Check outdoor fan error. Check outdoor fan motor error. Check clogging of outdoor PMV. (PMV1,2) Check clogging of indoor/outdoor heat exchangers. Check air short-circuiting in outdoor unit. Check clogging of SV2 circuit. Check outdoor P.C. board (I/F) error. Check indoor fan system error. (Cause of air volume decrease) Check valve opening of indoor PMV. Check miscabling of communication line between indoor and outdoor. Check operation error of check valve of discharge pipe. Check circuit of gas balance SV4 valve. Check mispiping of discharge gas/suction gas main pipe. Check operation error of check valve of discharge gas pipe. Check circuit of SV11 valve. (Clogging, OFF at one side only) Check clogging of circuit at auxiliary heat exchanger side. (Miswiring, Disconnection, Wiring missing) Check Flow selector unit. Check leakage of SVD valve and operation error. Check wiring inside of FS unit. (SVD/SVS coil miswiring, etc.) Check wiring between FS unit and indoor unit. (Miswiring, Disconnection, Wiring missing) • Check circuit of SV5 valve. • Check refrigerant overcharge.
Check code Outdoor 7-segment display Main remote controller Check code Sub-code P22
P22
0: IGBT shortage 1: Position detection circuit error 3: Motor lock error 4: Motor current error detection C: TH sensor temp. error D: TH sensor error E: Vdc error
Detected Check code name AI-NET position central control remote controller 1A
FAN-IPDU Outdoor fan IPDU error
Status
Error detection condition
Check item (position)
(Sub-code: 0) • Check fan motor. (Interphase short-circuit) • Short-circuit current was detected at start • Check fan IPDU error. time. • Short-circuit current was detected when checking IGBT short-circuit before start time.
All stop
(Sub-code: 1) • The standard value of detection circuit of fan IPDU current fluctuated at start time.
• Check fan IPDU error.
All stop
(Sub-code: 3) • Abnormal current was detected within 30 seconds after start time.
• Check fan motor. (Lock, phase missing) • Check cause of abnormal overload at start time. • Check connection of connector to fan motor.
All stop
(Sub-code: 4) • Check power supply voltage. • Check fan IPDU error. • Short-circuit current was detected when 2 seconds or more passed after start time. • Over-current was detected when 30 seconds or more passed after start time.
All stop
(Sub-code: C) • Heat sink sensor (TH) of fan IPDU detected 95°C error.
• Check outdoor fan system. • Check fan IPDU error. • Check fixation between fan IPDU and heat sink.
All stop
(Sub-code: D) • Heat sink sensor (TH) of fan IPDU detected short-circuiting or open.
• Check fan IPDU error.
All stop
(Sub-code: E) • Check input power supply voltage of the fan IPDU. • Check power supply P.C. board error of the fan IPDU. • Input power supply voltage of the fan IPDU over the setup value was detected. • Check error of external electrolytic condenser. • Input power supply terminal of the fan IPDU was unconnected. • Power supply P.C. board error of the fan IPDU
135
All stop
P26
P26
01: Compressor 1 side 02: Compressor 2 side
14
IPDU
G-Tr short-circuit protection error
All stop
Instantaneous over-current was detected when • Check connector connection and wiring on IPDU P.C. board. compressor started. • Check compressor error and defect of compressor coil. • Check outdoor P.C. board (IPDU) error.
P29
P29
01: Compressor 1 side 02: Compressor 2 side
16
IPDU
Compressor position detection circuit error
All stop
Position detected was not normal.
P31
—
—
47
Indoor
Corresponding E07/L07/L03/L08 was detected when other Other indoor error (Group follower unit unit only stops. indoor unit in the group was defective. error)
• Check connector connection and wiring. • Check compressor error and defect of compressor coil. • Check P.C. board (IPDU) error. • Check indoor P.C. board.
Error detected by TCC-LINK central control device Check code Outdoor 7-segment display Display on central control device Check code Sub-code
AI-NET central control remote controller
Detected position
TCC-LINK
C05
—
—
C06
—
—
C12
—
—
P30
Differs according to error contents of the with alarm
Check code name
Status
Error detection condition
Check item (position)
TCC-LINK central control Operation Signal is not transmit from • Check central control device error. device transmission error continued. central control device. • Check communication line error of central control device. • Check setup of terminator resistor. TCC-LINK central control Operation Signal is not received from • Check central control device error. device receiving error continued. central control device. • Check communication line error of central control device. • Check setup of terminator resistor. • Check the power of connecting destination connected device. • Check P.C. board error of the connected device.
HA control interface Interface batch alarm of HA control interface TCC-LINK
Follower unit error of group control
Operation Error was input in HA continued. control interface
• Check error input.
• Check the error code of the unit with alarm. Operation An error occurred in continued. follower unit of the group control. ([P30] is displayed only on the central remote controller.)
136
Duplicated central control Operation Central control addresses • Check the address setup. address continued. were duplicated.
(L20 is displayed.)
Error detected by AI-NET central control device Check code Outdoor 7-segment display
Detected position
Check code name
Status
Error detection condition
Check item (position)
Check code
Sub-code
AI-NET central control remote controller
—
—
—
97
AI-NET
AI-NET communication system error
Operation E07/L07/L03/L08 was continued. detected when other indoor unit in the group was defective.
• Check multiple network adapters. • Check wire and miscabling of remote controller: Only one network adapter can be connected to communication line of remote controller.
—
—
—
99
AI-NET
Duplicated network adapters
Operation Multiple network adapters continued. were connected to communication line of remote controller. (Detected at central controller side)
• • • •
—
—
—
b7
AI-NET
Error in indoor group
Operation Error of follower unit in the • Check follower unit in the group. continued. group
Main remote controller
Check communication line, miscabling, and power of indoor unit. Check communication. (X, Y terminals) Check network adapter P.C. board. Check the central controller (Central control remote controller, etc.)
* These errors are concerned to communication of remote controllers (A, B) and central system [AI-NET X, Y], and the main remote controller displays [E01], [E02], [E03], [E09], or [E18] in some cases and displays none in other cases according to the error.
Cautions when servicing for compressor 1. Removing wires of both compressors check output of the inverter as described below.
How to check inverter output 1. Turn off the power supply. 2. Remove the compressor lead cables from the compressors. (Be sure to remove lead cables of both compressors.) 3. Turn on the power supply and start cooling or heating operation. In this time, pay attention to touch the fasten receptacle terminal lug of the compressor leads so that they do not contact with other fasten receptacle terminal lug or other position (unit cabinet, etc.). 4. Check output voltage of compressor lead cable at inverter side. When the output voltage does not satisfy the criteria in the following table, replace IPDU P.C. board. No.
Measured position
Criteria
1
Between Red and White
400 V to 650 V
2
Between White and Black
400 V to 650 V
3
Between Black and Red
400 V to 650 V
∗ After checking the output, when connecting the compressor lead again to the compressor terminal, check surely there is no distortion on the fasten terminal lug. If it is loosened, caulk it with pinchers, etc and then connect lead to the terminal.
How to check resistance of compressor winding 1. Turn off the power supply. 2. Remove the compressor lead cables from the compressors. In each compressor, check the winding resistance between phases and resistance of the outdoor cabinet using a tester. • Is not it earthed? → Normal if 10MΩ or more are measured • Is not shorted between windings? → Normal if 0.7Ω to 0.9Ω are measured (Use a precise digital tester.)
How to check the outdoor fan motor 1. Turn off the power supply. 2. Take off three connectors (U.V.W) from the fan IPDU P.C. board. 3. Turn the fan with hands. If the fan does not turn, it is a fan motor error (Lock). Replace the fan motor. If the fan turns, measure the winding resistance between the phases of the connector (Motor winding) with a tester. If 13 to 33Ω are measured, it is normal. (Use a digital tester.)
137
9-5. Diagnosis Procedure for Each Check Code Check code name
Check code
[E01] / [–]
Cause of operation
Check code
Check code name
[E03] / [97]
Communication error between indoor and remote controller (Detected at indoor side)
(TCC-L / AI-NET)
Communication error between 1. Remote controller interconnecting cable error indoor and remote controller (Detected at remote controller side) 2. Indoor power supply error
(TCC-L / AI-NET)
3. Indoor P.C. board error 4. Remote controller address setup error 5. Remote controller P.C. board error
NO
Correct interconnection cable of remote controller.
YES
Correct connection and check circuit cabling.
Is the interconnection cable of remote controllers (A/B) normal?
Cause of operation No communication from remote controller and communication adaptor
This error is detected when the indoor unit cannot receive a signal from the remote controller. Check communication wiring of the remote controllers A and B. As communication is impossible, this fault code [E03] is not displayed on the main remote controller. It is displayed on TCC-LINK central controller.
YES Is there no disconnection or connector contact error on harness out of terminal block of indoor unit?
Check code
Check code name
[E04] / [04]
Indoor/Outdoor communication circuit error (Detected at indoor side)
(TCC-L / AI-NET)
NO NO
Is a group control operation?
Cause of operation 1. Power of outdoor unit was firstly turned on. 2. Connection error of communication line between indoor and outdoor 3. Terminal resistance setup error on outdoor header unit. 4. Address setup error
YES NO
Is power of each indoor unit turned on?
Check power connection status of indoor unit. (Turn on power again.)
YES
®
Was power turned on in order of indoor unit outdoor unit?
NO
®
Turn on power again in order of indoor unit outdoor unit.
YES
138
NO
Is power applied to remote controller? AB terminals: Approx. DC18V
®
Check indoor P.C. board. Defect Replace
Is connection (U1/U2 terminals) of indoor/outdoor interconnection cable normal?
YES
NO
Correct interconnection cable.
YES
Are two remote controllers used without the correct identification?
YES
Change one to main/other to sub. (Remote controller address connector)
NO
Is the end terminal resistance setup of outdoor unit normal?
NO
Correct the end terminal resistance setup.
YES
®
Check remote controller P.C. board. Defect Replace Is address setup correct?
NO
Set up address again.
YES
Check code
Check code name
[E02] / [–]
Remote controller sending error
(TCC-L / AI-NET)
Cause of operation Signal could not be sent to indoor unit. Check the communication wire of the remote controller.
Is power applied to fuse (F03) on indoor P.C. board?
YES
®
Sending circuit error of the remote controller Replace remote controller.
NO
Check connection of interconnection cable between indoor and outdoor is correct, and then connect communication line connector on indoor P.C. board (CN40) to CN44 (EMG).
YES
Is there no noise, etc?
* It is not displayed on 7-segment display of the central control controller. Is communication wiring between remote controller and indoor unit correct?
NO
YES
Check noise etc. and eliminate it if any.
NO
Correct the communication wiring.
®
Check indoor P.C. board. Defect Replace
For details, refer to “Troubleshooting in test operation”.
Check code name
Check code
[E06] / [04]
Cause of operation
Decreased number of indoor units 1. Communication lines (U1, U2) connection error between indoor and outdoor 2. Connector connection error of communication for indoor P.C. board 3. Connector connection error of communication for outdoor I/F P.C. board 4. Power supply of indoor unit (Is power turned on?)
(TCC-L / AI-NET)
Check code
Check code name
Cause of operation
[E07] / [–]
Indoor/Outdoor communication circuit error (Detected at outdoor side)
1. Outdoor communication terminal resistance setup error 2. Indoor/outdoor communication connection error
(TCC-L / AI-NET)
Is setup of terminal resistance of outdoor unit normal?
NO
YES Sub-code: No. of indoor units which received signals normally
Is there no mis-wiring/ disconnection on communication line betweenindoor and outdoor?
Is interconnection cable (U1, U2) between indoor and outdoor short-circuited?
YES Correct communication line.
NO
NO Is connection of CN40 connector on indoor P.C. board normal?
Correct setup of terminal resistance.
YES
NO NO
Is connection of interconnection cable between indoor and outdoor correct?
Correct short-circuit.
YES
YES Is connection of CN01 connector on outdoor I/F P.C. board normal?
Correct communication line.
NO
Correct wiring of the connector.
YES
139
Is power of indoor turned on?
YES NO
Is there an error on power cable to an outdoor unit?
Turn on power of indoor unit.
NO YES
Did a power failure occur?
NO
Is F400 (fuse) on I/F P.C. board failed?
YES * Check conduction with tester.
Correct power cable.
NO
Clear the fault code.
Turn on power to start operation.
YES
YES YES
Is there noise source?
Check noise etc. and eliminate it if any.
Is there no noise, etc?
NO NO
®
Check indoor P.C. board. Defect Replace
Eliminate noise.
(NOTE) 1. When signal is not sent for a certain period from the indoor unit which has been sending signals normally, [E06] is displayed.
®
Outdoor I/F P.C. board failure Replace
I/F P.C. board failure However an emergent operation is available by inserting connector from CN01 to CN33.
Check code
Check code name
[E08] / [96]
Duplicated indoor addresses
Cause of operation Indoor addresses are duplicated.
(TCC-L / AI-NET)
Check code
Check code name
[E12] / [42]
Automatic address start error
(TCC-L / AI-NET)
Sub-code: Duplicated indoor address
Using a main remote controller (RBC-AMT21E), check the setup item codes (DN code) 12, 13, and 14. When there is no address duplication, check to the following flowchart.
Is cable connection to communication line normal?
NO Correct cable connection.
Cause of operation 1. When indoor automatic address started, other refrigerant circuit system was setting automatic address. (Sub code : 01) 2. When outdoor automatic address started, the indoor automatic address was being set. (Sub-code: 02)
Sub-code: 01: Communication between indoor and outdoor 02: Communication between outdoor units
NO
Are U1, U2, U3, and U4 connectors connected? YES
YES Is communication line connected to the different outdoor unit?
Turn on power of outdoor unit again.
Disconnect relay connector of U1, U2, U3, and U4.
YES
Set up address again. (Refer to “Address setup procedure”.)
NO Is indoor unit quantity connected to outdoor unit correct?
NO Correct communication line.
YES
Check code
Check code name
[E15] / [42]
No corresponding indoor unit during automatic address
(TCC-L / AI-NET)
Set up indoor address again.
140 Check code
Check code name
[E09] / [99]
Duplicated master remote controller
(TCC-L / AI-NET)
Are two remote controllers set up as two master remote controllers?
YES
Cause of operation Setup of master remote controller is duplicated.
Correct setup of remote controllers one as a master, and the other as sub (remote controller address connector).
Is communication line between indoor and outdoor normal?
Cause of operation 1. Communication line connection error between indoor and outdoor. 2. Indoor power system error 3. Noise from surrounding devices 4. Power failure 5. Indoor P.C. board error
NO Correct communication line.
YES Is connection of CN40 connector on indoor P.C. board correct?
NO
Correct connection.
YES
NO
®
Check remote controller P.C. board. Failure Replace
Is connection of CN01 connector on I/F P.C. board of header outdoor unit correct?
NO Correct connection.
YES Is there any connection error of power cable? Check code
Check code name
[E10] / [CF]
Communication error in indoor P.C. board assembly
(TCC-L / AI-NET)
Cause of operation Indoor P.C. board error failure
YES Correct power cable.
NO Did a power failure occur?
YES
Set up address again after resetting power supply.
NO Is there any fault on power line?
YES
Check power voltage on line. Eliminate noise, etc.
Is there a noise source? NO
NO
®
Check indoor control P.C. board. Failure Replace
Set up address again after resetting power supply.
YES
Eliminate noise.
Check code
Check code name
[E16] / [89]
Connected indoor units capacity over
(TCC-L / AI-NET)
Sub-code: 00 : Capacity over
Cause of operation 1. There are 48 or more connected indoor units. 2. Capacity over of total connected indoor units. 3. Incorrect setup of indoor/outdoor capacity
Check code
Check code name
Cause of operation
[E18] / [97/99]
Communication error between indoor header and follower
Regular communication between indoor header and follower is unavailable.
(TCC-L / AI-NET)
Are remote controller interconnection wires (A/B) normal?
01 : ~ : Number of connected indoor units
NO
Correct remote controller interconnection wires.
YES
Correct connection. Check circuit wire.
NO
Check power connection status of indoor unit.
YES YES Is backup operation of outdoor unit being set up?
Perform setup of no detection for over capacity.
Is there any disconnection of connector or wiring from terminal block of indoor unit?
NO
NO NO Is No. of connected indoor units correct?
Excessive indoor units are connected. Correct miswiring.
NO Is a group control operation?
YES
YES NO
Is setup of indoor unit HP correct?
Correct HP setup.
Is the power of all indoor units turned on?
YES
Is total capacity of connected indoor units within 135%? (*1)
YES NO
Ensure capacity of connected indoor units within 135% of outdoor units.
®
Check indoor P.C. board. Failure Replace
Check indoor address.
YES
141
Correct indoor address. For a service P.C. board, check outdoor HP setup. (Set up jumper 9, 10, 11, and 12.)
OK
Set up outdoor HP. (Refer “How to exchange interface P.C. board”.)
NG
Check outdoor interface P.C. board.
(∗ ∗1) When capacity of the outdoor unit is 12HP, up to a maximum capacity 120% of indoor units can be connected.
Check code name
Check code
[E19] / [96]
Cause of operation
Header outdoor units quantity error 1. Misconnection of interconnection cable between indoor and outdoor 2. Outdoor I/F P.C. board error
(TCC-L / AI-NET)
Sub-code: 00: No header unit 02: Two or more header units
Are communication lines (U1, U2) between indoor and outdoor connected to multiple outdoor units?
YES
Connect communication line between indoor and outdoor to one unit per 1 system.
NO
Connect communication line between indoor and outdoor.
NO Is communication line between indoor and outdoor connected to one unit per 1 system? YES
Check I/F P.C. board.
Reference) When the power supply of the outdoor unit is first turned on, the check code [E19 00] is displayed until the power supply of the indoor units are turned on. However is not an error. When the power supply of the indoor units are this turned on, the check code is automatically reset.
Check code
Check code name
[E20] / [42]
Unit connected to other line during automatic address
(TCC-L / AI-NET)
Cause of operation When starting automatic indoor address, a device in another refrigerant system is connected.
Sub-code: 01: Connection of outdoor of another system 02: Connection of indoor unit of another system
Check code
Check code name
Cause of operation
[E25] / [15]
Duplicated address setup of terminal outdoor units
Addresses are duplicated by manual setting of outdoor address
(TCC-L / AI-NET)
Never set up the outdoor address manually.
Separate the wire between systems according to address setup method.
Check code
Check code name
Cause of operation
[E23] / [15]
Communication sending error between outdoor units
1. Interconnection cable error between outdoor unit 2. Communication error between outdoor units, I/F P.C. board error 3. Terminal resistance setup error between outdoor units
(TCC-L / AI-NET)
Is there miscabling or disconnection on communication line between outdoor units?
YES Correct communication line.
Check code name
[E26] / [15]
Decrease of connected outdoor units
(TCC-L / AI-NET)
Cause of operation 1. Outdoor unit backup setup 2. Outdoor power error 3. Communication line connection error between outdoor units 4. Connector error for communication 5. Outdoor I/F P.C. board error
Sub-code: No. of outdoor units which received signals normally YES
Is outdoor unit setting backup?
Clear the error and then start operation. (*1)
NO NO
NO
142
Is connection of CN03 connector on outdoor I/F P.C. board normal?
Check code
Is main power of follower unit turned on?
Turn on the main power supply.
YES
NO Correct wiring of cable connector.
YES
NO
Is communication line between outdoor units connected normally?
Correct connection of communication line.
YES Is main power of outdoor unit turned off?
YES Turn on main power of outdoor unit.
Is communication connector (CN03) between follower outdoor units connected?
Correct connection. (Communication connector: CN03)
YES
NO
(∗ ∗1) How to clear the error
Check I/F P.C. board. Is the terminal resistance between outdoor units turned on? (SW30 Bit 1)
NO
Set SW01/SW02/SW03 on I/F P.C. board of header unit to 2/16/1, and push SW04 for 5 seconds or more. (7-segment display: [Er.] [CL])
NO Turn the terminal resistance to ON.
YES YES Did power failure occur?
Clear fault code.
Check code
Check code name
[E28] / [d2]
Terminal outdoor unit error
Cause of operation
NO
Terminal unit error
(TCC-L / AI-NET) Is there no noise source, etc? NO
®
Check outdoor I/F P.C. board. Defect Replace
YES Check and eliminate noise, etc
Sub-code: Detected outdoor unit number
An error occurred on the terminal unit. Confirm the check code of the terminal unit using 7-segment display on the I/F P.C. board of the terminal unit and check it according to the diagnostic procedure for each fault code. How to identify the terminal outdoor unit on which error occurred Under condition that [E28] is displayed on the 7-segment display on the header unit, when pushing SW04 for 1 second or more, the fan on the faulty outdoor unit will rotate. Pushing SW05 alone, stops the fan rotation.
Check code
Check code name
[E31] / [CF]
IPDU communication error
Cause of operation
(TCC-L / AI-NET)
1. Connection error of communication line between IPDU and I/F P.C. board 2. I/F P.C. board error 3. IPDU P.C. board error 4. External noise
Check code
Check code name
[F01] / [0F]
Indoor TCJ sensor error
Cause of operation TCJ sensor Open/Short
(TCC-L / AI-NET)
Is TCJ sensor connector (CN102: Red) on indoor P.C. board normally connected?
NO
Correct connection.
YES
Sub-code: 01: IPDU1 error 03: IPDU1, 2 error 05: IPDU1, fan IPDU error 07: All IPDU error or communication line error
02: IPDU2 error 04: Fan IPDU error 06: IPDU2, fan IPDU error between IPDU-I/F P.C. boards, or outdoor I/F P.C. board error
NO
Are characteristics of TCJ sensor resistance value normal? ∗ YES
∗ If the fan IPDU is abnormal, be sure to check the voltage output on the fan power P.C. board.
Replace TCJ sensor.
* Indoor unit temperature sensor characteristics See Characteristics-2.
®
Check indoor main P.C. board. Defect Replace Is jumper lead setup on the outdoor I/F P.C. board correct? (Jumper 7, 8, 9 ON)
NO
Connect the jumper lead.
YES Are communication connectors between I/F fan power P.C. board, and IPDU connected?
YES Correct connection.
Check code
Check code name
[F02] / [0d]
Indoor TC2 sensor error
Cause of operation TC2 sensor Open/Short
(TCC-L / AI-NET)
NO
143
Is there disconnection on communication line between IPDU and I/F P.C. board?
YES Connect the communication line.
Is TC2 sensor connector (CN101: Black) on indoor P.C. board normally connected?
NO Correct connection.
YES
NO Is there voltage between pin 4 and pin 5 of CN600 on I/F P.C. board? (Measure with tester: DC0 to 5 V)
NO
I/F P.C. board error
NO
Are characteristics of TC2 sensor resistance value normal? * YES
* Indoor unit temperature sensor characteristics See Characteristics-2.
YES Is there voltage deflection between pin 3 and pin 5 of CN600 on I/F P.C. board? (Measure with tester: DC 0 to 5V, 5 pin GND)
NO
IPDU P.C. board error
Replace TC2 sensor.
Check indoor main P.C. board. Defect ® Replace
YES
® ®
On the fan power supply P.C. board, 1) CN503: Between pins 1 and 5 12V 2) CN503: Between pins 2 and 5 7V 3) Between +5V and GND of CN505: 5V
NO
Replace fan power P.C. board.
Check code
Check code name
[F03] / [93]
Indoor TC1 sensor error
Cause of operation TC1 sensor Open/Short
(TCC-L / AI-NET)
YES Replace P.C. board according to auxiliary code.
Auxiliary code
P.C. board to be replaced
01
IPDU1
02
IPDU2
03
IPDU1, 2
04
Fan IPDU
05
IPDU1, fan IPDU
06
IPDU2, fan IPDU
07
IPDU1, 2, fan IPDU, I/F
Is TC1 sensor connector (CN100: Brown) on indoor P.C. board normally connected?
NO
Correct connection.
YES
Are characteristics of TC1 sensor resistance value normal? * YES Check indoor main P.C. board. Defect ® Replace
NO
Replace TC1 sensor.
* Indoor unit temperature sensor characteristics See Characteristics-2.
Check code
Check code name
[F04] / [19]
TD1 sensor error
Cause of operation TD1 sensor Open/Short
(TCC-L / AI-NET)
Check code
Check code name
[F10] / [0C]
Indoor TA sensor error
Cause of operation TA sensor Open/Short
(TCC-L / AI-NET)
This check code means detection of Open/Short of TD1 sensor. Check disconnection of connector (TD1 sensor: CN502, White) and characteristics of sensor resistance value. (Refer to Outdoor unit temperature sensor characteristics.) If sensor is normal, replace outdoor I/F P.C. board.
Check code
Check code name
[F05] / [A1]
TD2 sensor error
Cause of operation TD2 sensor Open/Short
(TCC-L / AI-NET)
This check code means detection of Open/Short of TA sensor. Check disconnection of connector (TA sensor: CN104, Yellow) and characteristics of sensor resistance value. (Refer to Outdoor unit temperature sensor characteristics.) If sensor is normal, replace indoor P.C. board.
Check code
Check code name
[F12] / [A2]
TS sensor error
Cause of operation TS1, TS2 sensor Open/Short
(TCC-L / AI-NET)
This check code means detection of Open/Short of TD2 sensor. Check disconnection of connector (TD2 sensor: CN503, Pink) and characteristics of sensor resistance value. (Refer to Outdoor unit temperature sensor characteristics.) If sensor is normal, replace outdoor I/F P.C. board.
Check code
Check code name
[F06] / [18]
TE1 sensor error
144 [F07] / [18]
TL sensor error
Cause of operation TL sensor Open/Short
(TCC-L / AI-NET)
This check code means detection of Open/Short of TL sensor. Check disconnection of connector (TL sensor: CN521, White) and characteristics of sensor resistance value. (Refer to Outdoor unit temperature sensor characteristics.) If sensor is normal, replace outdoor I/F P.C. board.
Check code
Check code name
[F08] / [1b]
TO sensor error
This check code means detection of Open/Short of TS sensor. Check disconnection of connector (TS1 sensor: CN504, White TS2 sensor: CN522, Black) and characteristics of sensor resistance value. (Refer to Outdoor unit temperature sensor characteristics.) If sensor is normal, replace outdoor I/F P.C. board.
TE1 sensor Open/Short
This check code means detection of Open/Short of TE1 sensor. Check disconnection of connector (TE1 sensor: CN505, Green) and characteristics of sensor resistance value. (Refer to Outdoor unit temperature sensor characteristics.) If sensor is normal, replace outdoor I/F P.C. board.
Check code name
02 : TS2 sensor
Cause of operation
(TCC-L / AI-NET)
Check code
Sub-code: 01: TS1 sensor
Cause of operation TO sensor Open/Short
(TCC-L / AI-NET)
This check code means detection of Open/Short of TO sensor. Check disconnection of connector (TO sensor: CN507, Yellow) and characteristics of sensor resistance value. (Refer to Outdoor unit temperature sensor characteristics.) If sensor is normal, replace outdoor I/F P.C. board.
Check code
Check code name
[F13] / [43]
TH sensor error
Cause of operation IGBT built-in sensor error in A3-IPDU
(TCC-L / AI-NET)
Sub-code: 01: Compressor 1 side 02: Compressor 2 side
This check code means IGBT built-in temperature sensor error. Check connection of connectors CN06 on IPDU P.C. board and CN600 on I/F P.C. board. If sensor is normal, replace IPDU P.C. board.
Check code
Check code name
[F15] / [18]
Outdoor temp sensor miscabling (TE1, TL)
(TCC-L / AI-NET)
Cause of operation 1. Misinstallation and misconnection of TE1 sensor and TL sensor 2. Resistance characteristics error of TE1 sensor and TL sensor 3. Outdoor P.C. board (I/F) error
NO
Are installed positions of TE1 sensor and TL sensor correct?
Outdoor I/F P.C. board TE1 sensor : CN505, Green TL sensor : CN521, White
YES Are connection of TE1 sensor connector and TL sensor connector normal?
NO
Check code
Check code name
[F23] / [43]
Ps sensor error
(TCC-L / AI-NET)
Is connection of Ps sensor connector correct? YES
Correct installed positions of TE1 sensor and TL sensor.
Are output voltage characteristics of Ps sensor normal? YES Correct connection.
YES Are resistance characteristics of TL sensor and TE1 sensor normal?
NO
YES
Correct connection.
Is there no leakage from SV4 valve?
* Outdoor unit temperature sensor characteristics See TE1 sensor : Characteristics-5. See TL sensor : Characteristics-3.
NO
Correct connection.
Connector: CN500, White NO
Sensor error
* 1 Pressure (Check joint) by pressure gauge 2 Pressure display on 7-segment display 3 Output voltage of I/F P.C. board If 1 and 2, 3 are different, an error of pressure sensor itself is considered. If 2 and 3 are different, check interface P.C. board.
NO
Is not refrigerant by passed from discharge to suction of 4-way valve?
YES
NO Check compressor.
YES Check 4-way valve.
Replace SV4 valve.
Check outdoor I/F P.C. board. Defect ® Replace
Cause of operation Output voltage error of Ps sensor
* TE1 sensor : Outdoor heat exchanger temp sensor TL sensor : Temp sensor between liquid tanks of outdoor P.M.V. 1/2
145
Check code
Check code name
[F24] / [43]
Pd sensor error
Cause of operation Output voltage error of Pd sensor
(TCC-L / AI-NET) Check code
Check code name
[F16] / [43]
Outdoor pressure sensor miscabling (Pd, Ps)
(TCC-L / AI-NET)
Are connection of Pd sensor and Ps sensor connectors correct?
NO
Cause of operation 1. High-pressure Pd sensor and lowpressure sensor Ps are exchanged. 2. Output voltage of each sensor is zero.
Correct connection of connectors. Pd sensor: CN501, Red Ps sensor: CN500, White
YES Are output voltage characteristics of Pd sensor and Ps sensor normal? YES
Are Pd/Ps output values Pd > Ps during compressor operation? YES
NO
Sensor error
Replace
1 Pressure (Check joint) by pressure gauge 2 Pressure display on 7-segment display 3 Output voltage of I/F P.C. board If 1 and 2, 3 are different, an error of pressure sensor itself is considered. If 2 and 3 are different, check interface P.C. board. NO
Check compressor.
* Value can be confirmed by 7-segment display function on outdoor I/F P.C. board.
It is output voltage error of Pd sensor. Check disconnection of connection of connector (Pd sensor: CN501) circuit and output voltage of sensor. If the sensor is normal, replace outdoor I/F P.C. board.
Check code
Check code name
[F29] / [12]
Indoor other error
(TCC-L / AI-NET)
Indoor P.C. board error EEROM error
This error is detected during operation of air conditioner of IC10 non-volatile memory (EEPROM) on indoor unit P.C. board. Replace service P.C. board. ∗ If EEPROM was not inserted when power was turned on or it is absolutely impossible to read/write EEPROM data, the automatic address mode is repeated. In this case, [97 error] is displayed on AI-NET central controller. (Approx. 3 minutes) (Power ON)
(Approx. 1 minute)
[SET DATA] is displayed on main remote controller.
[SET DATA] disappears.
Pd SW01/02/03=1/1/2 Ps SW01/02/03=1/2/2 (Repetition)
Check outdoor I/F P.C. board. Replace Defect
Cause of operation
LED (D02) 1Hz flashes for approx. 10 seconds on indoor unit P.C. board.
Reboot (Reset)
Check code
Check code name
[F31] / [1C]
Outdoor EEPROM error
(TCC-L / AI-NET)
Is there any trouble of outdoor unit power supply?
Cause of operation 1. Outdoor unit power error (Voltage, noise, etc.) 2. Outdoor I/F P.C. board error
Check code
Check code name
[H02] / [1d]
Compressor error (Lock)
Cause of operation 1. 2. 3. 4. 5.
(TCC-L / AI-NET)
Check power voltage and line. Correct power line. Check external noise, etc.
YES
NO
Outdoor unit power line error Compressor circuit system error Compressor error Refrigerant stagnation in compressor shell IPDU P.C. board error
Sub-code: 01: Compressor 1 side 02: Compressor 2 side
Check I/F P.C. board. NO
Is power voltage of outdoor unit normal? 1
1 380 – 415V ± 10%
YES
Check code
Check code name
[H01] / [1F]
Compressor breakdown
(TCC-L / AI-NET)
Cause of operation 1. 2. 3. 4. 5.
Does voltage drop occur when other compressor starts?
Outdoor unit power line error Compressor circuit system error Compressor error Cause of abnormal overload operation IPDU P.C. board error
YES
Correct power line.
NO YES Does OCR of MG-SW operate?
Reset OCR manually. 3
NO Is wiring or connector connection on IPDU P.C. board normal?
Sub-code: 01: Compressor 1 side 02: Compressor 2 side
NO
Correct connector connection or wiring.
YES Is power voltage of outdoor unit normal?
YES
NO
Is not it an abnormal overload?
146
380 – 415V ± 10%
NO
YES Does voltage drop occur when other compressor starts?
Correct cause of overload.
Is there no refrigerant stagnation in compressor shell?
YES Correct power line.
YES
Is case heater output normal?
Operation starts. Is connection of wiring or connection of connector on IPDU P.C. board normal?
Check case heater.
NO Correct connector connection or wiring.
NO
Is compressor normal? 2
YES
YES Is winding resistance between phases of corresponding compressor normal? (Note 1)
NO
Compressor error (Motor burning, etc.)
YES Is not it an abnormal overload? Take off lead cable of compressor. 1. Check resistance between windings: It is normal if there are 0.7 to 0.9 . 2. Check insulation between outdoor cabinet and terminal: It is normal if there are 10M or more.
Compressor error
2 Check the following items mainly. 1. Existence of abnormal sound and abnormal vibration during operation or starting 2. Abnormal overheat of case during operation or stop time (Never touch with hands.) 3. Current of compressor lead during operation or starting time (No varied change of current) change 3 If OCR operates even after manual reset of OCR, check whether the wiring to the current sensor (T02) of Comp-IPDU is correct or not.
Check IPDU P.C. board.
YES
NO
Correct refrigerant stagnation in compressor shell.
NO
NO
NO
YES
Correct cause of overload.
S
C
Check code
Check code name
Cause of operation
[H03] / [17]
Current detective circuit system error
1. Cabling or connector connection error on IPDU P.C. board 2. IPDU P.C. board error
(TCC-L / AI-NET)
Sub-code: 01: Compressor 1 side 02: Compressor 2 side Check IPDU P.C. board.
Note 1 * After checking the output, when connecting the compressor lead again to the compressor terminal, check surely there is no distortion on the Fasten receptacle terminal. If it is loosened, caulk it with pinchers, etc and then connect lead to the terminal firmly.
R
Wiring or connector connection on IPDU P.C. board normal?
NO
Correct connector connection or cabling.
YES
Details of compressor power connecting section
Check IPDU P.C. board.
Check code
Check code name
[H04] / [44]
Compressor 1 case thermo operation
(TCC-L / AI-NET)
[H14] / [44]
Compressor 2 case thermo operation
(TCC-L / AI-NET)
Is case thermo circuit normal? 1. Connector connection 2. Wiring 3. I/F P.C. board (Note 1) YES Are service valves of gas pipe and liquid pipe of outdoor unit fully opened?
Cause of operation 1. 2. 3. 4. 5. 6. 7. 8.
Case thermo circuit error I/F P.C. board error Service valve closed Outdoor PMV clogging SV4 valve leak, Coil misinstallation 4-way valve error Compressor error Refrigerant shortage
NO
Repair case thermo circuit.
(Note 1) 1. Case thermo is usually closed. 2. Operation temperature of case thermo is 120˚C. NO
Check code
Check code name
[H06] / [20]
Low-pressure protective operation
(TCC-L / AI-NET)
5. 6. 7. 8.
Open service valves fully.
YES NO
Are characteristics of low-pressure sensor normal? YES
Open service valves fully.
NO
YES
Is there mispiping of discharge gas and suction gas main pipes?
Connector CN300, 301, White
Correct SV2 and SV4 circuits.
Check wiring, installation and connection.
YES
Repair outdoor PMV.
Exchange low-pressure sensor.
* 1 Pressure by pressure gauge (Check joint) 2 Pressure display on 7-segment display 3 Output voltage of I/F P.C. board If 1 and 2, 3 are different, an error of pressure sensor error is considered. If 2 and 3 are different, check I/F P.C. board.
Are SV2 and SV4 circuits normal?
NO
Service valve close Ps sensor error SV2, SV4 circuit error Miscabling of communication between indoor and outdoor Indoor/outdoor fan and condenser error Indoor/outdoor PMV clogging Indoor/outdoor heat exchanger clogging Refrigerant shortage
NO
Are service valves of gas and liquid pipe of outdoor unit fully opened?
YES Are outdoor PMV1/2/3 normal? 1. Connector connection 2. Wiring 3. Coil 4. Valve body 5. I/F P.C. board
Cause of operation 1. 2. 3. 4.
Correct piping.
NO Is indoor unit connected to different refrigerant systems?
YES
YES
147
Start operation.
Correct cabling.
(Check with miswiring check function of outdoor unit.)
NO NO
Is flow selector normal?
Check flow selector.
YES In cooling season, go to (A), In heating season, go to (B)
Are SV41 and SV42 Valve circuits normal? 1. Incorrect installation and connection of SV41 and SV42 2. Leakage from SV41, 42 circuit
NO SV4 valve: Connector CN311, Blue
(A) Cooling
Correct SV4, SV5, SV11 valve circuits. Does indoor fan operate normally in cooling season?
YES
NO
YES YES
Does not refrigerant bypass from discharge to suction through 4-way valve?
YES
Cleaning
Check 4-way valve.
NO
YES
NO
YES
Check piping.
Repair faulty parts.
Is connection or coil normal?
Check indoor P.C. board. Failure ® Replace NO Repair faulty parts.
YES YES
Refrigerant shortage or, clogging or pipe deformed
Replace PMV body.
Is there clogging of the valve? NO
NO NO Is compressor normal? (Note 2) YES
NO
YES
Is there clogging of indoor air filter or heat exchanger?
Is indoor PMV normal?
NO Is not refrigerant bypassed from discharge to suction?
Are following items normal? 1. Connection 2. Condenser 3. Motor 4. Fan
(B) Heating
Compressor error Is outdoor fan operating normally in heating season?
(Note 2) Check the following items mainly. 1. Existence of abnormal sound and abnormal vibration during operation or when starting 2. Abnormal overheat of case during operation or stop (Do not touch.) 3. Current of compressor during operation or starting (No rapid current change) YES
Is flow selector unit normal?
YES YES Cleaning
Check flow selector unit.
NO
Is indoor fan system normal? • Fan cracked • Fan loose
NO
Check outdoor I/F P.C. board. Failure ® Replace
YES
Is there clogging of outdoor heat exchanger?
Repair faulty parts.
NO
NO Refrigerant shortage, clogging, pipe breakage
Is outdoor PMV normal?
(After checking there is no slogging or pipe breakage, charge refrigerant again.)
YES
NO Refrigerant shortage, clogging, pipe deformed
Check code
Check code name
[H07] / [d7]
Low oil level protection
(TCC-L / AI-NET)
Are TK1, TK2, TK3, and TK4 sensors connected correctly? Is sensor fitted correctly or mis-installed.
Cause of operation 1. 2. 3. 4. 5. 6. 7. 8.
Valves of balance pipes closed. Miscabling or misinstallation of TK1 to TK4 sensors TK1 to TK4 sensor error Gas leak or oil leak of all outdoor units Refrigerant stagnation of compressor case SV3A, 3B, 3D, 3C, 3E valve error Clogging of oil return circuit from oil separator Clogging of oil-equation circuit system
NO
Correct miswiring. CN514, TK2: CN515 ( TK1: TK3: CN516, TK4: CN523 )
YES Are TK1 and TK2 sensors connected correctly? Is sensor fitted correctly or mis-installed. Are sensor characteristics normal?
NO
Correct miswiring. (TS1: CN504, TS2: CN522) Sensor error ® Replace
* Characteristics-2
YES Abnormal Check leakage of SV6 circuit.
Replace defective parts.
Normal
(*1) a) Leakage check for SV3A valve (for multiple outdoor unit system) • Turn off the power supply, take off connector of SV3A valve, and then start a test operation after power-ON. • Check the temperature change at secondary side of SV3A valve during operation (1 in the figure on the next page). • If temperature is increased, it is a leakage of SV3A valve. Replace SV3A valve.
b) Leakage check for SV3C valve • Turn off the power supply, take off connector of SV3C valve, and then start a test operation after power-ON. • After operation for several minutes, check temperature at secondary side of SV3C valve (2 in the figure on the next page). • If temperature is high (equivalent to discharge temperature TD), it is a leakage of SV3C valve. Replace SV3C valve. (Even if there is leakage from SV3C valve does not occur, temperature of SV3C valve at secondary side rises during operation. When the checked temperature is equivalent to TD temperature, it is a leakage of SV3C valve. Replace SV3C valve.)
c) Clogging check for SV3B valve (for multiple outdoor unit system) Abnormal
Check setup of cooling only indoor units is correct.
Set up cooling only operation mode. Item code (DN) OF Cooling only operation mode: 0001
Normal NO Are characteristics of TK1 to TK4 normal?
148
YES
Sensor error ® Replace
* Characteristics-4
Abnormal
Determine position where gas leaked and repair. (Recharge, refill oil.)
Check gas leak of outdoor unit. (Check oil leak at the outdoor unit.) Normal NO
Repair the flow selector unit.
Is the flow selector unit normal? YES Check accumulation of refrigerant in compressor case.
In some cases, it may be difficult to check for leakage or clogging of refrigerant in low ambient temperature condition. In this case, it may take longer for the system to warm up before commencing checks. (Criteria: Discharge temperature of TD1 and TD2 are 60°C or higher)
NO
(*1) Check leakage of solenoid valve. (SV3C) Check clogging. (SV3E)
YES Replace defective parts
• While outdoor unit is operating, set up SW01/02/03 = [2] [1] [3] to 7-segment display [Hr], and push SW04 for 2 seconds or more, [Hr] [2] is displayed. • Set up SW02 = [9], and turn on SV3A, SV3B, SV3C valves (7-segment display [Hr] [ 3-]). • While outdoor unit is operating, check temperature change at secondary side of SV3B valve (3 in the figure on the next page). • If temperature does not rise (equivalent to suction temperature), it is a clogging of SV3B valve. Replace SV3B valve.
d) Clogging check for SV3E valve • While the outdoor unit is operating, set up SW01/02/03 = [2] [1] [3] the 7-segment display A displays [Hr], and push SW04 for 2 seconds or more, [Hr] [ 2] is displayed. • Set up SW02 = [10], and turn on SV3E valve (7-segment displays [Hr] [ ]). • After operating for several minutes, check the pipe temperature at the secondary side of the SV3E valve. If it is the equivalent to the outside temperature, SV3E valve may be clogged. Replace SV3E valve. • Note: If SV3E valve is clogged, the temperature of all TK1 to TK4 sensors do not change.
Refrigerant accumulation No leakage or clogging Correct accumulation of refrigerant in compressor case, reset power supply and start operation.
(*2) Check clogging in oil recovery circuit of the oil separator. (Capillary, Strainer) Check clogging of SV3D valve.
Check oil level judgment of each compressor.
(*2) Clogging check for SV3D valve of oil return circuit from oil separator a) Oil return circuit YES Replace defective parts
No clogging SW01/02/03=1/16/1 are displayed on 7-segment display.
b) Clogging check for SV3D valve
Are all the oil levels appropriate? NO YES Eliminate cause of stagnation.
Check clogging of oil-equalization circuit. (*3)
• While outdoor unit is operating, check temperature (secondary side of capillary) on oil return circuit (5 in the figure on the next page). If temperature is equivalent to suction temperature, a clogging of strainer of oil return circuit or capillary is considered. Repair the clogged part.
Clogging
Indoor/outdoor PMV error (Cause of refrigerant stagnation) Discharge check valve error, etc.
(Note) When refrigerant stagnates in compressor shell, there may appear to be a low oil level.
Replace defective parts
• While outdoor unit is operating, set up SW01/02/03 = [2] [1] [3] to 7-segment display [Hr], and push SW04 for 2 seconds or more, [Hr] [2] is displayed. • Set up SW02 = [7], and turn on SV3D valve (7-segment display [Hr] [ 3d]). • If temperature is low at secondary side of the valve or it does not change, clogging of valve, capillary, or strainer is considered ( 6 in the figure on the next page).
(*3) Check for solenoid valve of outdoor unit (for multiple outdoor unit system) a) Clogging check for SV3A valve • While outdoor unit is operating, set up SW01/02/03 = [2] [1] [3] to 7-segment display [Hr], and push SW04 for 2 seconds or more, [Hr] [2] is displayed. • Set up SW02 = [4], and turn on SV3A valve (7-segment display [Hr] [ 3A]). • If temperature is low at secondary side of the valve or it does not change, clogging of valve or check valve is considered (1 in the figure).
b) Clogging check for SV3C valve • While outdoor unit is operating, set up SW01/02/03 = [2] [1] [3] to 7-segment display [Hr], and push SW04 for 2 seconds or more, [Hr] [2] is displayed. • Set up SW02 = [6], and turn on SV3C valve (7-segment display [Hr] [ 3C]). • If temperature does not increase, clogging of valve or strainer is considered (2 in the figure).
Check code
Check code name
[H08] / [d4]
Oil level detective temperature sensor error
(TCC-L / AI-NET)
Cause of operation TK1 to TK4 sensor Open/Short
Sub-code: 01: TK1 sensor error 02: TK2 sensor error 03: TK3 sensor error 04: TK4 sensor error This error is an oil level temperature sensor error. Check for disconnection of the wiring and resistance value of the sensor. If the sensors are normal, replace the outdoor I/F P.C. board.
Circuit
Connector
TK1
CN514 (Black)
TK2
CN515 (Green)
TK3
CN516 (Red)
TK4
CN523 (Yellow)
(*4) a) Clogging check for oil-equalization circuit • Operate the outdoor unit (drive both compressors in the unit). • After operating for 10 minutes, check temperature of TK1 and TK2 sensors and temperature of oil equalization circuit capillary (7 in the figure) have increased.
Check code
Check code name
[H16] / [d7]
TK1 temperature detective circuit error (Sub-code: 01)
(TCC-L / AI-NET)
(Criteria)
Cause of operation
TK1, TK2=Td1, Td2 temperature - Approx. 10 to 30°C Oil-equalization capillary tubes should be significantly higher than outside air temperature and suction temperature. • If temperature is low, a malfunction of capillary, strainer, or check valve is to be considered. Repair the defective parts.
149
High-pressure sensor
5
Has TK1 sensor become detached?
1. Connection of TK1 sensor. Error in resistance value of TK1 sensor 2. Oil-equalization circuit error (Check valve, capillary clogging, strainer clogging) 3. Refrigerant stagnation in case of compressor shell
YES
Correct installation of sensor.
Check joint
NO
(SV2) Oil separator
Is there incorrect wiring or installation on TK1/TK2/TK3/TK4 sensors?
(
* Characteristics-4
NO
(SV3D) Solenoid valve (SV42)
Solenoid valve (SV41)
High-pressure SW
High-pressure SW
Sensor (TD2)
(TD1)
Compressor 1 (Inverter)
Are characteristics of TK1 sensor resistance value normal?
Sensor (TK3) Strainer
Strainer
(TK1)
NO
Sensor error
* Outdoor unit temp sensor characteristics-4 Error Replace clogged part.
Start a test operation in COOL or HEAT mode.
2
TK1 sensor temp is displayed on 7-segment display with SW01/02/03=[1] [11] [2]. Check TK1 sensor temp. approx. 10 minutes after compressor 1 has operated. If low temperature continues (approximately outside ambient temp.) or temperature does not change, a clogging of strainer of oil-equalization circuit, clogging of capillary tube, or malfunction of check valve is to be considered.
Compressor 1
Strainer
No error
(TK2) Oil tank
(SV3E)
)
YES
Compressor 2 (Inverter)
6
Correct wiring/installation. TK1: CN514 TK2: CN515 TK3: CN516 TK4: CN523
YES
Capillary tube
(TK4)
7
TK1
4 7 1
Solenoid valve (SV3B)
Strainer Balance pipe Packed valve
Check the clogging of SV3E valve. (Note 1)
(SV3A)
3
Check valve
Oil tank
Error (Note 1) Refer to item [H07] error.
No error Check I/F P.C. board
Replace SV3E valve.
Check code
Check code name
Cause of operation
Check code
Check code name
Cause of operation
[H16] / [d7]
TK2 detective circuit system error (Sub-code: 02)
1. Connection of TK2 sensor. 2. Error in resistance value of TK2 sensor (see 9-7 Sensor characteristics). 3. Oil-equalization circuit error (check valve, capillary clogging, strainer clogging). 4. Refrigerant stagnation in case of compressor shell.
[H16] / [d7]
TK3 temperature detective circuit error (Sub-code: 03)
1. Connection of TK3 sensor. 2. Error in resistance value of TK3 sensor (see 9-7 Sensor characteristics). 3. Error of SV3C valve circuit periphery (check capillary clogging, strainer clogging). 4. Refrigerant stagnation in case of compressor shell.
(TCC-L / AI-NET)
Has TK2 sensor become detached?
YES
Correct installation of sensor.
(TCC-L / AI-NET)
Has TK3 sensor become detached?
NO
Is there incorrect wiring or installation on TK1/TK2/TK3/TK4 sensors?
YES
Correct wiring/installation. TK1: CN514 TK2: CN515 TK3: CN516 TK4: CN523
Is there incorrect wiring or installation on TK1/TK2/TK3/TK4 sensors?
Sensor error
Are characteristics of TK3 sensor resistance value normal?
(
NO * Outdoor unit temp sensor characteristics-4
)
YES
Does OCR of MG-SW operate?
Correct installation of sensor.
NO
NO
Are characteristics of TK2 sensor resistance value normal?
YES
Correct wiring/installation. TK1: CN514 TK2: CN515 TK3: CN516 TK4: CN523
YES
(
NO NO
Sensor error
* Outdoor unit temp sensor characteristics-4
)
® Replace
YES YES
Reset OCR manually.(*2)
After power reset, check capillary choke of SV3C valve bypass. Error Replace clogged part (Capillary).
Start a test operation in COOL or HEAT mode. NO
TK3 sensor temp is displayed on 7-segment display with SW01/02/03=[1] [13] [2].
150
After power reset Error Replace clogging part.
Start a test operation in COOL or HEAT mode. TK2 sensor temp is displayed on 7-segment display with SW01/02/03=[1] [12] [2].
Check TK3 sensor temp. approx. 10 minutes after compressor 2 has operated. If low temperature continues (approximately outside ambient temp.) or temperature does not change, a clogging of parallel capillary is considered.
Strainer
No error
Check TK2 sensor temp approx. 10 minutes after compressor 2 has operated. If low temperature continues (approximately outside temp) or temperature does not change, a clogging of strainer of oil-equalization circuit, clogging of capillary or malfunction of check valve is considered.
SV3E valve Compressor 2
TK3
No error Strainer
Check the clogging of SV3E valve. (Note 1)
Capillary tube TK2 Check the clogging of SV3E valve. (*1)
Error
Oil tank
*1 Refer to item [H07] error.
No error
Check I/F P.C. board
Replace SV3E valve. *2 If OCR operates even after manual reset of OCR, check whether the wiring to the current sensor (T02) of Comp-IPDU is correct or not.
No error
Check I/F P.C. board
Error (Note 1) Refer to item [H07] error.
Replace SV3E valve.
Check code
Check code name
Cause of operation
Check code
Check code name
Cause of operation
[H16] / [d7]
TK4 temperature detective circuit error (Sub-code: 04)
1. Connection of TK4 sensor. 2. Error in resistance value of TK4 sensor (see 9-7 Sensor characteristics). 3. Check clogging and malfunction of SV3E valve circuit. 4. Oil-equalization circuit error (check capillary clogging, strainer clogging). 5. Refrigerant stagnation in case of compressor shell.
[L04] / [96]
Duplicated setup of outdoor line address
Outdoor line addresses are duplicated.
(TCC-L / AI-NET)
(TCC-L / AI-NET)
YES Are there duplicate line address setups?
Are communication wire connections of [U1.U2], [U3.U4], and [U5, U6] normal? Has TK4 sensor become detached?
YES
Correct the line address setup.
NO
Correct installation of sensor.
NO
Correct the wire connection.
YES
NO
Is there incorrect wiring or installation on TK1/TK2/TK3/TK4 sensors?
Correct wiring/installation. TK1: CN514 TK2: CN515 TK3: CN516 TK4: CN523
YES
(
NO
Are characteristics of TK4 sensor resistance value normal?
NO
)
Repeat the address setup. (Refer to “Address setup”.)
Sensor error ® Replace
YES
Does OCR of MG-SW operate?
®
Check outdoor I/F P.C. board. Failure Replace
YES
Reset OCR manually.(*2)
Check code
Check code name
Cause of operation
[L05] / [96]
Duplicated indoor units with priority (Displayed on indoor unit with priority)
1. Two or more prior indoor units exist.
(TCC-L / AI-NET)
NO
151
Check the clogging of SV3E valve. (*1) Error
No error
Check I/F P.C. board
This check code is displayed on the set indoor unit when setup of indoor unit with priority is duplicated. • Priority setup with two or more units is not available. Choose one prior unit in one refrigerant circuit system.
*1 Refer to item [H07] error. *2 If OCR operates even after manual reset of OCR, check whether the wiring to the current sensor (T02) of Comp-IPDU is correct or not.
Replace SV3E valve.
Check code name
Check code
Cause of operation
Check the clogging of SV3E valve.
[L06] / [96] (TCC-L / AI-NET)
Check code
Check code name
Cause of operation
[L03] / [96]
Duplicated indoor header units
There were two or more indoor header units within the same remote controller group.
(TCC-L / AI-NET)
1) Check the connection of the remote controller after the connection has been changed. 2) If the group configuration and address are normal when power has been turned on, the mode automatically shifts to address setup mode. (Re-setup of address) → Refer to “Address setup”.
Duplicated indoor units with priority Two or more indoor units with priority (Displayed on the indoor unit other than are duplicated. one with priority and on the outdoor unit)
Sub-code: No. of indoor units with priority
When indoor unit with priority is duplicated, this fault code is displayed on the unit other than the setup indoor unit and outdoor unit. • As only one indoor unit with priority is valid, change the setup.
Check code
Check code name
[L07] / [99]
Group line in individual indoor unit
(TCC-L / AI-NET)
Is there group wiring?
YES
Cause of operation The group line is connected in the individual indoor unit.
Item code (D1) 12: Line address Item code (D2) 13: Indoor address Item code (D3) 14: Group address
Check setup item code DN 12, 13, and 14 addresses.
NO
Check code
Check code name
[L10] / [88]
Outdoor capacity unset
(TCC-L / AI-NET)
Cause of operation The model selection jumper of the outdoor I/F P.C. board does not match the model.
Service I/F P.C. board for the outdoor unit is common to all outdoor units. The service I/F P.C. board will need to be set up for the correct model based upon the faulty I/F P.C. board, which it is replacing. Set up the model based upon the I/F P.C. board assembly change procedure.
YES Is there an individual indoor unit.
Correct indoor group address.
NO
®
Check indoor P.C. board. Failure Replace
Check code
Check code name
[L17] / [46]
Inconsistent models of outdoor units
(TCC-L / AI-NET) Check code
Check code name
[L08] / [99]*
Indoor group / address unset
Cause of operation
Cause of operation There are outdoor units on the communication line other than Super Module Multi Flex type such as Super Module Multi or Super Module Multi ice regenerative type
Indoor address unset
(TCC-L / AI-NET)
Is the power on all the indoor units turned on?
Are the connected outdoor units those for flex on 1 system? (Check model name.)
NO
NO
Replace outdoor units of other models with specified models
Turn on the power of indoor units.
YES
YES
152
Is the check code [L17] displayed even if turning power on again of all the connected outdoor units on 1 system alone?
Disconnect connectors between [U1, U2] and [U3, U4]. Turn on the power of outdoor unit again.
NO
Correct communication line between outdoor units.
YES
Clear addresses. (Refer to “Address clear”.)
Are all the connected outdoor I/F P.C. board's on 1 system P.C. board's of outdoor units for Super Module Multi Flex?
Re-execute address setup. (Refer to “Address setup”.)
Change the incorrectly built-in outdoor I/F P.C. board's with I/F P.C. board's for Super Module Multi Flex.
YES
Note) This code is displayed when the power is turned on at the first time after installation. (Because the address is not yet set up)
Check code
Check code name
[L09] / [46]
Indoor capacity unset
Cause of operation Indoor capacity unset
(TCC-L / AI-NET)
Are capacity setups of indoor units unset?
NO
YES
Set up capacity data of indoor unit. (Setup item code (DN) = 11)
NO Check indoor P.C. board. Replace Defect
Check again whether there is any other outdoor unit or not on the communication line in 1 system. If any, turn off power of the corresponding outdoor unit and then check once more.
∗ Using 7-segment on I/F P.C. board, check the model name on each outdoor unit. For check, when putting the rotary switch on SW01/02/03=16/16/16, it is an outdoor I/F P.C. board, for Super Module Multi Flex if “F” is displayed at the left side of 7-segment [A] part.
Check code
Check code name
Cause of operation
Check code
Check code name
[L18] / [8A]
Flow selector unit system error
An indoor unit which has been operated in cooling only mode is operated in heating mode without setup for cooling only mode.
[L29] / [CF]
IPDU quantity error
(TCC-L / AI-NET)
NO
Is every indoor unit been set up for cooling only mode?
Set up All cooling mode. Item code (DN)=OF Cooling only operation mode=0001
YES Check flow selector unit.
Cause of operation
(TCC-L / AI-NET)
1. Incorrect model setup in service for I/F P.C. board 2. Communication error between IPDU, fan IPDU and I/F 3. IPDU, fan IPDU, I/F P.C. board error
Sub-code: 01: IPDU1 error 02: IPDU2 error 03: IPDU1, 2 error 04: Fan IPDU error 05: IPDU1, fan IPDU error 06: IPDU2, fan IPDU error 07: All IPDU error or disconnection of communication line between IPDU-I/F P.C. board or outdoor I/F P.C. board error
Is jumper setup of outdoor I/F P.C. board correct? (Jumpers 7, 8, 9 ON)
NO
Correct connection.
YES
Check code
Check code name
[L20] / [98]
Duplicated central control addresses
(TCC-L / AI-NET)
Cause of operation Central control addresses are duplicated.
YES
Is communication connector between IPDU and I/F P.C. board connected?
Correct connection.
NO
Are two or more central control system with identical network addresses connected?
YES
Correct the network address of the central control system.
YES
Is the communication line between IPDU and I/F P.C. board disconnected?
Reconnect communication line.
NO
NO
153
Check the network adaptor on the indoor P.C. board.
Is there voltage fluctuation between pin 4 and pin 5 of CN600 on I/F P.C. board (measure by tester: DC 0 to 5 V).
NO
I/F P.C. board error
YES
Check code
Check code name
[L28] / [46]
Quantity over of connected outdoor units
(TCC-L / AI-NET)
Is No. of connected outdoor units below 3 units?
Cause of operation 1. Quantity over of connected outdoor units 2. Connection error of communication line between outdoor units 3. Outdoor I/F P.C. board error
NO Max. 3 units are allowed for flex system.
YES Check outdoor I/F P.C. board.
YES
NO
IPDU P.C. board error
Both IPDU (No.1, No.2) and fan IPDU did not return the communication.
® ®
On the fan power supply P.C. board, 1) CN503: Between 1 and 5 pins 12V 2) CN503: Between 2 and 5 pins 7V 3) Between +5V and GND at the side of CN505: 5V
NO
Replace fan power supply on P.C. board.
YES
YES
Is the communication line between outdoor units correct?
Is there voltage fluctuation between pin 3 and pin 5 of CN600 on I/F P.C. board (measure by tester: DC 0 to 5 V).
Replace IPDU P.C. board with trouble.
NO Correct connection of the communication line.
Auxiliary code
P.C. board to be replaced
01
IPDU1
02
IPDU2
03
IPDU1, 2
04
Fan IPDU
05
IPDU1, fan IPDU
06
IPDU2, fan IPDU
07
IPDU1, 2, fan IPDU, I/F
Check code
Check code name
[L30] / [b6]
Interlock in indoor unit from outside
(TCC-L / AI-NET)
Is outside device connected to connector CN80?
Cause of operation Outside error was input.
Check code
Check code name
[P03] / [1E]
Discharge temp TD1 error
(TCC-L / AI-NET)
NO
Check indoor P.C. board. Replace Failure
NO
Check outside device. Failure Replace
YES
Does outside device correctly operate?
Cause of operation 1. Service valve of outdoor unit closed. 2. Outdoor PMV1, 2 error 3. TD sensor error 4. Refrigerant short, clogging in pipe 5. 4-way valve error 6. SV4 circuit leakage, misinstallation 7. SV5 circuit leakage 8. SV6 circuit clogging 9. Discharge gas/Suction gas pipes mispiping 10. Flow selector unit error
YES Are service valves of outdoor discharge gas, suction gas, and liquid pipe fully opened?
Check cause of the operation.
NO Open service valves fully.
YES
Check code
Check code name
[L31] / [–]
Extended IC error
(TCC-L / AI-NET)
YES
154
Are there any faults with the outdoor unit power supply?
Cause of operation 1. Outdoor unit power error 2. Outdoor I/F P.C. board error
Are outdoor PMV1 and PMV2 normal? 1. Connector connection 2. Wiring 3. Coil 4. Valve itself 5. Outdoor P.C. board
NO Repair outdoor PMV. * Connector CN300, 301 White
YES
Check power voltage and line. Check auxiliaty noise, etc.
NO
Is resistance characteristic of TD1 sensor normal? YES Is there any refrigerant leakage on discharge gas to suction side on the 4-way valve?
Check outdoor I/F P.C. board.
NO * Refer to Outdoor unit temperature sensor characteristics-4.
Replace TD1.
NO Check 4-way valve.
YES SV4 circuit 1. Are not coils of SV41 and SV42 valves mounted reversely? 2. Is no leakage from SV41?
NO
Correct mounting of valve coils or replace SV41 valve.
YES Check code
Check code name
[P01] / [11]
Indoor fan motor error
(TCC-L / AI-NET)
Cause of operation
Abnormal Replace defective parts.
Check leakage of SV5 circuit.
1. Cabling error 2. Check fan motor.
Normal Abnormal
∗ For the models installed with AC fan motor only
Replace defective parts.
Check clogging of SV6 circuit. Normal
Is there a connection error or disconnection of CN076 connector?
YES
Correct cabling circuit for the connector connection.
NO
Check mispiping of discharge gas / suction gas main pipes.
Correct piping.
Normal NO
YES Is not there mechanical lock of fan motor?
Abnormal
Replace fan motor.
Repair flow selector unit.
Is the flow selector unit normal? YES
NO
®
Check indoor P.C. board. Failure Replace
Is not indoor unit in other refrigerant line connected?
NO Correct wiring.
YES Refrigerant short, clogging, pipe breakage
(Check there is no pipe breakage, and then recharge refrigerant.)
Check code
Check code name
[P04] / [21]
Actuation of high-pressure SW
(TCC-L / AI-NET)
Cause of operation
Sub-code: 01: Compressor 1 side 02: Compressor 2 side
NO Is SV4 circuit normal?
All heating operation
Refrigerant overcharge, clogging,pipe breakage, abnormal overload condition
YES
NO Is indoor PMV normal? YES
YES
Check and correct cabling.
YES
®
Check I/F P.C. board. Failure Replace NO
Is connector connection, coil normal?
NO
YES Repair faulty parts.
Are there any obstructions in the operation of the indoor heat exchanger? 1 Air filter clogging 2 Heat exchanger clogging 3 Air short circuit
NO
Are connector connection, heat exchanger, fan, and fan motor normal? YES
Eliminate the interfered causes.
YES
Does heating indoor fan normally operate?
NO
NO
®
Check parts. Failure Replace
Are parts of high-pressure SW normal?
Repair SV4 circuit.
Coil error, clogging, ( disconnection of wiring, etc. )
YES
NO Is circuit cabling normal?
YES
C All heating operation
Note) High-pressure SW is normally closed. (B contact)
NO Does high-pressure SW operate?
A
1. High-pressure SW error 2. Service valve closed 3. Pd sensor error 4. Indoor/outdoor fan error 5. Indoor/outdoor PMV choke 6. Indoor/outdoor heat exchanger clogging, air short circuit 7. SV2 circuit error 8. SV4 circuit error 9. SV5 circuit error 10. Discharge line check valve malfunction 11. Refrigerant overcharge
Repair faulty parts.
NO Is service valve fully opened?
Open service valve fully.
NO Is 4-way valve normal?
YES
155
Check for mispiping of discharge/suction gas main pipes.
Abnormal
Are characteristics of TC2 and TCJ sensor resistance value normal?
YES
Correct piping.
Replace 4-way valve.
Normal
YES
Abnormal
NO
Replace defective parts.
Check operation of PMV3 SV12 valve.
Replace TC2 or TCJ sensor.
Is SV11 circuit normal?
Normal Abnormal
Reset power supply, and start a test operation corresponding to the season.
® To All heating operation ® To All cooling operation
Repair faulty position.
Is there clogging NO of the valve?
B C
NO
Are indoor units of different refrigerant circuit connected?
Replace the high-pressure sensor.
YES
All cooling operation NO YES
Is there no crack or coming-off of fan?
Refrigerant overcharge, clogging, pipe breakage, abnormal overload condition
NO Repair faulty parts. Connector connection, fan IPDU, fan motor, wiring
YES
Are there any obstructions in the operation of the indoor heat exchanger? 1. Air filter clogging 2. Heat exchanger clogging 3. Air short circuit
YES Eliminate the interfered causes.
Check code
Check code name
[P05] / [AF]
Open phase, negative phase
(TCC-L / AI-NET)
NO NO Repair SV2 circuit.
Is SV2 circuit normal? YES A
Replace PMV body.
with miscabling check ( Check ) function of outdoor unit.
Check and correct the cabling.
Does cooling outdoor fan normally operate?
®
Check indoor P.C. board. Failure Replace
YES
Are characteristics of high-pressure sensor normal?
B
YES
Repair the flow selector unit.
Is the flow selector normal? Normal
NO
(
Coil error, clogging, disconnection of wiring, etc.
)
• Check the phase power line of outdoor unit. • Check error of outdoor I/F P.C. board. • Check there is no looseness, etc of terminal.
Cause of operation 1. Power supply open phase 2. Power supply negative phase
Check code
Check code name
[P07] / [1C]
Heat sink overheat error
Cause of operation
(TCC-L / AI-NET)
1. 2. 3. 4. 5.
Power voltage error Outdoor fan system error Heat sink installation error Clogging of hear sink cooling duct IPDU P.C. board error (TH sensor error)
Check code
Check code name
[P12] / [11]
Indoor fan motor error
(TCC-L / AI-NET)
Turn off power supply. Sub-code: 01: Compressor 1 side 02: Compressor 2 side NO
Is power voltage normal?*
Correct power line.
* 380–415V ± 10% YES NO
Is wiring of IPDU normal?
* Detectable only in models with DC fan motor 4-way Air Discharge Cassette, or Concealed Duct Standard type Under Ceiling, or High Wall type
(
YES
)
Correct connector connection.
NO
Correct wiring such as cable to compressor.
YES
Remove connectors CN333 and CN334 on indoor P.C. board (MCC-1402).
NO
Is indoor fan normal?
Is there connection error or disconnection on connector CN333, CN334 of indoor P.C. board (MCC-1402)?
Cause of operation 1. Cabling error of fan motor connector 2. Fan motor error 3. Indoor P.C. board error
Check fan and fan motor.
YES Is fixing between IPDU and heat sink loose?
YES
Does fan turn without trouble when turning it with hands?
Tighten screws.
NO Clear blocking.
Is resistance value between each phase at motor side of fan motor connector CN333 on indoor P.C. board (MCC-1402) correct? *1
NO
156
Check IPDU P.C. board.
YES
Check code
Check code name
[P10] / [0b]
Indoor overflow error
(TCC-L / AI-NET)
Cause of operation 1. 2. 3. 4.
Float SW operation error Drain pump operation error Clogging of drain pipe Indoor P.C. board error
YES
NO
Correct connector connection.
YES NO
Does float SW operate?
NO Is wiring normal?
YES
Check and correct wiring.
YES
®
Check indoor P.C. board. Failure Replace
YES
Check drain pipe, etc.
NO
Is power supply to drain pump normal?
NO
CN333
• Check there is 220–240 V voltage of 1-3 pin of CN68 on indoor P.C. board.
NO
Replace indoor fan motor.
NO
Replace indoor fan motor.
*3 Check fan motor position detective signal. • Measure voltage with tester between CN334 1 and 5 on indoor P.C. board (MCC-1402) under condition of CN333 and CN334 installed and power-ON. ® Turn fan slowly with hands so that pin voltage fluctuates between 0 and 5V. • Between 4 and 5: 5V
®
Check indoor P.C. board (MCC-1402). Failure Replace
®
Check indoor P.C. board. Failure Replace
YES Replace drain pump, and check cabling.
Replace indoor fan motor.
*2 Check insulation resistance value of fan motor position detective circuit. • Is winding 1 (Yellow lead) to 4 (Pink lead) opened/shorted? ® Resistance should be 5 to 20kW
Is output of indoor fan motor position detective signal correct? *3
YES
NO
*1 • Is not winding 1 (Red lead) to 3 (White lead), 3 (White lead) to 5 (Black lead), 5 (Black lead) to 1 (Red lead) opened/shorted? ® Resistance value should satisfy the follows. [4-way Air Discharge Cassette type] MMU-AP0091H, AP0301 ® Approx. 70 to 100W MMU-AP0361H, AP0561 ® Approx. 35 to 50W [Concealed Duct Standard, Under Ceiling, High Wall type] 15 to 35W • Check insulation resistance between the cabinet and 1, 3, 5? ® Should be 10W or more
Is resistance value at motor side of fan motor connector CN334 on indoor P.C. board (MCC-1402) correct? *2
Sub-code: Indoor address with trouble
Does drain pump operate?
Replace indoor fan motor.
YES YES
Is there blocking of heat sink cooling duct?
Is float SW connector (Indoor control P.C. board CN34) connected normally?
NO
CN334
Check code name
Check code
[P13] / [47]
Cause of operation
Outdoor liquid back detection error 1. PMV1/PMV2 error
(TCC-L / AI-NET)
2. 3. 4. 5. 6.
Are connections of outdoor PMV1/PMV2 connectors correct?
NO
Pd sensor, Ps sensor error Clogging of SV2 circuit Clogging of SV3B circuit, balance pipe Leakage on main discharge pipe Outdoor I/F P.C. board error
Correct connector connection. (CN300, CN301)
YES
Are operations of outdoor PMV1/PMV2 normal?
Check code name
Gas leak detection TS condition (Sub-code: 01)
(TCC-L / AI-NET)
Are service valves at gas and liquid side fully opened?
Cause of operation 1. 2. 3. 4.
Outdoor unit service valve closed Outdoor PMV error TS1 sensor error Refrigerant shortage, clogging refrigerant circuit 5. 4-way valve error 6. SV4 circuit error
NO
Open service valves fully.
YES
NO
PMV error
YES
Are characteristics of Pd sensor/Ps sensor output voltage normal?
Check code
[P15] / [AE]
NO
Is outdoor PMV1, 2 normal? 1. Connector connection 2. Wiring 3. Coil 4. Valve body 5. Outdoor I/F P.C. board
NO
Repair outdoor PMV.
Connectors CN300, 301 White
Pd sensor/Ps sensor error YES
YES NO Is SV2 valve coil correctly connected?
Correct connector connection. (CV2: CN302)
YES
YES
157
Is there any miswiring or misinstallation on TS1 and TS2 sensors? NO
Check I/F P.C. board.
Are characteristics of TS2 sensor resistance normal?
YES Correct miswiring/installation
Does not discharge refrigerant gas bypass to suction side through 4-way valve?
NO
Replace TS2 sensor.
Refer to outdoor unit temperature sensor characteristics-3.
YES
Check and replace 4-way valve and coil.
NO
Is there no leakage of SV41 and 42 valve circuits?
NO
valve body, ( Coil, disconnection of cable, etc )
YES
Check mispiping of discharge gas/ suction gas main pipes.
Repair SV41 and SV42 circuits.
Abnormal
Correct piping.
Normal
Is the flow selector unit normal?
Abnormal
Repair the flow selector unit.
Normal
Refrigerant shortage, clogging, pipe breakage.
(Check there is no clogging and pipe breakage, and then recharge refrigerant.)
Check code
Check code name
[P15] / [AE]
Gas leak detection TD condition (Sub-code: 02)
(TCC-L / AI-NET)
Are service valves on gas and the liquid sides fully opened?
1. 2. 3. 4. 5.
Cause of operation
Check code
Check code name
Cause of operation
Outdoor unit service valve closed Outdoor PMV error TD sensor error SV4 circuit error Refrigerant shortage, clogging refrigerant circuit
[P17] / [bb]
Discharge temp TD2 error
1. Outdoor unit service valve closed 2. Outdoor PMV error 3. TD sensor error 4. Refrigerant shortage, clogging of refrigerant circuit 5. 4-way valve error 6. SV4 circuit leakage, misinstallation 7. SV5 circuit leakage 8. SV6 circuit clogging 9. Mispiping of discharge gas/suction gas pipes 10. Flow selector unit error
NO
(TCC-L / AI-NET)
Open the service valves fully.
YES
Is outdoor PMV1, 2 normal? 1. Connector connection 2. Cabling 3. Coil 4. Valve body 5. Outdoor I/F P.C. board
Are service valves of gas and liquid sides fully opened? NO
Repair outdoor PMV.
* Connectors CN300, 301 White
Is outdoor PMV normal? 1. Connector connection 2. Cabling 3. Coil 4. Valve body 5. Outdoor I/F P.C. board
YES
158
Is SV4 valve circuit normal? (Coil misinstallation, valve leakage)
NO
NO
Repair outdoor PMV.
* Connectors CN300, 301 White
Replace TD1 or TD2 sensor.
* Refer to outdoor unit temperature sensor characteristics-4.
YES Are characteristics of TD2 sensor resistance normal?
NO
YES
Repair SV41 and SV42 circuits.
(
YES
Open service valves fully.
YES
YES Are characteristics of TD1, TD2 sensor resistance normal?
NO
Coil, valve body, coil installation, disconnection of cable, etc.
)
Does not discharge refrigerant gas by pass to suction sidethrough 4-way valve?
NO
Replace TD2 sensor.
* Refer to outdoor unit temperature sensor characteristics-4. NO
Check 4-way valve.
YES Are there indoor units connected in different refrigerant circuit?
NO
Correct cabling.
YES
Check leakage of SV5 and SV11 circuits.
Abnormal
Replace defective parts.
SV4 circuit 1. Are not SV41 and SV42 valve coils installed reversely? 2. Is there no leakage through SV42 circuit?
NO
Correct installation of valve coil. Replace SV42 valve.
YES NO Check leakage of SV5 circuit.
Replace defective parts.
Normal YES Check for mispiping of discharge gas/suction gas main pipes.
Abnormal
NO Correct piping.
Replace defective parts.
YES
Normal Abnormal Is the flow selector unit normal?
Check clogging of SV6 circuit.
Repair the flow selector unit.
Check mispiping of discharge gas/ suction gas main pipes.
NO
Correct piping.
YES Normal
NO Is the flow selector unit normal?
Refrigerant shortage, clogging, pipe breakage.
(Check there is no clogging and pipe breakage and then recharge refrigerant.)
Repair the flow selector unit.
YES Are there indoor units connected in different refrigerant circuit? YES Refrigerant shortage, clogging, pipe breakage.
NO
Correct cabling.
the mis-wiring check ( Use function of outdoor unit. ) there is no clogging and pipe leakage, ( Check ) and then recharge with refrigerant.
Check code
Check code name
[P19] / [08]
4-way valve operation error
Cause of operation
(TCC-L / AI-NET)
1. 2. 3. 4.
4-way valve error TS1 sensor/TE1 sensor error Pd sensor/Ps sensor error TE sensor/TL sensor misconnection
Check code
Check code name
[P20] / [22]
High-pressure protective operation
Cause of operation
(TCC-L / AI-NET)
Sub-code: Detected outdoor unit No.
NO
Is 4-way valve coil connector connected?
Correct connector connection. (4-way valve coil: CN317)
YES Correct connector connection. TS1 sensor: CN504 TE1 sensor: CN505 Pd sensor: CN501 Ps sensor: CN500
NO
Are TS1, TE1, Pd, Ps sensor connectors connected? YES
NO
Check mispiping of discharge gas/ suction gas main pipes.
NO
NO
®
Check parts. Failure Replace
YES
Normal
Are output voltage characteristics of Pd and Ps sensors normal?
Open service valves fully.
YES
Replace sensor.
YES
Abnormal Correct piping. Abnormal
Check operation of PMV3 SV12.
Replace sensor.
Normal
Replace defective parts. Abnormal
159
Is the flow selector unit normal?
YES
Pd sensor error Service valve closed. Indoor/outdoor fan error Indoor/outdoor PMV clogging Indoor/outdoor heat exchanger clogging SV2 circuit error SV4 circuit error SV5 circuit error Outdoor I/F P.C. board error Operation error of check valve of main discharge pipe 11. Refrigerant overcharge
NO Are service valves fully opened?
Are characteristics of high-pressure sensor normal?
Are characteristics of resistance value of TS1 and TE1 sensors normal?
1. 2. 3. 4. 5. 6. 7. 8. 9. 10.
Repair the flow selector unit.
Normal
Are connection and installation of TE1 and TL sensors correct?
NO
Correct connection and installation.
Reset power supply, and start a test operation corresponded to the season.
YES B
Reset the power supply and start heating test operation.
All cooling operation
Does cooling outdoor fan normally operate? YES
All cooling operation ® To B All heating operation ® To C * 1. Pressure by pressure gauge (Check joint) 2. Pressure display on 7-segment display 3. Output voltage of I/F P.C. board If 1 and 2, 3 are different, an error of pressure sensor is considered. If 2 and 3 are different, check I/F P.C. board.
NO Correct faulty parts. YES
Is there no fan crack or coming-off?
NO
Replace the FS unit.
Is the flow selector unit normal?
Correct faulty parts. (Connector connection, fan IPDU, fan motor, wiring)
NO NO
YES
Is outdoor PMV1, 2 normal?
YES Does 4-way valve operate? NO
Does refrigerant gas discharge to suction side through 4-way valve? *1
NO
If an error did not occur in test operation, restart the operation.
YES
Correct faulty position.
YES Are there any obstructions to the operation of the heat exchanger? 1. Blocked heat exchanger 2. Air short circuit NO
(Connector connection wiring, coil mounting, valve clogging, etc) YES Eliminate the interfered causes.
NO
Is SV2 circuit normal?
4-way valve error
Check 4-way valve.
Repair SV2 circuit.
YES
(Coil error, clogging, disconnection of cable, etc.) NO
Is SV4 circuit normal?
*1 Check TS and TE temperature of the outdoor unit which compressors is operated. (I/F) SW01=[1], SW02=[6], SW03=[2] ® TS sensor temperature SW01=[1], SW02=[7], SW03=[2] ® TE sensor temperature
Judgment criteria TE sensor: Normal if TE ≤ 20˚C except summer season (Outside temp 20˚C or lower) TS sensor: Normal if TS ≤ 40˚C except summer season (Outside temp 20˚C or lower)
Repair SV4 circuit. (Coil error, clogging, disconnection of cable, etc.)
YES Does the check valve of the main discharge pipe operate normally? YES Refrigerant overcharge, clogging, pipe breakage, abnormal overload condition
NO
Repair check valve. ® Replace
C
Check code
Check code name
[P22] / [1A]
Outdoor fan IPDU error
(TCC-L / AI-NET)
All heating operation
Is connector connection of indoor heat exchanger fan or fan motor normal?
NO
Does heating indoor fan normally operate? YES
Sub-code:
YES NO Repair faulty parts.
0 ∗ : IGBT short circuit 3 ∗ : Motor lock error C∗ : TH sensor error (Heat sink overheat) E ∗ : Vdc error
YES NO
Are characteristics of sensor TC2 and TCJ resistance normal?
YES
Are wire connections on the fan IPDU and the power P.C. board assembly normal?
NO
NO
1 ∗ : Position detect circuit error 4 ∗ : Motor current error detected D∗ : TH sensor error
Correct cable connector connection.
YES
YES Repair faulty parts.
Fan lock Fan IPDU P.C. board error Overload External cause such as power surge Fan IPDU power P.C. board error
NO
Is indoor PMV normal?
Is connector connection coil normal?
Cause of operation 1. 2. 3. 4. 5.
Replace TC2 or TCJ sensor.
Is the outdoor fan motor locked?
YES
NO
NO Is there a clogging?
®
Check indoor P.C. board. Faulty Replace
Is winding resistance of the motor correct? 13 to 33W (Between R and S, R and T, S and T)
YES Replace PMV body .
160
Is check valve of main discharge pipe normal?
NO
Repair check valve.
Repair check valve.
® Replace ® Replace
Retightening of screws, etc.
YES
Eliminate the interfered causes. Is there no problem such as stuffing or blast blowing to discharge port of outdoor fan? NO
Repair SV5 circuit.
Is SV5 circuit normal?
(
YES Abnormal Check operation of 4-way valve.
Coil error, choke, disconnection of cable, etc. Replace 4-way valve.
Normal Abnormal Check clogging of SV11 circuit.
Replace defective parts.
Normal
Refrigerant overcharge, clogging, pipe breakage, abnormal overload condition
YES
Replace fan IPDU.
NO
YES
NO
YES
Is the fan IPDU firmly attached to the heat sink.
Is sub-code of outdoor I/F P.C. board [0d]?
NO
Are there indoor units connected to different refrigerant circuits?
Replace motor.
YES
YES
YES Are there any obstructions to the operation of the heat exchanger? 1. Air filter clogging 2. Blocked heat exchanger 3. Air short circuit
NO
NO the mis-wiring check function ( Use ) of outdoor unit.
Check and correct cabling.
Check fan IPDU.
)
YES
Correct cause of overload.
Check code
Check code name
[P26] / [14]
G-Tr short-circuit protection error
(TCC-L / AI-NET)
Cause of operation 1. 2. 3. 4.
Outdoor unit power error IPDU error/Cable connection error Compressor error IPDU P.C. board error
Check code
Check code name
[P29] / [16]
Compressor position detective circuit error
(TCC-L / AI-NET)
Cause of operation 1. Wire connection error. 2. Compressor error 3. IPDU P.C. board error
Sub-code: 01: Compressor 1 side 02: Compressor 2 side Sub-code: 01: Compressor 1 side 02: Compressor 2 side
Is the power supply voltage to the outdoor unit normal?
NO Correct power line.
Are the connectors and wiring to the compressor normal?
NO
Check and correct circuit and wires, i.e. to the compressor, etc.
YES
Compressor error ® Replace
YES
Compressor error ® Replace
YES
Compressor error ® Replace
YES YES
Is wire connector connection on the IPDU P.C. board normal?
NO
Is it grounded? Correct the wire connections.
NO
YES NO Is compressor operation normal?
Replace compressor.
Is there a winding short? (Is winding resistance 0.1 to 0.3W?) NO
YES
Is smoothing condenser normal? (1500µF, 350V)
NO
Is the winding open circuit? Check capacity valve external appearance.
NO
YES
161
Replace IPDU P.C. board.
Check IPDU P.C. board. Failure ® Replace
Check code
Check code name
[P31] / [47]
Other indoor error (Group follower unit error)
(TCC-L / AI-NET)
Cause of operation Other indoor unit in the group has a error.
When the header unit of the group detects [E03, L03, L07, L08 error], the follower unit(s) in the group display [P31] error and stop. There are no check code displays or alarm record on the main remote controller.
Check code
Check code name
[–] / [97]
AI-NET communication line error
Cause of operation AI-NET communication line error
(TCC-L / AI-NET)
Are AI-NET X and Y communication lines normal?
NO
Correct communication line.
YES Are connections of CN01, CN02, and CN03 connectors on network adaptor P.C. board (MCC-1401) and CN309 and CN41 connectors on indoor P.C. board normal?
NO
Correct connection of connectors.
YES Are remote controller communication lines (A, B) normal?
NO
Check connection of A, B terminal. Correct communication line of remote controller.
YES Is there no connection error on the power line?
YES
Correct power line.
NO
162
Is not main power supply turned on?
YES
Turn on the main power supply.
NO Did a block-out occur?
YES
Clear check code.
NO Is the network address changed by the main remote controller?
YES
NO YES
Eliminate noise, etc.
Is there any noise etc.? NO Can other indoor units be controlled from AI-NET central remote controller, or is the operation status of indoor unit the same?
Unavailable (Others are same.)
®
Check central controller. Failure Replace
YES Does the network adaptor P.C. board LED (D01) turn on?
NO
Can the NO indoor unit be controlled from the main remote controller?
®
Check indoor P.C. board. Failure Replace
YES YES Check power transformer of the network adaptor P.C. board (MCC-1401). Failure Replace
®
9-6. 7-Segment Display Function n 7-segment display on the outdoor unit (Interface P.C. board) On the interface control P.C. board, a 7-segment LED is provided to check the operating status. The displayed contents are changed by combining the setup numbers of the rotary switches (SW01, SW02 and SW03) on the I/F P.C. board.
Interface P.C. board SW06
7-segment display A
7-segment display B
SW06
SW07
SW08
SW09
D600
3rd. place
2nd. place
SW05
CN32 SW04 D601 D602 D603
D600
1st. place
SW08
CN30 CN31
CN30 CN31
2nd. place
SW07
SW05
CN32 SW04 D601 D602 D603
SW15
D604
SW15
D604
Display A
Display A
1st. place
SW09
SW01
SW02
SW03
Display B
SW01
SW02
Display B
SW03
u Check procedure when the system has stopped due to an trouble When the system has stopped due to an trouble in the outdoor unit, execute the following check procedure. 1. Open the panels of the outdoor unit, and then check the 7-segment display. The check code is shown on the right side of 7-segment display B. [U1] [¡¡¡] ([¡¡¡]: Check code) ∗ Rotary switch setup for confirming the check code: SW01 [1], SW02 [1], SW03 [1]. However the check code [OOO] is displayed for 3 seconds and the sub-code [OOO] for 1 second are alternately displayed if a sub-code is provided. 2. Confirm the check code, and then follow the check procedure detailed for the diagnosis of the fault. 3. [U1] [E28] on the 7-segment display means an error on the follower unit. change. Push and hold switch SW04 on the header unit for 2 seconds or more. Only the fan of the outdoor unit with a fault will operate. Open the panel of the corresponding unit, and then confirm the ceck code shown on the 7-segment display. 4. Perform the check procedure based on each check code diagnosis.
How to read the check display 7-segment display
0
1
2
3
4
5
6
7
8
9
A
b
C
d
E
a
c
e
G
h
i
n
o
r
S
t
V
y
–
u
163
F
H
J
L
P
1. Data display of system information (Displayed on the header outdoor unit only) SW01 SW02 SW03 1
1
2
3
4
5
6
7
8
9
3
Display contents Refrigerant name
System capacity
No. of outdoor units
No. of connected indoor units/ No. of units with cooling thermo ON No. of connected indoor units/ No. of units with heating thermo ON Compressor command correction amount Release control
Oil-equalization control
Oil-equalization request
Displays refrigerant name.
A
Model with refrigerant R410A
r4
10A
Model with refrigerant R407C
r4
07C
A
[ 5] to [48]
B
[HP]
A
[ 1] to [ 4]
B
[ P]
: 5 to 48HP
: 1 to 4 units
A
[ 0] to [48]
B
[C0] to [C48] : 0 to 48 units (No. of units with cooling thermo ON)
: 0 to 48 units (No. of connected units)
A
[ 0] to [48]
B
[H0] to [H48] : 0 to 48 units (No. of units with heating thermo ON)
: 0 to 48 units (No. of connected units)
A
Data is displayed with hexadecimal notation
B A
Normal time : [ r], During release control: [r1]
B
—
A
Normal time : [oiL-0]
B
During oil equation : [oiL-1]
A
Displays with segment LED lighting pattern
B
Display A
Display B
A F G B E
C D Dp
10
11
12
13
Refrigerant/oil recovery operation
Automatic address
Demand operation
Optional control (P.C. board input)
U2
U3
U4
F in the left figure goes on: Header requests oil equalization. C in the left figure goes on: Follower requests oil-equalization. (Outdoor unit number)
A
During sending of cooling refrigerant oil recovery signal : [C1]. Normal time : [C ]
B
During sending of heating refrigerant oil recovery signal : [H1]. Normal time : [H ]
A
[Ad]
B
Automatic addressing : [FF], Normal time : [ ]
A
[dU]
B
Normal time : [ ]. In 50% to 90% : [ 50 to 90] When controlling by communication line input : [E50 to E90]
Displays optioned control status
A
B
h.∗
∗.∗.∗.
Priority on cooling
c.∗
∗.∗.∗.
Heating only
H.∗
∗.∗.∗.
Cooling only
C.∗
∗.∗.∗.
Priority on No. of operating indoor units
n.∗
∗.∗.∗.
Operation mode selection : In heating with priority (Normal)
U.∗
∗.∗.∗.
∗.… .
∗.∗.∗.
Start input
∗.1.
∗.∗.∗.
Stop input
∗.0.
∗.∗.∗. ….∗.∗.
Priority on specific indoor unit Batch start/stop
: Normal
∗.∗.
Night low-noise operation : Normal
∗.∗.
Operation input Snow fan operation : Normal Operation input 14
Option control (BUS line input)
15
Unused
16
—
B
∗.∗.
1.∗.∗. ∗.….∗.
∗.∗.
∗.1.∗.
Same as above
A
—
B
—
∗ mark: Indicates none on display 164
2. Data display of outdoor unit information (Displayed on each outdoor unit) SW01 SW02 SW03 1
1
1
Display contents Error data
A
Displays outdoor unit number: [U1] to [U4]
B
Displays check code (Latest code only is displayed.) There is no check code: [– – –] There is sub-code: Check code [∗ ∗ ∗] for 3 seconds, sub-code [– ∗ ∗] for 1 second alternately
push function : Fan of unit with error only drives. 7-segment A: [E1] push function : Fan of normal unit only drives. 7-segment A: [E0] push function : Interruption of fan operation function 2
3
—
Operation mode
A
—
B
—
A
Stop: [ ] Normal cooling: [ C], Normal heating: [ H], Normal defrost: [ J]
B 4
5
Outdoor unit HP
Compressor operation command
—
A
5HP: [ 5], 6HP: [ 6], 8HP: [ 8], 10HP: [10], 12HP: [12]
B
[HP]
A
No.1 compressor operation command is displayed. Data display with Hexadecimal notation: [00 to FF]
B
No.2 compressor operation command is displayed. Data display with Hexadecimal notation: [00 to FF]
push function 7-segment display (A/B) 6
7
8
9
Outdoor fan step
Compressor backup
—
Control valve output data
10
11
12
A
[FP]
B
Step 0 to 31: [ 0 to 31]
A
Displays No.1 compressor setup status Normal: [ ], Backup setup: [C1]
B
Displays No.2 compressor setup status Normal: [ ], Backup setup: [C2]
A
—
B
—
Displays control output status of solenoid valve
A
B
4-way valve: ON
H. 1
………
4-way valve: OFF
H. 0
………
SV2: ON / SV5: OFF
2. 1
… 5. 0
SV2: OFF / SV5: ON
2. 0
… 5. 1
SV3A: ON / SV3B: OFF / SV3C: OFF /SV3D: OFF
3. 1
0 0 0
SV3A: OFF / SV3B: ON / SV3C: OFF /SV3D: OFF
3. 0
10 0
SV3A: OFF / SV3B: OFF / SV3C: ON /SV3D: OFF
3. 0
0 1 0
SV3A: OFF / SV3B: OFF / SV3C: OFF /SV3D: ON
3. 0
0 0 1
SV41: ON / SV42: OFF
4. …
10…
SV41: OFF / SV42: ON
4. …
0 1…
—
……
………
—
……
………
∗∗
∗ ∗. P
…∗
∗ ∗. P
13
14 15 16
PMV1 /PMV2 opening
Displays opening data (Decimal) (Total opening)
— Oil level judgment status
: Inverter frequency is exchanged to decimal notation. : [∗ ∗ ] [∗ ∗ H] (Normal display by pushing )
— A
[oL] [SW05] push SW function: The following data is displayed for 2 seconds. * During oil shortage in compressor 1: [L …], during oil shortage in compressor 2: [… L]
B
Initial display: [… … …], Oil level judgment result: [A. #. ∗] Judgment result of compressor 1 in [#], compressor 2 in [∗] (0: Normal, 1, 2: Shortage) is displayed.
165
3. Data display of outdoor cycle (Displayed on each outdoor unit) SW01 SW02 SW03 1
1
2
Display contents Pd pressure data
Pd pressure (MPaG) is displayed with decimal data. (MPaG: Approx. 1/10 value of kg/cm2G data)
2
Ps pressure data
3
PL pressure conversion data Estimated pressure of liquid line (MPaG) is displayed with decimal data.
4
TD1 sensor data
5
Ps pressure (MPaG) is displayed with decimal data.
TD2 sensor data
7 8
TS1 sensor data
B ∗. ∗ ∗
P S.
∗. ∗ ∗
P L.
∗. ∗ ∗
Temperature sensor data (°C) is displayed with decimal notation.
Symbol
td
111
Data
• Symbol display for 1 sec. and data display for 3 sec. are alternately displayed.
∗
∗ ∗. ∗
Symbol
td
211
Data
∗
∗ ∗. ∗
Symbol
tS
111
Data
∗
∗ ∗. ∗
Symbol
tS
211
Data
∗
∗ ∗. ∗
Symbol
tE
—
Data
—
—
tL
• Data is displayed in [∗]. 6
A P d.
• Negative data is displayed as [– ∗ ∗ ∗ ∗].
TS2 sensor data TE sensor data
9
TL sensor data
Symbol Data
∗
10
TO sensor data
Symbol
to
Data
∗
Symbol
F1
11
TK1 sensor data
Data
∗ F2
12
TK2 sensor data
Symbol Data
∗
13
TK3 sensor data
Symbol
F3
Data
∗
Symbol
F4
Data
∗
14
TK4 sensor data
15
—
A
—
B
—
16
—
A
—
∗ ∗. ∗ ∗ ∗. ∗ ∗ ∗. ∗ ∗ ∗. ∗ ∗ ∗. ∗ ∗ ∗. ∗
B
4. Data display of indoor unit information (Displayed on the header unit only) SW01 SW02 SW03 4
1 to 16 1 to 3 Receiving status of indoor BUS communication
B
Display contents Receiving time: [… … 1], Not received: [… … …]
5
Indoor check code
B
6
Indoor capacity (HP) horse power
B
7
Indoor request command (S code)
B
No check code: [– – –] 0. 2, 0. 5, 0. 8, … 1, 1. 2, 1. 7, … 2, 2. 5, … 3, 3. 2, … 4, … 5, … 6, … 8, 1 0, 1 6, 2 0 Data is displayed with Hexadecimal notation [… … 0 to … … F] : Heating
8
Indoor PMV opening data
B
Data is displayed with Hexadecimal notation
9
Indoor TA sensor data
B
Data is displayed with Hexadecimal notation
10
Indoor TF sensor data
B
Data is displayed with Hexadecimal notation
11
Indoor TCJ sensor data
B
Data is displayed with Hexadecimal notation
12
Indoor TC1 sensor data
B
Data is displayed with Hexadecimal notation
13
Indoor TC2 sensor data
B
Data is displayed with Hexadecimal notation
NOTE) Indoor address No. is chosen by changing SW02 and SW03. SW03 SW02
Indoor address
7-segment display A
1
1 to 16 SW02 setup number
[01] to [16]
2
1 to 16 SW02 setup number + 16
[17] to [32]
3
1 to 16 SW02 setup number + 32
[33] to [48]
166
5. Outdoor EEPROM check code display (Displayed on the header unit only) ∗ The latest check code written in EEPROM on each outdoor unit is displayed. (It is used when confirming the check code after power supply has been reset.) Set SW01 to 03 as shown in the following table and the push SW04 for 5 seconds or more to display an check code. W01 1
SW02 SW03 1
16
7-segment display
Display contents
A
B
The latest check code of the header unit 1 (U1)
E. r
1. – –
2
The latest check code of the follower unit 1 (U2)
E. r
2. – –
3
The latest check code of the follower unit 2 (U3)
E. r
3. – –
n 7-segment display A, B
Display A
D600
Display B
D601
D602
D603
9-7. Sensor Characteristics 9-7-1. Outdoor Unit
Characteristic-3 40
n Temperature sensor characteristics
Outdoor TS1, TS2, TO, TL sensors
Resistance [k ]
30
20
10
0 -10
0
10
20
30
40
50
60
70
Temperature [˚C] Characteristic-4 200
10
Outdoor TD1, TD2, TK1, TK2, TK3, TK4 sensors
5
Resistance [k ] (65˚C or higher)
100
50
0
10
20
30
40
50
60
70
80
90 100 110 120 130 140 150
0
Temperature [˚C] Characteristic-5 20
Outdoor TE1 sensor
150
15
100
10
50
5
0 -30 -20 -10
0 0
10
20
30
40
50
Temperature [˚C]
167
60
70
80
90 100
Resistance [k ] (10˚C or higher)
200 Resistance [k ] (10˚C or lower)
Resistance [k ]
150
D604
n Pressure sensor characteristics • I/O cable connection table High pressure side (Pd)
Pin No.
Low pressure side (Ps)
Input/Output name
Lead wire color
Input/Output name
Lead wire color
1
OUTPUT
White
—
—
2
—
—
OUTPUT
White
3
GND
Black
GND
Black
4
+5V
Red
+5V
Red
• Output voltage — Pressure High pressure side (Pd)
Low pressure side (Ps)
0.5 to 3.9 V DC
0.5 to 3.5 V DC
0 to 3.33 MPa
0 to 0.98 MPa
5 Output at low pressure side (V)
Output at high pressure side (V)
5
3.9
0.5
3.5
0.5
0
3.33 Pressure (MPa)
4.41
0
5.1
0.98
1.47
5.1 Pressure (MPa)
9-7-2. Indoor Unit n Temperature sensor characteristics
Resistance [k ]
30
20
10
0
10
20
30 40 50 Temperature [˚C]
200 Resistance [k ] (10˚C or lower)
Indoor TA sensor
20 Indoor TC1, TC2, TCJ sensors
Characteristic-2 150
15
100
10
50
5
0 -30
0 -20 -10
0
168
10
20
30 40 50 60 Temperature [˚C]
70
80
90 100
Resistance [k ] (10˚C or higher)
Characteristic-1
40
9-8. Pressure Sensor Output Check 9-8-1. Outdoor Unit n Pd sensor characteristics 0 to 4.41MPa (0.5 to 5V output with 0 to 4.41MPa) Voltage check between CN501 and pins on the outdoor unit I/F P.C. board (Tester Pd Pd VOLT (MPa) (kg/cm²) 0.00 0.00 0.0 0.02 0.00 0.0 0.04 0.00 0.0 0.06 0.00 0.0 0.08 0.00 0.0 0.10 0.00 0.0 0.12 0.00 0.0 0.14 0.00 0.0 0.16 0.00 0.0 0.18 0.00 0.0 0.20 0.00 0.0 0.22 0.00 0.0 0.23 0.00 0.0 0.25 0.00 0.0 0.27 0.00 0.0 0.29 0.00 0.0 0.31 0.00 0.0 0.33 0.00 0.0 0.35 0.00 0.0 0.37 0.00 0.0 0.39 0.00 0.0 0.41 0.00 0.0 0.43 0.00 0.0 0.45 0.00 0.0 0.47 0.00 0.0 0.49 0.00 0.0 0.51 0.01 0.1 0.53 0.03 0.3 0.55 0.05 0.5 0.57 0.07 0.7 0.59 0.08 0.9 0.61 0.10 1.1 0.63 0.12 1.3 0.65 0.14 1.4 0.66 0.16 1.6 0.68 0.18 1.8 0.70 0.20 2.0 0.72 0.22 2.2 0.74 0.24 2.4 0.76 0.26 2.6 0.78 0.28 2.8 0.80 0.30 3.0 0.82 0.31 3.2 0.84 0.33 3.4 0.86 0.35 3.6 0.88 0.37 3.8 0.90 0.39 4.0 0.92 0.41 4.2 0.94 0.43 4.4 0.96 0.45 4.6 0.98 0.47 4.8
Pd Pd VOLT (MPa) (kg/cm²) 1.00 0.49 5.0 1.02 0.51 5.2 1.04 0.53 5.4 1.06 0.54 5.5 1.07 0.56 5.7 1.09 0.58 5.9 1.11 0.60 6.1 1.13 0.62 6.3 1.15 0.64 6.5 1.17 0.66 6.7 1.19 0.68 6.9 1.21 0.70 7.1 1.23 0.72 7.3 1.25 0.74 7.5 1.27 0.76 7.7 1.29 0.77 7.9 1.31 0.79 8.1 1.33 0.81 8.3 1.35 0.83 8.5 1.37 0.85 8.7 1.39 0.87 8.9 1.41 0.89 9.1 1.43 0.91 9.3 1.45 0.93 9.5 1.47 0.95 9.6 1.48 0.97 9.8 1.50 0.99 10.0 1.52 1.00 10.2 1.54 1.02 10.4 1.56 1.04 10.6 1.58 1.06 10.8 1.60 1.08 11.0 1.62 1.10 11.2 1.64 1.12 11.4 1.66 1.14 11.6 1.68 1.16 11.8 1.70 1.18 12.0 1.72 1.20 12.2 1.74 1.21 12.4 1.76 1.23 12.6 1.78 1.25 12.8 1.80 1.27 13.0 1.82 1.29 13.2 1.84 1.31 13.4 1.86 1.33 13.6 1.88 1.35 13.8 1.90 1.37 13.9 1.91 1.39 14.1 1.93 1.41 14.3 1.95 1.43 14.5 1.97 1.44 14.7
Pd Pd VOLT (MPa) (kg/cm²) 1.99 1.46 14.9 2.01 1.48 15.1 2.03 1.50 15.3 2.05 1.52 15.5 2.07 1.54 15.7 2.09 1.56 15.9 2.11 1.58 16.1 2.13 1.60 16.3 2.15 1.62 16.5 2.17 1.64 16.7 2.19 1.66 16.9 2.21 1.67 17.1 2.23 1.69 17.3 2.25 1.71 17.5 2.27 1.73 17.7 2.29 1.75 17.9 2.31 1.77 18.0 2.32 1.79 18.2 2.34 1.81 18.4 2.36 1.83 18.6 2.38 1.85 18.8 2.40 1.87 19.0 2.42 1.89 19.2 2.44 1.90 19.4 2.46 1.92 19.6 2.48 1.94 19.8 2.50 1.96 20.0 2.52 1.98 20.2 2.54 2.00 20.4 2.56 2.02 20.6 2.58 2.04 20.8 2.60 2.06 21.0 2.62 2.08 21.2 2.64 1.10 21.4 2.66 2.12 21.6 2.68 2.13 21.8 2.70 2.15 22.0 2.72 2.17 22.2 2.73 2.19 22.3 2.75 2.21 22.5 2.77 2.23 22.7 2.79 2.25 22.9 2.81 2.27 23.1 2.83 2.29 23.3 2.85 2.31 23.5 2.87 2.33 23.7 2.89 2.35 23.9 2.91 2.36 24.1 2.93 2.38 24.3 2.95 2.40 24.5 2.97 2.42 24.7
169
Pd Pd VOLT (MPa) (kg/cm²) 2.99 2.44 24.9 3.01 2.46 25.1 3.03 2.48 25.3 3.05 2.50 25.5 3.07 2.52 25.7 3.09 2.54 25.9 3.11 2.56 26.1 3.13 2.57 26.3 3.15 2.59 26.4 3.16 2.61 26.6 3.18 2.63 26.8 3.20 2.65 27.0 3.22 2.67 27.2 3.24 2.69 27.4 3.26 2.71 27.6 3.28 2.73 27.8 3.30 2.75 28.0 3.32 2.77 28.2 3.34 2.79 28.4 3.36 2.80 28.6 3.38 2.82 28.8 3.40 2.84 29.0 3.42 2.86 29.2 3.44 2.88 29.4 3.46 2.90 29.6 3.48 2.92 29.8 3.50 2.94 30.0 3.52 2.96 30.2 3.54 2.98 3.04 3.56 3.00 30.5 3.57 3.02 30.7 3.59 3.03 30.9 3.61 3.05 31.1 3.63 3.07 31.3 3.65 3.09 31.5 3.67 3.11 31.7 3.69 3.13 31.9 3.71 3.15 32.1 3.73 3.17 32.3 3.75 3.19 32.5 3.77 3.21 32.7 3.79 3.23 32.9 3.81 3.25 33.1 3.83 3.26 33.3 3.85 3.28 33.5 3.87 3.30 33.7 3.89 3.32 33.9 3.91 3.34 34.1 3.93 3.36 34.3 3.95 3.38 34.5 3.97 3.40 34.7
rod at pin side) Pd Pd VOLT (MPa) (kg/cm²) 3.98 3.42 34.8 4.00 3.44 35.0 4.02 3.45 35.2 4.04 5.48 35.4 4.06 3.49 35.6 4.08 3.51 35.8 4.10 3.53 36.0 4.12 3.55 36.2 4.14 3.57 36.4 4.16 3.59 36.6 4.18 3.61 36.8 4.20 3.63 37.0 4.22 3.65 37.2 4.24 3.67 37.4 4.26 3.69 37.6 4.28 3.70 37.8 4.30 3.72 38.0 4.32 3.74 38.2 4.24 3.76 38.4 4.36 3.78 38.6 4.38 3.80 38.8 4.40 3.82 38.9 4.41 3.84 39.1 4.43 3.86 39.3 4.45 3.88 39.5 4.47 3.90 39.7 4.49 3.92 39.9 4.51 3.93 40.1 4.53 3.95 40.3 4.55 3.97 40.5 4.57 3.99 40.7 4.59 4.01 40.9 4.61 4.03 41.1 4.63 4.05 41.3 4.65 4.07 41.5 4.67 4.09 41.7 4.69 4.11 41.9 4.71 4.13 42.1 4.73 4.15 42.3 4.75 4.16 42.5 4.77 4.18 42.7 4.79 4.20 42.9 4.81 4.22 43.0 4.82 4.24 43.2 4.84 4.26 43.4 4.86 4.28 43.6 4.88 4.30 43.8 4.90 4.32 44.0 4.92 4.34 44.2 4.94 4.36 44.4 4.96 4.38 44.6 4.98 4.39 44.8
n Ps sensor characteristics 0 to 1.48MPa (0.5 to 5V output with 0 to 1.48MPa) Voltage check between CN500 and pins on the outdoor unit I/F P.C. board (Tester Ps Ps VOLT (MPa) (kg/cm²) 0.00 0.00 0.0 0.02 0.00 0.0 0.04 0.00 0.0 0.06 0.00 0.0 0.08 0.00 0.0 0.10 0.00 0.0 0.12 0.00 0.0 0.14 0.00 0.0 0.16 0.00 0.0 0.18 0.00 0.0 0.20 0.00 0.0 0.22 0.00 0.0 0.23 0.00 0.0 0.25 0.00 0.0 0.27 0.00 0.0 0.29 0.00 0.0 0.31 0.00 0.0 0.33 0.00 0.0 0.35 0.00 0.0 0.37 0.00 0.0 0.39 0.00 0.0 0.41 0.00 0.0 0.43 0.00 0.0 0.45 0.00 0.0 0.47 0.00 0.0 0.49 0.00 0.0 0.51 0.00 0.0 0.53 0.01 0.1 0.55 0.02 0.3 0.57 0.02 0.2 0.59 0.03 0.3 0.61 0.03 0.4 0.63 0.04 0.4 0.65 0.05 0.5 0.66 0.05 0.5 0.68 0.06 0.6 0.70 0.07 0.7 0.72 0.07 0.7 0.74 0.08 0.8 0.76 0.09 0.9 0.78 0.09 0.9 0.80 0.10 1.0 0.82 0.11 1.1 0.84 0.11 1.1 0.86 0.12 1.2 0.88 0.12 1.3 0.90 0.13 1.3 0.92 0.14 1.4 0.94 0.14 1.5 0.96 0.15 1.5 0.98 0.16 1.6
Ps Ps VOLT (MPa) (kg/cm²) 1.00 0.16 1.7 1.02 0.17 1.7 1.04 0.18 1.8 1.06 0.18 1.8 1.07 0.19 1.9 1.09 0.19 2.0 1.11 0.20 2.0 1.13 0.21 2.1 1.15 0.21 2.2 1.17 0.22 2.2 1.19 0.23 2.3 1.21 0.23 2.4 1.23 0.24 2.4 1.25 0.25 2.5 1.27 0.25 2.6 1.29 0.26 2.6 1.31 0.26 2.7 1.33 0.27 2.8 1.35 0.28 2.8 1.37 0.28 2.9 1.39 0.29 3.0 1.41 0.30 3.0 1.43 0.30 3.1 1.45 0.31 3.2 1.47 0.32 3.2 1.48 0.32 3.3 1.50 0.33 3.3 1.52 0.34 3.4 1.54 0.34 3.5 1.56 0.35 3.5 1.58 0.35 3.6 1.60 0.36 3.7 1.62 0.37 3.7 1.64 0.37 3.8 1.66 0.38 3.9 1.68 0.39 3.9 1.70 0.39 4.0 1.72 0.40 4.1 1.74 0.41 4.1 1.76 0.41 4.2 1.78 0.42 4.3 1.80 0.42 4.3 1.82 0.43 4.4 1.84 0.44 4.5 1.86 0.44 4.5 1.88 0.45 4.6 1.90 0.46 4.6 1.91 0.46 4.7 1.93 0.47 4.8 1.95 0.48 4.8 1.97 0.48 4.9
Ps Ps VOLT (MPa) (kg/cm²) 1.99 0.49 5.0 2.01 0.49 5.0 2.03 0.50 5.1 2.05 0.51 5.2 2.07 0.51 5.2 2.09 0.52 5.3 2.11 0.53 5.4 2.13 0.53 5.4 2.15 0.54 5.5 2.17 0.55 5.6 2.19 0.55 5.6 2.21 0.56 5.7 2.23 0.56 5.8 2.25 0.57 5.8 2.27 0.58 5.9 2.29 0.58 6.0 2.31 0.59 6.0 2.32 0.60 6.1 2.34 0.60 6.1 2.36 0.61 6.2 2.38 0.62 6.3 2.40 0.62 6.3 2.42 0.63 6.4 2.44 0.64 6.5 2.46 0.64 6.5 2.48 0.65 6.6 2.50 0.65 6.7 2.52 0.66 6.7 2.54 0.67 6.8 2.56 0.67 6.9 2.58 0.68 6.9 2.60 0.69 7.0 2.62 0.69 7.1 2.64 0.70 7.1 2.66 0.71 7.2 2.68 0.71 7.3 2.70 0.72 7.3 2.72 0.72 7.4 2.73 0.73 7.4 2.75 0.74 7.5 2.77 0.74 7.6 2.79 0.75 7.6 2.81 0.76 7.7 2.83 0.76 7.8 2.85 0.77 7.8 2.87 0.78 7.9 2.89 0.78 8.0 2.91 0.79 8.0 2.93 0.79 8.1 2.95 0.80 8.2 2.97 0.81 8.2
170
Ps Ps VOLT (MPa) (kg/cm²) 2.99 0.81 8.3 3.01 0.82 8.4 3.03 0.83 8.4 3.05 0.83 8.5 3.07 0.84 8.6 3.09 0.85 8.6 3.11 0.85 8.7 3.13 0.86 8.8 3.15 0.86 8.8 3.16 0.87 8.9 3.18 0.88 8.9 3.20 0.88 9.0 3.22 0.89 9.1 3.24 0.90 9.1 3.26 0.90 9.2 3.28 0.91 9.3 3.30 0.92 9.3 3.32 0.92 9.4 3.34 0.93 9.5 3.36 0.94 9.5 3.38 0.94 9.6 3.40 0.95 9.7 3.42 0.95 9.7 3.44 0.96 9.8 3.46 0.97 9.9 3.48 0.97 9.9 3.50 0.98 10.0 3.52 0.99 10.1 3.54 0.99 10.1 3.56 1.00 10.2 3.57 1.01 10.2 3.59 1.01 10.3 3.61 1.02 10.4 3.63 1.02 10.4 3.65 1.03 10.5 3.67 1.04 10.6 3.69 1.04 10.6 3.71 1.05 10.7 3.73 1.06 10.8 3.75 1.06 10.8 3.77 1.07 10.9 3.79 1.08 11.0 3.81 1.08 11.0 3.83 1.09 11.1 3.85 1.09 11.2 3.89 1.10 11.2 3.89 1.11 11.3 3.91 1.11 11.4 3.93 1.12 11.4 3.95 1.13 11.5 3.97 1.13 11.5
rod at pin side) Ps Ps VOLT (MPa) (kg/cm²) 3.98 1.14 11.6 4.00 1.15 11.7 4.02 1.15 11.7 4.04 1.16 11.8 4.06 1.17 11.9 4.08 1.17 11.9 4.10 1.18 12.0 4.12 1.18 12.1 4.14 1.19 12.1 4.16 1.20 12.2 4.18 1.20 12.3 4.20 1.21 12.3 4.22 1.22 12.4 4.24 1.22 12.5 4.26 1.23 12.5 4.28 1.24 12.6 4.30 1.24 12.7 4.32 1.25 12.7 4.34 1.25 12.8 4.36 1.26 12.9 4.38 1.27 12.9 4.40 1.27 13.0 4.41 1.28 13.0 4.43 1.29 13.1 4.45 1.29 13.2 4.47 1.30 13.2 4.49 1.31 13.3 4.51 1.31 13.4 4.53 1.32 13.4 4.55 1.32 13.5 4.57 1.33 13.6 4.59 1.34 13.6 4.61 1.34 13.7 4.63 1.35 13.8 4.65 1.36 13.8 4.67 1.36 13.9 4.69 1.37 14.0 4.71 1.38 14.0 4.73 1.38 14.1 4.75 1.39 14.2 4.77 1.39 14.2 4.79 1.40 14.3 4.81 1.41 14.3 4.82 1.41 14.4 4.84 1.42 14.5 4.86 1.43 14.5 4.88 1.43 14.6 4.90 1.44 14.7 4.92 1.45 14.7 4.94 1.45 14.8 4.96 1.46 14.9 4.98 1.47 14.9
9-8-2. Flow Selector Unit (FS Unit) Leakage of SVD valve or SVS valve, etc; Positions to be checked and check code when a trouble such as miswiring occurred. Phenomenon which appears as result (Corresponding indoor unit or flow selector unit) Part name
Trouble mode
Operation mode
Correspon ding indoor unit
Clogging
All heating operation All Mainly cooling, part heating operation Heating unit Mainly heating, part cooling operation Heating unit
Leakage
All cooling operation (SV11 ON) All Mainly cooling, part heating operation Cooling unit Mainly cooling, part heating operation Cooling unit All cooling operation (SV11 OFF)
SVD valve
May become Not Not almost normal cooled heated capacity
171 SVS valve
All cooling operation All Mainly cooling, part heating operation Cooling unit Mainly heating, part cooling operation Cooling unit All heating operation
All
Leakage
¡SVD circuit – SVS circuit
¡
¡
¡ ¡
¡ SVD circuit
• Temperature of TCJ and TC1 become high similar to heating. (All heating circuit) • Discharge gas pipe at outdoor unit side of the flow selector unit is rather hot. • Refrigerant circulating sound is not heard from SVS valve, but it is heard from SVD valve.
B
¡ SVS circuit
• Gas pipe at indoor side of the flow selector unit is cold. (Cooling L18 “Flow circuit, Liquid pack) selector unit • Refrigerant circulating sound is not heard from SVD valve, but it is error” heard from SVS valve.
C
¡ SVS circuit
• TCJ is higher than normal indoor unit. • Gas pipe at indoor side of the flow selector unit is not cold. • Refrigerant circulating sound is heard from SVSS valve. P19 “4-way valve reversal • Compared with normal indoor unit, TCJ is low. • Temperature of suction gas pipe at outdoor side of the flow error” selector unit is higher than that of normal flow selector unit. • Refrigerant circulating sound is heard from SVS valve circuit.
¡
l Indoor unit, flow selector unit
• In start time, when exchanging mode from cooling to heating after defrost operation, refrigerant shock sound may be heard.
All All cooling operation (SV11 ON) Mainly cooling, part heating operation Cooling unit Mainly heating, part cooling operation Cooling unit
¡
¡ SVDD circuit
• Refrigerant circulating sound may be heard from SVDD valve circuit. • Suction gas pipe at outdoor unit side of the flow selector unit may be hot.
All heating operation All Mainly cooling, part heating operation Heating unit Mainly heating, part cooling operation Heating unit
¡
¡ SVDD circuit
• Refrigerant circulating sound may be heard from SVDD valve circuit.
Miswiring/ All All cooling operation (SV11 ON) Misinstallation Mainly cooling, part heating operation Cooling unit of coil SVD ↔ SVS Mainly heating, part cooling operation Cooling unit
¡
¡ SVDD circuit
• Refrigerant circulating sound may be heard from SVDD valve circuit. • Suction gas pipe at outdoor unit side of the flow selector unit may be hot.
All heating operation All Mainly cooling, part heating operation Heating unit Mainly heating, part cooling operation Heating unit
¡
l Indoor unit, flow selector unit
• In start time, when exchanging mode from cooling to heating after defrost operation, refrigerant shock sound may be heard.
Leakage
A
• Refrigerant circulating sound is heard from SVD valve circuit. • TCJ is high and SH is little. (Liquid pack)
¡ SVSS circuit
¡
• Compared with normal indoor unit, TCJ is higher. • Suction gas pipe at outdoor side of the flow selector unit is hot. • Refrigerant circulating sound is heard in bypass from SVD valve to SVS valve.
All heating operation All Mainly cooling, part heating operation Heating unit Mainly heating, part cooling operation Heating unit
Clogging
Example of refrigerant flow
¡ SVD circuit
Mainly cooling, part heating operation Heating unit Mainly heating, part cooling operation Heating unit
SVDD valve
Judgment and position to be checked
• TC1 is lower than normal indoor unit. • Temperature of suction gas pipe at indoor side of the flow selector unit is lower than that of normal FS unit.
¡
All All heating operation Mainly cooling, part heating operation Heating unit Mainly heating, part cooling operation Heating unit Clogging
cooling sound Detection of check code ¡ Circulating sound
¡
All
All All cooling operation (SV11 ON) Miswiring/ Misinstallation Mainly cooling, part heating operation Cooling unit Mainly cooling, part heating operation Cooling unit of coil SVD ↔ SVS
l Abnormal
Phenomenon which appears as result (Corresponding indoor unit or flow selector unit) Part name
Trouble mode
Clogging SVSS valve
Leakage
Operation mode
Correspon ding indoor unit
Judgment and position to be checked
lIndoor unit,
• Operation is changed from heating to cooling.
Single heating Simultaneous cooling (Indoor heating) Simultaneous heating (Indoor heating)
¡
lIndoor unit,
• Refrigerant impact sound is heard at defrost time.
Single heating Simultaneous cooling (Indoor heating) Simultaneous heating (Indoor heating)
¡
¡SVSS circuit
Single cooling (SV11 OFF)
172
Incorrect piping Single cooling Discharge pipe ↔ Simultaneous cooling (Indoor cooling) Suction gas pipe Simultaneous heating (Indoor cooling)
Disconnection Signal line Contact error Power supply line Miswiring
cooling sound Detection of check code ¡ Circulating sound
¡
Selector unit
Selector unit
¡
Check valve Discharge–Liquid Capillary clogging Single heating bypass capillary, Simultaneous cooling (Indoor heating) Check valve Simultaneous heating (Indoor heating)
Piping Discharge pipe Liquid pipe Gas pipe
l Abnormal
Single cooling Simultaneous cooling (Indoor cooling) Simultaneous heating (Indoor cooling)
Single cooling (SV11 ON) Simultaneous cooling (Indoor cooling) Simultaneous heating (Indoor cooling)
Check valve leakage
May become Not Not almost normal cooled heated capacity
P15 [Gas leak detection]
¡ ¡
• Refrigerant sound may be heard from SVSS valve circuit. • Temperature of suction gas pipe at outdoor side of the selector unit is higher than that of normal selector unit.
¡Check valve circuit
• Gas short is observed and PD and PS may be lower than those in normal time. • TD and TS may be higher than those in normal time.
• Refrigerant sound may be heard from check valve. • Discharge gas pipe is cold or it may be frozen. • TCJ and TC1 are heated same as heating. (Heating circuit) • Discharge gas pipe at outdoor side of selector unit is fairly heated.
¡
In some cases, phenomena such as above occur.
Example of refrigerant flow
Suction gas pipe
Suction gas pipe
Discharge gas pipe
Discharge gas pipe
Discharge gas pipe
Liquid pipe
Liquid pipe
Liquid pipe
SVS
SVDD
SVD
SVS
SVDD
SVD
SVS
SVDD
SVD
SVSS
SVSS
SVSS
173 PMV
PMV TC1
TC2
TCJ
PMV TC1
TC2
TCJ
TCJ
A • SV11 ON • SVD leakage • SVS ON
TC1
TC2
B • SVD ON • SV11 ON
C • SVS ON
Reference Refrigerant circulating example of flow selector unit when a trouble occurred
Suction gas pipe
CPU
Key switch
Remote controller communication circuit
Indoor unit #1
A
174
Central control X remote controller (Option) Y (In case of AI-NETWORK)
AI-NET communication circuit
Key switch DC5V
Power circuit
B
Power circuit
#2
Secondary battery
A
B
#3
A
B
Max. 8 units are connectable. *1 Indoor control P.C. board (MCC-1402) Remote controller communication circuit
DC20V DC12V
CPU H8/3687
*1 However in a case that the network adaptor is installed when 2 remote controllers are connected, maximum 7 units are connectable.
EEPROM
TA sensor
DC5V
DC5V
Power circuit
CN1
*3
DC5V
Network adaptor (Option) Network Remote adaptor controller P.C. board communication (MCC-1401) circuit
Function setup
CPU CN2
Switch setup
TCI sensor
CPU H8/3039
Driver
Transformer
TC2 sensor
Same as left
Same as left
TCJ sensor
*2
*2
*4 PMV
Float input CPU TMP88CH 47FG (TMP88PH 47FG)
None for Concealed Duct type
*4
Drain pump
Power circuit
Indoor fan motor
Fan motor control circuit
Outside output Start Alarm Ready Thermostat ON COOL HEAT FAN
AC BUS synchronous communication signal input circuit circuit U1 U2 L
N
U1 U2 L
N
DC280V
Power supply L
N U1
U2
U1
U2
Indoor/Outdoor communication
Outdoor unit Power supply 1Ø220-240V, 50Hz
*3 The weekly timer cannot be connected to the simple wired remote controller. *4 Nome for high wall spearate sold parts for under ceiling.
HA
Louver motor
*2 The network adaptor is installed to only one unit.
Outdoor unit
Power supply Outdoor unit
10. CONFIGURATION OF CONTROL CIRCUIT
Display LED
LCD driver
10-1. Indoor Unit
Display LCD Function setup
10-1-1. Indoor Controller Block Diagram
Display LCD
4-way Air Discharge Cassette Type, Concealed Duct Standard Type, Under Ceiling Type, High Wall Type, 1-way Air Discharge Cassette Type (2 Series), Slim Duct Type
Weekly timer
1. Connection of wired remote controller
Wired remote controller (Up to 2 units)
Weekly timer
Display LCD
Display LCD
Display LED
Function setup
CPU
Key switch
Remote controller communication circuit
Indoor unit #1
A
175
(In case of AI-NETWORK)
Key switch DC5V
Power circuit
B
Power circuit
#2
Secondary battery
A
B
#3
A
B
Max. 8 units are connectable. *1 Indoor control P.C. board (MCC-1403) Remote controller communication circuit
DC20V
*1 However in a case that the network adaptor is installed when 2 remote controllers are connected, maximum 7 units are connectable.
EEPROM
DC12V
AI-NET communication circuit
CPU H8/3687
DC5V
TA sensor
DC5V
Power circuit
CN1
*3
DC5V
Network adaptor (Option)
Central control X remote controller (Option) Y
Function setup
CPU CN2
Network Remote adaptor controller P.C. board communication (MCC-1401) circuit
LCD driver
Switch setup
Power circuit
CPU H8/3039
Driver
*2 The network adaptor is installed to only one unit.
TCI sensor
*6
Transformer
TC2 sensor
Same as left
Same as left
TCJ sensor
*2
*2
*5 PMV
*4 Nome for concealed duct, Floor standing cabinet Floor standing concealed
Float input None for Concealed Duct
Louver motor
*4 Drain pump
Fan motor control circuit
*5 Indoor fan motor
Outside output Start Alarm Ready Thermostat ON COOL HEAT FAN
HA
*5 Nome for concealed duct, Floor standing cabinet Floor standing concealed Floor standing
AC BUS synchronous communication signal input circuit circuit U1 U2 L
N
L
N U1
U2
U1
U2
Indoor/Outdoor communication
Outdoor unit Power supply 1Ø220-240V, 50Hz
U1 U2 L
Power supply
Transformer
*3 The weekly timer cannot be connected to the simple wired remote controller.
Outdoor unit
*6 Nome for 1-way discharge cassette YH type.
N
Power supply Outdoor unit
2-way Air Discharge Cassette Type, 1-way Air Discharge Cassette Type (1 Series), Concealed Duct High Static Pressure Type, Floor Standing Cabinet Type, Floor Standing Concealed Type, Floor Standing Type
Wired remote controller (Up to 2 units)
B Wireless remote controller kit Sensor P.C. board
Network Remote adaptor controller P.C. board communication (MCC-1401) circuit
Central control X remote controller (Option) Y (In case of AI-NETWORK)
AI-NET communication circuit
Indoor control P.C. board (MCC-1402) Remote controller communication circuit
DC20V DC12V DC5V
CPU H8/3687
Power circuit TA sensor
DC5V
Power circuit
EEPROM
Switch setup
TCI sensor
CPU H8/3039
Driver
TC2 sensor TCJ sensor *3 Float input
Transformer PMV
Buzzer
Remote controller communication circuit
CPU
Sensor circuit
#2
A
B
#3
A
B
Emergent operation SW Function setup SW
Display LED
Same as left
Same as left
*2
*2
None for Concealed Duct
HA
Louver motor
176
CPU TMP88CH 47FG (TMP88PH 47FG)
None for Concealed Duct type
*3 Drain
pump
Power circuit
Indoor fan motor
Fan motor control circuit
Outside output Start Alarm Ready Thermostat ON COOL HEAT FAN
AC BUS synchronous communication signal input circuit circuit U1 U2 L
N
U1 U2 L
N
DC280V
Power supply L
N U1
U2
U1
U2
Indoor/Outdoor communication
Outdoor unit
Power supply Outdoor unit
Outdoor unit Power supply 1Ø220-240V, 50Hz
Max. 8 units are connectable. *1 *1 However in a case that the network adaptor is installed when 2 wireless remote controller kits are connected, maximum 7 units are connectable. *2 The network adaptor is installed to only *3 Nome for high wall spearate sold parts for under ceiling. one unit.
2. Connection of wireless remote controller kit
A
Network adaptor (Option)
4-way Air Discharge Cassette Type, Concealed Duct Standard Type, Under Ceiling Type, High Wall Type, 1-way Air Discharge Cassette Type (2 Series), Slim Duct Type
Indoor unit #1
A
B
#2
Network adaptor (Option) Network Remote adaptor controller P.C. board communication (MCC-1401) circuit
Central control X remote controller (Option) Y (In case of AI-NETWORK)
AI-NET communication circuit
B
#3
A
B
Indoor control P.C. board (MCC-1403) Remote controller communication circuit
DC20V
EEPROM Wireless remote controller kit
DC12V
CPU H8/3687
DC5V
TA sensor
DC5V
Power circuit
A
Switch setup
Power circuit
TCI sensor *5 TC2 sensor
CPU H8/3039
Driver
TCJ sensor *4
Transformer
Remote controller communication circuit
Sensors
Display section
Same as left
Same as left
*2
*2
Float input
PMV
None for Concealed Duct
Louver motor
177
*3 Drain pump
Fan motor control circuit
*4 Indoor fan motor
Outside output Start Alarm Ready Thermostat ON COOL HEAT FAN
HA AC BUS synchronous communication signal input circuit circuit U1 U2 L
N
Power supply
Transformer L
N U1
U2
U1
U2
Indoor/Outdoor communication
U1 U2 L
Outdoor unit
N
Power supply Outdoor unit
Outdoor unit Power supply 1Ø220-240V, 50Hz
Max. 8 units are connectable. *1 *1 However in a case that the network adaptor is installed when 2 wireless remote controller kits are connected, maximum 7 units are connectable. *2 The network adaptor is installed to only one unit.
*3 Nome for concealed duct, Floor standing cabinet Floor standing concealed *4 Nome for concealed duct, Floor standing cabinet Floor standing concealed Floor standing *5 Nome for 1-way discharge cassette YH type.
2-way Air Discharge Cassette Type, 1-way Air Discharge Cassette Type (1 Series), Concealed Duct High Static Pressure Type, Floor Standing Cabinet Type, Floor Standing Concealed Type, Floor Standing Type
Indoor unit #1
Display LCD
Display LCD
Display LED
LCD driver
Function setup
CPU
Key switch
CPU CN2
Remote controller communication circuit
Indoor unit #1
A
CN1
Key switch DC5V
*3
DC5V
Power circuit
Power circuit
Secondary battery
B Wireless remote controller kit Sensor P.C. board
Network adaptor (Option) Network Remote adaptor controller P.C. board communication (MCC-1401) circuit
178
Central control X remote controller (Option) Y (In case of AI-NETWORK)
AI-NET communication circuit
Indoor control P.C. board (MCC-1402) Remote controller communication circuit
DC20V DC12V DC5V
CPU H8/3687 Switch setup
TCI sensor TC2 sensor TCJ sensor *4 Float input
Transformer PMV
DC5V
Buzzer
CPU
Sensor circuit
#2
A
B
#3
A
B
Emergent operation SW Function setup SW
Display LED
Same as left
Same as left
*2
*2
None for Concealed Duct
HA
Louver motor
CPU TMP88CH 47FG (TMP88PH 47FG)
None for Concealed Duct type
*4
Power circuit
CPU H8/3039
Driver
Remote controller communication circuit
EEPROM
TA sensor
DC5V
Power circuit
Function setup
Drain pump
Power circuit
Indoor fan motor
Fan motor control circuit
Outside output Start Alarm Ready Thermostat ON COOL HEAT FAN
AC BUS synchronous communication signal input circuit circuit U1 U2 L
N
U1 U2 L
N
DC280V
Power supply L
N U1
U2
U1
U2
Indoor/Outdoor communication
Outdoor unit Power supply 1Ø220-240V, 50Hz
Max. 8 units are connectable. *1
Outdoor unit
Power supply Outdoor unit
*1 However in a case that the network adaptor is installed, maximum 7 units are connectable. *2 The network adaptor is installed to only one unit. *3 The weekly timer cannot be connected to the simple wired remote controller. *4 Nome for high wall spearate sold parts for under ceiling.
3. Connection of both remote controller and wireless remote controller kit
Weekly timer
4-way Air Discharge Cassette Type, Concealed Duct Standard Type, Under Ceiling Type, High Wall Type, 1-way Air Discharge Cassette Type (2 Series), Slim Duct Type
Wired remote controller
Weekly timer
Display LCD
Display LCD
Display LED
LCD driver
Function setup
CPU
Key switch
Remote controller communication circuit
Indoor unit #1
A
Function setup
CPU CN2
CN1
Key switch DC5V
*3
DC5V
Power circuit
Power circuit
Secondary battery
B
#2
Network adaptor (Option) Network Remote adaptor controller P.C. board communication (MCC-1401) circuit
179
Central control X remote controller (Option) Y (In case of AI-NETWORK)
AI-NET communication circuit
B
#3
A
B
Indoor control P.C. board (MCC-1403) Remote controller communication circuit
DC20V
EEPROM Wireless remote controller kit
DC12V
CPU H8/3687
DC5V
TA sensor
DC5V
Power circuit
A
Switch setup
Power circuit
TCI sensor *6 TC2 sensor
CPU H8/3039
Driver
TCJ sensor *5 Float input
Transformer PMV
Remote controller communication circuit
Sensors
Display section
Same as left
Same as left
*2
*2
None for Concealed Duct
Louver motor
*4 Drain pump
Fan motor control circuit
*5 Indoor fan motor
HA
Outside output Start Alarm Ready Thermostat ON COOL HEAT FAN
AC BUS synchronous communication signal input circuit circuit U1 U2 L
L
Max. 8 units are connectable. *1
*2 The network adaptor is installed to only one unit.
N U1 U1
U2 U2
Indoor/Outdoor communication
Outdoor unit Power supply 1Ø220-240V, 50Hz
*3 The weekly timer cannot be connected to the simple wired remote controller.
*4 Nome for concealed duct, Floor standing cabinet Floor standing concealed *5 Nome for concealed duct, Floor standing cabinet Floor standing concealed Floor standing
U1 U2 L
Power supply
Transformer
*1 However in a case that the network adaptor is installed, maximum 7 units are connectable.
N
Outdoor unit
N
Power supply Outdoor unit
*6 Nome for 1-way discharge cassette YH type.
2-way Air Discharge Cassette Type, 1-way Air Discharge Cassette Type (1 Series), Concealed Duct High Static Pressure Type, Floor Standing Cabinet Type, Floor Standing Concealed Type, Floor Standing Type
Wired remote controller
EEPROM
DC fan output Power supply
Optional power supply
PMV output
180
Remote controller power supply LED DC fan return
*1 Drain pump output
*1 Float SW
Fan output HA (T10) TA sensor Optional output Flap (Used only for 4-way Air Discharge Cassette Type,Under ceiling type)
TCJ sensor EXCT DISP Used for CHK servicing
Remote controller inter-unit cable TC1 sensor Indoor/Outdoor communication (Also used for communication of the central control system)
TC2 sensor
*1 Indoor/Outdoor communication (Spare)
*1 Nome for under ceiling, high wall
10-1-2. Indoor P.C. Board
Filter/Option error input
MCC-1402 4-way Air Discharge Cassette Type, Concealed Duct Standard Type, Under Ceiling Type, High Wall Type, 1-way Air Discharge Cassette Type (2 Series), Slim Duct Type
Microcomputer operation LED
Indoor/Outdoor communication (Spare) PMV output
Microcomputer operation LED
Indoor/Outdoor communication (Also used for communication of the central control system)
EEPROM
Power transformer (Primary side) (AC200V) *1 Flap
Remote controller power supply LED
HA (T10)
181 Optional output
Remote controller inter-unit wire
Drain pump output Optional power supply
EXCT AC fan output
TA sensor
TCI sensor
Outside error input
TC2 sensor
Filter/Option error input
DISP Used for CHK servicing
TCJ sensor Float SW * Short plug is inserted in Concealed Duct High Static Pressure type, Floor standing cabinet type, Floor standing type, Floor stabding conceded type.
*1 2-way Air discharge cassette, 1-way Air discharge cassette, Floor standing only.
MCC-1403 2-way Air Discharge Cassette Type, 1-way Air Discharge Cassette Type (1 Series), Concealed Duct High Static Pressure Type, Floor Standing Cabinet Type, Floor Standing Concealed Type, Floor Standing Type
Power transformer (Secondary side) (AC11V, 14V, 20V)
Power supply
MCC-1520 2-way Air Discharge Cassette Type, 1-way Air Discharge Cassette Type (1 Series), Concealed Duct High Static Pressure Type, Floor Standing Cabinet Type, Floor Standing Concealed Type, Floor Standing Type
C03
+
CN01 1
C90
IC01
+
CN02
6
+
IGO GND
1
+
+15V
6
MCC-1520-01 COMPONENT SIDE
Power supply trans side (Input)
Control P.C. board side (Output)
10-1-3. Flow Selector Unit P.C. Board MCC-1431-01
182
10-1-4. Optional Connector Specifications of Indoor P.C. Board Function Humidifier output
Fan output
—
Option output
Outside error input
Connector No.
Pin No.
CN66
DC12V
Output
DC12V
Output
ON/OFF input
0V (COM)
Operation output
CN32
CN61
CN60
CN80
Remarks
Specifications
In heating, thermo ON, Fan ON, Humidifier output ON * Humidifier provided, Drain pump ON is set up by CN70 short-circuit or from remote controller. (DN=40) Shipment setup: ON with indoor unit operation and OFF with stop are linked. * Single operation by FAN button on remote controller is set up from remote controller (DN=31) HA ON/OFF input (J01: YES/NO=Pulse (At shipment) / Static input select)
Main prohibition input Operation stop of main remote controller is permitted / prohibited by input. ON during operation (Answerback of HA)
DC12V (COM) Alarm output
ON during alarm output
DC12V (COM) Defrost output
ON when outdoor unit is defrosted
Thermo ON output
ON during Real thermostat ON (Compressor ON)
COOL output
ON when operation mode is cooling system (COOL, DRY, Cool/Heat Auto cooling)
HEAT output
ON when operation mode is heating system (HEAT, Cool/Heat Auto cooling)
Fan output
ON when indoor fan is ON (During use of air cleaner/Interlock cabling)
DC12V (COM)
Generate check code “L30” (for 1 minute continuously) to stop forcedly the operation.
DC12V (COM) Outside error input
—
CN20
—
—
—
—
CN70
—
—
—
CHK operation check
CN71
Check mode input
0V
Display mode input
0V
Exhibition mode enables to communicate by indoor unit and remote controller only. (When power has been turned on.) Timer short (Usual)
Demand input
Indoor unit forced thermostat OFF operation
DISP exhibition mode
EXCT demand
CN72
CN73
0V
183
Used for indoor operation check. (Outdoor does not communicate with remote controller, and outputs specified operation such as indoor fan “H”, drain pump ON, etc.)
10-2. Outdoor unit Positions to be checked on the interface P.C. board (MCC-1429)
CN03 backup CN01 For inter-unit cable between indoor and outdoor units
For outdoor unit cable between outdoor units CN03 Pressure sensor (Ps) Pressure sensor (Pd)
CN01 backup BUS terminal Terminator resistor select SW30
UART communication CN600
RMV CN300,301
Option input/output CN508,509,510, 515,501,512 Jumper select
SV61 CN309
Sensor input TD1 , CN502 TD2 , CN503 TK1 , CN514 TK2 , CN515 TK3 , CN516 TK4 , CN523 TE1 , CN505 TL , CN521 TS1 , CN504 TO , CN507 TS2 , CN522
SW41/42 CN311
SV51 CN310 SV2 CN312
5V GND
SV3A CN324
12V
SV3B CN313
3.3V
SV3C CN314
Connection of power supply transformer CN100
SV11 CN322
Option input/output CN511 High pressure swith1
Dina-doctor connecting terminal CN800
High pressure swith2
SV12 CN319
For transformer power supply CN401,402
Case heater 1 Case heater 2 Accumulator heater For expansion BUS power supply CN325
SV3D SV3E CN323 4-way valve CN317
SW06 to 14
SW01,02,03
Comp. case thermo 2 input CN307 SW04,05,15
7-segment LED
184
Comp. case thermo 1 input CN305
L1, L2, L3, N-phase input CN400
Inverter P.C. board (MCC-1502) [IPDU1, IPDU2]
Compressor output
Power supply input (AC400V)
+12V
GND Input current sensor (T02)
+5V
Communication between I/F and Comp. IPDU
Reactor 2 (IPDU2 only is connected.)
AC230V input
DC330V output (IPDU1 only is connected.) DC330V input
Electrolytic condenser (+, -)
Connection between IPDU1 and 2 Reactor 1 (IPDU1 only is connected.)
185
Power supply P.C. board for fan (MCC-1439)
Communication between I/F and fan IPDU
+12V AC230V input
GND
Judgement +12V terminal 1 – 5 +7V terminal 2 – 5 Communication between fan IPDU
(
)
+7V output
DC330V output (For Comp. IPDU) Electrolytic condenser
CN500 DC330V output for fan IPDU (Judgemant : DC 180–370V)
186
10-2-1. Outdoor Interface P.C. Board Dip switch function exchange setup list Part type
Initial setup at shipment
Exchange contents
SW01 Rotary SW 4bit 16 step Display / Operation switch (1)
For 7-segment display / service operation
[1]
SW02 Rotary SW 4bit 16 step Display / Operation switch (2)
For 7-segment display / service operation
[1]
SW03 Rotary SW 4bit 16 step Display / Operation switch (3)
For 7-segment display / service operation
[1]
SW04 Push SW
For service [Operation/Start]
[Operation/Start] by pushing
—
SW05 Push SW
For service [Stop/End]
[Stop/End] by pushing
SW06 SW 4bit
—
(Based on the following setup)
Bit 1
Backup setup
Bit 2
Bit 4
Bit 3
Bit 2
Bit 1
Bit 3
OFF
OFF
OFF
OFF
Normal
OFF
Bit 4
—
—
OFF
ON
No.1 COMP backup
OFF
—
—
ON
OFF
Bit 1 Power peak-cut control exchange
OFF OFF
No.2 COMP backup OFF: 0 – 100%, ON: Middle – 100%
OFF
Bit 2 Power peak-cut control exchange (Expansion) (For 4-steps exchange)
OFF
Bit 3
—
—
OFF
Bit 4
—
—
OFF
Bit 1 Outdoor address setup exchange
OFF: Auto setup (Normal), ON: Manual setup
OFF
Bit 2 Judge indoor capacity over
OFF: YES (Normal), ON: NO
OFF
Bit 3 Correction of installed pipe size
OFF: Normal, ON: Size UP (For outdoor expansion)
OFF
SW07 SW 4bit
n Header unit
SW09 SW 4bit
Bit 4 Judge abnormal No. of connected indoor units OFF: No error judgment, ON: Error
OFF
Bit 1
OFF
—
—
Bit 2 Outdoor fan high-static pressure shift
OFF : Normal, ON: High-static pressure shift
OFF
Bit 3
OFF: Normal, ON : INV frequency upper limit restriction
OFF
OFF: Normal, ON: Fan rpm upper limit restriction
OFF
SW10 SW 4bit Sound reduction control Bit 4
SW11 SW 4bit
SW12 SW 4bit
Bit 2
—
—
OFF
Bit 3
—
—
OFF
Bit 4 Operation when indoor overflow detected
OFF: System stop, ON : System operation continues
OFF
Bit 1 PMV manual operation selected
OFF: PMV1, PMV2 ON : PMV3
OFF
Bit 2
—
—
OFF
Bit 3
—
—
OFF
Bit 4
—
—
OFF
Bit 1
—
—
OFF
Bit 2
—
—
OFF
Bit 3
—
—
OFF
SW13 SW 4bit Bit 4 Line address setup SW14 SW 4bit
Bit 1, 2, 3, 4
SW30 SW 2bit
OFF Line address setup
Refer to item “Address setup procedure”
OFF
Bit 2 Terminator resistor between outdoor units
OFF: No Terminator resistor ON : Exists
ON
CN30 Check connector
Manual full opening setup of PMV
Opened: Normal, Short: Opened fully
Open
CN31 Check connector
Manual full closing setup of PMV
Opened: Normal, Short: Opened fully
Open
CN32 Check connector
Check for assembly line in factory.
Opened: Normal, Short: Check mode
Open
* The outdoor unit connected with indoor/outdoor communication line becomes automatically the master unit. No manual setting is necessary.
187
11. BACKUP OPERATIONS (EMERGENCY OPERATION) When a trouble occurs in an outdoor unit or in one of the compressors in an outdoor unit, the malfunctioning unit or compressor stops and a backup operation (emergency operation) is available through the other functioning outdoor units and compressors. A backup operation can be set up following the procedure below.
11-1. Before Backup Operation The method of the backup operation will differ depending on the type of trouble. Refer to the following table. Trouble contents
Setup procedure
Backup operation method
When a trouble occurs on one of the compressors in the same unit (Note 1)
Compressor backup
To item 2
Outdoor unit backup or outdoor unit backup during cooling season (Note 2)
To item 3 or item 4
When a trouble occurs on the both compressors in the same unit Trouble of the compressor coil (Such as defect of compressor coil) When a trouble occurs on the refrigerating system parts, fan system parts, or electric system parts When a trouble occurs on the temperature sensor or pressure sensor
When a trouble of the compressor coil etc has occurred, deterioration of the oil will be high. Therefore do not perform a backup operation, as other units within the system may be damaged. (Note 2) Only one outdoor unit within a given system can be subjected to the backup procedure. (Note 1)
11-2. Compressor Backup Setup Outline When a trouble occurs on one of the two compressors, follow the procedure below. If it is necessary perform a backup operation on the other normal compressor.
Procedure 1. Turn off the main power supplies to all the units connected to the system. 2. As shown below set up the switch SW06 on the interface P.C. board on the outdoor unit on which the compressor has failed.
SW06 Bit 1
Bit 2
Bit 3
Bit 4
OFF
OFF
OFF
OFF
No.1 compressor (Left side) is defective.
ON
OFF
OFF
OFF
No.2 compressor (Right front side) is defective.
OFF
ON
OFF
OFF
Initial setup at shipment from factory
3. Turn on the main power supplies of all of the units connected to the system. After the backup set up for the outdoor unit in cooling season is complete, check the system operates.
188
11-3. Backup Setup for Outdoor Unit Outline In this model, setup of the backup operation is available in either the header unit or the follower unit in a situation where the outdoor units are defective. In a system in which two or more outdoor units are connected, carry out the backup operation on the outdoor unit if the error modes described below occur. • Compressor error (Rare short error or when one compressor cannot operate, etc.) • Pressure sensor (Pd, Ps) / Temperature sensor (TD1, TD2, TS1, TE1, TK1, TK2, TK3, TK4, TL) error Note only one outdoor unit within a given system can be subjected to the backup procedure.
Procedure 1. Turn off the main power supplies to all the units connected to the system.
[Set up procedure for the malfunctioning outdoor unit] (The following work is common to the header unit and follower units in the system.) 2. Turn on both bit 1 and 2 of the SW06 on the interface P.C. board. 3. Fully close the liquid service valve when the outdoor PMV is suspected to be leaking (i.e. when the PMV will not close fully). 4. Turn on the main power supplies of all of the units connected to the system. If the fault is a compressor insulation error, remove the wiring to the compressor before turning the power supply on. After the backup set up for the outdoor unit in cooling season is complete, check the system operates.
Turn on bit 1 and bit 2 of dip SW06.
189
12. OIL LEVEL JUDGMENT DISPLAY The judgment result of the current oil level of the compressor can be confirmed by the switch setup on the interface P.C. board on the outdoor unit. Confirm the result using the following procedure.
1. Operation procedure Interface P.C. board on the outdoor unit which displays oil level judgment
1) Operation starts. 3) Result of oil level judgment is displayed.
2) Set SW01/SW02/SW03 to 1/16/1.
4) After confirmation, return SW01/SW02/SW03 to 1/1/1.
1) Start the operation. 2) Set the rotary switches SW01/02/03 on the interface P.C. board to 1/16/1. 3) The result of the oil level judgement is displayed on the 7-segment display. 7-segment display [oL] [A00] The right 3 digits indicate the judgment result. The judgment results of the oil level in compressor 1 and compressor 2 are displayed. (Example: A ¡ o = ¡ : Oil level result of compressor 1, o : Oil level result of compressor 2
Display example 7-segment display
[oL] [A00] : Oil level is good in compressor 1 and 2. [oL] [A01] : Oil level is good in compressor 1 and short in compressor 2 [oL] [A20] : Oil shortage in compressor 1 and good in compressor 2
Judgment result in compressor 2 Judgment result in compressor 1 For the contents of judgment result, refer to the following table.)
7-segment display oil level results 7-segment display
Judgment result
Contents
0
Appropriate
1 2
Shortage
A
TK1 circuit error
TK1 circuit error is found. If this judgment continues, the system stops for protection.
B
TK2 circuit error
TK2 circuit error is found. If this judgment continues, the system stops for protection.
C
TK3 circuit error
TK3 circuit error is found. If this judgment continues, the system stops for protection.
D
TK4 circuit error
TK4 circuit error is found. If this judgment continues, the system stops for protection.
Oil level inside of the compressor is appropriate. Shortage of oil level in the compressor (Both A1 and A2 indicate shortage.) If this judgment continues, the system stops for protection.
4) After confirmation, return SW01/SW02/SW03 to (1/1/1).
190
13. REFRIGERANT RECOVERY WHEN REPLACING THE COMPRESSOR 13-1. Refrigerant Recovery in the Malfunctioning Outdoor Unit A pump-down function is available in this system. For multiple outdoor unit systems, execute pump-down by using the normal outdoor units and the refrigerant can be recovered from the outdoor unit, which is to be repaired.
13-1-1. Before Refrigerant Recovery Operation Pay attention to the following items during pump-down operation. 1. The refrigerant recovery rate changes with the outside temperature in the pump-down operation. When the pump-down operation has finished, recover the remaining gas using a recovery device and measure the amount of recovered refrigerant. 2. Executing the pump-down operation when heating the accumulator of the malfunctioning outdoor unit improves refrigerant recovery rate. 3. While both outdoor PMVs are closed the refrigerant in the heat exchanger cannot be recovered. If executing brazing after pump-down operation, recover the refrigerant in the heat exchanger before starting.
13-1-2. Refrigerant Recovery Procedure (If no backup operation for the outdoor unit has been implemented) Procedure Turn on the power supply to the system, and ensure system operation is stopped. If the fault is an insulation error in the compressor, remove the wiring to the compressor before turning on the power supply.
[Set up the malfunctioning outdoor unit as follows] 1. Using a charge hose, connect the check joint of the liquid pipe and the check joint at the low pressure side, then purge the air in the hose (to recover refrigerant in the heat exchanger and the liquid tank). 2. Fully close the service valve of the liquid pipe of the malfunctioning outdoor unit. Keep service valves of the gas pipe and the balance pipe open. 3. If it is thought that the oil has deteriorated due to a faulty compressor, take off the SV3A valve connector of the malfunctioning outdoor unit, so that the oil does not flow in the other outdoor units. 4. Set the rotary switches SW01/02/03 to 2/11/1 on the interface P.C. board of the malfunctioning outdoor unit, [rd] [ ] is displayed on the 7-segment display. 5. Press SW04 for 5 seconds or more, [rd][ FF] is displayed on 7-segment display and then pump down starts. ∗ When interrupting the operation, turn off the power supplies to all of the outdoor units or push SW05 on the interface P.C. board. Malfunctioning outdoor unit 3 If oil deteriorates due to a faulty compressor, remove SV3A connector.
2 Close fully service valve at liquid side. (Keep gas and balance side opened.)
4 Set rotary SW01/02/03 to 2/11/1. [rd] [ ] are displayed. ¯ Push the push SW04 for 5 seconds or more. 5 [rd] [ FF] are displayed.
P.C. board of the malfunctioning outdoor unit
Operation during pump down operation Outdoor unit Outdoor unit with trouble Other outdoor units
1 Connected with check joint of the liquid pipe and check joint at low pressure side by a charge hose and purge.
Operation contents Compressor stops. Outdoor fan ON PMV1 and PMV2 open. SV3A/3B/3C/3D/3E ON Operates in test COOL operation
191
6. Fully close the service valve in the gas pipe of the malfunctioning outdoor unit approximately 10 minutes after the system has started. 7. Push SW04 of the malfunctioning outdoor unit, to display the pressure data (MPa). For each successive push of SW04, the data display changes as shown in the example below.
Display Example [rd] [ 11] Initial display
[Pd] [1.20] High pressure
[Ps] [1.20] Low pressure
[Select an outdoor unit for pressure adjustment as follows] 8. When operating the pump down mode, the outdoor unit which has the lowest unit number is selected as the outdoor unit for the pressure adjustment. Unit No. When SW01/02/03 are set to 1/1/1, the number displayed on the 7-segment display indicates the unit number ([U#][---]: # indicates the unit number)
[Set up all other outdoor units as follows] 9. Fully close the service valves of all the other outdoor unit balance pipes. Only keep the service valves of the balance pipes of the unit in which the pressure adjustment will be made and the malfunctioning unit fully open.
[Setup for outdoor unit for adjustment of pressure] 10. Set up the rotary SW01/02/03 to 1/2/2 on the interface P.C. board of the outdoor unit in which the pressure adjustment will be made. 11. The low pressure (Ps) data is displayed on the 7-segment display. Slowly close the service valve of the gas pipe and adjust so that a pressure of 0.12 MPa is displayed. 12. When the low pressure (Ps) of the malfunctioning outdoor unit is almost the same as that of the unit in which the pressure adjustment has been made, fully close the service valve of the gas pipe in the unit which the pressure adjustment was made.
[Set up the malfunctioning outdoor unit as follows] 13. When the pressure of the malfunctioning outdoor unit is below 0.1 MPa, fully close the service valve of the balance pipe and push SW05 on the interface P.C. board to finish the pump down operation. 14. Turn off the power supplies to all of the outdoor units and use a refrigerant recovery device to recover the remaining refrigerant in the outdoor unit, in which the pump down operation has been completed. Be sure to measure the recovered refrigerant, as the same amount of refrigerant will be required to be recharged after the repair. 9 Fully close the balance pipes of the outdoor units except the unit for pressure adjustment and unit with the malfunction.
6 Fully close the service valve of the gas pipe approx. 10 minutes after the system has started. Malfunctioning outdoor unit 7 The low pressure is displayed by pushing SW04. [Ps] [###]
13 When low pressure of the malfunctioning outdoor unit is below 0.10 MPa, fully close the service valve of the balance pipe.
8 The lowest number outdoor unit is selected as the outdoor unit for pressure adjustment. 10 The low pressure is displayed by setting SW01/02/03 to 1/2/2. [Ps] [###]
11 Close service valve of the gas pipe gradually while checking the low pressure, and then adjust the pressure to 0.12 MPa. 12 When low pressure of the malfunctioning outdoor unit and low pressure of the outdoor unit for pressure adjustment becomes almost same, fully close the service valve of gas pipe on the outdoor unit for pressure adjustment
14 Turn off the power of all the outdoor units. Using a recovery device, reclaim the remaining refrigerant in the outdoor unit in which pump-down operation has finished and measure the amount.
Return all rotary switches SW01/02/03 to 1/1/1.
192
(Refrigerant recovery procedure (backup)) If the power of the malfunctioning unit cannot be turned on, the PMV cannot be opened, therefore the amount of recovered refrigerant decreases compared with the usual pump down operation. Using a refrigerant recovery device, recover the remaining gas in the unit and measure the recovered refrigerant, as the same amount of refrigerant will be required to be recharged after the repair.
Procedure [Set up the malfunctioning outdoor unit as follows] 1. Using a gauge manifold, connect the check joint of the liquid pipe and the low pressure side, and then purge air in the hose (to recover refrigerant in the heat exchanger and the liquid tank). 2. Fully close the service valve of the liquid pipe in the malfunctioning outdoor unit (keep the service valves of the gas pipe and the balance pipe open).
[Set up the unit selected as the header unit as follows] 3. Set up the rotary SW01/02/03 to 2/5/1 on the interface P.C. board of the selected header outdoor unit, [C.] [ ] is displayed on 7-segment display. 4. Push SW04 for 5 seconds or more, the system operates in the test cooling operation when [C.] [ C] is displayed on the 7-segment display. Set up the rotary SW01/02/03 to 1/2/2 on the interface P.C. board of the selected header outdoor unit to display the low pressure data (MPa) on the 7-segment display. 5. Push the SW04 for 2 seconds, the low pressure (MPa) is displayed on 7-segment.
1 Connect check joint of the liquid pipe and low pressure side by the gauge manifold, and then purge air inside of the hose.
Header unit with trouble
Unit selected as the header unit
2 Close fully service valve of the liquid pipe. (Keep gas valve of pipe and balance pipe opened.) Interface P.C. board 4 Set rotary SW01/02/03 to 2/5/1. [C. ] [ ] are displayed.
¯
Push SW04 for 5 seconds or more. 5 [C. ] [ –C] are displayed (Test cooling operation starts.)
® ®
®
¯ ® ® ®
6 Low pressure (MPa) is displayed by pushing the push SW04. Pd Ps Td1 Td2 TS TE C—C
6. Fully close the service valve of the gas pipe on the malfunctioning outdoor unit approximately 10 minutes after the system has started.
[Select an outdoor unit for pressure adjustment as follows] 7. Select the header unit as the unit for pressure adjustment.
[Set up all other outdoor units as follows] 8. Fully close the service valves of the other outdoor unit balance pipes. Only keep the service valves of the balance pipes of the header unit and the malfunctioning unit fully open.
193
[Setup for header unit] 9. The low pressure (Ps) data is displayed on the 7-segment display. Slowly close the service valve of the gas pipe and adjust so that a pressure of 0.12 MPa is displayed. 10. When the manifold gauge pressure of the malfunctioning outdoor unit is almost the same as that of the header unit in which the pressure adjustment has been made, fully close the service valve of the gas pipe in the header unit.
[Set up the malfunctioning outdoor unit as follows] 11. When the manifold gauge pressure of the malfunctioning outdoor unit becomes below 0.1 MPa, fully close the packed valve of the balance pipe and then push SW05 on the interface P.C. board to finish the pump down operation. 12. Turn off the power supplies of all of the outdoor units, and use a refrigerant recovery device to recover the remaining refrigerant in the outdoor unit, in which the pump down operation has been completed. Be sure to measure the recovered refrigerant, as the same amount of refrigerant will be required to be recharged after the repair.
8 Fully close the balance pipes of the outdoor units other than the master unit and the malfunctioning unit.
6 Fully close the service valve of the gas pipe approx. 10 minutes after the system has started. Outdoor unit with trouble
7 The header unit is selected as the outdoor unit for pressure adjustment.
11 When the low pressure of the malfunctioning outdoor unit is below 0.10 MPa, fully close the service valve of the balance pipe. Push the switch SW05 to finish the pump-down operation. 10 Turn off the main power supplies of all the outdoor units. Using a recovery device, recover the remaining refrigerant in the outdoor unit in which pump-down operation has finished and measure the amount.
Return all SW01/02/03 of the header unit to (1/1/1) to complete the work.
194
9 Close service valve of the gas pipe while checking the low pressure, and then adjust the pressure to 0.12 MPa. 12 When the pressure of the malfunctioning outdoor unit (manifold gauge) and pressure of the header unit become almost same, close valve of the gas pipe fully.
13-2. How to Operate the System During Repair of the Malfunctioning Outdoor Unit Procedure 1. Follow the aforementioned “13-1. Refrigerant Recovery in the Malfunctioning Outdoor Unit”. 2. Recover the refrigerant in the system by using a recovery device. The refrigerant amount to be recovered is determined based upon the capacity of the malfunctioning outdoor unit (see the following table). Example) In a case of backup for 10 hp-outdoor unit in 30 hp system: in the original system hp (30 hp system) = 37.5 kg Refrigerant amount in system hp (20 hp system) after backup = 28.0 kg Refrigerant amount to be recovered = 37.5 – 28.0 = 9.5 kg 3. For the unit which the refrigerant has been recovered, execute “Outdoor Unit Backup Setup” of another section. System HP
Combination of outdoor units
Refrigerant amount (kg)
8
8
13.5
10
10
14.0
12
12
14.5
16
8
8
21.5
18
10
8
23.0
20
10
10
25.0
24
8
8
8
30.0
26
10
8
8
31.5
28
10
10
8
33.0
30
10
10
10
34.5
195
13-3. Process after Repair After completion of the repair work, perform vacuuming of the outdoor unit using the following procedure.
Procedure 1. Short CN30 on the interface P.C. board on the outdoor unit for which the repair work has been completed, to open the PMV fully. (Confirm that Bit 1 of SW12 is OFF.) Note) The PMV opening by using short CN30 returns the PMV to fully closed after 2 minutes. To continue to fully open status, turn off the power supply of the outdoor unit within 2 minutes after using short CN30. 2. Be sure to perform vacuuming from the following three check joints. (Liquid pipe, discharge pipe, and suction pipe)
Propeller fan
FM Fan motor Sensor (TE1) Strainer
(Right side)
Pulse motor valve
(Left side)
Solenoid valve (SV12) (PMV2)
Main heat exchanger
Strainer Strainer
Check valve
Sub heat exchanger (Right side) Sub heat exchanger (Left side)
(PMV3)
4-Way valve
Check valve Solenoid valve (SV11)
Solenoid valve (SV5)
Check High-pressure valve sensor Solenoid Capillary Check joint tube valve (SV6) Capillary tube Strainer
Sensor (TL)
Solenoid valve (SV3D)
Solenoid valve (SV2)
Check valve
Compressor 1 (Inverter)
Capillary tube
Capillary tube
Solenoid valve (SV3E)
Check valve
Solenoid valve (SV3C)
Sensor (TK3)
Strainer Strainer Check valve
Check valve
Capillary tube
Capillary tube
Sensor (TK1)
Strainer
Solenoid valve (SV42) Highpressure switch Sensor (TD2)
Sensor (TK2) Oil tank
Sensor (TK4)
Capillary tube
Capillary tube
Strainer
Solenoid valve (SV3A) Strainer
Check valve
Solenoid valve (SV3B) Check valve
Service valve of balance pipe
Service valve at liquid side
Service valve at discharge gas side
Check joint
Strainer
Highpressure switch Sensor (TD1)
Check joint
LowSensor pressure (TS1) sensor Sensor (TS2)
Oil separator
Capillary tube Solenoid valve (SV41)
Liquid tank
Capillary tube
Compressor 2 (Inverter)
(PMV1)
Sensor (TO)
Main heat exchanger
Service valve at suction gas side
196
Accumulator
14. LEAKAGE/CLOGGING OF OIL-EQUALIZATION CIRCUIT Check code list for leakage, clogging of outdoor refrigerant circuit and oil circuit parts Trouble by clogging Position with trouble (See next page.)
Unit issuing check code
Outdoor PMV
A
Corresponding unit
High-pressure protective operation Low-pressure protective operation Discharge temp. error
Check valve of main discharge pipe collective section
B
Corresponding unit
High-pressure protective operation High-pressure SW system error
P20 Abnormal high-pressure up P04-XX
Check valve of discharge pipe
C
Corresponding unit
High-pressure SW system error
P04-XX Abnormal high-pressure up
Check valve of oil-equalization circuit Capillary Strainer
D
Corresponding unit
Oil level detective circuit error Oil level down error
H16-XX Oil-equalization circuit error or H07 oil-shortage judgment
SV3A valve
E
Other connected unit
Oil level down error
H07
Excessive oil amount
SV3B valve
F
Corresponding unit
Oil level down error
H07
Shortage of oil amount
SV3C valve
G
Other connected unit
Oil level down error
H07
Excessive oil amount
SV3D valve SV3D valve circuit capillary Strainer
H
Corresponding unit
Oil level down error
H07
Shortage of oil amount
SV3E valve
I
Corresponding unit
Oil level detective circuit error Oil level down error
Oil return capillary
J
Corresponding unit
Oil level down error
SV3C bypass capillary
K
Corresponding unit
Oil level detective circuit error
Position with trouble (See next page.)
Unit issuing check code
Outdoor PMV
A
Corresponding unit
Outdoor liquid back error Oil level down error
Check valve of main discharge pipe collective section
B
Corresponding unit
Oil level down error Compressor breakdown Compressor error (Lock)
H07 Refrigerant stagnation H01-XX H02-XX
Check valve of discharge pipe
C
Corresponding unit
Oil level down error Compressor breakdown Compressor error (Lock)
H07 Refrigerant stagnation H01-XX H02-XX
Check valve of oil-equalization circuit
D
Corresponding unit
Oil level down error
H07
Excessive oil amount (Leaked side) Shortage of oil amount (Normal side)
SV3A valve
E
Corresponding unit
Oil level down error
H07
Shortage of oil amount
SV3C valve
G
Corresponding unit
Oil level down error
H07
Judgment of oil shortage
Part name
Phenomena (Corresponding unit)
Check code to be detected P20 H06 P03 P17
H16-04 H07
H07 H16-03
High-pressure up Low-pressure down Discharge temp. up
Oil-equalization circuit error Judgment of shortage Shortage of oil amount Shortage of oil amount Oil-equalization circuit error
Trouble by leakage Part name
Phenomena (Corresponding unit)
Check code to be detected
NOTE) XX: Error on sub-code
197
P13 H07
Refrigerant stagnation
Propeller fan
FM Sensor (TE1) Strainer
Fan motor
(Right side) Sensor (TO)
Main heat exchanger
Pulse motor valve (Left side) Solenoid valve (SV12)
Main heat exchanger
(PMV2) Strainer
A Strainer
Check valve
Auxiliary heat exchanger (Right side) Auxiliary heat exchanger (Left side)
(PMV3)
4-Way valve
Check valve Solenoid valve (SV11)
Solenoid valve (SV5)
High-pressure sensor
H
Solenoid Capillary Check joint tube valve (SV6) Capillary tube Strainer
Sensor (TL)
Solenoid valve (SV3D)
K
Highpressure switch Sensor (TD1)
I
Check valve
Solenoid valve (SV2)
Solenoid valve (SV3E)
Check valve
Solenoid valve (SV3C)
Sensor (TK3)
Check valve
Check valve
Capillary tube
Capillary tube
Strainer
F
Highpressure switch Sensor (TD2)
Capillary tube
Solenoid valve (SV3A)
Check valve
Solenoid valve (SV3B) Check valve
Service valve at liquid side
Service valve at discharge gas side
Service valve at suction gas side
198
Accumulator
D
J
Sensor (TK4)
Strainer
Service valve of balance pipe
C
G
Solenoid valve (SV42)
Sensor (TK2) Oil tank
Capillary tube
Strainer
Check joint
Capillary tube
Strainer Strainer
Sensor (TK1)
E
LowSensor pressure (TS1) sensor Sensor (TS2)
Oil separator
Capillary tube
Compressor 1 (Inverter)
Check joint
Check valve
B
Strainer
Capillary tube Solenoid valve (SV41)
Liquid tank
Capillary tube
Compressor 2 (Inverter)
(PMV1)
15. REPLACING COMPRESSOR 15-1. Compressor Replacing Procedure (Outline) WARNING Never recover the refrigerant into outdoor unit. Be sure to use a refrigerant recovery device for refrigerant recovery for reinstallation or repair work. Recovery into the outdoor unit is unavailable; otherwise a serious accident such as rupture or ingury could occur.
START
NOTE) Full opening operation of PMV by CN30 short-circuiting rwill return to fully closed after 2 minutes have passed. To continue full-opening status, turn off power to the outdoor unit within 2 minutes.
Recover refrigerant from outdoor unit, using a suitable device.
Turn off power to the troubled outdoor unit.
Remove the troubled compressor.
Measure oil amount in the troubled compressor.
(
Check oil color of the troubled compressor. ASTM: Is 4 or more? Judge the oil status based on the oil color, and then decide to exchange the troubled compressor only or both compressors.
NO
)
Exchange the malfunctioning compressor only.
YES Replace both the malfunctioning compressor and the normal compressor.
Measure the oil amount in the normal compressor.
Adjust oil amount based upon the measured oil amount.
Install two compressors.
Check for leakage in the malfunctioning outdoor unit.
Vacuum the malfunctioning outdoor unit.
* This flowchart is the standard for replacing compressors. Each case must be considered on individual circumstances. Replace the compressors based on the following conditions of judgement. 1. Oil of 1900 cc is charged in a compressor for service. 2. The amount of oil is 3800 cc in an outdoor unit at shipment. 3. When a compressor is removed, it usually contains 800 to 1400 cc of oil. Oil separator usually holds 0 to 1000 cc of oil.
Charge the refrigerant.
END
199
15-2. Replacing Compressor Exchanging a compressor When changing the compressor, extract oil from the defective compressor and based on the quality of the oil, make the decision of whether to change one or both compressors. If oil colour ASTM is 4.0 or more, both compressors should be replaced.
CAUTION The compressor can weigh in excess of 20kg. One person should not attempt to lift it alone.
M5 screws (2 positions)
Removal of defective compressor • • • •
Turn off the power supply to the defective unit. Remove the front panel. (M5 × 7) Remove the cover on the electric parts box. (M4 × 2) Remove the screws (M5 × 2) that fix the electric parts box to the outdoor unit. • Remove the tabs for temporary hooking the lower part of the electric parts box. Note) Due to the center of gravity of the electrical box, pay careful attention as the box may fall out.
Claw for temporary hooking
• Remove the tabs from the upper part of the electric parts box and move it to the valve side. Note) The electrical parts box may become unstable. If it does, disconnect all cables and completely remove the electrical parts box. • • • •
Remove the lower duct. (M4 × 4) Remove the sound-insulation mat. Remove the crank case heater. Remove the terminal cover of the compressor, the wiring to the compressor and the case thermostat unit. Note) Remove the cables from the compressor side only.
Hooks
WARNING Be aware that if oil is present when brazing a fire could occur.
Ensure the cable ends are insulated with electrical tape. • Remove the discharge pipe, suction pipe, and oil-equation pipe. • Remove the hexagonal bolts fixing the compressor. (One side of hexagon: 13mm × 2 pcs. a compressor) Note) Only two hexagonal bolts are provided per compressor. • Remove the compressor.
Measurement of the quantity of oil in the defective compressor • Place the defective compressor on a scale, and use the weight to calculate the oil quantity. Oil amount in the defective compressor: A [cc] = (Removed compressor mass (kg) –23.5) × 1042 (Specific gravity of oil: 1042 cc/kg) Note)
Positions to be removed (3 positions) (In case of right side) * Left side is same as right side
• When compressor holds no oil, mass is 23.5 kg.
Lower duct
Compressor/ Sound-insulation mat
200
M4 screws (4 positions)
Color check of oil in the defective compressor • Lay the defective compressor down, extract a little oil from the oil-equalization pipe and then check the oil colour based on the oil colour sample. • Determine the number of compressors to replace based on the oil colour: • ASTM below 4: Replace the defective compressor • ASTM above 4: Replace both compressors
Compressor
Oil-equation pipe
When replacing only the defective compressor Adjustment of oil amount in the service compressor (Oil amount 1900cc at shipment) • Adjust the oil amount in the service compressor based on the amount of oil found in the defective compressor by following instructions below. 1. If the amount of oil in the defective compressor is 0 < A < 1000 1) Adjust the amount of oil in the service compressor to 1000 cc. Lay the service compressor down, and extract 900 cc of oil from the oil-equalization pipe. Note) Do not extract more than 900 cc as a compressor fault may be caused. • If the amount of oil in the defective compressor is below 500 cc, a fault in the oil-equalization circuit is possible. Check the compressor using “15-3. Procedure to Identify the Cause of Compressor Oil Shortage”. 2. If the amount of oil in the defective compressor is 1000 < A < 1900 1) Adjust the amount of oil in the service compressor to A cc. Lay the service compressor down and extract (1900 - A) cc of oil from the oil-equalization pipe. 3. If the amount of oil in the defective compressor is 1900 < A 1) Adjust the amount of oil in the service compressor to A cc. Insert a hose into the discharge pipe or oil equation pipe of the service compressor and then add (A 1900) cc of oil using a funnel.
Compressor
201
When replacing both the defective and normal compressors Removal of normal compressor • Remove the normal compressor in the same way as the defective compressor. Note) • Be sure to apply insulation to the removed cable terminals with insulating tape, etc.
WARNING Be aware that if oil is present when brazing, a fire eruption could occur.
Measurement of oil amount in the normal compressor • As with measurement of oil amount in the defective compressor, place the defective compressor on a scale, and use the weight to calculate the oil quantity. Oil amount of the normal compressor: B [cc] = (Removed compressor mass (kg) –23.5) × 1042 (Specific gravity of oil: 1042 [cc/kg]) Note) • When the compressor holds no oil, the compressor mass is 23.5kg.
Adjustment of oil amount in the service compressor • Adjust the oil amount in the service compressors based on the amount of oil found in the defective compressor (A cc) and normal compressor (B cc) by following instructions below. 1. If the total amount oil in both the compressors is 0 < (A + B) < 2000 1) Adjust the amount of oil in the two service compressors to 1000 cc each. Lay the two service compressors down, and extract 900 cc of oil from each of the oil-equalization pipes. • If the amount of oil in the defective compressor is below 500 cc, a fault in the oil-equalization circuit is possible. Check the compressor using “15-3. Procedure to Identify the Cause of Compressor Oil Shortage”. 2. If the total amount of oil in both the compressors is 2000 < (A + B) < 3800 1) Adjust oil amount in the two service compressors to A + B [cc] each. 2 • Lay the two service compressors down and extract 3800 – (A + B) [cc] of oil from each oil-equalization pipe. 2 3. If the total amount of oil in both the compressors is: 3800 < A 1) Adjust the amount of oil in both the service compressors to A + B [cc] each. 2 (Insert a hose into the discharge pipe or oil equation pipe of the service compressor and then add A + B – 1900 [cc] of oil using a funnel.) 2
Compressor
202
Installation of compressor • Install the compressor in the reverse procedure of removal. • When removing the compressor, the terminals may become loose. If this happens crimp them with pliers and then check there are no looseness. Note) • Only two hexagonal bolts are provided to fix the compressor. • The tightening torque of the hexagonal bolt to fix the compressor is 200kg/cm. • If oil has been extracted from the accumulator, braze the cutoff pipe after pinching.
Vacuuming In case of single outdoor system • Connect vacuum pump to the valve charge ports on the liquid, gas pipes and the check joint on the highpressure side and then vacuum. • Vacuum until the vacuum low-pressure gauge indicates 1 (mmHg). Note) • Before vacuuming, open PMV1, 2 fully. Vacuuming of the outdoor heat exchanger will not occur if PMV 1 and 2 are closed.
In case of multiple outdoor unit systems • In the case of conducting the refrigerant recovery at replacing the compressor, perform vacuuming as “13-3. Process after Repair ”.
Full opening of PMV1, PMV2 • • • •
Turn on the power to the outdoor unit. Confirm that Bit 1 on SW12 is OFF. Short CN30 on I/F P.C. board on the outdoor unit. Turn off the power to the outdoor unit within 2 minutes of short-circuiting.
Refrigerant charging • Add the same amount of refrigerant as the remaining refrigerant from charge port of the liquid service valve.
203
15-3. Procedure to Identify the Cause of Compressor Oil Shortage
Is there any disconnection, mis-cabling, or incorrect installation of sensors on the unit of which the compressor has been replaced?
NO
Correct miscabling or incorrect installation of the sensors: TK1: CN514/TK2: CN515 TK3: CN516/TK4: CN523
YES
NO
Are the sensor characteristics of TK1, TK2, TK3 and TK4 sensors correct?
Sensor error
® Exchange
YES
Check oil-equalization circuit in the following procedure once the compressor is removed.
Check items and procedure for the oil-equalization circuit under when the compressor has been removed
Check for refrigerant stagnation in compressor
Check for oil shortage in compressor
Check items
Position
Procedure
Outdoor PMV1, 2, 3 leakage Check valve leakage on main discharge pipe
A B
1) Pressurize with nitrogen through check joint of liquid pipe and check for pressure at check joint of discharge pipe. If pressure of check joint of discharge pipe is high, leakage from outdoor PMV 1,2, 3 and check valve of main discharge pipe are possible. Exchange the parts. 2) If the pressure cannot be found, open outdoor PMV 1,2,3 fully and recheck pressure. If the pressure from the discharge check joint is high, leakage from check valve of main discharge pipe is possible. Exchange the parts.
Check valve leakage of discharge pipe
C
3) If gas leaks from the brazed discharge pipe where compressor has been removed, when pressurized with nitrogen from the check joint of the main discharge pipes, the discharge pipe check valves is possibly leaking. Exchange the parts.
Check valve leakage of oil-equalization circuit
D
4) If gas leaks from the brazed oil-equalization pipe where compressor has been removed, when pressurized with nitrogen from the check joint of the discharge pipe, the check valve of oil-equalization circuit is a possibly leaking. Exchange the parts.
SV3A valve leakage SV3B valve clogging
E F
5) Pressurize with nitrogen with the check joint on the discharge pipe then open SV3B valve manually. If gas leaks from the brazed suction pipe where the compressor should be, there may be a leak in SV3A valve. Exchange the parts.
SV3E valve clogging. Clogging of oil-return capillary
G H
6) Open SV3E valve manually while pressurizing with nitrogen using the check joint on the discharge pipe. If there is no leakage at the brazed suction pipe where the compressor was removed, the SV3E valve or oil return capillary may be clogged. Exchange the parts.
SV3D valve capillary clogging. Clogging of oil-return capillary
I H
7) Open SV3E valve manually while pressurizing with nitrogen from the check joint of the discharge pipe. If there is no leakage at the brazed suction pipe where the compressor was removed, the SV3D valve/capillary or oil return capillary may be clogged. Exchange the parts.
204
Propeller fan
FM Fan motor Sensor (TE1) Strainer
(Right side) Sensor (TO)
Main heat exchanger
Pulse motor valve (Left side) Solenoid valve (SV12) Strainer
A Strainer
Check valve
Auxiliary heat exchanger (Right side) Auxiliary heat exchanger (Left side)
(PMV3)
4-Way valve
Check valve Solenoid valve (SV11)
Solenoid valve (SV5)
Capillary tube Check valve
High-pressure sensor Solenoid Capillary Check joint tube valve (SV6) Capillary tube Strainer
Sensor (TL)
Solenoid valve (SV3D)
Nitrogen pressure
Highpressure switch Sensor (TD1)
Nitrogen pressure
Sensor (TS2) Solenoid valve (SV2)
Oil separator
Check valve
Check valve
Sensor (TK3)
Strainer Strainer Check valve
Check valve
Capillary tube
Capillary tube
Sensor (TK1) Solenoid valve (SV3E)
Strainer
Solenoid valve (SV42) Highpressure switch Sensor (TD2)
Sensor (TK2) Oil tank
D
Solenoid valve (SV3A)
Solenoid valve (SV3B)
Check valve
Check valve Service valve at liquid side
Service valve at discharge gas side
Service valve at suction gas side
H
C
Capillary tube
Strainer
Service valve of balance pipe
Accumulator
Sensor (TK4)
Capillary tube
Strainer
Check joint
Capillary tube
Solenoid valve (SV3C)
Capillary tube
Compressor 1 (Inverter)
Check joint
LowSensor pressure (TS1) sensor
Strainer
Capillary tube Solenoid valve (SV41)
Liquid tank
I
B
Main heat exchanger
(PMV2)
Compressor 2 (Inverter)
(PMV1)
G
E
205
F
H
16. REPLACING PROCEDURE OF PARTS No. 1
Part to be exchanged
Work procedure
Cabinet
Remarks Discharge cabinet
REQUIREMENT Wear protective clothing on your hands as other components may cause and injury etc.
2)
Disassembling 1) Stop the unit operation and turn off the power supply to the unit. Screws (4 corners)
2) Remove the screws on the discharge cabinet. (M5 × 16, 4 pcs.) 3) Remove the screws (Front/rear at lower side) on the cabinet. (M5 × 10, 7 pcs. each)
5 5) Suction cabinet (Front and rear)
4) Remove the screws on the service panel. (M5 × 10, 3 pcs.) 5) Remove the screws (Front/rear sides) on the suction cabinet. (M5 × 10, 4 pcs. each) (M4 × 10, 2 pcs. each) 6) Remove the screws (Right/left sides) on the side panel. (M5 × 10, 4 pcs. each)
3 Lower cabinet tab 3) (Front and rear)
6) Side board (Right and left)
4) Service panel
Reassembly Reassemble the cabinet in the reverse procedure ( 6) → 1) ) on the above “Disassembling Procedure”. However be sure to follow the following points when assembling the discharge cabinet. M Cautions when assembling the discharge cabinet The hooking tabs ∗ (6 positions) located on the inside edge of the discharge cabinet, are to be correctly fitted into the relevant slots on the right/left side panels. Failure to do so may result in unit vibration. 2
Propeller fan motor
* Hooking tab 2 × 3 positions each at longitudinal direction
(
)
REQUIREMENT Wear protective clothing on your hands as other components may cause and injury etc.
Discharge cabinet
2)
Disassembling 1) Stop the unit operation and turn off the power supply to the unit. 2) Remove the screws on the discharge cabinet. (M5 × 16, 4 pcs.)
206
Screws (4 corners)
No. 2
Part to be exchanged Propeller fan motor
Work procedure
Remarks
3) Remove the flange nut fixing on the fan motor and propeller fan. (To tighten the nut, turn it clockwise.)
3) Flange nut
4) Remove the square washer. 5) Remove the propeller fan. NOTE Gently pull the straight upwards.
4) Square washer washer
6) Remove the connectors (3 positions) from IPDU P.C. board on the inverter fan and then pull out the fan motor lead upwards. 7) Remove the fixing screws (4 pcs.) on the fan motor.
6)
7) Scre Screws ws (4 positions) Route of the the fan an motor lead
Remo e the connector Remove and pull it out upwards upwards. upwards.
Detailed photo of connector
Signal line
M Cautions when exchange/reassembling the fan motor
Power line
D-cut face of motor shaft
1)
1) Match the D-cut surface of the motor with the mark on the fan, insert the propeller fan. (If tightening the D-cut surface when out of position, the propeller fan will melt due to friction heat, which will cause the unit to malfunction.) 2) Be sure to attach the square washer. (Failure to do so will result in abnormal sound and vibration being generated.) 3) Tighten the flange nut with 15N•m (153kg•cm). 4) Insert the hooking tabs on the discharge cabinet securely into the tab holes on the cabinet. (Refer to the photo in the previous page; 3 positions each at front and rear sides, total 6 positions)
207
®
Fan mark Positioning to D-cut face of shaft
No. 3
Part to be exchanged Heat exchanger
Work procedure
Remarks
REQUIREMENT
2) Motor base
Wear protective clothing on your hands as other components may cause and injury etc. Before beginning the procedure, ensure the refrigerant has been reclaimed from the outdoor unit, using a suitable refrigerant recovery device.
Heat exchanger exchanger (Left) Heat exchanger exchanger (Right) 3) Motor base bracket
M Disassembling (Example): Heat exchanger (Right)
5) Support
1) Remove the cabinet. 2) Remove the motor base. (M5 × 10, 4 pcs.) 3) Remove the motor base bracket. (M5 × 10, 5 pcs.)
4) Heat exchanger exchanger fixing board
4) Remove the screws on the heat exchanger fixing board. (M5 × 10, 6 pcs.)
6) Waterproof board
5) Remove the screws on the support. (M5 × 10, 3 pcs.) 6) Remove the screws on waterproof board. (M4 × 10, 3 pcs.) 7) Remove the brazing section on the connected pipe (8 positions). 8) Remove the screws on the support at the rear side, and then pull out the heat exchanger. (M5 × 10, 2 pcs.)
7) Brazing section (4 positions at header side)
7) Brazing section (4 positions at distributor side) 8) Rear side
8) Support
Draw it out it backwards. (Draw it out forwards in case of a left side heat exchanger.)
208
No. 4
Part to be exchanged HeInverter assembly M Removal of box
Work procedure
Remarks
REQUIREMENT Wear protective clothing on your hands as other components may cause and injury etc.
3 Screw 3) Scre
1) Stop the unit operation and turn off the power supply to the unit. 2) Remove the inverter cover. (M4 × 10, 2 pcs.)
3 3) Screw Scre 4) Fixing claw cla
3) Remove the fixing screws on the box. (1 pc. each at upper and lower sides.) 4) Lightly push down the fixing tab at the lower side to enable the box to be removed. 5) Remove the hooking tab at the upper side while holding the ceiling board with both hands.
5)
to ard you. Pull out toward you.
Reassembly and cautions 2)
1) Hook the upper tab. 2) Push in the lower part. Be sure to check there is no pinching of the cables at the corners on the rear side. 3) Tighten the fixing screws on the upper and lower sides. (1 pc. each at upper/lower part)
2) When pushing in the lower part, be sure to check that the cable is not be stretched.
209
No. 5
Part to be exchanged Inverter assembly M Removal of P.C. board and electric parts
1. Noise filter P.C. board 2. Interface P.C. board
Remarks
Work procedure
REQUIREMENT Wear protective clothing on your hands as other components may cause and injury etc.
4. IPDU P.C. board for fan 1. Noise filter P.C. boards
2. Interface P.C. board (Control P.C. board)
1) Stop the unit operation and turn off the power supply to the unit. 2) Remove the cables and then the P.C. board from the board edge spacer at the corner.
Exchange of service P.C. board For the interface P.C. board, it is necessary to set up the jumper links, etc for each model. Refer to “Exchange procedure of interface P.C. board”.
3. IPDU P.C. board
3. IPDU P.C. board (For driving of compressor 1) 3. PDU P.C. board (For driving of compressor 2)
1) Stop the unit operation and turn off the power supply to the unit. 2) Remove the heat sink (Radiator plate) fixing screws. ∗ (M4 × 16, 2 pcs.) 3) Remove the cables.
2) Screw
4) Remove the P.C. board from the card edge spacer at the corners. ∗ Heat sink fixing screw, compressor lead cables (U, V, W), etc, M4 screw tightening torque (1.47±0.1N•m)
Exchange of service P.C. board For the IPDU P.C. board, it is necessary to set up the jumper links, etc for each model. Refer to “Exchange procedure of IPDU P.C. board”.
4. IPDU P.C. board for fan
1) Stop the unit operation and turn off the power supply to the unit. 2) Remove the wires. 3) Remove the heat sink (Radiator plate) fixing screws. * (M4 × 8, 4 pcs.) ∗ Tightening torque of screw for heat sink fixing board (1.47 ± 0.1N•m)
210
3) Screw
No. 5
Part to be exchanged Inverter assembly M Removal of P.C. board and electric parts
Remarks
Work procedure
REQUIREMENT Wear protective clothing on your hands as other components may cause and injury etc.
5. Reactor 6. Transformer
1) Stop operation, and then turn the power supply to the unit.
7. Electrolytic capacitor
2) Take off the screws (3 positions) on the terminal block installation board. 3) Take off the fixing screws on each part and then remove the cables. ∗ ∗ Caution when removing the electrolytic capacitor (No.7)
Reactor, transformer and electrolytic condenser are stored at the rear side of the terminal block. 2) Screw
1) Electrolytic capacitors will discharge over time. As the natural discharge by the electlytic capacitor may be unavailable and voltage may remain in some cases due to trouble conditions, be sure to confirm discharge of the capacitor.
2) Screw 2) Screw
Terminal block installation board
2) Use a suitable resistive load (100Ω/40W or equivalent) to discharge the capacitor or plug of the soldering iron, make continuity and discharge between and poles. Recommendation will check the voltage with a DC volt meter. NOTE Do not discharge using a tool (e.g. screwdriver) as the capacitor charge can cause an injury.
5. Reactor (2 pieces)
3) Screw
3) Screw
6. Transformer
7. Electrolytic condenser Plug of soldering iron
211
No. 6
Part to be exchanged Pressure sensor positions of 2-way valve coil
Work procedure
SV3C
Rear side
Remarks
SV3B
SV3A
Oil tank
Liquid tank SV3D SV2 SV6
Accumulator Oil separator
PS sensor
SV41
SV11
Compressor(2)
Compressor(1) SV42
PD sensor SV5 Front side SV12
7
Temperature sensor positions and identification
Front side of air conditioner
Front side
TS2 sensor TS1 sensor(Grasy)
TD1 sensor(Yellow)
Accumulator
Compressor(1)
212
TD2 sensor(Red)
Compressor(2)
No. 7
Part to be exchanged Temperature sensor positions and identification
Work procedure
Remarks
Rear side of air conditioner Accumulator Rear side TK3 sensor(White) TK1 sensor(Black) Accumulator side (Front side)
Oil separator
TK2 sensor(Blue) Rear side TK4 sensor(Green) Liquid tank
8
Attachment/ detachment of pipe fixing rubber
Oil tank
This air conditioner has been designed so that vibration has been reduced to a minium by incorporating in the lower section of the unit, the use of eyeglass rubber fixing brackets and SUS bands. Both of which greatly help to reduce vibration and improve unit reliability.
Used positions of SUS fixing band: Total 5 positions
Û
Ø6.35 Ø15.88 between SV3E valve and suction
Û
Ø8.0 Ø25.4 between SV2 valve and discharge
Û
Ø6.35 Ø15.88 between SV3C valve and discharge pipe
Û
Û
Ø8.0 Ø19.05 between SV42 valve and suction pipe
Ø8.0 Ø19.05 between SV41 valve and suction pipe
213
No. 8
Part to be exchanged Attachment/ detachment of pipe fixing rubber
Work procedure
REQUIREMENT
Remarks
1)
Wear protective clothing on your hands as other components may cause and injury etc.
Disassembling 1) Squeeze the band either side of the clip to release.
Compress the rubber to release the cup.
1)
2) Pushing in the tab side of SUS band the tab comes off from square hole.
Push in the band towards the arrow mark.
Assembly
Align the direction of the slits and then attach to each pipe.
1) Individually fit each rubber bracket to the relevant pipe.
1)
2) For assembly align the tab side of the SUS band to the slit side of the rubber bracket.
1)
3) Attach the rubber band so that there is no gap between the SUS band and the the fixing rubber bracket. Pay special attention no to create a gap at the hair pin of the rubber band. Matching the tabs, the slide them.
4) Squeeze the rubber bracket and band so that the hook part of the band clips into the square hole.
Align the tabs to the slit side of the rubber.
2)
Slide it. Push the band against the rubber to eliminate any gaps.
3)
Slide the square hole side towards the arrow mark.
4)
Push the tab side up against the rubber.
214
No. 9
Part to be exchanged Exchange of accumulator
Work procedure
Remarks
REQUIREMENT Wear protective clothing on your hands as other components may cause and injury etc. Before beginning the procedure, ensure the refrigerant has been reclaimed from the outdoor unit, using a suitable refrigerant recovery device. 1) Remove the lower cabinet (rear side). 2) Remove the fixing screws (M6 × 3 pcs.) from the accumulator leg ⇔ base board. 3) Remove the accumulator fixing board ∗ ⇔ fixing screws on accumulator (M6 × 2 pcs.) ∗ The accumulator fixing board is fixed to the middle partition board. (Take off only the screws, which fix the accumulator unit.) 4) Remove the pipe (brazing part) connected to the SV2 valve. 5) Remove the discharge cabinet fan and motor base. 6) Remove the accumulator cover ⇔ fixing screws (M5 × 4 pcs.) of the middle partition board and then pull it upwards. 7) Using a pipe cutter, cut off the entrance/exit pipe of accumulator at the specified position. (For the cut-off position, refer to the Manual attached to the repair parts.) 6) Accumulator cover
8) Pull the accumulator upwards.
7) Cut pipe at entrance/exit ports.
3) Accumulator fixing board
6)
6) Two screws each at front and rear 8) Middle partition par tition board
4) SV2 valve 3) Two screws
Accumulator 2) Three screws
4) Brazing part with SV2 assembly
215
No. 10
Part to be exchanged
Work procedure
Exchange of 4-way valve
Remarks
REQUIREMENT Wear protective clothing on your hands as other components may cause and injury etc. Before beginning the procedure, ensure the refrigerant has been reclaimed from the outdoor unit, using a suitable refrigerant recovery device. 1) Remove the lower cabinet (Front side). 2) Remove the inverter box according to the item “How to remove the inverter box”. 3) Remove the brazed sections on PMV assembly at 3 positions. (Refer to the figure below.) 4) Remove the brazed sections on the 4-way valve at 4 positions. ∗ When brazing, prepare a shield plate, etc. so that the brazing flames do not burn the wires.
Remove brazed sections at 2 positions on the strainer. Remove brazed sections at 3 positions on the 4-way valve. PMV assembly 4-way valve body
Remove brazed sections at 2 positions under PMV.
Remove brazed sections at 1 position under 4-way valve.
After removal of PMV assembly
Before removal of PMV assembly
216
17. P.C. BOARD 17-1. Indoor Unit 17-1-1. Exchange of P.C. Board for Indoor Service Part code
P.C. board model
Label display on P.C. board
431-6V-207
MMU-AP✻✻ ✻✻1WH series ✻✻ ✻✻ MMU-AP✻✻ ✻✻1YH series MMU-AP ✻✻ ✻✻1SH series ✻✻ MMD-AP✻✻ ✻✻1H series ✻✻ MML-AP✻✻ ✻✻1H series ✻✻ MMU-AP✻✻ ✻✻1BH series ✻✻ MMF-AP✻✻ ✻✻1H series
MCC-1403
03RD M01
431-6V-210
MMD-AP✻✻ ✻✻1BH series ✻✻
MCC-1402
03DD M02
431-6V-269
MMU-AP✻✻ ✻✻1H series ✻✻ ✻✻ MMC-AP✻✻ ✻✻1H series ✻✻ MMK-AP✻✻ ✻✻1H series ✻✻ MMD-AP✻✻ ✻✻1SPH/SH series ✻✻ MMU-AP✻✻ ✻✻2SH series
MCC-1402
03DD M03
Model type
Requirement when exchanging the P.C. board assembly for indoor service The fixed memory (herein EEPROM, IC10) stores the model type and capacity code, which are set upon shipment from the factory. Data set upon installation (i.e. line/indoor/group addresses) are also stored in the EEPROM. Proceed with the exchange of the P.C. board as shown in the procedure below. After exchange, confirm the settings for master/sub, etc. are correct and carry out a test operation.
Exchange procedure
Method 1 Before exchange, it is possible to turn on the power of the indoor unit and read out the setup contents from the wired remote controller.
Readout of EEPROM data: Procedure 1
ò Exchange of P.C. board for service & power ON: Procedure 2
ò Programming the EEPROM data: Procedure 3
ò Power supply reset (All the indoor units connected to the remote controller are reset in case of group operation control)
217
Method 2 Before exchange, it is impossible to read out the setup contents due to EEPROM error. Exchange of P.C. board for service & power ON: Procedure 2
ò
Writing-in of the setup data such as the model name, capacity code, indoor unit address high ceiling setup, connection setup of option, etc to EEPROM based upon customer’s information: Procedure 3
ò
Power supply reset (All the indoor units connected to the remote controller in case of group operation control)
Procedure 1 : Readout setup contents from EEPROM (Contents of EEPROM with setup changed at local site include setup at shipment from the factory are read out.)
1
1. Push SET + CL + TEST buttons simultaneously for 4 seconds or more. (Corresponds to number of the operation diagram of the remote controller in page 218.) ∗ In a group operation control, the firstly displayed unit No. indicates the header indoor unit No. In this case, is displayed in the item code (DN). The fan of the selected indoor unit operates, and also starts swinging in a model with flap.
2
2. Every pushing UNIT , the indoor unit Nos. in the group control are displayed successively. (Corresponds to number of the operation diagram of the remote controller in page 218.) Specify the indoor unit No. to be exchanged. ∗ The fan of the selected indoor unit operates, and also starts swinging in a model with flap. 3. Using temperature setup / buttons, the item code (DN) can be moved up/down one by one. (Corresponds to number of the operation diagram of the remote controller in page 218.) 4. First change the item code (DN) from → . (Setup of filter sign lighting time) In this time, make a note of contents of the displayed setup data. 5. In the next time, change the item code (DN) using / buttons. Make a note of contents of the setup data as same as the above. 6. Then repeat item 5., and make a note of contents of the important setup data as indicated in the attached table (Example). Item code necessary at minimum ∗ The item code (DN) is consisted with to )) . DN Contents DN No. may jump on the way.
3
7. When noting has finished, push TEST button to
6
return to the normal stop status. (Corresponds to number of the operation diagram of the remote controller in page 218.) (It requires approx. 1 minute to operate the remote controller.)
10
Type
11
Indoor unit capacity
12
Line address
13
Indoor address
14
Group address
SET DATA UNIT No.
R.C.
No.
TEMP.
3 5 6 1
FILTER RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
4
UNIT
2 218
Type and capacity of the indoor unit are necessary to set up the revolution frequency of the fan.
Procedure 2 : Exchange of P.C. board for service 1. Exchange P.C. board with a P.C. board for service. In this time, the jumper line (cut) setup or the (short-circuit) connecting connector setup on the previous P.C. board should be reflected on P.C. board for service. (See the blow figures.)
(MCC-1402)
JP1
(MCC-1403)
CN41
CN34
JP001
CN041
CN030 From the left CN112,111,110 When short-circuited plug is mounted to P.C. board before change, re-mount the short-circuited plug as previons.
2. It is necessary to set Indoor unit to be exchanged : Remote controller = 1 : 1 Based upon the system configuration, turn on power of the indoor unit with one of the following items. 1) Single (Individual) operation Turn on power of the indoor units and proceed to Procedure 3. 2) Group operation A) In case that power of the exchanged indoor unit only can be turned on Turn on power of the exchanged indoor unit only and proceed to Procedure 3. B) In case that power of the indoor units cannot be turned on individually (Case 1) a) Remove temporarily the group wire connected to the terminal blocks A and B of the exchanged indoor unit. b) After connecting the remote controller wire only to the removed terminal block, turn on power of the indoor units and proceed to Procedure 3. ∗ When the above methods cannot be used, follow to the two cases below. C) In case that power of the indoor units cannot be turned on individually (Case 2) a) Remove all CN41 connectors of the indoor units in the same group except those of the exchanged indoor unit. b) Turn on power of the indoor units and proceed to Procedure 3. ∗ After Procedure 3 operation has finished, be sure to return the temporarily removed group wire or CN41 connector to the original connection. Indoorunit Indoorunit P.C. board P.C. board
Indoorunit
Service P.C. board of the unit to be changed
(Case 1) A B
A B
A B
Group wire
(Case 2)
Indoorunit Indoorunit P.C. board P.C. board CN 41
A B
Remove CN41 connectors of the indoor units other than the units to be changed in the same group.
A B
Remote controller Indoorunit
Service P.C. board of the unit to be changed
A B
Group wire
219
Remove the group wire of the terminal blocks A and B of the changed indoor unit, and then install the remote controller only.
Remote controller
Procedure 3 : Writing-in of setup contents to EEPROM (The EEPROM contents which are installed on the service P.C. board have been set up at shipment from the factory.)
1
1. Push SET + CL + TEST buttons simultaneously for 4 seconds or more. (Corresponds to number of the operation diagram of the remote controller in page 218.) ( is displayed in the UNIT No box.) In this time, is displayed in the item code (DN). The fan of the indoor unit operates, and also starts swinging in a model with flap. 2. Using temperature setup / buttons, the item code (DN) can be moved one step up 1 or down one by one. (Corresponds to number of the operation diagram of the remote controller in page 218.) 3. First set up the type and capacity code of the indoor unit. (The data at shipment from the factory is written in EEPROM by changing the type and capacity code.) 1) Set to the item code (DN). (As before) 2) Using the timer time / buttons, set up the type. (Corresponds to number of the operation diagram of the remote controller in page 218.) (For example, 0001 indicates 4-way Air Discharge Cassette type.): Refer to the attached table.
3
4
5
3) Push SET button. (OK if display goes on.) (Corresponds to number of the operation diagram of the remote controller in page 218.) 4) Using temperature setup / buttons, set to the item code (DN). 5) Using the timer time / buttons, set up the capacity code. (For example, 0012 indicates 027 type.): Refer to the attached table. 6) Push SET button. (OK if display goes on.) 7) Push TEST button to return to the normal stop status. 4. In the next, the contents such as address setup, which were set up at the local site after installation are written in EEPROM. Execute again the operation in the above item 1.). 5. Using temperature setup / buttons, set to the item code (DN). (Lighting time setup for filter sign) 6. Compare the contents of the setup data which is displayed in this time with contents noted in a memo in Procedure 1 and customer’s information. 1) If data is incorrect, change it using the timer time / buttons so that it matches with contents noted in SET a memo, and then push button. (OK if display goes on.) 2) Do nothing if data is same as those in the memo. / buttons, change the item code (DN). 7. Using temperature setup Check also the contents of the setup data and then change them it to those in the memo. 8. Then repeat operations in items 6. and 7. 9. After setup operation, push TEST button to return to the normal stop status. (Corresponds to number of the operation diagram of the remote controller in page 218.) In a group operation, turn off the power supply once, return the group wires between indoor units and CN41 connectors as before, and then turn on power of all the indoor units. (It requires approx. 1 minute to operate the remote controller.) ∗ The item code (DN) is consisted with to )) . DN No. may jump on the way. Even if pushing SET button after changing the data incorrectly, the data can be returned to one before
6
change by pushing
CL
button before changing the item code (DN). P.C. board (MCC-1402)
P.C. board (MCC-1403)
EPROM (IC10)
EEPROM layout EEPROM (IC10) is attached to IC socket. To remove it, use a pair of tweezers, etc. To attach EEPROM, arrange the direction as shown in the following figures. ∗ In exchanging time, pay attention not to bend the lead wire of IC.
EPROM (IC10)
Align notch directions of IC socket and EEPROM for installation. Notch IC socket
220
Notch
EPROM
Record the contents of the following before exchanging P.C. boards. (Item code list) DN
Item
Memo
Setup at shipment from factory
01
Filter sign lighting time
According to type
02
Dirty condition of filter
0000: Standard
03
Central control address
0099: Undefined
06
Heating inlet temp. shift
0002: +2°C (Floor standing: 0)
0d
Cooling Auto mode existence
0001: No auto mode cooling/heating
0F
Cooling only/Heat pump select
0000: Heat pump
10
Type
According to model type
11
Indoor unit capacity
According to capacity code
12
Line address
0099: Undefined
13
Indoor unit address
0099: Undefined
14
Group address
0099: Undefined
19
Louver type (Air direction adjustment)
According to type
1E
Temp. width between cooling and heating automatic selective control points
0003: 3 deg (Ts ± 1.5)
28
Automatic restart from power failure
0000: None
HA terminal (T10) selection
0000: Normal
Sensor select
0000: Body sensor
5d
High ceiling selection
0000: Standard
60
Timer setup (Wired remote controller)
0000: Possible
(
* Automatic selection by connected outdoor unit
2A 2E 30 31 32 40
Type Item code [10] Setup data
Indoor unit capacity Item code [11] Type
Model abb. name
Setup data
Model
Setup data
Model
0000∗
Invalid
0016
—
0001
007 type
0017
048 type
0002
—
0018
056 type
0003
009 type
0019
—
0000
1-way Air Discharge Cassette
MMU-AP✻✻✻SH
0001∗
4-way Air Discharge Cassette
MMU-AP✻✻✻H
0002
2-way Air Discharge Cassette
MMU-AP✻✻✻WH
0003
1-way Air Discharge Cassette (Compact type)
MMU-AP✻✻✻YH
0004
—
0020
—
0004
Concealed Duct Standard
MMD-AP✻✻✻BH
0005
012 type
0021
072 type
—
0022
—
Slim Duct
MMD-AP✻✻✻SPH MMD-AP✻✻✻SH
0006
0005
0007
015 type
0023
096 type
0006
Concealed Duct High Static Pressure
MMD-AP✻✻✻H
0008
—
0024
—
0007
Under Ceiling
MMC-AP✻✻✻H
0009
018 type
0025
—
0008
High Wall
MMK-AP✻✻✻H
0010
—
0026
—
0011
024 type
0027
—
0009 0010
Floor Standing Cabinet
MML-AP✻✻✻H
0012
027 type
0028
—
0011
Floor Standing Concealed
MML-AP✻✻✻BH
0013
030 type
~
—
0012
(Floor Standing 8, 10HP)
0014
—
0034
—
0013
Floor Standing (Below 6HP)
0015
036 type
MMF-AP✻✻✻H
* The initial setup value of EEPROM installed on the service P.C. board
221
)
17-2. Outdoor Unit 17-2-1. Cautions in Service for Compressor 1. When checking the inverter output, remove the both wires of the compressor as follows.
17-2-2. How to Check Inverter Output 1. Turn off the power supply. 2. Remove the compressor lead from the compressor. (Be sure to remove lead wires of both compressors.) 3. Turn on the power supply and drive the air conditioner in cool or heat mode. In this case, be careful so that a fasten terminal of the compressor lead does not come to contact with other fasten terminal or you don’t touch other parts (Set cabinet). 4. Check the output voltage of the compressor lead at the inverter side. If the result is not accepted by the following criteria, replace IPDU P.C. board. No.
Measuring position
Criteria
1
Between Red and White
360V to 520V
2
Between White and Black
360V to 520V
3
Between Black and Red
360V to 520V
∗ After check of output, sufficiently check there is no distortion on the fasten terminals when reconnecting the compressor lead to the compressor terminals. If any distortion is found, caulk the fasten terminal with pliers, etc. and then connect it.
1. Turn off the power supply. 2. Remove the compressor lead from the compressor. 3. Using a tester, check the winding resistance between each phases of each compressor and resistance of the outdoor cabinet. • Is not grounded? → It is normal if there are 10MΩ or more. • Is not short-circuited between windings? → It is normal if there are 0.1Ω to 0.3Ω. (Use a precise digital tester.)
17-2-3. How to Check Outdoor Fan Motor 1. Turn off the power supply. 2. Remove three fasten terminals (U, V, W) of the fan motor from IPDU P.C. board for the outdoor fan. 3. Turn the fan with hands. If it is not turned, a fan motor error (Lock) is considered. Replace the fan motor with a new one. When it is turned, measure the winding resistance between each phases of the fasten terminal (motor winding) with a tester. It is normal if the winding resistance between phases are 13 to 33Ω. (Use a precise digital tester.) Procedure
Part name Outdoor fan motor
Measure resistance of each winding with a tester. Red
U Position
Resistance
Red-White
13~33Ω 13~33Ω 13~33Ω
Black-Red White-Black White V
Black W
222
(Normal temp.)
17-2-4. How to Check Fan Power Supply P.C. Board and Fan IPDU The fan power supply P.C. board supplies DC power. It supplies DC280V for the fan IPDU, and DC12V and DC7V for the control power supply respectively. If the control power is not supplied, a communication error (Error code [E31]) is out.
1. How to check fan power supply P.C. board (MCC-1439) As shown in the following table, measure the voltage of the check positions with a digital tester. No. 1 2
Check position
Criteria
Between CN500 and
DC260 to DC340V
Between CN500 and
DC12V
Between CN500 and
DC7V
Check item DC280V output Control power voltage
3
2. How to check fan IPDU 1. Check that the lead wires are correctly inserted into 250 fasten terminal of DC280V input and into the communication connector (CN01). 2. After then replace the fan IPDU if an abnormality is recognized.
MCC-1439 Front View
CN503 F500
CN505 RED
10A 250V~
CN504 BLU UART 2
J502 J504 J501
IC501 1
C520
+
R
10
R518
5
L501
T500
6 R519 D505
~
F501 T6.3A 250V~
+ R505
DB500 1
223
3
CN500
1
3
3 CAPA 1
CN502 BLU DC IN/OUT
MCC-1439-05S COMPONENT SIDE
CN500 WHI DC OUT
BLK CN506
C507
+ ~
C531
+
R503
C513
L506
–
C526
C523
6 C521
R511
L500
IC500
C508 RY500
+
C524
+
R513 GO IC503
11
1
3
C522
5
+7V
+
RED CN510
AC IN
C520
J500
6 UART 11
1 J505 J503
1
C501
C509
5
CN503 WHI
R523
5 UNIT 3 1
GND +5V
+12V
17-2-5. Interface Board Replacement Procedure This service board is commonly installed in different models. If the board assembly is to be replaced, check the displayed inspection contents and replace the board with the correct version for the model and follow this procedure.
Replacement steps 1. 2. 3. 4.
Turn off the power supply of the outdoor unit. Remove the connectors, fasteners and screw terminals connected to the interface P.C. board. Remove the interface P.C. board from the six card edge spacers. Disconnect the jumper wires of the service board, as instructed in the table below. The jumper setting differs from the one to be replaced. If the model is not specified, inspection code “L10” is displayed and the equipment will not operate. No. At shipment
Model name Service P.C. board
J09
J10
J11
Yes
Yes
Yes
1
MMY-MAP0802FT8-INV
Disconnect
Disconnect
Leave intact
2
MMY-MAP1002FT8-INV
Leave intact
Disconnect
Leave intact
3
MMY-MAP1202FT8-INV
Disconnect
Leave intact
Leave intact
5. Set dip switch settings of the service board to the switch settings detailed below before replacement. Dip Switch
Setting contents
SW07
Demand setting
SW10
Outdoor fan high static pressure setting, etc.
SW13
System address setting
SW14 SW30
Terminating resistance setting
6. After setting the jumper wires of the service board, install the service board in the outdoor control unit (Confirm that it is securely fixed to the card edge spacers.) 7. Connect the connector and fasten terminals (confirm that they are correctly and securely inserted). 8. If a component part on the board is bent during board replacement, adjust it manually so that it is not in contact with other parts/components. 9. Install the cover then turn on the power supply. Check the operation.
IC02
IC01
Jumper wire replacement place (J09, 10, 11) IC300
IC301
CN314 CN311
224
17-2-6. Comp-IPDU Board Replacement Procedure Manual This service board is commonly installed in different models. If the board assembly is to be replaced, replace it properly in with the correct version for the model and follow this procedure.
Replacement steps 1. 2. 3. 4. 5. 6.
Turn off the power supply to the outdoor unit. Confirm that the capacitor has been fully discharged (confirm that the voltage between CN13 and CN15 is 0 V). Remove the connectors, fasteners and screw terminals connected to the A3-IPDU board. Remove 2 screws that fix the IGBT (Q200) of the Comp-IPDU board to the heat sink. Remove the Comp-IPDU board from the four card edge spacers. Set the dip Switch (SW801) of the Comp-IPDU board, as instructed in the table below. If the model is not specified, inspection “L29” is displayed and the equipment will not operate. SW801
Comp-IPDU No. Bit 1
Bit 2
JAt shipment
ON
ON
No.1
ON
ON
No.2
ON
OFF
7. After setting the dip Switch of the service board, apply silicone grease evenly onto the IGBT and install it in the outdoor control unit (Confirm that it is securely fixed to the card edge spacers). 8. Fix the IGBT of the Comp-IPDU board to the heat sink with two screws. 9. Connect connectors/fasteners and confirm they are correctly and securely inserted. 10. If a component part on the board is bent during board replacement, adjust it manually so that it does not touch other parts or components. 11. Install the cover then turn on the power supply. Check the operation.
Board layout of the inverter
Switch layout on the P.C. board IC101
T03 Noise filter board
T01
SW801 Fan IPDU Power supply P.C. board assembly
Interface board IC222 Magnetic switch
CN26
Terminal
CN13 Comp-IPDU
Comp-IPDU
No.1
No.2
CN17
225
CN15 Q200 T02
T05
T04
17-2-7. Notice for Wiring Wiring for service shall be done according to the wiring diagram. Special caution is needed for the reactor, which has different connecting points on the COMP-IPDU1 and COMP-IPDU2.
COMP-IPDU No.1
COMP-IPDU No.2
TO REACTOR 1
TO REACTOR 2
CN20 (REACTOR 1) CN21 (REACTOR 1)
CN08 (REACTOR 2) CN07 (REACTOR 2)
P.C. board noise P.C. filter board
P.C. board interface
power
P.C. board P.C. board Comp-IPDU Comp-IPDU No.1 No.2
Inverter front view
DANGER The electrolytic capacitors in this panel are charged to 660 volts D.C. Before servicing, turn off the power supply and allow the capacitor to discharge for at least 10 minutes. (Purpose: Discharge the capacitor) Discharge to a safe level of 10 volts D.C. or LESS. Test with a D.C. Voltmeter as shown.
CN13 (CAPA–) CN15 (CAPA+)
10V, DC
Comp-IPDU No.1 & No.2
COMP-IPDU No. 1 and COMP-IPDU No.2 have the same electric potential, measure both. Never discharge the capacitor terminals with any metal implement. Personal injury or equipment damage may result.
226
Inverter Assembly Configuration
Fan IPDU Power supply P.C. board for fan
BUS terminal block
Relay connector
IPDU1
Magnet swith
IPDU2
Noise filter Interface P.C. board Power supply terminal block
Over-current relay
227
TOSHIBA CARRIER CORPORATION 2 CHOME 12-32, KONAN, MINATOKU, TOKYO, 108-0075, JAPAN Copyright © 2005 TOSHIBA CARRIER CORPORATION, ALL Rights Reserved.