Mitsubishi Electric Substation Administrative System : MELSAS-S Supporting higher efficiency and round-the-clock reliable operation of various power distribution devices through intuitive monitoring and sound maintenance
Merit
1
Improved Economic Efficiency
Contributes to reducted lifecycle costs of power distribution equipment Reduced operating costs and increased energy savings via monitoring and control of power-factor and power demand Greatly reduced wiring costs (including costs of materials, testing and installation) through use of a transmission system More efficient daily/regular inspections and restoration after accidents
As a total solution for supervisory control of power distribution equipment, MELSAS-S realizes reliable control during normal operation, reduced maintenance and support for automatic measures in the event of accidents and power interruptions.
Economical Solution
Merit
2
Easy Operation
Increased Reliability
Greatly enhances system reliability through use of optical-fiber signal transmission lines
High Reliability
Higher resistance to noise thanks to the use of optical fibers
Merit
3
Increased Operability
Improved visibility and operability of monitoring display screens Simple monitoring and operability enabled as a result of innovative graphic panel and intuitive, easy-to-view screen layout.
1
2
System Network Various systems available to suit a range of budgets
Total remote monitoring
Remote monitoring
Remote logging
Remote monitoring
Total supervisory control
Desktop monitoring control
Data logger
Graphic panel supervisory control
Fully centralized control for efficient operation and energy savings.
Switch screens and turn devices on/off via touch-panel operations.
Record daily/monthly reports and display data for efficient operation.
Features graphic panels (or mini graphic panels) to support recognition of equipment status and failures at a glance.
Host communication interface
Host network
Type D
Type L
Central monitoring room
Type K
Type T
MELSAS-S
Modbus-RTU, MELSECNET, Ethernet, etc.
Allows communication with other systems such as building and plant control systems.
to host communication interface * Please consult us.
Optical-fiber transmission line.
All types are applicable.
Type M
On-site monitoring
On-site monitoring panel Enhanced efficiency of on-site inspections and measures in an accident
Remote station
Remote station
(local unit installed)
Power distribution equipment
High-voltage C-GIS
3
System Network
(local unit installed)
CC-Link, CDL, Modbus-RTU
I/O connection (hard-wired)
Power transformer
• Operating status and failure display • Measurement data display • Power-factor regulating capacitor control • Automatic control of selective load cutoff • Emergency guidance display • Uninterruptible power supply control
Medium-voltage switchgear
CC-Link, CDL, Modbus-RTU
Medium-voltage switchgear
System Network
4
Models
Flexibility for future expansion
The perfect solution for supervisory control of power distribution equipment in new and existing buildings, plants and other settings System configuration example
Highly flexible system configurations
Flexibility to suit system configurations both small and large Abbreviations PR: Printer OPS: Operator console station GP: Graphic panel
System configuration examples
Central devices
Terminal devices
Operator console
Remote station
(supervisory control unit, data processing unit)
(local unit)
Operator console station
Equipment under supervisory control
Power distribution equipment GIS and transformers
Remote station
Monitor
Type-T
System
Optical transmission
PR
RS
Total supervisory control system RS
I/O connection*2
LU
Equipment
LU
Equipment
LU
Equipment
LU
Equipment
LU
Equipment
LU
Equipment
LU
Equipment
LU
Equipment
• Total solution incorporating type-K and -L functions • Centralized management of operating status of power distribution equipment for efficient operation and energy savings
Monitor PR
Medium-voltage switchgear
Type-D
*1
Features
CC-Link, Modbus-RTU, CDL transmission
GP
RS: Remote station LU: Local unit TP: Touch panel display
Optical transmission
Desktop supervisory control system
RS
RS
CC-Link*3
• Supervisory control system incorporating type-L and on/off functions • Displays a diagram of the power system on the monitor (optional) (for type-T, diagram is displayed continuously on the graphic panel)
Monitor
CDL transmission, Modbus-RTU
Type-L
PR
Optical transmission
RS
Data logger monitoring system RS
Simple system expansion and wiring cost reduction
• Records failures, alarms and measurement values
*1 MELSECNET: Data link for Mitsubishi Electric PLCs *2 I/O connection: Input and output via hard-wired connection *3 CC-Link: Mitsubishi Electric open-architecture network under MELSEC
• Status and failure monitoring • Upper and lower limit monitoring • Message list display • Measurement data display • Power demand monitoring • Printouts of daily and monthly reports • Printouts of messages
Dual-loop optical transmission line Max. distance 30km (1 or 2km* between units) 1
Remote station
Local unit • Output of operation signals • Input of status • Input of failures • Input of analog signals • Input of pulse signals
Type-M
• Graphic panel display • Status monitoring • Failure monitoring • Equipment selection operation • Alarm output
Monitoring / Measurement / Recording
*1 With SI optical cable: 1km With GI optical cable: 2km For details, see transmission specifications on page 7. (Installed locally)
Local unit
On-site monitoring system
System
TP
LU
Equipment
• Facilitates more efficient use and operation on-site • Features graphic panels (or mini graphic panels) to support recognition of equipment status and failures at a glance
Item
Local unit
• Enhanced efficiency of on-site inspections and accident measures • Possible to switch screens via touch-panel operation (alarm output and on/off functions are not available)
••Wiring cost for a signal connection between local unit (LU) and electrical equipment can be reduced using CC-Link Modbus-RTU or CDL transmission. •Signal connections to existing equipment or other company's equipment are possible with I/O connections.
Maximum number of control points
Items in parentheses can be supported as options.
Content
Type-T
Type-D
Type-L
Type-K
Type-M
Supervisory control unit
Turns devices on/off and displays on graphic panel
○
ー
ー
○
ー
Data processing unit
Collects data, displays on monitor and prints out
○
○
○
ー
ー
Local unit
Inputs/Outputs data and controls locally
Output of operation signals (DO)
For output of signals for switching devices on/off
1 station
Max. 16 stations 500× 2 points
500× 2 points
ー
500× 2 points
ー
1000 points
1000 points
500 points
64 points
500 points
64 points
Input of status signals (DI)
For input of signals for status of devices
1000 points
Input of failure signals (DI)
For input of signals indicating device failures
1500 points
1500 points
1500 points
Input of analog signals (AI)
For input of analog input signals indicating voltage, current, etc.
1500 points
1500 points
1500 points
Input of pulse signals (PI)
For input of pulse signals indicating watt-hour, etc.
1000 points
1000 points
1000 points
ー
For display of status and failures on graphic panel
400 points
ー
400 points
Graphic panel display (ANN)
5
RS
RS
• Type-M can be used as a local unit for Types T, D,L or K. • Various combinations are available for Types T, D, L and K. • Supervisory control ispossible at two or more stations.
Unit configuration
Monitoring / Operation
Optical transmission
Data processing unit
Maximum number of control points
Supervisory control unit
(Installed in central control room)
Type-K
Operator console station
GP
Graphic panel supervisory control system
ー
(50 points) (16 points)
Models
ー
6
Achieving high functionality and reliability
General specifications Operator console
100VAC (UPS power)
Remote station
100VAC / VDC (UPS power)
Operator console
Ground resistance of 100Ω or less (dedicated) Ground resistance of 100Ω or less (dedicated)
B-1
B-2 B-3 B-4 B-5
Graphic panel
K
M
○
−
−
○
○
○
−
−
○
−
○
−
−
○
−
○
○
○
○
○
CPU
○
○
○
−
−
17-inch LCD with 16.77 million color display Optional touch operation also available Resolution: 1920 X 1080 dots
○
○
○
−
−
No corrosive gas No xcessive dust
Digital output
DO card
○
○
○
−
−
○
○
○
−
−
Printer
Black ink A4-size page printer Optional color printer available
○
○
○
−
−
Others
DVD drive
○
○
○
−
−
32-bit microcomputer
○
○
○
○
○
On/Off signal Dry (no voltage) a-contact output output (digital) 1 second momentary output
○
○
−
○
−
Status failure signal input (digital)
Dry (no voltage) a-contact input Rated input current: 24VDC, 4mA
○
○
○
○
○
Input/Output Measurement Voltage/current input 0 - ±10V, input resistance: 1MΩ signal input card
○
○
○
△
△
(analog)
4 - 20mA, input resistance: 250Ω
A-2 Supervisory control unit
GP
Monitor
On/Off Control
Mouse
HD
C-1
○
Signal transmission with MP21, MP22, MCD-3, LSZ
○
○
○
○
○
Signal transmission with MP21, MP22, MP23, CC-Link remote I/O terminal, CC-Link remote AI terminal
○
○
○
○
○
Transmission with Modbus-compatible device
○
○
○
○
○
MCD-3 LSZ
Power supply, noise filter, DC-DC convertor, etc.
○
○
○
○
○
Medium-voltage switchgear
○
△
△
LU-1
LU-2
LU-N
C-2
C-3
C-3
D-2 CDL transmission
D-2 CC-Link transmission
MCD-3
I/O connection
Existing equipment GIS, transformer
Medium-voltage switchgea
AI card
• Rated input voltage: 0-10VDC (input resistance: 1MΩ) • Rated input current: DC4-20mA (input resistance: 250Ω)
Converter
CPEV-S 0.9φ
Medium-voltage switchgear
• • • • • •
PI card +
−
24VDC CPEV-S 0.9φ
Medium-voltage switchgear
MP MP MP
Medium-voltage switchgear
On/Off control Digital output
Status/Failure
Terminating resistor (included with master unit)*1 1/2W 110Ω
100VDC
DA
DA
DB
DB
DG
DG
SLD
SLD
CC-Link dedicated cable
FG
Digital input
On
Off
CB
MP23
To next unit
Measurement Digital input
*1 Terminating resistor must be mounted to CC-Link terminating connection station.
• Transmission media: Please use a CC-Link dedicated cable. • Transmission distance: 1,200m at 156kbps 900m at 625kbps 400m at 2.5Mbps 160m at 5Mbps 100m at 10Mbps
• Rated input voltage: 0 - 110V AC • Rated input current: 0 - 5AAC
100VDC
On/Off control
D-2
Host transmission
Transmission speed: 156kbps Transmission distance: 1,200m (depending on transmission speed) Number of transmission terminals: max. 64 units
GI-50/125
Modbus-RTU
Transmission speed: 115kbps Max. transmission distance: 1,200m Number of transmission terminals: 32 units/card
RS 232 RS 485
RS232C signal transmission
Transmission speed: 9600bps Max. transmission distance: 15m Expandable with optical modems
Dedicated cable
Transmission speed: 10/100Mbps
Category 5 or greater twisted pair cable for Ethernet
Modbus-RTU
Max. segment length: 100m Max. cascade connections: 4
Transmission speed: 115kbps Max. transmission distance: 1,200m Number of transmission terminals: 32 units/card
A3, black and white laser printer A4, inkjet color printer A3, inkjet color printer
UPS 1kVA, 3kVA
Battery back-up time: 10min Non-interruption switchover synchronized with commercial power
Display device Measurement data / digital display
Others
Communication with total supervisory control devices, central monitoring devices, other monitoring devices of other-companies E-mail notification function
Transmission card
17, 19 inches LCD with touch operation
Digital input
On
S
Off
• Contact a contact input, dry contact • Rated input voltage: 24VDC • Rated input current: 10mA
*2
P
MCD-3B MP23
N −
+
24VDC
Measurement
• Contact a contact output, dry contact • Rated load: 100V, 3.5A (AC) 110V, 0.15A (DC)
CB
N
CPEV 0.9∼1.2φ
• Rated input voltage: 0 - 100V • Rated input current: 0 - 5A
To next unit
Digital input
*2 MCD Series: Centralized control display device
24VDC
Status/Failure Digital input
S N
• Contact a contact input, dry contact • Rated input voltage: 24VDC • Rated input current: 10mA
*3
P N −
+
24VDC
CPEV 0.9∼1.2φ
LSZ-80
To next unit *3 LSZ Series: CDL transmission terminal unit
24VDC
Measurement Analog input
RS 232 RS 485
S N P N −
︸
Twisted pair cable
10/100 BASE-T
Printer B-5
Transmission speed: 9600bps Max. transmission distance: 1.5km (depending on number of terminals) Number of transmission terminals: 32 units/card
17, 19, 20, 23, 26, 42 inches LCD
A4, black and white laser printer
Dedicated cable
CDL signal transmission
Ethernet
B-2
Status/Failure
︸
D-3
In-panel transmission
2km
SI-200/250
Monitor
Specification
Transmission card
CC-Link signal transmission
1km
Device name
Transmission card
GI optical cable option (supplied by subcontractor)
MELSECNET/H Transmission speed: 10Mbps Max. transmission distance: 30km
Optional devices Distance between stations Cable specification
CDL transmission connection
Main line transmission
Specification
Contact photocoupler input Input spec: Input for 2 seconds or longer Rated input voltage: 24VDC Rated input current: 10mA (source type)
︸
D-1
Item SI optical cable (supplied by subcontractor)
Contact a contact output, dry contact Input spec: Input for 100 milliseconds or longer Rated input voltage: 24VDC Rated input current: 4mA Input resistance: approx 5.6kΩ Common line: 1 common line for 1 point
• Contact a contact output, dry contact • Opening capacity: 250VAC, 1A 220VDC, 0.1A 110VDC, 0.3A
• • • •
FG
Digital output
Signal transmission specifications
Contact a contact output, dry contact Input spec: Input for 1 second or longer Rated input voltage: 24VDC Rated input current: 4mA Input resistance: approx. 5.6kΩ Common line: 1 common line for 1 point
PR
C-1
Measurement Dry (no voltage) a-contact input or open collector input signal input Rated input current: 24VDC, 4mA (pulse) Make time: 100ms or longer
○
• • • • • •
−
CVV2E
Contact a contact output, wet contact Output spec: Momentary output for 1 second Rated current: 2A Rated load:240VAC 0.5A (Cosφ=0.35) 24VDC, 1A (L/R=7 msec) • Common line: 1 common line for on/off of applicable device
B-1 CPU
C-1
Analog input
Medium-voltage switchgear
CVV2E
24VDC
Pulse input
B-4
Main optical transmission line (dual-loop)
RS
+
Measurement
C B
−
B-5
CPU
D-1
Digital input
Measurement
B-3 Keyboard
A-1
Status/Failure
Off
On
• • • •
Data processing unit
B-2
DVD
A-3
Display
Remarks
TX
CX
Surge killer
TX
24VDC
GP : Graphic Panel LU : Local Unit PR : Printer HD : Hard Disc RS : Remote Station
Power distribution equipment
CX
Other systems (central monitoring device, etc.)
Total remote monitoring (Type-T)
Recommended Signal cable
Surge killer
On/Off control
Operator console
Mouse
CDL transmission card CC-Link transmission card Modbus transmission card Others
20 to 85% RH (no condensation)
Ambient atmosphere
D-3 Host transmission
109 keyboard
Local unit
Remote station
L
Alarm buzzer (major/minor failure output)
CPU
0 to 40°C
Humidity
Remote station
︸
C-3
LED display Silk screen printing Optional mosaic panel also available
D
32-bit microcomputer Main memory: 1GB or more Hard-drive available space: 80GB or more
C-1
C-2
32-bit microcomputer
T
Others
Keyboard
Temperature
Signal type
+
System type Specification
On/Off control Dedicated key array Selective operation / panel Double-key action system
Monitor
10 to 85% RH (no condensation)
Status / Failure DI card
Supervisory control unit
Operator console
A-3
Data processing unit
A-2
CPU
Humidity
○:Standard △:Option
Device specifications Device name
Common
10 to 35°C
Transmission card
Remote station
A-1
Ambient Remote station conditions
Temperature
I/O connection (hard-wired)
Power supply Data processing unit Grounding
Specifications for interface with power distribution equipment
100VAC / VDC (UPS power)
Supervisory control unit
CC-Link transmission connection
Specifications
+
24VDC
CPEV 0.9∼1.2φ
LSZ-AI
Converter
• Rated input voltage: 0 - 10VDC • Rated input current: DC 4 - 20mA
To next unit
Modbus-RTU are also arailable.
7
Specifications
Specifications
8
Wide range of system functions
Type-D: Desktop supervisory control system
Type-K: Graphic panel supervisory control system
Type-M: On-site monitoring system
○ : Standard
Turn individual devices on/off (type-1)
Single devices can be turned on/off using a dedicated keyboard.
Turn individual devices on/off (type-2)
Single devices can be turned on/off using a mouse or via a touch panel (option).
○
ー
ー
○
ー
P12- 7
ー
○
ー
ー
ー
Display of analog measurement values
Analog data is measured and displayed in digital and bar-graph format on the monitor. Upper/Lower limits can be displayed and adjusted.
P11- 3
○
○
○
ー
○
Upper and lower limit monitoring
Constant monitoring of analog-data upper/lower limits.
P11- 3
Display of pulse measurement values
Hourly pulse data is measured and displayed on the monitor.
*1
○
○
○
ー
ー
○
○
○
ー
ー
Equipment status (on/off) is monitored constantly and displayed on the monitor.
P11- 2
Demand monitoring
Power demand is monitored and an alarm is issued if the level is forecast to exceed the contract value. Monitoring details are displayed on the monitor (max. 32 units).
P11- 6
○
○
○
ー
ー
Trend display of measurement values
Graphs of trends over time for selected and registered analog-data items are displayed. Data is recorded every 10 seconds and stored for four hours.
P11- 5
○
○
○
−
−
Failure alarm monitoring
Equipment failures and recoveries are monitored constantly and displayed on the monitor.
P11- 4
○
○
○
−
○
Event logger
Status variation, equipment failures, time-series data of upper/lower limit faults for analog data and processes in progress are displayed on the monitor.
P11- 4
○
○
○
−
−
Graphic panel display
Equipment status (on/off) and failures are displayed on a graphic panel.
P13- 1
○
ー
ー
○
ー
Printouts of event record
Enables printouts of status variation, equipment failures, and time and details of upper/lower limit faults for analog data as required or after a certain amount of data has accumulated.
P12- 8
○
○
○
ー
ー
Regular and arbitrary printouts of daily report
Enables printouts of instantaneous, cumulative, average, maximum and minimum values of selected and registered analog-data items in table format as required or at a specified time every day. Up to five years worth of data can be stored and printed out in table format.
P12- 9
○
○
○
ー
ー
Regular and arbitrary printouts of monthly report
Enables printouts of monthly total, average, maximum, minimum and cumulative values of selected and registered pulse-data items in table format as required or at a specified time on the first day of every month. Up to five years worth of data can be stored and printed out in table format.
P12- 9
Storage of daily and monthly reports
Daily/Monthly reports can be stored in Excel format.
P12- 9
Hard-copies of data display
Data can be printed out as it is displayed on the monitor.
Self-diagnostic function
Equipment and transmission system status are monitored. Any errors are displayed and an alarm is issued.
○
○
○
○
○
Alarm output
Alarm sounds in the event of an equipment failure.
○
○
○
○
ー
Status monitoring
○
○
○ ○
○
○
○ ○
○
○
○ ○
ー
ー
ー ー
○
ー
ー ー
△ : Option
Function
Controls
Outline
Optional functions
System type Preference page Type-T Type-D Type-L Type-K Type-M
Monitoring and measurement functions
Monitoring and measurement functions
Control
Function
Recording functions
Type-L: Data logger monitoring system
Recording functions
System functions
Type-T: Total supervisory control system
Others Interface function
Functions
Outline
System type Preference page Type-T Type-D Type-L Type-K Type-M
Demand control
When power demand exceeds the upper limit, load is cut-off starting with low-priority loads (max. 8 circuits).
P13- 2
△
△
△
ー
ー
Power-factor regulation with capacitors
Reactive power is monitored and capacitors automatically regulate power-factor to a level close to 100% via on/off operations (max. 8 circuits x 3 banks).
P14- 3
△
△
△
△
△
Power interruption and recovery control
Automatic control of circuit breakers (on/off) after power-supply interruptions and recoveries.
△
△
△
△
△
Selective cutoff of loads (load shedding)
When power supply exceeds the generator capacity, load is cut-off starting with low-priority loads.
△
△
△
ー
ー
Factory utility monitoring
Status and failures of plant utilities such as water supply, sewage, boilers and compressors are monitored.
△
△
△
△
△
Single line diagram and panel arrangement display
Equipment status and failures are displayed in a single-line diagram or via a schematic of the panel arrangement.
△
△
△
ー
△
Display of opening and closing time of circuit breakers
Circuit breaker opening/closing times are displayed (only valid when MCD-3 and CDL signal transmission are in use).
△
△
△
ー
△
Guidance display for operation support
Flowcharts of operating processes are displayed.
△
△
△
ー
△
Guidance display for emergency operation
In emergencies, operating guidance and contact information are displayed.
△
△
△
ー
△
Display of operational history
Circuit breaker usage hours and No. of on/off operations are recorded and
△
△
△
ー
△
Display of waveform of instontaneous voltage drop
Waveform, voltage and time of instantaneous voltage drops (effective values) are recorded and displayed.
△
△
△
ー
ー
Regular and arbitrary printouts of annual reports
Enables printouts of cumulative monthly values, and average, maximum, minimum and cumulative total values of selected and registered pulse-data items for the year in table format as required or at a specified time on January 1st every year. Up to ten years worth of data can be stored and printed out in table format.
△
△
△
ー
ー
E-mail alarms
E-mail alerts regarding analog demand and failure data are sent to a registered e-mail address (e-mail server required).
△
△
△
ー
ー
Data exchange through Ethernet
Enables online data exchange between the data processing unit and personal computers of users via the Ethernet.
△
△
△
△
ー
Touch panel operation on monitor
Displays can be switched via touch-screen operations (17- and 19-inch monitor).
△
△
△
ー
ー
Remoto monitoring via telephone
Operating status of remote electrical equipment can be monitored via telephone.
△
△
△
ー
ー
BACnet
Electrical sub-system (B-BC) is installed to support BACnet communications (IEIEJ-G-0006: 2006) via the central monitoring system (B-OWS).
△
△
△
△
△
P12- 7
Others
Excel is a registered trademark of Microsoft Corporation.
1 Only displays the list of analog data.
9
Functions
Functions
10
Display/Printouts
Easy-to-view multicolor display and document output
Examples of monitor screen display 1 Menu selection
Network example 4 Message list display (event logger)
7 Display of single line diagram (option)
Communication A system structure allowing functions to be shared through general communications can be easily created. System structure enabling network communications
Host system RS-232C Power supply
CPU
I/F
MELSECNET Ethenet MS MS-OZ OZK
I/O
Modbus-RTU CDL bus EMC-B
Modbus-RTU CDL bus
EMC-B
LS
MCD
Control center (C/C)
Easy to select desired items via mouse operations.
2 Display of equipment status
Supports immediate recognition of ongoing failures and irregularities.
5 Trend display
MCD
LS
Medium-voltage switchboard (M/C)
Diagrams are displayed showing equipment status and failures.
8 Sample printout of alarms and events
Redundant systems for high reliability Redundant systems can be configured through use of various devices to create a system suited to the operational and environmental conditions.
Duplex configuration of CPU and host station System operation can be continued without failure even when one of CPU's is in failure or stopped for maintenance.
Host computer system
C P U
M S
|
O Z
M S
|
O Z K
RS-232C
Sub unit
CDL bus
C P U
M S
|
O Z
M S
|
O Z K
Computer link
9 Sample printout of daily reports
MELSECNET (optical)
Power supply
6 Demand monitoring
Enables printouts of the time and details of status variation and equipment failures/recoveries.
Computer link
3 Measurement value display
Visual representation of analog-data load trends.
Power supply
Equipment status is displayed in list format (single-line diagram not shown).
Main unit
EMC-B
Visual representation of measurement values.
11
Display/Printouts
Cumulative power consumption is displayed in graph form.
EMC-B1
Enables printouts of hourly measurement data such as maximum and minimum values.
Display/Printouts
12
Options
Wide range of easy-to-use optional functions
1 Graphic Panel Display
3 Capacitor Control for Power-factor Regulation (Reactive-power Control)
Single-line diagrams are displayed on the graphic panel to facilitate quick and easy comprehension of equipment status and failures. Example of graphic panel Graphic panel supervisory control system (Type-K)
Current reactive power (VAR) is measured, and capacitors are used to automatically regulate the power-factor to close to 100% (reactive power close to 0) through controlling the on/off operation of capacitor switches in a cyclic manner.
Example capacitor control for power-factor regulation
VAR1 52S1
Features
1. Silk screen printing (An optional mosaic panel also available) 2. Status display: LED (red/green) (Example) 52R1 3. Failure display: Individual / Collective LED display available. (Example)
2. The MELSAS-S monitoring computer can be used to set the reactive power upper limit on the advancing side (cut-off using capacitor switches) and the lower limit on the delay side (turn on/off using capacitor switches).
52 C2
52 C1
1. Smooth capacitor use is possible by cyclically controlling the on/off operations of capacitor switches (Mode 1 in figure on right).
Total supervisory control system (Type-T)
VAR2 52S2 52B
Capacitor switch 88 C18
88 C11
Power-factor regulating capacitor Mode 1
Bank 1 1
88 C28
88 C21
Bank 2 8
*1
1
8
*1 Up to 8 circuits can be contained in each bank.
Layout MELSAS-S introduction Layout example
Minor failure
4. Operation selection mode display: LED (amber) 5. Standard paint color: Base color: 5Y4/0.5 Busbar, symbols: DIC517, N9 (white) Text: N9 (white)
RS5
Factory 1
RS4
Optical fiber cable
2 Demand Control When demand exceeds the level-two alarm line, after a set amount of time, the input power is accumulated, and loads are cut-off starting with those of lower priority.
Type T
RS3 RS1
Item monitored
Demand Control Example
Power demand
Contract demand
Service gate
Item monitored
Final upper
Main gate
RS2
Demand control output (2 second pulse output)
Power distribution monitoring system
Type-T
For power receiving equipment
RS1
For factory 1 power distribution equipment A
RS2
Security room, for alarm equipment
RS3
For factory 1 power distribution equipment B
RS4
Factory 1 total management system, for communication interface
RS5
Control conditions 0 Initial upper
0
5
10
20
30 0
5
10
20
Level-one Demand alarm
Cutoff output (automatic)
Level-one
Level-two 1
2
3
30
Two-on output
Level-two 16
After 2 min. 5 sec. Each 1 min.
1
16
3 2 1
2
t 1
3
After 2 min. 5 sec. Each 1 min.
3
Cutoff signal is output after level-two demand alarm is issued continuously for a set amount of time (priority 1 only). Subsequenrly, cutoff every minute (priority 2 to 16).
*1
2
Power should be turned on again manually when demand returns to under the level-two alarm line. Control plan Measurement line
Turn-on output (manual)
Level-two alarm line Level-one alarm line
Use / Non-use
Use
Non-Use
Use
Time (in minutes) from start of 30 minute demand monitoring in which demand alarm does not activate can be set. 1had not been turned on, so fires blank even though cutoff signal is output. 1 to 16 indicate facility connection load. Procedures up to output point terminal block exposure are included in installation work covered by Mitsubishi Electric. Installation work performed by the customer includes selection of controller priority and items to be controlled as well as external line cable installation.
13
Options
Level-one demand alarm issued Level-two demand alarm issued Level-two demand alarm restored Level-one demand alarm restored
Mitsubishi Electric cubicle-type gas insulated switchgear (C-GIS)
Mitsubishi Electric medium-voltage switchgear “MS”
Existing equipment
Options
14
Network
Dimensions
Flexible transmission network
Equipment shaped to suit the application and installation space
Compact designs matched to the application enabling easy system setup in electrical rooms. Outline of operator consoles
Main line optical transmission
B
MELSECNET / H MELSECNET / 10
Inside panel Outdoors (reinforced)
1000
2000
AS-A
SG-AW
AS-D
SG-DL
Monitor
PR
500
GP
Select a cable type according to MELSECNET to be used, environmental conditon, and maximum distance between stations. 700
Network
Maximum distance between stations (m)
TP: Touch panel display PR: Printer
1. Total supervisory control system (Type-T)
Special skills and tools are required for connection of optical fiber cables and connectors. In addition, specialized connectors are required. Environmental conditon
GP: Graphic panel Monitor: LCD display
AS: H-PCF plastic clad glass fiber AG: SGF-GI all quartz glass
Core structure
350
MELSECNET/H: 400m when set to 25Mbps
1200 or 1400
Maintenance space
650
A
1000
700
1
2
3
A
800
1200
1600
B
700
1100
1500
(Note): Dimension 1400 is for A3 or 15-inch printer.
◎ : Recommended cable
Environmental conditon Number of cores
SG-AW
SG-DL
1000
1000
2000
2000
Inside panel
Outdoors (reinforced)
Inside of panel
Outdoors
2 cores
2 cores
2 cores
Single core × 2
SI
GI
GI
200
50
50
Clad (µm)
250
250
125
125
Transmission loss (dB/km)
6.0
6.0
3.0
3.0
DL-72ME
DL-72ME
DL6-CP
DL6-CP
2.8
11.0
2.8 × 5.6
12.0
Yellow
Black
Blue
Black
Sheath material
PVC
PE
PVC
LAP
Allowable tension (N)
196
735
160
490
Outer diameter (mm) Sheath color
Allowable bending diameter (mm)
When fixed
Operating temperature (°C)
700
SI 200
Connector
260 1200 or 1400
120
ー20∼70
ー20∼70
ー20∼60
ー20∼60
Reinforced fiber
Sheath
Sheath
700
Bench type E
30
Intervening material
Maintenance space
Cubicle type
100
Optical fiber
300
800
3. Supervisory system (Type-K)
30
Optical fiber core
Monitor
PR
Core (µm)
Type
2. Desktop supervisory control system (Type-D), data logger system (Type-L)
B
GP GP
Intervening rope
500
MELSECNET / H MELSECNET / 10
◎ AS-D
Intervening rope Center tension member
Structure Presser tape Sheath Tension member
Reinforcement
700
Distance between stations (m)
◎ AS-A
472
Cable type
2350
Optical-fiber specifications
Core wire
Sheath
Intervening material
1200 or 1500
A
Single core
D
Maintenance space
650
350
1000
Specify as follows for a purchase order Example of ordering SI type
1
2
3
4
1
2
3
A
1200
1600
2000
2400
D
800
1200
1600
B
1000
1400
1800
2200
E
700
1100
1500
700
Series name of optical fiber cable Select optical cable (series name) according to MELSECNET series. Series names for optical-fiber cable: AS, AQ, QH, QL, SG, M
5. Remote station
4. Local monitoring system (Type-M)
Connector attachment
A. Stand-alone
2P: Connectors attached to both ends / 1P: Connector attached to one end (SG only) / None: Cable only (on-site installation, etc.)
B. Wall-mountied
Cable length
Select a cable type according to operation environment.
TP
Wall
2350
Cable type
2350
Example of ordering GI type
600
Specify necessary length in 1m units.
A: Inside panel / B: Indoors / C: Outdoors / D: Outdoors (reinforced)*1 AW: Inside panel 2-core type (SG only) / BV: Indoors (SG only)*2 DL: Outdoors LAP type (QL, SG only)*2 / EL: Outdoors layer twisted type (SG only)*2
C: DL6-CP, F: FC connector, S: SC connector
Right side connector type (specify for SG type only)
500
300
(Note): Number of I/O connecting points per one panel: max. 30 points CDL transmission connecting points: max. 100 points
*1 2D for 2-core x 2, and 3D for 2-core x 3 (except for SG) *2 For BV, DL, and EL, specify 2-core, 4-core, or 6-core at the end of type name (except for QL).
Left side connector type (specify for SG type only)
Wall
Wall
A
B
1
2
Maximum Connecting Number
A
700
800
200 points
B
400
600
250 points
50
(Note): Number of I/O connecting points per one panel: max. 200 points
A
B
50
(Note): Number of I/O connecting points per one panel: max. 200 points
1
2
Maximum Connecting Number
A
700
800
200 points
B
400
600
250 points
C: DL6-CP, F: FC connector, S: SC connector
15
Network
Dimensions
16
Ordering Information Information required when ordering
4. Remote Station
To make an order, please fill out each item below.
□ Type-D Others □ Type-M □ Type-T □ Type-L □ Type-K On-site monitoring □ Training simulator Total supervisory Desktop supervisory Data logger system Supervisory control system □ Capacitor control unit control system control system system □ Power interruption and recovery control unit
2 3 4 5 6 7 8 Remarks
Future
×2
Present
×2
Future
×2
Present
×2
Future
×2
Present
×2
Future
×2
Present
×2
Future
×2
Present
×2
Future
×2
Present
×2
Future
×2
Present
×2
Future
×2
Maximum
Upper portion of the panel
Lower portion of the panel
I/O
Control wire tap
Wall-mounted
Stand-alone
Total
RS type
Remarks
×2
Present
1
On/Off output
Subtotal
Pulse input
Analog input
Failure input
Condition input
Electrical room
Connection with equipment
CDL transmission
2. Input / Output Points
Input/Output point
384
768
384
256
192×2
Put a check mark in one of the two.
Put a type and number.
Put a check mark in one of the two.
□Non-standard □Non-standard
(2) Graphic panel
□Silk prints
□Mosaic panel
(3) On/Off operation method
□Tag selection
(4) Failure display on the graphic panel
□Touch Panel failure message display
(5) Monitor
□17-inches LCD
(6) Printer
□A4 page printer
(7) Measurement value display on graphic panel
Option
17
Ordering Information
□500 X 300 X 600 (W X D X H) Number of I/O connection points: 30/panel
(2) Control power supply
□100VDC □200VAC
(3) Signal connection with equipment
□CDL transmission
(4) Auxiliary relays for signal transfer
̶
□Necessary for on/off signal output □Necessary for condition signal input □Necessary for failure signal input
(1) Main transmission line (installation responsibility)
□SI optical cable □Arranged by customer
□GI optical cable □Arranged by Mitsubishi Electric
(2) Host computer link
̶
□RS232C □Ethernet
6.Optional Functions
□Width: 800 □Width: 1200 □Width: 1600 □Width: 1200 □Width: 1600 □Width: 2200 □Width: 2400 □Width: 1200
□OA desk type (Type-D, Type-L, Type-T)
・Wall-mounted
□800 X 600 X 1950 (W X D X H) Number of I/O connection points: 250/panel □Others □800 X 600 X 1000 (W X D X H) Number of I/O connection points: 50/panel □Others □100VAC (UPS power) □200VAC □I/O connection
5. Transmission
3. Operator Console (1) Box type □Bench (Type-T, Type-K) □Cubicle (Type-K)
□630 X 400 X 2350 (W X D X H) Number of I/O connection points: 200/panel
(1)Box type ・Stand-alone
1. System Type
□Width: 1400 □Non-standard (with A3 or 15-inch printer)
System schematic diagram display Panel arrangement display Capacitor control Power interruption/recovery control Demand control Selective load shedding control Data exchange through Ethernet Pager failure alarm LCD touch operation Display of open/close time limit of circuit breaker Cumulative cutoff current display Higher harmonic display Operation support guidance display Operational guidance display in emergency Operation history display (operation hours, the number of on/off times) Annual report / arbitrary annual report
Type-T △ △ △ △ △ △ △ △ △ △ △ △ △ △ △ △
Type-D △ △ △ △ △ △ △ △ △ △ △ △ △ △ △ △
Type-L △ △ △ △ △ – △ △ △ △ △ △ △ △ △ △
△:Option Type-K Type-M – △ – △ △ △ △ △ – – – △ – – △ △ – – – △ – △ – △ – △ – △ – △ – –
7. Accessories
□Individual selection
(1) UPS power supply
̶
□Individual failure LED display □Batch failure LED display
(2) Printer cartridge (types T, D and L only) (3) System FD (types T, D and L only) (4) Printing paper (types T, D and L only) (5) Chair
Two pcs One box Two boxes (500 sheets / box) ̶
□21-inch LCD □17-inch LCD with touch operation □21-inch LCD with touch operation □A3 page printer □A4 color inkjet printer □15-inch dot printer □Analog meter □Digital meter
8. Spare Units (1) Input/output card (2) CPU unit (3) CPU power supply (4) Input/output power supply (5) Noise filter (6) Memory back-up battery
̶ ̶ ̶ ̶ ̶ ̶
Required □ □ □ □ □ □ □ □ □ □ □ □ □ □ □ □
□UPS 3kVA : units □UPS 5kVA : units □One more □One set □One chair
□One piece each □One unit □One unit □One unit □One unit □One