Bitronics D/3 Orion. ® ... write values to ProLinx Gateway ... ProLinx 5303-MBP-
MNET Modbus Plus to Modbus TCP/IP Gateway Hardware Specifications.
Modbus Plus to Modbus TCP/IP
Bitronics D/3 O r i® on Bitronics D/3 Orion
®
Modbus Plus to Modbus TCP/IP OrionLX Interface Application
This document summarizes an interface (physical, communication, software) between the OrionLX Automation Platform and a third party product. This interface has been set up and tested by NovaTech and can be supported by NovaTech Applications Engineering. OrionLX connectivity to Modbus Plus (MB+) devices can be accomplished through the use of the ProSoft Technology ProLinx 5303-MBP-MNET Modbus Plus to Modbus TCP/IP Communication Gateway. Both Modbus TCP/IP Client (Master) and Server (Slave) modes are supported by the gateway, as illustrated below:
Master
Ethernet Network
Modbus Plus (MB+) Network
OrionLX as Modbus TCP/IP Client
Switch MB+ IED OrionLX writes to 4xxxx memory locations OrionLX polls 4xxxx memory locations
ProLinx Module as
ProLinx Module as
Mod TCP/IP Server
node on MB+
4000-point database (includes Global Data) plus 300-point diagnostics
Peer-to-Peer token passing communication ProLinx module reads values from & writes values to MB+ IEDs or MB+ IEDs read values from & write values to ProLinx Gateway
Slave Ethernet Network OrionLX as Modbus TCP/IP Server
Modbus Plus (MB+) Network Switch MB+ IED
ProLinx Module writes to OrionLX 4xxxx memory locations ProLinx Module reads OrionLX 4xxxx memory locations
ProLinx Module as Mod TCP/IP Client
ProLinx Module as node on MB+
4000-point database (includes Global Data) plus 300-point diagnostics
Peer-to-Peer token passing communication ProLinx module reads values from & writes values to MB+ IEDs or MB+ IEDs read values from & write values to ProLinx Gateway
ProLinx 5303-MBP-MNET Modbus Plus to Modbus TCP/IP Gateway Hardware Specifications • 24V dc, nominal, 18V dc to 36V dc acceptable range • Draws 500 mA at 24 Vdc • -4°F to +122°F (-20°C to +50°C) operating temperature • Dimensions: 5.20 inches High x 2.07 inches Wide x 4.52 inches Deep
Dual Modbus Plus ports (ports are hardware-redundant, not independently configurable.)
ProLinx #5303-MBP-MNET Protocol Support Modbus Plus • 64 nodes supported with up to 5 route path entries per node • Global In data supported - 64 nodes with 32 16-bit 4x registers maximum per node • Global Out data supported - Up to 32 16-bit 4x registers maximum output from the gateway node • Supports reading and writing only 4x Holding Registers (Modbus Function Codes 3 & 16) Please note: Bit reads and writes are not supported in the current Modbus Plus driver. Modbus TCP/IP – Supports Client (Master) and Server (Slave) functions • Supports Function Codes 1, 2, 3, 4, 5, 6, 15, & 16; for binary and word reads and writes • Simultaneously supports up to 5 Servers on Service Port 502 and up to 5 Servers on Service Port 2000 • Offers one Client with up to 200 configurable commands to poll other Servers on the Modbus TCP/IP network; may mix commands to Service Port 502 or 2000
Application Notes - Data is exchanged between networks by reading from, writing to, and storing in the gateway’s memory database, which holds 4000 16-bit words of user application data. - Requires configuration and record-keeping to cross-map Modbus TCP/IP and Modbus Plus. - “Industrial” ratings: 24V dc powered and -40F to +1220F operating temperature.
Ordering The ProLinx 5303-MBP-MNET Modbus Plus to Modbus TCP/IP Gateway can be ordered from NovaTech in Lenexa, Kansas at (913)451-1880 or from a ProSoft distributor (www.prosoft-technology.com). The material in this document was obtained from the latest ProSoft documentation. For more information please contact ProSoft at (661)716-5100.
Contact: Copyright © 2010 NovaTech, LLC. All rights reserved. All brand and product names mentioned in this document are trademarks of their respective owners. NovaTech is a registered trademark of NovaTech, LLC. The information in this literature is subject to change without notice and is not to be construed as a warranty. IA_ModbusPlustoModbusTCPIP_112310
NovaTech, LLC Orion Utility Automation 13555 West 107th Street Lenexa, KS 66215
T: 913.451.1880 F: 913.451.2845 E:
[email protected] www.novatechweb.com
Modbus Plus to Modbus TCP/IP
®
One RJ45 Ethernet port with Modbus TCP/IP Ethernet protocol (MBAP on Service Port 502; Encapsulated Modbus on Service Port 2000)
Orion
One serial configuration port for upload and download
D/3
The ProLinx module provides:
Bitronics
Bitronics D/3 O r i® on Bitronics D/3 Orion
®
Modbus Plus to Modbus TCP/IP OrionLX Interface Application