Power Transmission and Distribution. PTD H 1T. HVAC Systems. ➢ 500 kV
conventional as also series compensated. ➢ 750 kV conventional as also series
...
UHV 1200 kV AC Transmission GRIDTECH 2007
Power Transmission and Distribution
H. Huang, D.Kumar, V. Ramaswami, D. Retzmann
Technical Alternatives for Bulk Power Transmission HVAC Systems ¾ 500 kV conventional as also series compensated ¾ 750 kV conventional as also series compensated ¾ 1200 kV conventional as also series compensated
HVDC Systems ¾ ± 500 kV bipole ¾ ± 550 kV bipole ¾ ± 600 kV bipole ¾ ± 800 kV bipole
Page 2
Dec.-06
PTD H 1T
Power Transmission and Distribution
Development of Voltages Levels for AC Power Transmission Voltage 1400 6 1200 kV 1000
5
800 600 400
2 200
4
3
experimental in commercial use
1
1900
1910
1920
1930
1940
1950
1960
1970
1980
1990
2000
Year
Page 3
Dec.-06
PTD H 1T
Power Transmission and Distribution
EHV and UHV AC Systems – at Present
1000 kV Line: SIL = 4 GW Transmission of 6-10 GW is feasible Page 4
Voltage Levels of 735 kV to 765 kV AC have been introduced in the following Countries: Canada, Brazil, Russia (USSR), South Africa, South Korea, U.S.A. and Venezuela UHV Transmission Lines (1000 kV and above) have been built in Russia and Japan Ekibastuz – Kokchetav (500 km) Kokchetav – Kustanay (400 km) Minami – Niigata / Nishi – Gunma (200 km) Kita – Tochigi / Minami – Iwaki (250 km) However, today these UHV Transmission Lines are operated at 500 kV Dec.-06
PTD H 1T
Power Transmission and Distribution
Product-Portfolio Non-Switching HV-Products Coil Products
Bushings
Current and Voltage Transformer
Page 5
Dec.-06
PTD H 1T
Line Traps
Arrester
Power Transmission and Distribution
Product Range Live-Tank High-Voltage Circuit-Breakers
Rated short-circuit breaking current [kA] 80 3AT4/5 63 3AT2/3 50 40 31.5 25 0
3AP1 FG 72.5
123
3AP1 FI 145
170
245
3AP2 FI 300
362
420
550
800 1000 Rated voltage [kV]
¾ The existing C.B. product range is covering 800 kV Scaling up to 1000 kV is possible Page 6
Dec.-06
PTD H 1T
Power Transmission and Distribution
High-Voltage Circuit-Breaker 3AT4/ 5 EI up to 1000 kV
¾ EHVAC C.B. is using proven design and can be scaled up from existing 550/800 kV type to 1000 kV ¾ R&D program may be decided for 1000kV according to specification ¾ Requirements for short circuit current and higher altitudes above sea-level have to be specified ¾ Ambient and environmental conditions have to be considered
Page 7
Dec.-06
PTD H 1T
Power Transmission and Distribution
1000 kV EHVAC Double Break Disconnectors from existing range of 800kV..... Technical Technical Data Data Rated Rated voltage voltage Rated lightning Rated lightning impulse impulse withstand withstand voltage voltage (1,2/50 (1,2/50µs) µs) Across the isolating distance Across the isolating distance Rated Rated switching switching impulse impulse withstand withstand voltage voltage Across Across the the isolating isolating distance distance Rated Rated current current Rated Rated short-time short-time current current
800 800 kV kV 2100 2100 kV kV 2235 kV 2235 kV 1300 1300 1725 1725 4000 4000 63 63
kV kV kV kV A A kA kA
...to 1000kV design: Up-scaling will cover the requirements on creepage distance & mechanical strength of porcelain Page 8
Dec.-06
PTD H 1T
Power Transmission and Distribution
1200 kV Power Transformer Prototype tested in 1972 ¾ EHVAC Transformer using proven design can be scaled up from existing 800 kV type ¾ R&D program may be decided for 1000kV according to specification ¾ Dielectric specification and transport dimensions determine R&D cost and time ¾ Test facilities are an open issue
Page 9
Dec.-06
PTD H 1T
Power Transmission and Distribution
Recent Activities for UHV Example AC Test Transformer 1200 kV
Transformer & Reactor Bushings: Type OTA; Trench UK *, Oil-Paper Technology Production: Hebburn/UK, MWB Shanghai/China Design for 1200 kV Transformer is available Reference: Henjang / China
Page 10
**now nowSiemens Siemens Dec.-06
Protected Creepage Distance: 10.5 m PTD H 1T
Power Transmission and Distribution
Development of UVH AC Transmission
Bundle of 8 Conductors
Rated Voltage: 1000 kV Maximum Operation Voltage: 1100 kV
Source:
Page 11
1000 Dec.-06kV Test Line PTD H in 1T China
Power Transmission and Distribution
Road Map for UVH AC Transmission in China 1000 kV Pilot Project Shaanbei
Jindongnan
Project Highlights: Totally 650km Length Including two UHV-AC Substations and one Switchgear Station
Nanyang
Source:
Jingmen Page 12
Dec.-06
PTD H 1T
Wuhan Power Transmission and Distribution
Specific Issues – for UHV AC The AC Measurements for UHV Capacitive Voltage Divider Type TEHMF Trench Canada * Production: Toronto und Shanghai In Service up to 800 kV Scaling-up for 1100 kV is no Problem
**now nowSiemens Siemens SF6 insulated CT and PT – Design is well proven Type SAS, SVS; Trench Germany * Production: Bamberg and Shanghai In Service up to 800 kV Scaling-up for 1100 kV is no Problem Page 13
Dec.-06
PTD H 1T
Power Transmission and Distribution
Tower Configurations 19 m
15.5 m
48 m
92 m
16.5 m
50 m
44 m
71 m
108 m
16 m
Line conductors
Kita – Iwaki
Ekibastuz – Kokchetav
8 x 31,5 mm ACSR
8 x 24.1 mm AS-330
6,5
8
Air gap clearance phase-earth [m] Page 14
Dec.-06
PTD H 1T
Power Transmission and Distribution
Bundle Design and Tower Configuration Voltage Phase conductor wire Outer diameter Sub conductor spacing
1000 kV 8 x 403/52 ACSR 27.7 mm 400 mm
44 m
Ø = 1.07 m
Page 15
Dec.-06
PTD H 1T
Power Transmission and Distribution
Calculation of Overhead Line Characteristic
Resistance Reactance Capacitance Surge impedance Surge impedance load Charging power Maximum surface gradient
Page 16
Dec.-06
PTD H 1T
0.0107 Ω/km 0.267 Ω/km 14.15 nF/km 245 Ω 4080 MW 4.45 MVAr/km 14.7 kV/cm
Power Transmission and Distribution
Electric Field Strength
50 m
5 kV/ m - 10 kV/ m 10 kV/ m - 20 kV/ m 20 kV/ m - 50 kV/ m 50 kV/ m - 100 kV/ m > 100 kV/ m
0m -50 m
0m
50 m
Sectional view of the transmission line vertical to the line axis
Page 17
Dec.-06
PTD H 1T
Power Transmission and Distribution
Reactive Power Demand of Overhead Lines as a Function of Load Reactive Power [MVAr/100 km] 600
1000 kV 400
750 kV 200
500 kV 380 kV 220 kV
0.5
0
1
1.5
P/SIL -200
-400
-600
Page 18
Dec.-06
PTD H 1T
Power Transmission and Distribution
1000 kV AC Transmission Line No-Load Operation V1 = 100 %
V2
QC
Need of shunt compensation
Page 19
Dec.-06
PTD H 1T
L (km)
QC (Mvar)
V2/V1
250
1,133
1.04
500
2,417
1.17
750
4,169
1.50
1000
7,670
2.45
Power Transmission and Distribution
Transmission System with Shunt and Series Compensation
P SIL
Θ Θ0 Kp = 0
Kp = Degree of shunt comp.
Kp = 0
Kp (ind)= 0.5 Ks = Degree of series comp.
Ks
Page 20
Load capability of transmission system referred to the surge impedance load Dec.-06
PTD H 1T
Ks Transmission angle as a function of degree of compensation
Power Transmission and Distribution
Load Capability of Transmission System Referred to Surge Impedance Load (SIL) P SIL
Kp (ind.)
Kp (cap.)
Kp = Degree of shunt compensation Page 21
Dec.-06
PTD H 1T
Power Transmission and Distribution
Power Frequency Overvoltage During 1-phase Auto-reclosing 5
V [p.u.] 4,5
Z0/Z1=2,0 Z0/Z1=1,0 degree of compensation
4 3,5 3 2,5 2 1,5 1 0,5 0 0%
10%
20%
30%
40%
50%
60%
70%
80%
90% 100% 110% 120% 130%
degree of shunt compensation
Power frequency overvoltage of disconnected phase during 1-phase auto-reclosing for different Z0/Z1 ratios of shunt reactor Page 22
Dec.-06
PTD H 1T
Power Transmission and Distribution
Ultra HVAC System > 1000 kV
Early research works on feasibility of 1100 kV system by AEP, Furnas and some manufacturers.
Further research works on 1000 kV by ENEL-CESI in Italy
1100 kV TEPCO line in Japan ( 140 km)
1100 kV line in Russia operated at 500 kV as reported
1000 kV demonstration line with 3 substations are currently under development in China
Conclusion: UHVAC technology is technically feasible. R&D works are needed on the equipment side