22. Relay catalogue. Safety Relay H-463. General. • 4 contacts. • Forced guided contact set. • According to EN 50205, application type A. • Ambient temperature ...
Safety Relay H-463 General

Connections • Soldering pins for PCB, pre-soldered with Sn100

• 4 contacts • Forced guided contact set • According to EN 50205, application type A • Ambient temperature – 25 … + 80 °C • Soldering heat resistance 260 °C/5s • RoHS compliance

Drive • Direct current, neutral monostable • Bistable upon request Approvals • CSA • TÜV Standards • EN 50205

Technical Data mechanical

Dimensions L x W x H (in mm)

dustproof: washtight:

typical 10 typical 14 typical 3,5 typical 4,5

Operating time NC-contact, contact opens Operating time NO-contact, contact closes Releasing time NO-contact, contact opens Releasing time NC-contact, contact closes

>10 7 cycles 50 g

Max. switching capacity Max. switching voltage Max. switching current Consant current Ith2 Constant current Ith2 at the same time over 2 contacts Constant current Ith2 at the same time over 3 contacts

AC 1.200 VA, DC *W AC 230/240 V, DC *V 6A 6A 6A 5A

AC-15 230/240 V DC-13 24 V

le = 1,5 A Ie = 2 A >10 5 cycles 6 A gL/gG-fuse

Electrical service life (with nominal load) Short-circuit capacity 1.000 A/AC 230 V * see DC-switching capacity

Over voltage category (Ü) III Degree of pollution (V) 2 Insulating material group II Insulation between Contact – Contact Contactset – Drive

Dimensions

22

Relay catalogue

ms ms ms ms

Mechanical service life (without load) Weight

Switching capacity

Insulation

42,7 x 16 x 38,8 42,7 x 16 x 39,9 15/15 g, 11 ms Half sinus 1,5/1,5 g, 10 – 150 Hz

Shock resistance NO-contact/NC-contact Vibration resistance NO-contact/NC-contact

Technical Data electrical

• IEC 61810-1

B-I = Basic insulation V-I = Reinforced (double) insulation

Nominal voltage network system AC 120/240 V AC 230/400 V V-l B-l V-l B-l

Air-/ creeping distance > 3 mm > 3 mm

Test voltage 50Hz/60s AC 2.500 V AC 2.500 V

Safety Relay H-463 Type key

Drive 0 DC polarized, monostable 5 DC neutral, bistable

Connections 3 Soldering pins for PCB and socket

Special version 1 Standard

Version 00 Standard 01 Special version

H O Z - 0 3 4 6 3 / 1 1 - 0 0 1 6 1 4 - 3 1 0 / 0 3 1 . 0 0 NO-contact Housing O dustproof (RT II)* D wash tight (RT III) C Dust protection base plate

Size 1 4 contacts

Coil See coil table

Contactset-number See contactset table

NC-contact

CO-contact

* Preferred version

AgCdO + 0,2 µm Au 030 031

Number of contacts NO/NC/CO-contacts 220 310

Contactset table

AgCdO + 5 µm Au 038 037

AgCdO AgSnO2 + 10 µm Au + 0,2 µm Au 034 040 032 043

AgSnO2 + 5 µm Au 041 044

Contact material Contactset number

All values at ambient temperature Tu = 20 °C

Coil table Number of contacts 310

Coil-No. 1626 1620 1614 1611 1709 1083 1303

Resistance R/Ω 32 130 500 1.900 3.100 10.000 25.000

Resistancetolerance ± 5% 7% 8% 7% 7% 9% 12%

U1/V

U2/V

U3/V

Urück/V

3,9 8,0 16,1 31,6 40,4 73,9 125,5

10,3 20,7 40,4 79,0 100,9 179,9 281,7

11 23 45 89 114 202 328

0,7 1,5 2,9 5,7 7,3 13,0 21,1

U1/V

U2/V

U3/V

Urück/V

3,9 8,0 16,1 31,6 40,4 73,9 125,5

10,3 20,7 40,4 79,0 100,9 179,9 281,7

11 23 45 89 114 202 328

0,5 1,1 2,1 4,2 5,4 9,5 15,4

Printing Unom/V 6 12 24 48 60 110 220

All values at ambient temperature Tu = 20 °C Coil-No.

Number of contacts 220

1626 1620 1614 1611 1709 1083 1303 U 1: U 2: U 3: U rück:

Resistance R/Ω 32 130 500 1.900 3.100 10.000 25.000

Resistancetolerance ± 5% 7% 8% 7% 7% 9% 12%

Printing Unom/V 6 12 24 48 60 110 220

Minimum operating voltage with consideration of coil self heating Thermal restricted maximum coil voltage Maximum admissible coil voltage to realize a contact gap of > 0.5 mm also at a contact fault Releasing voltage

Further coils are possible and available

Relay cataogue

23

Safety Relay H-463 Running types

Article-No. 463-1013 463-1014 463-1034 463-1119 463-1122 463-1145 463-1164 463-1179 463-1185 463-1195 463-1212 463-1220

Type key HOZ-03463/11-001620-220/030.00 HOZ-03463/11-001620-310/031.00 HOZ-03463/11-001614-310/031.00 HOZ-03463/11-001626-220/030.00 HOZ-03463/11-001614-220/030.00 HOZ-03463/11-001614-220/038.00 HOZ-03463/11-001303-220/030.00 HOZ-03463/11-001614-310/037.00 HOZ-03463/11-001620-220/038.00 HOZ-03463/11-001614-220/038.00 HOZ-03463/11-001083-220/038.00 HOZ-03463/11-001520-220/038.01

Printing Unom DC 12 V DC 12 V DC 24 V DC 6 V DC 24 V DC 24 V DC 220 V DC 24 V DC 12 V DC 24 V DC 110 V DC 12 V

U1/V

2 NO / 2 NC (220)

Connection grid Few on soldering side

8,0 8,0 16,1 3,9 16,1 16,1 125,5 16,1 8,0 16,1 73,9 8,0

U2/V

U3/V

20,7 20,7 40,4 10,3 40,4 40,4 281,7 40,4 20,7 40,4 179,9 20,7

Urück/V

23 23 45 11 45 45 328 45 23 45 202 23

3NO / 1 NC (310)

Inactive area

Diagrams current (A)

Contactgap:

current (A)

Arc duration

0

Switching voltage

DC-switching capacity

24

Relay catalogue

0

Switching cycles

Electrical service life

1,1 1,5 2,9 0,5 2,1 2,1 15,4 2,9 1,1 2,1 9,5 1,1

Safety Relay H-463 Accessories

Socket for PCB mounting

Base plate for dust protection and insulation strength: 2,5 kV Article-No.: 463-8002

Article-No.: 463-8001

Relay catalogue

25