Catalogue request. 32 ... This is Part 2 of our catalogue series; it contains our fire
protection ceiling ...... Knauf AMF - Office Düsseldorf Mobile: (0) 171 - 315 45 40.
06/2009
PERFORMANCE CEILINGS M ore s c op e f or i n n ovat i on
F IRE PR OTEC TIO N PROGRAMME PART 2
MADE IN GERMANY
RESPONSIBILITY FOR PEOPLE AND ASSETS
NORBERT FIGGE, ARCHITECT, DETLEFSEN&FIGGE ARCHITECTURE FIRM, KIEL
Fire protection means preventing the outbreak and spread of fire and smoke. The protection of health and life is of utmost importance to the people located within the building. That’s why specific requirements on fire resistance period and fire behaviour, based on a classification of the type and usage of the building, need to be fulfilled. The objective is to provide the rescue and fire fighting teams with a sufficiently safe environment to evacuate the people from the building and, where applicable, bring any valuable objects to safety. The quality of the building materials used often plays a decisive role in determining whether a fire is able to spread unhindered or is contained at the seat of the fire and able to be extinguished quickly and successfully.
In the case of German public buildings, the properties of escape routes is regulated on the basis of the fire protection ordinances of the German Länder. These stipulate, for example, that the escape routes must remain intact and smoke-free for a specified period of time. They must not contain any flammable building materials or furnishings and must be segregated into individual fire zones. By rigorously adhering to the fire protection ordinances during planning and implementation, lives can be saved and material and intangible damages minimized. AMF has been manufacturing special and certified fire protection systems for this purpose for several decades. AMF’s in-house and field technicians can provide support both in the planning and implementation phase of any building project that has fire protection requirements.
TABLE OF CONTENTS Introduction Fire Protection Building Material Classification Building Component Classification Soffit Construction Types Fire Tests
2 3
4
5 6 8
AMF Test Certificates Structural Fire Protection F30 Under Gang-Nail Truss F90 Under timber joists / trapezoidal decking / Trapezoidal Sheeting Independent Fire Protection
9 10
12
14 16
AMF Test Certificates Wall Brackets F30 Uno / + Metal F30 Dual + Metal F30 Mono AMF Projects Offices / Contact Persons Catalogue request
18
Product Index
35
19 20 22 26 28 30 32
We have restructured our product catalogues to make it easier for you to find what you are looking for. This is Part 2 of our catalogue series; it contains our fire protection ceiling products. Parts 1 and 3 – 6 of our catalogue series contain comprehensive information about our other product lines. You can obtain these catalogues by filling out the reply card at the end of this catalogue or simply by downloading them from www.amfceilings.com
2
Structural fire protection
Independent fire protection
Structural fire protection involves classifying the suspended ceiling together with the soffit and the grid installation as a whole. AMF THERMATEX ceilings achieve building component classifications of F30 to F120 depending on the type of soffit. We have developed special fire protective ceilings for certain applications:
Independent fire protection ceilings are tested for their fire resistance period irrespective of the type of soffit located above. They offer up to 30 minutes of fire protection from above and below:
System F30 under gang-nail truss
F30 Uno / + Metal
System F90 under timber joists and trapezoidal decking
F30 Dual + Metal F30 Mono
3
FIRE CLASSIFICATION
Building material classification
The DIN EN 13501-1 standard is used to assess and classify building materials according to their fire behaviour.
The A2-s1,d0 class corresponds to the national building-regulation term: “non-combustible”.
It sets the requirements for the materials on the surface of building components, e.g. ceiling claddings, i.e. their behaviour when in direct contact with radiant heat or flames.
AMF THERMATEX panels are classified as A2-s1,d0 in accordance with DIN EN 13501-1 and are therefore “non-combustible”. The material class is mostly printed on the rear of the panel as well as on the packaging labels.
The classification into combustible and non-combustible building materials doesn‘t describe the intrinsic behaviour of the material. The behaviour under fire load depends on the surface type and form, the presence of bonding agents, the processing technique used, etc. The certifications are therefore only valid for the building material or composite building material actually tested. Other compositions can exhibit a less favourable fire behaviour.
4
Test certificates are available on request.
Building component classification
According to DIN EN 1365-2 (fire load from “below”) and DIN EN 1364-2 (fire load from “below” and “above”), not only are the suspended ceilings relevant to the achievement of the individual fire resistance classed but also the construction as a whole, i.e. the soffit located above, as well as installations such as light fittings, loudspeakers, anemometers, etc. that need to be suspended separately from the soffit.
Fire resistance class
Fire resistance period in minutes
F30
> 30
F60
> 60
F90
> 90
F120
> 120
The suspended ceiling and soffit should prevent the passage of fire and temperature for as long as possible. This time is called the fire resistance period, e.g. > 30 minutes. This fire resistance period is defined in the fire resistance classes and determined on the basis of DIN EN 1363-1 in consideration of the criteria for testing.
5
SOFFIT CONSTRUCTION TYPES
AS PER DIN 4102 Part 2
TYPE I SOFFIT CONSTRUCTION AERATED CONCRETE
HOLLOW CORE
Steel beam Suspended ceiling
Suspended ceiling
TYPE II SOFFIT CONSTRUCTION REINFORCED CONCRETE ON STEEL BEAMS
Steel beam Suspended ceiling
TYPE III SOFFIT CONSTRUCTION REINFORCED CONCRETE
RIBBED CONCRETE SOFFIT
Suspended ceiling Suspended ceiling
6
SPECIAL CEILINGS UNDER TIMBER ROOF
UNDER TIMBER JOISTS
Timber joist
Timber joist Thermal insulation
Suspended ceiling
Suspended ceiling
UNDER TRAPEZOIDAL DECKING ON STEEL BEAMS
UNDER GANG-NAIL TRUSS
Thermal insulation Trapezoidal decking Steel beam Suspended ceiling Suspended ceiling
UNDER TRAPEZOIDAL DECKING ON TIMBER JOISTS Thermal insulation Trapezoidal decking Timber joist Suspended ceiling CONCRETE-FILLED TRAPEZOIDAL DECKING ON STEEL BEAMS Trapezoidal decking Steel beam Suspended ceiling
7
FIRE TESTS
1200
Maximum 1100 K 1100
Temperature difference in the furnace (K)
1000 900
Minimum 900 K
800 700 600 500
The light-weight suspended ceiling and the grid construction located above are installed and tested in a fire chamber.
400 300
The tests are conducted on the basis of a so-called “standard temperature curve” (see image) in nationally and internationally accredited test institutes.
200 100 0
10
20
30
40
50
60
70
80
90
100
Test duration (min)
Standard temperature curve
PREREQUISITES FOR CLASSIFICATION
The suspended ceiling must remain intact for the entire duration of the test. The deflection of the suspended ceiling must not exceed the permitted maximum loading. The surface temperature rise on the side opposite the fire must be no greater than 140 K on average and no greater than 180 K at any measurement point.
8
DEPENDENCE OF STRUCTURAL FIRE PROTECTION ON THE SOFFIT III
Reinforced concrete d=50 mm
Reinforced concrete d=50 mm
Fire resistance class
Ceiling module size
System solution
Test certificate No.
Thickness
Aerated concrete d=125 mm
II
Building material class
I
TEST CERTIFICATES
AMF panels
mm
mm
Further test certificates are available from AMF Technical support on request Tel: +49 (0) 8552 - 422 - 53
Soffit type as per DIN 4102
SYSTEM A - CONCEALED SYSTEM F120-AB
F120-AB
F90-AB
F90-AB
F90-AB
F90-A
F90-A
F90-A
F120-AB
F120-AB
A2 s1,d0
15 600 x 600 625 x 625 and rips
ABP P - 3096 / 0968 74329
A2 s1,d0 A2 s1,d0
15
ABP P - 3777 / 7779 MPA BS 801277
A2 s1,d0
15
ABP P - 3775 / 7759 MPA BS 732741
SYSTEM C - EXPOSED SYSTEM
F90-AB F90-A
F90-AB
F90-AB
A2 s1,d0
F90-A
F90-A
A2 s1,d0
F90-AB
F90-AB
A2 s1,d0
1200 x 600 1250 x 625 and rips 15
ABP P - 3778 / 7789 MPA BS 801279
F90-A
Ceiling module size in mm
F90-A
15
1250 x 625 625 x 625
Thickness in mm
SYSTEM C - EXPOSED SYSTEM
A2 s1,d0
ABP P - 3769 / 7699 MPA BS 3159 / 1519a MN
Timber joists
Timber roof
Building material class
SPECIAL CEILINGS
Tested certificate No.
SYSTEM C – EXPOSED SYSTEM F60 -B
F90 -B
A2 s1,d0
15
A2 s1,d0
40
A2 s1,d0
15
3019 / 893 / 09 625 x 625 and rips
ABP P - 3097 / 0978 3387 / 2882
SYSTEM C – EXPOSED SYSTEM F30 -B
under gang-nail truss
600 x 600 625 x 625 and rips
3478 / 7612
9
STRUCTURAL FIRE PROTECTION
In the case of structural fire protection, not only the suspended ceiling but also the structure as a whole is of relevance to the achievement of a particular fire resistance class. AMF ceilings achieve building component classifications of F30 to F120 depending on the type of soffit. We have developed special fire protection ceilings for certain applications:
AMF FIRE PROTECTION CEILINGS THERMATEX System F30 under gang-nail truss System F90 under timber roof / trapezoidal decking
10
11
SYSTEM F30 under gang-nail truss 5
9 8
2
4
1
3
6 7
1
AMF - THERMATEX panel, 15 mm
2
Main runner, 24 x 38 mm
3
Cross tee, 24 x 38 mm
4
Wall trim, 24 x 24 mm
5
Quick-assembly suspension hanger
6
Max. module dimension, 625 mm
7
Max. module dimension, 625 mm
8
Max. distance between hangers, 1250 mm
9
Max. distance between main runners, 1250 mm
Test certificates must be adhered to.
Edge details
SK 24
VT 24
Exposed System Having further developed and recertified the tried-and-proven F30 under gang-nail truss System in both the recessed and square-edged versions, we have not only secured a decisive technical advantage on the market both for ourselves and for you, but also achieved a range of rationalization effects. You will benefit from these in a number of ways! AMF has tested the exposed System C for F30 under gang-nail truss in various applications, e.g. discount and regular supermarkets, factories and workshops, etc. … . AVAILABLE FORMATS 625 x 625 mm, further formats available on request AVAILABLE SURFACE PATTERNS
Rock wool / glass wool
120 mm
Battens
40 / 60 mm
Max. distance between battens
1250 mm
Fastening method
Grooved nails (or Spax)
Suspension height from lower edge of battens to upper edge of mineral fibre panel 110 mm Max. distance between main runners
1250 mm
Max. distance between hangers
1250 mm
AMF ceiling panel
15 mm
Max. format size
625 x 625 mm
Edge
VT / SK
THERMATEX Fine Stratos Fine Stratos micro Star Mercure
SK: square-edged, VT: recessed, GN: concealed, AW: shiplap. Please observe the test certificates and installation instructions in the Ceiling Systems Catalogue. Further accessories available as per price list!
12
Fire resistant light boxes for recessed fittings for fire protection ceilings, all as per test certificates EA24 External corner for RWL 24 / 24
EI24 Internal corner for RWL 24 / 24
EA-S External corner for SRW 25 / 15 / 8 / 15
EI-S Internal corner for SRW 25 / 15 / 8 / 15
Module size:
600 x 600 mm / 625 x 625 mm / 1200 x 600 mm 300 x 1200 mm / 312,5 x 1250 mm Panel thickness: 19 mm Internal height: 100 mm Other formats and heights available on request
Lid 19 mm Side panels
Further wall trims available! Wall angle RWL 31 / 31
Shadow trim SRW 20 / 20 / 20 / 20
Recessed fitting, e.g. luminaire Fix the bottom edge of the side panels with gypsum plaster or intumescent mastic.
Shadow trim SRW 25 / 15 / 8 / 15
For VT
pre-notched for tee-section
Test certificates must be adhered to.
Filler piece FUE - 15 / 24
Wall trims / Hangers…
DoS or DoH
SNA
SHD
Fire Resistant Light Box
ANo ANu
DoS or DoH BS 10 SNA
SAH - 5
13
SYSTEM F90 under timber joists / trapezoidal decking TIMBER JOISTS CEILING
11
10
5
9
2
8
4
1 3
7 6
1 2 3 4 5 6 7
AMF - THERMATEX panel, 40 mm Main runner, 24 x 38 mm Cross tee, 24 x 38 mm Wall trim, 24 x 24 mm
8
Quick-assembly suspension hanger Max. module dimension, 625 mm Max. module dimension, 625 mm
10
9
11
Max. distance between hangers, 900 mm Max. distance between main runners, 625 mm Timber joist Covering boards (24 mm), or particle board (19 mm)
Test certificates must be adhered to.
Under Timber Joists The AMF F90 functional ceiling under timber joists or trapezoidal decking is equally suited for installation in old buildings and modern industrial halls. Stringent demands on fire resistance are often made when renovating old buildings with timber roofs. Using the F90 functional ceiling as per certificate under timber you can achieve the fire resistance class F90, even for old buildings, without having to clad the timber joists. This ceiling is also outstandingly suited for installation under trapezoidal decking, as used in modern industrial buildings.
AVAILABLE FORMATS 600 x 600 / 625 x 625 mm, further formats available on request AVAILABLE SURFACE PATTERNS THERMATEX Fine Stratos, micro Star
SK: square-edged, VT: recessed, GN: concealed, AW: shiplap. Please observe the test certificates and installation instructions in the Ceiling Systems Catalogue. Further accessories available as per price list!
14
TRAPEZOIDAL DECKING ON E.G. STEEL BEAMS
TIMBER JOISTS CEILING WITH PLASTER Cladding of the wooden beams with lathwork 12
12
11 11
10
10 5 5 9 9 2
8
4
1
2
8
4
3
1 3
7 6
7 6
1 2 3 4 5 6 7
AMF - THERMATEX panel, 40 mm Main runner, 24 x 38 mm Cross tee, 24 x 38 mm Wall trim, 24 x 24 mm
8
Quick-assembly suspension hanger Max. module dimension, 625 mm Max. module dimension, 625 mm
10
9
11 12
Max. distance between suspension hangers, 900 mm Max. distance between main runners, 625 mm
1
Lathwork Timber joist Covering boards (24 mm), or particle board (19 mm)
5
2 3 4
6 7
AMF - THERMATEX panel, 40 mm Main runner, 24 x 38 mm Cross tee, 24 x 38 mm Wall trim, 24 x 24 mm
8
Quick-assembly suspension hanger Max. module dimension, 625 mm Max. module dimension, 625 mm
10
9
11 12
Max. distance between hangers, 850 mm Max. distance between main runners, 625 mm Steel beam Purlin Mineral wool insulation
Test certificates must be adhered to.
Fire Resistant Light Box
Under Trapezoidal decking
Lid 40 mm Side panels
Fix the bottom edge of the side panels with gypsum plaster or intumescent mastic.
Recessed fitting, e.g. luminaire
Flush-mounted light fitting with fire protection; certified as F90 under timber joists and F90 under purlins. Module size: 600 x 600 mm / 625 x 625 mm Panel thickness: 40 mm Internal height: 80 mm Other formats and heights available on request Must be installed as per the test certificate!
15
INDEPENDENT FIRE PROTECTION
Independent fire protection ceilings, for example, “light-weight suspended ceilings“, fulfil the requirements for fire protection from both the ceiling void (ceiling cavity) and from the underside of the ceiling. Installations like light fittings, manholes, loudspeakers, pictograms, etc. as well as all connections (such as connectors to light partitions, bulkheads, etc.) also need to be tested and classified.
AMF FIRE PROTECTION CEILINGS F30 Uno / + Metal F30 Dual + Metal F30 Mono
16
In the event of a fire emanating from the ceiling void (the most frequent fire load by the way), AMF fire protection ceilings protect the escape routes below for 30 minutes protected. These independent fire protection ceilings are rated and classified as “smoke proof“.
17
System solution
For fire loads from below, the fire resistance class of the „suspended ceiling only“ is valid for all ceiling and roof constructions located above.
A fire load is applied in the ceiling void. The ceiling or roof construction located above must have at least the same F- class.
mm
Fire resistance class
Further test certificates are available from AMF’s Application Technology Dept. on request Tel: +49 (0) 8552 - 422 - 53
Fire load from above
Ceiling module size
Fire load from below
Test certificate No.
AMF panels
Thickness
“Suspended ceiling only“ as per DIN 4102
Building material class
TEST CERTIFICATES
mm
AMF - SYSTEM F30 MONO Exposed system
F30 -B A2 s1,d0
F30 -A
40 F30 -B F30 -A
A2 s1,d0
1250 x 625 and 625 x 625
ABP P - 3099 / 0998 1977 / 3405 ABP P - 3100 / 1008 1987 / 3406
AMF - SYSTEM F30 UNO / + METAL Self-supporting construction
F30 -B A2 s1,d0
F30 -A
3281/8179 40
600 x 1400
F30 -B F30 -A
A2 s1,d0
3020/5469
A2 s1,d0
3448/7312
AMF - SYSTEM F30 UNO / + METAL Self-supporting construction
F30 -B F30 -A
40 F30 -B F30 -A
300 x 1800
A2 s1,d0
3924/6901
A2 s1,d0
ABP P - 3540 / 5408 3823 / 5340
AMF - SYSTEM F30 DUAL + METAL Removable + swing down construction
F30 -B F30 -A
108 F30 -B F30 -A
300 x 2500 ABP P - 3541 / 5418 3633 / 5071
A2 s1,d0
AMF - SYSTEM F30 DUAL + METAL Wall bracket
F30 -B F30 -A F30 -B F30 -A
18
A2 s1,d0 87 or 108 A2 s1,d0
ABP P - 3545 / 7982 7391 / 5996 300 x 2500 ABP P - 3780 / 7809 7392 / 6006
WALL BRACKETS
HORIZONTAL WALL BRACKET
ANGLED WALL BRACKET
Solid wall
3
3
2
1
2
1 2 3
Fire protection element Horizontal wall bracket Solid wall
1 2 3
1
Fire protection element Angled wall bracket Bulkhead
Advantages at a Glance trouble-free installation with no suspension hangers from the soffit adjustable wall bracket for single or twin margin reduction in costs thanks to fewer lengths paneling with fireboard panels horizontal - 16 - 26 cm, 90º adjustment range angled - 11 -18 cm, 45º adjustment range fastening to solid wall by means of sets of 2 dowels and screws, e.g. KDM 6 / 80 every 625 mm or less fastening to light-weight partitions my means of sets of 2 screws to metal studs 5.5 / 70 mm; max. distance between studs: 625 mm
19
SYSTEM F30 UNO / + METAL
2
1
6
Re
3
5
info are rcem e into facto nt pr the r y-fi ofile ele tted s me nts .
4
1
2 3 4 5 6
600 x 1400 x 40 mm or 50 mm Uno element for METAL FACE 40 mm THERMACOR panel 50 or 100 mm bandraster Reinforcement profile Bandraster at 1482 mm centres Nonius hangers every 700 mm
600 x 1400 mm Uno Element 1
600 x 1400 x 50 mm Uno element
1
600 x 1400 x 40 mm Uno element
2
METAL FACE 100 mm bandraster
2 3
100 mm bandraster Bandraster at 1482 mm centres
Bandraster at 1482 mm centres 50 mm THERMACOR panel
4
40 mm THERMACOR panel
3 4 5
1
5
2
3
1
AVAILABLE SURFACE PATTERNS THERMATEX Fine Stratos Fine Stratos micro Star Metal in white similar to RAL 9010, plain Metal in white similar to RAL 9010, perforated
3
4
2
600 x 1400 x 50 mm Uno element METAL FACE Fill 50 mm bandraster with plaster Bandraster at 1432 mm centres 1
1 2
3
600 x 1400 x 40 mm Uno element Fill 50 mm bandraster with plaster Bandraster at 1432 mm centres
1
2
3
4
2
SK: square-edged, VT: recessed, GN: concealed, AW: shiplap. Please observe the test certificates and installation instructions in the Ceiling Systems Catalogue. Further accessories available as per price list!
20
3
40
2
4
50
1
40
AVAILABLE FORMATS 600 x 1400 mm 300 x 1800 mm, further formats available on request
4
50
The biggest advantage of System F30 Uno is its fire protection capacity from above and below. When a fire attack occurs from above, i.e. from the ceiling void, the lifesaving escape routes remain free of smoke and heat. When a fire attack occurs from below, the services in the ceiling void are protected.
3
BULKHEAD 4
7
5
6
8 1
2 2
3
2
1
4
Au
1
sst
eifu n im gspro Re Ele fi info me le sin rce nt me inte d we nt p g ri rkse into rofi ert itig l e t 5 he e s are lem fa ent ctor s. y-fi 5 tte d
3
3
2 6 1 2 3 4
Uno element Wall trim
5
Plasterboard panel U-shaped profile
7
Mineral wool C-shaped wall stud
6
Soffit Solid wall or light partition
8
4
MARGIN
4
7 8 3
4
1 2 3 4 5 6
Vernier suspension hangers every 700 mm
300 x 1800 x 50 mm Uno element 100 mm bandraster
1
3
4
Bandraster at 1882 mm centres THERMACOR panel
5
METAL FACE
Uno element
5
U-shaped profile
Wall trim C-shaped transverse ceiling profile, separation a=400 mm Solid wall or light partition
6
Fireboard panel Nonius hangers every 680 mm C-shaped profile Levelling connector
2
4
7
8 9
Perimeter detail WALL BRACKET
300 x 1800 x 40 mm Uno element 100 mm bandraster
5
Bandraster at 1882 mm centres THERMACOR panel
See Page 19 for details 3
160
3
2
2 3
300 x 1800 mm Uno Element
2
6
1
4
1
1
5
300 x 1800 x 40 mm Uno element 40 mm THERMACOR panel 50 or 100 mm bandraster Reinforcement profile Bandraster at 1882 mm centres
9
4
6
1
7 4
4
2
5
2
40
1 50
1
2
3
≈ 187 - 287
3 1
3 4
5
3 4
12.5 mm Fireboard
7
300 x 1800 x 50 mm Uno element
300 x 1800 x 40 mm Uno element
2
Fill 50 mm bandraster with plaster Bandraster at 1832 mm centres METAL FACE
2
Fill 50 mm bandraster with plaster Bandraster at 1832 mm centres
1
3
4
6
Approved fixings according to statical requirements Wall bracket Solid wall or light partition
1 40
2
Uno element Wall trim 15 mm Fireboard
1
50
1
Uno element
2
3
2
3
max. Ø 70 mm
Recessed fittings with fire resistant light boxes for mineral and metal
21
SYSTEM F 30 DUAL + METAL
4
1010
55
12
11 9 3
88 7 6
2
1
4 5 6
11
Flush-mounted light fitting Spacer strip (mineral) Light box (mineral) Adjustable shadow trim Fireboard strip Wall insulation with intumescent strip
12
Wall insulation with mineral wool
7 8 9 10
EU-ZERTIFIZIERT
Panel head filler Gypsum board margin Lighting element
SRW AK adjustable with edge overlap
23
3
9
2
Modular elements comprising 39 mm thick mineral panels at top and bottom Steel edge profile
42
1
2 -37 7
24
Construction
The AMF System F30 Dual fire protection ceiling fulfils all the building component classification requirements as per DIN 4102 and EN 1364-2 both from above, the void, and from below, in the case of room fires. They therefore take into consideration the often neglected fire hazard arising from the presence of materials such as electrical cables, conduits and data cables in the ceiling void, some of which can be highly flammable. This ready-to-install system eliminates time-consuming and costly installation work. Attachment of the modular elements to solid walls or light partitions is fast and trouble-free - even for extra long spans - thanks to shadow trims. Installation options include tested and firesafe integrated lighting systems.
AVAILABLE FORMATS 300 x 1200 - 2500 mm, further formats available on request AVAILABLE SURFACE PATTERNS THERMATEX Metal in white similar to RAL 9010, plain Metal in white similar to RAL 9010, perforated
SK: square-edged, VT: recessed, GN: concealed, AW: shiplap. Please observe the test certificates and installation instructions in the Ceiling Systems Catalogue. Further accessories available as per price list!
22
SWING-DOWN DUAL ELEMENT 1
DEMOUNTABLE DUAL ELEMENT 1
Plasterboard
Intumescent strip Alternative: perimeter detail with mineral wool
19 47 19 87
1
Plasterboard
2
Intumescent strip Alternative: perimeter detail with mineral wool
1
Light F30 partition
Solid wall or light partition
2
2
Corridor length
2
Corridor width
Adjustable shadow trim with material thickness of 2.0 mm on the wall side. Fastening to the solid wall by means of dowels and screws at max. 210 mm intervals.
Wall connection towards the end of the corridor with slimmer modular element widths due to unfavourable ceiling proportions and without compensating margin.
MARGIN
DEMOUNTABLE DUAL ELEMENT
1
1
19 47 19 87
Light F30 partition
2
Corridor width
42/20/23/24 mm shadow trim, material thickness 1.5 mm. Fastening to solid walls by means of dowels and screws at max. 210 mm intervals. At light partitions, use sets of 2 drywall screws, e.g. 4.2 x 35 mm, in the region of the studs, a F30 (metal stud wall) or solid wall
Parallel Bandraster
5
1
Dual element
2
Steel edge profile Panel head filler Bandraster Mineral wool
3 4 5
3 4
2 1
Light F30 partition
For rooms and corridors with a width greater than 2500 mm it is possible to use a parallel bandraster construction both with solid and light walls. Bandraster profiles of 50 / 75 / 100 / 125 mm width can be used. In applications such as this the bandraster profiles should be installed with AMF strips and mineral wool. This construction type also allows trouble-free access to the ceiling void by removal of the AMF module elements. A swing-down construction is also possible using a special bandraster.
2 3
4 1 2 3
Intumescent strip Fireboard panel Mineral wool
1
5 4 5
Thermacor strips Bandraster
25
SYSTEM F30 MONO
5
9
8 4
1
2
3
7 6
1
Mono panel
2
Covering strip (factory fitted) Cross profile Wall trim, 24 x 24 mm Quick-assembly suspension hanger Max. module dimension, 625 mm
3 4 5 6 7 8 9 10
10
Max. module dimension, 625 mm Suspension spacing, alternating between 750 and 500 mm Max. distance between main runners, 625 mm Main runner
Construction The AMF System F30 Mono fire protection ceiling is an independent system that offers optimum safety and economy. This means that in the event of a fire in the ceiling void, the System F30 Mono fire protection ceiling will protect the life-saving escape routes below; conversely - in the event of a fire from below - it will protect the services installed in the ceiling void.
AVAILABLE FORMATS 600 x 600 / 625 x 625 mm, further formats available on request AVAILABLE SURFACE PATTERNS THERMATEX Fine Stratos Fine Stratos micro Star
SK: square-edged, VT: recessed, GN: concealed, AW: shiplap. Please observe the test certificates and installation instructions in the Ceiling Systems Catalogue. Further accessories available as per price list!
26
750 500
625
mm
Fire-resistant light box for recessed luminaires. Module size: 600 x 600 mm / 625 x 625 mm Panel thickness: 40 mm Internal height: 80 mm Other formats and heights available on request
mm
mm
Demountable panel
AMF Mono panels without cover strips
Lid 40 mm Side panel
Recessed fitting, e.g. luminaire
Fix the bottom edge of the side panels with gypsum plaster or intumescent mastic.
AMF Mono panels with cover strips applied on all sides
For fire loads only from above, main profile separation = 1250 mm, otherwise as per test certificate For fire loads only from below or from below and above, main runner spacing = 625 mm, otherwise as per test certificate
Perimeter detail
Fire Resistant Light Box
WALL BRACKET
Detail for installation of recessed light fittings for exposed grid system (System C installation, SK-type edge)
5
See Page 19 for details 160
3 4
6
1
max. 5mm
7
2
≈ 187 - 287
Mono element Module dimension
1 2 3 4
Mono panel Wall angle bracket 15 mm Fireboard panel 12.5 mm Fireboard panel
5
6 7
Approved dowels according to statical requirements Wall bracket Solid wall or light partition
For installations like lighting, ventilation, sprinkler facilities, etc., the height of the base must not exceed 5 mm.
27
AMF PROJECTS GERMANY
INLAND REVENUE OFFICE, WIESBADEN AMF Project
Wiesbaden Inland Revenue Office
Contractor
State Construction Office of Wiesbaden
AMF Product
Hinged dual / metal in white, perforated
Quantity
2,000 m2
28
GENERAL NOTES
DRAFT SPECIFICATIONS AND TECHNICAL INFORMATION
IMPORTANT ADVICE Due to reproduction processes colours shown in this catalogue may differ from the actual product colour. Product selection should always be made using AMF samples. All details and technical information stated in this brochure or other publicity material referring to AMF ceiling systems are based on test reports obtained under laboratory conditions. All system details conform with current technology and are based on the use and compatibility of AMF products and system components used in both internal and external tests. AMF accepts no liability or responsibility for use of third party components, or for any variations to conditions stipulated in test data. We recommend not to mix production batches on projects.
For copies of draft specifications please telephone +49 (0) 1805 - 54 22 00 fax +49 (0) 1805 - 54 22 55, email
[email protected] http://www.amfceilings.com Full technical information, assessments, test reports, samples etc. are available on request. We recommend you consult AMF staff for all AMF systems subject to authoritative approval!
All technical data is subject to change without prior notice and is governed by AMF Terms and Conditions of Sale. This catalogue supersedes all previous editions. Errors and omissions excepted. Printing errors excepted.
1
Details siehe Systemlösungen. Technische Bestimmungen Seite 48-49 Programm Teil 1
29
KNAUF AMF SALES ORGANISATION Knauf AMF GmbH & Co. KG Postal address: Postfach 1263, D-94476 Grafenau Business address: Elsenthal 15, D-94481 Grafenau
Knauf AMF Office Grafenau Sales Code +43 Central Sales Region (Southern Germany, Austria, Switzerland) Fritz Schneck Mobile: (0) 171 - 6 12 95 92 Eduard Schönberger Tel.: (0) 85 52 - 422 26 Roland Biebl Tel.: (0) 85 52 - 422 14 Olga Eibl Tel.: (0) 85 52 - 422 972 Michael Lentner Tel.: (0) 85 52 - 422 925 Northern Sales Region (Northern Germany, Benelux, Scandinavia) Karl-Heinz Kuhn Mobile: (0) 171 - 6 12 36 30 Thomas Moser Tel.: (0) 85 52 - 422 78 Sandra Stockinger Tel.: (0) 85 52 - 422 56 Jakob Reitberger Tel.: (0) 85 52 - 422 57 Western Sales Region (Western Europe, America, Middle East, Africa) Karl Wenig Mobile: (0) 171 - 9 35 49 60 Klaus Scholz Tel.: (0) 85 52 - 422 19 Georg Laudi Tel.: (0) 85 52 - 422 66 Martin Riedl Tel.: (0) 85 52 - 422 981 Marion Sammer Tel.: (0) 85 52 - 422 967 Tamara Eder Tel.: (0) 85 52 - 422 941 Johanna Hartl Tel.: (0) 85 52 - 422 901 Eastern Sales Region (East Europe, Northern Asia, Far East) Karl Wenig Mobile: Christoph Cieply Tel.: Silvia Raab Tel.: Nataliya Eberl-Tsvyk Tel.: Andreas Riedl Tel.: Sergej Kalina Tel.: Gennadi Marksitzer Tel.: Stefan Blöchl Tel.: Karin Urbanek Tel.:
Knauf AMF - Office Dresden Lars Streubel Knauf AMF - Office Frankfurt Fridolin Helfenbein Knauf AMF - Office Mannheim Ivo Bährle Knauf AMF - Office Nürnberg Christian Veith Knauf AMF - Office Karlsruhe Stefan Lemler Knauf AMF - Office Stuttgart Marcus Kaufmann-Bertsche Knauf AMF - Office München Bernhard Jahnel Knauf AMF Austria Norbert Schiffauer
Marc Peeters
Code +32 Mobile: (0) 476 - 22 76 94 e-mail:
[email protected] Code +31 Mobile: (0) 6 - 100 35789 e-mail:
[email protected]
Western Sales Knauf AMF Italy
Fabrizio Chiesa Tommaso Di Bernardo Massimiliano Cesetti Giovanna Toniolo
Code +39 Mobile: e-mail: Mobile: e-mail: Mobile: e-mail: Mobile: e-mail: Mobile: e-mail:
348 - 41 12 099
[email protected] 340 - 40 01 342
[email protected] 340 - 40 01 319
[email protected] 340 - 40 01 312
[email protected] 331 - 57 44 314
[email protected]
Mobile: e-mail: Mobile: e-mail: Mobile: e-mail: Mobile: e-mail: Mobile: e-mail: Mobile: e-mail: Mobile: e-mail: Mobile: e-mail: Mobile: e-mail:
(0) 6 - 16 31 94 66
[email protected] (0) 6 - 09 86 04 86
[email protected] (0) 6 - 08 00 39 13
[email protected] (0) 6 - 27 32 21 03 glescoffi
[email protected] (0) 6 - 15 04 93 18
[email protected] (0) 6 - 09 03 89 71
[email protected] (0) 6 - 24 29 24 61
[email protected] (0) 6 - 34 61 57 19
[email protected] (0) 6 - 16 01 90 51
[email protected]
Knauf AMF France
Marketing / Advertising Marlene Egginger Carina Sieghart
Tel.: (0) 85 52 - 422 994 Tel.: (0) 85 52 - 422 988
Consignment / Dipatch Michael Winter Thomas Kliemsch Christina Weber Erich Fürst Stefanie König
Tel.: Tel.: Tel.: Tel.: Tel.:
(0) 85 52 - 422 16 (0) 85 52 - 422 22 (0) 85 52 - 422 902 (0) 85 52 - 422 957 (0) 85 52 - 422 909
Product Management / Technical Support Andreas Schiedeck Tel.: (0) 85 52 - 422 982 Andreas Niermann Tel.: (0) 85 52 - 422 977 Wilhelm Holzinger Tel.: (0) 85 52 - 422 53 Stefan Schmidl Tel.: (0) 85 52 - 422 74 Markus Mück Tel.: (0) 85 52 - 422 976 Internat. Communication / Standard nature Alexander Mayer Tel.: (0) 85 52 - 422 54
Knauf AMF Technical Offices
Jean-Christophe Cornu Philippe Paillart Olivier Lecourt Gilles Lescoffier Patrice Cordon Pierre Laxalde Christian Kernevez Stéphane Cavrero Christophe Alignol
Knauf AMF Germany Code +49 Knauf AMF - Office Hamburg Mobile: (0) 171 - 617 30 83 Hans Stach e-mail:
[email protected] Knauf AMF - Office Bremen / Oldenburg Stefan Seehafer Mobile: (0) 160 - 96 88 73 54 e-mail:
[email protected] Knauf AMF - Office Hannover Mobile: (0) 170 - 438 59 71 Antonius Sprenger-Pieper e-mail:
[email protected] Knauf AMF - Office Berlin Mobile: (0) 175 - 578 93 84 Martin Bierhoff e-mail:
[email protected] Knauf AMF - Office Düsseldorf Mobile: (0) 171 - 315 45 40 Manuel Schons e-mail:
[email protected] Knauf AMF - Office Leipzig Mobile: (0) 171 - 612 03 36 Axel List e-mail:
[email protected]
Code +33
Knauf AMF Greece Aggelos Sinodinos
Central / Northern Sales
30
Code +43
Knauf AMF Netherlands Koen Van de Pol
(0) 171 - 23 58 300
[email protected] (0) 171 - 612 03 53
[email protected] (0) 171 - 30 22 652
[email protected] (0) 171 - 45 865 77
[email protected] (0) 171 - 613 36 49
[email protected] (0) 160 - 90 98 6463
[email protected] (0) 151 - 17 41 05 73
[email protected]
Mobile: (0) 664 - 344 53 50 e-mail:
[email protected]
Knauf AMF Benelux
Giorgio Marenco (0) 171 - 9 35 49 60 (0) 85 52 - 422 21 (0) 85 52 - 422 67 (0) 85 52 - 422 64 (0) 85 52 - 422 17 (0) 85 52 - 422 65 (0) 85 52 - 422 62 (0) 85 52 - 422 73 (0) 85 52 - 422 995
Mobile: e-mail: Mobile: e-mail: Mobile: e-mail: Mobile: e-mail: Mobile: e-mail: Mobile: e-mail: Mobile: e-mail:
Knauf AMF Uk Peter Harris Peter Symons Alan Davidson Nichola Dalton Elaine Barker Jeff Hall
Code +30 Mobile: 697 - 286 9796 e-mail:
[email protected] Mobile: e-mail: Mobile: e-mail: Mobile: e-mail: Mobile: e-mail: Mobile: e-mail: Mobile: e-mail:
Code +44 (0) 7876 - 50 7198
[email protected] (0) 7876 - 025 841
[email protected] (0) 7780 - 970 000
[email protected] (0) 7789 - 865 837
[email protected] (0) 7789 - 007 610
[email protected] (0) 7876 - 050 903
[email protected]
Knauf AMF Spain / Portugal Luis Cabañero Moreno Fernando Valdivia Daniel López Miguel Fernández
Code +34 Mobile: e-mail: Mobile: e-mail: Mobile: e-mail: Mobile: e-mail:
Knauf AMF Middle East Sreejith Panicker Khalid Khatri Knauf AMF Turkey İlhan Yasar Burak Oncu Yasin Donmez
Code +971 Cel: e-mail: Cel: e-mail:
50 6407172
[email protected] 50 7085757
[email protected]
Mobile: e-mail: Mobile: e-mail: Mobile: e-mail:
Code +90 533 - 430 87 68
[email protected] 533 - 332 9195
[email protected] 533 - 332 9196
[email protected]
Knauf AMF Iran Martin Riedl Saeed Mirali Akbar
Mobile: e-mail: Mobile: e-mail:
+49 (0) 175 - 46 71 174
[email protected] 912 - 45 85 301
[email protected]
Mobile: (0) 18 21 535 21 e-mail:
[email protected]
Cel: e-mail: Renata Caputo Cardoso Cel: e-mail: Paula Epíscopo Omizzolo Cel: e-mail: Rafael Bueno Carvalho Cel: e-mail: Viviana Barbagelata Del Carpio Cel: e-mail:
Code +55 11 9203 - 6605
[email protected] 11 9296 - 0826
[email protected] 11 9265 - 6461
[email protected] 11 9286 - 0473
[email protected] 11 9173 - 6941
[email protected]
Eastern Sales Code +420 602 227 613
[email protected] 602 650 938
[email protected] 602 553 930
[email protected]
Knauf AMF Poland Krzysztof Szczepaniak
Code +48 (0) 602 592 706
[email protected] (0) 602 575 077
[email protected] (0) 602 551 510
[email protected]
Mobile: e-mail: Mobile: e-mail: Mobile: e-mail:
Knauf AMF Latvia / Estonia Ivars Šmalcs
Knauf AMF Hungary Miklòs Laczka László Mohai Knauf AMF Slovenia / Bosnia Aleš Gabrovšek
Knauf AMF Bulgaria / Macedonia Jawor Otaschlijski Mobile: e-mail: Kiril Gyuzelev Mobile: e-mail: Knauf AMF Romania / Moldavia Trajan-Florin Vujdea Monica Minoiu Florian Ilie Dragomir
Mobile: e-mail: Mobile: e-mail office: Mobile: e-mail:
Knauf AMF Russia Alexey Prokhorov Alexander Gnesdilov Evgeni Pavlov Sergej Rakov Oksana Geraschenko Knauf AMF Ukraine Maria Bokun Yuri Zimin
Knauf AMF South East Asia Hugo Chang
Teddy Dsouza Chandra Panchani Dipankar Shome Knauf AMF Australia Fabian Propoggia
Code +40 (0) 744 - 303 600
[email protected] (0) 745 - 944 611
[email protected] (0) 745 - 669 942
[email protected] Code +7
Mobile: e-mail: Mobile: e-mail: Mobile: e-mail: Mobile: e-mail: Mobile: e-mail:
(8) 910 - 465 83 58
[email protected] (8) 916 424 45 04
[email protected] (8) 911 - 734 74 74
[email protected] (8) 912 997 22 22
[email protected] (8) 988 - 510 33 35
[email protected]
Mobile: e-mail: Mobile: e-mail:
Code +380 (0) 44 - 203 1618
[email protected] (0) 50 - 331 8687
[email protected]
Knauf AMF China Liu Xin
Code +359 (0) 888 - 21 99 79
[email protected] (0) 887 - 56 28 57
[email protected]
Code +86 Mobile: 1 38 17 69 75 28 e-mail:
[email protected] Code +886 Mobile: 9 32 15 60 66 e-mail:
[email protected] Code +91 Mobile: e-mail: Mobile: e-mail: Tel.: e-mail:
(0) 9867 1565 64
[email protected] (0) 9818 5851 82
[email protected] (0) 9343 5163 11
[email protected]
Code +61 Mobile: (0) 433 30 52 22 e-mail:
[email protected]
Code +371 Mobile: (0) 291 - 32 227 e-mail:
[email protected]
Knauf AMF Lithuania Virginijus Šiugžda
Code +385 Mobile: (0) 91 - 638 14 22 e-mail:
[email protected]
Knauf AMF India
Knauf AMF Czech Republic / Slovakia Petr Fitzner Mobile: e-mail: Libor Holub Mobile: e-mail: Petra Ostra Mobile: e-mail:
Wojciech Krzyzowski
Knauf AMF Croatia Igor Cvek
Code +20
Knauf AMF Brazil Fábio Miceli Teixeira
Michal Czachor
Knauf AMF Serbia and Montenegro Code +381 Dejan Popovič, dig. Mobile: (0) 11 - 344 16 13 e-mail:
[email protected]
Code +98
Knauf AMF Africa Wael El-Gamel
609 - 51 29 28
[email protected] 609 - 70 02 22
[email protected] 690 - 61 51 56
[email protected] 609 - 00 66 39
[email protected]
Code +370 Mobile: (0) 61 22 12 21 e-mail:
[email protected] Mobile: e-mail: Mobile: e-mail:
Code +36 (0) 20 - 460 39 02
[email protected] (0) 20 - 264 18 70
[email protected] Code +386
Mobile: (0) 41 - 650 443 e-mail:
[email protected]
31
AMF PROGRAMME PERFORMANCE CEILINGS
PERFORMANCE CEILINGS
PERFORMANCE CEILINGS
More scope for innovation
More scope for innovation
More scope for innovation
CEILING SYSTEMS CATALOGUE
FIRE PROTECTION
ACOUSTICS
PROGRAMME PART 1
PROGRAMME PART 2
PROGRAMME PART 3
MADE IN GERMANY
MADE IN GERMANY
Part 1
MADE IN GERMANY
Part 2
Part 3
PERFORMANCE CEILINGS
PERFORMANCE CEILINGS
PERFORMANCE CEILINGS
More scope for innovation
More scope for innovation
More scope for innovation
HEALTH & HYGIENE
SOUND, LIGHT & E-TECH
MATERIAL & DESIGN
PROGRAMME PART 4
PROGRAMME PART 5
PROGRAMME PART 6
MADE IN GERMANY
MADE IN GERMANY
Part 4
Part 5
MADE IN GERMANY
Part 6
AMF APPLICATIONS PERFORMANCE CEILINGS More scope for innovation
EDUCATION
MADE IN GERMANY
Part 1
All Programme catalogues can be obtained by sending in the fax reply card or by download from www.amfceilings.com 32
PERFORMANCE CEILINGS M ore s c op e f or i n n ovat i on Knauf AMF GmbH & Co. KG Elsenthal 15 D-94481 Grafenau Germany
REPLY CARD FAX NO.: +49 (0) 85 52 / 422 - 32 Please send me information on:
Part 1 CEILING SYSTEMS CATALOGUE Part 2 FIRE PROTECTION Part 3 ACOUSTICS Part 4 HEALTH & HYGIENE Part 5 SOUND, LIGHT & E-TECH Part 6 MATERIAL & DESIGN
Please send me information on:
Please send me:
EDUCATION
AMF PRICE LIST
Name
Position
Company
Address
Town & Post Code
Telephone
E-mail
33
WWW.AMFCEILINGS.COM ENTER THE WORLD OF CEILINGS
WWW.AMFCEILINGS.COM Are you looking for specific information for your project?
Do you need information quickly?
Click LITERATURE to gain immediate access to AMF data.
Education Healthcare Commercial Whatever your project - the AMF website will find you a variety of solutions to match your requirements.
For ongoing projects:
Test reports Draft specifications Technical Information, brochures and downloadable data sheets
We offer you a user-friendly menu, a wide choice of designs and performance options. For Industry news
Latest events,
New products,
Projects and AMF company information.
And if you require further assistance just click on CONTACT US to communicate with our local Area Manager.
34
AMF PRODUCT INDEX PRODUCT
AMF PROGRAMME
B
Bandraster System I Beamex System
AMF PROGRAMME
N
Part 1 Ceiling Systems Catalogue Part 5 Sound,Light&E-tech
C
Cleanactive Clean Room Concealed System
PRODUCT
Net 4/8 Nevada
Part 6 Material&Design Part 6 Material&Design
P
Part 4 Health&Hygiene Part 4 Health&Hygiene Part 1 Ceiling Systems Catalogue
Pinhole Plain
Part 1 Ceiling Systems Catalogue Part 1 Ceiling Systems Catalogue
R D
Dual F30
Part 2 Fire Protection
E
Exposed System
Part 1 Ceiling Systems Catalogue
Part 6 Material&Design Part 2 Fire Protection Part 1 Ceiling Systems Catalogue Part 1 Ceiling Systems Catalogue Part 2 Fire Protection Part 2 Fire Protection Part 1 Ceiling Systems Catalogue Part 1 Ceiling Systems Catalogue
G
Gypsum
Part 6 Material&Design
H
Hygena
Part 6 Material&Design Part 6 Material&Design
S
F
Fibrafutura Fire resistance: steal beams Fine Fresko-Saturn Fine Stratos / -micro Fire resistance: timber joists Fire resistance: mezzanine floors Free Span System F Fresko
Ranura Rilievo
Soundmosaic Star Symetra System A System C System F System I
Part 5 Sound,Light & E-tech Part 1 Ceiling Systems Catalogue Part 6 Material & Design Part 1 Ceiling Systems Catalogue Part 1 Ceiling Systems Catalogue Part 1 Ceiling Systems Catalogue Part 1 Ceiling Systems Catalogue
T
THERMATEX Acoustic THERMATEX Alpha THERMATEX Comfort THERMATEX Comfort dB THERMATEX dB Acoustic THERMATEX Thermaclean S THERMATEX Thermofon
Part 3 Acoustics Part 3 Acoustics Part 3 Acoustics Part 3 Acoustics Part 3 Acoustics Part 4 Health&Hygiene Part 3 Acoustics
Part 4 Health&Hygiene U
K
Kombimetall
Uno F30
Part 2 Fire Protection
Part 3 Acoustics W
L
Laguna / -micro Light Ceilings Livada
WOOD Symetra
Part 6 Material&Design
Part 1 Ceiling Systems Catalogue Part 5 Sound,Light&E-tech Part 6 Material&Design
M
Mercure Metall Mono F30
Part 1 Ceiling Systems Catalogue Part 6 Material&Design Part 2 Fire Protection
35
AMF-PROGRAMME: Part 1 CEILING SYSTEMS CATALOGUE Part 2 FIRE PROTECTION Part 3 ACOUSTICS Part 4 HEALTH & HYGIENE Part 5 SOUND, LIGHT & E - TECH Part 6 MATERIAL & DESIGN
AMF APPLICATIONS: Part 1 EDUCATION
Knauf AMF GmbH & Co. KG Elsenthal 15 D-94481 Grafenau Germany Phone: +49 (0) 85 52 / 422 - 0 Fax: +49 (0) 85 52 / 422 - 32 e-mail:
[email protected] http://www.amfceilings.com