Single-Phase Induction Motor Indirect Field Oriented Control Under Nominal Load Ademir Nied, José de Oliveira, Franciéli L. de Sá

Rafael de F. Campos, Luis H. R. de C. Stival

Electrical Engineering Department Universidade do Estado de Santa Catarina-UDESC Joinville, Brazil [email protected], [email protected], [email protected]

C&E - Controls and Electronics Whirlpool Latin America Joinville, Brazil [email protected], [email protected]

Abstract—This paper discusses the performance of a single-phase induction motor drive under nominal load in a closed-loop vector-controlled system. The control strategy to be applied is known as indirect field oriented control. Single-phase induction motor when operating as two-phase motor has its dynamic performance increased. With the use of a standard three-phase voltage-source inverter, space vector pulse width modulation can be implemented. Experimental results show the effectiveness of the control system.

greatest number of switches, so the losses of the system are increased.

Keywords- indirect field oriented control, induction motor, single-phase induction motor, motor drive, Space-vector modulation.

The purpose of this paper is to examine the operation of a single-phase induction motor when operated from a variable frequency power supply under load condition.

I.

The application of power electronic inverters, along with pulse width modulation (PWM), increased the performance of single-phase induction motors. The most widely use PWM techniques are sinusoidal PWM and space vector PWM. In [7], [8] and [9] some PWM strategies are discussed when applied to a single-phase induction motor drive.

The field oriented strategy that will be described is based on [1] and [2]. However, these papers do not include experiments with load applied to the single-phase induction motor. The control method to be applied is the indirect field oriented control (IFOC).

INTRODUCTION

Single-phase induction motors are widely used in fractional and sub-fractional horsepower applications, usually in locations where only single-phase energy supply is available. In literature, the performance of a single-phase induction motor drive under field oriented control has been analyzed in [1], [2] and [3].

Experimental results illustrating the drive performance under rated load condition are presented and discussed. II.

These papers use the dq model to derive the motor equations and treat the single-phase induction motor as an unsymmetrical two-phase induction motor since most singlephase induction motors (split-phase, capacitor-start, capacitorrun and capacitor-start capacitor-run) usually have a main and auxiliary stator winding asymmetrical and displaced 90 degrees apart from each other.

SINGLE-PHASE INDUCTION MOTOR MODEL

The derivation of the motor model is based on classical assumptions: linearity of the magnetic circuit, constant air-gap length and the motor windings produce sinusoidal distribution of magnetic field in the air-gap. Consistent with these assumptions the dynamic model of the single-phase induction motor is derived following the approach presented in [6], which describe an asymmetric single-phase induction machine in the stationary reference frame (denoted by superscript s):

With the growing concern about low-cost operation and the efficient use of energy, single-phase induction motors have gained interest for low-power applications, especially for domestic or commercial applications where a three-phase power supply is not available.

⎡v dss ⎤ ⎡rds ⎢ s ⎥=⎢ ⎢⎣v qs ⎥⎦ ⎣ 0

Different inverter topologies for single-phase induction motor drive have been proposed. Commonly, three types of topologies are studied: two-leg, three-leg and four-leg twophase inverters [4], [5].

⎡0⎤ ⎡rr ⎢ 0⎥ = ⎢ 0 ⎣ ⎦ ⎣

The first topology is known as H-bridge voltage inverter with two-legs and a mid-point provide by a capacitive divider. The second is composed of three-legs with the mid-point provided by the common leg. The third possibility has the

789

0 ⎤ ⎡i dss ⎤ d ⎡λ sds ⎤ ⎢ ⎥+ ⎢ ⎥ rqs ⎥⎦ ⎢i qss ⎥ dt ⎢λ sqs ⎥ ⎣ ⎦ ⎣ ⎦

(1)

s s 0 ⎤ ⎡i dr ⎤ d ⎡λ dr ⎤ ⎡ 0 1⎤ ⎡λ sdr ⎤ ⎢ ⎥ ⎢ ⎥ + ωr ⎢ + ⎢ ⎥ (2) ⎥ s s − 1 0⎥⎦ ⎣⎢λ sqr ⎥⎦ rr ⎦ ⎢i qr ⎥ dt ⎢λ qr ⎥ ⎣ ⎣ ⎦ ⎣ ⎦

PEDS2009 s ⎤ 0 ⎤ ⎡i ds ⎡ Ldsr ⎢ ⎥+⎢ s Lqs ⎥⎦ ⎢i qs 0 ⎣ ⎥⎦ ⎣

⎡λ sds ⎤ ⎡ Lds ⎢ ⎥=⎢ ⎢⎣λ sqs ⎥⎦ ⎣ 0 ⎡λ sdr ⎤ ⎡ Lr ⎢ ⎥=⎢ ⎢⎣λ sqr ⎥⎦ ⎣ 0

s 0 ⎤ ⎡i dr ⎤ ⎡ Ldsr ⎥⎢ s ⎥ + ⎢ 0 Lr ⎦ ⎢i qr ⎣ ⎥⎦ ⎣

P(Te − Tm ) = J

s ⎤ 0 ⎤ ⎡i dr ⎢ ⎥ s Lqsr ⎥⎦ ⎢i qr ⎣ ⎥⎦ s ⎤ 0 ⎤ ⎡i ds ⎢ ⎥ s Lqsr ⎥⎦ ⎢i qs ⎣ ⎥⎦

dω r + Bωr dt

s s s s Te = P( L qsr i qs i dr − Ldsr i ds i qr ) .

⎡0⎤ ⎡rr ⎢ ⎥=⎢ ⎣0 ⎦ ⎣ 0

(3)

(4)

⎤ ⎡L ⎡λer ds1 ⎢ er ⎥ = ⎢ ds ⎢⎣λ qs1 ⎥⎦ ⎣ 0

(5)

⎤ ⎡L ⎡λer dr ⎢ er ⎥ = ⎢ r ⎢⎣λ qr ⎥⎦ ⎣ 0

(6)

v , v , i , i , i , i , λ , λ , λ , λ . The terms s qs

s ds

s qs

s dr

s qr

s ds

s qs

s dr

s qr

self-inductance and their respective mutual inductance. The dq stator resistance and rotor resistance are denoted by rsd , rsq , rr

⎡rdds ⎢ ⎣rqds

=

=

λ sqs1

where

s s s s v ds = v ds 1 ; v qs = v qs1 / k .

III.

rds + rqs' 2

2

sin( 2θ er )

r 'qs = k 2 rqs and θ er represents the instantaneous

λer dr = λr ;

(8)

IV.

(9)

λerqr = 0 .

(17)

INDIRECT FIELD CONTROL

Considering (17) the condition for flux orientation, the slip frequency can be derived by (12) and (14):

ω err =

(10)

1

τ r λr

er Ldsr i qs 1

(18)

where ω err = ω er − ω r and τ r = Lr / rr . Similarly, the torque and flux equations can be shown to be

ROTOR FLUX CONTROL

To establish the rotor flux orientation is necessary to rewrite the motor equations transforming the electrical variables into the rotor flux reference frame (denoted by superscript er), taking into account the relations (7)-(9) and (10). Thus er ⎤ ⎡v ds ⎡rdds 1 ⎥=⎢ ⎢ er r ⎢⎣v qs 1⎥ ⎦ ⎣ qds

⎤ ⎥ ⎥ ' ⎥ rds − rqs − cos(2θ er ) ⎥ 2 ⎦

rds − rqs'

The condition for rotor flux oriented control is to align the flux vector along the d-axis of the rotating frame, i.e.

The new expression for the torque which presents no oscillating terms can be rewritten as: s s s s Te = PLdsr (i qs 1i dr − i ds1 i qr ) .

⎡ rds + rqs' rds − rqs' + cos(2θ er ) rdqs ⎤ ⎢ 2 2 ⎥=⎢ rqqs ⎦ ⎢ rds − rqs' sin(2θ er ) ⎢ 2 ⎣

electrical angle between the rotor flux vector and the stationary reference frame.

(7) /k ,

(15)

(16)

balances the rotor currents and rotor fluxes, thus eliminating the oscillation term. The relation to balance the torque equation can be written as:

λ sqs

(14)

asymmetry of the stator windings. In (16), the relations between the stator resistances are presented as:

In order to apply the IFOC strategy in a single-phase induction motor, the ac term that appears in the torque expression must be eliminated. In (6) one can notice that the torque oscillation appears due to the asymmetry in the mutual inductance. To overcome this issue, in [1] is proposed a relation k = Ldsr / Lqsr between the mutual inductances that

λsds1 ;

er 0 ⎤ ⎡i ds1 ⎤ ⎢ ⎥ ⎥ er Ldsr ⎦ ⎢i qs ⎣ 1 ⎥⎦

The presence of time dependent resistance terms in the stator equations, rdds , rdqs , rqds and rqqs , are due to the

and P indicates the motor pole pairs. Te and Tm are the motor electromagnetic torque and the load torque, respectively. J, B and ωr are the moment of inertia, viscous friction coefficient and the motor speed, respectively.

λ sds

er 0 ⎤ ⎡i dr ⎤ ⎡ Ldsr ⎢ ⎥+⎢ ⎥ er 0 Lr ⎦ ⎢i qr ⎣ ⎥⎦ ⎣

(13)

where ωer is the instantaneous angular velocity of the rotating rotor flux vector.

Lds , Lqs , Lr and Ldsr , Lqsr denote the dq stator and rotor

s s s s i ds = i ds 1 ; i qs = kiqs1 ,

er 0 ⎤ ⎡i dr ⎤ ⎥ ⎢ er Ldsr ⎥⎦ ⎢i qr ⎣ ⎥⎦

er 0 ⎤ ⎡i ds1 ⎤ ⎡ Ldsr ⎥+⎢ ⎢ er Lds ⎥⎦ ⎢i qs 0 ⎣ 1 ⎥⎦ ⎣

er er er er Te = PLdsr [i qs 1i dr − i ds1i qr ]

The dq voltages, currents and stator and rotor fluxes are: s ds

er er ⎤ 0 ⎤ ⎡i dr ⎤ d ⎡λ dr ⎤ ⎡0 − 1⎤ ⎡λer dr ⎢ ⎥ ⎢ ⎥ + (ω er − ω r ) ⎢ + ⎢ ⎥ ⎥ er ⎥ er rr ⎦ ⎢i qr ⎥ dt ⎢λer ⎣1 0 ⎦ ⎣⎢λ qr ⎥⎦ ⎣ ⎦ ⎣ qr ⎥⎦ (12)

Te =

PLdsr er i qs1λ r Lr

dλ r λ r 1 + = L i er . τ r τ r dsr ds1 dt

er ⎤ er ⎤ rdqs ⎤ ⎡i ds ⎡0 − 1⎤ ⎡λer d ⎡λ ds1 ⎤ 1 ds1 ⎥ + ω er ⎢ ⎢ ⎥ ⎢ + ⎥ ⎢ ⎥ ⎥ er er rqqs ⎦ ⎢i qs dt ⎢λer ⎣1 0 ⎦ ⎣⎢λ qs1 ⎦⎥ ⎣ qs1 ⎥⎦ ⎣ 1 ⎥⎦ (11)

(19) (20)

The indirect field control adds an estimated slip frequency to the shaft and integrates the total to obtain the oriented angle,

790

PEDS2009

θ er =

∫τ

1 r λr



er Ldsr i qs 1 dt + ω r dt .

(21)

er u ds =−

Fig.1 presents the block diagram of the indirect rotor flux control. Since it is necessary to calculate the voltage command for a voltage-source inverter, the stator voltage equations for rotor flux control can be derived by (11), (13) and (14): ⎛ rds + r 'qs L2 er ⎜ + srd vds 1 = ⎜ 2 Lrτ r ⎝ +

rds − rqs' 2

⎛ rds + r 'qs er ⎜ vqs + 1 = ⎜ 2 Lrτ r ⎝ −

rds − rqs' 2

rds − rqs' 2

2

er sin(2θ er )iqs 1

(22)

(27)

The set of equations established is required for a rotor flux oriented control in the indirect method. A. Drive Configuration and PWM Although there are various methods of driving single-phase machine one of the known methods to acquire low-cost high performance is to remove the capacitor from the auxiliary winding so the motor can be viewed as a two-phase machine [1], [2]. That way is possible to implement the field-oriented control.

er sin( 2θ er )ids 1

(23)

However, the stator voltage equations are dependent on both stator currents. Therefore, it is necessary to remove the decoupling terms so one can have a linear control of the stator voltages. Rewriting (22) and (23) ⎛ rds + r ' qs L2 er ⎜ v ds = + srd 1 ⎜ 2 Lrτ r ⎝

er ⎞ ⎟i er + σ L di ds1 + u er ds ds ds ⎟ ds1 dt ⎠

(24)

⎛ rds + r ' qs L2 er ⎜ v qs = + srd 1 ⎜ 2 Lrτ r ⎝

er ⎞ ⎟i er + σ L di qs1 + u er ds ds qs ⎟ qs1 dt ⎠

(25)

er sin(2θ er )i qs 1

rds − r ' qs L srd λ r er er cos(2θ er )i qs − ω er σ ds L ds i ds 1 − 1 Lr τ r 2 . rds − rqs' er sin( 2θ er )i ds + 1 2

⎞ er L λ er ⎟i + σ L − ωr srd r − ωer ids ds ds 1σ ds Lds ⎟ qs1 dt Lrτ r ⎠ rds − rqs'

2

er u qs = −ω r

er diqs 1

er cos(2θ er )iqs 1+

rds − rqs'

(26)

er ⎞ er ⎟i + σ L dids1 − Lsrd λr − ω i er σ L ds1 ds ds er qs1 ds ds ⎟ dt Lrτ r ⎠

er cos(2θ er )ids 1+

L2srd

+

rds − r ' qs L srd λ r er er − ω er i qs cos(2θ er )i ds 1σ ds L ds + 1 Lr τ r 2

The inverter topology in Fig. 2 was chosen to drive the single-phase induction motor because it makes use of a common configuration applied to tree-phase inverters and it can improve motor drive performance. Along with that, it is necessary to determine which modulation strategy will maintain the quadrature control in an efficient way. Instead of using a common sinusoidal modulation, a space vector pulse with modulation (SVPWM) technique can be applied.

er er where u ds and u qs represent the decoupling terms and are

given by

Fig. 1. Block diagram of the indirect rotor flux control system.

791

PEDS2009

Fig. 3(a) shows the actual (ωr) and reference (ω*) motor speed under the IFOC system. Fig. 3(b) shows the dq motor currents. The asymmetry of the motor can be verified by the difference in amplitude of the stator currents. In order to verify how the IFOC system reacts under load condition a new set of tests were performed. The load applied to the system consists of a 0.8-Hp dc motor connected to a resistor that serves as the dynamometer of the motor. It was set a rated load to be applied to the single-phase induction motor.

Fig. 2. Semi full-bridge inverter topology.

Fig. 4(a) presents the motor speed (ωr) and the speed reference (ω*) for the IFOC. It can be seen that when the system is started the actual motor speed can track the reference speed with no significant delay. Fig. 4(b) shows the load step applied to the motor. When the load is applied the actual speed and the flux reference sense slightly the disturbance as it is seen in Fig 4(a). Finally, Fig. 4(c) presents the stator current during the moment in which the load is applied.

The SVPWM technique applies voltage vectors generated by the voltage-source inverter to control the torque and flux of the machine. Similar to the three-phase inverter feeding a three-phase induction motor, in a three-phase inverter feeding a two-phase induction motor there are eight voltage vectors to be applied. These voltages vectors are synthesized so that the power switches work in the most efficient way. This modulation method is discussed in [7] and [9] and will not be presented in this paper. V.

EXPERIMENTAL RESULTS

The speed control of the single-phase induction motor was implemented in accordance with Fig. 1. Firstly, the motor was set to run with no load attached to the shaft. To show the dynamic control achieved by the IFOC system the speed was reversed. (a)

(b)

(a)

(c) (b)

Fig. 4. IFOC – Under load: (a) motor speed (1 V = 44,34 rad/s); (b) rated load step (1 V ≅ 0,5 HP); (c) stator currents.

Fig. 3. IFOC – No Load: (a) motor speed (1 mV = 0,47 rad/s), (b) stator currents (100 mV = 1 A).

792

PEDS2009

REFERENCES

CONCLUSION This paper investigated the field oriented control for singlephase induction motor drive system with and without load. Due to the natural asymmetry of the single-phase induction motor some transformations were carried out so the IFOC method could be implemented.

[1]

[2]

To verify the drive performance some experimental tests were carried out. The dynamic behavior of the IFOC was investigated during speed reversal transients. The applied control method delivered good performance with the actual speed tracking the reference speed during all transients.

[3]

[4]

In order to show the effectiveness of the control systems when driving a single-phase induction motor, tests under load condition were performed. The IFOC presented good dynamic behavior during the load transients. When the disturbance was sensed the control systems could keep up the reference speed.

[5]

[6]

The results obtained were considered satisfactory and showed the performance of a single-phase induction motor drive under load does not differ from the performance without load.

[7]

[8]

ACKNOWLEDGMENT [9]

The authors wish to acknowledge the support provided by Universidade do Estado de Santa Catarina (UDESC) for this investigation.

793

M. B. R. Corrêa, C. B. Jacobina, A. M. N. Lima and E. R. C. da Silva “Rotor-flux-oriented control of a single-phase induction motor drive,” IEEE Trans. Ind. Electron., vol. 47, no. 4, pp. 832-841, Aug. 2000. M. B. R. Corrêa, C. B. Jacobina, A. M. N. Lima, and E. R. C. da Silva,“Vector Control Strategies for Single-Phase Induction Motor Drive Systems,” IEEE Trans. Ind. Electron., vol. 51, no. 5, pp. 1073–1080, Oct. 2004. M. Popescu, D.M. Ionel and D.G. Dorrell, “Vector control of unsymmetrical two-phase induction machines,” in Conf. Rec. IEEE IEMDC’01, 2001, pp. 95-101. D. G Holmes and A. Kotsopoulos, “Variable speed of single and two phase induction motors using a three phase voltage source inverter” in Conf. Rec. of IEEE-IAS Annual Meeting 1993, Vol. 1, pp. 613 – 620. S. S. Wekhande, B. N. Chaudhari, S. V. Dhopte and R. K. Sharma, “A Low Cost Inverter Drive for 2-Phase Induction Motor” in IEEE 1999 International Conference on Power Electronics and Drive Systems, PEDS’99, July 1999, Hong Kong. P. C. Krause, O. Wasynczuk, and S. D. Sudhoff, Analysis of Electric Machinery and Drive Systems. 2th ed., Wiley-IEEE Press, 2002. M. B. R. Corrêa, C. B. Jacobina, A. M. N. Lima and E. R. C. da Silva, “A Three-Leg Voltage Source Inverter for Two-Phase AC Motor Drive Systems,” Transactions on Power Electronics, vol. 17, no. 4, pp. 517523, July 2002. J. Do-Hyun and Y. Duck-Yong, “Space-Vector PWM Technique for Two-Phase Inverter-Fed Two-Phase Induction Motors,” IEEE Trans. on Industry Applications, vol. 39, no. 2, pp. 542-549, Mar/Apr 2003. M. A. Jabbar, A. M. Khambadkone and Z. Yanfeg, “Space-Vector Modulation in a Two-Phase Induction Motor Drive for Constant-Power Operation,” Transactions Ind. Electron., vol. 51, no. 5, pp. 1081-1088, Oct. 2004.