Seismic Retrofit of Industrial Precast Concrete Structures Using

0 downloads 0 Views 4MB Size Report
This paper presents seismic retrofit of one typical single-story industrial-type ... In Turkey, precast concrete is one of the most preferred type of construction.
ATC & SEI 2015

693

Seismic Retrofit of Industrial Precast Concrete Structures Using Friction Dampers: Case Study from Turkey S. Yildirim1; A. Kalyoncuoglu1; B. Erkus2; and Y. Tonguc1

Downloaded from ascelibrary.org by Istanbul Teknik Universitesi on 12/08/15. Copyright ASCE. For personal use only; all rights reserved.

1

Promer Consulting Engineering Ltd. Co., Mutlukent Mah. 5.Cadde 1967. Sok. No. 14 Umitkoy, Ankara 06800. E-mail: [email protected]; [email protected]; [email protected] 2 Dept. of Civil Engineering, Istanbul Technical Univ., Maslak, Istanbul 34469. Email: [email protected] Abstract This paper presents seismic retrofit of one typical single-story industrial-type precast reinforced concrete building structure located in Turkey using rotational friction dampers. This project consist of retrofitting twelve precast reinforced concrete buildings and it is considered to be the first fully engineered and completed application of supplemental energy dissipation devices for retrofitting purpose in Turkey. In Turkey, precast concrete is one of the most preferred type of construction for all type of industrial structures due to their low cost, fast construction, and availability in rural areas. Unfortunately, most of these structures constructed before “Specification for Buildings to be Built in Seismic Zones (2007) (TEC)” are not well-engineered and are expected to have very poor performance when exposed to a major seismic event. One of the importand official instutions of Turkey decided to undertake a major project to retrofit their single story precast concrete buildings. It is required that buildings will not be vacated during retrofit and disturbance to the building operation will be the minimum. Existing building structures are examined and reviewed in detail, and based on the comparison of several retrofitting schemes, it was concluded that seismic retrofit with energy dissipation devices is a feasible option for the subject buildings. Rotational friction dampers are selected as the supplemental energy dissipation device. ASCE 41-06 is employed for the damper design and performance evaluation. The most effective damper configuration and capacities are selected after an intensive iterative trial-and-error linear study. Finally, nonlinear time-history analyses are performed for seven pairs of historical ground motion acceleration data and it is shown that proposed retrofit scheme satisfies the desired performance goals for both DBE and MCE events. In overall, it is considered that proposed retrofit scheme with dampers provides a viable solution to the stakeholders of the project from performance, design, constructability, and economical points of view. Some application photos were presented and methods are explained in detail in the paper.

© ASCE and ATC 2015 Improving the Seismic Performance of Existing Buildings and Other Structures 2015

ATC & SEI 2015

694

Downloaded from ascelibrary.org by Istanbul Teknik Universitesi on 12/08/15. Copyright ASCE. For personal use only; all rights reserved.

INTRODUCTION Precast structural forms have been developed for economic and time dependent reasons with evolving technology. Especially in industrial buildings, precast concrete structures are widely used due to their advantages such as low cost, short construction period and availability in rural areas. Unfortunately, most of the precast concrete buildings built before Turkish Code 2007 is not well engineered or not well contracted in Turkey. It is expected that these buildings have very poor structural performance in an expected major seismic event in Turkey. In 1999 Kocaeli and 1999 Duzce earthquakes, many precast concrete structures were either fully collapsed or had significant damage causing economical and life lost. Also suspension of production due to the earthquake damages in industrial buildings, have led to catastrophic economic losses. Precast reinforced concrete buildings have some design disadvantages such as nonsatisfactory weak connections, bad load transfer mechanism, overturning problems of the main beams in an earthquake and no diaphragm behavior at the roof level of the building. Beam column connections are simple connections using pin or welding. It is observed in previous earthquakes that these types of connections were not successful to keep the beam in place. Beams were dropping down or having overturning problem breaking the pin or welding. Horizontal load transfer between columns generally provided by gutter beams in these building. Mostly gutter beams are structurally weak members and have heavy corrosion damage as a reason of water drainage system in the roof. Moreover they are connected to columns via simple pins. Thus, load carrying and transfer capacity of these beams are not strong enough. Also, the structures have a roof frequently that is either not designed to act as a diaphragm or low diaphragm capacity. This can be resulted as failure of secondary beams at the roof due to seismic loads. While Turkish Seismic Code that is currently being prepared is supposed to have a more detailed special chapter related to prefabricated structures, existing precast concrete building stock possesses a major risk and needs to be mitigated. Due to the low quality of engineering or construction explained above, most of the industrial buildings do not fulfill requirements of existing Turkish Seismic Code (2007). Generally, retrofit of these buildings is not considered because the cost of retrofit may exceed to the original cost of the structure. Also, building owner is not willing to proceed a retrofit due to high cost of evacuating the building or stop working. In addition, classical retrofitting methods like as jacketing and adding structural elements require a major disturbance to the operations of buildings including relocation expenses. Further, it is hard to retrofit weak connections of the building. Therefore, retrofitting of precast reinforced concrete buildings are not feasible mostly and has not been applied much in Turkey. Having understood this risk, Ministry of The Official Institution decided to undertake a major project to retrofit their single story precast concrete buildings, where twelve buildings are planned to be retrofitted as the first phase of the project. It is required that buildings will not be vacated during retrofit and disturbance to the building operation will be the lowest level. Existing building structures are examined and reviewed in detail, and based on the

© ASCE and ATC 2015 Improving the Seismic Performance of Existing Buildings and Other Structures 2015

ATC & SEI 2015

695

Downloaded from ascelibrary.org by Istanbul Teknik Universitesi on 12/08/15. Copyright ASCE. For personal use only; all rights reserved.

com mparison off several retrofitting sch hemes, it w was concludeed that seism mic retrofit witth energy disssipation dev vices is a feaasible optionn for the subjject buildinggs. Th he structuree is exposed to high seismic eneergy duringg a major eearthquake. Stru uctural elem ments absorb b this energ gy by havinng damage. Friction daampers are dessigned to traansform this earthquake energy to hheat by meanns of frictionn to reduce thee load on stru uctural elemeents. In this project rotattional frictioon dampers aare selected as the supplem mental energ gy dissipatio on. This pap aper presentss seismic reetrofit of a typ pical one of twelve t singlee-story industrial-type pprecast reinfoorced concreete building stru uctures locaated in Turrkey. This project p is cconsidered to be the first fullyeng gineered and d completed application of supplemeental energy dissipation devices for retrrofitting purp pose in Turk key.

EX XISTING ST TRUCTURE E INFORM MATION Thee typical stru ucture which h is subject to this paperr, was one sstory buildinng and have 9 nine n bays in long directio on. Outside and inside pphotos of thee structure aare given in Fig gure 1a, Figu ure 1b, Figurre 1c and Fig gure 1d. Geoometrical prooperties of thhe building aree given in Fig gure 2. There are 18 colu umns which have dimennsion of 40cm mx40cm.

(1a)

(1b b)

(1c)

(1d d)

Figure F 1. Outside and inside i photo os of the strructure(1a. L Left Side, 1b. Right Side, 1c. Inside, I 1d. IInside)

© ASCE and ATC 2015 Improving the Seismic Performance of Existing Buildings and Other Structures 2015

ATC & SEI 2015

696

C A A

B

Figure 2. Geometrical propertiees of the buiilding Sitee investigattion was peerformed in n the structture to dettermine conndition and geo ometry of th he building.. All investigation of tthe structuraal elements was made acccording to TEC (2007). Reinforcem ments were ddetermined bby using bothh ferroscan equ uipment and d visual inspection after removing cclear cover oof concrete oof columns (Figure 3).

Figure F 3. Ideentification of column reinforcemeent with cleearing the coover and feerro-scan. Com mpressive concrete c strrength of th he columns was determ mined by taking core sam mples. Comp pressive streength core sample s resullts of concreete were corrrected and calculated acco ording to meethods suggeested by AC CI 318. Accoording to ressults of the periments off 9 core sam mples, concreete compresssive strengthh was found as 35 MPa exp wh hich was suiitable and proper p to use damper aapplication. IInteractive ddiagram of 40x x40 column type was calculated c by y using Xtraact Section Analysis sooftware and giv ven in Figure 4. Soil typ pe of the laand was deteermined as Z2 accordinng to TEC. Alsso, snow loaad was consid dered as 75 kg/m2 k accorrding to TS4498. -700 00 Axial Force (kN)

Downloaded from ascelibrary.org by Istanbul Teknik Universitesi on 12/08/15. Copyright ASCE. For personal use only; all rights reserved.

A = 7.40m 7 B = 14.90m 1 C = 4.10m 4

-500 00

M Moment (kNm m) 0-90° degreee 45° degree

-300 00 -100 00 0

00 10

200

300

4000

100 00

Figure 4. Column C inteeractive diag gram (40cm mx40cm sym mmetrical coolumns)

© ASCE and ATC 2015 Improving the Seismic Performance of Existing Buildings and Other Structures 2015

ATC & SEI 2015

697

AN NALYSIS OF O THE STR RUCTURE

Downloaded from ascelibrary.org by Istanbul Teknik Universitesi on 12/08/15. Copyright ASCE. For personal use only; all rights reserved.

Mathem matical modeel of the buiilding was ccreated by ussing SAP20000 analysis sofftware. Both h linear anallysis and no onlinear partt of analysiss were condducted with Sap p 2000. Strucctural modell of bare fram me was giveen in Figure 5.

Figuree 5: SAP200 00 Structuraal Model Design objectives are a set Imm mediate Occuupancy for tthe Design B Basis Earth (DB BE) and Colllapse Preven ntion for thee Maximum Considered Earthquake (MCE) for thee structure according to ASCE41-06 6. Assessmeent analysis results and number of elem ments which h was is not satisfy the reegulations p roperly was given in Taable 1. Table 1: Analy ysis results of existing buildings b foor DBE and MCE earth hquakes

STOR RY DRIFT BASE SHEA AR FORCE (KN) IMMEDIAT I TE OCCUPA ANCY COLLAPSE E PREVENT TION COL LLAPSE

E EXISTING B BUILDING X DIRECT TION Y DIRECTION DBE MCE DBE MCE 2.04% 3.06% 2.04% 3.06% 1537.98 2307.78 1537.98 2307.78 4 0 0 0 14 4 0 18 0 14 0 0

Infill walls, w which contribute c to o the stiffnesss of the struucture, are innvestigated by using strut models. m Stru ut model dim mensions werre calculatedd by using m model which oposed by Mainstone M (1979). Fou ur strut moodels were defined to model as pro equ uivalent of in nfill wall witth different openings. o Innfill walls weere considerred in linear anaalysis but diisregarded in n nonlinear analysis off retrofitting since the lload on the walls was much h higher than n infill wallss capacity, leeading crackking all of thhe walls. There is a steel plaate in the roo of with a 0.55mm thicknness, it was pproved that thiss plate effeects modal behavior b off the structuure to a lim mited extend. Thus, a rep presentative sheet coverr was defin ned to top of the building in thhe analysis. Com mparison off modal inforrmation betw ween bare frrame and fraame with dam mpers were giv ven in Table 2. Table 2: Moda al informatiion of the bu uildings T WITHOUT IN NFILL WA ALL Tx (sec) Ty (sec) 0.6 613 0..613 BA ARE FRAM ME 0.4 431 0..361 FR RAME WIT TH DAMPE ERS

W WITH INFIILL WALL Txx (sec) Tyy (sec) 0..598 0.267 0..428 0.263

© ASCE and ATC 2015 Improving the Seismic Performance of Existing Buildings and Other Structures 2015

ATC & SEI 2015

698

Downloaded from ascelibrary.org by Istanbul Teknik Universitesi on 12/08/15. Copyright ASCE. For personal use only; all rights reserved.

RE ETROFITTIING OF TH HE STRUCT TURE Retrofittting structurre with conv ventional meethods are vvery difficultt and costly beccause of the hinged desig gn of structu ure and it waas required thhat building will not be vaccated during g retrofit. Therefore, T dampers d weere used to retrofit thee building. Mo oreover som me more preccautions werre taken to aassure load transfer mechanism of thee structure su uch as desig gning comprression bars between coolumns and some steel members to keeep the beam m in its placce. Equivallent static pprocedure waas used for preeliminary an nalyses, wheere design base b shear w was reducedd based on the added equ uivalent dam mping. Effecctive dampin ng ratios off the dampeers were callculated by usin ng Equation ns 1 which was w suggested d by ASCE77-10.

0.64

1

1

Eq. 1

In Equation E 1, is hysterresis loop adj djustment facctor which iss taken as 0,,5. is the com mponent of effective daamping of th he structure due to the inherent disssipation of eneergy by elem ments of thee structure. is effectivve ductility ddemand on tthe seismic force-resisting system. Equ uation 2 whiich was sugggested by A ASCE41-13 w was used to calculate reducced base sh hear force due d to the eequivalent ddamping eneergy of the sysstem. In Equ uation 2, is i the reducin ng coefficiennt and is eequivalent daamping.

4/ 5.6

ln 10 00

Eq. 2

The mo ost promising g damper co onfiguration and capacitiies are selectted after an inteensive iterative trial-and d-error study y. Accordingg to this conffiguration, ddampers are plaaced at the beam-colum mn connectiions, whichh are pin-coonnected, inn the short direection. In th he long direcction, steel compression c members ar are designed in order to pro ovide load trransfer betweeen frames. Then, steel braces withh dampers arre placed in onee or severaal bays. Lo ocations werre given inn Figure 6,, Figure 7, Figure 8, resp pectively. SA AP2000 stru uctural modeels of retrofiitted frame w were given iin Figure 9. Perrformance off the column ns was shown n to satisfy tthe desired ggoals for botth DBE and MC CE events.

Figuree 6. Damperrs locations in X Directtion

© ASCE and ATC 2015 Improving the Seismic Performance of Existing Buildings and Other Structures 2015

ATC & SEI 2015

699

Downloaded from ascelibrary.org by Istanbul Teknik Universitesi on 12/08/15. Copyright ASCE. For personal use only; all rights reserved.

Figuree 7. Damperrs locations in Y Directtion

Figuree 8. Damperrs locations in Y Directtion

Figu ure 9: SAP2 2000 Struct ural Model Finally,, nonlinear time-history y analyses aare perform med for seveen pairs of histtorical grou und motion acceleration n data. Histoorical grounnd motion aacceleration datta were scalled to the MCE M respon nse spectra by using S SeismoMatchh software. Infformation off earthquakess that used in nonlinear time-historyy analysis w was given in Tab ble 3. Table 3: Earth hquake info ormation Dü üzce (1999) Dü üzce (1999) Errzincan (1992 2) Heector (1999) Ko obe (1995) Ko ocaeli (1999) Laanders (1992))

Station Bolu Düzce Erzincan n Hector Mine M Shinosak ka İzmit Joshuatrree

Magn nitude (Mw) 7.2 7.2 7.8 7.1 6.9 7.6 7.3

© ASCE and ATC 2015 Improving the Seismic Performance of Existing Buildings and Other Structures 2015

Downloaded from ascelibrary.org by Istanbul Teknik Universitesi on 12/08/15. Copyright ASCE. For personal use only; all rights reserved.

ATC & SEI 2015

700

The comparison of damping ratios for both linear and nonlinear methods was given in Table 4. Nonlinear damping ratios for different seven pairs of historical ground motion acceleration data were given in Figure 10. Also base shear force – time and displacement – time diagrams were given between Figure 11 and Figure 18 for only Kocaeli (1999) – İzmit and Düzce (1999) – Düzce earthquakes. The earthquake name numbered as (1) like (Kocaeli(1)) represents that the earthquake FN data(Fault normal) was loaded in X direction while FP data(Fault parallel) was loaded in Y direction and vice versa for the earthquake name numbered as (2). Table 4: The comparison of damping ratios for analysis type MCE Earthquake

X Direction

Y Direction

LINEAR DAMPING

11%

16%

NONLINEAR DAMPING (AVERAGE)

17%

34%

70% 60%

Columns Damper (X Direction) Damper (Y Direction)

50% 40% 30% 20% 10% 0%

Figure 10. Nonlinear energy consumption ratios of columns and dampers for different seven pairs of historical ground motion acceleration data

© ASCE and ATC 2015 Improving the Seismic Performance of Existing Buildings and Other Structures 2015

Kocaeli1 - X Direction

1500 1000 500 0 -500 -1000 -1500

Base Shear Force (kN)

Base Shear Force (kN)

701

Bare Frame Retrofitted

0

10 20 Time (sec)

Kocaeli1 - Y Direction

800 600 400 200 0 -200 -400 -600 -800

Bare Frame Retrofitted

0

10 20 Time (sec)

Kocaeli1 - X Direction

80 60 40 20 0 -20 -40 -60 -80

Bare Frame Retrofitted

0

10 20 Time (sec)

Top Displacement (mm)

Top Displacement (mm)

Figure 11. Base Shear Force – Time diagram of Kocaeli (1999) - İzmit – 1 earthquake Kocaeli1 - Y Direction

40 20 0 -20 -40 -60 -80 -100 -120 -140

30

Retrofitted Bare Frame

0

10 20 Time (sec)

30

Figure 12. Top Displacement – Time diagram of Kocaeli (1999) - İzmit – 1 earthquake Kocaeli2- X Direction

1500 1000 500 0 -500

-1000

Bare Frame Retrofitted

-1500 0

10 20 Time (sec)

Base Shear Force (kN)

Base Shear Force (kN)

Downloaded from ascelibrary.org by Istanbul Teknik Universitesi on 12/08/15. Copyright ASCE. For personal use only; all rights reserved.

ATC & SEI 2015

Kocaeli2- Y Direction

800 600 400 200 0 -200 -400 -600 -800

Bare Frame Retrofitted 0

10 20 Time (sec)

Figure 13. Base Shear Force – Time diagram of Kocaeli (1999) - İzmit – 2 earthquake

© ASCE and ATC 2015 Improving the Seismic Performance of Existing Buildings and Other Structures 2015

702

Top Displacement (mm)

100 50 0 -50

Retrofitted Bare Frame

-100 0

10 20 Time (sec)

Top Displacement (mm)

Kocaeli2 - X Direction

150

Kocaeli2 - Y Direction

140 120 100 80 60 40 20 0 -20 -40

30

Retrofitted Bare Frame

0

10 20 Time (sec)

30

Düzce-Düzce 1 - X Direction 1500 1000 500 0 -500

-1000

Bare Frame Retrofitted

-1500

Base Shear Force (kN)

Figure 14. Top Displacement – Time diagram of Kocaeli (1999) - İzmit – 2 earthquake

Base Shear Force (kN)

Downloaded from ascelibrary.org by Istanbul Teknik Universitesi on 12/08/15. Copyright ASCE. For personal use only; all rights reserved.

ATC & SEI 2015

800 600 400 200 0 -200 -400 -600 -800

Düzce-Düzce 1 - Y Direction

Bare Frame Retrofitted

0 10 20 10 20 30 Time (sec) Time (sec) Figure 15. Base Shear Force – Time diagram of Kocaeli (1999) - İzmit – 1 earthquake 0

© ASCE and ATC 2015 Improving the Seismic Performance of Existing Buildings and Other Structures 2015

30

Düzce1 - X Direction

100 50 0 -50 -100 -150 -200 -250 -300

Retrofitted Bare Frame

0

10 20 Time (sec)

Top Displacement (mm)

Top Displacement (mm)

703

Düzce1 - Y Direction

150 100 50 0 -50

Retrofitted Bare Frame

-100

30

0

10 20 Time (sec)

30

1500

Düzce-Düzce2 - X Direction

1000 500 0 -500 Bare Frame Retrofitted

-1000 -1500

Base Shear Force (kN)

Base Shear Force (kN)

Figure 16. Top Displacement – Time diagram of Kocaeli (1999) - İzmit – 1 earthquake 800 600 400 200 0 -200 -400 -600 -800

Düzce-Düzce2 - Y Direction

Bare Frame Retrofitted

0 10 20 30 20 Time (sec) Time (sec) Figure 17. Base Shear Force – Time diagram of Kocaeli (1999) - İzmit – 2 earthquake 0

Düzce2 - X Direction

150 100 50 0 -50

Retrofitted Bare Frame

-100 0

10 20 Time (sec)

30

Top Displacement (mm)

Top Displacement (mm)

Downloaded from ascelibrary.org by Istanbul Teknik Universitesi on 12/08/15. Copyright ASCE. For personal use only; all rights reserved.

ATC & SEI 2015

Düzce2 - Y Direction

100 50 0 -50 -100

Retrofitted Bare Frame

-150 0

10 20 Time (sec)

Figure 18. Top Displacement – Time diagram of Kocaeli (1999) - İzmit – 2 earthquake

© ASCE and ATC 2015 Improving the Seismic Performance of Existing Buildings and Other Structures 2015

30

ATC & SEI 2015

704

Linear assessment analysis off the retrofittted structurre for DBE and MCE eveents were giv ven in Tablee 5. Results show s that prooposed retroofit scheme ssatisfies the dessired perform mance goals for MCE ev vents.

Downloaded from ascelibrary.org by Istanbul Teknik Universitesi on 12/08/15. Copyright ASCE. For personal use only; all rights reserved.

Table 5: Linea ar assessmen nt analysis results

STOR RY DRIFT BASE SHEA AR FORCE (KN) IMMEDIAT I TE OCCUPA ANCY COLLAPSE E PREVENT TION COL LLAPSE

RET TROFITTED D BUILDING G X DIREC CTION Y DIRE ECTION DBE MCE DBE MCE 1.14% 1.02% 1.18% 1.20% 1010.82 1368.41 903.627 1247 18 18 18 18 0 0 0 0 0 0 0 0

RE ETROFITTIING PROC CESS After design d analysis was don ne, detailed technical drrawings werre prepared and d application n of retrofittting was staarted. Retroofitting instaallation proccesses were acccomplished in i 1 month with w minimu um disturbannce in the buuilding. Theere were no neeed to vacate the building g during thee retrofitting process. Phhotos of the retrofitting app plication werre given in Figure F 19.

Figuree 19. Photoss of retrofittted structurre CO ONCLUSIO ONS Perrformance go oals of ASCE 41-06 and d Turkish Eaarthquake Coode 2007 weere satisfied retrrofitting usin ng frictional dampers an nd some addiitional steel members. Innstallations of steel membeers and dam mpers at site were complleted more oor less withinn 1 months nts of client aas well. witthout any need to evacuaate the buildiing meeting requirement Tottal damping ratios calcu ulated were 11% 1 and 16 % for linearr calculations for X and Y directions d reespectively whereas w thee damping rratios were ccalculated aas 17% and 34% % for nonlin near calculattions for X and a Y directiions respectiively. Calcuulated ratios sho owed that lin near analysiss is 45%-50% % conservattive for this pproject.

© ASCE and ATC 2015 Improving the Seismic Performance of Existing Buildings and Other Structures 2015

ATC & SEI 2015

705

ACKNOWLEDGMENTS

Downloaded from ascelibrary.org by Istanbul Teknik Universitesi on 12/08/15. Copyright ASCE. For personal use only; all rights reserved.

The authors thank Official Institution, Istanbul Technical University Civil Engineering Department and Promer Company for all contributions to this paper. This paper covers some of the studies in Retrofitting project of an important Official Institution (Name could not be mentioned due to NDA). REFERENCES American Concrete Institute(ACI), (2014). Building Code Requirements for Structural Concrete, Farmington Hills, Michigan, USA. American Society of Civil Engineers (ASCE), (2006). Seismic Rehabilitation of Existing Buildings, USA. American Society of Civil Engineers (ASCE), (2010). Minimum Design Loads for Buildings and Other Structures, USA. Mainstone, R. J., (1971). On the stiffness and strengths of infilled frames, Proceedings, Institution of Civil Engineers, Supplement IV, 57–90. Ministry of Public Works and Settlement, (2007). Specification for Buildings to be Built in Seismic Zones, Government of Republic of Turkey, Turkey. SAP2000, Integrated Structural Analysis and Design Software, Computers and Structures, Inc. SeismoMatch, Seismosoft Earthquake Engineering Software Solutions, Italy. Turkish Standard Institue(TS), (1997), Calculation values of load on structural design(TS498), Ankara. Xtract Cross Section Analysis Program for Structural Engineers, 3.0.8, 2007.