Technical Data

4 downloads 208 Views 2MB Size Report
once the temperature in the room has reached its set point, the low ... outdoor temp. 7ºCDB, 6ºCWB; equivalent refrige
Air Conditioners

Technical Data Super Inverter

EEDEN12-100

RZQ-C

• Outdoor Unit • Super Inverter • RZQ-C

TABLE OF CONTENTS RZQ-C

1

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Nominal Capacity And Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

............................................................... 8

Combination table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Combination Table

6

................................................... 9

Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cooling/Heating Capacity Tables

7

8

10

12

Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dimensional Drawings with Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . .

12 13

Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

14

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

15

Piping Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Piping Diagram Twin Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Piping Diagram Triple Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Piping Diagram Double Twin Application . . . . . . . . . . . . . . . . . . . . . . . . . . .

15

Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

19

Wiring Diagrams - Single Phase

11

12

13

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Centre of Gravity

9

5

Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Options

5

3 4

Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4

3

16 17 18

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Sound Power Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sound Pressure Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

20 21

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

22

Installation Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fixation and Foundation of Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

22

Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

24

Operation Range

• Split - Sky Air • Outdoor Unit

23

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

1

• Outdoor Unit • Super Inverter • RZQ-C

1 k ir Sne Uv n- rI o t or Ci de - l tpQ puZ S•OR •

1 1

2

Features Outdoor units for pair, twin, triple, double twin application The Sky Air® inverter is developed for use in light commercial applications, provides a more comfortable environment and offers great savings in energy consumption to shop, restaurant and office owners



During start up, the room can be cooled down or heated very quickly; once the temperature in the room has reached its set point, the low power operation starts to save energy.



Daikin outdoor units are neat, sturdy and can easily be mounted on a roof or terrace or simply placed against an outside wall



The use of inverter type outdoor units results in an air conditioning system with a high energy efficiency and very low sound level



Outdoor units are fitted with a scroll compressor, renowned for its low noise and high energy efficiency



An inverter driven compressor allows the capacity to be adjusted precisely to match variations in room and outside temperatures



A special acryl precoated fin for anti-corrosion treatment on the heat exchanger ensures greater resistance against severe weather conditions

• Split - Sky Air • Outdoor Unit

• Outdoor Unit • Super Inverter • RZQ-C

2

Specifications

2-1 Nominal Capacity And Nominal Input Cooling capacity

Nom.

FDQ200B8V3B9 / RZQ200C7Y1B

FDQ250B8V3B9 / RZQ250C7Y1B

kW

20.0 (1)

24.1 (1)

3

Heating capacity

Nom.

kW

23.0 (2)

26.4 (2)

Power input

Cooling

Nom.

kW

6.23

8.58

Heating

Nom.

kW

6.74

8.22

1

EER

3.21

2.81

COP

3.41

3.21

2

Piping connections

Liquid

Quantity

1

Type

Braze connection

OD Gas

mm

9.52

12.7

Quantity

1

Type

Braze connection

OD

mm

22.2

Heat insulation

Both liquid and gas pipes

Notes (1) Cooling: indoor temp. 27ºCDB, 19.0ºCWB; outdoor temp. 35ºCDB; equivalent piping length: 5m; level difference: 0m (2) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 5m; level difference: 0m

2-2 Technical Specifications Capacity control Casing Dimensions

RZQ200C7Y1B

Method Colour

Daikin White

Material

Painted galvanized steel plate

Unit

Packed unit

Weight Packing

Height

mm

Width

mm

930

Depth

mm

765

1,680

Height

mm

1,855

Width

mm

1,055

Depth

mm

860

Unit

kg

183

Packed unit

kg

217

Material

184 218 Carton

Weight Packing 2

RZQ250C7Y1B

Inverter controlled

kg

Material

4.02 Wood

Weight

kg

20.85

Packing 3

Material

Plastic

Weight

kg

0.265

Heat exchanger

Length

mm

1,778

mm

2.00



2.112

Rows

Quantity

54

Fin pitch Passes

Quantity

18

Face area Quantity

2

Empty tubeplate hole Quantity

Stages

0

Tube type

ø8 Hi-XSS

Fin

Type

Non-symmetric waffle louvre

Treatment Fan

Hydrophilic and corrosion resistant

Type

Propeller fan

Discharge direction

Vertical

Quantity Air flow rate

1 Cooling

Heating

External static pressure

Max.

Nom.

m³/min

171

Super low

m³/min

-

Nom.

m³/min

171

Super low

m³/min

-

cfm

-

cfm

-

Pa

78

• Split - Sky Air • Outdoor Unit

3

• Outdoor Unit • Super Inverter • RZQ-C

2

Specifications

2-2 Technical Specifications Fan motor

RZQ200C7Y1B

1

Model

Brushless DC motor

Output

1

RZQ250C7Y1B

Quantity W

Speed

2

750.00

Cooling

Super low

rpm

-

Heating

Super low

rpm

-

Sound power level

Nom.

dBA

78

Sound pressure level

Nom.

dBA

57

Compressor

Quantity

1

Model

Inverter

Type

Operation range

Refrigerant

Hermetically sealed scroll compressor

Speed

rpm

7,980

Output

W

3.08

Crankcase heater

W

33 -5.0

Cooling

Ambient

Min.

ºCDB

Max.

ºCDB

46.0

Heating

Ambient

Min.

ºCWB

-15.0

Max.

ºCWB

15.0

Type

R-410A

Charge

kg

8.3

Control Circuits Refrigerant oil

Quantity

1

Type

Synthetic (ether) oil

Charged volume Piping connections

9.3 Electronic expansion valve

l

Drain

ID

Piping length

OU - IU

2.0

mm Max.

-

m

100

Defrost method

Reversed cycle

Defrost control

Sensor for outdoor heat exchanger temperature

Safety devices

Item

01

High pressure switch

02

Fan driver overload protector

03

Overcurrent relay

04

Inverter overload protector

05

PC board fuse

2-3 Electrical Specifications Power supply

RZQ200C7Y1B

Name

RZQ250C7Y1B

Y1

Phase

3N~

Frequency

Hz

50

Voltage

V

380-415

Min.

%

-10

Max.

%

Voltage range Current

Zmax

Wiring connections

For power supply

List

Recommended fuses

For connection with indoor

10 No requirements

A

25

Quantity

5

Remark

Earth wire included

Quantity

4

Remark

Earth wire included

Power supply intake Notes

Outdoor unit only

(1) Sound power level is an absolute value that a sound source generates. (2) Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (3) Sound values are measured in a semi-anechoic room. (4) Power supply to the FDQ indoor unit is separate (5) See separate drawing for electrical data

4

• Split - Sky Air • Outdoor Unit

• Outdoor Unit • Super Inverter • RZQ-C

3

Electrical data

3-1

Electrical Data

3

RZQ200-250C Unit combination Indoor unit

Outdoor unit

Hz-volts

Power supply Voltage range MCA

Comp. TOCA

MFA

MSC

OFM RLA

kW

IFM FLA

kW

FLA

1 3

3D056844D

SYMBOLS MCA TOCA MFA MSC RLA OFM IFM FLA kW

NOTES

: Min. Circuit Amps (A) : Total Over Current Amps (A) : Max. Fuse Amps (A) (See note 7) : MSC means the max. current during the starting of compressor. (A) : Rated Load Amps (A) : Outdoor Fan Motor (A) : Indoor Fan Motor : Full Load Amps : Fan Motor Rated Output (kW)

1

2 3

4 5 6 7

RLA is based on the following conditions: Power supply: 50Hz - 400V Cooling Indoor temperature 27°CDB/19°CWB Outdoor temperature 35°CDB Heating Indoor temperature 20.0°CDB Outdoor temperature 7.0°CDB/6.0°CWB TOCA means the total value of each OC set Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed operation range limits Maximum allowable voltage unbalance between phases is 2% MCA represents maximum input current. MFA represents capacity which may accept MCA (next lower standard fuse rating, min.15A) Select wire size based on the larger value of MCA or TOCA MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)

• Split - Sky Air • Outdoor Unit

5

• Outdoor Unit • Super Inverter • RZQ-C

3

Electrical data

3-1

Electrical Data

RZQ200-250C

1 3

Unit combination Indoor unit Outdoor unit FBQ100C7VEB x 2 FBQ71C7VEB x 3 RZQ200C7Y1B FBQ60C7VEB x 3 FBQ50C7VEB x 4 FBQ125C7VEB x 2 RZQ250C7Y1B FBQ60C7VEB x 4

Hz-volts

50 - 400

Power supply Voltage range

Max. 50Hz 440V Min. 50Hz 360V

MCA 17.2 17.3 17.3 18.4 18.2 18.4

MFA

Comp. RLA

W

OFM FLA

IFM

20

13.3

750

0,7

W 350x2 350x3 350x3 140x4 350x2 350x4

FLA 1,6x2 1,1x3 1,1x3 1,1x4 2,1x2 1,1x4

3TW29041-3A

SYMBOLS MCA MFA RLA OFM IFM FLA kW

6

: Min. Circuit Amps (A) : Max. Fuse Amps (See note 4) (A) : Rated Load Amps (A) : Outdoor Fan Motor (A) : Indoor Fan Motor : Full Load Amps : Fan Motor Rated Output (W)

NOTES 1 2 3 4 5 6

RLA is based on the following conditions: Indoor temperature 27°CDB/19°CWB Outdoor temperature 35°CDB Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed operation range limits Maximum allowable voltage unbalance between phases is 2% MCA represents maximum input current., MFA represents capacity which may accept MCA (next lower standard fuse rating, min.15A) Select wire size based on the larger value of MCA. MFA is used to select the circuit breaker and earth leakage circuit breaker

• Split - Sky Air • Outdoor Unit

• Outdoor Unit • Super Inverter • RZQ-C

3

Electrical data

3-1

Electrical Data

3

RZQ200-250C

Unit combination

Minimum Ssc value [kVA]

1 3

4TW29041-2

NOTES -In accordance with EN/IEC 61000-3-12*, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Ssc** ^ minimum Ssc value. - (*) European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and % 75A per phase. - (**) Short-circuit power

• Split - Sky Air • Outdoor Unit

7

• Outdoor Unit • Super Inverter • RZQ-C

4

Options

4-1

Options

Available options for RZQ200,250C

1 4

Name of option Central drain pan kit Refrigerant branch piping

Kit name RZQ200C7Y1B

RZQ250C7Y1B KWC26B280

Twin

KHRQ22M20TA

Triple

KHRQ250H7

Double twin Demand adaptor

KHRQ22M20TA (3x) KRP58M51 4TW29049-1

8

• Split - Sky Air • Outdoor Unit

• Outdoor Unit • Super Inverter • RZQ-C

5

Combination table

5-1

Combination Table

3

Possible combinations and standard capacity for twin, triple and double twin operation Possible indoor combination

1

Simultaneous operation

Outdoor models

Twin

Triple

Out

Out

In

In

In

In

5

Double twin Out

In

In

In

In

RZQ200C7Y1B

100-100 (KHRQ22M20TA)

60-60-60 71-71-71 (KHRQ250H)

50-50-50-50 (3x KHRQ22M20TA)

RZQ250C7Y1B

125-125 (KHRQ22M20TA)

---

60-60-60-60 (3x KHRQ22M20TA)

In

3TW29049-2A

NOTES 1

Possible indoor units:FCQ50-125, FFQ50,60, FHQ50-125, FBQ50-125, FAQ71,100, FUQ71-125, FDQ125

2

Individual indoor capacities are not given because the combinations are for simultaneous operation (=indoor units installed in same room).

3

No mix of different indoor types within the same installation is allowed.

4

Between brackets are the required Refnet kits mentioned, that are necessary to install the combination.

• Split - Sky Air • Outdoor Unit

9

• Outdoor Unit • Super Inverter • RZQ-C

6

Capacity tables

6-1

Cooling/Heating Capacity Tables

RZQ200C7Y1B Cooling

6

Coefficient of power input (-)

Coefficient of power input (-)

1

Heating

Capacity range

Capacity range Rated point

Cooling Capacity (kW)

Cooling

Heating Capacity (kW)

Rated point

Outdoor temperature (°C DB) Indoor

25 SHC (KW) 17.0 17.1 17.1 17.1 17.0 16.8

TC (KW) 20.2 21.3 21.8 22.3 23.4 24.4

°CWB 16 18 19 20 22 24

CPI 0.82 0.83 0.84 0.84 0.85 0.86

30 SHC (KW) 16.3 16.4 16.4 16.4 16.3 16.1

TC (KW) 19.4 20.4 20.9 21.4 22.4 23.4

CPI 0.90 0.91 0.92 0.92 0.94 0.95

35 SHC (KW) 15.5 15.7 15.6 15.6 15.6 15.4

TC (KW) 18.6 19.5 20.0 20.5 21.4 22.4

CPI 0.98 0.99 1.00 1.01 1.02 1.03

TC (KW) 17.7 18.6 19.1 19.6 20.5 21.4

40 SHC (KW) 14.8 14.9 14.9 14.9 14.9 14.7

CPI 0.97 0.98 1.00 1.02 1.03

TC (KW) 25.4 25.3 25.1 24.9 24.7

CPI 1.06 1.07 1.08 1.09 1.10 1.12

Heating Indoor

-15 TC (KW) 10.8 10.8 10.7 10.6 10.5

°C WB 16 18 20 22 24

Outdoor temperature (°C WB) -5 0 TC CPI TC CPI (KW) (KW) 13.9 0.91 15.5 0.96 13.8 0.93 15.4 0.97 13.7 0.94 15.3 0.99 13.6 0.96 15.2 1.01 13.5 0.98 15.1 1.02

-10 CPI 0.83 0.84 0.85 0.87 0.88

TC (KW) 12.2 12.2 12.1 12.0 11.9

CPI 0.87 0.88 0.90 0.91 0.93

6

10

TC (KW) 23.3 23.2 23.0 22.8 22.7

CPI 1.01 1.03 1.04 1.06 1.08

SYMBOLS

(m3/min)

AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. Caution: TC and SHC are shown by kW.

TC SHC PI CPI

(°C WB) (°C DB)

NOTES

1. 2.

3.

4.

Ratings shown are net capacities which include a deduction for indoor fan motor heat. On the figure the mark with O show the max. capacity at standard conditions. show the rated capacity and rated coefficient of power On the figure the mark with input. However the max. capacity is not guaranteed except at standard condition. SHC is based on indoor EWB and EDB. SHC for other dry bulb temp. = SHC + SHC*. SHC* = SHC correction for other dry bulb = 0.02 x AFR (m³/min.) x (1-BF) x (DB*-EDB) Add SHC to SHC*. (Pair)

: Total cooling (heating) capacity (kW) : Sensible heat capacity (kW) : Power input (comp. + indoor and outdoor fan motors) : Coefficient of power input (-)

Capacities are based on the following conditions. Outdoor air: 85% RH However, the condition rated capacity in heating is 7°C DB / 6°C WB. Corresponding refrigerant piping length: 5.0 m. Level difference: 0m Coefficient of power input is the percantage when the rated value is defined as 1.00. The value contains less than 5% error according to indoor unit type. Heating performance include the drop of frost formation. Air flow rate and (BF) are given in table below.

5. 6. 7. 8.

(Twin) FDQ200 AFR (BF)

69 (0.31)

FCQ100C x 2

FCQ100B x 2

FBQ100B x 2

FBQ100C x 2

FHQ100 x 2

FUQ100 x 2

FAQ100 x 2

23.5 x 2 (0.16 x 2)

28 x 2 (0.16 x 2)

27 x 2 (0.2 x 2)

32 x 2 (0.13 x 2)

24 x 2 (0.14 x 2)

29 x 2 (0.07 x 2)

23 x 2 (0.1 x 2)

AFR (BF)

(Triple) AFR (BF)

FCQ60C x 3

FCQ71C x 3

FCQ60B x 3

FCQ71B x 3

FFQ60 x 3

FBQ60B x 3

FBQ71B x 3

FBQ60C x 3

FBQ71C x 3

FHQ60 x 3

FHQ71 x 3

FUQ71 x 3

FAQ71 x 3

13.5 x 3 (0.21 x 3)

15.5 x 3 (0.19 x 3)

18 x 3 (0.1 x 3)

18 x 3 (0.1 x 3)

15 x 3 (0.11 x 3)

19 x 3 (0.11 x 3)

19 x 3 (0.11 x 3)

18 x 3 (0.15 x 3)

18 x 3 (0.08 x 3)

17 x 3 (0.2 x 3)

17 x 3 (0.1 x 3)

19 x 3 (0.07 x 3)

19 x 3 (0.08 x 3)

FCQ50C x 4

FCQ50B x 4

FFQ50 x 4

FBQ50B x 4

FBQ50C x 4

FHQ50 x 4

12.5 x 4 (0.21 x 4)

15 x 4 (0.16 x 4)

12 x 4 (0.16 x 4)

14 x 4 (0.15 x 4)

16 x 4 (0.16 x 4)

14 x 4 (0.1 x 4)

(Double Twin) AFR (BF)

9.

Rated power input of each model is given in table below: (Pair)

(Twin) FDQ200

Cooling Heating

6.23 6.74

FCQ100C x 2

FCQ100B x 2

FBQ100B x 2

FBQ100C x 2

FHQ100 x 2

FUQ100 x 2

FAQ100 x 2

5.69 6.40

5.69 6.40

6.16 6.12

5.99 5.72

6.78 7.34

6.71 6.69

5.99 6.92

Cooling Heating

(Triple) Cooling Heating

FCQ60C x 3

FCQ71C x 3

FCQ60B x 3

FCQ71B x 3

FFQ60 x 3

FBQ60B x 3

FBQ71B x 3

FBQ60C x 3

FBQ71C x 3

FHQ60 x 3

FHQ71 x 3

FUQ71 x 3

FAQ71 x 3

5.99 6.74

5.99 6.74

5.99 6.74

5.99 6.74

6.01 6.54

6.48 6.45

6.48 6.45

6.31 6.05

6.31 6.05

7.14 7.73

7.14 7.73

7.07 7.04

6.30 7.28

FCQ50C x 4

FCQ50B x 4

FFQ50 x 4

FBQ50B x 4

FBQ50C x 4

FHQ50 x 4

5.99 6.74

5.99 6.74

6.01 6.54

6.48 6.45

6.31 6.05

7.14 7.73

(Double Twin) Cooling Heating

10

• Split - Sky Air • Outdoor Unit

3TW29041-4

• Outdoor Unit • Super Inverter • RZQ-C

6

Capacity tables

6-1

Cooling/Heating Capacity Tables

3

RZQ250C7Y1B Heating

1

Coefficient of power input (-)

Coefficient of power input (-)

Cooling

6

Capacity range

Capacity range

Cooling Capacity (kW)

Heating Capacity (kW)

Rated point

Rated point

Cooling Indoor

25 SHC (KW) 21.5 21.5 21.5 21.4 21.2 20.9

TC (KW) 24.5 25.7 26.2 26.8 28.0 29.1

°CWB 16 18 19 20 22 24

CPI 0.79 0.80 0.80 0.81 0.81 0.82

TC (KW) 23.5 24.6 25.2 25.7 26.8 27.9

Outdoor temperature (°C DB) 30 35 SHC CPI TC SHC (KW) (KW) (KW) 20.7 0.88 22.5 19.8 20.6 0.89 23.6 19.8 20.6 0.90 24.1 19.8 20.5 0.91 24.6 19.7 20.3 0.92 25.7 19.5 20.1 0.93 26.7 19.3

CPI 0.98 0.99 1.00 1.01 1.02 1.03

CPI 0.82 0.85 0.88 0.92 0.95

Outdoor temperature (°C WB) -5 0 TC CPI TC CPI (KW) (KW) 16.6 0.87 18.4 0.91 16.4 0.90 18.2 0.95 16.3 0.94 18.0 0.99 16.1 0.97 17.9 1.03 16.0 1.01 17.7 1.06

TC (KW) 26.9 26.6 26.4 26.2 25.9

TC (KW) 21.5 22.5 23.0 23.5 24.5 25.6

40 SHC (KW) 19.0 18.9 29.0 18.9 18.7 18.4

CPI 0.92 0.96 1.00 1.04 1.08

TC (KW) 29.2 28.9 28.7 28.4 28.2

CPI 1.08 1.09 1.10 1.11 1.12 1.13

Heating Indoor

-15 TC (KW) 13.2 13.1 12.9 12.8 12.7

°C WB 16 18 20 22 24

-10 CPI 0.77 0.80 0.84 0.87 0.90

TC (KW) 14.7 14.6 14.5 14.3 14.2

6

10 CPI 0.98 1.02 1.06 1.10 1.14

SYMBOLS

(m3/min)

AFR : Air flow rate BF : Bypass factor EWB : Entering wet bulb temp. EDB : Entering dry bulb temp. Caution: TC and SHC are shown by kW.

TC SHC PI CPI

(°C WB) (°C DB)

NOTES

1. 2.

3.

Ratings shown are net capacities which include a deduction for indoor fan motor heat. On the figure the mark with O show the max. capacity at standard conditions. On the figure the mark with show the rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed except at standard condition. SHC is based on indoor EWB and EDB. SHC for other dry bulb temp. = SHC + SHC*. SHC* = SHC correction for other dry bulb = 0.02 x AFR (m³/min.) x (1-BF) x (DB*-EDB) Add SHC to SHC*. (Triple)

5. 6. 7. 8.

Capacities are based on the following conditions. Outdoor air: 85% RH However, the condition rated capacity in heating is 7°C DB / 6°C WB. Corresponding refrigerant piping length: 5.0 m. Level difference: 0m Coefficient of power input is the percantage when the rated value is defined as 1.00. The value contains less than 5% error according to indoor unit type. Heating performance include the drop of frost formation. Air flow rate and (BF) are given in table below.

(Twin) FDQ250

AFR (BF)

4.

: Total cooling (heating) capacity (kW) : Sensible heat capacity (kW) : Power input (comp. + indoor and outdoor fan motors) : Coefficient of power input (-)

89 (0.34)

AFR (BF)

FCQ125C x 2

FCQ125B x 2

FBQ125B x 2

FBQ125C x 2

FHQ125 x 2

FUQ125 x 2

FDQ125 x 2

27.5 x 2 (0.19 x 2)

31 x 2 (0.07 x 2)

35 x 2 (0.14 x 2)

39 x 2 (0.16 x 2)

30 x 2 (0.13 x 2)

32 x 2 (0.07 x 2)

45 x 2 (0.25 x 2)

(Double Twin) AFR (BF)

9.

FCQ60C x 4

FCQ60B x 4

FFQ60 x 4

FBQ60B x 4

FBQ60C x 4

FHQ60 x 4

13.5 x 4 (0.21 x 4)

18 x 4 (0.1 x 4)

15 x 4 (0.11 x 4)

19 x 4 (0.11 x 4)

18 x 4 (0.15 x 4)

17 x 4 (0.2 x 4)

Rated power input of each model is given in table below: (Pair)

(Twin) FDQ250

Cooling Heating

8.58 8.22

FCQ125C x 2

FCQ125B x 2

FBQ125B x 2

FBQ125C x 2

FHQ125 x 2

FUQ125 x 2

FDQ125 x 2

8.91 8.68

8.91 8.68

9.14 7.94

8.98 7.38

10.22 8.95

9.30 8.68

9.53 7.35

Cooling Heating

(Dounle Twin) Cooling Heating

FCQ60C x 3

FCQ71C x 3

FCQ60B x 3

FCQ71B x 3

FFQ60 x 3

FBQ60B x 3

9.39 9.13

9.39 9.13

9.49 8.48

9.62 8.36

9.46 7.80

10.76 9.43

3TW29051-4

• Split - Sky Air • Outdoor Unit

11

• Outdoor Unit • Super Inverter • RZQ-C

7

Dimensional drawings

7-1

Dimensional Drawings

RZQ200-250C (Pitch of foundation bolt holes)

(Pitch of foundation bolt holes)

1

4-15 X 22.5 - mm - Oblong holes (foundation bolt hole)

7

6 (for 8HP)

Detail for front side

Detail for bottom side

(Knock-out hole)

(Knock-out hole)

(Knock-out hole)

Notes 1 Detail for front side and detail for bottom side indicate the dimensions after fixing the attached piping. 2 Gas pipe (Heat pump type) J22.2 Brazing connection Liquid pipe (Heat pump type) J9.5 Brazing connection ... For 200-type J12.7 Brazing connection ... For 250-type (Knock-out hole)

1 2 3 4 5 6 7 8 9 10

Liquid pipe connection port see note 2. Gas pipe connection port see note 2. Grounding terminal inside of switch box (M8) Power cord routing hole (side) J62 Power cord routing hole (front) J45 Power cord routing hole (front) J27 Power cord routing hole (bottom) J65.5 Wire routing hole (front) J27 Pipe routing hole (front) Pipe routing hole (bottom)

(Knock-out hole)

3TW29044-1

12

• Split - Sky Air • Outdoor Unit

• Outdoor Unit • Super Inverter • RZQ-C

7

Dimensional drawings

7-2

Dimensional Drawings with Accessories

3

RZQ200-250C

1 7

NOTES 1

Central drain pan kit

KWC26B280

• Split - Sky Air • Outdoor Unit

3TW27244-1

13

• Outdoor Unit • Super Inverter • RZQ-C

8

Centre of gravity

8-1

Centre of Gravity

RZQ200-250C

1 8

Center of foundation bolt hole

Center of foundation bolt hole (oblong hole)

Center of foundation bolt hole

Center of foundation bolt hole (oblong hole)

4TW29049-4

14

• Split - Sky Air • Outdoor Unit

• Outdoor Unit • Super Inverter • RZQ-C

9

Piping diagrams

9-1

Piping Diagrams

3

RZQ200-250C (Pair) Strainer Receiver

Solenoid valve

A 9.52 12.70

Model RZQ200C RZQ250C

1

Heat exchanger pipe Filter

Filter

Check valve

Check valve Check valve

Electronic expansion valve

9

Fan

Check valve Electronic expansion valve

Heat exchanger 4-way valve

High pressure sensor

Pressure regulating valve

High pressure switch

Indoor heat exchanger

Compressor

Low pressure sensor

Field piping J A Fan

Indoor unit

Filter

Capillary tube

Strainer

Oil separator

Solenoid valve

Field piping J22.20 Stop valve (With service port on on-site piping side J7.9mm flare connection)

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

• Split - Sky Air • Outdoor Unit

Outdoor unit

3TW29045-1

15

• Outdoor Unit • Super Inverter • RZQ-C

9

Piping diagrams

9-2

Piping Diagram Twin Application

RZQ200-250C (Twin) Strainer Receiver

Solenoid valve

1

Heat exchanger pipe Filter

A 9.52 12.70

9

Model RZQ200C RZQ250C

Check valve

Check valve

Filter

Check valve

Fan

Check valve Electronic expansion valve

Electronic expansion valve Heat exchanger 4-way valve

High pressure sensor

Pressure regulating valve

High pressure switch

Compressor Capillary tube

Field piping

Fan

Strainer

Oil separator

Solenoid valve

Indoor heat exchanger

Field piping Low pressure sensor

Branch pipe (Option)

Field piping J22.20

Indoor heat exchanger

Field piping

Fan

Stop valve (With service port on on-site piping side J7.9mm flare connection)

Outdoor unit

Field piping

Indoor unit

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

16

Filter

Field piping J A

Indoor unit

• Split - Sky Air • Outdoor Unit

3TW29045-2

• Outdoor Unit • Super Inverter • RZQ-C

9

Piping diagrams

9-3

Piping Diagram Triple Application

3

RZQ200-250C (Triple) Strainer Receiver

Solenoid valve

A 9.52 12.70

1

Heat exchanger pipe Filter

Model RZQ200C RZQ250C

Filter

Check valve

Fan Check valve Electronic expansion valve

Indoor heat exchanger

9

Check valve

Check valve

Electronic expansion valve Heat exchanger 4-way valve

Field piping

Fan

Pressure regulating valve

High pressure sensor

Field piping

Oil separator

Solenoid valve

Indoor heat exchanger High pressure switch

Field piping J A

Compressor Capillary tube

Field piping Field piping

Indoor unit Indoor heat exchanger

Branch pipe (Option)

Field piping J22.20 Low pressure sensor

Stop valve

Filter

Fan

Strainer

Indoor unit

(With service port on on-site piping side J7.9mm flare connection)

Outdoor unit Field piping

Fan

Field piping

Note: The pipes between the branch and the indoor units should have the same size as the indoor connections.

Indoor unit

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

• Split - Sky Air • Outdoor Unit

3TW29045-3

17

• Outdoor Unit • Super Inverter • RZQ-C

9

Piping diagrams

9-4

Piping Diagram Double Twin Application

RZQ200-250C (Double twin) Indoor heat exchanger

Strainer

9

Field piping

Fan

Model RZQ200C RZQ250C

Heat exchanger pipe Filter

Check valve

Check valve

Field piping

Filter

Indoor unit

Fan Check valve

Check valve Electronic expansion valve

Field piping J 9.52

Indoor heat exchanger

Solenoid valve

Receiver

1

A 9.52 12.70

Electronic expansion valve Heat exchanger

Field piping J15.90

4-way valve

Field piping

High pressure sensor

Pressure regulating valve

Field piping

Indoor unit

Solenoid valve Oil separator

Fan

Indoor heat exchanger High pressure switch

Branch pipe Field piping J A

Compressor Capillary tube

Field piping

Field piping J22.20

Field piping

Low pressure sensor

Indoor unit Field piping J 9.52

Indoor heat exchanger

Field piping J15.90

Stop valve (With service port on on-site piping side J7.9mm flare connection)

Field piping Fan

Field piping

Indoor unit

• Split - Sky Air • Outdoor Unit

Outdoor unit

Note: The pipes between the branch and the indoor units should have the same size as the indoor connections.

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

18

Filter

Fan

Strainer

(Option)

3TW29045-4

• Outdoor Unit • Super Inverter • RZQ-C

10

Wiring diagrams

10 - 1 Wiring Diagrams - Single Phase

3



1



10







∼ ∼



• Split - Sky Air • Outdoor Unit

19

• Outdoor Unit • Super Inverter • RZQ-C

11

Sound data

11 - 1 Sound Power Spectrum

11

Sound power level (dB)

1

RZQ250C - Cooling

Sound power level (dB)

RZQ200C - Cooling

3TW29047-3

Octave band center frequency (Hz)

3TW29057-3

NOTES 1 2 3

20

Octave band center frequency (Hz)

NOTES

dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6μW/m2 Measured according to ISO 3744

• Split - Sky Air • Outdoor Unit

1 2 3

dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6μW/m2 Measured according to ISO 3744

• Outdoor Unit • Super Inverter • RZQ-C

11

Sound data

11 - 2 Sound Pressure Spectrum

3 RZQ200C - Heating

3TW29047-1

2 3 4

5

Coil Data is valid at free field condition (measured in a Microphone semi-anachoic room) Switchbox dB(A) = A-weighted sound pressure level (A-scale according to IEC) Location of microphone Reference acoustic pressure 0dB = 20Pa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Curve for RZQ200C7Y1B in cooling mode

1 2 3 4

5

Sound pressure level (dB) Octave band center frequency (Hz)

3TW29057-2

NOTES

3 4

5

Data is valid at free field condition (measured in a Coil Microphone semi-anachoic room) Switchbox dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20Pa Location of microphone If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Curve for RZQ200C7Y1B in heating mode

RZQ250C - Heating

Sound pressure level (dB)

3TW29057-1

2

Octave band center frequency (Hz)

NOTES

RZQ250C - Cooling

1

11

3TW29047-2

Octave band center frequency (Hz)

NOTES 1

1

Sound pressure level (dB)

Sound pressure level (dB)

RZQ200C - Cooling

Octave band center frequency (Hz)

NOTES

Coil Data is valid at free field condition (measured in a Microphone semi-anachoic room) Switchbox dB(A) = A-weighted sound pressure level (A-scale according to IEC) Location of microphone Reference acoustic pressure 0dB = 20Pa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Curve for RZQ200C7Y1B in cooling mode

• Split - Sky Air • Outdoor Unit

1 2 3 4

5

Data is valid at free field condition (measured in a Coil Microphone semi-anachoic room) Switchbox dB(A) = A-weighted sound pressure level (A-scale according to IEC) Location of microphone Reference acoustic pressure 0dB = 20Pa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Curve for RZQ200C7Y1B in heating mode

21

22

• Split - Sky Air • Outdoor Unit

10 or more

200 or more

300 or more

500 or more

100 or more

Wall height unrestricted

50 or more

50 or more

10 or more

200 or more

400 or more

100 or more

20 or more



50 or more

10 or more

400 or more

Wall height unrestricted

100 or more

20 or more

300 or more

500 or more

100 or more

500 or more

50 or more

50 or more

10 or more

10 or more

500 or more

500 or more

100 or more

500 or more

600 or more

300 or more

100 or more

100 or more

20 or more

20 or more

Notes: 1 Heights of walls in case of Patterns 1 and 2: Front: 1500 mm suction side: 500 mm Side: Height unrestricted. Installation space to be shown in this drawing is based on the cooling operation at 35 degrees outdoor air temperature. When the design outdoor air temperature exceeds 35 degrees or the load exceeds maximum ability because of much generation load of heat in all outdoor unit, take the suction side space more broadly than the space to be shown in this drawing. 2 If the above wall heights are exceeded then h1/2 and h2/2 should be added to the front and suction side service spaces respectively as shown in the figure on the right. 3 When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available always bearing in mind the need to leave enough space for a person to pass between units and wall and for the air to circulate freely. (If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits.) 4 The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.

50 or more

500 or more

300 or more

For centralized group layout

50 or more

50 or more

10 or more

10 or more

50 or more

50 or more

10 or more

10 or more

100 or more

500 or more

100 or more

300 or more

500 or more

300 or more

100 or more

100 or more

20 or more

20 or more

12

10 or more



300 or more

For installation in rows

For single unit installation

3TW29049-3

50 or more

50 or more

10 or more

10 or more

1

12

RZQ200-250C

• Outdoor Unit • Super Inverter • RZQ-C

Installation

12 - 1 Installation Method

• Outdoor Unit • Super Inverter • RZQ-C

12

Installation

12 - 2 Fixation and Foundation of Units

3 1 12

• Split - Sky Air • Outdoor Unit

23

• Outdoor Unit • Super Inverter • RZQ-C

13

Operation range

13 - 1 Operation Range RZQ200-250C

Cooling

1

Indoor temp. (°CWB)

Operation range

Allowable range of operation (warming-up)

Heating

Outdoor temp. (°CWB)

Allowable range of operation (pull-down)

Operation range

Outdoor temp. (°CDB)

13

Indoor temp. (°CDB) 4TW26566-1

24

• Split - Sky Air • Outdoor Unit

Please fill out the requested information Please fill out the requested information

Daikin Europe N.V. participates in the Eurovent Certification programme for Air conditioners (AC), Liquid Chilling Packages (LCP), Air handling units (AHU) and Fan coil units (FCU), Check ongoing validity of certificate online: www.eurovent-certification.com or using: www.certiflash.com”

Daikin products are distributed by:

The present leaflet is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this leaflet to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin Europe N.V.

EEDEN1 2 - 1 0 0

Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende

EEDEN12-100 • 04/12 • Copyright © Daikin The present publication supersedes EEDEN11-100 Printed on non-chlorinated paper. Prepared by Goekint Graphics NV, Belgium Responsible Editor: Daikin Europe N.V., Zandvoordestraat 300, B-8400 Oostende

Daikin’s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental issues. For several years Daikin has had the intention to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste.