and automatically initiates event analysis and reporting and the output in the form
of HTML, print or report file. LS. P. 2007-a fp.tif. Fig. 13/91. SIMEAS Q ...
13 Power Quality / SIMEAS Q
SIMEAS Q Power Quality Recorder Function overview
LSP2007-afp.tif
Features
Fig. 13/91 SIMEAS Q
Description SIMEAS Q is a compact, cost-effective power quality recorder and has been developed to provide full-area monitoring of power quality according to EN 50160 and IEC 61000 standards. The increasing use of non-linear energy consumers or unbalanced loads has a huge impact on the network quality of the electrical power supply. Many electrical devices in the industry need a proper power supply for accurate operation. A poor quality of the power supply affects the operational reliability inside a network of different consumers and can lead to a costexpensive loss of the availability of different devices, for example NC machines. Therefore a coverage acquisition und evaluation of the quality of energy supply is necessary. SIMEAS Q devices are installed at various measuring points in order to record a series of measurements of the required values for an analysis of the network quality. In addition to all relevant measured variables, the SIMEAS Q can also record system disturbances, always when an upward or downward limit value violation has occurred. The recorded values can be called up and evaluated using a PC.
Siemens SIP · 2006
SIMEAS Q is available in 3 device versions with the following communication interfaces: – RS232 – RS485 – PROFlBUS-DP Furthermore the device version SIMEAS Q with PROFIBUS-DP interface opens up another area of application. Together with programmable control systems (PLCs), it can be used as a “sensor” for electrical measured variables. The basic task of data transmission and archiving for several SIMEAS Q devices is automatically managed by the “SICARO Q Manager” software installed on the PC, whereby the data transmission route between the individual SIMEAS Q devices and the PC can be achieved in a number of ways. The SICARO PQ is a software product for evaluating measured values with respect to international standards, e.g. EN 50160 or IEC 61000 or according to definable compatibility levels. For analysis with SICARO PQ, the measured values are automatically first fetched and stored by SICARO Q Manager software. SICARO PQ automatically accesses the stored measured values and automatically initiates event analysis and reporting and the output in the form of HTML, print or report file.
• Recorder for all data required for analysis of the quality of the product “electricity” • Compact design in assembly housing • Long-distance data transmission using various communication routes • Measurement data buffer for up to 70,000 measured values each with time stamp • Measurement and recording of up to 250 measured variables simultaneously • Suitable for monitoring single-phase power supply networks and three or four-wire three-phase AC networks • Continuous and/or event-controlled recording of up to 250 different measured variables • 2 relay outputs Possible measured values • R.m.s. values of phase voltages • R.m.s. values of phase currents • System frequency • Active, reactive and apparent power, as well as power factor per phase and for the overall system • Balance factor of currents and voltages • Flickers • Harmonic voltages and harmonic currents up to the 40th harmonic • Total harmonic distortion (THD) • Active, reactive and apparent output of the overall system Communication interfaces • Serial RS232 and RS485 interface for direct and modem connections with up to 115200 bps • Standards-compliant PROFIBUS-DP interface for connection to programmable controllers or PC with up to 12 Mbps
13/63
13
13 Power Quality / SIMEAS Q
Connection Different connection methods or system configurations are possible, depending on the application and existing infrastructure. One is to use a central PC as the master. It is then possible to set up a system for measured-value acquisition and evaluation using the SICARO Q-Manager software. For long distances individual devices or the complete RS485 bus with Ethernet converter may be used. An other possibility is to link up to a PLC system where the SIMEAS Q is connected to the central master as a slave. The PROFIBUS interface, implemented and certified according to standard EN 50170 Volume 2, enables fast adaptation to a PLC systems. That way, measured values acquired with the SIMEAS Q can be used for control tasks.
Fig. 13/92 Using the SICARO Q Manager software and a PC with several SIMEAS Q units
Detailed information on how to retrieve measurement data from SIMEAS Q via PROFIBUS is available to everyone in the SIMEAS Q user description1). The open communication interface permits data transmission between SIMEAS Q units and all types of PROFIBUS-DP Masters, such as programmable controllers or personal computers (with integrated PROFIBUS-DP hardware). Function blocks are available for the SIMATIC S7-300 and S7-400 PLC systems, with an internal or external DP interface1). They permit fast configuration of customer-specific PLC programs for applications combining SIMEAS Q with these PLC systems. Functions Recording of measured values is possible in two modes, which can be used simultaneously.
13
• Continuous recording • Recording in the case of a limit value violation In “continuous recording“ mode, the SIMEAS Q can record measured quantities as defined in the standards (e.g. EN 50160). Acquisition of maximum and minimum values of measured quantities within the measurement period (averaging time) is also possible.
Fig. 13/93 SIMATIC S7 PLC as the master station with various PROFIBUS-DP slaves
“Recording in the case of limit value violation” means that measurement data are recorded when the average measured value violates one or more defined upper or lower limits (thresholds). When a limit value is violated, the current time and date information and the mean value since the last limit value violation of that measured quantity are stored in the memory. This type of recording is primarily used for recording voltage dips. To record voltage dips, the lowest possible averaging time of 10 ms is selected. During measurement, the SIMEAS Q compares the rms values = 10 ms with the set thresholds and is thus able to record very short voltage dips. Relay outputs The SIMEAS Q is fitted with 2 relay outputs (opto-relays). One of the following functions can be assigned to these outputs:
• Energy metering pulse per settable energy value for: − Active energy, energy import − Active energy, energy export − Reactive energy, capacitive − Reactive energy, inductive − Apparent energy • Indication active power import (contact open) or active power export (contact closed) • Limit power factor (PF (cos ϕ)) (contact closed for as long as PF is lower than a settable limit value) • Pulses an voltage dips (contact closed for 500 ms if violation of the threshold below rated voltage detected) The relay outputs enable the SIMEAS Q to be used for acquisition of measured values and for energy metering.
• Indication device active (switched on) 1) www. simeas.com
13/64
Siemens SIP · 2006
13 Power Quality / SIMEAS Q
Software The SIMEAS Q PAR software and SICARO Q Manager software can be downloaded free of charge via the Internet at www.powerquality.de or www.simeas.com. If SIMEAS Q units are connected to a PLC system as slaves, only the SIMEAS Q PAR software is required to set the SIMEAS Q parameters. To configure the SIMEAS Q, a cable is required to connect the PC. A separate parameterization package is available for this, containing the parameterization software and the connecting cable required for the respective unit version.
Fig. 13/94 SICARO Q Manager Main menu with system structure Menu item for measurement settings
SIMEAS Q PAR configuration software The SIMEAS Q PAR parameterization software is executable under the Windows 2000/XP operating systems. The software allows you to define the device address, so that each device is uniquely identified and to configure the SIMEAS Q for the communication protocol to be used (RS232, RS485 or PROFIBUS DP) in order to prepare it for the measurement task. SICARO Q Manager – software for measured-value acquisition The SICARO Q Manager software, executable under the Windows 2000 / XP operating systems, is a software product for configuring a system with several SIMEAS Q units and for gathering the measured values from the SIMEAS Q units, displaying them, storing them in PQ archives and making them available for further processing. • Functional scope − Graphic configuration of a system structure with the connected SIMEAS Q units. − Automatic transmission and storage of the measurement data from the connected units. − Display of retrieved measurement data. The display takes the form of rotary dial instruments, bar charts and numerical values.
Siemens SIP · 2006
Fig. 13/95 SICARO Q Manager Display of the currently transmitted measured values
− Automatic, cyclic time setting of all connected units to align the SIMEAS Q’s internal clock with the system time of the PC. − Automatic conversion of stored measurement data for analysis with the SICARO PQ software. − Conversion of stored measurement data to ASCII format. After conversion, the data can be further processed with suitable software, e.g. Microsoft Excel.
13
13/65
13 Power Quality / SIMEAS Q
Software SICARO PQ - the analyzing tool The SICARO PQ software, executable under the Windows 2000 / XP operating systems, is a software product for evaluating measured values based on international standards, e.g. EN 50160 or IEC 61000 or according to customer-specific compatibility levels. For analysis with SICARO PQ, the transmitted measured values first have to be archived using the SICARO Q Manager software. The archived data are then the data source for the analysis software. For evaluation and reporting, the reference levels have to be applied and a reporting template has to be selected. Evaluation procedure • Manual selection of data archive • Manual selection of measured quantities and time range • With selected settings for analysing reports (quality profiles) by using of functional task scheduler it is possible to create automatic jobs for printing reports or creating reports in HTML format.
Fig. 13/96 SICARO PQ Display and analysis of continuous measured values
Fig. 13/97 SICARO PQ Analysis of voltage dips using a CBEMA plot
13
Fig. 13/98 For regular reporting, e.g. every day, every week, every month, every year the Windows Task Scheduler is used
13/66
Siemens SIP · 2006
13 Power Quality / SIMEAS Q
Connection examples
Single-phase alternating current
Four-wire three-phase current, same load
Three-wire three-phase current, same load
Three-wire three-phase current, any load
Four-wire three-phase current, any load (low-voltage network)
Four-wire three-phase current, any load (high-voltage network)
13
The input connections shown above are only examples. Currents and voltages up to the maximum permissible values can be connected even without current and voltage transformers. Voltage transformers can also be connected in a delta or wye connection. All input or output terminals not needed for measurement remain unconnected.
Siemens SIP · 2006
13/67
13 Power Quality / SIMEAS Q
Technical data Input Maximum rated system voltage Permissible dynamic range Rated frequency fEN Frequency range fE Waveform
Measurement functions (continued) For connection to AC systems only Y 230/∆ 400 V VY = 280 V; IE = 6 A 50 Hz, 60 Hz ± 5 Hz th Sinusoidal or distorted up to 40 harmonic
Input alternating current IE Input rated current IE Power consumption per current path Dynamic range Continuous overload Surge withstand capability
6A 12 A 200 A acc. to IEC/EN 60688
Input alternating voltage VE Power consumption Input to ground Rated voltage VEN Continuous overload Surge withstand capability
0.02 VA at VEN = 100 V / 3 0.33 VA at VEN = 230 V Max. 230 V (3-phase) 1.2 x VN = 280 V 2 x VN = 460 V acc. to IEC/EN 60688
Min. 1 A; max. 6 A Approx. 0.06 VA at IE = 6 A
Current Measuring range Accuracy Storage
Active power, apparent power, reactive power Accuracy Storage
Power factor Accuracy Storage
Auxiliary voltage Rated voltage variant 1 Permissible tolerance range Rated voltage variant 2 Permissible tolerance range Power consumption
Multi-range PSU AC/DC 24 to 60 V DC ± 20 % of the rated voltage 110 to 250 V DC and 100 to 240 V AC / 45 to 65 Hz +15/-20 % of the rated voltage 3.5 W per connection
Binary outputs Permissible voltage Permissible current Internal resistance Permissible switching frequency Measurement functions Number of channels
Calculation method Sampling rate
13
Resolution Voltage Measuring range Accuracy Storage
2 via opto-relays ± 100 V AC/DC 150 mA permament 500 mA for 100 ms ≤ 10 Ω 10 Hz 3 voltage inputs with common neutral N 3 current inputs Fast Fourier transform 6400 Hz for 50 Hz system frequency 7680 Hz for 60 Hz system frequency per voltage or current input 14 bits 0 to 280 V Typically ≤ 0.1 % of rating Continuously independently selectable averaging time 1 to 3600 s storage of max., min. and average values possible On limit value violation independently selectable averaging time 10 ms to 3600 s 5 settable limits
Symmetry Measurement Accuracy Storage
Frequency Accuracy Storage
Harmonics Frequency range Accuracy Storage
Flicker factor Measurement Accuracy Storage
13/68
0 to 6 A Typically ≤ 0.1 % of rating Continuously independently selectable averaging time 1 to 3600 s storage of max., min. and average values possible On limit value violation independently selectable averaging time 10 ms to 3600 s 5 settable limits Typically ≤ 0.2 % of rating Continuously independently selectable averaging time 1 to 3600 s storage of max., min. and average values possible On limit value violation independently selectable averaging time 1 to 3600 s 2 settable limits each Typically ≤ 0.2 % Continuously independently selectable averaging time 1 to 3600 s storage of max., min. and average values possible On limit value violation independently selectable averaging time 1 to 3600 s 2 settable limits For measurement in 3-phase system voltage and current Typically ≤ 0.2 % Continuously independently selectable averaging time 1 to 3600 s storage of max., min. and average values possible On limit value violation independently selectable averaging time 1 to 3600 s 2 settable limits ≤ 5 mHz Continuously independently selectable averaging time 1 to 3600 s storage of max., min. and average values possible On limitv value violation independently selectable averaging time 1 to 3600 s 2 settable limits Up to 40th harmonic per voltage or current input Acc. to IEC 61000-4-7 Class B Continuously independently selectable averaging time 1 to 3600 s storage of max., min. and average values possible On limit value violation independently selectable averaging time 1 to 3600 s 2 settable limits per harmonic ASt/AIt or PSt/PIt per voltage input Acc. to IEC 61000-4-15 (IEC 60 868) Continuously averaging time Ast and Pst 10 min averaging time AIt and PIt 120 min
Siemens SIP · 2006
13 Power Quality / SIMEAS Q
Technical data Measurement functions (continued) Active energy, import Active energy, export Reactive energy, capacitive Reactive energy, inductive Apparent energy Accuracy Typically ≤ 0.2 % Storage Continuously, selectable averaging time 1 to 60 min Electrical tests Stress tests Dielectric test Input circuits against each other Aux. voltage against interface and relay outputs Input circuits against interface and relay outputs Impulse voltage withstand test Input circuits against each other Aux. voltage against interface and relay outputs Input circuits against interface and relay outputs Temperature and climatic stress
Industrial atmosphere SO2 H2S Mechanical stress Vibrations, sinusoidal stationary use Vibrations, sinusoidal transportation Seismic stress stationary use Shock, half-sine wave, stationary use Shock, half-sine wave, for resistance Shock, half-sine wave, continuous shock Safety Mechanical resistance to shock and impact Degree of protection Housing Terminals Safety class Temperature and protection from propagation of fire Insulation Clearance and creepage distance
Siemens SIP · 2006
Acc. to IEC/EN 61010-1 Acc. to EN 61010-1 3.7 kV, 50 Hz, 1 min
Electromagnetic compatibility Immunity 1 MHz burst disturbance test Electrostatic discharge Radiated electromagnetic field disturbance test Burst Surge Conducted disturbances induced by radio-frequency fields
Acc. to EN 61000-6-2, EN 60688 Acc. to IEC 60255-22-1, 2.5 kV, 400 Hz Acc. to IEC 61000-4-2 Class III Acc. to IEC 61000-4-3, ENV 50204 Acc. to IEC 61000-4-4 Acc. to IEC 61000-4-5 Acc. to IEC 61000-4-6 Class III
Magnetic field
Acc. to EN 61000-4-8 Class IV, IEC 60688, IEC 60255-6
Emission
Acc. to EN 50081-1, EN 50081-2
3.7 kV, 50 Hz, 1 min
Conducted interference
Acc. to CISPR 22, EN 55022, VDE 0878 Part 22
5.55 kV, 50 Hz, 1 min Acc. to EN 61010-1 6.8 kV, 1.2/50 µs
Noise field intensity
Acc. to CISPR 11, EN 55011, VDE 0875 Part 11
Disturbances power supply systems
Acc. to IEC 61000-3-3, IEC 61000-3-2
6.8 kV, 1.2/50 µs 10.2 kV, 1.2/50 µs Acc. to IEC/EN 60688 -10 °C to 55 °C, no condensation during operation Acc. to IEC 60068-2-42 DIN 40046 Part 36 Acc. to IEC 60068-2-43 DIN 40046 Part 37 Acc. to IEC 60068-2-6, IEC 60255-21-1 Acc. to IEC 60068-2-6, IEC 60255-21-1 Acc. to IEC 60068-3-3, IEC 60255-21-3 Acc. to IEC 60068-2-27, IEC 60255-21-2 Acc. to IEC 60068-2-27, IEC 60255-21-2 Acc. to IEC 60068-2-29, IEC 60255-21-2
Communication interface Interface Connection technique
9-pin SUB-D connector female
Transmission options PROFIBUS DP Transmission rate
From 9 600 Bit/s to 12 MBit/s
RS232 interface Transmission rate
Modem-capable From 300 Bit/s to 115 200 Bit/s
RS485 interface Transmission rate
From 300 Bit/s to 115 200 Bit/s
Data memory 2 MB memory for measurement data
Memory up to 70 000 measured values, each with time information
Program memory
256 kByte EEPROM
Real-time clock Internal real-time clock Format Deviation Back-up Synchronization and setting
Year, month, day, hour, minute, second 100 ppm With lithium battery Via communication interface
Unit design Acc. to IEC 61010-1, IEC 60068-3-75 IP 40 IP 20 Safety class 1 Acc. to IEC 60255-6, IEC 61010-1 Acc. to EN 61010-1, pollution degree 2, overvoltage category III
Dimensions
90 x 75 x 105 mm (W x H x D)
Housing
Snap-on housing for DIN rail mounting Degree of protection IP40
Connection elements - Aux. power supply - Voltage inputs - Current inputs - Binary outputs - Communication interface
Degree of protection IP20 Terminal for max. 2.5 mm 2 2 Terminal for max. 2.5 mm 2 Terminal for max. 4 mm 2 Terminal for max. 2.5 mm 9 pin SUB-D connector
Weight
Approx. 0.7 kg
13
13/69
13 Power Quality / SIMEAS Q
Selection and ordering data
Description
Order No.
SIMEAS Q
7KG8000 – 8
oo20
Interface With PROFIBUS-DP interface With modem-capable RS232 interface With RS485 interface
A B C
Auxiliary voltage 24 to 60 V DC 110 to 250 V DC and 100 to 240 V AC 45 to 65 Hz
SIMEAS Q parameterization package for SIMEAS Q with RS232 interface
A B 7KG8050-8BC20
Software SIMEAS Q PAR for configuration and calibration of SIMEAS Q units with an RS232 interface on a PC Connecting cable SIMEAS Q to PC Length 4 m
SIMEAS Q parameterization package for SIMEAS Q with RS485 interface or PROFIBUS DP interface
o
7KG8050-8A 20
Software SIMEAS Q PAR for configuration and calibration of SIMEAS Q units with RS485 or PROFIBUS-DP interface on a PC Connecting cable SIMEAS Q to PC incl. RS232/RS485 converter Plug-in power supply unit for converter Auxiliary voltage 230 V AC 50 Hz 110 V AC 60 Hz
RS232-RS485 converter incl. cable
A B
o
7XV5700- BB00
Connecting cable SIMEAS Q to PC Plug-in power supply unit for converter Auxiliary voltage 230 V AC 50 Hz 110 V AC 60 Hz
0 1
Ethernet hub for substations Serial hub for serial, asynchronous data transmission (for more details see part 14 of SIP Catalog)
7XV5655-0BA00
Ethernet modem For serial, asynchronous data transmission (for more details see part 14 of SIP Catalog)
7XV5655-0BB00
13
13/70
Siemens SIP · 2006
13 Power Quality / SIMEAS Q
Selection and ordering data
Description
Order No.
Software SICARO Q Manager incl. SIMEAS Q PAR
o1
7KG8000-5BB20-
Delivered on CD-ROM Manual German English
SICARO PQ incl. SICARO Q Manager and SIMEAS Q PAR
A B
o
7KE6000-5GE
Software for analysis of network quality Complete license on CD-ROM with manual in English and German Update version on CD-ROM only for an update of an existing SICARO PQ installation/license to the current released version. Send the old order number
2 4
13
Siemens SIP · 2006
13/71
13 Power Quality / SIMEAS Q
Dimension drawings in mm / inch
Front view
Side view
7KG8000 SIMEAS Q Fig. 16/47
13
13/72
Siemens SIP · 2006