Study on partial discharge detection of power transformer based on AVR

0 downloads 0 Views 524KB Size Report
Jun 5, 2005 - diagnostic of the power transformer's insulation have become one of the ... Keywords: Partial Discharge, power transformer, on-line monitoring, ...
Proceedings of 2005 Intemational Symposium on Electrical Insulating Materials, June 5-9,2005, Kitakyushu, Japan

P1-59

Study on Partial Discharge detection of power transformer based on AVR

Jun Guo *, Wen Shu, Xueqin Zhang, Bo Gao, Peng Wang, and Guangning Wu Southwest Jiaotong University, School of Electrical Engineering, Chengdu, 6 1003l,Sichuan, P.R.China

* E-mail: [email protected] Abstract: As the increasing voltage grade of power electrical equipment, on-line monitoring and diagnostic of the power transformer’s insulation have become one of the most important studies in high voltage research. At the same time, lots of researches have shown that the insulation aging has direct relationship with the partial discharge (PD) activities. A new instrument, which based on AVR, is introduced to measure the characteristics of PD in large power transformers accurately. In addition, it can also be used to on-line monitoring of the PD activities under high field conditions. Keywords: Partial Discharge, power transformer, on-line monitoring, AVR the transformer’s operation.

INSTRUCTIONS

Most of the current PD on-line monitoring The traditional inspection and repair of

systems are all expensive, with low reliability.

the so-called “maintenance

Using in the traction transformer in the electrical

routine”[]], the preventative maintenance based

railway, these PD monitoring systems are always

on schedule. This kind of maintenance had do lots of contributions to the power equipments’

cost one third or more of the transformer’s price.

overhaul and management. However, this kind

substations. A new PD on-line monitoring

of preventative maintenance can’t monitor the

system, based on AVR micro control unit, has been introduced.

transformer is

transformer’s operation conditions, and it can do nothing with the prediction of transformer’s insulation status and its trend of development. It

That’s too expensive to apply it in all traction

MONITORING PRINCIPLE

indicates that the traditional preventative inspection can not fit the actual requirement. At

The most obvious phenomenon of partial

that time, the real-time, effective insulation on-line monitoring has been widely researched

discharge is the movement of charges between

and

Recently, high voltage power

on the electron of test sample. Moreover, the

equipments’ insulation on-line monitoring and

duration of every discharge is very short, which

dielectrics, which will cause the voltage variety

diagnostics has become one of the important

is about 10 ns in gas or 1 us in oil. Based on

research topics. And the Partial Discharges (PD), as an effective parameter to allude the insulation

Maxwell electromagnetic theory, these fast rise time pulses will generate high frequency

fault and aging, has attracted more and more

electromagnetic signals radiating outside. The

attention. Within the

transformer’s partial

common PD detection methods are all based on

discharge on-line monitoring system, it could not

these two principles. These methods are Pulse

only cooperate with the traditional differential protection, over current protection, heavy gas

Current Detection, Radio Interference Voltage,

protection, etc., but can also real time monitor

The Radio Frequency Monitoring was

Dielectric Loss Analysis, etc.

- 522 -

adopted in this. system, which used a high

sensor. At that time, the sensor’s quantity factor

frequency current sensor, Rogowski coil, to pick

(Q-factor) is above 100. And the sensor’s output

up the discharge signals from the transformer

winding’s neutral ground wire, earth of casing

transfer function is tied up with the Integral Resistor and the tune number of sensor. Ignored

wire and 3-phases entrance bushing. With these

the stray capacitance in the circuit, the output

sensors, it could detect the partial discharges in

transfer function is,

the transformer effectively. in which the R is the resistance of the Integral

SYSTEM CONSTRUCTURE

Resistor, whiie the This PD on-line monitoring system mainly

N is

the tune number of

sensor.

included three parts, the PD sensor, the data collection unit and the workstation, as its show in figure 1.

cormmication

bus

Fig. 2 Rogowski based high frequency current sensor and

Fig.1 Construction block diagram of transformer’s

its equivalent circuit Here, M is the mutual inductance

PD on-line monitoring system

between the winding and the core, .Cs is the stray

PD SENSORS PD sensors are the core of the whole

capacitance of the circuit, Rs is the internal resistance o f

system; it has direct relationship with the design

integral resistance.

the sensor, Ls i s the internal inductance, and R is the

of data collection unit and the measurement effect of the system. Using to detect the wide band, low magnitude, short pulse duration PD

characteristics in the range of 10 lcHz to 20 MHz,

pulses, Rogowski coil based high frequency

it also has other benefits such as fast response,

current sensor was adopted. The sensor’s

high sensitivity, few skewness, safety and

The experiment was shown that this sensor has

flat

amplitude

frequency

response

construction and equivalent scheme are shown in

credibility. Thus, this sensor could not only

figure 2. Here, the Mn-Zn soft magnetic ferrite

collect the PD signals, but also has good

was used for the core of the sensor, which has an

noiseproof feature, which fit for the field PD

excellent response in high frequency (up to 1

detection in substations.

MHz). Also, it decides the sensor’s bandwidth.

DATA COLLECTION UNIT

The bandwidth should be considered seriously. A proper bandwidth wilt get nice results and cut down the cost. In the PD detection, it is quite enough to get an effective result if the discriminable pulses are equal or above 250 per quarter circle[41.In that case, the system was set to work at 100 kHz. So did the

In the transformer’s PD detection, the q-n. ‘p-n figures could be obtained, just from detecting and doing the statistic analysis of PD peak magnitude, peak number and its relationship with phases. With these figures, the transformer’s inside faults could be obtained, the further analysis, such as to assess the operation

- 523 -

status of the'transformer could be done. A 100

frequency, while the bode rate could reach 576

kHz peak-holding data collection system was

kHz Further more, the ATPUS8515 has 64kB

adopted, which fulfilled the demand of the

extended RAM, and its pin form and functions

PD on-line monitoring, and

are similar with the traditional MCU 8051 series,

transformer's

'

decreased the cost of the whole system. The

which have high compatibility with 8051 series

block diagram of this data collection system is shown in figure 3. This system adopted the

point of the PD data collection unit. According

micro control unit (MCU), AT90S8515, as the

to sampling theorem, the sampling rate of data

'core centre process unit (CPU), helping with

collection unit should be 2 times faster than the

peak-holding and sampling circuit, AID converting circuit, and communication level

rate is adopted. Using the traditional data

converting circuit, to collect the PD signals and

coliection unit, the sampling rate should be 600

n

Peak-holding-sampling circuit is the key

signals, actually, 6 or 8 times faster of sampling

kHz in order to detect the 100 lcHz signals,

send these.signals to the workstation.

which is too hard to do for a micro control unit.

Sensor's Output

The peak- holding - sampling circuit was designed to address this problem. Its block diagram is shown in figure 4 I

"

Fig.4 the block diagram of peak-holding circuit

Workstation

The input PD signals firstly compared with

threshold comparator, the comparator opens the

Fig3 The block diagram of data collection unit

The micro control unit, AT9OS8515, is one kind of AVR unit. ARC unit is one kind of Reduced Instruction Set CPU (RISC),designed by Mr. A and Mr. V in 1997. It utilized the

positive peak-holding when the input signal is bigger than the threshold value, while opens the negative peak-holding as the input is lower than the threshold value. The two peak-holdings send

concept of Harvard structure, which could pre-load instructions, so the instructions could be

their output to the switch, which is controlled by

execute per clock period. The AT903 series'

larger one and sends it to the AID converter. The

operation speed can reach 50 ns per instruction consumption is about 1 mA to 205 mA (typical

two peak-holding will be reset every time when the sampling is over. Using this kind of peak-holding-sampling unit, the sampling rate

consumption, 100 nA when WDT dosed). Its

do not be limited by the sampling theorem, 100

inside 16-bits FLASH could re-write more than Receiver (UART) do not tie up with inside timer

lcHz of sampling rate could detect 100 kHz peak values of the PD signal, which is enough for the fault diagnostic and is not hard for the AVR

and SPI,

type's micro control unit.

while working at 20 M H z , and its power

1 000 times. Its universal Asynchronous so it could work at the normal integral

another comparator. The switch chooses the

- 524 -

.

MAX7821, the %-bits high speed AID converter made by MfiZM, was selected to’do

.

CONCLUSION r

..I

* . .

I

the A/D conversion. The sampling time is I O us,

The principle and the construction of the

since the system’s sampling rate is 100 , M z . Th;

,

AID conversion time of MAX7821 ‘is less than 700 ns, so there‘s about 9 us left to do the

’’

peak-holding,

.

AVR based transformer’s PD on-line monitoring

system has been introduced. The system selected

sampling control and other

the wide band current sensor to detect the PD signals so as to assure the anti-jamming,

functions, which is quite enough to assure the

sensitivity and linearity. The high performance

validity of the collection data.

AVR micro contro1.unit was adopted to increase

,

the system’s running speed, and the workstation WORKSTATION

could process the data rapidly and display the results friendly. Different kinds of interface are

Workstation offers an friendly interface and

the further analysis of PD signals. The software is. designed by CVULabwindows, one kind of visual instrument software. Compared with the

set in the system so it could communication with the upper operation system freely.

ACKNOWLEDGEMENT

traditional instrument, the software is the core, .

and it has more flexibility so that the users could

The author acknowledges National Science Fund

add their special functions in it. The main functions are monitoring parameter setting, PD

o f China (NSFC project number 50377035, NSFC project number 5041 1140516), Fok Ying

signal process, fault diagnostic, fault alarm, etc..

Tung Education Fund (project number 91060)

Normally, the system automatic detects the PD two times per day, and calculate the @-q-n 3D

Control and Simulation of Power System and

PD finger print, according to it, the transformer’s

operation status could be estimated. AIL the detecting data are stored in data base in order to reflect the FD development and for reviewing by

and opening project of State Key Laboratory of Generation Equipment of Tsinghua University for their financial support. REFERENCE

the operators and the remote operation system. The software’s structure diagram is shown in figure 5.

+ PD Data Analysis System

[ l ] Xu Qin, Wang Jin. “Summarize of the

research

of power

electrical

instruments’

overhaul,” Electrical Network Technic, Volume 24, Issues, 2000, pp.48-52.

[21 Yan Zhang. “Electrical Insulation on-line Monitoring,” Beijing, Water Conservancy and

Electric Power Press, 1995, Nov. [3] Guo Bihong, Yang Xiaohong. “Analysis of Application

Status

of

Power

Electrical

Instruments on-line monitoring in China,” Electrical Network Technic, 23, Issues, 1999, pp.65-68.

Volume

141 Qiu Changrong. “Electrical Instrument’s Fig. 5 The structure diagram of workstation

Partial Discharge and its Detection,” Beijing, Mechanical Industry Press, 1994, Sep.

- 525 -

Suggest Documents