■ Overview • Basic variants optimized for costs • Interface for the connection of expansion modules, up to 24 digital inputs, 16 digital outputs, 8 analog inputs and 2 analog outputs can be addressed • With connection option for LOGO! text display TD (can be connected to all LOGO! 0BA6 basic versions) Note: SIPLUS extreme products are based on Siemens Industry standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added.

■ Technical specifications Article number

6AG1052-2CC01-2BA6

6AG1052-2MD00-2BA6

6AG1052-2HB00-2BA6

6AG1052-2FB00-2BA6

Based on

6ED1052-2CC01-0BA6

6ED1052-2MD00-0BA6

6ED1052-2HB00-0BA6

6ED1052-2FB00-0BA6

SIPLUS LOGO! 24CO

SIPLUS LOGO! 12/24RCO

SIPLUS LOGO! 24RCO

SIPLUS LOGO! 230RCO

• Min.

-40 °C; = Tmin

-40 °C; = Tmin

-40 °C; = Tmin

-40 °C; = Tmin

• max.

70 °C; = Tmax; 55 °C @ UL/cUL use

70 °C; = Tmax; 55 °C @ UL/cUL use

70 °C; = Tmax; 55 °C @ UL/cUL use

70 °C; = Tmax; 55 °C @ UL/cUL use

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)

100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)

100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)

100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)

- against biologically active substances / conformity with EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

- against chemically active substances / conformity with EN 60721-3-3

Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!

- against mechanically active substances / conformity with EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Ambient conditions Ambient temperature in operation

Extended ambient conditions • Relative to ambient temperatureatmospheric pressure-installation altitude

Relative humidity - With condensation, max.

Resistance

Siemens ST 70 · 2015

2/15

2

© Siemens AG 2015

LOGO! logic module LOGO! modular SIPLUS LOGO! modular pure variants

■ Ordering data

2

Article No.

Article No.

SIPLUS LOGO! 24o

Accessories

24 V DC supply voltage, 8 digital inputs 24 V DC, of which 4 can be used in analog mode (0 to 10 V), 4 digital outputs 24 V DC, 0.3 A, integrated time switch; without display and keyboard; 200 function blocks can be interlinked, modular expansion capability

SIPLUS Upmiter upstream device

Extended temperature range and exposure to media

Further accessories

6AG1052-2CC01-2BA6

SIPLUS LOGO! 230RCo 115/230 V AC/DC supply voltage, 8 digital inputs 115/230 V AC/DC, 4 relay outputs 10 A, integral time switch; without display and keyboard; 200 function blocks can be interlinked, modular expansion capability Extended temperature range and exposure to media

6AG1052-2FB00-2BA6

SIPLUS LOGO! 24RCo 24 V AC/DC supply voltage, 8 digital inputs 24 V AC/DC, 4 relay outputs 10 A, integral time switch; without display and keyboard; 200 function blocks can be interlinked, modular expansion capability Extended temperature range and exposure to media

6AG1052-2HB00-2BA6

SIPLUS LOGO! 12/24RCo 12/24 V DC supply voltage, 8 digital inputs 12/24 V DC, of which 4 can be used in analog mode (0 to 10 V), 4 relay outputs 10 A, integral time switch; without display and keyboard; 200 function blocks can be interlinked, modular expansion capability Extended temperature range and exposure to media

2/16

Siemens ST 70 · 2015

6AG1053-1AA00-2AA0

for reliable operation at the battery of combustion engines

6AG1052-2MD00-2BA6

See LOGO! modular pure variants, page 2/14