왘 Software MX4 SCADA’s exceptional flexibility maximizes your productivity by allowing optimal system architecture in the way that best suits you giving you access to powerful, dynamic features for both centralised and distributed processing.
Further Publications within the PLC Range Technical catalogues System Q, AnU/QnA, AnS/QnAS, FX family
Technical Catalogues
Product catalogues for programmable logic controllers and accessories for the MELSEC series
Technical catalogue Networks Product catalogue for Master and Slave modules as well as accessories for the use of programmable logic controllers in open networks and MELSEC networks
Additional Services You will find current information on updates, alterations, new items, and technical support on MITSUBISHI ELECTRIC's web pages (www.mitsubishi-automation.com). The products section of the MITSUBISHI home site includes various documentations of the whole product range by MITSUBISHI ELECTRIC as well as the current version of this catalogue on hand. All manuals and catalogues can be downloaded. The content is updated daily and to date is provided in German and English.
About this product catalogue Due to the constantly growing product range, technical alteration, and new or changed characteristical features, this catalogue is updated frequently. Texts, figures and diagrams shown in this product catalogue are intended exclusively for explanation and assistance in planning and ordering the operator terminals of the HMI series and the associated accessories. Only the manuals supplied with the units are relevant for installation, commissioning and handling of the units and the accessories. The information given in these documentations must be read before installation and commissioning of the units or software. Should questions arise with regard to the planning of modules described in this product catalogue, do not hesitate to contact the german branch of the MITSUBISHI ELECTRIC EUROPE B.V. in Ratingen or one of its distributors (see cover page). © MITSUBISHI ELECTRIC EUROPE B.V. 04/2004 (10th edition)
2
HMI
MITSUBISHI ELECTRIC
CONTENTS
HMI BASICS
INTRODUCTION AND CONFIGURATION
웇 Introduction of the HMI control units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 웇 HMI and networks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
GOT SERIES CONTROL TERMINALS 웇 웇 웇 웇
System description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Text display units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Panel description and specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Communications modules und adapters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
MAC E SERIES OPERATOR TERMINALS
웇 System description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 웇 Panel description and specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 웇 Industrial PC’s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
ACCESSORIES 웇 웇 웇 웇 웇 웇
Backlights, protective film sheets, keyboard extension. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 PROFIBUS/DP adapters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Profibus connector, interface boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Storage media . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Interface converter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
DIMENSIONS
웇 GOT series control units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 웇 MAC E series control units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 웇 Industrial PC’s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
PROGRAMMING SOFTWARE 웇 Visualisation software for GOT and FX-DU control units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 웇 Programming software for GOT series control units GT-Works . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 웇 Programming software for MAC E series control units E-Designer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 웇 Programming software for MAC E series control units E-View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 웇 Software-based HMI solution GT SoftGOT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 웇 Process visualisation software MX4 SCADA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
APPENDIX 웇 Order form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 웇 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
MITSUBISHI ELECTRIC
HMI
3
INTRODUCTION AND CONFIGURATION
BASICS
HMI Control Units for Human-Machine Communication The interface between human and technology Users of today’s factory automation systems want more and clearer information on the control systems of their plant and machinery. HMI control terminals and process visualisation software enable an informative dialogue between operator and machine, making them the ideal complement to the MELSEC PLC systems. HMI control units make factory system functions transparent, enabling the operator to monitor and edit process data quickly and easily. You can choose between HMI control units with text and graphical displays. Fully programmable function keys and displays make the units even more user-friendly. The units can be programmed and configured with a PC running the intuitive Windows-based programming software package. HMI units can be installed directly on your machines and require nearly no additional modules for connection to the PLC. They provide direct access to all information and process data, with text or graphical displays. An IP65 rating (and higher) ensures that the HMIs will always perform reliably, even under the toughest conditions.
Features 앬 Simple installation and user-friendly operation 앬 Broad range of applications 앬 Clear text and graphics process displays
앬 Report generation for quality control
and process data exchange
앬 Precise, informative messages and
instructions in error situations
TERMINAL GRAPHIC OPERATION
M CE A
E X T
POWER
MITSUBISHI
-. 0
POWER
NUM
F1
F2
F3
7
8
1
6
F4
3
2
4
5
9
Specifications
A985GOT
A975GOT
A970GOT
A950GOT A953GOT
F940WGOT
F940GOT
F940/943GOT F930GOT Handy-GOT
F930GOT
F920GOT
Display unit
TFT, 256-col.
TFT, 256-col.
SBD: STN, SBA: STN, 8-col. 8-col. LBA: EL, 2-col. LBD: STN, mono
TFT, 256-col.
STN, 8-col./mono backlit
STN, 8-col./mono backlit
STN, 2-col.
STN, 2-col. backlit
STN,2-col./ white/red backlit
Display format (W x H) / mm character height Resolution; characters x lines (pixles) Applicable PLC Applicable third party manufact.
246 x 184.5
211 x 158
211 x 158
115 x 86
155.5 x 87.8
115 x 86
115 x 86
117 x 42
117 x 42
60 x 30
200 x 75 160 x 60 (800 x 600) (640 x 480) All MELSEC PLC systems All major PLC manufacturers
160 x 60 (640 x 480)
40 x 15 (320 x 240)
60 x 14 (horiz.) 40 x 15 29 x 30 (vert.) (320 x 240)
40 x 15 (320 x 240)
15 x 5 (240 x 80)
30 x 5 (240 x 80)
16 x 4 (128 x 64)
Printer interface
Integrated
Integrated
Integrated
RS232C
RS232C
RS232C
RS232C
RS232C
Memory type External I/O connectors Real-time clock
Flash-RAM 8 Via PLC
Flash-RAM 8 Via PLC
Flash-RAM 8 Via PLC
Flash-RAM 2 Via PLC
Flash-RAM 3 Integrated
Flash-RAM 2 Integrated
Flash-RAM 2 Integrated
Flash-RAM 2 Integrated
Keyboard
Touch-panel
Touch-panel
Touch-panel
Touch-panel
Function keys
Up to 1900 touch-keys 1 (POWER) 2.35 kg
Up to 1200 touch-keys 1 (POWER) 1.7 kg
Up to 1200 touch-keys 1 (POWER) 1.78 kg
Up to 3000 touch-keys 1 (POWER) 1.0 kg
LED indicators Weight
4
HMI
— RS232C
Flash-ROM 2 Integrated Touch-panel Touch-panel Touch-panel Touch-panel Membrane/ Touch-panel Max. 50 touch- Max. 50 touch- Max. 50 touch- Max. 50 touch- 8/max. 50 touchkeys/screen keys/screen keys/screen keys/screen keys/screen 1 (POWER) 1 (POWER) 6 — 8 (green) 0.79 kg 1.0 kg 0.79 kg 0.3 kg 0.6 kg
RS232C Flash-ROM 2 Integrated Membrane 6 — 0.3 kg
MITSUBISHI ELECTRIC
INTRODUCTION AND CONFIGURATION
ETHERNET
MELSECNET
P R O F
I
PROCESS FIELD BUS
B U S
Supported Networks 앬 Modem Links Enables connections over larger distances. 앬 Ethernet and MAC-Net For connection of multiple MAC E control units to the PLC system in installations extending over larger areas. 앬 MELSECNET Enables high-speed access (up to 10 Mbaud) to the PLC from multiple locations via the A900GOT or the MAC E900T/E900VT/ E910T. 앬 Dual Driver support The MAC E series control units can be used e.g. as an interface between 2 systems. This feature is supported from O/S version 6 (not for MAC E50)
앬 PROFIBUS/DP
MAC E series control units can be connected as slaves in systems using the open field bus protocol. 앬 Multidrop-Net Enables programming and data logging from a central location using a PC; the individual stations operate autonomously and independently of one another. 앬 No-Protocoll-Link Enables connection of barcode readers and other serial devices to the PLC via the MAC E series control units. 앬 A-BUS/Q-BUS Direct connection of the A900GOT and MAC E900T/900VT/910T (A-BUS only) to the PLC’s expansion port for fast communications.
FX-10DU-E FX-10DM-E MAC E50 MAC E100 MAC E150 MAC E200 MAC E300
HMI and networks Network support, communication between devices and data exchange are all standard features in today’s factory automation systems. The HMI control units and process visualisation software provide full support for the commonest standard networks. The control units are normally connected to the PLC’s RS422 port, which provides a 1:1 link. In MELSECNET the control units can be configured as slaves. If you require a standard open network you can choose between PROFIBUS/DP, CC-Link and Ethernet TCP/IP. A unique option is the 1:n link provided by MAC-Net and the fast Ethernet (up to 100Mbits) for MAC E series, a configuration which enables several MAC E units to access the PLC simultaneously. Data communications over longer distances via modem are also possible – this means you can monitor and edit your configuration, programs and data from the comfort of your desk. Interfaces 앬 RS422 앬 RS232C 앬 RS485/RS422 (optional) 앬 MELSEC A-BUS (optional) 앬 MELSEC Q-BUS (optional) 앬 PROFIBUS/DP (optional) 앬 Ethernet TP (coaxial or twisted pair, optional) 앬 CC-Link (optional)
MAC E600
MAC E610/ MAC E615
MAC E700
MAC E710
MAC E900T MAC E900VT
MAC E910T
LCD
LCD
LCD, mono, backlit
LCD, momo, backlit
LCD, mono, LCD backlit
LCD, mono, backlit
LCD, mono, backlit
LCD, 16 graysc./ 256 colours, backlit
LCD, 256colours, backlit
LCD, 256colours, backlit
TFT/ TFT/ 256 colours, 256 colours, backlit backlit
TFT/ 256 colours, backlit
8
8
5
5
5
132 x 38
132 x 38
115 x 86
120 x 90
120 x 90
214 x 161
214 x 161
214 x 161
16 x 2
16 x 2
FX family —
FX family —
—
—
EEPROM — Via PLC
EEPROM — Via PLC
20 x 4 / 40 x 8 (240 x 64) All MELSEC PLC systems (MAC E50: only MELSEC FX, AnS, AnU) All major PLC manufacturers RS232C, — RS232C, RS232C, — RS422 RS422 RS422 Flash-RAM Flash-RAM Flash-RAM Flash-RAM Flash-RAM 2 2 2 2 2 — Integrated Integrated Integrated Integrated
Membrane Membrane
16 x 2
20 x 2
20 x 2
5 20 x 4
Membrane Membrane Membrane Membrane Membrane
—
—
4 soft keys 4
4 soft keys 5
— 0.2 kg
— 0.15 kg
— 0.2 kg
— 0.5 kg
— 0.25 kg
MITSUBISHI ELECTRIC
5 (2-col.) 0.7 kg
8/max. 128 (opt.) 16 (2-col.) 1.5 kg
20 x 8 / 40 x 16 320 x 240 (240 x 128)
40 x 30 40 x 30 (320 x 240) (320 x 240)
80 x 60 (640 x 480)
80 x 60 (640 x 480)
80 x 60 (640 x 480)
RS232C, RS422 Flash-RAM 2 Integrated
RS232C, RS422 Flash-RAM 2 Integrated
RS232C, RS422 Flash-RAM 2 Integrated
RS232C, RS422 Flash-RAM 2 Integrated
RS232C, RS422 Flash-RAM 2 Integrated
RS232C, RS422 Flash-RAM 2 Integrated
RS232C, RS422 Flash-RAM 2 Integrated
Membrane
Touch-panel
Membrane Touch-panel
Membrane
Membrane
Touch-panel
16/max. 128 (opt.) 16 (2-col.) 1.6 kg
touch-keys/ max. 128 (opt.) 1 (POWER) 1.7 kg
16/max. 128 (opt.) 14 (2-col.) 1.7 kg
22 /max. 128 (opt.) 20 (2-col.) 3.5 kg
22 + 28 / max. 128 (opt.) 20 + 28 (1-col.) 3.5 kg
touch-keys / max. 128 (opt.) — 3.5 kg
8/touch-keys/ max. 128 (opt.) 8 (2-col.) 1.7 kg
HMI
5
BASICS
PLC, HMI and different Networks in Cooperation
OPERATOR TERMINALS GOT
BASICS
A900GOT Series Operator Terminals Complex processes displayed simply The graphic operator terminals of the A900GOT series represent the top products by MITSUBISHI ELECTRIC. They provide a high-resolution touchsensitive screen. State changes and user inputs can be entered easily. A vast number of indicating instruments like indicators, pressure gauges, analog and digital
Extension slot for memory card
measuring devices, etc. can be replaced by corresponding graphical objects. Lots of ready-to-use practical objects are included in the MS Windows® compatible programming software and reduce program development time.
Moreover, the A900GOT is capable of displaying texts with up to 26,000 international characters. With the GOT the user accesses all special function modules in order to test individual parts of the plant. The PLC programs can be monitored graphically (ladder diagram).
Touch-sensitive screen
Network interface
TERMINAL GRAPHIC OPERATION
M CE A
M-CARD ACCESS ON RESET
E X T
POWER
MITSUBISHI MEMORY CASSETTE A9GT-FNB4M
MODEL
4Mbytes
DATE
INPUT 100-240VAC
~
MITSUBISHI
RUN OUTPUT (LG)
(FG)
L
L
12/24VDC 0,1A + -
RS-232-C
9811A
MITSUBISHI ELECTRIC
CORPORATION
MADE IN JAPAN
BD992C032H12
PARALLEL
Power indicator Speaker connection
RS232C interface
Interface for future expansions
Dust cover – Behind the dust cover is the mounting place for the memory cartridge.
M-CARD ACCESS
M-CARD ACCESS
ON
ON RESET
RESET
MITSUBISHI MEMORY CASSETTE A9GT-FNB4M
MODEL
4Mbytes
DATE
9811A
CORPORATION MITSUBISHI ELECTRIC BD992C032H12 MADE IN JAPAN
MITSUBISHI A BUS INTERFACE UNIT A9GT-BUS2S
MODEL
MITSUBISHI MEMORY CASSETTE MODEL A9GT-FNB4M INPUT 100-240VAC
~
RUN OUTPUT (LG)
(FG)
L
L
12/24VDC 0,1A + -
RS-232-C
Extension No. Switch 1~7 “EXTENSION NO.” 8,9,0 “Use prohibited”
4Mbytes
PARALLEL
DATE
9811A
CORPORATION MITSUBISHI ELECTRIC BD992C032H12 MADE IN JAPAN
INPUT 100-240VAC
~
RUN OUTPUT (LG)
(FG)
L
L
12/24VDC 0,1A + -
RS-232-C
PARALLEL II // OO 0~7 8,9
Slot Switch I / O SLOT “Use prohibited”
DATE
9806A
CORPORATION MITSUBISHI ELECTRIC BD992C032H08 MADE IN JAPAN
REAR SIDE IN OUT DISPLAY SIDE
Insert the memory cartridge Power supply terminal bar – The power supply unit is already integrated
6
HMI
Parallel printer interface
Insert the communications module
MITSUBISHI ELECTRIC
OPERATOR TERMINALS GOT
Provided Connections for A900GOT
GRAPHIC OPERATION
BASICS
A900GOT TERMINAL
M CE A
E X T
POWER
MITSUBISHI
Q06HCPU
POWER
5 6 7 8
BASE UNIT MODEL Q38B SERIAL 0205020E
9 A B PULL
C D
USB
USB
2
E F
0 1 2 3 4 5 6 7 8 9
4
L 5
L
6
L 7
L
8
L 9
L
A
L L
B C
L L
D E
L L
F COM
PULL
RUN T.PASS SD ERR.
QC30R2
MNG D.LINK RD L ERR.
0 1 2 3 4 5 6 7 8 9
X1
V+ C VH 2
I+
SLD V+ C VH 3
I+
SLD V+ C VH 4
I+
0 1 2 3 4 5 6 7 8 9
MODE
AC30/300R4-25P
SLD A.G.
NC (FG)
COM
RS-232
RS-232
24VDC 4mA
FX-232CAB1
STATION NO. X10 I+
SLD
3
L
3
QJ71BR11 RUN
C VH 1
1
L
2
ERROR V+
L L
1
4
PULL
01234567 89ABCDEF FUSE
01234567 89ABCDEF
MODE RUN ERR. USER BAT. BOOT
Q64AD
QY80
QX80
Q06HCPU
MODE RUN ERR. USER BAT. BOOT
Q61P-A2
12VDC 24VDC 0.5A
A/D 0~±10V 0~20mA
QJ71BR11
MITSUBISHI
System Q FX9GT-CAB0
100-240 VAC
S/S L
N
X1 X0
MITSUBISHI
X3 X2
X5 X4
X6
X15 X7 X11 X13 X10 X12 X14
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 IN
POWER RUN ERROR
FX1N-24MR OUT
0 1 2 3 4 5 6 7 10 11 Y6 Y10 Y5 Y3 Y2 Y1 Y11 Y0 0V COM4 Y7 COM2 COM3 Y4 24+ COM0 COM1
MELSEC AnS/QnAS series
24MR -ES/UL
Personal Computer
MELSEC FX family
General Operating Conditions Item
Display
Main body
Ambient temperature in operation
0 – +40 °C
0 – +55 °C
Ambient relative humidity
10 – 90 % (non-condensing)
Storage temperature
-20 – +60 °C
Noise durability
1000 Vpp tested by noise generator; 1 µs at 30 – 100 Hz
Dielectric withstand voltage
1500 V AC, > 1 min / 500 V DC, > 1 min
Shock resistance
15 G (3 times each in 3 directions)
Vibration resistance
1 G: resistant to vibrations from 57 – 150 Hz for 80 min. along all 3 axes
Altitude
Max. 2000 m above NN
Over-voltage category
Max. 11
Pollution level
Max. 2
EMC
89 / 336 / EEC and 93 / 68 / EEC
Environment
Avoid environments containing aggressive gases
Cooling
Self-cooling
Certifications
UL / CSA / CE
MITSUBISHI ELECTRIC
HMI
7
OPERATOR TERMINALS GOT
BASICS
Operator Terminals F900GOT The F900GOT Series - A Window through to Your MELSEC PLC Would you like to cut your costs and improve efficiency? You can with the F900GOT series control units. The graphic display configuration on the touch screen is variable, giving the operating staff quick, clear and easily-comprehensible access to information on machine functions. The graphical control unit F900GOT combines particularly easy operation with maximum functionality and modest space requirements.
In addition to standard display and diagnostics functions this unit also supports fully-programmable graphical images and ”touch-keys”. You can store up to 500 user-defined screens, up to three of which can be displayed simultaneously and overlapping on the backlit LC display. The units feature an integrated real-time clock, password access control and alarm and recipe handling.
Data communication with the MELSEC FX-, MELSEC AnS/QnAS or MELSEC AnU/QnAseries is performed via the RS422 port as standard. A printer can be connected to the integrated RS232 port. The control unit is programmed with the FX-PCS/DU-WIN-E or GT-Works software package running on a PC under MS Windows®. Programs can be stored either in the control unit’s integrated, battery-powered RAM or in plug-in EPROM modules.
F940GOT
F930GOT
Touch screen
POWER
Power indicator
RS232C interface
RS232C
RS422 PROGRAMMABLE
CAUTION
Lithium
COM1 RS232C
Backup battery PROGRAMMABLE
CONTROLLER MITSUBISHI MODEL F940GOT-SWD TERMINAL
CONTROLLER MITSUBISHI MODEL F930GOT-BWD GRAPHIC OPERATION TERMINAL
. 11 SERIAL NO. 970340 V.1 ION MITSUBISHI ELECTRIC CORPORAT
GRAPHIC OPERATION
. 11 SERIAL NO. 912370 V.1 ION MITSUBISHI ELECTRIC CORPORAT
EXP-I/F
COM0 RS422 CN-OP
CAUTION
Extension slots for communication modules Power supply terminal bar*
RS422 interface *The power supply unit is already integrated
8
HMI
MITSUBISHI ELECTRIC
OPERATOR TERMINALS GOT
BASICS
Provided Connections of F900GOT Units to a MELSEC PLC System
F940GOT
POWER
FX-232-CAB1
FX-50DU-CAB0/EN
QC30R2
FX-40DU-CAB/EN
Q06HCPU
POWER
5 6 7 8
BASE UNIT MODEL Q38B SERIAL 0205020E
9 A B PULL
C D
USB
USB
2
E
0 1 2 3 4 5 6 7 8 9
F
4
L 5
L
6
L 7
L
8
L 9
L
A
L L
B C
L L
D E
L L
F COM
PULL
RUN T.PASS SD ERR.
MNG D.LINK RD L ERR. 100-240 VAC
STATION NO. X10
0 1 2 3 4 5 6 7 8 9
S/S L
N
X1 X0
I+
SLD
3
L
3
QJ71BR11 RUN
C VH 1
1
L L
2
ERROR V+
L
1
4
PULL
01234567 89ABCDEF FUSE
01234567 89ABCDEF
MODE RUN ERR. USER BAT. BOOT
Q64AD
QY80
QX80
Q06HCPU
MODE RUN ERR. USER BAT. BOOT
Q61P-A2
I+
SLD V+ C VH 3
I+
SLD V+ C VH 4
MITSUBISHI
X1
V+ C VH 2
I+
0 1 2 3 4 5 6 7 8 9
X3 X2
X5 X4
X6
X15 X7 X11 X13 X10 X12 X14
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 IN
POWER RUN ERROR
MODE
FX1N-24MR OUT
0 1 2 3 4 5 6 7 10 11 Y6 Y10 Y5 Y3 Y2 Y1 Y11 Y0 0V COM4 Y7 COM2 COM3 Y4 24+ COM0 COM1
24MR -ES/UL
SLD A.G.
NC (FG)
COM
RS-232
RS-232
24VDC 4mA
12VDC 24VDC 0.5A
A/D 0~±10V 0~20mA
QJ71BR11
MITSUBISHI
MELSEC System Q
MELSEC AnS/QnAS series
MELSEC FX family
General Operating Conditions Item
F900GOT
Ambient temperature in operation
0 – +50 °C
Ambient relative humidity
35 – 85 %
Storage temperature
-20 – +70 °C
Noise durability
1000 Vpp tested by noise generator; 1 µs at 30 – 100 Hz
Dielectric withstand voltage
1500 V AV, > 1 min.
Shock resistance
10 G (3 times each in 3 directions)
Vibration resistance
2 G: resistant to vibrations from 10 – 55 Hz for 2 h. along all 3 axes; 0.5 G when mounted on a DIN-rail
Insulation resistance
> 5 MΩ (500 V DC)
Grounding
Class 3 (100 Ω)
Environment
Avoid environments containing aggressive gases
Cooling
Self-cooling
Certifications
UL / CSA / CE
MITSUBISHI ELECTRIC
HMI
9
OPERATOR TERMINALS GOT
왎 Text Control Panels FX-10 D첸-E Text control panels FX-10 DM-E / FX-10 DU-E BASICS
FX-10 DU-E
CLR
ENT
FNC
FX-10 DM-E
Specifications
FX-10 DM-E
Applicable PLC
MELSEC FX
Power supply
V DC 5 ± 5 % (via PLC)
The text control panels FX-10 DM-E and FX-10 DU-E make the funtions of the controlled system transparent to the user. They provide a key-oriented user-interface each and enable the user to monitor and edit process data in the PLC. The displays are arranged in 2 rows for 16 characters each. Functions can be invoked and values can be edited via keys. The application will be stored in the integrated EEPROM. Special features: 앬 Word device monitoring 앬 Comments or message can be attached to up to 8 devices 앬 Current and set values can be altered for the displayed device 앬 Display of actual values and editing of setting values of timers and counters, of data registers and file registers 앬 Display of the current operation of the sequential program instructions 앬 Password protection 앬 Current time of the real-time clock can be displayed and set 앬 Display of text, programmable via the keyboard or the FX-PCS/DU-WIN-E software (only for FX-10DU-E)
FX-10 DU-E MELSEC FX 5 ± 5 % (via PLC)
Power consumption
mA 220
220
Compensation time after voltage loss
ms