Implementation Guideline for Digital Interface to Instrument ...

1 downloads 137 Views 2MB Size Report
Jul 7, 2004 - 1 SCOPE. This document gives additional information on how to implement a digital communication interface
UCA International Users Group 10604 Candler Falls Court Raleigh, NC 27614 Tel: +919-847-2241, Fax: +919-847-2939 http://www.ucainternational.org

IMPLEMENTATION GUIDELINE FOR DIGITAL INTERFACE TO INSTRUMENT TRANSFORMERS USING IEC 61850-9-2 1

SCOPE

This document gives additional information on how to implement a digital communication interface to non conventional instrument transformers according to IEC 61850-9-2 and IEC 60044-7/8. The purpose of the document is to define a subset of IEC 61850-9-2 that shall support a fast market introduction of this standard. The subset facilitates first implementations, especially in existing products. It further clarifies uncertainties with respect to the interpretation of the standards and/or to precisely define what options to choose in case the standards permit a choice of options. The paper defines all the generally binding issues and is intended to be used together with Protocol Implementation Documents (PID’s) that are established for all equipment supporting this digital interface. The PID’s of the individual equipment then define what functions a unit supports and how it reacts to error conditions. The purpose of the definitions stated below is to ensure that equipment designed accordingly is interoperable within the limits defined in the PID documents of the connected units.

2

SUMMARY

The subset of IEC 61850-9-2 defined in this document only supports the service SendMSVMessage. As a consequence, the communication is unidirectional from the merging unit to the bay level devices and does not need to support the MMS stack. Therefore, implementation in existing bay level devices is straightforward. The document further defines a logical device merging unit and a encoding="UTF-8"?> Implementation Guideline for Digital Interface to Instrument Transformers using IEC 61850-9-2 Modification Index: R2-1 Last date of storage: 2004-07-07

Page 18 / 31 < ln> 0.001 0 0.01 0 20 24.1 Î o.k., since 2 < 231 • The max binary value becomes 217.1 x 27.0 = 224.1 Note: Voltage measurement: • Distance- and accurate reverse power- functions are not applied for voltages below 6 kV. • For voltage measurement on objects with rated voltages below 3 kV, class 0.5 for metering is sufficient. Current measurement: • For current measurement on objects with rated current below 100 A, class 0.5 for metering is sufficient. • Highest current values have to be expected for faults near terminals of large generators. In such cases the maximum short-circuit current is limited by the block transformer to below 10 times the rated generator current.

Implementation Guideline for Digital Interface to Instrument Transformers using IEC 61850-9-2 Modification Index: R2-1 Last date of storage: 2004-07-07

Page 23 / 31

21 22 25 26 28 29 211 212 213 214 215 216 217

218

219

220

221

222

Max. current expected 25 Irated

Max. current expected 65 I

223

rated

224

225

226

227

228

Value for generator and transformer protection applications. (Accuracy limit factor = 50)

229

230

Value for busbar and line protection applications. (Accuracy limit factor = 130)

Doubling, to take into account a full DC-offset of the short-circuit current.

1'000 kA (r.m.s.)

210

100 kA (r.m.s.)

Move this line - together with the arrows applicable to the rated current of the object. The two arrows shall remain within the +/- 31 Bit scale. (Application similar to the good old „slide-ruler“)

10 kA (r.m.s.)

27

Class 0.2S/2 Class 0.2S Class 0.5S

Class 0.1 Class 0.2 Class 0.5 Class 1

1 kA (r.m.s.)

141 A (peak) 100 A (r.m.s.)

Rated object current 100 A (r.m.s.) in this example

24

10 A (r.m.s.)

Phase currents and 3 I0 23

1 A (r.m.s.)

Requirement for distance, DEF et al protection functions

100 m A (r.m.s.)

1 mA = LSB

20

10 m A (r.m.s.)

Peak value (sinusoidal waveform) r.m.s. value

1 m A (r.m.s.)

231

2'147 kA (peak)

Figure 6 – Nomogram for current

Implementation Guideline for Digital Interface to Instrument Transformers using IEC 61850-9-2

Modification Index: R2-1 Last date of storage: 2004-07-07

Page 24 / 31

21

22

25

26

28

29

211

212

213

214

215 216

217

218

219

220

221

222

223

224

225

226

227

228

229

230

10'000 kV (r.m.s.)

231

21'475 kV (peak)

The maximum rated voltage factor is chosen to be 2.5 to cover most applications (instead of only 1.9 according to IEC 60044-7).

Maximum voltage = 2.5 Urated

Move this line - together with the arrows applicable to the rated voltage of the object. The two arrows shall remain within the +/- 31 Bit scale. (Application similar to the good old „slide-ruler“)

1'000 kV (r.m.s.)

210

Class 0.1 Class 0.2 Class 0.5 Class 1 Class 3P Class 6P

100 kV (r.m.s.)

14.1 kV (peak) 10 kV (r.m.s.) Rated object voltage 10 kV (r.m.s.) in this example

27

1 kV (r.m.s.)

24

100 V (r.m.s.)

Requirement for distance, DEF et al protection functions

10 V (r.m.s.)

Phase to ground voltages and 3 U0

23

1 V (r.m.s.)

10 mV = LSB

20

100 mV (r.m.s.)

Peak value (sinusoidal waveform) r.m.s. value 10 m V (r.m.s.)

Figure 7 - Nomogram for voltage

Implementation Guideline for Digital Interface to Instrument Transformers using IEC 61850-9-2

Modification Index: R2-1 Last date of storage: 2004-07-07

Page 25 / 31

APPENDIX E: REFERENCE ARROW ORIENTATION SYSTEM Legend U I N E

Voltage Current Neutral Earth (IEC notation) = Ground (ANSI notation)

Indices A B C N E P 1 2 0

(subscript) Phase A Phase B Phase C Neutral Earth = Ground Parallel overhead line, if applicable Positive sequence Negative sequence Zero sequence

The positive sense of arrows (phasors) follows the „load vector system“ i.e., the voltage-drop across a resistor is in phase with the current. DBB OHB IE

Double Bus Bar arrangement 1½ (One and a Half) Breaker arrangement Earth (ground) return current

Implementation Guideline for Digital Interface to Instrument Transformers using IEC 61850-9-2 Modification Index: R2-1 Last date of storage: 2004-07-07

Page 26 / 31 Parallel Line (ov erhead line)

3 I 0p Feeder under consideration

IA A

UAB

UAN

IB B

UBC

UBN

UCA

IC C

UCN

N

3 I0

UAE UB E UCE

Z = 0 …. inf inite

U0

IE = 3 I 0 3 U 0 = U AE +U BE+U CE

3 I 0 = I A+I B+I C

E

3 I 0p is mainly used f or mutual zero-sequence compensation in distance to f ault locators

Figure 8 - Generic three phase system including voltages and currents

Implementation Guideline for Digital Interface to Instrument Transformers using IEC 61850-9-2 Modification Index: R2-1 Last date of storage: 2004-07-07

Page 27 / 31 Bus 1 Bus 2

QA1

P1

IA, IB, IC , (3I0)

BZ1 P2 IN

HV Tertiary

IA, IB, IC , (3I0) P2

P1 P2

P1

IN

P1 P2

LV

IA, IB, IC , (3I0)

P2

P2

IE

P1

P1

Figure 9 - Currents in DBB (double bus bar) arrangement

Implementation Guideline for Digital Interface to Instrument Transformers using IEC 61850-9-2 Modification Index: R2-1 Last date of storage: 2004-07-07

Page 28 / 31 Bus 1 Difference of tw o currents

QA11

P1

IA11- IA31 IB11- IB31 IC11- IC31 (3I011- 3I031)

BZ11

IA11. IB11, IC11, (3I011)

P2 Feeder 1

QA31

P1 BZ31

IA31. IB31, IC31, (3I031)

Sum of tw o currents

P2 Feeder 2

IA21+ IA31 IB21+ IB31 IC21+ IC31 (3I021+ 3I031)

P2 BZ21

IA21. IB21, IC21, (3I021)

P1 QA21 IN

HV

Bus 2

Tertiary

IA, IB, IC , (3I0) P2

P1 P2

P1

IN

P1 P2

IA, IB, IC , (3I0)

LV P2

P2 IE

P1

P1

Figure 10 - Currents in OHB (one and a half breaker) arrangement

Implementation Guideline for Digital Interface to Instrument Transformers using IEC 61850-9-2 Modification Index: R2-1 Last date of storage: 2004-07-07

Page 29 / 31

Figure 11 shows the connections between conventional equipment and CT’s. The neutral of the CT’s is formed on object-side. The primary current and the current in the protection relay are “in phase”. The arrow orientation is in line with the system used for NCIT’s (as defined in IEC 600448, clause 11.1.3). The drawing shall help to co-ordinate mixed mode configurations (mixed-mode uses digital data streams from NCIT’s and inputs from conventional CT’s and VT’s). Furthermore the diagram shall illustrate that IN, as it is used with conventional CT’s, results in IN = - 3 I0.

N IA

B

IB

C

IC Protection A B C N

IA

3 I0 = IA + IB + IC

IB IC IN = -3 I0

IE = 3 I0 = IA + IB + IC

Figure 11 – Reference arrow orientation system, conventional CTs with CT star-point (neutral) on object side

Implementation Guideline for Digital Interface to Instrument Transformers using IEC 61850-9-2 Modification Index: R2-1 Last date of storage: 2004-07-07

Page 30 / 31

Figure 12 shows an alternative connection for conventional equipment as used by several vendors i.e., the neutral of the CT’s is formed on bus-side. In this case the arrow orientation for the secondary equipment is inverted (The primary current and the current in the protection unit are “in counter phase”. This must be considered for directional- and differential- functions. To ease adaptation to the two conventions, the IEC61850-9 inputs should preferably be selectable: direct or inverted.

N IA

B

IB

C

IC Protection A B C N

IA

3 I0 = IA + IB + IC

IB IC IN = -3 I0

IE = 3 I0 = IA + IB + IC

Figure 12 - Reference arrow orientation system, conventional CTs with CT star-point (neutral) on bus-side

Implementation Guideline for Digital Interface to Instrument Transformers using IEC 61850-9-2 Modification Index: R2-1 Last date of storage: 2004-07-07

Page 31 / 31

CHANGE INFORMATION Date

Change Index

Document State

Author

Remarks

04-03-01

2.0a

Released

Ch. Brunner

04-07-07

2.1

Released

Ch. Brunner

Version released at UCA usersgroup meeting Modifications in Figure 4 (Length of ConfRev) and 5 (Quality fields)

Implementation Guideline for Digital Interface to Instrument Transformers using IEC 61850-9-2 Modification Index: R2-1 Last date of storage: 2004-07-07

Suggest Documents