Jan 14, 2003 ... Heating Controllers. RMH760. • Heating controller for medium-size and large
buildings. The RMH760… is used as a heating circuit or primary ...
3
131
PRELIMINARY EDITION 14.01.2003
Synco™700
Heating Controllers
RMH760
• Heating controller for medium-size and large buildings. The RMH760… is used as a heating circuit or primary controller. The controller is supplied with 28 preprogrammed heating plants • Boiler temperature control, control of a second heating circuit and DHW heating with option modules • Menu-driven operation with separate operator unit (plug-in type or detached) Use Buildings
• • • • • •
Office and administrative buildings Commercial buildings and shops Schools Hospitals Industrial buildings and workshops Apartment blocks and terraced houses
Plants
• • • • •
Heating sections of ventilation and air conditioning plants Distribution zones of ventilation and air conditioning plants Heating systems with own heat source Heating zones of a larger plant Basic load heating systems
CE1N3131en 14.01.2003
Siemens Building Technologies HVAC Products
Functions Note
Several of the functions listed require option modules.
Room operating modes
Room operating modes are: • AUTO: Automatic changeover between 3 setpoints according to the time program • Comfort: Continuously heating to the Comfort setpoint • Precomfort: Continuously heating to the Precomfort setpoint • Economy: Continuously heating to the Economy setpoint • Protective mode: Heating to the setpoint of Protective mode, if necessary
Clock functions
• Year clock with automatic summer-/wintertime changeover • 7-day clock for time program with a maximum of 6 switching points per day, for 1 or 2 heating circuits
Holiday functions
• • • •
Ready configured inputs
2 ready configured inputs for: • Flow temperature (averaging possible) • Outside temperature
Freely configurable inputs
3 freely configurable inputs, optionally for: • Reception of the following measuring signals: − Room temperature (averaging possible) − Return temperature − Wind speed − Intensity of solar radiation • Connection of a remote setpoint adjuster with relative or absolute room setpoint adjustment • Connection of an external switch for: − Operating mode changeover − Timer function − Changeover to holiday mode − Changeover to special day − Indication of faults
Note
If more than 3 configurable inputs are required, option modules must be used.
Remote operation
Remote operation with multifunctional room unit via Konnex bus
Control functions
• Heating circuit controller − Weather-compensated flow temperature control via the heating circuit mixing valve, with adjustable setpoints of Comfort, Precomfort, Economy and Protective mode − Adjustable influence of room temperature, solar radiation and wind − Optimized setback and heating up − Boost heating and quick setback − Automatic heating limit for demand-dependent control of the heating with adjustable heating limits for the Comfort and Economy modes − Automatic changeover to summer operation (heating off) − Room model for room functions without room sensor
Holiday and special day program with 16 periods per year Selectable room operating mode for the holiday periods Selectable DHW operating mode for the holiday periods Time program for special days
2/15 Siemens Building Technologies HVAC Products
Data sheet RMH760
Preliminary Edition 14.01.2003
CE1N3131en 14.01.2003
• Primary controller Demand-dependent precontrol via the mixing valve in the common flow, based on the received heat demand signals Limitation functions
• • • •
Maximum limitation of the room temperature Minimum and maximum limitation of the flow temperature Minimum or maximum limitation of the return temperature Limitation of the rate of flow temperature increase
Switching functions
• • • • •
Control of an actuator with 3-position or DC 0...10 V control Pump control (system or heating circuit pump) Control of maximum 2 twin pumps Indication of heat demand Configurable relays
Supervisory and protective functions
• • • • • • •
Mixing valve overrun, mixing valve kick Pump overrun, pump kick Outside temperature-dependent frost protection for the plant Frost protection for the building Overload supervision Fault relay Handling of status and error messages
Service functions
• • • •
Password protection for the configuration Outside temperature simulation Wiring test Storage and reset of parameter sets
Boiler functions (requiring boiler module RMZ781)
• Demand-dependent boiler temperature control • Boiler pump control • Control of a 1- or 2-stage or modulating burner
Second heating circuit (requiring heating circuit module RMZ782)
• Control of a second heating circuit • Maintained boiler return temperature with own mixing circuit • Control of an actuator with 3-position or DC 0...10 V control
DHW functions (requiring DHW module RMZ783)
• • • •
Note
For a more detailed description of all controller functions, refer to Basic Documentation CE1P3131en.
Storage tank charging with charging pump, with or without mixing valve control Storage tank charging via internal or external heat exchanger Time programs for DHW heating and the circulating pump Operating modes: AUTO, continuously Normal, continuously Reduced, Protective mode
Type summary Heating controller
Type of unit Heating controller (de, fr, it) Heating controller (en, fr, nl, es) Heating controller (sv, fi, no, da) Heating controller (pl, cs, sk, hu)
Type reference RMH760-1 RMH760-2 RMH760-3 RMH760-4
Data Sheet CE1N3131en CE1N3131en CE1N3131en CE1N3131en
3/15 Siemens Building Technologies HVAC Products
Data sheet RMH760
Preliminary Edition 14.01.2003
CE1N3131en 14.01.2003
Operator/service units
Operator unit, plug-in type Operator unit, detached Servicetool
RMZ790 RMZ791 OCI700.1
CE1N3111en CE1N3112en CE1N5655en
Option modules
Boiler module Heating circuit module DHW module Twin pump module Universal module with 4 universal inputs and 4 relay outputs Universal module with 4 universal inputs and 2 analog and 2 relay outputs Module connector for detached option modules
RMZ781 RMZ782 RMZ783 RMZ786
CE1N3135en CE1N3135en CE1N3135en CE1N3145en
RMZ787
CE1N3146en
RMZ788 RMZ780
CE1N3147en CE1N3138en
Ordering When ordering, please give type reference according to the above table. The required operator unit and option modules must be ordered as separate items. Room units, sensors, actuator and valve must also be ordered separately. Equipment combinations Suitable sensors
Type of sensor
Suitable remote setpoint adjusters
Suitable actuators
Type reference Data Sheet QAC22 QAC32 QAD22 QAE2… QAE21.3 QAA24 QAA64 QVV60 QLS60
CE1N1811E CE1N1811E CE1N1801E CE1N1791E CE1N1832E CM1N1721E CM1N1722E CM1N19XXE CM1N1943E
Type of room unit Room temperature sensor with setpoint adjuster Room temperature sensor with setpoint readjuster Room unit with Konnex interface
Type reference QAA25 QAA27 QAW740
Data Sheet CM1N1721E CM1N1721E CE1N1633en
Type of remote setpoint adjuster Remote setpoint adjuster, signal 0...1000 Ω Remote setpoint readjuster, ±3 K
Type reference Data Sheet BSG21.1 CE1NXXXXen BSG21.5 CA1NXXXXen
Outside sensor Outside sensor Strap-on temperature sensor Immersion temperature sensor Immersion temperature sensor Room temperature sensor Room temperature sensor Wind effect sensor Solar impact sensor Suitable room units
Type of sensing element, Signal LG-Ni 1000 NTC 575 LG-Ni 1000 LG-Ni 1000 LG-Ni 1000 LG-Ni 1000 LG-Ni 1000 DC 0...10 V DC 0...10 V
All types of electromotoric and electrohydraulic actuators from SBT HVAC Products can be used: • Operating on AC 24…230 V • 3-position control • DC 0...10 V modulating control For detailed information about actuators and valves, refer to Data Sheets CE1N4000E…4999E.
4/15 Siemens Building Technologies HVAC Products
Data sheet RMH760
Preliminary Edition 14.01.2003
CE1N3131en 14.01.2003
Product documentation Type of document
Number
Product Range Description
CE1N3146en
Basic Documentation
CE1P3130en
Installation instructions
7431903390
Operating Instructions (de, fr, it)
7431903450
Declaration of Conformity (CE)
CE1T3100en
Environmental Declaration
CE1E3100en
Technical design
Precontrol can only be provided by the controller. There are 2 choices: With mixing valves: With system pump: P1 P2 Y1
3131S02
Use of individual devices Precontrol
The controller is supplied with 28 basic types of heating plant preprogrammed. They have been selected to cover the majority of standard applications. Some of them require option modules. When commissioning a plant, the relevant basic plant type must be entered. All associated functions, terminal assignments, settings and displays will automatically be activated, and parameters not required will be deactivated.
3131S01
Mode of operation
M1
M1 B1 B7
B1*
B7*
B1 Flow temperature sensor B1* Flow temperature sensor (optioanal, for display only) B7 Return temperature sensor (optional, for minimum limitation) B7* Return temperature sensor (optional, for maximum limitation) M1 System pump (can be a twin pump) Y1 Mixing valve
Measuring input B7 for the return temperature can be configured for either minimum or maximum limitation. The control of 1 or 2 heating circuits can be provided either by the controller or the RMZ782 heating circuit module. The available choices are the same with both types of unit, provided the required connection terminals are present or can be configured. Please also note the following: • If the controller and heating circuit module do not have a sufficient number of configurable connection terminals, an additional option module can be used • If the controller is used as a primary controller, the RMZ782 heating circuit module must be used for the control of the heating circuit • A second heating circuit must be controlled with the RMZ782 heating circuit module • Measuring input B7 for the return temperature can be configured for either minimum or maximum limitation B5 R5 A5 B9 B91 B92 B1 M1
B7*
Y1 B7
3131S39
Heating circuit control
A5 B1 B5 B7 B7* B9 B91 B92 M1 R5 Y1
Room unit (optional) Flow temperature sensor Room temperature sensor (optional) Return temperature sensor (optional, for minimum limitation) Return temperature sensor (optional, for maximum limitation) Outside sensor Solar impact sensor (optional) Wind effect sensor (optional) Heating circuit pump (can be a twin pump) Remote setpoint adjuster (optional) Mixing valve 5/15
Siemens Building Technologies HVAC Products
Data sheet RMH760
Preliminary Edition 14.01.2003
CE1N3131en 14.01.2003
Boiler temperature control requires the RMZ781 boiler module. There are 2 choices: Boiler pump in the flow: Boiler pump in the bypass: G2 3131S03
G1 B2
3131S04
Boiler temperature control
B2
M1 B7
B7
Maintained boiler return temperature
B2 B7
Boiler temperature sensor Return temperature sensor (optional, for minimum limitation) M1 System or bypass pump (E1: can be a twin pump)
M1
In plants with maintained boiler return temperature, the following types of modules are required, in addition to the controller: • Heating circuit module RMZ782; it controls the boiler return temperature via a mixing valve, depending on the temperature acquired with B1. The module also controls boiler pump M1 • Boiler module RMZ781; this module controls the boiler temperature depending on the temperature acquired with B2, and also controls system pump M2 One of the basic types 4–... must be selected on the controller.
B2
3131S41
G3 RMZ781
M2 B1 M1 RMZ782
Y1
Boiler return temperature sensor (controlled variable) Boiler temperature sensor Boiler pump (can be a twin pump) System pump (can be a twin pump) Mixing valve Balancing valve
DHW heating requires the RMZ783 DHW module. There are 5 choices: DHW2 B4
E7
3131S34
DHW1
B3 E7
M4 M3
B4*
B3
B4 E7 M3
B4*
B3*
M4
B3 B4 E7
M5 Y1
3131S37
DHW4 3131S36
DHW3
M4
B4*
Y1
M3
B4
3131S35
DHW heating
B1 B2 M1 M2 Y1 Y2
Y2
M3
M4
B4*
Y2
6/15 Siemens Building Technologies HVAC Products
Data sheet RMH760
Preliminary Edition 14.01.2003
CE1N3131en 14.01.2003
B3*
B3
3131S38
DHW5 B4
B3 B3* B4 B4* E7 M3 M4 M5 Y1 Y2
M4
E7 B4*
M5
M3
Charging temperature sensor Primary flow temperature sensor (optional) Storage tank sensor at the top Storage tank sensor at the bottom (optional) Electrical immersion heater (optional) Charging pump (can be a twin pump) Circulating pump (optional) Primary pump (can be a twin pump) Mixing valve 2-port valve
Basic types The illustrations contained in this section use the following symbols for precontrol, boiler temperature control and DHW heating:
RMH760
RMZ782
RMH760
RMZ783
0-5
3131S06
RMH760
0-3
RMH760
RMZ783
0-4
RMZ783
RMH760
RMZ782
With all basic types 1–x, primary controller variants P1 and P2 can be selected. 3131S13
1-3
RMH760
RMZ783
RMZ782
RMH760
RMZ783
3131S14
RMH760
1-2
RMZ782
1-4
3131S12
1-1
3131S11
Basic types 1–x
0-2
DHW heating 3131S08
0-1
3131S07
Basic types 0–x
Boiler temperature control
3131S09
Precontrol
3131S05
Note on illustrations
RMH760
RMZ782
RMZ782
7/15 Siemens Building Technologies HVAC Products
Data sheet RMH760
Preliminary Edition 14.01.2003
CE1N3131en 14.01.2003
3131S15
1-5
RMH760
RMZ782
RMZ782
RMH760
2-3
RMZ783
RMZ782
RMH760
RMZ783
RMZ782
RMZ782
RMZ782
RMZ782
2-4
RMH760
2-5
RMZ782
RMH760
3131S23
RMZ781
3-2
RMZ781
3-1
RMH760
RMZ781
RMH760
RMZ783
RMZ781
RMZ783
RMH760
3131S26
3-0
3131S25
With all basic types 3–x, boiler pump variants G1 and G2 can be selected. 3131S22
Basic types 3–x
RMH760
3131S21
RMH760
2-2
RMZ783
3131S20
RMH760
3131S17
2-1
3131S18
2-0
3131S19
With all basic types 2–x, primary controller variants P1 and P2 can be selected. 3131S42
Basic types 2–x
RMZ783
3-3
8/15 Siemens Building Technologies HVAC Products
Data sheet RMH760
Preliminary Edition 14.01.2003
CE1N3131en 14.01.2003
RMZ781
RMH760
3131S27
3131S24
3-4
3-5
RMZ782
RMZ781
RMZ783
RMH760
RMZ782
For minimum limitation of the boiler return temperature, basic types 4–x have their own mixing circuit.
RMZ782
RMZ782
4-4
4-3
RMZ781
RMH760
3131S31
RMZ783
RMZ783
RMH760
RMZ782
RMZ781
RMZ782
RMH760
RMZ781
RMZ782
RMH760
RMZ782
4-5
RMZ782
RMH760
RMZ781
RMZ781
3131S33
4-2
4-1
3131S32
RMZ781
3131S30
4-0
3131S28
For minimum limitation of the boiler return temperature, basic types 4–x have their own mixing circuit
3131S29
Basic types 4–x
RMZ783
RMH760
RMZ782
Mechanical design Basic design
The controller consists of terminal base and controller insert. It has a plastic housing with the printed circuit boards, 2 terminal levels and carries the connecting elements (electrical and mechanical) for an option module.
9/15 Siemens Building Technologies HVAC Products
Data sheet RMH760
Preliminary Edition 14.01.2003
CE1N3131en 14.01.2003
The controller can be fitted to a top hat rail conforming to EN 60 715-TH35-7.5, or can be mounted directly on a wall. Operation takes place with either a plug-in type or detached operator unit (refer to section "Type summary").
1
2
3
11 3144Z01
Operating, indicating and connecting elements
4 1 2 3 4 5 6 7 8 9 10 11
5
6 7
8
9
5
11
10
Connection facility for the service interface (RJ45 socket) Connection facility for the operator unit (with removable cover) LED (green) for indication of operation Fault button with LED (red) for indication of faults and for resetting Openings for plug-in type operator unit RMZ790 Button for assignment of the device address LED (red) for indication of the programming process Mounting facility for fitting the controller to a top hat rail Fixing facility for a cable tie Electrical and mechanical connection elements for the option module Rest for the terminal cover
Engineering notes • The controller operates on AC 24 V. Operating voltage must conform to the requirements of SELV (safety extra low-voltage) • The transformers used must be safety isolating transformers featuring double insulation to EN 60 742 and EN 61 558-2-6; they must be suited for 100 % duty • Fuses, switches, wiring and earthing must be in compliance with local regulations • The lines of the measuring circuits carry protective low-voltage, those to the 3position actuator and the pumps carry AC 24...230 V • Sensor wires should not be run parallel to mains carrying cables powering fans, actuators, pumps, etc. • The controller can be used with a maximum of 4 option modules • The reference room for control with a room temperature sensor should be the room that cools down quickest. That room may not be equipped with thermostatic radiator valves; manual valves must be locked in their fully open position Mounting and installation notes • Standard mounting location is the control panel. Not permitted are wet or damp spaces. The permissible environmental conditions must be observed • Suitable mounting locations are walls (in rooms or control panels) and front panels • The control panel must be prepared for the proposed operator unit. This applies to both the variant and the outer dimensions • Disconnect the equipment from power supply during mounting and installation • The controller insert may not be removed from the terminal base!
10/15 Siemens Building Technologies HVAC Products
Data sheet RMH760
Preliminary Edition 14.01.2003
CE1N3131en 14.01.2003
• If option modules are used, they must be attached to the right side of the controller in the correct order. This means in agreement with ascending type reference numbers: RMH760 – RMZ781 – RMZ782 – RMZ782 – RMZ783 – RMZ786 – RMZ787 – RMZ788. • The option modules require no wiring between one another or to the controller; the electrical connections are made automatically when attaching the modules. If it is not possible to arrange the option modules side by side, the first of the detached modules must be connected to the last previous module or to the controller using the RMZ780 module connector. In that case, the maximum cable length is 10 m • All connection terminals for protective extra low-voltage (sensors and data bus) are located on the upper terminal block, those for mains voltage (actuators and pumps) on the lower terminal block • Each terminal (spring cage terminal) can accommodate only one solid wire or one stranded wire. For making the connections, the cables should be stripped for 7 to 8 mm. To introduce the cables into the spring cage terminals and to remove them, a screw driver size 0 or 1 is required; cable strain relief can be provided with the help of the fixing facility for cable ties • The controller is supplied complete with Installation and Operating Instructions Commissioning notes • The operator unit can be removed and plugged in or connected while the controller is in operation • For commissioning, there are several auxiliary functions available (refer to «Service and operating functions») • Commissioning is carried out with the RMZ79... operator unit or the OCI700.1 service tool Disposal notes Larger plastic parts carry material identifications conforming to ISO/ DIS 11 469 to facilitate environment-compatible disposal. Technical data Operating voltage*
Rated voltage Rated frequency Max. power consumption (without modules) Fusing of supply lines
AC 24 V (±10 %) 50 Hz 12 VA max. 16 A
Functional data
Reserve of clock Software class Mode of operation to EN 60 730
15 h A 1b (automatic operation)
Relay outputs*
Rated voltage range Rated current range Switch-on current Switching capacity as valve actuator relay
AC 24...230 V 0.02…2 (2) A ≤15 A for ≤ 20 ms max. 15 VA
* Nomenclature of electrotechnical variables as per EN 60 730-1
Other inputs and outputs
For definition of all other inputs and outputs, refer to «Connection terminals»
Interfaces
Konnex bus Type of interface Transceiver
Konnex-TP1 TP-UART 11/15
Siemens Building Technologies HVAC Products
Data sheet RMH760
Preliminary Edition 14.01.2003
CE1N3131en 14.01.2003
Baud rate Bus loading number (SBT) Decentral bus power supply, can be switched off Type of cable
Connection of room unit QAW740 Cable Cable length Service tool connection facility
9.6 kBit/s
20 mA 2-core, without shielding, twisted pairs, connections not interchangeable dia. 0.8 mm normally 350 m (>350 m: refer to Konnex document) RJ45 socket
For more information about the Konnex bus, refer to the following pieces of documentation: • Data Sheet CE1N3127en • Basic Documentation CE1P3127en Permissible cable lengths To the sensors Copper cable 0.6 mm dia. Copper cable 1.0 mm2 Copper cable 1.5 mm2 To the room units QAA2... Copper cable 0.6 mm dia. Copper cable 1.0 mm2 Copper cable 1.5 mm2 Degrees of protection
Materials and colors
Permissible ambient conditions
Norms and standards
20 m 50 m 80 m 20 m 50 m 80 m
Degree of protection of housing to EN 60529 Safety class to EN 60730 Degree of contamination to EN 60 730
IP20 (when mounted) corresponding to safety class II if adequately mounted normal contamination
Controllers Packaging
Polycarbonate, RAL 7035 (light-grey) corrugated cardboard
Transport Temperature Humidity Storage Temperature Humidity Operation Temperature Humidity
–25..+70 °C