Untitled - "ENERGOPOMIAR-ELEKTRYKA" Sp. z oo

2 downloads 137 Views 23MB Size Report
Graphical firmware Hydrosoft enables Hydrocal parameters setting and data ... in -oil measurements, ZVCM 1001 device for bushings monitoring and SMT ...
Power Research and Testing Company

„ENERGOPOM1AR-ELEKTRYKA”Ltd.

The Company was established in 1992 after ownership changes of Electric and Energy Management Department of ZPBE Energopomiar Gliwice. We continue activities of ZPBE Energopomiar and use tens of years experience in work for power industry. We employ high-qualified engineers and technicians, with long-time experience, what guarantees professional service and quality of our products. The Company policy is that all employees take part in meeting customers requirements, by realizing and promotion of principle:

COMPANY CORE BUSSINESS IS: services and measurement – research work for the power engineering and for other branches of industry comprising all stages of electric energy management, beginning with generation, through transmission and distribution and ending with all ways of utilization; full

engineering

service

at

building/production/

operation and refurbishment stages of power industry objects (Contract Supervisor), technical consulting in selecting new project solutions,

QUALITY

IS NOT INCIDENT

devices, protection systems and equipment used in power engineering and in other branches of industry; tests and evaluation of electrical power engineering equipment,

It is assured by our laboratories certified in Polish Centre of Accreditation: Measuring Devices Laboratory (certificate no. AP 063) for calibration of control and measurement apparatus Testing Laboratory of Switchgears and Substations (certificate no. AB269) which deals with: inspection and testing technical properties of low and medium voltage apparatus, accessories and devices,

comprehensive work connected with environment protection against noise, vibrations, electric and magnetic field, as well as hazard caused by electric energy devices under voltage, expertise and post-fault analysis, expert opinions about introducing green energy sources into National Power System, production of test and measurement equipment as well as diagnostics apparatus.

research of 50 Hz electromagnetic field (produced by power and industrial sources) influence on people and environment, thermovision inspections of temperature distribution in power apparatus, measurements of noise, produced by industrial and energy objects and HV transmission lines, PD measurements in electrical apparatus.

Detailed description of our services and production scope is on our internet page: www.elektryka.com.pl

CONTENTS Advanced technology and

three-phase circuit analyser type ANOT-10 .............................. 2

functionality are attributes of control-measurement and diagnostics devices produced by Energopomiar-Elektryka.

control meter type LK-10.................................... 4 meter test device type TL-1 ...................................... 6 transformer diagnostic device type UDT-2................................... 8

Our devices are developed on the base of Customers needs and operation experience. Close co-operation with users allows to optimize technical features and measurement abilities.

Gas-in-Oil-Analysis System with Transformer Monitoring Functions type Hydrocal -1003/1005.......... 10

Ordered devices could be independently checked in our Measuring Devices Laboratory (including accredited scope – Accreditation Certificate AP 063).

transformer’s tap-changer position indicator type PZT-30 ................................ 12 shock recorder type RW-1 .................................. 14 microprocessor-controlled chronograph type SM-1 .................................. 16 phase shifter type PF ....................................... 18 three-phase voltage generator type GU3F.................................. 20 current source type PWPN-1.............................. 22 telecontrol device type RL-64D ............................... 24

We offer devices for following applications: current transformers testing, switch tests, transformer diagnostics and protection, transport assessment of transformers and generators, loading of measuring transformers,

switch contacts anticoincidence meter type MND-26 ............................. 26 DC current source type WPS-300 / WPS-600 ........... 28 power supply for switch’s coils type ZCW-1 ................................ 30

measurement of electrical energy parameters, time measurements,

electrocution voltage selector type ZNR-1 ................................. 32

transient recordings, testing of electric energy meters, checking resistance of bolted joints, verifying of current releases, synchronization and parallel connection of two power energy systems, testing of earthing systems, testing of Electronic Protection Systems, ferroresonance signals suppression, LV and MV lines protection, telecontrol.

electrocution voltage selector type ZNR-2 ................................. 34 electrocution voltage meter type MNR-1 ............................... 36 current source type WP-100 .............................. 38 current source type WP-1000 ............................ 40 current source type WPu-4000 .......................... 42 DC/AC current source type WPPS-300 .......................... 44 current transformer testing device type TP-100................................ 46

ANOT-10

[three-phase circuit analyser]

AC current measurement

ranges: 5 A, 15 A (with Dietz clamp meter or current loop: 700 A)

Allowable uncertainty of AC current measurement

±(0,1 % of reading + 1 digit)

AC voltage measurement

Ranges: 450 + 10 % V single phase voltage; 780 + 10 % V interfacial voltage

Allowable uncertainty of AC voltage measurement

±(0,1 % of reading + 1 digit)

Active, reactive and apparent power measurement

Ranges: up to 2000 (VA, W, var) for Aaron circuit: up to 2500√3 W

Allowable uncertainty of active and apparent power measurement of reactive power measurement

±(0,2 % of reading + 2 digits) ±(0,5 % of reading + 2 digits)

Active, reactive and apparent energy measurement

Range: 1000 kWh. Measurement control by: STOP button, probe, voltage or current appearance.

Allowable uncertainty of active, reactive and apparent energy measurement

±(0,5 % of reading + 5 digits)

Phase angle measurement

Range: ± 180°

Allowable uncertainty of phase angle measurement

±(0,5 % of reading. + 1 digit) for voltage >10 V

Frequency

Range: 48 ÷ 52 Hz

Allowable uncertainty of frequency measurement

±(0,1 % of reading + 1 digit)

Phase rotation indicator

Min. voltage: 10 V

Operation temperature

-5 °C ÷ +40 °C

Enclosure protection

IP 67

Power supply

90 ÷ 250 V, 50 Hz

Dimensions

460 x 350 x 115 mm

Weight

about 10 kg

2

DESCRIPTION Analyser is useful for energy meter testing, checking of current transformer, determination of phase rotation and three-phase circuits symmetry, harmonic analysis and vector diagram plotting. Results are correct also for signals with distortion (True RMS). Automatic range changing and matching to network voltage increase device compatibility. Type of measurement is selected from keyboard. Internal memory allows data recording, with cyclic saving more than 4000 (more than 2000 in older version) measurement results. Analyser with Dietz clamps is placed in measuring box.

PURPOSE Analyser is assigned for measurements and recording of one-phase and three-phase network parameters. Results of measurements are shown on display and, through RS232 interface, can be sent to computer and printed. ANOT-10 can measure: one-phase and multi-phase voltage in one- and three-phase circuits, phase currents, active, reactive and apparent power in one- and three-phase circuits and in Aron circuit, active power of arbitrary combination of currents and voltages (for checking connection correctness in three phase circuit), active, reactive and apparent energy, energy meter error and ratio of current transformers, frequency, harmonics and transients, angle between currents and voltages in three phase circuit.

3

LK-10 [control meter]

Voltage range

45÷270 V resolution: 0,01 V for U(L) < 100 V; 0,1 V for U(L) > 100 V

Current range (direct measurement)

up to 10 A; resolution: 0,001 A

Current range (indirect measurement) – clamp meter

up to 100 A; resolution: 0,01 A; Φ of clamp meter hole 12 mm

Direct measurement: allowable uncertainty of voltage and current measurement allowable uncertainty of active power and energy measurement allowable uncertainty of reactive power and energy measurement

±(0,1 % of reading + 1 digit) ±(0,2 % of reading + 1 digit) ±(0,5 % of reading + 1 digit)

Indirect measurement – clamp meter allowable uncertainty of current, power and energy measurement

±(1 % of reading +1 digit)

Rated power consumption

14 VA

Voltage inputs

U1, U2, U3, N

Current inputs

I1, I2, I3

Inputs: clamp meter

Dietz clamp meter up to 100 A

Inputs: measuring head ...

... meter’s type GL-10; ... manual type GR-10

Operation temperature

-5 °C ÷ +40 °C

Enclosure protection

IP 67

Power supply (mains) Power supply (from measured circuit)

100 ÷ 240 V, 50 Hz 230 V, 50 Hz

Dimensions

380 x 260 x 130 mm

Weight

about 2 kg

4

DESCRIPTION Control meter accuracy is defined at level 0.1%. Direct and indirect (Dietz clamps) currents inputs extend meter’s usability. It is possible to connect meter head (e.g. GL-10) and hand probe (e.g. GR-10) for checking slow-running meters. The possibility of test report direct printing on thermal printer, connected to control meter is a very useful facility. LK-10 meter enables determining the error of meter’s counter, direction of phase rotation and measurements (True RMS) of voltages, currents, power and energy. Control meter is small and lightweight, its safety and tightness enclosure

provides

good

protection

in

rough

operating

conditions. This device is assigned for Power Utility services, it is specially useful in fighting against illegal power consumption, combined with neodymium magnets applying. Very high accuracy class and low, competitive price are additional features of the meter.

PURPOSE Control meter LK-10 enables uncertainty determination of induction and electronic energy (active and reactive) meters, as well as measurement of basic parameters of one- and three phase networks.

5

TL-1

[meter test device]

Rated power consumption

3 VA

Power settings for meter test

5 ÷ 65 W or 1000 W

Current range with resolution

up to 10 A 0,001 A

Max. displayed measurement uncertainty

-100 % ÷ +1000 %

Allowable uncertainty

±(0,5% of reading + 1 digit)

Operation temperature

-5 °C ÷ +40 °C

Power supply (from measuring phase)

230 V, 50 Hz

Dimensions

250(190) x 95 x 45 mm

Weight

about 0,75 kg

6

DESCRIPTION Meter test device TL-1 has suitable ABS enclosure and a leather case, which make easy handling of device and its accessories. TL-1 is energized from internal battery or power network, from which tested meter is supplied. In upper part of enclosure there is a socket with pin probes (or cables) and Neutral cable, ended with clamp for connection to meter’s terminal strip. The socket for measuring head (for automatic uncertainty measurements of induction and electronic meters) is placed in bottom part of enclosure. The head with a stand is an optional accessory of device TL-1. The device TL-1 is equipped with keyboard and LCD display for showing measurements results and messages. In TL-1 memory are saved 12 mostly occurred meter’s factors, but user can insert any other factor. Before start of meter checking, user should disconnect meter’s current coil from consumer electric circuit. Current flow through meter’s current coil is forced by internal TL-1 circuit. This solution made possible elimination of additional device for meter’s load (e.g. so-called dryer). TL-1 device enables meter testing with power about 1000 W, and measurement of meter’s starting current using step load (with step 5 W) in range 5÷65 W, what is 0.5% of rated current for many meters. Advantages: • no external power source, which emits a lot of heat, • quick connection to meter (disconnected only meter’s load), • display of percentage error of checked meter, • power supply from measuring circuit, • leather case for device with accessories.

PURPOSE Microprocessor controlled device TL-1 is assigned for quick “on-site” meter testing. Percentage error of meter and its starting current are checked. Easy maintenance and simple connection make possible checking of almost every induction and electronic meter, in one- or three-phase circuit. “On –site” test requires only disconnection of the meter’s current coil from “after-meter” consumer’s circuit.

7

UDT-2

[transformer diagnostic device]

OLTC characteristic self-time measurement

max. measurement duration time 300 s

Exciting current measurement

0 ÷ 100 mA AC

Resistance measurement

1 mΩ ÷ 100 Ω

Regulating range of resistance measurement current

0 ÷ 15 A DC

Regulating range of resistance measurement voltage

0 ÷ 30 V DC

Transformer ratio measurement

1/ √3 ÷ 50

Torque of motor driving OLTC measurement

max. measured motor power 6 kW

Operation temperature

-5 °C ÷ +40 °C

Power supply

230 V, 50 Hz

Dimensions

560 x 420 x 170 mm (without transportation box))

Weight

about 14 kg

8

DESCRIPTION Device components: • mobile computer (notebook), connected with measurement cassette by USB interface, • measurement cassette Euro3U, with galvanic separation 3 kV, • current source for resistance measurement and OLTC tests, • Windows XP system. Options and accessories: • torque of motor driving OLTC measurement, • cables with silicone insulation, • transportation box, • additional cables with terminals for simultaneous connection of all transformer phases. Software: • designed for Windows XP system, • co-operation with Excel spreadsheet, with automatic reporting, • intuitive using of all measurement functions • Warranty service: 24 months • After-warranty service – with preference conditions.

PURPOSE Transformer Diagnostic Device type UDT-2 is appropriate for after-assembly, periodic and after-fault measurements of transformers, operating in power industry, according to Transformer Maintenance Manual (IET 2006), agreed with main transformer manufacturers and diagnostics companies in Poland. Every UDT device is checked and certified by Measurement Devices Laboratory (accredited by PCA cert. no. AP 063). Measuring software is subjected to change in order to meet Customer needs, upgrades are periodically delivered to Customers.

9

HYDROCAL-1003/1005

Measured concentrations

[Gas-in-Oil-Analysis System with Transformer Monitoring Functions]

Hydrocal 1003

Hydrocal 1005

Hydrogen H2

0 ppm … 2.000 ppm ± 15 % of the measuring value ± 25 ppm

0 ppm ... 2.000 ppm ±15% ± 25 ppm

Carbon monoxide CO

0 ppm ... 2.000 ppm ± 20 % of the measuring value ± 25 ppm

0 ppm … 2.000 ppm ±20% ± 25 ppm

Moinsture-in-oil H2O

absolute 0 ppm … 100 ppm, ± 3 % of the measuring value ± 3 ppm

Absolute 0 ppm … 100 ppm ±3% ± 3 ppm

Acethylene C2H2

0 ppm … 2.000 ppm ±20% ± 5 ppm

Ethylene C2H4

0 ppm … 2.000 ppm ±20% ± 10 ppm Oil Temperature: -20 °C ... +90 °C

Operation temperature Ambient temperature: -50 °C ... +55 °C 4 x analogue DC inputs: 0/4 ... 20 mA

4x analogue DC inputs: 0/4 ... 20 mA

4 x analogue inputs: 0/4 ... 20 mA / 0 ... 10 V (configurable by jumpers)

6 x analogue AC inputs: 0 ... 80 V +20%

Analogue outputs (4…20 mA)

3 x analogue outputs: 4-20 mA (H2, CO, H2O concentration) 1 x analogue outputs: 4 ... 20 mA (free configurable)

5 x analogue outputs (H2, C2H2, C2H4, CO, H2O, configurable)

Digital outputs

4 x 12 V relay outputs (20 V DC / V AC, 2A, 60 W) 8 x opto-coupler outputs

5 x 12 V DC-relay outputs 5 x 5 V DC opto-coupler outputs

Communication

RS-232, RS-485, internal on-board modem (GSM 14.4 kBit / analogue 56 kBit)

RS-232, RS-485, Ethernet (copper-wired or fibre optical)

Analogue inputs

Protection class

IP 55

Power supply

110 V / 230 V ± 20 %, max. 350 VA, 50/60 Hz

Dimensions

215 x 215 x 215 mm

263 x 263 x 257 mm

Weight

about 8 kg

about 9 kg

10

DESCRIPTION

PURPOSE

Hydrocal 1003-1005 (MTE Meter Test Equipment, Switzerland) Intelligent system for the individual measurement of dissolved gas in oil contents:

Monitoring system SMT-EE is designed for transformer on-line diagnostics. It consists of Hydrocal device for gas-in-oil and moisturein-oil measurements, ZVCM 1001 device for bushings monitoring and SMT software for data visualization and processing. Additional signals from temperature sensors and current transformers could be use in system, what allows calculation of hot-spot and insulation ageing rate.



hydrogen (H2) and carbon monoxide CO – model 1003



hydrogen (H2), carbon monoxide CO, acetylene (C2H2),

ethylene (C2H4) – model 1005 and moisture (H2O) in the insulating oil of power transformers. Hydrocal is mounted on a valve on the transformer tank, without necessity of transformer switch-off. Graphical firmware Hydrosoft enables Hydrocal parameters setting and data reading from memory. Hydrocal is equipped with communication interfaces for connection with external systems. Software associated with Hydrocal 1003/1005 system allows: •

on-line, remote monitoring of all measured values,



trends of gas-in-oil and moisture content,



notifying user in case of alarm (by SMS too),



communication with external SCADA systems.

ZVCM - 1001

Software SMT (Transformer Monitoring System)

ZVCM-1001 device, manufactured by ZTZ Services Intl. (USA) is used for transformer bushings monitoring by test-tap current measurement. It co-operates with sensors, mounted on bushing test-tap. Device enables measurement of relative bushing capacity and dielectric loss factor tan_delta of bushing’s insulation. ZVCM-1001 is equipped with serial interface RS232/ RS485 for configuration and communication with SCADA systems.

Current measurement range

1 mA ÷ 140 mA, ±1.5 % of the measuring value, resolution 0.1mA

Tan_delta measurement range

0 % ÷ 100 %, accuracy ±1.5 % of the measuring value, resolution: 0.01 %

Communication

Serial interface RS-232, RS-485, protocol MODBUS RTU

Operation temperature

-35 °C ÷ +50 °C

Humidity

0 ÷ 90 %, non-condensing

Power supply

230 V AC, power consumption: 3 W

SMT software is made on ASIX platform, which is widely used for creation SCADA/HMI systems. Besides displaying actual results of gas-in-oil and moisture-in-oil concentration measurements, bushings parameters and other measured quantities, it signalizes transformer status as normal, warning and alarm. Data, obtained form Hydrocal and ZVCM devices are stored in database, and allow determination of trends in chosen time period. SMT enables both visualization of cooling system parameters and OLTC status, in co-operation with cooling system controller. SMT software provides many possibilities of event reports and graphical presentation of data. It can collaborate with other systems, according to Windows data exchange standards (OLE servers, DDE, OLE2, OLE DB protocols). SMT is fully scalable and can be matched for monitoring of single transformer, as also several units in substation or power plant.

11

PZT-30

[transformer’s tap-changer position indicator]

Allowable transmitter-receiver cables resistance

300 Ω

Max. number of tap changer positions

27

Transmitter-receiver code

BCD, binary, proprietary

Output receiver code

BCD, binary

Current output

0 ÷ 5 mA 0 ÷ 20 mA 4 ÷ 20 mA

Communication

RS 485 [MODBUS RTU]

Operation temperature

-15 °C ÷ +40 °C

Power supply

230 V, 50 Hz

Transmitter dimensions

170 x 170 x 90 mm

Receiver dimensions

160 x 135 x 67 mm

Transmitter weight

1 kg

Receiver weight

1,5 kg

12

DESCRIPTION Device is composed of transmitter and receiver. Transmitter consists of 27 position rotation switch and coder card, which are coupled mechanically with tap changer. Receiver is installed on substation area information table, on LCD display are shown: actual tap-changer position, total number of switchovers from the moment of position indicator installation, switchover history with direction (up and down), time and data stamp. Indicator shows operation statistics: percentage time of operation on each position. Indicator enables co-operation with voltage regulator by output interface: current 0 ÷ 20 mA or 0 ÷ 5 mA, or digital: binary or BCD code. Serial RS 485 interface (MODBUS RTU protocol) enables communication between receiver and SCADA system.

PURPOSE The newest version of indicators (previous PZT-21 to PZT-29) is PZT-30 device. Tap-changer position indicator is designed for remote reading of number of actually chosen tap and for recording operation data of tap-changer. Indicator makes possible sending information about tap position through current output or BCD/digital output and serial interface RS 485 with MODBUS RTU protocol.

13

RW-1

[shock recorder]

Acceleration range

-6 g ÷ +6 g

Measurement resolution

± 0,1 g

Measurement and recording

axes: X, Y, Z

Memory capacity

4000 measurements

Current consumption

about 4 mA

Duration of operation

up to 60 days

Communication

RS 232

Operation temperature

-40 °C ÷ +85 °C

Power supply

Lithium battery or AKU

Dimensions

210 x 245 x 105 mm

Weight

about 4 kg

14

DESCRIPTION Recorder is equipped with LCD display and keyboard, for settings change and calibration related to device mounting. Recorded data are saved in EPROM memory together with date and time of event. For better explanation of records, every power on/off event is recorded. After operation user can browse saved data directly on LCD display, print them on internal printer or send to computer through RS 232 interface. Software (Windows based) enables visualization of recorded data. Recorder has internal battery, which allows continuous operation during 60 days.

PURPOSE Recorder is destined for simultaneous measurement and recording (in three axes: X, Y, Z ) of accelerations (g-load) occurred during loading, shipment and unloading of transformers, generators, motors, medical equipment and other shock-sensitive devices.

15

SM-1

[microprocessor-controlled chronograph]

Control voltage

5 ÷ 250 V DC or 50 ÷ 230 V AC *)

Measurement ranges automatically selected

0 ÷ 999,9 ms 0 ÷ 9,999 s 0 ÷ 99,99 s 0 ÷ 999,9 s 0 ÷ 9999 s

Allowable uncertainty

±(0,01 % of reading + 1 digit)

Duration of operation without charging

8 hours

Operation temperature

-5 °C ÷ +40 °C

Enclosure protection

IP 66

Power supply

internal rechargeable battery with possibility of charging from network 230 V, 50 Hz

Dimensions

230 x 200 x 80 mm

Weight

about 2 kg

Warning

*) with AC voltage control, additional inaccuracy may occur: not more than 0,5 ms for 50 V and 0,1 ms for 230 V

16

DESCRIPTION Chronograph is equipped with 2 separate inputs: start and stop. It could be controlled by AC/DC voltage appearance or disappearance or by open/close contacts. The voltage polarity on inputs is arbitrary. Chronograph enables following measurements: pulse duration, time between pulses appearance, pulses spacing interval, relay operation time, duration of contacts close and open, sum of several measured times.

PURPOSE Chronograph is assigned for time measurements in electrical power protection automation systems. Internal battery enables operation in places without proper main power supply.

17

PF

[phase shifter]

Current regulation range

0 ÷ 2 A, 0 ÷ 10 A, 0 ÷ 20 A

Power of current source

up to 40 VA

Voltage regulation range

0 ÷ 120 V

Power of voltage source

up to 40 VA

Phase angle regulation range

0 ÷ 360°

Allowable uncertainty of voltage measurement

±(1 % of reading + 1 digit)

Allowable uncertainty of current measurement

±(1 % of reading + 1 digit)

Allowable uncertainty of phase angle measurement

±(1° + 1 digit)

Allowable uncertainty of time measurement

±(0,01 % of reading + 1 digit)

Operation temperature

-5 °C ÷ +40 °C

Enclosure protection

IP 67

Power supply

230 V, 50 Hz

Dimensions

430 x 320 x 110 mm

Weight

about 8 kg

18

DESCRIPTION Phase shifter generates on its output alternate current and voltage (sinusoidal, 50 Hz) with controlled amplitude and current-voltage phase angle. It is provided with digital voltmeter, ammeter, time and angle measurement device.

PURPOSE Phase shifter PF is designed for testing of angle-sensitive protection devices e.g. phase-comparative or earth fault safeguards. It makes possible measurement of operation angle and start-up time of protection device.

19

GU3F

[three-phase voltage generator]

Max. output voltage

120 or 300 V

Output power

40 VA / phase

Allowable uncertainty

±(1 % of reading + 1 digit)

Operation temperature

-5 °C ÷ +40 °C

Enclosure protection

IP 67

Power supply

230 V, 50 Hz

Dimensions

430 x 320 x 110 mm

Weight

20 kg

20

DESCRIPTION Single phase supply voltage 50 Hz, after reducing is shifted by angle 120°, for three phase star making. After amplification, the voltages are fed to output by step-up transformer. Generator has two-stage voltage control – concurrent for selected phases and separate for each single phase with possibility of elimination given phase.

PURPOSE Voltage generator is assigned for testing devices supplied by three-phase voltages. It enables simulation of system asymmetry and fault/decay of arbitrary phase voltage. It is used e.g. for protection systems checking.

21

PWPN-1 [current source]

Current regulation range: - at range 5 A and load up to 80 mΩ - at range 20 A and load up to 30 mΩ Voltage regulation range with load from 15 kΩ

0÷5A 0 ÷ 20 A 0 ÷ 230 V AC

Allowable uncertainty

±(1 % of reading + 1 digit)

Operation temperature

-5 °C ÷ +40 °C

Enclosure protection

IP 67

Power supply

230 V, 50 Hz

Dimensions

270 x 246 x 174 mm

Weight

about 6 kg

22

DESCRIPTION Device PWPN-1 generates sinusoidal current or voltage with power frequency and controlled amplitude. It is equipped with ammeter/voltmeter. User can choose generated and measured variable (current or voltage) by two-position switch, selected variable is indicated by LED (A or V).

PURPOSE Current source type PWPN-1 is designated for checking current transformer load, measuring sensitivity of current protection devices etc.

23

RL-64D [telecontrol device]

Delay of command transmission - standard output - power output

2,2/4,2 ms + time filter, standard output; single/multi 4,0/6,0 ms + time filter, power output; single/multi

Delay of continuous digital transmission

0,4 ms

Number of command signals

4 up to 20, possibility of continuous command transmission

Voltage ranges on command input

24 V, 60 V, 120 V, 250 V DC, configurable command input voltage threshold 70% Un

Command output: - standard - power

electromechanical relay: 1000 V, 100 W switched current 1 A, continuous current 2,5 A, switching time 1 ms electromechanical relay: 7500 V, 50 W switched current 3 A, continuous current 5 A, switching time 3 ms

Linear interface - electrical - optical

E1 2 Mbit/s acc. to G.703.6, symmetrical out/input 120 Ω or X.21 nx64 kbit/s 2 Mbit/s, singlemod., operation in II or III aperture, distance 20 up to 120 km

Option:

2 optical interfaces

Linear canal connection time

< 5 ms

Output signal

Frame acc. to ITU-T G.704; linear code HDB3

Substation digital interface

V.24 asynchronous 19,2 bit/s; V.24 synchronous nx64 kbit/s; V.35 nx64 kbit/s; X.21 nx64 kbit/s

Supervising interface - local / remote

USB, RS232 / Ethernet 10/100 BaseT, protocol SNMP

Capacity of events log Time resolution

1000 events, with time stamp 1 ms, with time sync between co-operating part of device

Time sync in device

Ethernet 10/100 BaseT, protocol SNTP in LAN network or GPS protocol NMEA

Available telecommunication services

Digital communication with interface asynchronous RS232, synchronous V.24, X.21, V.35; telephone analogue interface with E&M signalling, analogue telephone channels (POTS),

Cabinet for 4÷8 commands/20 commands

cassette 3U / 6U

Operation temperature

0 °C ÷ 45 °C

Power supply

230 V, 50 Hz or 220 V DC, 40 VA

Dimensions 3U

483 x 133 x 298 mm

Weight

5,5 kg

24

MND-26

[switch contacts anticoincidence meter]

Time measurement range

up to 23 s

Resolution

0,1; 0,2; 0,5; 1,0 ms

Allowable uncertainty

±(0,01 % of reading + 1 digit)

Number of measuring contacts

6

Memory

90 measurements

Number of inputs "START"

2

Triggering voltage (external start)

110 ÷ 220 V AC / DC

Switch coil control

2 control outputs

Switch-off coils control voltage (internal start)

48 ÷ 220 V DC

Analogue channels

3, current

Measuring range in analogue channels

-5 A ÷ +5 A

Operation temperature: meter/printer

–5 °C ÷ +40 °C / + 5 °C ÷ +35 °C

Enclosure protection

IP 67

Power supply

230 V, 50 Hz + internal battery

Dimensions

500 x 390 x 190 mm

Weight

about 11 kg

26

DESCRIPTION Meter MND-26 is microprocessor-based mobile device for switch contacts anticoincidence determination in cycles: W, Z, WZ, ZW, WZW, with taking into account arming time too. Measurement can be started internally – it performs automatically in predetermined time, or it can be initiated by external voltage signal 110 ÷ 220 V AC/DC. It is possible to start measurement by changing state of one contact (only anticoincidence measurement, but without necessity of voltage control of switch). The results are stored in memory and displayed on LCD screen. It is possible to print results on internal printer (Kafka type) and send them to computer or pendrive, using USB interface. Duration of contacts vibration can be read from printed copy or from recorded time diagram, using computer software. During time and current measurements, voltage of switch coils supply is measured too. Meter with printer is placed in suitcase and can be supplied from internal battery. Charging device is built in meter, printer is optional accessory.

PURPOSE Switch contacts anticoincidence meter MND-26 is designated for simultaneous measurement of open and close times up to 6 switch contacts, what enables determination of their operation anticoincidence. This meter allows analogue signals recording (e.g. currents in switching on and off coils and arming current).

27

WPS-300/600 [DC current source]

Output current regulation range for WPS-300 for WPS-600

20 ÷ 380 A 20 ÷ 600 A

Time of current forcing for WPS-300 for WPS-600

2 ÷ 255 s 2 ÷ 15 s

Max. output power

1,5 kW

Voltage measurement resolution

0,1 mV

Current setting resolution

2A

Current ripples

2,5 A) by generation switch off (LED signalling >I).

PURPOSE Power supply for switch coils is designated for switches operation testing with reduced and elevated supply voltage.

31

ZNR-1

[electrocution voltage selector]

Output power

3,5 kVA

Output voltage

100, 200, 400 V AC

Current regulation

smooth up to 50 A AC

Allowable uncertainty

±(0,2 % of reading + 2 digits)

Operation temperature

-5 °C ÷ +40 °C

Enclosure protection

IP 42

Power supply

230 V, 50 Hz

Dimensions

530 x 430 x 210 mm

Weight

about 50 kg

32

DESCRIPTION ZNR-1 is current source of rated power 3.5 kVA, which generates alternating current up to 50 A, with arbitrary long time. Selector is equipped with digital ammeter and voltmeter for output parameter measurements. High value of current enables obtaining measuring voltages higher than noise voltage level and achievement of required measurement accuracy. When measuring circuit resistance is high, one can use two additional output voltage ranges: - 200 V AC and current up to 18 A, - 400 V AC and current up to 9 A. Version with output voltage 1000 V is available on special request.

PURPOSE Electrocution voltage selectors are used for forcing measurement current in tested earth electrode system, during touch and step voltage measurements. Voltage selector and electrocution voltage meter MNR-1, which provides touch and step voltage measurements, form complete set for earth system testing.

33

ZNR-2

[electrocution voltage selector]

Output power

7,5 kVA

Output voltage

150, 300 V AC

Current regulation

smooth up to 60 A AC

Allowable uncertainty

±(0,2 % of reading + 2 digits)

Operation temperature

-5 °C ÷ +40 °C

Power supply

230 V or 400 V, 50 Hz

Dimensions

465 x 660 x 880 mm

Weight

about 75 kg

34

DESCRIPTION ZNR-2 is current source of rated power 7.5 kVA, which generates alternating current up to 60 A, with arbitrary long time. Selector is equipped with digital ammeter and voltmeter for output values measurements. High value of current enables obtaining measuring voltages higher than noise voltage level and achieving of required measurement accuracy. Two ranges of output voltage and changeable polarity considerable extend its usability. Modular-designed device is placed on hand truck, which enables easy transportation and movement.

PURPOSE Electrocution voltage selectors are used for forcing measurement current in tested earth electrode system, during touch and step voltage measurements, on soils with decreased conductivity (rocks, sands). Voltage selector and electrocution voltage meter MNR-1, which provides touch and step voltage measurements, form complete set for earth system testing.

35

MNR-1

[electrocution voltage meter]]

Voltage measurement range

100 mV ÷ 100 V, 50 Hz

Accuracy class

1,5

Input resistance

about 300 kΩ

Resistor shunts

1000 Ω, 1500 Ω, 3000 Ω

Signalling range

20 ÷ 100 % of voltage range

Power supply

internal Cd-Ni battery (with possibility of charging from internal supply)

Dimensions

450 x 350 x 120 mm

Weight

about 5 kg

36

DESCRIPTION Electrocution voltage measurement is performed by measuring probes set and mobile meter, with possibility of selecting proper range and input resistance. The result of measurement is presented on indicating instrument. The measuring set consists of suitcase with electrocution voltage meter, measuring cables, power supply cable for battery charging and probes: 2 plate probes (280 x 140 mm) for putting on ground and 2 flexible probes for hands.

PURPOSE Meter is assigned for measurements of electrocution voltage, that occurs in power energy objects area, particularly near earth systems and metal structures.

37

WP-100 [current source]

Load current Izn

0 ÷ 100 A

Max. power

500 VA

Output voltage regulation range

0 ÷ 250 V (for current 0,8 A)

Allowable uncertainty of voltage measurement

±(0,2 % of reading + 2 digits)

Allowable uncertainty of current measurement

±(0,2 % of reading + 2 digits)

Rated power consumption

600 VA

Operation temperature

-5 °C ÷ +40 °C

Power supply

230 V, 50 Hz

Dimensions

475 x 357 x 176 mm

Weight

about 25 kg

38

DESCRIPTION WP-100 is assigned for continuous operation with current range from 0 to In, and voltage range from 0 to 250 V. Current circuit is isolated from power supply network. Voltage circuit has galvanic connection with power supply network. Current source has digital display for showing values of forced current, voltage and time. Device is equipped with over current and thermic safeguard, what protect it from overheating or failure. Control of current source operation is provided by choose one of 5 different operation modes.

PURPOSE Source WP-100 is assigned for supply devices, which request checking and for regulations of circuits, dependent on current value e.g. current transformers, over current relays etc.

39

WP-1000 [current source]

Time measurement range

0 ÷ 166 minutes

Max. temporary current

3000 A

Max. continuous current

1500 A

Max. source voltage

2500 V

Max. output power

3 kVA

Allowable uncertainty of voltage measurement

±(0,2 % of reading + 2 digits)

Allowable uncertainty of current measurement

±(0,5 % of reading + 5 digits)

Memory capacity

64 measurements

Operation temperature

-5 °C ÷ +40 °C

Power supply

230 V, 50 Hz

Dimensions

400 x 880 x 610 mm

Weight

50 kg

40

DESCRIPTION Current source is multifunctional device using microprocessor technology for controlling high power systems. Current source provides AC 50 Hz current, regulated from 0 to 3000 A. Up to 1500 A the current is supplied by any time. Above this value operating time is 3 s, 3000 A is generated by 1s. Beside high current circuits current source is equipped with regulated source 2500 V / 1 A and 500 V / 5 A for making magnetization characteristics of instrument transformers 1 A and 5 A. Maximum provided power is 3 kVA. Test parameters as current ratio, ratio uncertainty, angle uncertainty, total uncertainty and loading power can be displayed on graphical display screen as measured or calculated values or in the form of diagram of given value versus current or voltage. All measured or calculated values can be saved and displayed on the screen or sent by RS 232 to computer. The power source is delivered with software (Windows based) enabling taking stored results from current source, their analysis, processing and conversion to spreadsheet. The software enables also transmission of some settings to current source. The current source consists of two modules mounted on hand truck. Beside of current source WP-1000 is manufactured also version WP-500 with lower output currents.

PURPOSE Test set WP-1000 is overseen for measurements of instrument transformers and can be used for checking of overcurrent relays and systems regulated by current or voltage, as well as protection automatics systems.

41

WPu-4000 [current source]

Rated load current Izn

0 ÷ 4000 A

Max. power

10 kVA

Output voltage regulation range

0 ÷ 400 V

Allowable uncertainty of voltage measurement

±(0,2% of reading + 2 digits)

Allowable uncertainty of current measurement

±(0,2% of reading + 2 digits)

Chronograph range

0,1 ms ÷ 100 h

Allowable uncertainty of chronograph measurement

±(0,01% of reading + 1 digit)

Operation temperature

-5 °C ÷ +40 °C

Power supply

400 V, 50 Hz

Dimensions

550 x 660 x 1000 mm

Weight

about 85 kg

42

DESCRIPTION Current source can generate currents up to several thousands amperes and has got module structure equipped with control panel, current source and hand truck enabling easy moving and transport. If it is permitted by outer circuit, the current source set can generate temporarily (15 s) 4200 A load. The source is equipped with high current terminals, supplying current from outputs 4000 A / 2,5 V or 100 A / 0,5 V alternatively. Every source should be used separately.

PURPOSE Current source WPu-400 has the highest power and output current in the series of current sources type WPu. It is portable testing set designed for AC current supply of devices which need checking and regulation of systems depended on the level of current or voltage e.g. thermal releases, current transformers, overcurrent releases, primary releases etc., and especially for testing of releases in power switches type APU.

43

WPPS-300 [DC/AC current source]

Current regulation range I AC

0 ÷ 300 A

Output voltage regulation range U AC

0 ÷ Uz (for current 4 A)

Current regulation range I DC

0 ÷ 100 A

Milivoltmeter range DC

0 ÷ 2000 mV

Max. sources power

800 VA for AC and 300W for DC

Allowable uncertainty of AC / DC voltage and current measurement

±(0,2 % of reading + 2 digits)

Rated power consumption

1000 VA

Operation temperature

-5 °C ÷ +40 °C

Humidity

up to 80 %

Enclosure protection

for special purpose II protection class IP 67

Power supply Uz

230 V, 50 Hz

Dimensions

486 x 392 x 191mm

Weight

about 27 kg

44

DESCRIPTION WPPS-300 is designed for continuous operation in full scale regulation of all output circuits. Device is equipped with digital readout of forced current, voltage and measured time. Digital stop watch is controlled by changes of status obtained: no-potentially or by any voltage signal. Current source is protected from damage and has got resistant case with ABS. For special demand the current source can be made in protection class II, IP 67.

PURPOSE AC and DC Current Source type WPPS-300 is designed for checking and regulations of protection automatic devices supplied with AC and DC current e.g. current transformers, overcurrent and voltage relays, releases thermal protection, switch contacts etc. during start-up and periodical tests. It enables: determination of instrument transformer ratio, controlling and setting of protection automatics systems, determination of release operating threshold, determination of self-times of switches, determination of resistance of switch main contacts.

45

TP-100

[current transformer testing device]

Max. power consumption

about 650 VA

Max. power of current output IPRI

600 VA

Current regulation range IPRI

0 ÷ 120 A

Current range ISEC

0 ÷ 10 A

Voltage range USEC

0 ÷ 100 V

Current source operation time IPRI for current up to 100 A

continuous

Output voltage regulation range U for load current I 0 ÷ 0,5 A

0 ÷ 1000 V

Allowable uncertainty of current and voltage measurement

±(0,2 % of reading + 2 digits)

Chronograph range

0 ÷ 100 h

Operation temperature

-5 °C ÷ +40 °C

Humidity

up to 80%

Power supply

230 V, 50 Hz

Dimensions

480 x 390 x 190 mm

Weight

about 25 kg

46 32

DESCRIPTION Instrument transformer tester enables: determination of angle uncertainty, current and real ratio and load of instrument transformer secondary side, determination and regulation of operation threshold in current and voltage release of switch, determination of time-current characteristic of overcurrent and thermal protection, determination of self times of switches and contactors, controlling and setting of other elements of protection automatics depended on current and voltage value, data archiving, analysis and transfer to computer.

PURPOSE Instrument transformer tester TP-100 is designed for checking of instrument transformers operating in semi-indirect and indirect systems used for making energy accounts. Checking should be done in the case of: carrying out acceptance, start-up, service and post-accident tests, when instrument transformer is damaged or verification marks are damaged or when both sides find erroneous indications or when the correct ratio is unknown (lack of rating plates). Besides, tester can be used for checking and regulation of protection automatics components supplied from AC voltage source, as switches, current and voltage relays, overcurrent and thermal releases etc.

47

Power Research and Testing Company „ENERGOPOMIAR-ELEKTRYKA” Ltd. PL 44-101 Gliwice, Świętokrzyska 2 tel. secretary’s office: +48 32 237 66 03 fax: +48 32 231 08 70 e-mail: internet:

[email protected] www.elektryka.com.pl