JNU Geothermal Heat Pump Project - 2014 Business of Clean ...

2 downloads 96 Views 2MB Size Report
JNU Geothermal Heat Pump Project. Catherine Fritz, AIA. Business of Clean Energy in Alaska Conference. April 29, 2011 ...
JNU Geothermal Heat Pump Project

Catherine Fritz, AIA Business of Clean Energy in Alaska Conference April 29, 2011

Juneau International Airport Basics

!! !! !! !! !! !! !!

400,000 annual enplanements Owned by City & Borough of Juneau Operates as an Enterprise, quasi-autonomous, led by a Board appointed by the elected city Assembly. Full Service Airport (121, 135, military, GA) Alaska Airlines is only Part 121 carrier Airfield constructed in 1930’s; terminal originated in 1948 Airport is constructed on filled wetlands

Terminal History 1948 Original terminal. 1957 2-story addition &Definition tower.of Sustainability 1972 North face addition. 1984 50,000 s.f. added.

Terminal Deficiencies

Terminal Improvements Project Priorities !!

Reduce Operating Costs –! –!

!!

Modernize Infrastructure –! –! –!

!!

Increase energy efficiency. Increase revenue opportunities.

Replace worn out mech/elect systems, interior finishes. Replace 1984 roof, including improving thermal envelope. Correct code deficiencies (including ADA).

Improve passenger experiences –! –! –! –! –!

Reduce congestion for passengers in baggage area, security screening, check-in, and departure lounge. Improve efficiencies and comfort of group tour passenger and baggage handling. Restore public meeting room to meet demand. Improve food and retail concessions, especially in secure departure lounge. Modernize the aesthetics of the terminal building.

Phased Approach Strategies !! Good

design, rather than lots of design. !! High performance envelope. !! Efficient lighting and energy standards. !! Consider alternative energy sources. !! Increase use of daylight. !! Modernize aesthetics.

Phase I Project Basics TOTAL PROJECT FUNDS = $23 million !! !!

FAA Funding: $9.9 million State of Alaska Funding: $2.8 million –!

!!

Included $513,000 Alaska Energy Authority Grant

City & Borough of Juneau Funding: $10.3 million

DESIGN TEAM: Jensen Yorba Lott Architects !! !!

Doug Murray, Mechanical Engineer Jim Rehfeldt, Energy Engineer

Exterior Improvements

R 45+ Roof R 40 Wall LED Exterior Lighting

Interior Improvements Daylight sensors Fluorescent & LED Interior Lighting

Expanded Bag Belt & Visitor Information Center Natural materials: terrazzo, slate, granite, cedar

Why Geothermal Heat Pumps? !!

!!

!!

!!

Energy benefits: greater efficiency; lower energy costs Equipment benefits: multiple small units v. central plant; ease of maintenance Building design benefits: space savings; lower construction costs Environmental benefits: low impact; modeling stewardship

JNU Feasibility Study Compared GSHP to new elect boilers. !! Considered various types of GSHP systems. !! Conducted Life Cycle Analysis of construction and operating costs. !! Study & Staff Cost = $40,000. !!

JNU’s GSHP System

!! !! !! !! !!

Closed Loop with 108 vertical borings, each 360 ft. deep. 16 miles of HDPE pipe in the field. 1.8 miles of piping in the Ice Melt System. 29 Electric Heat Pumps: 26 water-to-air (Climate Master); 3 water-to-water (McQuay). 1 Climate Master Direct Outside Air Supply (DOAS) unit.

Conceptual Design

Loop Field = 110 ft. x 275 ft. under commuter/charter aircraft tie-down area. Geothermal loop is sized to accommodate replacement of pre-1985 portions of terminal.

Drilled Vertical Borings

Spring/Summer 2009

Pipe Fusion

Loop Field Construction

Loop Field Construction

Into the Pump Room

Into the Ceilings Water to air heat pumps located in ceilings

Ice-Melt System

Water to water heat pumps serve the ice melt piping system.

Building Controls JNU system uses Alterton WebTalk for convenient access for multiple viewers.

Geothermal is Part of a Building System High Performance Envelope Upgrade Equipment Energy source generation Energy conservation policies

Project Recognition 2010 Community Award of Excellence From Alaska Municipal League

Design Challenges !! !! !! !!

Collaboration between Owner and Designer Who is responsible for the design? Specialty expertise combined with state registered design professional Lack of product expertise (relying on sales reps) Breaking the work into 2 components: Loop Field Construction and Building Construction. –! –! –!

Risks inherent in low bid procurement Risk of 2 contractors Harri Plumbing & Heating was Subcontractor for both.

Test Boring Challenges Accessing expertise and resources

July 20

Contracting Challenges !! !! !!

Politics of new technology: who is qualified to do the work? Attracting qualified bidders “The way we always do it” thinking IGSHPA Certification

www.igshpa.okstate.edu

Construction Challenges Weather: Too Hot

Construction Challenges

Weather: Too Wet

Snow Removal Equipment Facilities

!!

4 acres of horizontal

loop field, construction Summer 2011. !! In-slab heating with water-to-water heat pumps. !! Roadway & utilities to be constructed Summer 2011.

Sustainable Solutions at Juneau International Airport Sustainable design Definition of Sustainability creates places (communities, buildings) that advance enduring well-being. It is responsive to need, beautiful, socially appropriate, and economically sound.