once the temperature in the room has reached its set point, the low ... outdoor temp. 7ºCDB, 6ºCWB; equivalent refrige
Air Conditioners
Technical Data Super Inverter
EEDEN12-100
RZQ-C
• Outdoor Unit • Super Inverter • RZQ-C
TABLE OF CONTENTS RZQ-C
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Nominal Capacity And Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
............................................................... 8
Combination table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Combination Table
6
................................................... 9
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cooling/Heating Capacity Tables
7
8
10
12
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dimensional Drawings with Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12 13
Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
14
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
15
Piping Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Piping Diagram Twin Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Piping Diagram Triple Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Piping Diagram Double Twin Application . . . . . . . . . . . . . . . . . . . . . . . . . . .
15
Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
19
Wiring Diagrams - Single Phase
11
12
13
10
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Centre of Gravity
9
5
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Options
5
3 4
Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
3
16 17 18
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Sound Power Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sound Pressure Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20 21
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
22
Installation Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fixation and Foundation of Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
22
Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
24
Operation Range
• Split - Sky Air • Outdoor Unit
23
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
1
• Outdoor Unit • Super Inverter • RZQ-C
1 k ir Sne Uv n- rI o t or Ci de - l tpQ puZ S•OR •
1 1
2
Features Outdoor units for pair, twin, triple, double twin application The Sky Air® inverter is developed for use in light commercial applications, provides a more comfortable environment and offers great savings in energy consumption to shop, restaurant and office owners
•
During start up, the room can be cooled down or heated very quickly; once the temperature in the room has reached its set point, the low power operation starts to save energy.
•
Daikin outdoor units are neat, sturdy and can easily be mounted on a roof or terrace or simply placed against an outside wall
•
The use of inverter type outdoor units results in an air conditioning system with a high energy efficiency and very low sound level
•
Outdoor units are fitted with a scroll compressor, renowned for its low noise and high energy efficiency
•
An inverter driven compressor allows the capacity to be adjusted precisely to match variations in room and outside temperatures
•
A special acryl precoated fin for anti-corrosion treatment on the heat exchanger ensures greater resistance against severe weather conditions
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Super Inverter • RZQ-C
2
Specifications
2-1 Nominal Capacity And Nominal Input Cooling capacity
Nom.
FDQ200B8V3B9 / RZQ200C7Y1B
FDQ250B8V3B9 / RZQ250C7Y1B
kW
20.0 (1)
24.1 (1)
3
Heating capacity
Nom.
kW
23.0 (2)
26.4 (2)
Power input
Cooling
Nom.
kW
6.23
8.58
Heating
Nom.
kW
6.74
8.22
1
EER
3.21
2.81
COP
3.41
3.21
2
Piping connections
Liquid
Quantity
1
Type
Braze connection
OD Gas
mm
9.52
12.7
Quantity
1
Type
Braze connection
OD
mm
22.2
Heat insulation
Both liquid and gas pipes
Notes (1) Cooling: indoor temp. 27ºCDB, 19.0ºCWB; outdoor temp. 35ºCDB; equivalent piping length: 5m; level difference: 0m (2) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 5m; level difference: 0m
2-2 Technical Specifications Capacity control Casing Dimensions
RZQ200C7Y1B
Method Colour
Daikin White
Material
Painted galvanized steel plate
Unit
Packed unit
Weight Packing
Height
mm
Width
mm
930
Depth
mm
765
1,680
Height
mm
1,855
Width
mm
1,055
Depth
mm
860
Unit
kg
183
Packed unit
kg
217
Material
184 218 Carton
Weight Packing 2
RZQ250C7Y1B
Inverter controlled
kg
Material
4.02 Wood
Weight
kg
20.85
Packing 3
Material
Plastic
Weight
kg
0.265
Heat exchanger
Length
mm
1,778
mm
2.00
m²
2.112
Rows
Quantity
54
Fin pitch Passes
Quantity
18
Face area Quantity
2
Empty tubeplate hole Quantity
Stages
0
Tube type
ø8 Hi-XSS
Fin
Type
Non-symmetric waffle louvre
Treatment Fan
Hydrophilic and corrosion resistant
Type
Propeller fan
Discharge direction
Vertical
Quantity Air flow rate
1 Cooling
Heating
External static pressure
Max.
Nom.
m³/min
171
Super low
m³/min
-
Nom.
m³/min
171
Super low
m³/min
-
cfm
-
cfm
-
Pa
78
• Split - Sky Air • Outdoor Unit
3
• Outdoor Unit • Super Inverter • RZQ-C
2
Specifications
2-2 Technical Specifications Fan motor
RZQ200C7Y1B
1
Model
Brushless DC motor
Output
1
RZQ250C7Y1B
Quantity W
Speed
2
750.00
Cooling
Super low
rpm
-
Heating
Super low
rpm
-
Sound power level
Nom.
dBA
78
Sound pressure level
Nom.
dBA
57
Compressor
Quantity
1
Model
Inverter
Type
Operation range
Refrigerant
Hermetically sealed scroll compressor
Speed
rpm
7,980
Output
W
3.08
Crankcase heater
W
33 -5.0
Cooling
Ambient
Min.
ºCDB
Max.
ºCDB
46.0
Heating
Ambient
Min.
ºCWB
-15.0
Max.
ºCWB
15.0
Type
R-410A
Charge
kg
8.3
Control Circuits Refrigerant oil
Quantity
1
Type
Synthetic (ether) oil
Charged volume Piping connections
9.3 Electronic expansion valve
l
Drain
ID
Piping length
OU - IU
2.0
mm Max.
-
m
100
Defrost method
Reversed cycle
Defrost control
Sensor for outdoor heat exchanger temperature
Safety devices
Item
01
High pressure switch
02
Fan driver overload protector
03
Overcurrent relay
04
Inverter overload protector
05
PC board fuse
2-3 Electrical Specifications Power supply
RZQ200C7Y1B
Name
RZQ250C7Y1B
Y1
Phase
3N~
Frequency
Hz
50
Voltage
V
380-415
Min.
%
-10
Max.
%
Voltage range Current
Zmax
Wiring connections
For power supply
List
Recommended fuses
For connection with indoor
10 No requirements
A
25
Quantity
5
Remark
Earth wire included
Quantity
4
Remark
Earth wire included
Power supply intake Notes
Outdoor unit only
(1) Sound power level is an absolute value that a sound source generates. (2) Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (3) Sound values are measured in a semi-anechoic room. (4) Power supply to the FDQ indoor unit is separate (5) See separate drawing for electrical data
4
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Super Inverter • RZQ-C
3
Electrical data
3-1
Electrical Data
3
RZQ200-250C Unit combination Indoor unit
Outdoor unit
Hz-volts
Power supply Voltage range MCA
Comp. TOCA
MFA
MSC
OFM RLA
kW
IFM FLA
kW
FLA
1 3
3D056844D
SYMBOLS MCA TOCA MFA MSC RLA OFM IFM FLA kW
NOTES
: Min. Circuit Amps (A) : Total Over Current Amps (A) : Max. Fuse Amps (A) (See note 7) : MSC means the max. current during the starting of compressor. (A) : Rated Load Amps (A) : Outdoor Fan Motor (A) : Indoor Fan Motor : Full Load Amps : Fan Motor Rated Output (kW)
1
2 3
4 5 6 7
RLA is based on the following conditions: Power supply: 50Hz - 400V Cooling Indoor temperature 27°CDB/19°CWB Outdoor temperature 35°CDB Heating Indoor temperature 20.0°CDB Outdoor temperature 7.0°CDB/6.0°CWB TOCA means the total value of each OC set Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed operation range limits Maximum allowable voltage unbalance between phases is 2% MCA represents maximum input current. MFA represents capacity which may accept MCA (next lower standard fuse rating, min.15A) Select wire size based on the larger value of MCA or TOCA MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
• Split - Sky Air • Outdoor Unit
5
• Outdoor Unit • Super Inverter • RZQ-C
3
Electrical data
3-1
Electrical Data
RZQ200-250C
1 3
Unit combination Indoor unit Outdoor unit FBQ100C7VEB x 2 FBQ71C7VEB x 3 RZQ200C7Y1B FBQ60C7VEB x 3 FBQ50C7VEB x 4 FBQ125C7VEB x 2 RZQ250C7Y1B FBQ60C7VEB x 4
Hz-volts
50 - 400
Power supply Voltage range
Max. 50Hz 440V Min. 50Hz 360V
MCA 17.2 17.3 17.3 18.4 18.2 18.4
MFA
Comp. RLA
W
OFM FLA
IFM
20
13.3
750
0,7
W 350x2 350x3 350x3 140x4 350x2 350x4
FLA 1,6x2 1,1x3 1,1x3 1,1x4 2,1x2 1,1x4
3TW29041-3A
SYMBOLS MCA MFA RLA OFM IFM FLA kW
6
: Min. Circuit Amps (A) : Max. Fuse Amps (See note 4) (A) : Rated Load Amps (A) : Outdoor Fan Motor (A) : Indoor Fan Motor : Full Load Amps : Fan Motor Rated Output (W)
NOTES 1 2 3 4 5 6
RLA is based on the following conditions: Indoor temperature 27°CDB/19°CWB Outdoor temperature 35°CDB Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed operation range limits Maximum allowable voltage unbalance between phases is 2% MCA represents maximum input current., MFA represents capacity which may accept MCA (next lower standard fuse rating, min.15A) Select wire size based on the larger value of MCA. MFA is used to select the circuit breaker and earth leakage circuit breaker
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Super Inverter • RZQ-C
3
Electrical data
3-1
Electrical Data
3
RZQ200-250C
Unit combination
Minimum Ssc value [kVA]
1 3
4TW29041-2
NOTES -In accordance with EN/IEC 61000-3-12*, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Ssc** ^ minimum Ssc value. - (*) European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and % 75A per phase. - (**) Short-circuit power
• Split - Sky Air • Outdoor Unit
7
• Outdoor Unit • Super Inverter • RZQ-C
4
Options
4-1
Options
Available options for RZQ200,250C
1 4
Name of option Central drain pan kit Refrigerant branch piping
Kit name RZQ200C7Y1B
RZQ250C7Y1B KWC26B280
Twin
KHRQ22M20TA
Triple
KHRQ250H7
Double twin Demand adaptor
KHRQ22M20TA (3x) KRP58M51 4TW29049-1
8
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Super Inverter • RZQ-C
5
Combination table
5-1
Combination Table
3
Possible combinations and standard capacity for twin, triple and double twin operation Possible indoor combination
1
Simultaneous operation
Outdoor models
Twin
Triple
Out
Out
In
In
In
In
5
Double twin Out
In
In
In
In
RZQ200C7Y1B
100-100 (KHRQ22M20TA)
60-60-60 71-71-71 (KHRQ250H)
50-50-50-50 (3x KHRQ22M20TA)
RZQ250C7Y1B
125-125 (KHRQ22M20TA)
---
60-60-60-60 (3x KHRQ22M20TA)
In
3TW29049-2A
NOTES 1
Possible indoor units:FCQ50-125, FFQ50,60, FHQ50-125, FBQ50-125, FAQ71,100, FUQ71-125, FDQ125
2
Individual indoor capacities are not given because the combinations are for simultaneous operation (=indoor units installed in same room).
3
No mix of different indoor types within the same installation is allowed.
4
Between brackets are the required Refnet kits mentioned, that are necessary to install the combination.
• Split - Sky Air • Outdoor Unit
9
• Outdoor Unit • Super Inverter • RZQ-C
6
Capacity tables
6-1
Cooling/Heating Capacity Tables
RZQ200C7Y1B Cooling
6
Coefficient of power input (-)
Coefficient of power input (-)
1
Heating
Capacity range
Capacity range Rated point
Cooling Capacity (kW)
Cooling
Heating Capacity (kW)
Rated point
Outdoor temperature (°C DB) Indoor
25 SHC (KW) 17.0 17.1 17.1 17.1 17.0 16.8
TC (KW) 20.2 21.3 21.8 22.3 23.4 24.4
°CWB 16 18 19 20 22 24
CPI 0.82 0.83 0.84 0.84 0.85 0.86
30 SHC (KW) 16.3 16.4 16.4 16.4 16.3 16.1
TC (KW) 19.4 20.4 20.9 21.4 22.4 23.4
CPI 0.90 0.91 0.92 0.92 0.94 0.95
35 SHC (KW) 15.5 15.7 15.6 15.6 15.6 15.4
TC (KW) 18.6 19.5 20.0 20.5 21.4 22.4
CPI 0.98 0.99 1.00 1.01 1.02 1.03
TC (KW) 17.7 18.6 19.1 19.6 20.5 21.4
40 SHC (KW) 14.8 14.9 14.9 14.9 14.9 14.7
CPI 0.97 0.98 1.00 1.02 1.03
TC (KW) 25.4 25.3 25.1 24.9 24.7
CPI 1.06 1.07 1.08 1.09 1.10 1.12
Heating Indoor
-15 TC (KW) 10.8 10.8 10.7 10.6 10.5
°C WB 16 18 20 22 24
Outdoor temperature (°C WB) -5 0 TC CPI TC CPI (KW) (KW) 13.9 0.91 15.5 0.96 13.8 0.93 15.4 0.97 13.7 0.94 15.3 0.99 13.6 0.96 15.2 1.01 13.5 0.98 15.1 1.02
-10 CPI 0.83 0.84 0.85 0.87 0.88
TC (KW) 12.2 12.2 12.1 12.0 11.9
CPI 0.87 0.88 0.90 0.91 0.93
6
10
TC (KW) 23.3 23.2 23.0 22.8 22.7
CPI 1.01 1.03 1.04 1.06 1.08
SYMBOLS
(m3/min)
AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. Caution: TC and SHC are shown by kW.
TC SHC PI CPI
(°C WB) (°C DB)
NOTES
1. 2.
3.
4.
Ratings shown are net capacities which include a deduction for indoor fan motor heat. On the figure the mark with O show the max. capacity at standard conditions. show the rated capacity and rated coefficient of power On the figure the mark with input. However the max. capacity is not guaranteed except at standard condition. SHC is based on indoor EWB and EDB. SHC for other dry bulb temp. = SHC + SHC*. SHC* = SHC correction for other dry bulb = 0.02 x AFR (m³/min.) x (1-BF) x (DB*-EDB) Add SHC to SHC*. (Pair)
: Total cooling (heating) capacity (kW) : Sensible heat capacity (kW) : Power input (comp. + indoor and outdoor fan motors) : Coefficient of power input (-)
Capacities are based on the following conditions. Outdoor air: 85% RH However, the condition rated capacity in heating is 7°C DB / 6°C WB. Corresponding refrigerant piping length: 5.0 m. Level difference: 0m Coefficient of power input is the percantage when the rated value is defined as 1.00. The value contains less than 5% error according to indoor unit type. Heating performance include the drop of frost formation. Air flow rate and (BF) are given in table below.
5. 6. 7. 8.
(Twin) FDQ200 AFR (BF)
69 (0.31)
FCQ100C x 2
FCQ100B x 2
FBQ100B x 2
FBQ100C x 2
FHQ100 x 2
FUQ100 x 2
FAQ100 x 2
23.5 x 2 (0.16 x 2)
28 x 2 (0.16 x 2)
27 x 2 (0.2 x 2)
32 x 2 (0.13 x 2)
24 x 2 (0.14 x 2)
29 x 2 (0.07 x 2)
23 x 2 (0.1 x 2)
AFR (BF)
(Triple) AFR (BF)
FCQ60C x 3
FCQ71C x 3
FCQ60B x 3
FCQ71B x 3
FFQ60 x 3
FBQ60B x 3
FBQ71B x 3
FBQ60C x 3
FBQ71C x 3
FHQ60 x 3
FHQ71 x 3
FUQ71 x 3
FAQ71 x 3
13.5 x 3 (0.21 x 3)
15.5 x 3 (0.19 x 3)
18 x 3 (0.1 x 3)
18 x 3 (0.1 x 3)
15 x 3 (0.11 x 3)
19 x 3 (0.11 x 3)
19 x 3 (0.11 x 3)
18 x 3 (0.15 x 3)
18 x 3 (0.08 x 3)
17 x 3 (0.2 x 3)
17 x 3 (0.1 x 3)
19 x 3 (0.07 x 3)
19 x 3 (0.08 x 3)
FCQ50C x 4
FCQ50B x 4
FFQ50 x 4
FBQ50B x 4
FBQ50C x 4
FHQ50 x 4
12.5 x 4 (0.21 x 4)
15 x 4 (0.16 x 4)
12 x 4 (0.16 x 4)
14 x 4 (0.15 x 4)
16 x 4 (0.16 x 4)
14 x 4 (0.1 x 4)
(Double Twin) AFR (BF)
9.
Rated power input of each model is given in table below: (Pair)
(Twin) FDQ200
Cooling Heating
6.23 6.74
FCQ100C x 2
FCQ100B x 2
FBQ100B x 2
FBQ100C x 2
FHQ100 x 2
FUQ100 x 2
FAQ100 x 2
5.69 6.40
5.69 6.40
6.16 6.12
5.99 5.72
6.78 7.34
6.71 6.69
5.99 6.92
Cooling Heating
(Triple) Cooling Heating
FCQ60C x 3
FCQ71C x 3
FCQ60B x 3
FCQ71B x 3
FFQ60 x 3
FBQ60B x 3
FBQ71B x 3
FBQ60C x 3
FBQ71C x 3
FHQ60 x 3
FHQ71 x 3
FUQ71 x 3
FAQ71 x 3
5.99 6.74
5.99 6.74
5.99 6.74
5.99 6.74
6.01 6.54
6.48 6.45
6.48 6.45
6.31 6.05
6.31 6.05
7.14 7.73
7.14 7.73
7.07 7.04
6.30 7.28
FCQ50C x 4
FCQ50B x 4
FFQ50 x 4
FBQ50B x 4
FBQ50C x 4
FHQ50 x 4
5.99 6.74
5.99 6.74
6.01 6.54
6.48 6.45
6.31 6.05
7.14 7.73
(Double Twin) Cooling Heating
10
• Split - Sky Air • Outdoor Unit
3TW29041-4
• Outdoor Unit • Super Inverter • RZQ-C
6
Capacity tables
6-1
Cooling/Heating Capacity Tables
3
RZQ250C7Y1B Heating
1
Coefficient of power input (-)
Coefficient of power input (-)
Cooling
6
Capacity range
Capacity range
Cooling Capacity (kW)
Heating Capacity (kW)
Rated point
Rated point
Cooling Indoor
25 SHC (KW) 21.5 21.5 21.5 21.4 21.2 20.9
TC (KW) 24.5 25.7 26.2 26.8 28.0 29.1
°CWB 16 18 19 20 22 24
CPI 0.79 0.80 0.80 0.81 0.81 0.82
TC (KW) 23.5 24.6 25.2 25.7 26.8 27.9
Outdoor temperature (°C DB) 30 35 SHC CPI TC SHC (KW) (KW) (KW) 20.7 0.88 22.5 19.8 20.6 0.89 23.6 19.8 20.6 0.90 24.1 19.8 20.5 0.91 24.6 19.7 20.3 0.92 25.7 19.5 20.1 0.93 26.7 19.3
CPI 0.98 0.99 1.00 1.01 1.02 1.03
CPI 0.82 0.85 0.88 0.92 0.95
Outdoor temperature (°C WB) -5 0 TC CPI TC CPI (KW) (KW) 16.6 0.87 18.4 0.91 16.4 0.90 18.2 0.95 16.3 0.94 18.0 0.99 16.1 0.97 17.9 1.03 16.0 1.01 17.7 1.06
TC (KW) 26.9 26.6 26.4 26.2 25.9
TC (KW) 21.5 22.5 23.0 23.5 24.5 25.6
40 SHC (KW) 19.0 18.9 29.0 18.9 18.7 18.4
CPI 0.92 0.96 1.00 1.04 1.08
TC (KW) 29.2 28.9 28.7 28.4 28.2
CPI 1.08 1.09 1.10 1.11 1.12 1.13
Heating Indoor
-15 TC (KW) 13.2 13.1 12.9 12.8 12.7
°C WB 16 18 20 22 24
-10 CPI 0.77 0.80 0.84 0.87 0.90
TC (KW) 14.7 14.6 14.5 14.3 14.2
6
10 CPI 0.98 1.02 1.06 1.10 1.14
SYMBOLS
(m3/min)
AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. Caution: TC and SHC are shown by kW.
TC SHC PI CPI
(°C WB) (°C DB)
NOTES
1. 2.
3.
Ratings shown are net capacities which include a deduction for indoor fan motor heat. On the figure the mark with O show the max. capacity at standard conditions. On the figure the mark with show the rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed except at standard condition. SHC is based on indoor EWB and EDB. SHC for other dry bulb temp. = SHC + SHC*. SHC* = SHC correction for other dry bulb = 0.02 x AFR (m³/min.) x (1-BF) x (DB*-EDB) Add SHC to SHC*. (Triple)
5. 6. 7. 8.
Capacities are based on the following conditions. Outdoor air: 85% RH However, the condition rated capacity in heating is 7°C DB / 6°C WB. Corresponding refrigerant piping length: 5.0 m. Level difference: 0m Coefficient of power input is the percantage when the rated value is defined as 1.00. The value contains less than 5% error according to indoor unit type. Heating performance include the drop of frost formation. Air flow rate and (BF) are given in table below.
(Twin) FDQ250
AFR (BF)
4.
: Total cooling (heating) capacity (kW) : Sensible heat capacity (kW) : Power input (comp. + indoor and outdoor fan motors) : Coefficient of power input (-)
89 (0.34)
AFR (BF)
FCQ125C x 2
FCQ125B x 2
FBQ125B x 2
FBQ125C x 2
FHQ125 x 2
FUQ125 x 2
FDQ125 x 2
27.5 x 2 (0.19 x 2)
31 x 2 (0.07 x 2)
35 x 2 (0.14 x 2)
39 x 2 (0.16 x 2)
30 x 2 (0.13 x 2)
32 x 2 (0.07 x 2)
45 x 2 (0.25 x 2)
(Double Twin) AFR (BF)
9.
FCQ60C x 4
FCQ60B x 4
FFQ60 x 4
FBQ60B x 4
FBQ60C x 4
FHQ60 x 4
13.5 x 4 (0.21 x 4)
18 x 4 (0.1 x 4)
15 x 4 (0.11 x 4)
19 x 4 (0.11 x 4)
18 x 4 (0.15 x 4)
17 x 4 (0.2 x 4)
Rated power input of each model is given in table below: (Pair)
(Twin) FDQ250
Cooling Heating
8.58 8.22
FCQ125C x 2
FCQ125B x 2
FBQ125B x 2
FBQ125C x 2
FHQ125 x 2
FUQ125 x 2
FDQ125 x 2
8.91 8.68
8.91 8.68
9.14 7.94
8.98 7.38
10.22 8.95
9.30 8.68
9.53 7.35
Cooling Heating
(Dounle Twin) Cooling Heating
FCQ60C x 3
FCQ71C x 3
FCQ60B x 3
FCQ71B x 3
FFQ60 x 3
FBQ60B x 3
9.39 9.13
9.39 9.13
9.49 8.48
9.62 8.36
9.46 7.80
10.76 9.43
3TW29051-4
• Split - Sky Air • Outdoor Unit
11
• Outdoor Unit • Super Inverter • RZQ-C
7
Dimensional drawings
7-1
Dimensional Drawings
RZQ200-250C (Pitch of foundation bolt holes)
(Pitch of foundation bolt holes)
1
4-15 X 22.5 - mm - Oblong holes (foundation bolt hole)
7
6 (for 8HP)
Detail for front side
Detail for bottom side
(Knock-out hole)
(Knock-out hole)
(Knock-out hole)
Notes 1 Detail for front side and detail for bottom side indicate the dimensions after fixing the attached piping. 2 Gas pipe (Heat pump type) J22.2 Brazing connection Liquid pipe (Heat pump type) J9.5 Brazing connection ... For 200-type J12.7 Brazing connection ... For 250-type (Knock-out hole)
1 2 3 4 5 6 7 8 9 10
Liquid pipe connection port see note 2. Gas pipe connection port see note 2. Grounding terminal inside of switch box (M8) Power cord routing hole (side) J62 Power cord routing hole (front) J45 Power cord routing hole (front) J27 Power cord routing hole (bottom) J65.5 Wire routing hole (front) J27 Pipe routing hole (front) Pipe routing hole (bottom)
(Knock-out hole)
3TW29044-1
12
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Super Inverter • RZQ-C
7
Dimensional drawings
7-2
Dimensional Drawings with Accessories
3
RZQ200-250C
1 7
NOTES 1
Central drain pan kit
KWC26B280
• Split - Sky Air • Outdoor Unit
3TW27244-1
13
• Outdoor Unit • Super Inverter • RZQ-C
8
Centre of gravity
8-1
Centre of Gravity
RZQ200-250C
1 8
Center of foundation bolt hole
Center of foundation bolt hole (oblong hole)
Center of foundation bolt hole
Center of foundation bolt hole (oblong hole)
4TW29049-4
14
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Super Inverter • RZQ-C
9
Piping diagrams
9-1
Piping Diagrams
3
RZQ200-250C (Pair) Strainer Receiver
Solenoid valve
A 9.52 12.70
Model RZQ200C RZQ250C
1
Heat exchanger pipe Filter
Filter
Check valve
Check valve Check valve
Electronic expansion valve
9
Fan
Check valve Electronic expansion valve
Heat exchanger 4-way valve
High pressure sensor
Pressure regulating valve
High pressure switch
Indoor heat exchanger
Compressor
Low pressure sensor
Field piping J A Fan
Indoor unit
Filter
Capillary tube
Strainer
Oil separator
Solenoid valve
Field piping J22.20 Stop valve (With service port on on-site piping side J7.9mm flare connection)
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
• Split - Sky Air • Outdoor Unit
Outdoor unit
3TW29045-1
15
• Outdoor Unit • Super Inverter • RZQ-C
9
Piping diagrams
9-2
Piping Diagram Twin Application
RZQ200-250C (Twin) Strainer Receiver
Solenoid valve
1
Heat exchanger pipe Filter
A 9.52 12.70
9
Model RZQ200C RZQ250C
Check valve
Check valve
Filter
Check valve
Fan
Check valve Electronic expansion valve
Electronic expansion valve Heat exchanger 4-way valve
High pressure sensor
Pressure regulating valve
High pressure switch
Compressor Capillary tube
Field piping
Fan
Strainer
Oil separator
Solenoid valve
Indoor heat exchanger
Field piping Low pressure sensor
Branch pipe (Option)
Field piping J22.20
Indoor heat exchanger
Field piping
Fan
Stop valve (With service port on on-site piping side J7.9mm flare connection)
Outdoor unit
Field piping
Indoor unit
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
16
Filter
Field piping J A
Indoor unit
• Split - Sky Air • Outdoor Unit
3TW29045-2
• Outdoor Unit • Super Inverter • RZQ-C
9
Piping diagrams
9-3
Piping Diagram Triple Application
3
RZQ200-250C (Triple) Strainer Receiver
Solenoid valve
A 9.52 12.70
1
Heat exchanger pipe Filter
Model RZQ200C RZQ250C
Filter
Check valve
Fan Check valve Electronic expansion valve
Indoor heat exchanger
9
Check valve
Check valve
Electronic expansion valve Heat exchanger 4-way valve
Field piping
Fan
Pressure regulating valve
High pressure sensor
Field piping
Oil separator
Solenoid valve
Indoor heat exchanger High pressure switch
Field piping J A
Compressor Capillary tube
Field piping Field piping
Indoor unit Indoor heat exchanger
Branch pipe (Option)
Field piping J22.20 Low pressure sensor
Stop valve
Filter
Fan
Strainer
Indoor unit
(With service port on on-site piping side J7.9mm flare connection)
Outdoor unit Field piping
Fan
Field piping
Note: The pipes between the branch and the indoor units should have the same size as the indoor connections.
Indoor unit
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
• Split - Sky Air • Outdoor Unit
3TW29045-3
17
• Outdoor Unit • Super Inverter • RZQ-C
9
Piping diagrams
9-4
Piping Diagram Double Twin Application
RZQ200-250C (Double twin) Indoor heat exchanger
Strainer
9
Field piping
Fan
Model RZQ200C RZQ250C
Heat exchanger pipe Filter
Check valve
Check valve
Field piping
Filter
Indoor unit
Fan Check valve
Check valve Electronic expansion valve
Field piping J 9.52
Indoor heat exchanger
Solenoid valve
Receiver
1
A 9.52 12.70
Electronic expansion valve Heat exchanger
Field piping J15.90
4-way valve
Field piping
High pressure sensor
Pressure regulating valve
Field piping
Indoor unit
Solenoid valve Oil separator
Fan
Indoor heat exchanger High pressure switch
Branch pipe Field piping J A
Compressor Capillary tube
Field piping
Field piping J22.20
Field piping
Low pressure sensor
Indoor unit Field piping J 9.52
Indoor heat exchanger
Field piping J15.90
Stop valve (With service port on on-site piping side J7.9mm flare connection)
Field piping Fan
Field piping
Indoor unit
• Split - Sky Air • Outdoor Unit
Outdoor unit
Note: The pipes between the branch and the indoor units should have the same size as the indoor connections.
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
18
Filter
Fan
Strainer
(Option)
3TW29045-4
• Outdoor Unit • Super Inverter • RZQ-C
10
Wiring diagrams
10 - 1 Wiring Diagrams - Single Phase
3
∼
1
∼
10
∼
∼
∼
∼ ∼
∼
• Split - Sky Air • Outdoor Unit
19
• Outdoor Unit • Super Inverter • RZQ-C
11
Sound data
11 - 1 Sound Power Spectrum
11
Sound power level (dB)
1
RZQ250C - Cooling
Sound power level (dB)
RZQ200C - Cooling
3TW29047-3
Octave band center frequency (Hz)
3TW29057-3
NOTES 1 2 3
20
Octave band center frequency (Hz)
NOTES
dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6μW/m2 Measured according to ISO 3744
• Split - Sky Air • Outdoor Unit
1 2 3
dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6μW/m2 Measured according to ISO 3744
• Outdoor Unit • Super Inverter • RZQ-C
11
Sound data
11 - 2 Sound Pressure Spectrum
3 RZQ200C - Heating
3TW29047-1
2 3 4
5
Coil Data is valid at free field condition (measured in a Microphone semi-anachoic room) Switchbox dB(A) = A-weighted sound pressure level (A-scale according to IEC) Location of microphone Reference acoustic pressure 0dB = 20Pa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Curve for RZQ200C7Y1B in cooling mode
1 2 3 4
5
Sound pressure level (dB) Octave band center frequency (Hz)
3TW29057-2
NOTES
3 4
5
Data is valid at free field condition (measured in a Coil Microphone semi-anachoic room) Switchbox dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20Pa Location of microphone If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Curve for RZQ200C7Y1B in heating mode
RZQ250C - Heating
Sound pressure level (dB)
3TW29057-1
2
Octave band center frequency (Hz)
NOTES
RZQ250C - Cooling
1
11
3TW29047-2
Octave band center frequency (Hz)
NOTES 1
1
Sound pressure level (dB)
Sound pressure level (dB)
RZQ200C - Cooling
Octave band center frequency (Hz)
NOTES
Coil Data is valid at free field condition (measured in a Microphone semi-anachoic room) Switchbox dB(A) = A-weighted sound pressure level (A-scale according to IEC) Location of microphone Reference acoustic pressure 0dB = 20Pa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Curve for RZQ200C7Y1B in cooling mode
• Split - Sky Air • Outdoor Unit
1 2 3 4
5
Data is valid at free field condition (measured in a Coil Microphone semi-anachoic room) Switchbox dB(A) = A-weighted sound pressure level (A-scale according to IEC) Location of microphone Reference acoustic pressure 0dB = 20Pa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Curve for RZQ200C7Y1B in heating mode
21
22
• Split - Sky Air • Outdoor Unit
10 or more
200 or more
300 or more
500 or more
100 or more
Wall height unrestricted
50 or more
50 or more
10 or more
200 or more
400 or more
100 or more
20 or more
50 or more
10 or more
400 or more
Wall height unrestricted
100 or more
20 or more
300 or more
500 or more
100 or more
500 or more
50 or more
50 or more
10 or more
10 or more
500 or more
500 or more
100 or more
500 or more
600 or more
300 or more
100 or more
100 or more
20 or more
20 or more
Notes: 1 Heights of walls in case of Patterns 1 and 2: Front: 1500 mm suction side: 500 mm Side: Height unrestricted. Installation space to be shown in this drawing is based on the cooling operation at 35 degrees outdoor air temperature. When the design outdoor air temperature exceeds 35 degrees or the load exceeds maximum ability because of much generation load of heat in all outdoor unit, take the suction side space more broadly than the space to be shown in this drawing. 2 If the above wall heights are exceeded then h1/2 and h2/2 should be added to the front and suction side service spaces respectively as shown in the figure on the right. 3 When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available always bearing in mind the need to leave enough space for a person to pass between units and wall and for the air to circulate freely. (If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits.) 4 The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.
50 or more
500 or more
300 or more
For centralized group layout
50 or more
50 or more
10 or more
10 or more
50 or more
50 or more
10 or more
10 or more
100 or more
500 or more
100 or more
300 or more
500 or more
300 or more
100 or more
100 or more
20 or more
20 or more
12
10 or more
300 or more
For installation in rows
For single unit installation
3TW29049-3
50 or more
50 or more
10 or more
10 or more
1
12
RZQ200-250C
• Outdoor Unit • Super Inverter • RZQ-C
Installation
12 - 1 Installation Method
• Outdoor Unit • Super Inverter • RZQ-C
12
Installation
12 - 2 Fixation and Foundation of Units
3 1 12
• Split - Sky Air • Outdoor Unit
23
• Outdoor Unit • Super Inverter • RZQ-C
13
Operation range
13 - 1 Operation Range RZQ200-250C
Cooling
1
Indoor temp. (°CWB)
Operation range
Allowable range of operation (warming-up)
Heating
Outdoor temp. (°CWB)
Allowable range of operation (pull-down)
Operation range
Outdoor temp. (°CDB)
13
Indoor temp. (°CDB) 4TW26566-1
24
• Split - Sky Air • Outdoor Unit
Please fill out the requested information Please fill out the requested information
Daikin Europe N.V. participates in the Eurovent Certification programme for Air conditioners (AC), Liquid Chilling Packages (LCP), Air handling units (AHU) and Fan coil units (FCU), Check ongoing validity of certificate online: www.eurovent-certification.com or using: www.certiflash.com”
Daikin products are distributed by:
The present leaflet is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this leaflet to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin Europe N.V.
EEDEN1 2 - 1 0 0
Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende
EEDEN12-100 • 04/12 • Copyright © Daikin The present publication supersedes EEDEN11-100 Printed on non-chlorinated paper. Prepared by Goekint Graphics NV, Belgium Responsible Editor: Daikin Europe N.V., Zandvoordestraat 300, B-8400 Oostende
Daikin’s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental issues. For several years Daikin has had the intention to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste.